MEDIUM VOLTAGE SWITCHGEAR AND CONTROLGEAR MODEL MS-E. IEC /12 /15 kv 25, 31.5, 40 ka

Size: px
Start display at page:

Download "MEDIUM VOLTAGE SWITCHGEAR AND CONTROLGEAR MODEL MS-E. IEC 62271-200 7.2 /12 /15 kv 25, 31.5, 40 ka"

Transcription

1 SWITCHGEAR AND CONTROLGEAR MODEL MS-E IEC /2 /5 kv,, ka

2 The MS-E conforms to IEC standard and is designed and manufactured utilising Mitsubishi Electric state-of-the-art technology, fully taking into account present and future power system requirements. Mitsubishi Electric has manufactured hundreds of thousands of medium voltage Page FEATUR 3 panels over the last almost 60 years. With this experience, Mitsubishi Electric has gained a reputation of manufacturing up-to-date and reliable medium voltage panels, and possesses a supply record that comprises satisfied customers from all across the globe. APPLICATIONS STANDARD RATINGS CONSTRUION. ENCLOSURE AND PARTITIONS 2. BUSBAR 3. VACUUM CIRCUIT BREAKER () 4. FUSED VACUUM CONTAOR 5. AUTOMATIC SHUTTERS 6. CABLE COMPARTMENT / CURRENT TRANSFORMERS 7. WIRING 8. EARTHING BUSBAR SWITCHGEAR ARRANGEMENT. EXAMPLE 2. STANDARD SEION VIEW AND DIMENSIONS 3. FOUNDATION 3 STANDARD DIGN 8 MS-E with gas exhaust duct MS-E with gas screen ka internal arc fault test of MS-E at KEMA s Netherlands laboratory Type testing of the MS-E was first performed at Mitsubishi Electric s High Power Testing Laboratory in Japan, and then by an independent external testing and certification authority, KEMA, in the Netherlands.. ENCLOSURE AND STRUURE 2. BUSBAR AND CONNEING CONDUOR 3. EARTHING BUSBAR 4. CONTROL CIRCUIT WIRING 5. PHASE / POLARITY ARRANGEMENT AND COLOUR CODING 6. WITHDRAWABLE EQUIPMENT 7. WITHDRAWABLE EQUIPMENT POSITIONS 8. SAFETY INTERLOCKS 9. PAINTING AND COLOUR 0. NAMEPLAT. SURGE (SWITCHING) PROTEIVE DEVIC ACCSORI. STANDARD ACCSORI 2. OPTIONAL ACCSORI 3. EARTHING DEVIC 4. GAS EXHAUST DU 5. GAS SCREEN 2 OPTIONS 24 SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 2

3 FEATUR 2 APPLICATIONS HIGH RELIABILITY Type testing of the MS-E was performed by an independent external testing and certification authority, KEMA, in the Netherlands. MS-E is designed with the benefit of Mitsubishi s vast medium voltage panels production experience of hundreds of thousands of panels over the last almost 60 years. All components, such as current transformers, voltage transformers and multi-function relays are made of the highest quality materials. Heat stress analysis of the switchgear structure has led to a heat-resistant design in which circuit breakers up to A are self-cooled (i.e. cooling fans not required). The reduced number of parts reduces the chance of failure. Mitsubishi MS-E provide control and protection of the power supply to motors, transformers, capacitors and other feeder circuits. The MS-E is available at rated voltages of to 5 kv, with rated short-circuit breaking capacities from to ka. MS-E is designed for indoor use and is particularly suitable for electric power plants, substations, industrial plants, commercial buildings, pumping stations, pipeline stations and transportation systems. SAFETY Partitions between compartments and an automatic shutter system (for withdrawable equipment primary junctions) completely isolate live parts. Safe operation and maintenance is ensured with the adoption of comprehensive interlocking mechanisms. In the event of an internal arc fault, the MS-E is designed to withstand the huge pressure and burning effect of the arc. (Relief flaps located on top of the panel open to limit pressure.) Withdrawable equipments are inserted / withdrawn whilst the front panel door is closed so that any arc proof rating is not compromised (in line with IEC requirements). Multiple protection relay Control (low voltage) compartment EASY INSTALLATION Installation and testing duration are considerably reduced as the panel is tested and adjusted in the factory and then delivered as a complete unit. FLEXIBLE DIGN Panels with main circuit and control cable entry from either the top or bottom are available. PROTEION Mitsubishi MP or EMC Multiple Protection relays are installed as standard. The MP or EMC relay provides protection, measurement, communications and control functionality. Withdrawable vacuum circuit breaker Withdrawable fused vacuum contactor Reinforced inspection windows Self-cooled horizontal busbars Cable compartment Figure 2- MS-E panel Figure - MP Multiple Protection relay Figure -2 EMC Multiple Protection relay 3 SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 4

