HVAC Applications. VFD considerations for HVAC systems...



Similar documents
The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

HVAC Processes. Lecture 7

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Variable Speed Drives

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

Commissioning - Construction Documents (Page 1 of 6)

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Drives and motors. A guide to using variable-speed drives and motors in data centres

Unidrive M Energy Savings

Yorkland Controls Ltd. Environmental Solutions TORONTO + MISSISSAUGA + LONDON (T)

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

VARIABLE FREQUENCY DRIVES Revised 4/30/ Mechanical Systems

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

VLT 6000 HVAC Series Contents

Commercial & Municipal Retrofit 2015 VFD Rebate

32VFD Variable Frequency Drives for Centrifugal Chillers

HVAC Systems: Overview

Heating, Ventilation and Air Conditioning Rebate Catalog Saving energy for a brighter future

Impact of Control System Technologies on Industrial Energy Savings

Specifying a Variable Frequency Drive s

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:


for Plans Examiners and Building Inspectors

Centrifugal Fans and Pumps are sized to meet the maximum

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Product Data Bulletin

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Introduction to Building Automation Systems (BAS)

Variable Air Volume - VAV

Fundamentals of HVAC Control Systems

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

Line Reactors and AC Drives

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Topvex SX/C, Topvex TX/C. Air Handling Unit

Element D Services Heating, Ventilating, and Air Conditioning

Energy Design Resources Commissioning Plan Outline Template

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

3/29/2012 INTRODUCTION HVAC BASICS

HVAC DRIVE H300 HVAC Drive for Building Automation

1 Temperature Derating Guide

EnVisioneering.

DIABLO VALLEY COLLEGE CATALOG

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

Printing and Publishing Energy Savings Guide

Conversion From Constant Flow System To Variable Flow

Sample - Existing Building Commissioning Plan

3466 Building Energy Management Training Systems

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

1.2 Refrigerant Equipment. General

Failure code manual. content

Introducing Bihun Commercial Services, Inc.

SmartVFD HVAC and BYPASS

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

HEATING, VENTILATION & AIR CONDITIONING

Building Controls MORE than a Time Clock. Building Automation is a Tool for the building to use to manage their environment

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

NX Series Inverters. HVAC Pocket Programming Guide

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

AABC Specifications for Testing and Balancing HVAC Systems

14. Troubleshooting Guide

Condensing Boiler Efficiency

Harmonic Distortion and Variable Frequency Drives

SECTION VARIABLE FREQUENCY DRIVES

ENHANCED LABORATORY HVAC SYSTEM

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

CGC s Hybrid System Loop Control

vacon hvac ac drives

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

G120P variable speed drive boost efficiency, cut costs

Using Time-of-Day Scheduling To Save Energy

Low voltage AC drives. ABB drives for HVAC Committed to your comfort zone

ASTACEA4 Inspect complex/central air conditioning systems

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

HVAC and Lighting Control Products for Open Building Automation Systems

CONTROL STRATEGIES FOR HVAC SYSTEMS

Product Data Bulletin

Relationship between large subject matter areas

How To Clean Up A Reactor Water Cleanup

Power Quality. Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost

Variable Frequency Drives and Energy Savings

NXL Series Inverters. HVAC Inverters made simple

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

HVAC Preventative Maintenance Basics. Presented by Mike Crawley

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

Drives and motors. A guide to using variable-speed drives and motors in car parks

Discover the power of e-learning! The Quick Guide to AC Variable Frequency

Model: DC-A2IO Advanced HVAC Controller

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

BSD Technical Standard Division 23: HVAC

HVAC BUILDING SERVICES

Transcription:

HVAC Applications VFD considerations for HVAC systems... 1

COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES) FREQ. DRIVE INVERTER DRIVE Inverter Duty Motors =?? = New motors meet NEMA MG 1, Part 31 = peak voltage of 1600 volts and a minimal rise time of 0.1 microseconds 2

Typical Large HVAC System Cooling Tower Fans Secondary Hot/Chilled Water Pumps Systems don t necessarily have all components. Supply Fan Condenser Water Pump Primary Hot/Chilled Water Pumps Return Fan 3

