Andre Gretler, LPLS BU Function Operation and Sales Low Voltage Systems ANSI vs IEC. BU 3101 Low Voltage Systems June 27, 2013 Slide 1



Similar documents
FAQs-Main switchboard design criteria

NEMA Enclosure Types

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Unified requirements for systems with voltages above 1 kv up to 15 kv

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU

The Intelligent AX1 Switchgear for Medium Voltage

MCC Ratings. Voltage Rating

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Switchgear and Metal-Enclosed Bus

New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac

Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon

SAFETY ALERT SWITCHBOARD INTERNAL SEGREGATION AND IP RATING. May 2014 BACKGROUND

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Sample - No Commercial Use

Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c Erlangen Germany.

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

Degrees of protection. IP codes. W.M.M. Menheere Holec Holland N.V. The Netherlands

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

Application Guide Selection of Type Enclosures

IR WINDOW CERTIFICATION GUIDEBOOK. Copyright CorDEX Instruments Ltd. ex.com. ID 4016 Rev A

Secondary Unit Substations

SIVACON The Versatile Low-Voltage Switchboard

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Extend the Life of Existing Switchgear

Securing your electrical installations Prisma,

BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E

Basics of Explosion Protection

ARC FLASH CALCULATIONS & LABELING REQUIREMENTS

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

MNS is Switchgear System Technical Overview

Technical Guide. SKM Arc Flash Line Side vs. Load Side

Atlanta Chapter IEEE Industry Applications Society

IP Rating Chart. 910 East Orangefair Lane Anaheim, CA USA , Fax

Technical Application Papers No.11 Guidelines to the construction of a low-voltage assembly complying with the Standards IEC Part 1 and Part 2

Primary and Secondary Electrical Distribution Systems

Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection

Fusible Disconnect Switch

The following components are common to most cubicles; this example is an ABB HK cubicle.

HIGH VOLTAGE SHORE CONNECTION

Arc Terminator Active Arc-Resistant Switchgear

The easy way to build switchgear and controlgear assemblies in compliance with the regulations

DF-DT (G) MEDIUM VOLTAGE SWITCHGEAR THE MODULAR CONCEPT. User Manual. SGC - SwitchGear Company nv - Moorstraat 24 - B-9850 Nevele - Belgium

Tables Technical data Standards Explanations Increased safety e

Understanding the Standards Surrounding Arc Flash Hazards and Arc Resistant Equipment

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

Application of Four-Pole Circuit Breakers within Data Centers

How to reduce exposure to arc flash hazards

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Automation & Power World Improving safety Through arc resistant switchgear and arc reducing components. ABB Wednesday, 23 March 2011 Slide 1

What are the basic electrical safety issues and remedies in solar photovoltaic installations?

METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.

Part 1 System Modeling & Studies for Existing Systems

Design of a New Generation of Internal Arc Resistant Switchgear

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

White Paper IK code: Impact protection in line with the IEC standard. By Sven Schnautz

UL Validated Testing of Arc-Resistant Motor Control Centers

ADS8 IP54 Direct-On-Line Starter Technical Focus. Replaces ADS7 Rated up to 9kW

Advantages of Fixed Circuit Breaker Switchgear

IEC & 2 standard. The reference for safe and reliable LV switchboards

HAZARDOUS AREA TECHNICAL GUIDE

Low Voltage Switchboards The Best Technical Solution for Your Ship

Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation

Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV

Safety By Design. Strategies for Electrical Contractors

Eaton Electrical Inc Cherrington Parkway Moon Township, PA United States tel:

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

2008 Eaton Corporation. All rights reserved.

MNS Low Voltage Switchgear System Guide

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Table of Contents. Review Answers...77 Final Exam...80

IEC specifications for LV assembly switchboards

Comparative study for cables and busbars

Choosing the Best Solution for Reducing Arc Energy

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Changing industry standards: friend or foe?