4 3. SWITCHGEAR AND CONTROLGEAR Ratings Type designation Applied standard Rated voltage 2 Rated frequency Rated insulation level 4 Short-duration power frequency withstand voltage, min. Lightning impulse withstand voltage Rated normal main busbar current Rated short-time withstand current, symmetrical [ka, rms] Rated peak withstand current [ka, peak] Rated duration of short-circuit [sec] Loss of Service Continuity category Internal Arc Classification 6 Accessibility type Arc test current Arc test current duration Location Ambient temperature Altitude a.s.l. Humidity R.H. Water vapour pressure Earthquake protection 7 Horizontal seismic withstand 8 Vertical seismic withstand [kv, rms] [Hz] [kv, rms] [kv, peak] [A, rms] [ka] [sec] [ C] [m] [%] [kpa] [m/s 2 ] [m/s 2 ] U r f r U d U p I r I k I p t k IAC MS-E IEC , ,,, 5,, 50 Hz: 2.5 I k, 60 Hz: 2.6 I k, 3 LSC2B-PM AFL, AFLR,, 0., 0.5, Indoor -5 ~ 000 max. 95 max. 2.2 average VACUUM CIRCUIT BREAKER Manufacturer Type designation Applied standard Rated voltage Rated frequency Rated normal current (self-cooling) Rated insulation level Short-duration power frequency withstand voltage, min. Lightning impulse withstand voltage Rated short-time withstand current Rated peak withstand current Rated duration of short-circuit Rated cable-charging breaking current Rated short-circuit breaking current Transient Recovery Voltage (TRV) Reference voltage Rate of Rise of Recovery Voltage (RRRV) Rated break time Rated short-circuit making current Rated control voltage Rated operating sequence Closing operation Motor current (at 0 V DC) Spring charging time Closing control current (at 0 V DC) Tripping control current (at 0 V DC) Auxiliary switch (contacts) Weight [kv, rms] [Hz] [A] [kv, rms] [kv, peak] [ka, rms] [ka, rms] [sec] [A, rms] [ka, rms] [kv] [kv/µs] [cycles] [ka, peak] [V DC] [A] [sec] [A] [A] [kg] U r f r I r U d U p I k I p t k I c I sc U a M Mitsubishi Electric 6/0-VPR-MMC IEC , 60,,, ,, 3 0,,, 3 63, 78.8, 00 48, 0, 220 O 3 min CO 3 min CO O 0.3 sec CO 3 min CO CO 5 sec CO (peak 6 A) Approx. 6 (after closing) a, 5b, A: A: 60 A: Hz: 2.5 I k, 60 Hz: 2.6 I k u c u c /t Type test 9 Withdrawable equipment 0 position Withdrawal / insertion method Maintenance access. High-voltage switchgear and controlgear-part : AC metal-enclosed switchgear and controlgear for rated voltages above kv and up to and including 52 kv kv and 5 kv apply to switchgear. 3. North American rating (range I, series II in IEC) kv rms ( kv peak) and 36 kv rms (95 kv peak) apply to switchgear. 5. A apply to kv and 2 kv switchgear. 6. Optional 7. General use, class B on the upper floor or roof of building according to JEM-TR Static acceleration of horizontal is 3.92 m/s 2 at base of structure. 9. Internal arc fault test. 0. Circuit breaker or Fused contactor or Voltage transformer. KEMA (Netherlands) Mid-mount External operation (with door closed) Front & rear, Front. Rated short-circuit breaking current ka 2 5 ka 3 2 ka North American rating (range I, series II in IEC). 3. A apply to kv and 2 kv switchgear. Figure 3- Withdrawable vacuum circuit breaker 5 SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 6

5 3. FUSED VACUUM CONTAOR Manufacturer Type designation Mitsubishi Electric MMFKVN 4 Applied standard Rated voltage Rated insulating voltage Rated frequency Rated operational current (self-cooling) Rated insulation level Short-duration power frequency withstand voltage, min. Lightning impulse withstand voltage Rated short-circuit breaking current [kv, rms] [kv, rms] [Hz] [A] [kv, rms] [kv, peak] [ka, rms] U r f r I e U d U p I sc IEC , 60, (Power fuse) The all-metal enclosure is completely earthed. Each compartment (control, withdrawable equipment, busbar and cable) is segregated from other compartments by earthed metal partitions. The front of the MS-E is divided into three kinds of compartments. The upper compartment is the control compartment, and the middle one is the withdrawable equipment compartment. The bottom-most compartment can be used for maintenance access. (See Figure 4-.) The multi-function relay (or meters, protective relays, control switches, etc.) is semi-flush mounted on the door of the control compartment. Rated control voltage [V AC/DC] U a 00, 0,, 220 Closing control current (at 00 V DC) [A] 4.8 Tripping control current (at 00 V DC) [A] 3.5 (Mechanical latch type) Auxiliary switch (contacts) 2a, 2b Operation system Electrical hold type, Mechanical latch type Weight [kg] M A: 90 0 A: 90 (for 3.3 kv) 00 (for 6.6 kv). Power fuse rating 20 A /x 50 A /b 00 A z/ 50 A zb A x/ A c/ 0 A v/ Contactor rating A w 0 A r Gas exhaust duct or gas screen (optional) Ventilator 2 Control compartment Withdrawable equipment compartment Busbar compartment Cable compartment Circuit breaker Earthing switch (optional) 3 Power cable Figure 4- Front compartments of MS-E (switchgear) Figure 3-2 Withdrawable fused vacuum contactor. Gas exhaust duct or gas screen required when Internal Arc Classification selected. Refer to p. 23 for more detail. 2. When the current within a compartment is A or greater, a ventilator is required for that compartment. However, not required if gas exhaust duct used. 3. Earthing truck is applied for 5 kv switchgear with I k > ka Load capacity selection table The main busbar is made of copper conductor. Voltage Unit type Motor Transformer Capacitor 2 (kw) (kva) (kvar) Voltage Unit type 3.3 kv 02F2VN 05F2VN 0F2VN 5F2VN 20F2VN 30F4VN F4VN kv 02F2VN 05F2VN 0F2VN 5F2VN 20F2VN 30F4VN F4VN 2. A series reactor must be provided. Motor (kw) Transformer Capacitor 2 (kva) (kvar) MS-E has bare busbars as standard. However, when required, the busbar can be insulated. Also, the main bus joints, such as the busbar joints between adjacent panels, can be shrouded with insulating covers. Other joints, such as those at the cable terminals, are covered with insulating tape. Connecting bars, such as those between busbars and circuit breaker bushings, or circuit breaker bushings and cable terminals, may also be optionally insulated. Figure 4-2 Main busbars (air-insulated) with tin plating 7 SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 8

