ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers



Similar documents
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

Telecommunications Infrastructure Standard for Data Centers Tutorial

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc

Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942: Data Center Standards

Data Center Design Considerations

How To Write An Infrastructural Standard For Data Center Infrastructure

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Corning Cable Systems Optical Cabling Solutions for Brocade

Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Zone Distribution in the Data Center

Migration to 40/100G in the Data Center with OM3 and OM4 Optical Connectivity

Data Centre Design ready for your future

TIA STANDARD. Telecommunications Infrastructure Standard for Data Centers TIA-942 TELECOMMUNICATIONS INDUSTRY ASSOCIATION

Data Center Topology Guide

Network Topologies and Distances

TIA 569 Standards Update Pathways & Spaces. Ignacio Diaz, RCDD April 25, 2012

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER

Network Design. Yiannos Mylonas

Ethernet 301: 40/100GbE Fiber Cabling and Migration Practices

Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure

Data Center Cabling Design Trends

ADC KRONE s Data Centre Optical Distribution Frame: The Data Centre s Main Cross-Connect WHITE PAPER

AMP NETCONNECT Data Center Cabling Solutions

Corning Cable Systems Optical Cabling Solutions for Brocade

Data Center Design for 40/100G

BICSI NxtGEN & Global Data Center Standards Update

Specifying an IT Cabling System

DESIGN GUIDELINES. Local Area Network

Structured and Point to Point Network Cabling for Industrial Automation

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

What is a Datacenter?

Video Systems and Data Center Design Wiring Plant Designation Terminology Infrastructure Deployment

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

The Three Principles of Data Center Infrastructure Design WHITE PAPER

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction

InstaPATCH Cu Cabling Solutions for Data Centers

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

CommScope. Enterprise Data Center Design Guide.

Building a Tier 4 Data Center on a Tier 1 Budget

Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations

Building Telecommunications Infrastructure Requirements

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

SECTION TELECOMMUNICATION ROOMS

Minimum Standards for Data/Voice Infrastructure in New Building Construction

Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.

Top of Rack: An Analysis of a Cabling Architecture in the Data Center

Design Guide. Universal Connectivity Grid. SYSTIMAX Solutions from CommScope

Migration Strategy for 40G and 100G Ethernet over Multimode Fiber

HIGHSPEED ETHERNET THE NEED FOR SPEED. Jim Duran, Product Manager - Americas WHITE PAPER. Molex Premise Networks

DATA CENTER NETWORK INFRASTRUCTURE. Cable and Connectivity for the Most Demanding Networks. BerkTekLevitonTechnologies.com

Designing the Data Center

This presentation to be used in conjunction with:

UT Southwestern Medical Center Information Resources Cable Installation Standard

ADC-APC Integrated Cisco Data Center Solutions

Standards. 5 ANSI/TIA/EIA-569-A (CSA T530)

VIDEO SURVEILLANCE OVER UTP WHITE PAPER INTRODUCING VIPER VIDEO SURVEILLANCE

White Paper: 10 Gigabit Ethernet over Twisted Pair Copper Systems

ATTACHMENT F 050R CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Trends and Standards in LAN Cabling Systems Intelligent Buildings

Data and Voice Network Infrastructure

Intelligent Cable Management Systems

Giganet Copper Cabling Training

TC Grounding and Bonding for Telecommunications Systems

Obsolete Fiber Technology? Not in my Data Center!

Policy Title-Aquia Data Center Operational Policy & Procedure. Policy ID - TSD-ADC001. Version - Version: 1.0. Supersedes Version 1.

Cabling and Building Infrastructure for Technology

Opportunities in data centers for the ITS professional

** PROPRIETARY ** SAMPLE COUNTY DATA CENTER PROJECT BUDGET ** PROPRIETARY **

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011

Data Center Designs and Hospital Operations

Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc.

