Loss & Continuity Testing with MPO/ MTP Connectors



Similar documents
99 Washington Street Melrose, MA Phone Toll Free Visit us at

What testing is required for PREMISES Fiber Optic Cabling and the standards used

Fibre optic testing best practices

Understanding Fiber Polarity: Implications at 10G, 40G, & 100G

Polymer Coated Fiber Cable (PCF)

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

The Need for Low-Loss Multifiber Connectivity

Cabling & Test Considerations for 10 Gigabit Ethernet LAN

Fiber in the Data Center

How To Make A Data Center More Efficient

Optical Fiber Data Center Field Testing. ANSI/BICSI Data Center Design and Implementation Best Practices

Overcoming OM3 Performance Challenges

TIA Releases Guidelines for Maintaining Polarity Using Array Connectors

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano

Design Guide. SYSTIMAX InstaPATCH 360 Traffic Access Point (TAP) Solution.

Measuring of optical output and attenuation

MPO. Fast Fibre Solution for Data Centres

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method

Arista 40G Cabling and Transceivers: Q&A

Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand

Network Monitoring - Fibre TAP Modules

Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations

How To Properly Maintain A Fiber Optic Infrastructure

Fibre Channel Fiber Cabling

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

Physical Infrastructure trends and certification requirements for Datacenters. Psiber s Global Village

Accurately Testing fibre Optic Cables

How To Make A Fibre Cable For A Data Centre

Kit Highlights and Key Features

Obsolete Fiber Technology? Not in my Data Center!

TEST & INSPECTION. Featured Data Center Products. OTDRs Certification Test Kits Inspection Cleaning

Optimizing Infrastructure Support For Storage Area Networks

Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...

Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM

Zone Distribution in the Data Center

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

Optical Fiber. Smart cabling: constructing a cost-effective, reliable and upgradeable cable infrastructure for your enterprise network

Patch Cords for Data Center Applications

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING

Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable

AMP NETCONNECT CABLING SYSTEMS FOR DATA CENTERS & STORAGE AREA NETWORKS (SANS) High-density, High Speed Optical Fiber and Copper Solutions

Optical Power Meter. Specification & User Manual

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

The Need for Speed Drives High-Density OM3/OM4 Optical Connectivity in the Data Center

Upgrading Path to High Speed Fiber Optic Networks

ST800K-U Optical Power Meter. User Manual V1.0

Field Measurements of Deployed Fiber

MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module

The Conversion Technology Experts. Fiber Optics Basics

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Reliable, Consistent, Quality

Enterprise Networks EMEA. Core Products FOR DATA CENTRES

SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS

Fiber Systems. Best Practices for Ensuring Polarity of Array-Based Fiber Optic Channels

7.4 3M No Polish Connector

DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES)

Specifying an IT Cabling System

CISCO 10GBASE X2 MODULES

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

SECURE Fiber Optic Products

Fiber Coupler Overview

Specifying Optical Fiber for Data Center Applications Tony Irujo Sales Engineer

HP Multimode OM3 LC/LC Optical Cables Overview. Models HP 50 m Multimode OM3 LC/LC Optical Cable

Field Installable Optical Connector for Cables

The High Cost of a Low-Cost Cable Certification Tester

The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations

Secure/Keyed LC System Solutions Overview

MTP Optical Fibre Configurations

DIAMOND AVIM Connector

How To Get A Better Signal From A Fiber To A Coax Cable

NaviTEK II. idealnwd.co.uk. Save money through using a single multifunction device for testing copper and fibre networks

Industry solutions: Broad cast

Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems

Physical Infrastructure trends and evolving certification requirements for Datacenters Ravi Doddavaram

HIGH QUALITY FOR DATA CENTRES ACCESSORIES AND INFRASTRUCTURE. PRODUCT CATALOG 12/2014 PRO-ZETA a.s.

