SMM. Installation Operation Maintenance



Similar documents
PANASONIC TROUBLE SHOOTING GUIDE

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

INSTALLATION OPERATING & MAINTENANCE MANUAL

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

14. Troubleshooting Guide

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

USER S MANUAL HSC-24A

INSTALLATION MANUAL. Address card EKAC10B

SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI

30RB/30RQ. Operation and maintenance instructions

DIABLO VALLEY COLLEGE CATALOG

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

Instruction manual for Firstline FCS12000CH

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

Failure code manual. content

Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split

Variable Air Volume - VAV

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Statement of Work. 3.0 Details of Service Pre Start-up Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

Nirvana. Cycling Refrigerated Dryers

1 General information

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

Midea Commercial Air Conditioner Malfunction Handbook

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

CLOSE CONTROL SYSTEM. PFD series provide you with highly reliable computer room cooling system. High Reliability

, User s Manual

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SWIMMING POOL HEAT PUMP Owners Manual

Install Guide CT101. Caution. Caution

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

MAKING MODERN LIVING POSSIBLE. Wiring Diagram DHP-R.

MAC-120HE-01 Air-Cooled Chiller

1 For All Non-Programmable Digital Thermostat

Technical Support Bulletin Nr. 20 Special AC Functions

Portable Air Conditioner

T-100-R Installation Guide

HEAT PUMP PROGRAMMABLE THERMOSTAT

ABNORMAL OPERATION Error code Display. Specifics Error Code. Subsection Error Code. Subsection and Specifics Error code target

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Technical Information

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t.

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Hot Water. Heat pump water heaters. Residential and Commercial R410a

Liebert Deluxe System/3

PORTABLE AIR CONDITIONER

Alerts and Delta T Diagnostics with the Prestige 2.0 IAQ Thermostat

MP-4000 Alarm List (Software version or later)

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

ECOCIAT. Domestic hot water heat recovery unit

LOBOY 16 AIR CONDITIONERS

QUICK INSTALLATION GUIDE

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

NetworkAIR FM Precision Air Conditioner. Operation and Maintenance

Ammonia Detection System Codes and Design Specifications

Aerona Air Source Heat Pumps

REFRIGERATED TYPE COMPRESSED AIR DRYERS INSTRUCTION MANUAL. For Sales & Service please contact:

Refrigeration & HVAC

Why and How we Use Capacity Control

Ceiling Mount Air Handler Manual

Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI

MicroTech III Unit Controller for Water Source Heat Pump Units

Water Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING

Cooling kw Heating kw

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

Model: DC-A2IO Advanced HVAC Controller

your comfort. our world. DNSS EcoSave A/C remote monitoring and malfunction prediction

pco 2 Standard Application Pack Control Code: FLSTDMFC0A Version 1.2 s manual

How To Save Energy With High Pressure Control

Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N

Condensing unit type EPSILON-ECHOS LE Technical information manual

A Class Air Source Heat Pump User Guide

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Owners Manual 2009 PRICE LIST DRYMAXTM. Compressed Air Treatment Products. Refrigerated Air Dryers

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

Wiring Diagram. Diplomat 400V 3N.

4 Alarm and info. Alarm. Yes Warning. No Information No Reset alarms > No Current list > Alarm log list > Delete alarm log > No

Owner s Manual RBC-AMS41E. Remote controller with weekly timer. Owner s Manual

MicroTech III Unit Controller for Water Source Heat Pump Units

COMPTROL 5000 INDEX 52. Issue 5.99 AIR CONDITIONING MICROPROCESSOR OPERATING INSTRUCTIONS. STULZ GmbH, Hamburg

Install Guide 3M-50. Caution. Caution

Automation System TROVIS 5100 Ventilation Controller TROVIS 5177

HEAT HEAT COOL HEAT PUMP COOL

User manual. Application program for pco 1, pco 2, pco 3. Standard Chiller Modular HP 1/4 Generic /Bitzer screw compressor and CAREL valve