6 3. VACUUM CIRCUIT BREAKER () The is easy to operate, with the closing spring charge indicator, the manual close and trip buttons, the operation counter and mechanical ON / OFF indicator all being located on the front of the circuit breaker. (See Figure 4-3.) The circuit breaker has two positions, Service and Test/Disconnected, and may be optionally padlocked at each position. When the is closed, the locks in each position by mechanical interlock. When the is opened, the interlock pin is released. The circuit breaker can be easily drawn out or inserted by a simple rotation action. (See Figure 4-3.) This is accomplished with the circuit breaker compartment door closed. Unauthorised racking can be prevented by padlocking the shutter for the draw-out handle aperture. The control circuit terminal of the circuit breaker is of manual connection type. The connector (see Figure 4-3) can be only attached when the is in the Test/ Disconnected position, and has the following mechanical interlocks. The circuit breaker cannot be inserted to the Service position when the control circuit terminals are not connected. The control circuit terminals cannot be disconnected when the circuit breaker is in the Service position. Circuit breakers of different ratings other than specified are mechanically prevented from being inserted into the Service position. 4. FUSED VACUUM CONTAOR The fused vacuum contactor is easy to operate, with the manual trip button for mechanical latch type, the operation counter and mechanical ON / OFF indicator all being located on the front of the fused contactor. (See Figure 4-4.) The fused contactor has two positions, Service and Test/Disconnected, and may be optionally padlocked at each position. When the contactor is closed, the fused contactor locks in each position by mechanical interlock. When the contactor is opened, the interlock is released. The fused contactor can be easily drawn out or inserted by a simple rotation action. (See Figure 4-4.) This is accomplished with the fused contactor compartment door closed. Unauthorised racking can be prevented by padlocking the shutter for the draw-out handle aperture. The control circuit terminal of the fused contactor is of manual connection type. The connector (see Figure 4-4) can be only attached when the fused contactor is in the Test/ Disconnected position, and has the following mechanical interlocks. The fused vacuum contactor cannot be inserted to the Service position when the control circuit terminals are not connected. The control circuit terminals cannot be disconnected when the fused vacuum contactor is in the Service position. Contactor of different ratings other than specified can be (optionally) mechanically prevented from being inserted into the Service position. Rating nameplate Rating nameplate Manual closing spring charging handle aperture Manual close button Operation counter Closing spring charge indicator Manual trip button for mechanical latch type Manual trip button Control circuit plug-in terminal Operation counter ON / OFF indicator ON / OFF indicator Racking truck Control circuit plug-in terminal Wheels Wheels Racking truck Power fuse Racking Auxiliary VT (optional) Vacuum Magnetic Contactor (VMC) Racking Front face-plate Figure 4-3 Vacuum circuit breaker details Figure 4-4 Fused vacuum contactor details 9 SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 0

7 5. AUTOMATIC SHUTTERS 6. CABLE COMPARTMENT / CURRENT TRANSFORMERS Inserting the withdrawable equipment into the Service position causes the shutters to automatically open. Drawing the withdrawable equipment out to the Test/Disconnected position causes the shutters to move and cover the primary junction contacts. Moulded-type current transformers are installed in the cable compartment. Figure 4-5 Shutters open Figure 4-6 Shutters closed Figure 4-9 Current transformers installed in cable compartment As shown below, the shutters operate on the busbar and cable sides. The shutters for the upper and lower primary junctions can be closed and opened individually, and can be (optionally) padlocked in the closed position. 7. WIRING Necessary control equipment such as auxiliary relays, terminal blocks and fuses are located in the control compartment. Ducting and bundling ensure that control wiring is systematic and neat. External control cable can be terminated to both sides of the compartment. Wiring to devices mounted on the door are protected from damage during opening or closing by vinyl tubing. Figure 4-7 Individual shutter operation Figure 4-0 Control compartment 8. EARTHING BUSBAR Figure 4-8 Optional padlocking of top and bottom shutters The earthing busbar is made of copper conductor. The shutters are made of metal and the following labels can be (optionally) provided. BUSBAR on shutter for busbar (line) side. CABLE on shutter for cable (load) side. The shutters can be (optionally) provided with a manually operated device to keep it in the opening position. The function of the device is cancelled by insertion of withdrawable equipment. MS-E has no plating earthing busbar as standard. However, when required, the earthing busbar can be optionally tin-plated. An earthing busbar is installed along the full length of the switchgear structure, with provision for earth cable connection at each end. The earthing busbar can be easily accessed from the front by removing the cover within the cable compartment. Figure 4- Earthing busbar (tin-plated) viewed from rear of panel SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 2

