Rittal White Paper 305: Selecting Air Conditioners for Industrial Enclosures By: Judith Koetzsch Mark Corcoran, Editor



Similar documents
Rittal White Paper 508: Economized Data Center Cooling Defining Methods & Implementation Practices By: Daniel Kennedy

Absolute and relative humidity Precise and comfort air-conditioning

CRAC Precision climate control units for data centres

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?

air conditioners how to choose a cooling system


LOBOY 16 AIR CONDITIONERS

Element D Services Heating, Ventilating, and Air Conditioning

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

CoolTeg Plus Chilled Water (CW) version: AC-TCW

BD150 INDUSTRIAL DEHUMIDIFIER USER MANUAL

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Analysis of data centre cooling energy efficiency

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Creating the Ideal Environment for Accelerated Drying Times on Construction and Restoration Projects

How does solar air conditioning work?

Choosing Close-Coupled IT Cooling Solutions

Failure code manual. content

DataCenter 2020: first results for energy-optimization at existing data centers

How To Get A Passive House

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: Uptime Racks:

Dehumidifier Users manual. For Models: DH45S DH65S

How To Improve Energy Efficiency In A Data Center

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

saving energy in comfort Factsheet Recair Enthalpy

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Rittal White Paper 507: Understanding Data Center Cooling Energy Usage & Reduction Methods By: Daniel Kennedy

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

Glossary of Heating, Ventilation and Air Conditioning Terms

White Paper Rack climate control in data centres

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

Air Conditioning 101. STN Presentation AC101

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

FOXAIR 60/50 ALL MODELS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Energy savings in commercial refrigeration. Low pressure control

Benefits of. Air Flow Management. Data Center

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Refrigeration Basics 101. By: Eric Nelson

Data Centre Infrastructure Assessment

Cooling Audit for Identifying Potential Cooling Problems in Data Centers

COOLSIDE box R410A. conditioned server - racks for direct installation into the room INVERTER E C

Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity

Material test chamber with mechanical convection

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Humidification Strategies for Data Centers and Network Rooms

Office of the Government Chief Information Officer. Green Data Centre Practices

Automatic air conditioning system (with the Lexus Display Audio system)

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

Defining Quality. Building Comfort. Precision. Air Conditioning

Characteristics of Evaporators

Daikin Altherma hybrid heat pump. The natural combination

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure

Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement

COMPARISON OF EFFICIENCY AND COSTS BETWEEN THREE CONCEPTS FOR DATA-CENTRE HEAT DISSIPATION

Single Zone LCD Thermostat Operating Instructions

Dehumidification Frequently Asked Questions

State of the Art Energy Efficient Data Centre Air Conditioning

Troubleshooting Your Refrigerator

Tech Byte 27: Small Computer Room and IT Closet Cooling

ECO-AIR AIR CONDITIONING

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Elements of Energy Efficiency in Data Centre Cooling Architecture

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

Roof Top Unit. Description Model Type Use With Air Distribution Box. Heat Pump B Integral Mechanical

USER S MANUAL HSC-24A

Driving Data Center Efficiency Through the Adoption of Best Practices

Meaco 30L and Meaco 40L dehumidifier instruction manual

HIGH EFFICIENCY RTU. HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

How To Improve Energy Efficiency Through Raising Inlet Temperatures

THE PSYCHROMETRIC CHART AND ITS USE

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling

Technical Support Bulletin Nr. 20 Special AC Functions

Energy Efficiency. Energy Efficient Home Cooling:

By Tom Brooke PE, CEM

PTAC Selection Guide. Optimize your spend with the right PTAC equipment!

SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

Split units TH with hermetic compressors

How To Run A Data Center Efficiently

Climasys Thermal Management System. Schneider Electric Universal Enclosures 2009

THE PSYCHROMETRIC CHART: Theory and Application. Perry Peralta NC State University

Dehumidifier D 850E. - Instruction manual version 02

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Get the FACTS about SEER and Deliver Better Customer Value

Rate of Heating Analysis of Data Centers during Power Shutdown

Portable Air Conditioner

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

RiMatrix S Make easy.

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Reducing Data Center Energy Consumption

Transcription:

Rittal White Paper 305: Selecting Air Conditioners for Industrial Enclosures By: Judith Koetzsch Mark Corcoran, Editor Executive Summary Choosing the right air conditioners for enclosures can have a tremendous impact on the overall performance and efficiency of industrial operations. Proper and efficient air conditioner cooling can significantly prolong the life of installed equipment, save energy and utility costs, and protect against unscheduled downtime. Although cooling is sometimes an afterthought during the course of planning a project at the enclosure layout level, with careful consideration and the right information, it can truly become an asset for increased productivity and profitability. This paper identifies different factors that should be considered when choosing air conditioners for industrial enclosures including internal heat loads, the various methods used to rate the cooling capacity of enclosure air conditioners, the impact of humidity and other ambient conditions, and energy efficiency. Understanding air conditioner performance diagrams and sizing tools in relation to application requirements is also covered.