Data Center Design for 40/100G

FIBER OPTIC ISOLATORS

Modern Data Center needs 10 th of April, Andrew Sedman, RCDD Head of Training and Technical Service R&M

DATA CENTRES POWERED BY EXCEL

Enabling 21 st Century Connectivity

M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. or (800) , (603)

TIER-1/TIER-2 FIBER CERTIFICATION KITS

SignalTEK II. Save money by using a single multifunction device in place of separate copper, fiber and Power over Ethernet (PoE) testers

Attaching the PA-A1-ATM Interface Cables

Plug & Play Universal Systems

ETD Fiber Optic Products

Cable Assemblies. Features and Benefits

Smart Cabling: Constructing a cost effective reliable and upgradeable cable infrastructure for your data centre/enterprise network

AMP NETCONNECT Data Center Cabling Solutions

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Installation Guide for GigaBit Fiber Port Aggregator Tap with SFP Monitor Ports

APPLICATION NOTE POLARIZATION MEASUREMENTS

Insertion Losses of Fiber Optical Connectors

M310 Data Center OTDR

MTP Solutions. MPO High Performance Fibre Optic Solutions for Data Centres SMARTER GLOBAL CONNECTIONS

Transcription:

Loss & Continuity Testing with MPO/ MTP Connectors Deployments of fiber optic systems in data centres are now using multimode ribbon fiber and typically MPO/MTP connectors, which have some very particular installation issues. Here we give an overview of how to tackle various issues related to testing the cabling for these systems. We mainly discuss multimode systems, however single mode ribbon fiber systems share very many common practices. Typically these deployments are for 40G / 100G Ethernet. Cabling may be installed for 100G Ethernet even if the immediate requirement is 40G, to allow for later incremental bandwidth upgrades. The 24 fibers used for 100G Ethernet can alternatively be used to carry three 40G systems. So this allows a choice of upgrade paths, eg to upgrade incrementally to 120G aggregate capacity by adding two extra 40G channels, or replace a 40G system with a single 100G channel. Standards are in development for 400G Ethernet. The incremental cost of installing 24 fiber 100G cabling, instead of 12 fiber 40G cabling, is actually quite modest, particularly in comparison to later re-wiring and facility disruption. The major additional cabling complexity may be a patch panel with breakout connections, which provides connection flexibility for future deployment options. Standards Compliance Internationally recognised standards are now in place, which define just about everything to do with data centre design. Just in the area of fiber optic cabling, there are standards for fiber types (Typically multimode OM3. OM4 etc), cable types (fire retardance, bend resistance, riser cables etc), cable installation (fire stops, ducting etc) connectors (LC, MPO etc), labelling conventions, Ethernet, optical wavelengths (CWDM etc), optical safety (mandatory), and finally: cable acceptance testing. Page 1 of 6

There is one aspect of the standards for fiber acceptance testing that everyone can agree on: they are currently a work in progress, and this is particularly true of MPO testing. So at the project definition stage, it is a good idea to review and refine the fiber cable acceptance test requirements, which sensibly end up as a combination of standards based requirements and the mandatory atory requirements of the particular transmission equipment in use. A good review at this point can reduce project cost, increase facility utilisation, and increase the useful LAN lifetime. A Very Small Acceptable Optical Loss! The majority of LAN transmission sion systems using MPO/MTP connectors have extremely tight end-todb. This tiny loss figure creates unique challenges end optical loss requirements, perhaps around 1.5 for precision loss measuring for cable certification. Much of the currently available test equipment and procedures do not achieve a level of repeatability (accuracy) that gives confidence that the tight specification has been achieved. The two reasons for this tight specification are to minimise per port electronics cost, and also because these systems are dispersion limited, not power limited. These systems use 850 nm and 50 micron core fiber, and end to end length is usually limited (by dispersion) to around 300 meters. Inspection & Cleaning Connector condition and cleanliness is a very major consideration, and is a most common cause of problems. Absolutely essential is a good quality microscope with an MPO/MPT specific adaptor, a supply of suitable specific cleaning materials (more than one type is good), and adequate time and know-how to use them. The default available MPO cleaners tend to do a reasonable job of cleaning the fiber ends only, but extra cleaning materials should be available to clean alignment pins, and sometimes the whole connector end face. Inspection and cleaning should be performed every time before a connector is mated. Cabling Disturbance Because of the combination of very low loss requirements, high fiber complexity and modest connector performance, it is essential that final testing and commissioning are accomplished with the lowest possible level of disturbance to connections. Also, once loss testing is done, any cabling disturbance might require the loss testing to be repeated. This means that an unusually strict test regime is appropriate, so that each acceptance level is completed with exceptional confidence. You Page 2 of 6