Automation Products. Low Voltage Switchgear MNS System Overview

Product Safety Considerations for Insulation Coordination of Low- Voltage Equipment. Scott Aldous, Compliance Engineer

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

Integrating SPDs in Switchgear & Switchboards Causes More Problems than it Solves

Modular Systems wind portfolio overview Power Collection and Grid Connection products

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Siemens tiastar TM Motor Control Center (MCC) Siemens All rights reserved.

Application Guide. MNS-SG Low Voltage, Metal-Enclosed, Drawout Switchgear

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

This section applies to the design and installation of transformers.

Evaluating Water-Damaged Electrical Equipment

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

Calculating Creepage and Clearance Early Avoids Design Problems Later Homi Ahmadi

Transcription:

Andre Gretler, LPLS BU Function Operation and Sales Low Voltage Systems ANSI vs IEC June 27, 2013 Slide 1

Business card André Gretler BU Function Operation and Sales Business Unit Low Voltage Systems ABB Switzerland Ltd. Low Voltage Power Fabrikstrasse 9 5600 Lenzburg, Switzerland Phone: +41 58 588 4201 Telefax: +41 58 588 4228 Mobile: +41 79 372 30 32 E-Mail: andre.gretler@ch.abb.com June 27, 2013 Slide 2

AGENDA 1. ANSI/UL vs. IEC Basics 2. ANSI/IEC in detail Spotlight s 3. Price comparison 4. Summary June 27, 2013 Slide 3

ANSI vs. IEC June 27, 2013 Slide 4

Why do we need standards? What the customer needed What was specified in the inquiry What the supplier quoted What was delivered What was installed What was commissioned June 27, 2013 Slide 5

ANSI vs. IEC Standards introduction IEC = International Electrotechnical Commission Founded in 1904 in St. Louis, MO Recognized by the World Trade Organization Consists of over 50 National Committees, each having equal voting rights Represents 85 % of the world s population and 95 % of the electric energy produced and consumed June 27, 2013 Slide 6

ANSI vs. IEC Standards applicable standards IEC 60439-1 IEC 61439 IEC 61641 IEC 60947-2 IEC 60947-4-1 IEC 60529 Low-voltage switchgear and controlgear assemblies Part 1: Typetested and partially typetested assemblies Low-voltage switchgear and controlgear assemblies Part 1: General rules Part 2: Power Switchgear and Controlgear assemblies Enclosed low-voltage switchgear and controlgear assemblies Guide for testing under conditions of arcing due to internal fault Low-voltage switchgear and controlgear Part 2: Circuit-breakers Low-voltage switchgear and controlgear Part 4-1: (Electromechanical) Contactors and motor-starters Degrees of protection provided by enclosures (IP Code) Medium Voltage Switchgear June 27, 2013 Slide 7

ANSI vs. IEC Standards applicable standards UL845 Motor Control Centers UL891 Low-Voltage Switchboards UL1558 (based on ANSI C37.20.1) Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear ANSI C37.20.7 Guide for testing metal-enclosed switchgear rated up to 38 kv for internal arcing faults UL50E (based on NEMA 250) Enclosures for Electrical Equipment, Environmental Considerations June 27, 2013 Slide 8

New IEC 61439 series New Structure of IEC 61439 series Introduction Why do we need standards? The valid IEC 60439 New Structure of IEC 614319 series Fundamental changes Testing MNS Platform IEC 60439 and IEC 61439 Overlapping IEC 61439-1 IEC 61439-2 IEC 60439-1, 5 years overlapping with IEC 61439-1 and -2 5 years overlapping IEC 61439-x IEC 60439-x, 3 years overlapping with IEC 61439-x 3 years overlapping All mentioned dates are preliminary and may change! 2009 2010 2012 2014 June 27, 2013 Slide 9