WHITE-RODGERS COMFORT-SET 90 SERIES

Thermostat with display

COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

Heat Pump Water Heater IOM Manual

Transcription:

SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation

Foreword These installation, operation and maintenance instructions are given as a guide to good practice in the installation, putting into service, operation, and maintenance by the user, of Trane SMM chillers.they do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Warranty Warranty is based on the general terms and conditions of Société Trane or Trane UK Ltd. The warranty is void if the equipment is repaired or modified without the written approval of Trane, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of chapter "Maintenance", it may entail cancellation of warranty and liabilities by Trane. Reception On arrival, inspect the unit before signing the delivery note. Specify any damage on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the local Trane Sales Office at the same time. The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the local Trane Office. Units are shipped with the refrigerant operating or holding charge and should be examined with an electronic leak detector to determine the hermetic integrity of the unit. The refrigerant charge is not included in the standard Trane Warranty Cover. General information About this manual Cautions appear at appropriate places in this instruction manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel. About the unit These SMM units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information contained in this manual applies to units designated SMM. Refrigerant The refrigerant provided by Société Trane or Trane UK Ltd meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the Société Trane or Trane UK Ltd warranty could be cancelled. American Standard Inc. 1999 2

Content Hardware...4 Function of the keys O and 1...5 Function of the keys,, + and -...5 How to reset the SMM?...5 Content of the menu A General information...5 B Customer configuration...6 C Events log and reset...6 D Customer configuration (rest)...6 E Information on pressures and refrigerant temperatures and optional temperatures...7 Explanation of the fault codes....8 3

Hardware Module Base Module de base 1 0 Auxiliary Modèle auxiliaire Module 4 3 2 1 When the jumper is in position 1, the auxiliary module is used to control the circuit 2. When the jumper is in position 2, the auxiliary module is used to control the fans. When the jumper is in position 3, the auxiliairy module is used to control the leaving hot water temperature. When the jumper is in position 4, the auxiliary module is used to allow to display the evaporator and condenser inlet water temperatures. 4

Operation of the module Function of keys O and 1 The key 1 is used to allow the start of the compressor. The key O is used to stop the chiller. When the operator press on key O, the following message appears : A operator stop How to reset the SMM? Press on the key 1. The hour and the leaving chilled water temperatures are displayed. The orange LED is switched off. Notes If one of the following faults is displayed : M comp A1 fault M comp A2 fault M comp B1 fault M comp B2 fault the corresponding overload relays must be reset before to reset the SMM. If one of the following faults is displayed M CKT 1 fault M CKT 2 fault the corresponding high pressure pressostats must be reset before to reset the SMM. How to have access to the menu A? Press 1 time on the key The following message appears Press 1 time on the key + **** A **** Chilled water set point is displayed. A 01 Value C To have access to the following information, press the key To exit the menu press the key during a few seconds. Information contained in the menu A A01 Active water setpoint A02 Evaporator water outlet mix temperature A03 Circuit 1 evaporator water outlet temperature A04 Circuit 2 evaporator water outlet temperature A05 Air temperature A06 Number of compressor A1 operating hours A07 Number of compressor A1 starts A08 Number of compressor B1 operating hours A09 Number of compressor B1 starts A10 Number of compressor A2 operating hours A11 Number of compressor A2 starts A12 Number of compressor B2 operating hours A13 Number of compressor B2 starts. 5

