Fire Alarm System Accessories



Similar documents
Hazardous Area Classifications and Protections

5/3/2010. Article 500 address the requirements for hazardous locations: Wiring Equipment

TrueAlarm Fire Alarm Systems

Intrinsically Safe Barrier Relays NY2 and 8501TO

SafeSite LED RTO Area Light - UL844. for Indoor and Outdoor Industrial Applications #

Hazardous Area Classifications and Protections

Practical Guidelines for Electrical Area Classification in Combustion Turbine-Generator Power Plants

D287/D288/D292/D293A/D293E

NEMA Enclosure Types

Classification of Hazardous Atmospheres

Electrical Classification

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Class/Division Hazardous Location

UFGS (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Basics of Explosion Protection

PLAN REVIEW GUIDE FOR FIRE ALARM

Explosion Protected White Paper Series #1: Imaging Challenges in Explosive Environments

Fire Fighter Phone System Installation Instructions

Today's world of increasing

Protection Systems. A UTC Fire & Security Company F Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS

Life Alarm Fire Alarm Controls

DUCT SMOKE DETECTOR D4120

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

Fire Control Panels. Remote Annunciator Panels. UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features. Introduction

FDNY C14 Certificate of Fitness Quiz

HAZARDOUS AREA TECHNICAL GUIDE

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL

AUTOMATIC LPG BOOKING, LEAKAGE DETECTION AND A REAL TIME LPG MEASUREMENT MONITORING SYSTEM

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P

DTW Works Master Specification Version 2006

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

Making sense of Intrinsic Safety and Intrinsically Safe Tools

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

12 Volt 30 Amp Digital Solar Charge Controller Installation & Operation Manual

Advanced Intelligent Modules. Overview. Description

HM-W536 Install Guide

Installation Instructions for Alarm Module Kit A043F059

Safety instructions VEGAFLEX FX8*(*).FC/ O****A/H*****

Color Mark Sensor with Red or Green LED E3S-VS

Release Control Fire Alarm Systems

SECTION SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

QCS Section 23 Part 2 Fire Alarm and Detection Systems Page 1 2. FIRE ALARM DETECTION SYSTEMS...2

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

TrueAlarm Fire Alarm Systems

FLARE MONITORS FLARE MONITOR (FM) PILOT MONITOR (PM) FLAME INTENSITY (FI)

IMPORTANT INSTRUCTIONS & OPERATING MANUAL. Houston 50 Inch Electric Wall Mounted Fireplace Black / White

E-PDD Duct Smoke Detector Installation Sheet

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

SECTION FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

Liquid Leakage Sensor Amplifier

Technical Data. Dimensions

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

TS93 EMR T/PT/TDE. Surface applied door closer

SafeSite LED High Bay - UL 844 for Indoor and Outdoor Hazardous Applications

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

Conventional Fire Detection and Extinguishant Control System Specification

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

Ventostat Wall Mount. Telaire Wall Mount CO 2. , Humidity and Temperature Transmitters. GE Measurement & Control. Features:

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

Model 201 Wiegand Touchpad Reader Installation Guide

PAINT BOOTH LIGHTING

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

CB200W Water Leak Detection Panel Application Guide

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Fire & Security DETECTORS

MCR1900 Media Converter 19-Slot Chassis

Fire detection equipment

WIRELESS STATUS MONITOR

SECTION FIRE ALARM AND DETECTION SYSTEMS

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

Electric motors can pose a serious threat when they are

Intersection Preassembled 19-inch Rack

8146/5 Series Breaker Panelboards

Contractors Guide Central Inverter System Installation

Buckeye Detection Systems Fixed Detection Systems Application Survey

40.3. Control Relays and Timers

EzFlex Combustible Gas Leak Detector Model EZ40

Isolating Barriers for our sensors A5S1 in Ex-areas Series D461

LIEBERT VNSA Installation Sheet

Mobrey Ultrasonic. MSP900SH Level and MSP900FH Flow Transmitters. Product Data Sheet February 2015 IP2032, Rev BA

SC100 Series Seismic Vibration Sensors. The Best Way to Protect High-Risk Commercial Assets