New IEC 61439 series New Structure of IEC 61439 series Introduction Why do we need standards? The valid IEC 60439 New Structure of IEC 614319 series Fundamental changes Testing MNS Platform IEC 60439-1 will be withdrawn in January 2014 Until this time it is still possible to deliver LV switchgear and controlgear assemblies acc. IEC 60439-1 if it was specified accordingly The documentation acc. IEC 60439-1 is valid until the standard is withdrawn IEC 61439-1 and -2 was published in January 2009 From now on it is possible to deliver LV switchgear and controlgear assemblies acc. IEC 61439-2 if it was specified accordingly Where an Assembly has previously been tested in accordance with IEC 60439-1, and the test result fulfills the requirements of IEC 61439-2, the verification of these tests need not be repeated June 27, 2013 Slide 10

ANSI vs. IEC Standards low voltage switchgear IEC 61439 switchgear and controlgear UL 845 motor-control centers UL 891 switchboards UL 1558 switchgear is the base for all IEC low-voltage switchgear and controlgear including motor-control centers Generic IEC definiton: assemblies 3 standards are the base for ULswitchgear and - controlgear including motor-control centers June 27, 2013 Slide 11

Pictures of SWGR & MCC June 27, 2013 Slide 12

ANSI vs. IEC Standards low voltage switchgear Motor Control Center ANSI/UL: Different standards for Switchgear and Motor Control Centers IEC: No differentiation, one common standard Temperature ratings ANSI: Ambient temperature between -30 C and +40 C IEC: Maximum of +40 C (options for +50/55 C) and minimum of -5 C (options for -15/25 C) Installation ANSI: Indoor and outdoor IEC: Indoor only June 27, 2013 Slide 13

ANSI vs. IEC Standards low voltage switchgear Interlocking ANSI: Specific rules; key-interlocking preferred IEC: General rules, electro-mechanic interlocking preferred Enclosure ANSI: Differentiation between enclosure and vent openings, minimum thickness IEC: No differentiation and no specification Insulation ANSI: Primary bus and connections to be insulated IEC: Bus bar design left to the manufacturer June 27, 2013 Slide 14

ANSI vs. IEC Standards low voltage switchgear Instrument Transformers ANSI: Window-type current transformers on both sides of the circuit breaker IEC: Cast resin current transformers on line-side of the circuit breaker Option for non-traditional current and voltage sensors in IEC switchgear Low Voltage Compartment ANSI: Depending on specific designs, there may not be a LV compartment relays and control are mounted on the circuit breaker compartment door IEC: LV compartment with metallic separation from HV compartments for relays and control June 27, 2013 Slide 15

ANSI vs. IEC Standards low voltage switchgear IEC states mainly electrical parameters Material quality to be use for supporters Protection against electrical shock Over voltage categories... UL states mainly mechanical parameters Material thickness for enclosure Hinge location Cladding design... As a consequence UL products don t differ much in their design June 27, 2013 Slide 17

Internal Arc Test Definitions (IEC 61641) low voltage switchgear Internal Arc Test Equivalent in UL SWGR standards, it comes up with ANSI C37.20.7 and IEEE Arc ignited by short-circuit wire at unprotected side of a functional unit Incoming ACB mechanically blocked to prevent trip during arcing Test completed after 0.3 s Selectivity of incoming breakers Maximum arc burning time in LV switchgear Test completed after 0.5 s Selectivity of incoming breakers Maximum arc burning time in LV switchgear June 27, 2013 Slide 18

Certification of products low voltage switchgear Certification process of LV products is very different UL: The Underwriter Laboratories dominate the certification The Underwriter Laboratories define together with the manufacturer the test program of the product IEC: The manufacturers dominate the certification The manufacturer declare with the CE-mark on the product the standard-conformity which is legally binding UL type tests may be accepted in the IEC-market IEC type tests are not accepted by UL even though they are exactly the same The IEC-type test might be performed in laboratories owned by the manufacturer, in Asia and Far-East 3 rd -party tests are a must! June 27, 2013 Slide 19