8 5 () / 2 / 5 kv, ~ ka MITSUBISHI MS-E SWITCHGEAR 3. EXAMPLE A. SINGLE-LINE DIAGRAM B. PANEL LAYOUT PF VMC Z : E. BUS: : LA: M: CR: : VT: Z: TR: VMC: PF: TR 3VT TR TR M M M M M M PF VMC PF VMC PF VMC Current Transformer Earthing Busbar Earthing Switch Lightning Arrester Motor CR suppressor Vacuum Circuit Breaker Voltage Transformer Zero-phase sequence Current Transformer Transformer Vacuum Magnetic Contactor Power Fuse CR LA 3VT TR Z Z Z Z Z Z Z LA 3VT CR Z E. BUS Z M M M Z Z TR 3VT LA 3VT 3VT 3VT CR 3VT LA Z PF VMC CR Z PF VMC PF PF VMC VMC Z TR M M M Z SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 4 Panel type Incomer Incomer + VT (fixed type) 2 2 Section view VT. Gas exhaust duct or gas screen (shown dashed) is required when Internal Arc Classification (IAC) be selected. 2. Arc proof ventilator (shown dashed) is required when AFLR of IAC be selected. 3. Depth given in parentheses applies when AFLR of IAC be selected. And if more than 2 cables / phase required, or is non-standard, then the depth will increase. 4. Height given in parentheses applies when IAC be selected. 0 S 0 S Rated voltage (kv) Shortcircuit current (ka) Rated current (A) Busbar Dimensions (mm) Width Depth 3 (D) Height 4 (H) Weight (t) Heat loss (2850) 2 (2850)

9 Panel type Section view Rated voltage (kv) Shortcircuit current (ka) Rated current (A) Busbar Dimensions (mm) Width Depth 3 (D) Height 4 (H) Weight (t) Heat loss Panel type Section view Rated voltage (kv) Shortcircuit current (ka) Rated current (A) or VT ratio Busbar / VT Dimensions (mm) Width Depth 2 (D) Height 3 (H) Weight (t) Heat loss Bus-tie Bus-tie + VT (fixed type) S 2 0 S (2 ) (2850) (2 ) 2 (2850) Outgoing feeder (transformer) Outgoing feeder (motor) VT (withdrawable) VT Z LA CR ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ 3 VT 6/0 V 3 EVT V 3 VT 000/0 V 3 EVT V 3 VT 3/0 V 3 EVT V 2 (2850) 2 (2850) 2 () (2850) VT Gas exhaust duct or gas screen (shown dashed) is required when Internal Arc Classification (IAC) be selected. Depth given in parentheses applies in case of incoming VT. And if is non-standard, then the depth will increase. Height given in parentheses applies when IAC be selected. Required only for dry-type transformers.. Gas exhaust duct or gas screen (shown dashed) is required when Internal Arc Classification (IAC) be selected. 2. Arc proof ventilator (shown dashed) is required when AFLR of IAC be selected. 3. Depth given in parentheses applies when AFLR of IAC be selected. And if more than 2 cables / phase required, or is non-standard, then the depth will increase. 4. Height given in parentheses applies when IAC be selected. 5 SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 6

