Ampacity simulation of a high voltage cable to connecting off shore wind farms



Similar documents
Module 1 : Conduction. Lecture 5 : 1D conduction example problems. 2D conduction

Power over Ethernet Requirements and Limitations due to the Cabling System

Cable Size Selection for Energy Efficiency

Effect of design parameters on temperature rise of windings of dry type electrical transformer

Offshore Wind Farm Export Cable Current Rating Optimisation

HEAT TRANSFER IM LECTURE HOURS PER WEEK THERMODYNAMICS - IM _1

M. GELDON Brugg Kabel CZ. Ing. D. RÚŽEK PREdistribuce. Switzerland Czech Rep. Czech Rep. Czech Rep., Switzerland Germany

Comparative study for cables and busbars

6 ELECTRICAL PARAMETERS

Supporting document to NORSOK Standard C-004, Edition 2, May 2013, Section 5.4 Hot air flow

Comparison of Power Título Transmission Line Models with Finite Elements

4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

WEEKLY SCHEDULE. GROUPS (mark X) SPECIAL ROOM FOR SESSION (Computer class room, audio-visual class room)

Integration of a fin experiment into the undergraduate heat transfer laboratory

Thermal Management of Electronic Devices used in Automotive Safety A DoE approach

Coupling Forced Convection in Air Gaps with Heat and Moisture Transfer inside Constructions

Steady Heat Conduction

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR

KNOW YOUR OPTIONS: 230 KV POWER CABLES

ENERGY. TECSUN DUO (PV) Twin Cables for Photovoltaics

Motor-CAD Software for Thermal Analysis of Electrical Motors - Links to Electromagnetic and Drive Simulation Models

Natural Convection. Buoyancy force

Section kv Power Cables

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

Estimating Line-Flow Limits

The soot and scale problems

MV CABLE TYPE C

Top Drive Service Loops. Conventional, Enhanced and Superior Solutions for Drilling Applications

Trace Layer Import for Printed Circuit Boards Under Icepak

THERMAL DESIGN AND TEST REQUIREMENTS FOR OUTSIDE PLANT CABLE TELECOMMUNICATIONS EQUIPMENT Al Marshall, P.E. Philips Broadband Networks

How To Calculate Thermal Resistance On A Pb (Plastipo)

Comparing naturally cooled horizontal baseplate heat sinks with vertical baseplate heat sinks

EXPERIMENTAL AND CFD ANALYSIS OF A SOLAR BASED COOKING UNIT

Thermal insulation. Don t be afraid of low temperatures. Institute for Technical Physics Holger Neumann

FREESTUDY HEAT TRANSFER TUTORIAL 3 ADVANCED STUDIES

A NUMERICAL AND EXPERIMENTAL STUDY OF THE FACTORS THAT INFLUENCE HEAT PARTITIONING IN DISC BRAKES

Numerical Simulation of Temperature and Stress Fields in the Rock Heating Experiment

Shrinking a power supply and the challenge to maintain high reliability.

CABLE CLAMPS FOR SINGLE- AND MULTI-CORE CABLES

Cable Installation Notes

Experimental Study of Free Convection Heat Transfer From Array Of Vertical Tubes At Different Inclinations

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide

Natural Convective Heat Transfer from Interrupted Rectangular Fins

Exergy Analysis of a Water Heat Storage Tank

Effects of Cell Phone Radiation on the Head. BEE 4530 Computer-Aided Engineering: Applications to Biomedical Processes

Learning Module 4 - Thermal Fluid Analysis Note: LM4 is still in progress. This version contains only 3 tutorials.

Measuring Optical and Thermal Properties of High Temperature Receivers

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

Everline Module Application Note: Round LED Module Thermal Management

Modelling of fire spread in car parks

OBJECTIVES THE STUDENTS WILL: Participate in cooperative problem solving in a group setting.

Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number R1D1. 13 January 2015

Carbon Cable. Sergio Rubio Carles Paul Albert Monte

POROUS BURNER - A New Approach to Infrared

EXPERIMENT 3a HEAT TRANSFER IN NATURAL CONVECTION

Figure 1 - Unsteady-State Heat Conduction in a One-dimensional Slab

Considerations for Predicting Thermal Contact Resistance in ANSYS.