12 Volt 30 Amp Digital Solar Charge Controller

9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

Fire Alarm System Plans Review Checklist Property location Date of Review

Triple Waveband Infra-Red Flame Detection

Arecont Vision H.264 Color or Day/Night SurroundVideo Series Installation Manual

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS

Transcription:

Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer isolated barrier modules: 2081-9062, Single channel 2081-9063, Dual channel Meets requirements of National Electrical Code Articles 500-517 for Hazardous Locations: Classes I, II, & III Divisions 1 & 2 Groups A, B, C, D, E, F, & G Compatible with Simplex intrinsically safe manual stations and simple apparatus: Refer to page 2 for compatible product details including compatible smoke detector model Product selection summary is detailed on page 7 Required accessories (ordered separately): 2975-9218, Red cabinet with solid door and lock 2081-9061, Module installation kit Description Simplex Intrinsically Safe Modules are for use with FM Approved Simplex control panels to make initiating device circuit wiring safe for use in locations where hazardous concentrations of flammable gases or other materials may exist. The intrinsically safe module is an isolated, power-limited barrier that limits the output current to a level below ignition for atmospheres defined by NEC Articles 500-517 for Classes I, II, & III, Divisions 1 & 2, Groups A, B, C, D, E, F, & G. Installation Considerations. The installation of intrinsically safe modules requires strict adherence to product compatibility lists and must be in accordance with all product installation instructions and applicable codes and wiring practices. Review all applicable references thoroughly before completing the intrinsically safe design. * Refer to page 2 for listing exceptions. This application is FM approved only. Contact your local Simplex product supplier for additional information. Listings and approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster. U.S.A. FM Intrinsically Safe Barrier Module Mounted in Cabinet (shown with cover removed, wiring and conduit shown for reference only) Specifications Barrier Modules 2081-9062 and 2081-9063** Input Voltage (Vin) Input Current (Iin) Output Voltage (VOUT) Output Current 4 to 35 VDC 40 ma maximum, limited by module impedance VIN < 23.7 V VOUT = VIN - (400 x IIN) - 0.7 V VIN > 23.7 V VOUT = VIN - (400 x IIN) Transfer current 40 ma Short circuit current 65 ma Operating Temperature 32 F to 120 F (0 C to 49 C) Operating Humidity Dimensions Up to 85% RH maximum @ 86 F (30 C) 4-1/2 H x 4-1/4 W (including terminal block) x 13/16 D (114 mm x 108 mm x 21 mm) 2975-9218 Cabinet; Required, Ordered Separately Dimensions Color 12 W x 8-3/8 H x 3-1/2 D (305 mm x 213 mm x 89 mm) Red 2081-9061 Installation Kit; Required, Ordered Separately Contents Bracket for barrier module mounting (35 mm DIN rail type), mounting hardware, control drawing, and required end-of-line resistors ** Refer to page 7 for listing of approved entity parameters and allowable wiring distances. S2081-0018-3 10/2003