How to have access to the menu B? Press twice on the key The following message appears How to have access to the menu C? Press 3 times on the key The following message appears **** B **** **** C **** Press 1 time on the key + The leaving chilled water temperature set point value is displayed. To change the value, press on the keys + or - To have access to the following parameters, press on the key To change the value of these parameters, press on the keys + or - To exit this menu, press the key during a few seconds. Parameters which can be modified in the menu B B01 Evaporator outlet temperature setpoint Setting -26.0 C to 30.0 C by 0,1 C increment. Default value 6.0. B02 Hot water outlet temperature setpoint Setting 20.0 C to 60.0 C by 0,1 C increment. Default value 45.0. B03 Auxiliary water outlet temperature sepoint Setting - 26.0 C to 60.0 C by 0,1 C increment. Default value 6.0. B04 Circuit 1 ON validation Enabled circuit : Enable. Disabled circuit : Disable. Default value : Enable B05 Circuit 2 ON validation Enabled circuit : Enable. Disabled circuit : Disable. Default value : Enable B06 Operating mode Cooling mode : Cooling Heating mode : Heating Serial link control : Extern Default value : Cooling B07 Remote control validation Remote control : Remote Local control : Local Default value : Local B08 Auxiliary setpoint validation Enabled circuit : Enable. Disabled circuit : Disable. Default value : Disable B09 Current date display B091 day - setting 1 to 31 B092 month - setting 1 to 12 B093 year - setting 00 to 99. B10 Current hour display B101 hour - setting 00 to 23 B102 Minutes - setting 00 to 59 B103 Seconds - setting 00 to 59. B11 Set this parameter at 0,0 C B12 Set this parameter at 0,0 C B13 Set this parameter at 0,0 C Press 1 time on the key + The last fault is displayed. Press successively on the key + to display the last 20 faults Press succesively on the key - to display the last fault. To exit this menu, press during a few seconds on the key. This menu is used also to reset the SMM (see parapragh How to reset the SMM?) How to have access to the menu D? Press 4 times on the key The following message appears Press 1 time on the key + The following message appears D01 **** D **** None To change the value, press on the keys + or - To have access to the following parameters, press on the key To change the values of these parameters, press on the keys + or -. To exit this menu, press on the key during a few seconds. Parameters which can be modified in the menu D D01 Cooling setpoint reset type None : None - On air : Air - On water : Ret. Wat. - Default value : None D02 Cooling reset starting value Setting 2 C to 55 C by 0,1 C increment. Default value 20.0. D03 Cooling reset value range Setting 2 C to 20 C by 0.1 C increment. Default value 10.0. D04 Cooling reset range Setting -15 C to 15 C by 0.1 C increment. Default value 5.0. D05 Heating setpoint reset type None : None - On air : Air - On water : Ret. Wat. - Default value : None D06 Heating reset starting value Setting 2 C to 55 C by 0,1 C increment. Default value 20.0. D07 Heating reset value range Setting 2 C to 20 C by 0.1 C increment. Default value 10.0. D08 Heating reset range Setting -15 C to 15 C by 0.1 C increment. Default value 5.0. 6