ANSI vs. IEC Standards summary For Switchgear ANSI / UL and IEC have very different philosophies IEC Standards define requirements for performance ANSI Standards define fabrication techniques and material solutions Neither ANSI / UL nor IEC is better Note, however, that UL does not define arc-resistance Do not try to mix and match ANSI /UL and IEC standards June 27, 2013 Slide 20

AGENDA 1. ANSI/UL vs. IEC Basics 2. ANSI/IEC in detail Spotlight s 3. Price comparison 4. Summary June 27, 2013 Slide 21

ANSI / IEC in detail 2.1 Arc Resistance (IEC 61641) 2.2 Grounding Systems (IEC 61439) 2.3 IP vs. NEMA (IEC 60529) 2.4 Internal Segregation (IEC 61493) 2.5 Diversity Factors (IEC 61439) June 27, 2013 Slide 22

Internal arc safety (ANSI C37.20.7) (IEC 61641) Through years of Arc Resistant testing and continual R&D ABB has proven designs offering the highest level of safety in power distribution equipment! June 27, 2013 Slide 23

Evolution of ANSI Arc Resistant Standards EEMAC G14-1 was published in 1987 in Canada Type A arc-resistant construction at the front only Type B arc-resistant construction at the front, back, and sides Type C arc-resistant construction at the front, back, and sides, and between compartments IEEE C37.20.7-2007 includes Type 1 similar to EEMAC Type A above Type 2 similar to EEMAC Type B above Annex A addresses suffixes B and C Type 1C Type 1, but also with arc-resistance designs or features between adjacent compartments Type 2B Type 2 with LV instrument compartment door open relay and maintenance personnel survive Type 2C Type 2 with arc-resistance features between adjacent compartments switchgear survives with minimum damage Type 2BC The ultimate in protection combines types 2B and 2C June 27, 2013 Slide 24

Evolution of Arc Resistant Standards Testing is performed with covers and doors properly secured (Type 2C) Testing is performed with instrument door open (Type 2B) Therefore, arc resistance rating is based on door and covers being properly secured Testing is performed at the prescribed voltage and current levels Specified flammable cotton indicators are positioned to detect the escape of hazardous gases, plasma, etc. Pass/Fail Criteria Door, covers, etc. do not open. Bowing or other distortion is permitted except on those which are to be used to mount relays, meters, etc. That no parts are ejected into the vertical plane defined by the accessibility type There are no openings caused by direct contact with an arc That no indicators ignite as a result of escaping gases or particles That all grounding connections remain effective June 27, 2013 Slide 25

Internal arc safety (IEC 61641) After 0.3s the current will be turned off and the test is complete 0.3s arc burning time enables selectivity of incoming breakers 0.3s is the maximum arc burning time in low-voltage switchgears 5 criterias will be checked after the test, i.e. no doors, covers opened no parts, which may cause hazards, flew off no holes were burned in the enclosure the operator *) in front of the switchgear in a distance of 300mm will not be seriously harmed protection earth system is still effective June 27, 2013 Slide 26 *) the operator is simulated by a wall of cotton... The cotton quality is about 150g/m², which is 50% thinner than typical electrician clothes

Internal arc safety (IEC 61641)!! 8E/4 withdrawable unit with ignition-wire 1,5mm² at the supply side June 27, 2013 Slide 27

Internal arc safety (IEC 61641) Test arrangement, MNS with cotton indicators at critical places Horinzontal indicators are only required in medium voltage Vertical cotton indicators up to 2m height Cotton indicator Switchgear front June 27, 2013 Slide 28

ANSI / IEC in detail 2.1 Arc Resistands (IEC 61641) 2.2 Grounding Systems (IEC 61439) 2.3 IP vs. NEMA (IEC 60529) 2.4 Internal Segregation (IEC 61439) 2.5 Diversity Factors (IEC 61439) June 27, 2013 Slide 29