Good Retrofit Candidates Large energy cost saving possibility Large motors Poor present efficiency Flows manually throttled back Malfunctioning mechanical flow modulation Inefficient control methods High energy costs Easy retrofit 4

Why Flow Control? HVAC systems are designed for worst case situations. Most of the time they have excess capacity. Controlling flow Saves energy Improves occupant comfort 5

Methods of Flow Control Air flow Inlet guide vanes Outlet dampers Variable pitch in motion fan Adjustable speed Fluid flow Throttling valve (two-way) Bypass valve (three-way) Adjustable speed 6

Why Adjustable Speed? Energy savings Secondary pumping example 7

Energy Requirements Important Curves Pressure Setpoint Pressure 50 45 40 35 30 25 20 15 10 5 0 0 100 200 300 400 500 600 F low Pump Curve Operating Point Control Curve System Curve P P 8

Energy Requirements Pressure 50 45 40 35 30 25 20 15 Power a Flow x Pressure 10 5 0 0 100 200 300 400 500 600 Flow 9

Energy Requirements Pressure 50 45 40 35 30 25 20 15 10 5 0 0 100 200 300 400 500 600 Flow Desired Flow 10

Energy Requirements Two-Way Valve (Throttling) Power Pressure 50 45 40 35 30 25 20 15 10 5 0 0 100 200 300 400 500 600 Flow 11

Energy Requirements Three-Way Valve (Bypass) Pressure 50 45 40 35 30 25 20 15 10 5 0 0 100 200 300 400 500 600 Flow Power Balancing Valve 12

Energy Requirements Adjustable Speed Pressure 50 45 40 35 30 25 20 15 10 5 0 0 100 200 300 400 500 600 Power Flow 13

Why Adjustable Speed? Energy savings System control Reduced maintenance Sound control 14

Why Adjustable Frequency Drives? High efficiency Easy retrofit Replace the existing motor starter Flexible mounting Simple control Minimum maintenance 15

Typical Large HVAC System Heat Rejection Section Cooling Tower Fans Chiller Condenser Water Pump 16

Cooling Tower & Fluid Cooler Fan Cooling Tower Fan 17

Cooling Tower Fan Fan Motors 18

Cooling Tower Fan Notes Traditional Control Methods None Poor efficiency Staging cells in multi-cell towers Poor efficiency High mechanical stress Dual-speed motors Moderate efficiency High mechanical stress 19

Cooling Tower Fan Notes, continued Traditional Control Methods, continued Variable pitch in motion fans Good efficiency, when functioning High maintenance, often don t function Other Concerns Wasting highly treated water Audible noise 20

Condenser Water Pump Cooling Tower Fan Condenser Water Pump 21

Condenser Water Pump Cooling Tower Pump Pump Motors 22

Condenser Water Pump Cooling Tower From Cooling Tower Strainer Differential Pressure Switch (Flow Proof) Motor To Chiller Pump Motors 23

Condenser Water Pump Notes Traditional Control Methods No active control It is important to maintain design flow for Proper cooling tower operation Proper chiller operation However the pump is often over-sized to compensate for pipe scaling later on Manually close a valve to reduce flow If the valve is closed a lot, a drive can save significant energy 24

Condenser Water Pump Cooling Tower Fan Chiller Condenser Water Pump 25

Heat Rejection Section Chiller Chillers 26

Chiller Notes While the chiller has a large motor, Inaccurate control can cause major problems Some chillers require constant torque Less energy savings Be sure you know its design and operation before considering retrofitting a chiller with a drive 27

Rooftop Units 28

Rooftop Units Notes Rooftop units generally don t have cooling towers and condenser water pumps They are often direct exchange (DX) heat with the outside air It can be economical to retrofit drives in the DX section 29

Typical Large HVAC System Chiller Secondary Hot/Chilled Water Pumps Boiler Primary Hot/Chilled Water Pumps 30

CHW, HW (Water Source Heat Pump Circulating & Booster) Primary Pumps Boilers or Chillers Primary Hot/Chilled Water Pump 31

Primary Pumps From Chillers Primary Pumps 32

Primary Pumps Air Separator From Chillers To Chillers Secondary Pumps Primary Pumps 33