D09 Generic input type 0..10 Volts 0..10 V 2..10 Volts 2..10 V 0.20 ma 0..20 ma 4..20 ma 4..20 ma Default value 0..10 V 10 V or 20 ma lead to a chilled water temperature set point reset of 20 C. D10 Evaporator pump stop timer Setting 1 to 10 mn by 1 mn increment. Default value 1. D11 Evaporator water pump automatical cleaning None None 6 hours 6 H 12 hours 12 H 24 hours 24 H 48 hours 48 H Default value None D12 Compressor lead-lag Increasing fix 1-2 Decreasing fix 2-1 Start and hour balancing Auto Automatic inversion at each start TRANE Default value TRANE The parameters D13 and D14 are used to determine the conditions under which the fault relays switch on. D13 Default 1 report type Displayed value Unit or circuit 1 manual reset default bit 0 1 Unit or circuit 2 manual reset default bit 1 2 Unit or circuit 1 automatic reset default bit 2 4 Unit or circuit 2 a utomatic reset default bit 3 8 Circuit 1 not available or in limit bit 4 16 Circuit 2 not available or in limit bit 5 32 Informational default on unit bit 6 64 Default value 1 D14 Default 2 report type Unit or circuit 1 manual reset default bit 0 1 Unit or circuit 2 manual reset default bit 1 2 Unit or circuit 1 automatic reset default bit 2 4 Unit or circuit 2 automatic reset default bit 3 8 Circuit 1 not available or in limit bit 4 16 Circuit 2 not available or in limit bit 5 32 Informational default on unit bit 6 64 Default value 2 Example : on a 2 circuit unit, we wish that the fault relay 1 (D13) switches on if a manual or an automatic reset fault occur. i.e.in the cases corresponding to the bits 0, 1, 2, and 3. In this case, we have to display the value 15 (1+2+4+8) D15 Serial link address Setting 0 to 62. Default value 0. Example of programmation of the chilled water temperature set point in function of the air temperature Expected operation Set Point point de ( C ) consigne ( C) 12 7 Values to be programmed Parameter Use For comfort type application, increasing the reset point when the air temperature decreases allows to obtain better C.O.P. at part load, so to decrease the energy consumption. How to have access to the menu E? Press 5 times on the key The following message appears Press 1 time on the key + 20 30 Outside Temp. temp.( C ) ext. ( C) Value B01 12,0 D01 The saturated refrigerant temperature inside circuit 1 evaporator is displayed. To have access to the following information, press on the key To exit this menu, press on the key during a few seconds. Air D02 20,0 D03 10,0 D04-5,0 **** E **** E 01 value C Information contained in the menu E E01 Circuit 1 evaporator saturated temperature E02 Circuit 1 evaporator saturated pressure E03 Circuit 1 condenser saturated temperature E04 Circuit 1 condenser saturated pressure E05 Circuit 2 evaporator saturated temperature E06 Circuit 2 evaporator saturated pressure E07 Circuit 2 condenser saturated temperature E08 Circuit 2 condenser saturated pressure E09 Evaporator water inlet temperature E10 Condenser water outlet temperature E11 Condenser water inlet temperature 7

Explanation of the fault codes Displayed Description Action messages I Service demand Service request on the unit : one of the compressor Contact Trane Service Agency configurated as presently has reached the value 1 I E2P par. chg When powering-up the module, one or more of the Check the configuration operating parameters in E2PROM was incorrect and has been corrected (default value). Check the configuration. I XRAM par. chg When powering-up the module, one or more of the Check the configuration operating parameters in XRAM was incorrect and has been corrected (default value). Check the configuration. I E2P par. prog. When powering-up the module, all the operating Check the configuration parameters in EPROM were incorrect and have been replaced by their default value. Make the configuration. A User ckt1 stop Circuit 1 is forced to stop due to the operator s For info only. No necessary action configuration (menu B04) A User ckt2 stop Circuit 2 is forced to stop due to the operator s For info only. No necessary action configuration (menu B05) A Ext. ckt1 stop Circuit 1 is forced to stop due to an external cause, For info only. No necessary action by the O/I input Auto/Stop 1. A Ext ckt2 stop Circuit 2 is forced to stop due to an external cause, For info only. No necessary action by the O/I input Auto/Stop 2. A Rem. ckt1 stop Circuit 1 is forced to stop by the serial link. For info only. No necessary action A Rem. ckt2 stop Circuit 2 is forced to stop by the serial link. For info only. No necessary action A User unit stop Unit is forced to stop due to the operator s For info only. No necessary action configuration. On single circuit units, this message is displayed if circuit 1 is devalidated (menu B04). On dual circuit this message is displayed if both circuits 1 and 2 are devalidated (menu B04 and menu B05) A Ext. unit stop Unit is forced to stop due to an external causes. On For info only. No necessary action single circuit units, this message is displayed if circuit 1 is devalidated (O/I input Auto-Stop 1). On dual circuit units, this message is displayed if both circuits 1 and 2 are devalidated (O/I input Auto/Stop 1 and Auto/Stop 2). A Rem. unit stop Unit is forced to stop by the serial link. On single For info only. No necessary action circuit units, this message is displayed if circuit 1 is devalidated by the serial link. On dual circuit units, this message is displayed if both circuits 1 and 2 are devalidated by the serial link. A Operator stop The unit is stopped by the operator who has pushed For info only. No necessary action key O. I E2prom fault A default occured when writing information in Switch off the SMM during 5 seconds E2PROM. The value in memory may not be right and thus corrected at next powering-up. A Ckt1 limiting One of the compressors of circuit 1 is prevented to For info only. No necessary action start because one of the limitation is active (evaporator 1 outlet water temperature below the evaporator outlet water temperature low setpoint, evaporator 1 refrigerant temperature below the refrigerant temperature low setpoint, evaporator outlet temperature too high). A Ckt2 limiting One of the compressors of circuit 2 is prevented to For info only. No necessary action start because one of the limitation is active (evaporator 2 outlet water temperature below the evaporator outlet water temperature low setpoint, evaporator 2 refrigerant temperature below the refrigerant temperature low setpoint, evaporator outlet water temperature too high). NB : this message can be displayed on 3 compressor units but without any influence on the operation of circuit 2. 8