Factors to Consider Internal Heat Load The internal heat load is the amount of heat energy produced by the electronics inside the enclosure, and it comes from the unused electricity running through the components. In order to specify the right air conditioner capacity for an application, it is critical to know the amount of heat energy (in BTU per hour or in Watts) that will be created by the equipment housed within the enclosure. How to Determine the Amount of Heat Energy to be Removed? There are multiple ways to determine the heat load inside an enclosure. One way is to add up the heat loads of all of the installed electronic components as specified by the component manufacturers as seen below. Example: Device Heat load as specified by the manufacturer 20 HP Drive 1500 Watts 1250 A Circuit breaker 200 Watts PLC 5 A 3 Watts Transformer 1000 VA 64 Watts Total 1667 Watts Another approach is to add up the electricity consumed by the electronics and then multiply it by the efficiency of the system. The resulting number equals the need for cooling capacity. For example, if an electronics system is consuming 500 Watts of power and it is 20% efficient, the system is only using 100 Watts of electricity for its actual function. The remaining 400 Watts is dissipated in the form of heat energy. Impacting Cooling Capacity In the world of electronics, cooling capacity is the maximum amount of thermal energy that a climate control product can remove, and it is shown either in Watts or BTU per hour (if necessary, to convert Watts into BTU per hour, multiply by 3.413). The cooling capacity, or performance, of a specific enclosure air conditioner not only depends on its overall design, but also on various application-specific factors. These factors include the ambient temperature, the maximum allowable internal temperature, and the operating frequency (in Hz). The ambient temperature (T a ) can significantly affect the cooling capacity of an air conditioner. If an air conditioner operates in high ambient temperatures (for example, the maximum operating temperature for Rittal TopTherm air conditioners is 131 F), it provides less cooling capacity. This is because air conditioners work by pulling the hot air from inside the electrical enclosure and transferring the thermal energy away from the cabinet to the surrounding environment. The hotter the outside air is, the ability of the air conditioner to transfer the enclosure heat energy out through the condenser coil is diminished. As to be expected, the opposite is true when air conditioners are placed in areas with lower ambient temperatures since the heat transfer through the condenser coil into the ambient air is quicker, consequently raising the cooling capacity of the air conditioner. The maximum allowable internal temperature (T i ) is also relevant to the cooling capacity of an air conditioner because it determines how much thermal energy needs to be removed from an enclosure and can vary from application to application. Typically, air conditioners operate by maintaining temperatures that do not exceed a specified set point. A recommended set point for 2

enclosure air conditioners lies between 86 F and 104 F, depending on the electronics installed in the enclosure. Lower temperature set points can easily lead to excessive condensation and should be avoided. Example: The set point of an air conditioner is set to 95 F and the differential (or switching hysteresis) setting is 9 F. The temperature inside the enclosure is allowed to increase to 95 F before the air conditioner starts to run to cool the temperature down to 86 F. Now that the differential to the set point has been reached, the air conditioner shuts off until the enclosure temperature rises to the set point of 95 F again. The third factor that influences the cooling capacity of an air conditioner is the operating frequency. Here in North America, 60 Hz is the norm, but throughout much of the world, 50 Hz is used. This is why, for example, most Rittal TopTherm Plus air conditioner models are dualrated, meaning that they can operate at both 50 and 60 Hz. A dual rating allows for the same air conditioner to be used all over the world where different power systems supply different frequencies. When an air conditioner is operating at 60 Hz, the fans and compressor actually rotate faster than at 50 Hz, resulting in higher performance for the air conditioner at 60 Hz. When evaluating an air conditioner stated to have a certain cooling capacity, it s important to consider under what temperature conditions, and at which operating frequency, that cooling capacity is provided. Why Some Manufacturers Determine Cooling Capacity Differently than Others In North America, no formal standard for testing or publishing cooling capacity exists, so most manufacturers use the maximum temperatures at which the air conditioner is designed to operate as reference points (maximum internal and external temperatures). The maximum operating temperatures can differ between air conditioner models as well as manufacturers. Typically, a maximum operating temperature is at 131 F. If indicated, the rating temperatures could be shown as L131/L131 or Ti 95/Ta 95 or 95 F/95 F. Traditionally the first number stands for the internal temperature. In Europe, a standard called DIN 3168/EN 814 part 500 (European standard for enclosure climate control) is used. This standard levels the playing field, and provides a more realistic measure of performance, by requiring all manufacturers to use the same temperature conditions to determine cooling capacity allowing users to make true one-to-one comparisons. Since Rittal is a global supplier of enclosure air conditioners, the cooling capacities shown on its units comply with existing standards. Helpful Tools Air Conditioner Performance Diagrams To determine the cooling capacity of an air conditioner under the above-described variable conditions, a performance diagram can be used. These charts show the cooling capacity of an air conditioner per the requirements of DIN 3168, as well as under different temperature scenarios including maximum operating conditions. This will help users to determine how a particular air conditioner will perform in a specific application. 3