10 (2) kv, ~ ka MITSUBISHI MS-E CONTROLGEAR 6 Panel type Section view Rated voltage (kv) Shortcircuit current (ka) Rated current (A) Busbar VMC 2 Dimensions (mm) Width Depth 3 (D) Height 4 (H) Weight (t) Heat loss Steel thickness is a minimum of mm ~ / 0 / Side cover (both ends of arrangement) : 2.0 mm Frame: 2.0 mm Door: 2.0 mm Outgoing feeder 2 VMC x VT Z 2 ~ ~ / 0 / 0 / 0 / 0 2 (2850) Ceiling plate: 2.0 mm Bottom plate: 2.0 mm Internal partitions: mm Mounting plates: 2.0 mm Standard front door / rear cover Position Structure Hinge location Handle location Handle lock. Gas exhaust duct or gas screen (shown dashed) is required when Internal Arc Classification (IAC) be selected. 2. Two VMCs are built in one panel. 3. If is non-standard, then the depth will increase. 4. Height given in parentheses applies when IAC be selected. Front Hinged doors ( 3) Left Right Optional Rear Bolted covers ( 2) () / 2 / 5 kv, ~ ka MITSUBISHI MS-E SWITCHGEAR Panel Hole for main circuit cable and earthing cable VT (withdrawable) Panel Front space Rear space Front space Rear space () 700 () () 700 () () Hole for control cable Hole for control cable (2) kv, ~ ka MITSUBISHI MS-E CONTROLGEAR Degree of protection Enclosure: IP3X Internal partitions: IP2X Conductor material: copper (JIS H3) Surface treatment: tin plating at busbar joints Auxiliary apparatus: high voltage insulated wire Conductor material: copper (JIS H3) Surface treatment: none (bare) Standard dimensions: 6 mm mm VMC 2 Panel Front space () Hole for control cable Rear space 700 () Hole for main circuit cable and earthing cable Wiring system: duct or bundled Insulation: V heat-resistant plastic (PVC) Size:. mm 2 Colour: yellow, except for earth wire (green) Wire numbering: indicated by "tube" ferrule Ring-type crimp lug (with insulated sleeve) Rear space given in parentheses applies when AFL of IAC be selected. 2. Two VMCs are built in one panel. Wire number Polarity indicated by colour (optional) The VT / test terminals and terminal blocks shown below are adopted as standard. VT secondary secondary 7 Test terminals Terminal block SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 8

11 5. PHASE / POLARITY ARRANGEMENT AND COLOUR CODING Main circuit and control circuit arrangements are as follows: AC st 2 nd 3 rd phase phase phase 8. SAFETY INTERLOCKS Action Interlock Conditions Rack withdrawable equipment Operate Earthing Switch Open withdrawable equipment door Close withdrawable equipment door / VMC state OFF Withdrawable Withdrawable Control circuit equipment position equipment door connector Disconnected 2 Disconnected Closed Attached 2 Earthing Switch OFF Cable door Closed (Viewed from front to back, top to bottom, or left to right from front.) DC st wire 2 nd wire Positive Negative Open cable door Disconnect control circuit Close / VMC Disconnected Service / Disconnected ON (Viewed from front to back, top to bottom, or left to right from front.) Main circuit colour identification is achieved with vinyl tape or coloured label at bus end where main cables are connected. AC Unless specially requested, the control circuit is not colour coded. (Identifying colour tube markers, with the standard colours shown below, can be optionally installed.) AC 3-phase AC -phase DC Apparatus Vacuum Circuit Breaker Fused Vacuum Contactor Voltage Transformer Neutral st 2 nd wire wire Neutral Positive Negative The withdrawable equipment has the following two positions: Service : Main and control circuit Connected Test/ Disconnected : Main circuit Disconnected Control circuit Connected (manual disconnection possible) The front door can be opened / closed when the withdrawable equipment is Test/Disconnected position. Red Yellow Blue Red Yellow Blue Black Red Blue Black Red Blue 6. WITHDRAWABLE EQUIPMENT Main circuit Automatic connection (self-aligning) Control circuit Manual connection 7. WITHDRAWABLE EQUIPMENT POSITIONS Earthing circuit (Carriage frame) Automatic connection (earthing shoe). 2. Figure 6- Earthing switch and cable compartment door interlock The earthing switch can be optionally provided. Excludes VT panel. External enclosure surfaces Surfaces are first cleaned and pretreated for rust. Two coats of paint are then applied: first, acrylic epoxy, and finally, melamine enamel. Internal enclosure surfaces As for external except only first coat of acrylic epoxy, or alkyd primer, applied. Finish colour Enclosure: Iight grey (Munsell No. 5Y 7/). Frame, meter covers, control devices and protection relay cases: manufacturer s standard. Nameplates are of plastic with black lettering on white background, fastened by plastic rivets, and are the following sizes: Panel arrangement name: 63 mm 35 mm Panel section name: 6 mm 50 mm Load Protection device for switching surge of Door interlock 9. PAINTING AND COLOUR 0. NAMEPLAT Rotary machine (electric motor & generator) CR Suppressor Figure 6-2 position-door interlock (derived from shutter mechanism). SURGE (SWITCHING) PROTEIVE DEVIC Dry-type transformer Lightning Arrester Oil-immersed transformer Not required Door interlock Racking interlock 9 SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 20

12 7 Optional earthing devices are available for safety during cable and busbar maintenance and/ or inspection. The following two types of earthing device Draw-out handle for withdrawable equipment can be provided upon request with the MS-E. Manual charging handle for closing spring Test Terminals test plug set for secondary circuit of VT & Lifter with bucket for withdrawable equipment Earthing truck for switchgear An earthing truck with fault-making capability which has the same operating mechanism as the circuit breaker. Figure 7-3 Earthing truck Integral earthing switch Lifter In the case of cable-side earthing, the earthing switch is integrated within the cable compartment. A mechanical interlock between the earthing switch and circuit breaker (or fused contactor) is provided. Draw-out handle Manual spring-charging handle Test plug set Lifter with bucket Figure 7- Standard accessories Bucket Bus-side earthing switches are usually integrated within a VT panel, and so employ electrical interlocking with the adjacent panel s circuit breaker. The mechanical indicator for the earthing switch s state can be checked from the front of the panel through a small, circular inspection window. Control circuit extension cable for withdrawn / VMC ON / OFF testing Earthing switch operating handle Load cable terminal Earthing switch Figure 7-4 Rear view of earthing switch Figure 7-5 Earthing switch operation Control circuit extension cable Operating handle Withdrawable equipment compartment door Figure 7-2 Optional accessory ON Earthing switch Cable compartment door OFF Mechanical interlock (door openable when E.S. ON) Front Figure 7-6 Section view of earthing switch 2 SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 22

