IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution



Similar documents
Transient Recovery Voltages (TRVs) for High-Voltage Circuit Breakers Part 2

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

The standards mentioned in this document

Design & Application of Power Circuit Breakers. Tutorial

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's

Contents. Description. Product Selection Guide

Medium Voltage Switchgear

High-Voltage GIS yesterday - today - tomorrow

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

A3-301 CURRENT INTERRUPTION WITH HIGH VOLTAGE AIR-BREAK DISCONNECTORS. J.H. SAWADA BC HYDRO (Canada) J.G. KRONE HAPAM B.V.

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS

How To Understand The Electrical Power Supply Of A Power Supply System

TWENTIES WORKSHOP, EWEA 2012 Unveiling the future energy system: full scale demonstrations to reach 2020 targets. 17th April 2012

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

Protection from Short-circuit

Cahier technique no. 193

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection

Capacitor Bank Switching with Vacuum Circuit Breakers

Trip circuit supervision relay. Type RXTCS

Unified requirements for systems with voltages above 1 kv up to 15 kv

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

Secondary Unit Substations

Product brochure Multi Functional Switchgear PASS M kv Flexible and compact switchgear solutions for windfarms

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

Engineering Specification

Proven vacuum switching technology from Siemens meets all requirements placed on circuit-breakers and contactors in medium-voltage switchgear up to

High-Voltage Circuit-Breakers 3AP1/ kv up to 550 kv. Power Transmission and Distribution

The Intelligent AX1 Switchgear for Medium Voltage

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

Safe and reliable distribution network ABB portfolio for medium-voltage indoor applications

Asset Management Plans

Primary and Secondary Electrical Distribution Systems

Outdoor vacuum circuit-breakers and reclosers for medium voltage. Switching technology for distribution networks. Answers for energy.

How To Choose A Transformer

Demand Outlook for T&D Electrical Equipment Market in India Transformer, Switchgear & Energy Meters

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Circulating Current Relay. Type IRXm

Fusible Disconnect Switch

Joslyn Clark Controls, Inc.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Medium voltage circuit breaker

ABB Fuses Competitive Advantages

ABB s Disconnecting Circuit Breakers Higher substation availability and lower environmental impact

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

cgmcosmos Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system

Disconnectors and Earthing Switches 36 kv up to 800 kv

New Distribution Class Arrester Ground Lead Disconnector Design Enhances Detonation Reliability and Improves Arrester Performance

What will MV switchgear look like in the future? by Jean-Marc Biasse

Advantages of Fixed Circuit Breaker Switchgear

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

Medium Voltage technical guide. Basics for MV cubicle design

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

SWITCHGEAR PROTECTION

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Hyperlinks are Inactive

High-Voltage Circuit-Breakers: Trends and Recent Developments Answers for energy.

Siemens Fusesaver. Highest availability and cost savings for your MV distribution network.

EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION

Primary-Side Transformer Protection

MEDIUM VOLTAGE SWITCHGEAR AND CONTROLGEAR MODEL MS-E. IEC /12 /15 kv 25, 31.5, 40 ka

SF6 Gas Insulated Ring Main Unit RMU. A Compact switchgear solution for secondary power distribution networks. Super Solution.

FACTS. Solutions to optimise network performance GRID

Permissible ambient temperature Operation Storage, transport

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Takfan Machinery and Mould Co Ltd. Plug in Bushing. LV Monoblock. RMU Bushing. 4 Way CT Terminal.

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Typical Data Requirements Data Required for Power System Evaluation

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

State, trends and evolutions of HV/EHV power cables systems and contributions of SC B1 to their ongoing progress

Welcome IEEE Members and Guests Jan 20, 2014

Medium voltage indoor circuit breakers ANSI/IEC solutions

Best Practice Catalog Generator Switchgear

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Gas-insulated switchgear type series 8DN8. up to 170 kv, 63 ka, 4000 A. Answers for energy.

6 ELECTRICAL PARAMETERS

SURGE PROTECTIVE DEVICES

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Magnus Callavik, ABB Power Systems, HVDC, Västerås, Sweden Phone: +46(0)

MEDIUM VOLTAGE SWITCHGEAR. DI-2, a modular concept combining all mediumvoltage

3AH5 Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Presentation to CIGRE Next Generation Network. Visit of Seine substation

Agenda February 28 PM: Medium Voltage. SIPROTEC technical workshop. Medium Voltage: cleverly & reliably switched. Q&A, Conclusion.

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Comparison between Gas- and Air Insulated Network Concepts with the Life Cycle Cost Method

NABL NATIONAL ACCREDITATION

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c Erlangen Germany.