Primary Pump Notes Traditional Control Methods No active control The pump is often oversized Flow is reduced by Trimming the pump s impeller Closing a pressure reducing valve When a valve significantly reduces flow, a drive can provide large energy savings 34

Primary Pump Notes Although some modern chillers can accept some amount of flow variation, be careful about attempting to actively control flow through either part of the chiller 35

Secondary Pumps Automatic valves at each coil control the flow of water to the coil. Boilers or Chillers Secondary Hot/Chilled Water Pump Primary Hot/Chilled Water Pump Variable flow in the secondary loop. Constant or Variable flow in the primary loop. 36

Secondary Pump Valve Motor Secondary Pump 37

Secondary Pump Secondary Pumps Valves Motors 38

Secondary Pump Notes Traditional Control Methods Valves control flow through each coil Two-way throttling valve Three-way bypass valve For proper operation, drive systems require two-way valves Therefore, retrofitting systems with threeway valves is more expensive 39

Secondary Pump Notes Tertiary pump systems are much like secondary pump systems Because the size of the motors is generally quite small, energy savings may also be small 40

Single Pump Loop Boilers or Chillers 3-Way Valve Total flow is constant. Variable flow through the coils. Constant or Variable flow through the boiler/chiller. Hot/Chilled Water Pumps 41

Single Pump Loop Notes Pumping systems that do not have separate primary and secondary loops present unique problems It will take significant work to convert it to a primary/secondary system Vary the flow through a chiller based manufacturers specifications Approach such systems with caution 42

Typical Large HVAC System Air Supply Section Supply Fan Return Fan 43

Air Supply Section Supply Fan Supply Fan 44

Air Supply Section Supply Fan 45

Air Supply Section Supply Fan Fans Drive Belt Motor Sheaves 46

Supply Fan Notes Traditional Control Methods Constant air volume systems have no direct method of reducing air flow The flow of water through the coils determines the temperature of the conditioned space Variable air volume systems use VAV boxes to restrict or redirect air when less flow is needed 47

Supply Fan Notes Methods of reducing fan capacity Outlet dampers Low efficiency Require maintenance Inlet guide vanes Moderate efficiency Require maintenance Variable pitch in motion fans Better efficiency Very high maintenance/costs Often multiple dampers per fan One per fan 48

Supply Fan Notes Old methods of reducing fan capacity Variable speed belt drives Low efficiency High maintenance Eddy current drives Low efficiency at low speeds High maintenance 49

Supply and Return Fans Supply Fan Return Fan 50

Air Supply Section Return Fan Fan Belt Drive Disconnect Switch Motor 51

Return Fan Notes Notes Traditional Control Methods Not controlled Controlled like the supply fan The method of providing the control signal depends on the control system A fixed amount less than supply flow A fixed difference between building and outdoor air pressure 52

Return Fan Notes Notes The main purpose of the return fan is to keep from over-pressurizing the building Not all systems require return fans 53

Examples of Some Air Supply Systems A wide variety of systems are used to control air flow Some are easy to retrofit with drives Others require more work to retrofit with drives The following are a few examples 54

VAV System with Fan Capacity Control The sensors and control signals for drives are already present. 55

Open Loop VAV System The sensors and control signals for drives are already present. 56

VAV System with Perimeter Terminal Reheat Static Pressure Sensor The sensors and control signals for drives are already present. 57

Dual Duct VAV System One drive for each fan. The sensors and controls are already in place. 58

VAV System with Bypass Boxes Add Static Pressure Sensor Close bypass part of VAV boxes. Add static pressure sensor to control fan. 59

Dual Duct System Terminal units designed for constant air flow make fan speed control less attractive. 60

Multi-Zone System Constant volume, multi-zone system. Requires adding VAV boxes and pressure sensors. 61

Terminal Reheat System Constant volume, multi-zone system. Requires adding VAV boxes and pressure sensors. 62

Induction Reheat System The induction units require high air velocity to function properly. 63

CAV Fan & Clean Room Supply Fan Air Filter Conditioned Space Pressure Sensor Supply Fan Drive