Displayed Description Action messages A Ckt1 HP limit. The condenser side refrigerant pressure on circuit 1 Check condenser cleaning and fan is too high, and the system reduces the number of state. compressors in operation until its complete stop if necessary. A Ckt2 HP limit. The condenser side refrigerant pressure on circuit 2 Check condenser cleanliness and fan is too high, and the system reduces the number of state. compressors in operation until its complete stop if necessary. A Low ambience The outdoor air temperature is lower than For info only. No necessary action the low ambient setpoint. A Ckt1 defrost Circuit 1 is de-icing and thus preventing the operation For info only. No necessary action of circuit 2 (if present) A Ckt2 defrost Circuit 2 is de-icing and thus preventing the operation For info only. No necessary action of circuit 1. A EVP water flow Loss of evaporator water flow during more than Check chilled water pump state. 2 sec. If one of the compressor was operating, then the default LED is lit, if not, it is not lit. A Sensor 4 main The customer analogical input is configurated as Check configuration of parameter D09 2..10V or 4..20 ma and the signal is lower than and analogic inlet. 1V or 2mA. A Sensor 1 I/O 2 Sensor 1 (air temperature) of module I/O 2 is out of Change the sensor. range (short circuit < -40 C, or circuit open > 80 C). A Sensor 1 I/O 3 Sensor 1 (condenser water outlet temperature) of Change the sensor. module I/O 3 is out of range (short circuit < -40 C, or circuit open > 80 C). A Sensor 1 I/O 4 Sensor 1 (evaporator water inlet temperature) of Change the sensor. module I/O 4 is out of range (short circuit < -40 C, or circuit open > 80 C). A Sensor 1 main Sensor 1 (evaporator 1 water outlet temperature) of Change the sensor. the main module is out of range (short circuit < -40 C, or circuit open > 80 C). A Sensor 2 main Sensor 2 (evaporator 1 refrigerant saturated Change the sensor. temperature) of the main module is out of range (short circuit < -40 C, or circuit open > 80 C). A Sensor 3 main Sensor 3 (evaporator 1 refrigerant saturated Change the sensor. temperature) of the main module is out of range (short circuit < -40 C, or circuit open > 80 C). A Sensor 1 I/O 1 Sensor 1 (evaporator 2 water outlet temperature) of Change the sensor. module I/O 1 is out of range (short circuit < -40 C, or circuit open > 80 C). A Sensor 2 I/O 1 Sensor 2 (evaporator 2 refrigerant saturated Change the sensor. temperature) of module I/O 1 is out of range (short circuit < -40 C, or circuit open > 80 C). A Sensor 3 I/O 1 Sensor 3 (condenser 2 refrigerant saturated Change the sensor. temperature) of module I/O 1 is out of range (short circuit < -40 C, or circuit open > 80 C). A Com I/O 1 The main module does not communicate anymore Check the link wiring with module I/O 1. Check the link wiring with this module as well as its address (circuit 2 board) A Com I/O 2 The main module does not communicate anymore Check the link wiring with module I/O 2. Check the link wiring with this module as well as its address (air-cooled unit board) A Com I/O 3 The main module does not communicate anymore Check the link wiring with module I/O 3. Check the link wiring with this module as well as its address (reversible unit board) A Com I/O 4 The main module does not communicate anymore Check the link wiring with module I/O 4. Check the link wiring with this module as well as its address (option board) 9