EARTHING SYSTEM CALCULATION

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Transcription:

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January, 2008

IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Content Introduction to IEC Technical Committee 17 (TC17) for Switchgear & Controlgear IEC Standards for High-Voltage Switchgear & Controlgear Standardization of the Ultra High Voltage (UHV) level Harmonization of IEC & IEEE Standards 2 > D.Dufournet, January 2008, SWICON 2008 2

Introduction to IEC Technical Committee 17 (TC17) for Switchgear & Controlgear 3 > D.Dufournet, January 2008, SWICON 2008 3

Organization of IEC TC17 TC 17 Switchgear and Controlgear Chairman: D. Dufournet Secretary: A. Bosma SC 17A High Voltage Switchgear and Controlgear Chairman: D. Dufournet Secretary: A. Bosma SC 17C High Voltage Switchgear and Controlgear Assemblies Chairman: S. Theoleyre Secretary: H. Koch SC 17B Low Voltage Switchgear and Controlgear Chairman: S. Kjellnas Secretary: J. Briant SC 17D Low Voltage Switchgear and Controlgear Assemblies Chairman: D. Hier Secretary: G. von Trentini 4 > D.Dufournet, January 2008, SWICON 2008 4

Scope of IEC SC17A and SC17C Scope of SC17A To prepare international standards regarding specifications for high-voltage switchgear and controlgear rated above 1 kv a.c. or above 1.5 kv d.c. Scope of SC17C To prepare international standards covering prefabricated assemblies which are combination of one or more parts of switchgear and controlgear exceeding 1 kv a.c., together with associated control and power equipment, measuring, signaling, protective, regulating equipment etc. 5 > D.Dufournet, January 2008, SWICON 2008 5

Membership of IEC SC17A & SC17C SC 17A Participating countries : 26 Observer countries : 19 SC 17C Participating countries : 27 Observer countries : 17 India is a full member of SC17A and SC17C 6 > D.Dufournet, January 2008, SWICON 2008 6

Meetings of IEC SC17A & SC17C IEC SC17A & 17C have plenary meetings every 18 months. The more recent one was organized in New Delhi, in April 2007, at the invitation of the Indian Bureau of Standards, with support from IEEMA, Power Grid Co and Indian manufacturers. 7 > D.Dufournet, January 2008, SWICON 2008 7

IEC Standards for High-Voltage Switchgear & Controlgear 8 > D.Dufournet, January 2008, SWICON 2008 8

General on SC17A-SC17C standards Market relevance Proven by large participation of experts World-wide acceptance IEEE standards for HV Switchgear are currently harmonized with IEC Emerging technologies Revision of standards for vacuum switching devices New standards for disconnecting circuit-breakers, by-pass switches, controlled switching UHV and impact of distributed generation: under consideration at CIGRE, revision of standards are planned. 9 > D.Dufournet, January 2008, SWICON 2008 9

IEC Standards for Switchgear & Controlgear Numbering system for switchgear standards A common numbering system has been established for Highvoltage switchgear. IEC 62271 is the basis of the standards of SC17A (High-voltage Switchgear) and SC17C (Highvoltage Switchgear Assemblies). The following rule is applied to the numbering of the standards: Common standards prepared by SC 17A and SC 17C start with IEC 62271-1; Standards of SC 17A start with IEC 62271-100; Standards of SC 17C start with IEC 62271-200; Guides prepared by SC 17A and SC 17C start with IEC 62271-300. 10 > D.Dufournet, January 2008, SWICON 2008 10

IEC Standards for Switchgear & Controlgear Main standards from SC17A 60265-1 Switches < 52 kv (1998) under revision (62271-103) 60265-2 Switches 52 kv (1998) under revision (62271-104) 60470 Contactors & contactor-based motor-starters (2000) under revision (62271-106) 61634 Use and handling of SF 6, under revision (62271-303) 62271-1 Common specifications, published 2007-10 62271-100 HV circuit breakers Ed 1.2 (2006-10), under revision 62271-101 Synthetic testing Ed.1.0 (2006-05) under revision 62271-102 Disconnectors & earthing switches (2003-08) under revision 62271-105 Switch-fuse combinations (2002) 11 > D.Dufournet, January 2008, SWICON 2008 11

IEC Standards for Switchgear & Controlgear Main standards from SC17A 62271-107 Fused circuit-switchers (2005-09) 62271-108 Disconnecting circuit breakers (2005-10) 62271-109 Series capacitors by-pass switches (2006-08) 62271-110 Inductive load switching (2005-06), under revision 62271-111 Overhead, pad-mounted, dry vault, and submersible automatic circuit reclosers and fault interrupters for systems up to 38 kv (2005-11) IEC-IEEE Dual Logo standard, under revision 62271-300 Seismic qualification (2006-11) 62271-310 Electrical endurance c.b. 72.5 kv (2004-04) revision approved in 2007-10 12 > D.Dufournet, January 2008, SWICON 2008 12