SYSTIMAX Solutions Data Center Planning Guide

Organizing and Managing Equipment Rooms

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

Security & Surveillance Cabling Systems

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

Cabinets 101: Configuring A Network Or Server Cabinet

CATEGORY 8: UNDERSTANDING THE NEW CATEGORY OF PERFORMANCE FOR BALANCED TWISTED PAIR CABLE

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

ANSI/TIA/EIA A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD

Products. Technology. Services. Delivered Globally. DATA CENTER SOLUTIONS

Data Center Network Infrastructure The Smart Choice For Your Data Center

Data Center Solutions

Gigabit Passive Optical Networks

Fabrics SDN and Big Data. What this means to your white space

How To Determine Data Center Reliability

Innovation. Volition Network Solutions. Leading the way in Network Migration through Innovative Connectivity Solutions. 3M Telecommunications

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

INTRODUCTION TO MEDIA CONVERSION

Pretium EDGE HD Solutions

Transcription:

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew jew@j-and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards subcommittee US Project Lead ISO/IEC data center standard 2006 J&M Consultants, Inc

Data Center Telecom Standards ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Co-chairs: Chris DiMinico & Jonathan Jew Published 2005 available through TIA at www.tiaonline.org ANSI/NECA/BICSI-002 Data Center Design and Implementation Best Practices co-chairs: Jonathan Jew & John Kacperski best practices complements TIA-942 2007 target

Purpose of TIA-942 Fill a void by providing nationally recognized standards for the design of data center telecommunications infrastructure. Provide information for a data center owners to understand data center design tradeoffs and to communicate design requirements to engineers and architects Establish a standard for data center tiers to replace several proprietary standards.

Purpose of TIA-942 Encourage early participation of telecom designers and information technology professionals in the data center design process Ensure that data centers can accommodate the needs of the equipment and technologies: Adequately sized cabling pathways Adequately sized and properly located telecom spaces Adhere to cabling distance restrictions for planned applications

Purpose of TIA-942 Define a standard telecommunications infrastructure for data centers Structured cabling system for data centers using standardized architecture and media Accommodate a wide range of applications (LAN, WAN, SAN, channels, consoles, building automation systems) Accommodate current and known future protocols (10 Gigabit Ethernet & 10 Gigabit Fibre Channel) Replace unstructured point-to-point cabling that uses different cabling for different applications Standards for data center telecom spaces and pathways Labeling scheme recommendations

Standard/Structured vs. Proprietary/Ptto-Pt Cabling Cabling can be used for multiple applications rather than installed for one application and then removed (or probably just left under the floor) Saves money Flexibility to deploy connections quickly Helps minimize under floor mess Multiple sources vs. single source Support for future high speed protocols Simpler troubleshooting & administration (improves uptime)

Why Structured Cabling is Important (Unstructured Example)

Why Structured Cabling is Important (Structured Example)

Relationship of Spaces BUILDING SITE BUILDING SHELL GENERAL OFFICE SPACE TELECOM ROOMS & EQUIPMENT ROOMS for spaces outside data center OFFICE BUILDING SUPPORT SPACE DATA CENTER SUPPORT STAFF OFFICES ENTRANCE ROOM(S) DATA CENTER ELECTRICAL & MECHANICAL ROOMS OPERATIONS CENTER TELECOM ROOM(S) for data center support spaces STORAGE ROOMS & LOADING DOCKS COMPUTER ROOM

Data Center Telecomm Spaces & Topology Offices, Operations Center, Support Rooms Horizontal Carriers Entrance Room (Carrier Equip & Demarcation) Backbone Carriers Telecom Room (Office & Operations Center LAN switches) Backbone Main Dist Area (Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes) Optional Backbone Cabling Backbone Horiz Dist Area (LAN/SAN/KVM Switches ) Backbone Backbone Horizontal Zone Dist Area Horizontal Optional Backbone Cabling Horiz Dist Area (LAN/SAN/KVM Switches ) Horizontal Optional Backbone Cabling Horiz Dist Area (LAN/SAN/KVM Switches ) Horizontal Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet)

TIA-942 Spaces Entrance Room (ER) - location of interface with campus and carrier entrance facilities Main Distribution Area (MDA) location of main cross-connect (MC) Horizontal Distribution Area (HDA) location of horizontal cross-connect (HC) Zone Distribution Area (ZDA) location of zone outlet (ZO) or consolidation point (CP) Equipment Distribution Area (EDA) location of horizontal cable outlet/patch panel server/equipment cabinets and racks

Collapsed Topology Carriers Carriers Offices, Operations Center, Support Rooms Main Dist Area (Carrier Equip, Demarcation, Routers, Backbone LAN/SAN/ KVM Switches, PBX, M13 Muxes) Computer Room Zone Dist Area Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet)