13 4. GAS EXHAUST DU For switchgear and controlgear requiring optional Internal Arc Classification (IAC), the gas exhaust duct must be fitted onto the top of panel. The gas exhaust duct ensure that 8 in the event of an internal arc fault, any hot gases or vapours are channeled away from personnel in the vicinity of the panel. CLASSIFICATION ITEM STANDARD DIGN SPECIAL SPECIFICATIONS AND/OR OPTIONS The gas exhaust duct may extend to the open air. The straight and maximum two meters design, which is standard, is available. The part of extension duct to reach to the open air will be supplied by others. The design guideline for them will be shown for consumer convenience. The gas exhaust duct is dismantled from the panels prior to shipping, and are re-attached on site. With gas exhaust duct, the switchgear and controlgear are designed to protect persons in the event of an internal arc fault of up to ka. Thus, in the event of internal arcing, there is no ejection of parts, no expulsion of hot gases (except from the gas exhaust duct) and the enclosure remains earthed. Minimum clearances of mm, 00 mm and mm from the panel to the room s ceiling, side walls and back wall, respectively, are required. Enclosure Degree of protection Padlocking facility for withdrawable equipment Position Shutters Internal Arc Classification (IAC) Accessibility type Arc test current Arc test current duration Cable entry Power Control IP3X Bottom Bottom IP3 IP32 IP4X IP42 Available Available AFL, AFLR,, ka 0., 0.5, sec Top Top Classification IAC AFLR signifies that the switchgear and controlgear are designed for access from the Front, Lateral ends and Rear by Authorised personnel only. AFL signifies that the switchgear and controlgear are designed for access from the Front and Lateral ends by Authorised personnel only. 5. GAS SCREEN The gas screen can be selected instead of the gas exhaust duct on condition that Busbars Plating Insulation Short-time withstand current Earthing busbar Plating Size Tin Bare,, ka rms ( sec.) 6 mm Silver Epoxy coat PVC,, ka rms (3 sec.) Tin 6 32, 6 mm ceiling height from floor of electrical room is 40 mm or over. Busbar compartment segregation between panels No segregation With segregation Cable lugs Specify type, size Gas exhaust duct Gas screen Main circuit Cable glands Specify type, size Cable termination material Heat-shrinkable material (Specify size and type) Wire type V, PVC, C (HIV ) Wire size / VT secondary: 2.0 mm 2 other:. mm 2 Control circuit Colour Yellow Extension gas exhaust duct Terminals Up to 5.5 mm 2 Terminal blocks Screw type (MITSUBISHI: Type TJX) (e.g. clip-on) Front Front. Tinned copper, heat resistant (JIS C 336) 23 Figure 7-7 Panel section with gas exhaust duct Figure 7-8 Panel section with gas screen SWITCHGEAR AND CONTROLGEAR SWITCHGEAR AND CONTROLGEAR 24

14 CLASSIFICATION ITEM STANDARD DIGN SPECIAL SPECIFICATIONS AND/OR OPTIONS Space heater power source Thermostat power source (for space heater) Interior lighting operated by Available door position switch Transparent plastic covers Available (behind door) (prevention of accidental contact with live parts) Equipment Integral earthing switch Available Earthing truck Available VT Fixed type (floor-mount) Withdrawable (mid-mount) Automatic Transfer System Slow speed (ATS) High speed Foundation bolts Available Channel base Available Secondary rating 5 A A Accuracy Measuring Protection for switchgear Class 0P20 Protection for controlgear 5P0 Burden Min. 5 VA Material Acrylic plastic Laminated plastic Nameplates Stainless steel Language English Measurement and Relay MITSUBISHI MP or EMC instruments and Protection Multiple Protection Relay protection relays SWITCHGEAR AND CONTROLGEAR

15 HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO , JAPAN Safety Precautions Please read the instruction manual before using the device. G-99-7-C7685-B HQ 0803 Printed in Japan (MDOC) Revised publication effective Apr. 8. Superseding publication of Mar. 7. Specifications subject to change without notice.