Grounding Systems (IEC 60439) (UL1558 UL845) All doors, plates and covers have to be grounded. It is possible to ground the door with the hinge only, when no device is mounted. (IEC & UL 845 only, not for UL1558) All doors have to be grounded by wire. IEC only if there is a device mounted When devices are door-mounted, the door shall be bonded to the main structure with a minimum No. 14 AWG conductor or equal. June 27, 2013 Slide 30

Grounding Systems (IEC 61364-1) 2.6.3 protective conductor (PE) conductor provided for purposes of safety, for example protection against electric shock Where items of equipment of the ASSEMBLY are designated, the designations used shall be identical with those in IEC 61364-1 June 27, 2013 Slide 31

Grounding Systems (IEC 61364-1) Solid grounding Solid grounding is the connection of a conductor, without any intentional impedance, from the neutral of a generator, power transformer, or grounding transformer directly to ground. Solid grounding is generally recommended for low-voltage systems when the automatic isolation of a faulted circuit can be tolerated or where it is not feasible to isolate a ground fault in a high-resistance grounded system. Systems used to supply phase-to-neutral loads must be solidly grounded as required by the National Electrical Code (NEC) NEC refers to IEC 61364-5-54. June 27, 2013 Slide 32

Grounding Systems (IEC 61364-1) June 27, 2013 Slide 33

Grounding Systems (IEC 61364-1) June 27, 2013 Slide 34

Grounding Systems (IEC 61364-1) June 27, 2013 Slide 35

Grounding Systems (IEC 61364-1) June 27, 2013 Slide 36

Grounding Systems (IEC 61364-1) Low-Resistance Grounding Mostly used in medium-voltage systems of 15 kv and below, especially where large rotating machinery is used. For large generators neutral resistor is usually selected to limit a minimum of 100 Amps up to a maximum of 1.5 times the normal rated generator current. The resistor ohmic value is selected to allow a ground-fault current acceptable for relaying. The grounding resistor can be rated for intermittent duty. In normal practice it is rated for 10 sec or 30 sec. June 27, 2013 Slide 37

Grounding Systems (IEC 61364-1) High-Resistance Grounding HRG June 27, 2013 Slide 38 AØ Source (Wye) N BØ CØ Common in ANSI for low voltage switchgear systems. Uses a neutral resistor or high ohmic value which is used to limit the current Ir, to a magnitude equal or slightly greater than the total capacitance charging current, 3 Ico. Normally ground-fault current is limited to 10A or less. When used in Ungrounded Systems Eliminates 100% of Transient overvoltages Ability to locate ground faults When used in Solidly-Grounded Systems Disruption to power continuity Eliminates 98% of Arc Flash / Blast Incidents Significantly reduces other 2%

ANSI / IEC in detail 2.1 Arc Resistance (IEC 61641) 2.2 Grounding Systems (IEC 61439) 2.3 IP vs. NEMA (IEC 60529) 2.4 Internal Segregation (IEC 61439) 2.5 Diversity Factors June 27, 2013 Slide 39

Degree of protection - Lettering code (IEC 60529) Code Letters International Protection IP 2 3 D First Numeral 0-6 Protection of Persons and resistance to Solid objects Second Numeral 0-8 Resistance to ingress of water Additional Letter (Optional) Enhanced personnel protection. June 27, 2013 Slide 40

Degree of protection - First numeral code (IEC 60529) Protection against ingress of solid foreign objects IP Example Requirements IP Example Requirements 0 No protection 4 Wire Max 1.0 mm 1 Back of hand Max 50 mm 5 Dust Limited dust 2 Finger Max 12.5 mm 6 Dust No dust 3 Tool Max 2.5 mm June 27, 2013 Slide 41

Degree of protection - Second numeral code (IEC 60529) Protection against harmful ingress of water IP Example Requirements IP Example Requirements 0 No protection 5 Jets 1 Vertically dripping 2 Dripping up to 15 6 Strong jets 3 Limited spraying 7 Temporary immersion (15 cm and 1 m) 4 Splashing 8 Immersion under pressure June 27, 2013 Slide 42