IEC Standards for Switchgear & Controlgear Main standards from SC 17C 60932 Additional requirements for enclosed switchgear 72.5 kv in severe climatic conditions (1988), under revision (future 62271-304) 61639 Direct connection between transformer-gis (1996) 61640 Gas insulated transmission lines (1998-07) 62271-3 Digital interfaces based on IEC 61850 (2006-06) 62271-200 Metal-enclosed switchgear and controlgear 52 kv (2003-11), under revision 13 > D.Dufournet, January 2008, SWICON 2008 13

IEC Standards for Switchgear & Controlgear Main standards from SC 17C 62271-201 AC insulation-enclosed switchgear and controlgear (2006-6) 62271-203 Gas-insulated metal-enclosed switchgear above 52 kv (2003-11), under revision 62271-205 Compact switchgear assemblies for rated voltages higher than 52 kv (2008-01) 62271-207 Seismic qualification (2007-08) 62271-209 Cable connections for GIS > 52 kv (2007-08) 14 > D.Dufournet, January 2008, SWICON 2008 14

Standardization of UHV level 15 > D.Dufournet, January 2008, SWICON 2008 15

Standardization of UHV Standardization of the Ultra-High Voltage level (> 800 kv a.c.) A symposium on UHV was organized in Beijing 18-21 July 2007, by IEC-CIGRE- SAC-SGCC (State Grid Company of China). It concluded the technology is mature enough so that standardization can be done urgently to coincide with starting projects in China and India. 16 > D.Dufournet, January 2008, SWICON 2008 16

Standardization of UHV Standardization of the Ultra-High Voltage level (> 800 kv a.c.) The first step is the definition of rated voltage(s) and insulation levels by TC28 and TC8. Concerning high-voltage switchgear, IEC SC17A asked CIGRE SC A3 to set up a new working group to study technical requirements for UHV equipment. CIGRE WG A3-22 has started its work in January 2007, a final report is expected end of 2008. Similar work is done for UHV with D.C. Since November 2007, the work in IEC and CIGRE on UHV is coordinated by a Joint IEC-CIGRE Coordination Group. Deadline for standardization : end of 2010 or 2011 17 > D.Dufournet, January 2008, SWICON 2008 17

Standardization of UHV Some topics currently studied by CIGRE WGA3-22 Insulation level (work also in progress in IEC TC 28) Circuit breakers Terminal fault TRV (First pole to clear factor : 1.3 or 1.2) DC time constant (120 ms) Short-line fault (Line surge impedance) Capacitive current switching (current, voltage factor) Shunt reactor switching (controlled switching) Disconnectors & Earthing switches Bus-charging and bus-transfer current switching Secondary-arc extinction 18 > D.Dufournet, January 2008, SWICON 2008 18

Standardization of UHV Some topics studied by CIGRE WG A3-22 2.5 DC time constant 1.52-0.50-1.5 0.51 0 45ms 100ms 120ms 150ms 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 I m( p. u. ) 0. 1ms/ gr i d F= 50 Hz DC time constant (ms) Third peak (p.u.)* Third peak (relative value) Peak 3rd loop x Duration (relative value) 45 1.33 82.6 % 70.9 % 100 1.61 100% 100% 120 1.66 103.3 % 108.1 % 150 1.72 106.9 % 114.1 % 19 > D.Dufournet, January 2008, SWICON 2008 19

Standardization of UHV Some topics studied by CIGRE WG A3-22 Surge impedance for SLF 1.00 Quadruple conductors with 810mm 2 in cross-section carrying 30-50 ka collided at 100-200ms. UHV lines have a high number of conductors with a large cross section. Time to Bundle Contraction (Sec.) 0.70 0.50 0.30 0.20 0.10 0.07 0.05 0.03 0.02 Symmetrical current Asymmetrical current Increasing number of conductors with larger cross section 810mm sq. 4 conductors 0.01 0 10 20 30 40 50 60 400 Breaking Current (ka) For UHV lines with 6-8 bundle conductors, bundle contraction is not completed when the fault current is interrupted, between 50-80ms after a fault initiation. It follows that a surge impedance of 360 ohm may be sufficient. 20 > D.Dufournet, January 2008, SWICON 2008 20

Harmonization of IEC & IEEE Standards for High voltage Switchgear & Controlgear 21 > D.Dufournet, January 2008, SWICON 2008 21

Harmonization of IEC-IEEE Standards Introduction Major advances have been made over the past 12 years towards the harmonization of IEC and ANSI/IEEE standards for high-voltage circuit-breakers, especially for capacitive current switching and short-circuit breaking tests. Since 1995, three main actions were undertaken Harmonization of ratings and test requirements for capacitive current switching, Harmonization of TRVs for breaking tests of circuitbreakers rated 100 kv and higher, Harmonization of TRVs for breaking tests of circuitbreakers rated less than 100 kv. 22 > D.Dufournet, January 2008, SWICON 2008 22