Air Conditioner Sizing When selecting an air conditioner, the easiest way to figure out how an air conditioner will perform at given temperatures is to use sizing software. These convenient tools typically walk users through the various factors that impact an application, and then determine the need for cooling. Rittal s Therm 5.14 sizing software, for example, can calculate what the internal enclosure temperature would be without any means of cooling before predicting how many BTU or Watts of cooling capacity the application requires and suggesting an appropriate part number. Calculating Air Conditioner Efficiency Reducing power consumption and increasing efficiency are vitally important to protecting the environment, and to saving money during the operation of air conditioners at the end user level. The formula to determine the efficiency of an air conditioner (shown below) is simple it s the ratio between useful cooling capacity and power consumption. The higher the cooling efficiency factor, the more efficient the air conditioner is. Example: Enclosure Air Conditioner: 460 V, 60 Hz Cooling capacity at 95/95, 60 Hz: 2700 Watt Power consumption at 95/95, 60 Hz: 1500 Watt Cooling efficiency factor = 2700 Watt 1500 Watt Cooling efficiency factor = 1.8 4

Calculating the Impact of Humidity An unavoidable side effect of using air conditioners is the dehumidification of the enclosure s interior air. As it cools down, part of the humidity contained in the air condenses on the evaporator coil. The reliable discharge of this condensate from the enclosure is important to consider, and is achieved by using condensate hoses and collection bottles in conventional units, or via condensate evaporators in more advanced products like Rittal s TopTherm PLUS. The amount of condensate that is created depends on relative humidity, the air temperature in the enclosure, the evaporator coil, and the air volume present in the enclosure. The Mollier h-x diagram (see next page) is used to show the water content of air depending on its temperature and relative air humidity. Calculation Example: An enclosure air conditioner has a temperature set point of Ti = 95 F. The relative ambient air humidity is 70%. If 95 F air is exchanged over the evaporator coil, the surface temperature of the evaporator coil (evaporation temperature of the refrigerant) is approximately 64 F. At the outer layer, adhering to the surface of the evaporator coil, water (condensate) is deposited at the dew point. The difference, Δx = x1 x2, indicates the amount of condensation that occurs per 2.2 lb of air with complete dehumidification. How airtight an enclosure is plays an important role in the amount of condensation that will occur in an application. Since the quantity of ambient air (and as a result, the amount of humidity) is limited in a properly sealed enclosure, the amount of condensation will be limited too. 5

Application Example Using Mollier h-x Diagram (above): Equation: W = V ρ Δx where: W = Water quantity in grams V = Volume in m 3 ρ = Density of the air in kg/m 3 Δx = Difference in water content in g/kg dry air (from the Mollier h-x diagram) Enclosure door closed, ambient air is not entering the enclosure only the humidity trapped inside of the enclosure is being dehumidified. V = W H D = 0.6 m 2 m 0.5 m V = 0.6 m 3 W = V ρ Δx = 0.6 m 3 1.2 kg/m 3 11 g/kg W = 7.92 g 8 ml. If placed into the same calculation example above, an enclosure that is not properly sealed will see more condensation. Ambient (humid) air can enter through poorly sealed cable entries, damaged or open enclosure doors, and damaged enclosure gaskets resulting in increased 6

condensation. If, for example, ambient air is entering the enclosure at a rate of 5 m 3 /h, a permanent condensation amount of 2.7 oz/h (80ml/h) may occur. Because of this, it s always recommended that control panels be operated with enclosure doors closed and that all sides of the enclosure are properly sealed and gasketed. In addition, it is advisable to use a door switch that interrupts the operation of the air conditioner while the enclosure door is open and to set the internal temperature of the enclosure only as low as is actually needed. Conclusions Selecting the right air conditioner for an industrial enclosure application is crucial to maximizing efficiency, performance, and overall return on investment. Knowing what factors to consider, and taking the time to properly evaluate the products available, can save money by reducing utility costs, drastically improve the life and reliability of installed equipment, and solidify operations as a whole through increased productivity and limiting unplanned downtime. About the Author Judith Koetzsch has been with Rittal since 2001 first working for Rittal GmbH & Co. Kg. in Germany as a part of the international climate control product management team, and then joining Rittal Corporation in the U.S. as Product Manager for Climate Control Products in 2006. The Rittal Corporation is the U.S. subsidiary of Rittal GmbH & Co. KG and manufactures the world s leading industrial and IT enclosures, racks and accessories, including climate control, power management and electronic packaging systems for industrial, data center, outdoor and hybrid applications. 1 Rittal Place Urbana, OH 43078 Toll free: 800-477-4000 Website: www.rittal-corp.com 7 2/10 WP305