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4 CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,

More information

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant

More information

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132

More information

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is

More information

e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN

e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services

More information

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125

Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125 Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated

More information

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. 2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to

More information

Unified requirements for systems with voltages above 1 kv up to 15 kv

Unified requirements for systems with voltages above 1 kv up to 15 kv (1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to

More information

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast. METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component

More information

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility

More information

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,

More information

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw 4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and

More information

Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV

Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV Installation, Operation and Maintenance Instructions Uniflex ABB PTMV SAFETY FIRST! For safe and correct usage note the following recommendations: Only install switchgear and switchboards in enclosed rooms

More information

The Intelligent AX1 Switchgear for Medium Voltage

The Intelligent AX1 Switchgear for Medium Voltage The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched

More information

Sample - No Commercial Use

Sample - No Commercial Use COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort

More information

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:

More information

FAQs-Main switchboard design criteria

FAQs-Main switchboard design criteria FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard

More information

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact

More information

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general

More information

MEDIUM VOLTAGE SWITCHGEAR CATALOGUE. Code: P2490_xx

MEDIUM VOLTAGE SWITCHGEAR CATALOGUE. Code: P2490_xx MEDIUM VOLTAGE SWITCHGEAR for secondary distribution CATALOGUE Code: P2490_xx CONTENTS 1 About us 2 Medium Voltage Business Unit Portfolio 3 Overview 8 Medium Voltage Switchgear Types. Equipment used.

More information

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Submit shop drawings for equipment provided under this section Shop drawings shall indicate: Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,

More information

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Masterclad Medium Voltage Passive Arc-Resistant Switchgear Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand

More information

Secondary Unit Substations

Secondary Unit Substations 14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically

More information

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com

More information

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element

More information

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units

7.2KV SL400 Withdrawable Vacuum Contactor-Fuse Combination Units Automotive Powering business worldwide Aerospace Eaton delivers the hundreds of power distribution products that are answering the demands of today s fast changing world. We help our customers worldwide

More information

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2

More information

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,

More information

Low Voltage Switchboards The Best Technical Solution for Your Ship

Low Voltage Switchboards The Best Technical Solution for Your Ship The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.

More information

HMS Air-Insulated Medium-Voltage Metal-Clad Switchgear. Internal Arc Proof

HMS Air-Insulated Medium-Voltage Metal-Clad Switchgear. Internal Arc Proof HMS Air-Insulated Medium-Voltage Metal-Clad Switchgear Internal Arc Proof HMS Air-Insulated Medium-Voltage Metal-Clad Switchgear [ Internal Arc Proof ] CONTENTS 04 06 10 15 General Construction Dimensions

More information

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision

More information

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

SF 6 Gas Insulated Switchgear Type SDF for 170 kv Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment

More information

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will

More information

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Bryan Johnson Product Group Manager, MV Switchgear ABB South Africa Contents Introduction... 3 What is an internal arc

More information

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application. Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Comparative study for cables and busbars

Comparative study for cables and busbars Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary

More information

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and

More information

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY

More information

Switchboard system. NorLine 800

Switchboard system. NorLine 800 Switchboard system NorLine 800 NorLine 800 SWITCHBOARD SYSTEM 2 NorLine 800 Switchboard system Table of contents Subject Page Table of contents 2 Overview 2-3 NorLine 800 technical specifications 4 Structural

More information

Medium Voltage Switchgear

Medium Voltage Switchgear Uniswitch Medium Voltage Switchgear 12 kv, 17.5 kv, 24 kv 630 A and 1250 A Operation and TABLE OF CONTENTS 1 Summary...1 1.1 General...1 1.2 Standards and specifications...2 1.3 Service conditions...3

More information

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR Copyright Material IEEE Paper No. PCIC 2003-13 Eddie Wilkie Eaton Cutler-Hammer 3990 Old Tasso Road NE Cleveland, TN 37312 USA Abstract

More information

How To Build A Germany Power Plant

How To Build A Germany Power Plant Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)

More information

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric

More information

IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES xl 3 configurable assemblies IEC 60439 >>> IEC 61439 GUIDE GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES XL 3 configurable assemblies guide to migration from IEC 60439 to IEC 61439

More information

Quick Connect. quick - simple - efficient. www.g-mw.de

Quick Connect. quick - simple - efficient. www.g-mw.de Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power

More information

GE Power Controls. MiniFORM Switchboards

GE Power Controls. MiniFORM Switchboards GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules

More information

MNS is Switchgear System Technical Overview

MNS is Switchgear System Technical Overview Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known

More information

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers

More information

Engineering Specification

Engineering Specification Engineering Specification Electrical 33KV AC INDOOR SWITCHGEAR NON-WITHDRAWABLE Owner: Approved by: Chief Engineer, Electrical Neal Hook Chief Engineer Electrical Authorised by: Version 2.1 Issued May

More information

The following components are common to most cubicles; this example is an ABB HK cubicle.

The following components are common to most cubicles; this example is an ABB HK cubicle. 4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.

More information

ADM1TE 5/30A DIN rail single phase two wire energy meter

ADM1TE 5/30A DIN rail single phase two wire energy meter ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.

More information

Switchgear and Metal-Enclosed Bus

Switchgear and Metal-Enclosed Bus Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found

More information

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility

More information

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading

More information

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear

Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic

More information

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils

More information

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT User Manual SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium +32 (0)9/321.91.12 - Fax +32 (0)9/321.91.13 - e-mail: info@switchgearcompany.eu

More information

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED

More information

UFES Active protection for switchgear

UFES Active protection for switchgear Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document

More information

Securing your electrical installations Prisma,

Securing your electrical installations Prisma, Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards

More information

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE

More information

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for.