Distributed Topology with Multiple ERs Offices, Operations Center, Support Rooms Carriers Primary Entrance Room (Carrier Equip & Demarcation) Carriers Carriers Carriers Telecom Room (Office & Operations Center LAN switches) Main Dist Area (Routers, Backbone LAN/SAN Switches, PBX, M13 Muxes) Secondary Entrance Room (Carrier Equip & Demarcation) Horiz Dist Area (LAN/SAN/KVM Switches ) Computer Room Zone Dist Area Horiz Dist Area (LAN/SAN/KVM Switches ) Horiz Dist Area (LAN/SAN/KVM Switches ) Horiz Dist Area (LAN/SAN/KVM Switches ) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet) Equip Dist Area (Rack/Cabinet)

Data Center Cable Types Local codes may require use of plenum-rated cable or limited combustible cable, but Article 645 of NEC doesn t require it Single-mode fiber (WAN, MAN, LAN, SAN, proprietary channel) Multimode fiber (LAN, SAN, channel, video) 850-nm 50/125 recommended 734- or 735- type coaxial cable (E1, E3, T3) two per circuit (75 ohm cable & connectors)

Data Center Cable Types Unshielded twisted pair (UTP) - T1 & lower speed circuits, voice, BAS, video, LAN, KVM, console typically Category 6 or Augmented Category 6 in data centers Mainframe channels (ESCON & FICON) can be accommodated by structured cabling system but are outside scope of TIA-942 Computer clustering & peripheral cabling (e.g. SCSI, Infiniband, RS-232) are outside scope of TIA-942

Carrier Circuit Lengths in Data Centers Cat 3 instead of Cat 5e or Cat 6 reduces circuit lengths for T-1s and E-1s significantly 735 coax (mini-coax) instead of 734 coax reduces circuit lengths for T-3s, E-1s, and E-3s significantly Optical fiber distances can drop off significantly with intermediate connections or splices Circuit length restrictions may : require additional entrance rooms, limit the location of telecom equipment, limit the size of the computer room Require demarcation of carrier circuits in MDA instead of entrance rooms

Circuit with Intermediate Panels Maximum cable lengths from demarcation point: T-1 s over 24 AWG Cat 3 UTP: 520 ft 13.0 ft / panel T-1 s over 24 AWG Cat 5/5e/6/6a UTP: 632 ft - 6.4 ft / panel T-3 s over 735 mini coax: 246 ft 1.6 ft / patch panel T-3 s over 734 coax: 480 ft 3.1 ft / patch panel 1G & 10G Ethernet Distances over MM Fiber (ft) Protocol Fiber Type 2 pnls 3 pnls 4 pnls 5 pnls 6 pnls 7 pnls 8 pnls 1GB-SX 62.5/125 984 951 852 721 590 426 131 1GB-SX 50/125 1968 1738 1508 1246 918 524 32 1GB-SX 50/125 LO 3280 2624 2230 1771 1312 721 98 10GB-SX 62.5/125 108 108 108 98 82 62 26 10GB-SX 50/125 268 268 259 229 180 127 16 10GB-SX 50/125 LO 984 984 885 754 623 426 82

Computer Room & Entrance Room Requirements Min clear height of 2.6m/8.5 ft Min door size 1m/3ft wide 2.13/7ft high Min dist floor loading 7.2 kpa/150lbf/ft 2, recommended min 12 kpa/250 lbf/ft 2 20 o C to 25 o C 40% to 55% relative humidity (reduces ESD) Any sprinkler systems must be pre-action system Common bonding network (CBN) equipotential ground reference Bond all cabinets and racks individually to CBN Bond cable trays, conduits, HVAC units, building columns, PDUs, panel boards, raised floor (every 6 th pedestal) to CBN

Equipment Racks & Cabinets Equipment is mounted in racks & cabinets from the front provide adequate clearance for installation of equipment (minimum of 3 feet, 4 feet is recommended). Cabinets and racks should be aligned with one edge along the edge of the floor tile. Arrange cabinets and racks on raised floor to permit tiles along the front and rear of the cabinets and racks to be lifted Floor tile cuts should be no larger than necessary to minimize air pressure loss.