Intrinsically Safe Barrier Module Compatibility Simplex 2081-9062 and 2081-9063 Intrinsically Safe Modules report alarms as a current limited condition. FM Approval is for use with the Simplex fire alarm control panels and peripheral devices described in the following selection chart. NOTE: Intrinsically Safe applications are NOT COMPATIBLE with Alarm Verification operation. Compatibility Reference Compatible Simplex Fire Alarm Control Panels and Modules Model Series Description 4004 and 4005 Class B IDCs, both standard and high current 4020 Class B IDCs 4100 Class B IDC module 4100-5004 4100U Class B IDC module 4100-5005 Zone Adapter Modules (ZAMs) Model Description 2190-9155 Class B (surface cover); MAPNET II communications only 2190-9156 Class B (flush cover); MAPNET II communications only 4090-9101 Compatible Initiating Devices* Class B, for use with compatible Simplex fire alarm control panels; MAPNET II or IDNet communications Manual Stations Model Series Description 2099-9767 Single Action Station 2099-9799 Double Action (Breakglass) Station Simple Apparatus Any device which does not store or generate more than 1.2 V, 100 ma, or 20 J (typically a dry contact heat detector or pushbutton switch) Compatible Smoke Detector (NOTE: NOT FM APPROVED, but tested as compatible with IDCs listed) Compatible IDCs 4100-5004 4100-5005 4090-9101 Description Hochiki Intrinsically Safe Photoelectric Smoke Detector Model SLR-E-IS with Hochiki Intrinsically Safe Detector Base Model YBN-R/4-IS; NOTE: Five (5) maximum per circuit; Available from Hochiki America * Although the above listed peripheral model numbers are FM Approved as Intrinsically Safe (except as noted), these peripheral devices and any simple apparatus must be selected for proper fire protection compatibility with the dust content and corrosion potential of the atmosphere to be protected. Installation Requirements 1. All equipment MUST be installed in accordance with the National Electrical Code, NEC ANSI/NFPA 70 Article 504, and ANSI/ISA-RP 12.6-1987. 2. Cable and/or conduit from Non-Hazardous and Hazardous locations MUST enter the barrier enclosure from opposite sides and MUST be sealed per National Electrical Code, Article 504. 3. Intrinsically Safe circuits MUST NOT be installed in the same cable, conduit, or raceway with non-intrinsically safe circuits. 4. Intrinsically Safe circuits are for indoor applications only. 5. Maximum line resistance from the Fire Alarm panel to the last device in the Hazardous location is 10. 6. The 2975-9218 cabinet must be equipped with a safety ground per NEC Article 250-42. The grounding conductor must be 12 AWG (3.31 mm 2 ) minimum (the barrier is not grounded). 7. For additional wiring information, reference the National Electrical Code, Articles 500 through 517 and Simplex Control Drawing 842-070. 8. Refer to page 7 for approved entity parameter information reference. 2 S2081-0018-3 10/2003

Installation Reference Pluggable input terminal block (green) Mounting bracket Pluggable output terminal block (blue) 2975-9218 Cabinet Cabinet ground terminal Approved by Conduit from fire alarm panel U.S.A. FM APPROVED Conduit to Hazardous area Cabinet grounding conductor, 12 AWG minimum Barrier module (green) Cable and/or conduit between barrier and hazardous area shall be sealed per National Electrical Code Article 504 Wiring Diagram Reference Diagram below is for reference only, refer to Control Diagram 842-070 for complete installation details. Compatible Simplex Style B Initiating Device Zone (+) Zone (-) For 4090-9101 ZAM only,15 k 1/2 W resistor (378-054) is required here Cabinet grounding conductor Non-Hazardous Location + In (11) - In (12) + In (11) - In (12) + In (9) - In (10) 2081-9062 Single Barrier Module 2081-9063 Dual Barrier Module + Out (1) - Out (2) + Out (1) - Out (2) + Out (4) - Out (5) Conduit required, seal per NFPA 70 Section 504-70 Hazardous Location Class I, II, III, DIV 1, 2 Groups A, B, C, D, E, F, G EOL Resistor 3.9 k (378-059) for: 4002 4004-9822 4004-9824 4005-9824 4.7 k (378-056) for: Manual Stations 4100, 4100 UT 2099-9767 or 2099-9799 4090-9101 and/or other devices that qualify as simple apparatus 6.8 k (378-058) for: 2190-9155 NOTE: Intrinsically safe circuits are for indoor applications only. 2190-9156 4004-9802 4004-9804 4005-9803 4005-9804 3 S2081-0018-3 10/2003