SIRCOVER. Manual changeover switches from 125 to 3200 A. Changeover switches. Function. Advantages. The solution for. The solution for Changeover switches svr_099_b_1_cat > Manufacturing industry. > Power distribution. 3200 Strong points svr_059_a_1_cat > complete range. > Easy connections. > Stable positions. > mproved

More information

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s

More information

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy. s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage

More information

NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD

NDQ5 Series. Automatic Transfer Switch. Shanghai Liangxin Electrical CO.,LTD Shanghai Liangxin Electrical CO.,LTD Address: No. 668 Heng An Road, Pu Dong New District, Shanghai Zip: 200137 Tel: 86-21-5012789 Fax: 86-21-58675966 E-mail: client@sh-liangxin.com LINE 1 LINE 3 LINE 5

More information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information

Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC

More information

SIVACON The Versatile Low-Voltage Switchboard

SIVACON The Versatile Low-Voltage Switchboard s SIVACON The Versatile Low-Voltage Switchboard Type-Tested Power Distribution Board 8PT The Obvious Solution for Global Challenges SIVACON Type testing in low-voltage switchgear is increasingly becoming

More information

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Electrical Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv Table of Contents 1. Introduction...2 1.1 Purpose... 2 1.2 Scope... 2 2. References...2 2.1... 2 2.2 Industry

More information

SENTRON Switching and Protection Devices Air Circuit Breakers

SENTRON Switching and Protection Devices Air Circuit Breakers Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General

More information

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2... Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast

More information

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in

Cross-beam scanning system to detect slim objects. 100 mm 3.937 in 891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC

More information

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay

More information

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR

SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed

More information

Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's

Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's Metal Enclosed Switchgears Metal Clad Switchgears Gas Insulated RMU's Catalogue 2011 Aktif trade mark for Medium voltage switchgears, Switching equipment and Kiosks with high quality and environmentally

More information

CAS 36 Ring Main Unit

CAS 36 Ring Main Unit Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly

More information

Power Management Module 2. Installation

Power Management Module 2. Installation Power Management Module 2 30 300 kva Installation Table of Contents Safety... 1 Safety Instructions... 1 Certification Standards Three Phase... 1 Product Safety... 2 Special Precautions... 2 System Description...

More information

This section applies to the design and installation of transformers.

This section applies to the design and installation of transformers. ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies

More information

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

Adjustment functions for both span and shift have been incorporated

Adjustment functions for both span and shift have been incorporated SENSORS FOR SERIES LED Type Wafer Alignment Sensor FX-0-F FT-F9 FD-F7 EX-F70/F60 M SH-7 FD-L4 M-DW The use of a safe LED light beam now allows for high precision detection with a resolution of 0!m (.8

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear Class 6055 Instruction Bulletin 6055-62 06/2012 Retain for future use. Hazard Categories and Special Symbols Read these instructions carefully

More information

Fusible Disconnect Switch

Fusible Disconnect Switch Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order

More information

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

DRM75A 230V 20/100A DIN rail single phase two wire energy meter DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002 NEW GAS INSULATED SWITCHGEAR (GIS) FOR ALL MEDIUM VOLTAGE APPLICATIONS H. Fink, ABB Calor Emag Mittelspannungs GmbH; M. Hyrenbach, ABB Calor

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

R.C.C.B. s two-pole LEXIC

R.C.C.B. s two-pole LEXIC 87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...

More information

INDOOR MEDIUM VOLTAGE SWITCHGEAR - UP TO 24kV. A division of ACTOM Pty Ltd

INDOOR MEDIUM VOLTAGE SWITCHGEAR - UP TO 24kV. A division of ACTOM Pty Ltd INDOOR MEDIUM VOLTAGE SWITCHGEAR - UP TO 24kV A division of ACTOM Pty Ltd ACTOM Indoor Medium Voltage Switchgear SBV range of products Prior to 1980, ACTOM s indoor vacuum arc switching is the switchgear

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

MCC Ratings. Voltage Rating

MCC Ratings. Voltage Rating MCC Ratings In addition to the various ratings of individual components used in motor control centers, the overall ratings of the motor control center must also be considered. Voltage Rating Motor control

More information

A. Shop Drawing submittals shall include, but not be limited to, the following:

A. Shop Drawing submittals shall include, but not be limited to, the following: SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical

More information

Series 8146/5-V37 and Series 8150/5-V37

Series 8146/5-V37 and Series 8150/5-V37 www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection

More information

italtec PRINTED CIRCUITS EQUIPMENT PRINTED CIRCUITS EQUIPMENT Insulator machines Echting machines Special equipment and machines

italtec PRINTED CIRCUITS EQUIPMENT PRINTED CIRCUITS EQUIPMENT Insulator machines Echting machines Special equipment and machines PRINTED CIRCUITS EQUIPMENT PRINTED CIRCUITS EQUIPMENT Insulator machines Echting machines Special equipment and machines On customer request it is possible to supply: Benches for PCB Oven for PCB Chemicals

More information