Degree of protection - Additional letter (IEC 60529) Additional Letter (Optional) IP Example Requirements A For use with first numeral 0 Back of hand Max 50 mm B For use with first numeral 0 & 1 Finger Max 12.5 mm x 80 mm C For use with first numerals 0, 1 & 2 Tool Max 2.5 mm x 100 mm long D For use with first numerals 0, 1, 2 & 3 Wire Max 1.0 mm x 100 mm June 27, 2013 Slide 43

NEMA Indoor nonhazardous Locations Table 2-1 [From NEMA 250-1997] Comparison of Specific Applications of Enclosures for Indoor Nonhazardous Locations Type of Enclosure Provides a Degree of Protection Against the Following Environmental Conditions Incidental contact with the enclosed equipment 1 2 4 4X 5 6 6P 12 12K 13 X X X X X X X X X X Falling dirt X X X X X X X X X X Falling liquids and light splashing - X X X X X X X X X Circulating dust, lint, fibers, and flyings ** Settling airborne dust, lint, fibers, and flyings ** - - X X - X X X X X - - X X X X X X X X Hosed down and splashing water - - X X - X X - - - Oil and coolant seepage - - - - - - - X X X Oil or coolant spraying and splashing - - - - - - - - - X Corrosive agents - - - X - - X - - - Occasional temporary submersion - - - - - X X - - - Occasional prolonged submersion - - - - - - X - - - * These enclosures may be ventilated. ** These fibers and flyings are nonhazardous materials and are not considered Class III type ignitable fibers or combustible flyings. For Class III type ignitable fibers or combustible flyings see the National Electrical Code, Article 500. June 27, 2013 Slide 44

NEMA Outdoor nonhazardous Locations Table 2-2 [From NEMA 250-1997] Comparison of Specific Applications of Enclosures for Outdoor Nonhazardous Locations Type of Enclosure Provides a Degree of Protection Against the Following Environmental Conditions 3 3R* 3S 4 4X 6 6P Incidental contact with the enclosed equipment X X X X X X X Rain, snow, and sleet ** X X X X X X X Sleet *** - - X - - - - Windblown dust, lint, fibers, and flyings X - X X X X X Hosed down - - - X X X X Corrosive agents - - - - X - X Occasional temporary submersion - - - - - X X Occasional prolonged submersion - - - - - - X * These enclosures may be ventilated. ** External operating mechanisms are not required to be operable when the enclosure is ice covered. *** External operating mechanisms are operable when the enclosure is ice covered. June 27, 2013 Slide 45

NEMA vs IEC (IEC 60529) Table A-1 [From NEMA 250-1997] Conversion of Enclosure Type numbers to IEC Classification Designations Cannot be used to convert IEC Classification Designations to NEMA Type numbers Enclosure Type Number NEMA Enclosure Classification Designation 1 IP10 2 IP11 3 IP54 3R 3S IP14 IP54 4 and 4X IP56 5 IP52 6 IP67 12 IP52 13 IP54 Note: It is not possible to state that an IP rating is equivalent to a NEMA Type Designation. However, it is possible to state that a NEMA Type is equivalent to an IP rating. An IP rating only considers protection against ingress of solid foreign objects and ingress of water. The NEMA Types consider these but also consider other items such as corrosions and construction details. June 27, 2013 Slide 46

Some details NEMA 250-2003 3 1 Type 1 Enclosures constructed for indoor use to provide a degree of protection to personnel against access to hazardous parts and to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt). 3 4 5 2 4 Type 12 Enclosures constructed (without knockouts) for indoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and circulating dust, lint, fibers, and flyings); and to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (dripping and light splashing). June 27, 2013 Slide 47