National Electrical Code Hazardous Location Classifications* Class I Locations Class I locations are those in which flammable gases or vapors are, or may be, present in the air in quantities sufficient to produce explosive or ignitable mixtures. Class I, Division 1 A Class I, Division 1 location is a location: 1. In which ignitable concentrations of flammable gases or vapors can exist under normal operating conditions; or 2. In which ignitable concentrations of such gases or vapors may exist frequently because of repair or maintenance operations or because of leakage; or 3. In which breakdown or faulty operation of equipment or processes might release ignitable concentrations of flammable gases or vapors, and might also cause simultaneous failure of electric equipment. Class II Locations Class II locations are those that are hazardous because of the presence of combustible dust. Class II, Division 1 A Class II, Division 1 location is a location: 1. In which combustible dust is in the air under normal operating conditions in quantities sufficient to produce explosive or ignitable mixtures; or 2. Where mechanical failure or abnormal operation of machinery or equipment might cause such explosive or ignitable mixtures to be produced, and might also provide a source of ignition through simultaneous failure of electric equipment, operation of protection devices, or from other causes; or 3. In which combustible dusts of an electrically conductive nature may be present in hazardous quantities. Class III Locations Class III locations are those that are hazardous because of the presence of easily ignitable fibers or flyings, but in which such fibers or flyings are not likely to be in suspension in the air in quantities sufficient to produce ignitable mixtures. Class III Division 1 A Class III, Division 1 location is a location in which easily ignitable fibers or materials producing combustible flyings are handled, manufactured, or used. General Note, Division 2 Categories Equipment marked Division 1 is suitable for both Division 1 and Division 2 locations. Group Definitions Class I: Group A. Atmospheres containing acetylene. Group B. Atmospheres containing hydrogen, fuel and combustible process gases containing more than 30 percent hydrogen by volume, or gases or vapors of equivalent hazard such as butadiene, ethylene oxide, propylene oxide, and acrolein. Group C. Atmospheres such as, ethyl ether, ethylene, or gases or vapors of equivalent hazard. Group D. Atmospheres such as acetone, ammonia, benzene, butane, cyclopropane, ethanol, gasoline, hexane, methanol, methane, natural gas, naphtha, propane or gases, or vapors of equivalent hazard. Class II: Group E. Atmospheres containing combustible metal dusts, including aluminum, magnesium, and their commercial alloys, or other combustible dusts whose particle size, abrasiveness, and conductivity present similar hazards in the use of electrical equipment. Group F. Atmospheres containing combustible carbonaceous dusts, including carbon black, charcoal, coal, or dusts that have been sensitized by other materials so that they present an explosion hazard. Group G. Atmospheres containing combustible dusts not included in Group E or F, including flour, grain, wood, plastic, and chemicals. Reference For additional information concerning these hazardous location classifications, refer to NFPA 70, the National Electrical Code. (A publication of NFPA, the National Fire Protection Association.) * Please note that the above information is summarized from NFPA 70, Article 500 and is presented for reference only. Refer to NFPA 70 for further information. 4 S2081-0018-3 10/2003

Description Single action stations require a firm downward pull to break the plastic rod visible below the pull lever and actuate a switch to sound the alarm. The front of the station is hinged and must be opened to reset the station and to replace the plastic rod. Double action stations require that the hammer, hung on the front of the station, be lifted and thrown downward against the glass window, thus breaking it to expose the recessed pull lever. As with the single action station, a firm downward pull of the pull lever actuates and locks in the alarm switch. Single action station reset. To reset the single action station, a key unlocks and opens the station which then permits the handle to return to its normal position when the station is relocked. If a break-rod is used, it must be replaced in order to complete the reset process. Double action station reset. The double action station is reset in a similar manner except that the glass window must be replaced to restore operation. Mounting Notes 1. For surface mounting, use a Simplex 2975-9178 red steel back box or a 2975-9022 aluminum back box. Do not substitute a box with a depth less than 2-3/16 (56 mm). Refer to drawing below. 2. For semi-flush mounting, use a standard single gang 2-1/2 (64 mm) deep switch box. DO NOT RECESS BOX, mount box flush or with 1/16 (2 mm) maximum protrusion. Refer to drawing on page 6. 3. For flush mounting, refer to drawing on page 6. 4. Wiring is 18 AWG minimum, 14 AWG maximum (0.82 mm 2, 2.08 mm 2 ). Intrinsically Safe Manual Stations 2099-9767 Intrinsically Safe Single Action Manual Station FIRE BREAK ALARM GLASS 2099-9799 Intrinsically Safe Double Action Breakglass Manual Station Surface Mounting Reference Knockouts located top and bottom 4" (102 mm) 2975-9178 Box FIRE ALARM 5-3/16" (132 mm) 5" (127 mm) PULL DOWN Station cover hinges open for installation access 2-3/16" (56 mm) 2975-9178 Box 1" (25.4 mm) 3-3/4" (95 mm) 5 S2081-0018-3 10/2003