Garage and Tunnel Fan Vent. Fan Smoke Sensor CO Sensor Vent. Fan Drive

Fume Hood Fan Fan Damper Positioning Motor & Limit Switch Fume Hood Fan Drive

Outside Air Damper Smoke Extraction Supply Fan Conditioned Space Close this damper Return Air Damper Return Fan Reverse this fan Smoke Sensor Relief Air Damper Supply Fan Drive

Stairwell Pressurization Fan Pressure Sensor Fan Drive

Exhaust Fan Fan Pressure Sensor Fan Drive

Application Interfacing Operator s controls Plain language for Operation Fault display Programming Manual speed control Remote mounting Application MACROs Hand/Off/Auto control Auto OFF HAND

Single Motor Bypass Circuit Breaker, Bypass & Output contactors and fuses to service the drive while running Points to consider Can the system run at full speed? Drive fusing Safety interlocks Automatic bypass Run permissive circuit

Application Interfacing Operator s controls Bypass Single motor Multiple motor

PI and PID Controller (Closed Loop / Set Point) Compares the desired process variable with the set point value Proportional to the error Integral function adds errors over time Derivative function considers the rate of change of error (only for fast response systems) PID Speed Control Reference Set Point Feedback Sensor Controlled System

Other Considerations Environment Enclosure type NEMA 1 NEMA 12 Circulating dust Dripping non-corrosive liquid NEMA 3R Outdoor

Other Considerations Environment 1-50 HP: NEMA 1 & 12, & 3R Outdoors = -15 to 50ºC (5 to 122ºF) No De-rate 60 HP - 550 HP: NEMA 1 & 12-15 to 40 C (5 to 104 F) Not exceed 10% de-rate @ 122 F

Harmonics What? Non-linear loads draw non-sinusoidal current from a sinusoidal line (current doesn t look like voltage): Non-incandescent lighting Computer Equipment UPS (Uninterruptible Power Supplies) Telecommunications equipment Copy machines Variable Frequency Drives Electronic/Controls for Facility Elec. Equip. / Systems, Security, HVAC / Mech. equipment Any load with a solid state AC to DC power converter 76

Harmonics Why worry? Harmonic Voltage Distortion Increased heating in motors and other electromagnetic equipment Noisy operation of electromagnetic equipment Malfunctioning of sensitive electronics Nuisance tripping of electronic circuit breakers Overheating of PF correction capacitors Tripping of PF protection equipment Equipment downtime Premature component failures Failed motors and capacitors 77

Harmonics Why worry? Harmonic Current Distortion Added heating in transformers and cables, reduces available capacity May stimulate a resonance condition Excessive voltage Shutdown / damage to electronic equipment May cause telephone or electronic interference Failed transformers, equipment Not in Compliance with CODES, STANDARDS, REGULATIONS, IEEE, GOOD DESIGN PRACTICE 78

Include: Reactors (Chokes) Least expensive when specified to be included with base drive package 5% impedance AC line reactors -or- DC link reactors Both types provide similar harmonic benefits Also Suppress voltage transients that can cause equipment damage Harmonic Distortion Calculations = only VFD contribution 79

RFI / EMI RFI = RADIO FREQ. INTERFERENCE conducted through the air EMI = ELECTROMAGNETIC INTERFERENCE conduct through AC power line EFFECTS SIMILAR TO HARMONIC DISTORTION! 80

RFI / EMI Hardware RFI / EMI FILTERS: WILL BE INCLUDED IN ALL VFD SIZES ACH 550: Meets EMC PRODUCT STANDARD EN61800-3 FOR THE FIRST Environment restricted level BENEFIT: VFD will not interfere with other electronic equipment Other electronic equipment will not interfere with VFD 81

Serial Communications BAS / DDC Company Alignment BACnet ALC (Automated Logic Corp.) Andover Controls Novar American Auto-Matrix Alerton Trane Delta Controls Teletrol Tridium JCI (Johnson Controls, Inc.) Honeywell KMC LonWorks Honeywell Invensys Distech Novar TAC (formally CSI) JCI Trane Staefa Circon ModBus RTU ASI Controls KMC Reliable Controls 82