Some details Type 3R Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and that will be undamaged by the external formation of ice on the enclosure Type 3 Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against access to hazardous parts; to provide a degree of protection of the equipment inside the enclosure against ingress of solid foreign objects (falling dirt and windblown dust); to provide a degree of protection with respect to harmful effects on the equipment due to the ingress of water (rain, sleet, snow); and that will be undamaged by the external formation of ice on the enclosure. June 27, 2013 Slide 48

ANSI / IEC in detail 2.1 Arc Resistands (IEC 61641) 2.2 Grounding Systems (IEC 61439) 2.3 IP vs. NEMA (EN 60529) 2.4 Internal Segregation (IEC 61439) 2.5 Diversity Factors June 27, 2013 Slide 49

Forms of internal separation (IEC 61439) Separation of bus bars, functional units and external terminals. Objectives Protection against contact with live parts belonging to the adjacent functional units. The degree of protection shall be at least IPxxB (IP2x covers IPxxB) Protection against the passage of solid foreign bodies from one unit to an adjacent unit. The degree of protection shall be at least IP2x Reasons behind: Limitation of the probability of initiating arc faults. Maintenance on disconnected functional units (See national regulations) Extension under voltage (See national regulations) June 27, 2013 Slide 50

Cubicle compartments (IEC 61439) Bus bar Internal segregation of functional areas Superior operator protection Separate access for Maintenance Extensions Retrofits Maintainable from the front 2200 mm high 25 mm pitch depth from 400 to 1200 mm Equipment Cable June 27, 2013 Slide 51

IEC 61439-1 forms The following table from Standard IEC 61439-1 highlights typical forms of separation which can be obtained using barriers or partitions: June 27, 2013 Slide 52

IEC 61439-1 forms June 27, 2013 Slide 53

ANSI segregation ANSI mainly describes the dielectric clearance between parts. UL 1558 Chapter 7.3 (Switchgear) There is one standard segregation like Form 4b in IEC UL 845 MCC Dielectric Clearance only, no segregation like Form 1 in IEC UL 891 Switchboard Dielectric Clearance only, no segregation like Form 1 in IEC June 27, 2013 Slide 54

ANSI / IEC in detail 2.1 Arc Resistance (IEC 61641) 2.2 Grounding Systems (IEC 61439) 2.3 IP vs. NEMA (IEV 60529) 2.4 Internal Segregation (IEC 61493) 2.5 Diversity Factors (IEC 61439) June 27, 2013 Slide 55

Diversity factor - Current Ratings (IEC 61439) ANSI IEC Rated Current Short Circuit Duration Peak Withstand Current Rated Current Short Circuit Duration Peak Withstand Current 600 A 2 sec 2.7 times 630 A 0.5 sec short 1 sec circuit 1200 A current 1250 A 2 sec 2000 A 2000 A 3 sec 2.5 (2.6) times short circuit current 3000 A 2500 A 4000 A 3150 A 5000 A 4000 A June 27, 2013 Slide 56

Diversity factor (IEC 61439) Clearance and creepage distances IEC defines creepage distances depending on supportermaterial quality, means better quality more compact IEC defines clearances depending on overvoltage category (rated voltage in combination with electrical network) UL just defines one value Example: with distances acc. to UL at 600V, IEC products would be able to reach insulation voltages > 2000V (material group 3, pollution degree 4) in comparison to this UL requires very small distances which are smaller than the IEC values and at 30% of the UL-values at the incoming side June 27, 2013 Slide 57

Diversity factor (IEC 61439) Units NEMA-sizes defines and standardize the sizes of the units, the variety is significantly lower, unknown in IEC (usually done and optimized together with customers) In general UL significant over-sizes the rated currents, i.e. 115% (the market requires even more over-sizing), unknown in IEC June 27, 2013 Slide 58

Diversity factor (IEC 61439) IEC 60439-1: Annex E (to be agreed between manufacturer and user). Most important items (among others) include: 4.7 Rated diversity factor In the absence of information concerning the actual currents, the following standard values are used: Number of main circuits 2 and 3 0,9 4 and 5 0,8 6 to 9 inclusive 0,7 10 (and above) 0,6 Diversity factor June 27, 2013 Slide 59