HOT AND COLD EQUIPMENT AISLES HOT AIR REAR FRONT FRONT REAR HOT AIR REAR FRONT CABINETS COLD CABINETS CABINETS AIR COLD AIR PREFORATED TILES PREFORATED TILES TELECOM CABLE TRAYS POWER CABLES TELECOM CABLE TRAYS POWER CABLES

Equipment Cabinets Front rails of cabinets must be recessed to provide adequate room for patch cables and wire managers Adequate space for cable management Arrange switches and patch panels to minimize patching between cabinets & racks Perforated tiles at front of cabinets One edge of cabinets placed at edge of tile

Under Floor Cabling Less cost than overhead if there is a raised floor Easier installation and better appearance than overhead cable tray Cables should be in cable trays - preferably wire basket or other trays that minimize blockage of airflow Provide adequate capacity for growth Separate fiber patch cords from copper cabling Separate twisted pair cable from power Full cable trays could potentially block airflow if not properly planned & coordinated (place in hot aisles) Confirm load of cable tray & cable on pedestals

Examples of Wire Basket Cable Trays For Cabling Under Raised Floor 24" 24" RAISED FLOOR TILE 1.375" 1.375" RAISED FLOOR TILE 8" FIBER 2" 4" 6" 6" 2" 4" 8" FIBER 1" SUPPORT STRUT SUPPORT STRUT 1" Main aisle fiber tray 4" 36" 12" 12" 12" min clearance between trays 18" 18" COPPER CABLING 6" 6" COPPER CABLING 1" SUPPORT STRUT SUPPORT STRUT 1" Main aisle copper tray 6" HOT AISLE 10.625" 4.625" HOT AISLE Server Row Server Row

Under Floor Example Color-coded PDU cables in hot aisles each cabinet fed from 2 PDUs Locking electrical receptacles Common Bonding Network/ Signal Ref Grid using bare copper conductor Each cabinet bonded to SRG Receptacles need to be labeled with PDU/panel ID & breaker #

Overhead Cabling Even in raised floors cable ladders typically installed over racks in telecom spaces for patching between racks (MDA/MDF, HDA/IDF, Entrance Room, Telecom Room/Closet) they are typically attached to the racks In server areas cable ladders/trays should be suspended from ceiling with multiple layers to provide adequate capacity Coordinate with other trades Requires adequate ceiling height for 12 clearance above each ladder Provide room for growth Separation from fluorescent lights (5 ) & power Protect fiber patch cords from copper

Overhead Cable Tray in HDA/IDF

Suspended Overhead Cable Tray 3 Layer cable tray system: Bottom layer copper Middle layer fiber Top layer power Signal Reference Grid in brackets attached to lower layer of trays Fiber patch cables may be in fiber duct attached to threaded rods

Patch Panels & Cable Management Good labeling speeds troubleshooting and reduces patching errors High density patch panels usually don t provide adequate space for labeling For non-angled patch panels, provide one-to-one ratio of patch panels to horizontal wire management Provide blank panels in empty spaces in cabinets Patch panels and cables should not block airflow from equipment Don t install patch panels on at both the front and back of a rack or cabinet to save space unless the patch panels can be serviced from the front

Facilities Specifications & Tiers Informative annex with general architectural, structural, electrical, mechanical, and telecommunications recommendations Annex includes detailed architectural, security, electrical, mechanical, and telecommunications recommendations for each Tier (expands on The Uptime Institute Tiers) Recommended specifications by tier are a uniform way to rate aspects of a data center design and are a starting point for initiating design requirements with qualified architects and engineers.

Reliability Tiers and Cabling

Future Work Additional revisions to electrical sections for harmonization with IEEE 1100 draft 2 Coaxial cabling addendum testing & additional specifications for connectors More detailed labeling standard for data centers Augmented Category 6 UTP 10 Gigabit Ethernet over UTP (10GBase-T) 10GBase-T over standard Cat 6 (up to 37 meters) with mitigation: Unbundle and randomize cables in the first 5 to 20 meters Unbundle and randomize patch cords Eliminate intermediate patch panels between horizontal cable patch panels and switches Use non-adjacent Cat 6 UTP ports for 10GBase-T Use Aug Cat 6 or shielded patch cords Longer patch cords Separate long and short cable runs

Conclusion TIA-942 is the first standard that specifically addresses data center telecommunications infrastructure. Primarily a telecom infrastructure standard, but about half of the content deals with facility requirements. Provides a flexible and manageable structured cabling system using standard media. Guidelines on a wide range of subjects useful to someone designing or managing a data center. TIA-942 is available now BICSI data center design best practices standard that complements TIA-942 is in development

QUESTIONS? Jonathan Jew Co-chair TIA TR-42.1.1 data center working group ANSI/TIA-942 Co-chair BICSI data center subcommittee ANSI/NECA/BICSI 002 Vice-Chair TIA TR-42.6 telecom administration subcommittee US National Committee Project Manager ISO/IEC 24764 data center standard President J&M Consultants, Inc. Website: www.j-and-m.com Email: jew@j-and-m.com