Harmonization of IEC-IEEE Standards Capacitive current switching Revision prepared by a common IEC-IEEE Task Force Introduction of class C1 (low probability of restrike) and class C2 (very low probability of restrike) and new test requirements. Implemented by IEC SC17A in the first edition of IEC 62271-100 (2001-05) Implemented by the IEEE Switchgear Committee in IEEE C37.04a (2003-07) and C37.09a (2005-09) 23 > D.Dufournet, January 2008, SWICON 2008 23

Harmonization of IEC-IEEE Standards Harmonization of TRVs, Ur < 100 kv Using the input from several working groups of CIGRE SC A3, IEC SC 17A started in 2002 the revision of TRV requirements for circuit-breakers of rated voltages higher than 1 kv and less than 100 kv. Aim: to cover cases not yet covered in edition 1.1 of IEC 62271-100, mainly Breaking terminal fault currents in systems with low capacitance on the supply side of circuit-breakers; Breaking short-line fault currents in the case of direct connection of the circuit breaker to an overhead line and with rated voltages 15 kv and < 52 kv 24 > D.Dufournet, January 2008, SWICON 2008 24

Harmonization of TRVs, Ur < 100 kv Cable systems and line-systems Envelope of Line system TRV Envelope of Cable system TRV U c t 3 The rate of rise of recovery voltage (RRRV) for line systems is approximately twice the value for cable systems 25 > D.Dufournet, January 2008, SWICON 2008 25

Harmonization of TRVs, Ur < 100 kv Harmonization of TRVs between IEC and IEEE IEC TRV Table 1a t3 t 3 Ukaf c ANSI TRV Outdoor c.b. ANSI TRV Indoor c.b. COMMON TRV TRV Cable-systems TRV Line-systems 26 > D.Dufournet, January 2008, SWICON 2008 26

Harmonization of TRVs, Ur < 100 kv Classes of Circuit breakers Circuit breaker Ur < 100 kv Cable-system Class S1 CS SLF? No Line-system Class S2 LS Direct connection to OH line Yes Cable-system Class S2 LS Direct connection to OH line Yes Short-line fault breaking performance is required for class S2 27 > D.Dufournet, January 2008, SWICON 2008 27

Harmonization of IEC-IEEE Standards Harmonization of TRVs, Ur 100 kv The harmonization of TRVs for circuit-breakers of rated voltages equal or higher than 100 kv was prepared by IEC Working Group 23 with active participation from members of the IEEE Switchgear Committee. The most significant change proposed was the adoption by IEEE of the two-parameter and four-parameter description of TRVs that is used in IEC. It was also proposed that IEC changes some values of TRV parameters and adopts a two-parameter TRV for test duty T30 (at 30% of rated short-circuit breaking current). 28 > D.Dufournet, January 2008, SWICON 2008 28

Harmonization of TRVs, Ur 100 kv Voltage U(kV) 250.0 u c & E 2 4-Parameter Reference Line 200.0 E 1 150.0 u 1 100.0 50.0 Exponential - Cosine Envelope 0 0.0 0 50 100 150 200 250 300 350 400 0 t1 t2 T2 t(us) Exponential-Cosine TRV envelope from ANSI/IEEE and new 4- parameter TRV harmonized with IEC 29 > D.Dufournet, January 2008, SWICON 2008 29

Harmonization of TRVs, Ur 100 kv The recommendations from the WG were approved by IEC and lead to amendment 1 to IEC 62271-100 published in May 2002. The adoption of harmonized TRVs is still in progress in IEEE, there are few deviations from the values already adopted by IEC. 30 > D.Dufournet, January 2008, SWICON 2008 30

Harmonization of IEC-IEEE Standards Conclusion Major advances have been made during the past twelve years towards the harmonization of IEC and ANSI/IEEE standards for high-voltage circuit-breakers, especially for capacitive current switching and short-circuit making and breaking tests. It allows already to perform common tests for capacitive current switching. Harmonization of TRVs for short-circuit breaking tests is in progress, IEC has already adopted the harmonized values in amendment 1 to IEC 62271-100, the work is well advanced in IEEE and should be completed shortly. When completed, harmonization of TRVs will allow to have common making and breaking tests according to IEC and ANSI/IEEE. 31 > D.Dufournet, January 2008, SWICON 2008 31

IEC & IEEE Switchgear Standards Conclusion IEC is actively revising its standards and creating new standards for high-voltage switchgear and controlgear, Experts from India, and 25 other national committees, are encouraged to join us in our continuous effort to improve our standards. 32 > D.Dufournet, January 2008, SWICON 2008 32

Thanks for your attention Good success to SWICON 2008 Questions? 33 > D.Dufournet, January 2008, SWICON 2008 33