Diversity factor (IEC 61439) 4000 A 1 2 3 4 5 6 7 8 9 10 Feeder with DF 1.0 Feeder with DF 0.6 400 A 630 A June 27, 2013 Slide 60

Diversity factor- summary (IEC 61439) UL 1558 Switchgear -> None UL 891 Switchboards -> Yes UL 845 MCC -> None Note: The diversity factor is not a derating factor! June 27, 2013 Slide 61

AGENDA 1. ANSI/UL vs. IEC Basics 2. ANSI/IEC in detail Spotlight s 3. Price comparison 4. Summary June 27, 2013 Slide 62

SWGR comparison - SLD 3150A 3150A 800A 800A 800A 800A 800A 800A Spare Spare Spare Spare Spare Spare Comparison based on a ANSI project Main bus 3200A June 27, 2013 Slide 63

SWGR Layout Dimensions ANSI 133.8w x 69d x 90h IEC 173.2w x 24d x 87h ANSI 3 400 x 1 750 x 2 286 IEC 4 400 x 600 x 2 200 June 27, 2013 Slide 64

SWGR - Price comparison Footprint IEC needs more cubicle and has a large footprint Material cost Based on the single cubicle solution, the material cost for copper and metal sheets are higher Labor Based on the single cubicle solution, the labor cost for assembling and wiring increases. Price relation ANSI IEC 1 : 1.75 June 27, 2013 Slide 65

ANSI to IEC MCC comparison - SLD 20hp 20hp 20hp 20hp 20hp 20hp 20hp 20hp 20hp 20hp Main lug only (Direct Incomer) Starter 20hp NEMA size 2 June 27, 2013 Slide 66

ANSI to IEC MCC comparison - Layout Dimensions ANSI 60w x 20d x 90h IEC 40w x 24d x 87h ANSI 1 540 x 500 x 2 200 IEC 1 040 x 600 x 2 200 June 27, 2013 Slide 67

ANSI to IEC MCC comparison - Summary Vertical Bus Bars ANSI 300A IEC 750A Segregation ANSI no segregation IEC Form 3 or more Cubicle design IEC cable compartment must be bigger Based on the design, the labor cost are higher Price relation ANSI IEC 1 : 1.75 June 27, 2013 Slide 68

IEC to ANSI MCC comparison - SLD 2000A 2000A 2000A diverse diverse diverse diverse diverse diverse diverse diverse diverse diverse 5 x <5.5kW 4 x 37kW 3 x <15kW 1 x 123kW 3 x <18kW 2 x 123kW (REV) 10 x <5.5kW 1 x 37kW 3 x <15kW 4 x 123kW 1 x <30 June 27, 2013 Slide 69

IEC to ANSI MCC comparison - Layout Dimensions ANSI 415w x 20d x 90h IEC 252w x 24d x 87h ANSI 10 540 x 500 x 2 200 IEC 6 040 x 600 x 2 200 June 27, 2013 Slide 70

IEC to ANSI MCC comparison - Summary Starter size IEC can be build more compact Footprint As larger the MCC as bigger the ANSI footprint Design IEC MCC are available arc resistant until 6300A ANSI needs more cubicles, labor cost is the same Price relation ANSI IEC 1 : 0.75 June 27, 2013 Slide 71

AGENDA 1. ANSI/UL vs. IEC Basics 2. ANSI/IEC in detail Spotlight s 3. Price comparison 4. Summary June 27, 2013 Slide 72

ANSI vs IEC summary One world two different Standards? Each standard has it specialty We can not mix the two standards None of them is better Each one has its price structure BU ABB 3101 Group Low Voltage Systems June 27, 2013 Slide 73

ANSI vs IEC summary Questions?? Thank you for your interest!! June 27, 2013 Slide 74

June 27, 2013 Slide 75