want to avoid going back in and disturbing things. For this reason, we suggest a phased approach as being most practical. Continuity Testing This is the most basic test: Does light get from end to end? As a minimum, this test is easily accomplished with a VFL source and one low quality breakout cable to connect to the VFL. Continuity testing usually doesn t need documenting. If a numbered low quality breakout cord is used each end, this could also double as a polarity test phase. The continuity test phase is usefully accompanied by thorough cleaning and inspection of the connectors. This achieves a few objectives. Bad connectors are the main cause of installation failures. Doing this here enables the installer to identify & re-work/replace bad connectors at the earliest (lowest cost) point, avoiding later cable disturbance. It also ensures that a bad connector does not contaminate the test cords or degrade other connectors. If the connector quality is inadequate, there may be little point proceeding further until this issue is fixed. Simple continuity testing has one big problem: it doesn t identify if fibers are swapped around. So for this we talk of: Polarity Testing Typically, the cable installation requires polarity testing, to ensure that a 1 n array of fibers at one end of a system, is correctly mapped to a 1 n array of fiber the other end. If the installation has a patch cable section so that connections can be split off to particular transmission equipment, niggling polarity mistakes can occur here. The polarity test needs a very high level of confidence, since if not 100% correct, there is no chance of a working outcome, and there could be a great deal of wasted work to find the swapped fibers. This will probably want a basic level of documenting, sufficient to record which fibers were tested, and the general array direction. Labelling You now have your system physically in place and light going to and fro in the right combinations. This is the perfect time to double-check and rectify all associated labelling, otherwise the next phase of loss testing could result in incorrect re-assembly due to discovered faults. Up to this point, the work has required a very methodical approach, however has otherwise been quite straightforward. Loss Testing Accuracy & Confidence Issues People use the terms repeatability, accuracy, reproducibility or uncertainty somewhat interchangeably. For loss testing in particular, there is little practical difference between them all, so we will use the term uncertainty. The real issue is what uncertainty happens when repeatedly measuring one item with different items of test equipment or test cords. Page 3 of 6

Quoted uncertainty values always imply a ± value, whether specifically mentioned or not. For example, a quoted uncertainty of 0.1dB is the same as ±0.1dB, usually with a 95% confidence level. As mentioned, the acceptable maximum loss figure may only be 1.5 db. If the test uncertainty is say 0.3 db, then measured losses from 1.2 1.8 db are marginal, and the maximum test value for guaranteed operation is 1.2 db. So every small improvement in uncertainty, yields a usefully larger allowable measured loss level, which will reduce installation cost. This easily explains the previous care on planning test cords, doing cleaning etc. In practice, repeatability / accuracy is optimised by a number of factors: 1. Use of low loss Elite test cords, and ensuring they are in top condition. 2. Use of an Encircled Flux compliant test source, followed by a mandrel wrap. 3. Use of very accurate loss test equipment, remembering that you are working on the limits of achievable loss test accuracy. For typical 850 nm testing, do not use an InGaAs power meter detector, since it is too wavelength sensitive and so reduces practical accuracy. The light source must also be highly repeatable and stable when the connected test cord is moved around. 4. Rigorous inspection and cleaning every time a connector is mated. 5. Performing test cord verification at the start of the job. 6. Use of appropriate data recording systems, since there will be plenty of test data. Test Cords A major loss test consideration is the test cord loss performance. As can be seen from the table, Elite MPO / MTP cords are available with per connector / fiber loss of below 0.35 db. Otherwise standard cords are clearly inadequate for testing. Here are the USConnec specifications for these connectors, and also shows why it is so undesirable to disturb the cabling after testing. MM MT Elite Multimode MT Standard Multimode MT SM MT Elite Single-mode MT Standard Single-mode MT Insertion Loss 0.1 db Typical (All 0.35 db Maximum 0.20 db Typical (All 0.60 db Maximum 0.10 db Typical (All 0.35 db Maximum 0.25 db Typical (All 0.75 db Maximum Optical Return Loss > 20 db > 20 db > 60 db (8 Angle Polish) > 60 db (8 Angle Polish) Testing will probably need a combination of straight MPO-MPO test cords, and breakout cords. Also ensure that connector pin polarities are correct, since trying to swap these pins in the field is not viable. A few tested through-connects is also helpful. Spare test cords will be required, in case some get degraded or damaged. The typical application environment uses a mix of LC and multi fiber connectors. So naturally one might assume that LC MPO breakout test cords are an obvious choice. However SC MPO Page 4 of 6