Intrinsically Safe Manual Station Semi-Flush Mounting Single Gang Box Mount Single gang box, 2-1/2" deep (64 mm), RACO #500 or equal (supplied by others) 4" Square Box Mount 4" (102 mm) square box, 2-1/8" (54 mm) minimum depth, RACO #231 or equal (supplied by others) Mount flush or with 1/16" (2 mm) maximum extension DO NOT RECESS 4" Square box with cover plate FIRE ALARM Station side view PULL DOWN Single gang cover plate, 3/4" (19 mm) extension, RACO #773 or equal (supplied by others) Wall surface Single gang box outline Semi-Flush Mount Side View Intrinsically Safe Manual Station, Flush Mounting Information Flush mount adapter kit 2099-9819, Black 2099-9820, Beige Box must be recessed into wall 1" to 1-1/8" (25.4 mm to 29 mm) 8" (203 mm) 6" (152 mm) Hole cutout must be a minimum of 6" H by 5" W (152 mm by 127 mm) 4-3/4" (121 mm) 6-3/4" (171 mm) Wall surface 4-11/16" (119 mm) square box, 2-1/8" (54 mm) minimum depth (by others) Front View Side View 6 S2081-0018-3 10/2003

Intrinsically Safe Product Selection Barrier Modules Model Description Notes 2081-9062 Single Channel Intrinsically Safe Barrier Module 2081-9063 Dual Channel Intrinsically Safe Barrier Module Required Accessories (ordered separately) Each module requires an 2081-9061 installation kit, and a 2975-9218 cabinet Model Description Notes 2081-9061 Intrinsically Safe Barrier Installation Kit Includes barrier module mounting bracket, mounting hardware, control drawing, and required end-of-line resistors 2975-9218 Intrinsically Safe Barrier Cabinet Cabinet is red with solid door and keyed lock Intrinsically Safe Manual Stations (ordered separately) Model Description 2099-9767 Single Action Manual Station 2099-9799 Double Action Manual Station (Breakglass) Manual Station Accessories Model Description 2975-9178 Surface Mount Steel Box, Red 2975-9022 Cast Aluminum Surface Mount Box, Red 2099-9819 Flush Mount Adapter Kit, Black 2099-9820 Flush Mount Adapter Kit, Beige 2099-9803 Replacement Breakglass 2099-9804 Replacement Break-Rod Refer to page 5 for details Refer to page 6 for details Compatible Smoke Detector (NOTE: Refer to page 2 for compatible IDCs) Model SLR-E-IS YBN-R/4-IS Description Hochiki Intrinsically Safe Photoelectric Smoke Detector Hochiki Intrinsically Safe Detector Base Requires a YBN-R/4-IS detector base Required for SLR-E-IS detector This smoke detector and base has been tested for compatibility but is not agency listed or approved; maximum of five (5) per circuit; available from Hochiki America Entity Parameters and Maximum Total Wiring Lengths from Control Panel to Last Device in Hazardous Area* Group Maximum Capacitance Maximum Inductance A, B 0.14 F 3.84 mh C, E 0.42 F 15.61 mh D, F, G 1.11 F 31.49 mh Open Circuit Voltage (V OC ) 28.4 V 97 ma Short Circuit Current (I SC ) 18 AWG 16 AWG 14 AWG 12 AWG 781 ft (238 m) 1250 ft (381 m) 2000 ft (610 m) 2000 ft (610 m) 3100 ft (945 m) * Refer to Control Drawing 842-070 for complete information. Wiring distances provided are for individual conductors in conduit with assumed parameters of 60 pf/ft and 0.2 H/ft. Metric wire equivalents: 18 AWG = 0.82 mm 2 ; 14 AWG = 2.08 mm 2 ; 12 AWG = 3.31 mm 2 7 S2081-0018-3 10/2003

Tyco, Simplex, the Simplex logo, MAPNET II, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. NEC, NFPA, and National Electrical Code are trademarks of the National Fire Protection Association. Tyco Safety Products Westminster Westminster, MA 01441-0001 USA S2080-0018-3 10/2003 www.tycosafetyproducts-usa-wm.com 2003 Tyco Safety Products Westminster. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.