Displayed Description Action messages M Fan inverter 1 Speed variator number 1 shows a problem during Not used a period longer than authorized. No circuit stop. M Fan inverter 2 Speed variator number 2 shows a problem during Not used a period longer than authorized. No circuit stop. A Fan protection One of the fan circuit breaker has tripped-out. Check fan state M Low ref. ckt1 Evaporator 1 refrigerant saturated temperature has Check expansion valve state and overtaken the refrigerant low temperature setpoint. refrigerant load M Low ref. ckt2 Evaporator 2 refrigerant saturated temperature has Check expansion valve state and overtaken the refrigerant low temperature setpoint. refrigerant load M Low water ckt1 Evaporator 1 water outlet temperature has overtaken Check chilled water flow the evaporator water low temperature setpoint. M Low water ckt2 Evaporator 2 water outlet temperature has overtaken Check chilled water flow the evaporator water low temperature setpoint. M Pressure ckt1 Circuit 1 has been put in consecutive stand-by too Check condenser cleanliness near : thus it is stopped. M Pressure ckt2 Circuit 2 has been put in consecutive stand-by too Check condenser cleanliness near : thus it is stopped. M Discharge ckt1 One of the circuit 1 compressors has operated during Check refrigerant load a too long period with a high discharge temperature : thus it is stopped. M Discharge ckt2 One of the circuit 2 compressors has operated during Check refrigerant load a too long period with a high discharge temperature : thus it is stopped. M Bypass ckt1 The hot gas by pass valve, used as an anti-freeze Not used protection has been requested during too long a period : the circuit 1 is stopped. M Bypass ckt2 The hot gas by pass valve, used as an anti-freeze Not used protection has been requested during too long a period : the circuit 2 is stopped. M Comp. A1 fault The compressor A1 default I/O input shows a default. Reset the overload relay of compressor A1 M Comp.B1 fault The compressor B1 default I/O input shows a default. Reset the overload relay of compressor B1 M Comp. A2 fault The compressor A2 default I/O input shows a default. Reset the overload relay of compressor A2 M Comp. B2 fault The compressor B2 default I/O input shows a default. Reset the overload relay of compressor B2 M ckt1 fault HP or LP fault on circuit 1 Reset pressostat HP, circuit 1 M ckt2 fault HP or LP fault on circuit 2 Reset pressostat HP, circuit 2 M Unit fault All the present compressor default I/O inputs Reset pressostats and thermal relays simultaneously show a default. Note The first letter of the displayed message indicates the type of default I = for information A = automatic reset default M = manual reset default. 10

Notes 11

Safety recommendations To avoid accidents and damage, the following recommendations should be observed during maintenance and service visits : 1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter "Installation". Always provide a pressure regulator. 2. Disconnect the main supply before any servicing on the unit. 3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel. Maintenance contract It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your intallation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty. Training The equipment described in this manual is the result of many years of research and continuous development. To assist you in obtaining the best use of it, and maintaining it in perfect operating condition over a long period of time, the constructor have at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and maintenance technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owing the unit by avoiding serious and costly breakdown. The constructor's policy is one continuous product improvement, and he reserves the right to alter any details of the products at any time without notice For additional information, contact : This publication is a general guide to install, use and properly maintain our products. The information given may be different from the specification for a particular country or for a specific order. In this event, please refer to your nearest office. Distributor / Installer stamp All rights reserved. No part of this publication may be reproduced or transmitted in any form or by any means without the written authorization of the constructor. L80 IM 022 GB - 0697 Supersedes L80 IM 022 E - 1196 Société Trane - Société Anonyme au capital de 41 500 000 F - Siège Social : 1, rue des Amériques - 88190 Golbey - France - Siret 306 050 188-00011 - RCS Epinal B 306 050 188 - Numéro d'identification taxe intracommunautaire : FR 83 306050188 An American Standard Company Printed in France Imprimeur