breakout cords are typically more robust, easier to handle, and offer slightly improved optical performance. However, SC-LC connections give inferior performance. Number the cords and label each end A/B. Test cords require Performance Verification before each use. This performance verification test is quite specific, and failure to do this preliminary test may invalidate all the following test results. The basic objective of the performance test is to ensure that the loss of the cords meets the basic accuracy requirements. However, there is a sting in this tail as follows: The test standards require a loss of eg 0.1 db or better for multimode fiber The elite average loss meets this specification However the actual per fiber maximum loss does not. We hope the standards folk will resolve this in due course. One potential way around this is that if the actual loss of each connection is recorded for each fiber during this test, then this loss can be used to compensate the following test results and improve accuracy. However in practice, this is excessively hard to implement, so the practical policy is to only use good cords. The Test Cord Verification Test is quite simple: test each test cord connector using two reference cords, and the loss of the connection must be within the allowed limit. In the case of MPO connectors, this will take a bit longer due to the number of fibers. What Test Uncertainty can I expect? This is a much discussed issue. Without going into any great detail, there are a few obvious pointers: The test cord performance test using Elite connectors could have losses of from 0 0.35 db per connector, giving a per mated connector uncertainty of ±0.18 db, This means that any overall test uncertainty must be at least ±0.18 db, and is likely to be larger once other factors as included. However once the test cords are plugged into presumably lower grade cords, the loss there could possibly jump to 0 0.75 db, giving a minimum per mated connector uncertainty of ±0.38 db. These are simple deductions based on connector specifications, and calculated uncertainty including all factors could only get worse. Alternatively, if suitable experiments are performed with the actual equipment and test cords, it may be possible to demonstrate a lower level of uncertainty, however this is specific to a particular item of test equipment, and particular test cords, and so has limited viability. General Loss Test equipment Choices There are three broad choices to make, which will depend on the scale of expected work: 1. Use a basic source and meter. This is excessively fiddly to perform, and so prone to error, since both instruments need moving for each fiber to be tested, so it s only sensible for a very small project. Page 5 of 6

2. Use a basic source and special MPO compatible meter, so that only the source needs moving for each fiber. For a modest equipment cost, this greatly simplifies testing. This also works for any fiber type, wavelength, or number of fibers per connector, or MPO pin configuration, so it has excellent flexibility, and the same equipment can be used for other work. A good choice for many mid-size projects, or cabling contractors. 3. A special MPO test set, However these usually only work at 850 nm and 12 fibers, so they are both expensive and inflexible, and so are useful for a specific large project. They are not so useful for testing breakout cables. Many such units on the market today also have InGaAs detectors, which significantly degrade their test accuracy at 850 nm. They have limited MPO pin configuration compatibility, which may limit referencing options. Whatever test equipment is selected will need some good reporting software. It may be a project requirement that it s impossible to modify the test results, to prevent tampering. Procedure Loss testing using solution 2 will generally proceed as follows (remembering to inspect and clean on each insertion): 1. Begin by verifying the test cords. Once these are proven to be adequate: 2. Reference the source and meter using a breakout cable and the desired number of reference cords. 3. Set up the MPO power meter at the far end of the test system 4. Start with the light source at fiber 1 on the breakout cable, take the loss reading 5. Move the light source only to the next fiber on the breakout cord, and take the loss reading 6. Etc 7. Go back to fiber 1 and note the reading (is within limits compared to the 1 st time) We found that using a Kingfisher light source KI2803 with power meter KI2600XL-Ge5, and this technique, the repeatability was determined by the test cords. Ease of testing and speed were both good, since only the source needed moving for each fiber. Loss testing using solution 1 will differ in that the power meter will need to be moved for each fiber. This coordinated shuffle greatly slows down the test process, and is error prone. Page 6 of 6