Calculating Heat Loss by Mark Crombie, Chromalox

HV Submarine Cable Systems Design, Testing and Installation

Understanding Plastics Engineering Calculations

INTERNATIONAL STANDARD

HEAT AND MASS TRANSFER

Power Dissipation Considerations in High Precision Vishay Sfernice Thin Film Chips Resistors and Arrays (P, PRA etc.) (High Temperature Applications)

Kresimir Bakic, CIGRE & ELES, Slovenia

The Three Heat Transfer Modes in Reflow Soldering

The simulation of machine tools can be divided into two stages. In the first stage the mechanical behavior of a machine tool is simulated with FEM

Ravi Kumar Singh*, K. B. Sahu**, Thakur Debasis Mishra***

HVDC Light Cables. Submarine and land power cables

STANDARD EXTRUDED HEAT SINKS

INJECTION MOLDING COOLING TIME REDUCTION AND THERMAL STRESS ANALYSIS

Safakcan Tuncdemir 1, William M. Bradley *2. 1. Introduction

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW

The Electrical Properties of Materials: Resistivity

Energy and Buildings

DSRQ - DSRSQ - DSRSQ-THERM

1150 hp motor design, electromagnetic and thermal analysis

WHITEPAPER. Cable and Connector for Hiperface dsl motor drive applications

Forms of Energy. Freshman Seminar

ME6130 An introduction to CFD 1-1

Express Introductory Training in ANSYS Fluent Lecture 1 Introduction to the CFD Methodology

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES

CHAPTER 6 THERMAL DESIGN CONSIDERATIONS. page. Introduction 6-2. Thermal resistance 6-2. Junction temperature 6-2. Factors affecting R th(j-a) 6-2

Energy Transport. Focus on heat transfer. Heat Transfer Mechanisms: Conduction Radiation Convection (mass movement of fluids)

HVAC air curtains. Type InduAir

DESIGN AND SIMULATION OF LITHIUM- ION BATTERY THERMAL MANAGEMENT SYSTEM FOR MILD HYBRID VEHICLE APPLICATION

Real Time Monitoring of Power Cables by Fibre Optic Technologies Tests, Applications and Outlook

The Effect of Forced Air Cooling on Heat Sink Thermal Ratings

Turbulent Flow Through a Shell-and-Tube Heat Exchanger

Journal bearings/sliding bearings

Essay 5 Tutorial for a Three-Dimensional Heat Conduction Problem Using ANSYS Workbench

Pushing the limits. Turbine simulation for next-generation turbochargers

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

AN EFFECT OF GRID QUALITY ON THE RESULTS OF NUMERICAL SIMULATIONS OF THE FLUID FLOW FIELD IN AN AGITATED VESSEL

International Electrotechnical Commission Standards

WHITEPAPER CABLE CONDUCTOR SIZING

Transcription:

Ampacity simulation of a high voltage cable to connecting off shore wind farms Eva Pelster 1, Dr. David Wenger 1 1 Wenger Engineering GmbH, Einsteinstr. 55, 89077 Ulm, mail@wenger-engineering.com Abstract: The ampacity of a cable depends on the cross-section of its conductor. When selecting a cable design for a specific application, it is of interest to choose the lowest possible conductor cross-section in order to reduce material costs. Therefore, an exact calculation of the ampacity is necessary; it is usually limited by the thermal resistance of the insulating cable materials. Commonly, the ampacity is determined using semi-empirical methods to evaluate the maximum temperatures. These methods include safety margins that may result in low ampacity values. In this study, COMSOL Multiphysics is used to determine temperature conditions in a high-voltage cable connecting offshore wind turbines. It is shown that the conventional analytical methods do not apply to the given conditions and the simulation is able to demonstrate alternative methods to determine the ampacity. between the standardised IEC calculation and a COMSOL simulation. Furthermore, it is to be shown that COMSOL Multiphysics may serve as an alternative to conventional calculation methods, particularly where an increasingly complex cable structure and cable periphery is to be taken into account. 2. Comparison of IEC calculation and COMSOL simulation 2.1 Single-conductor cable For the first example, the ampacity of a single-conductor cable is determined in accordance with a maximum permissible conductor temperature. Keywords: cable ampacity, thermal resistance, heat conductivity, temperature profile, cable simulation 1. Introduction The procedure for cable design is described in the IEC standard. One of the typical demands to be observed is the maximum permissible temperature of the conductor, in particular with a view to keeping the temperatures in the insulation material low. To meet this demand, it is usual to select a cable cross-section appropriate to the desired maximum current, as the conductor cross-section directly influences the heat losses arising in the conductor concerned. As the costs of conductor materials are very high, precise calculation of the current carrying capacity is of extreme importance. The IEC standard describes the procedure for calculation of this capacity in accordance with defined limit temperatures. The calculations are based on simple heat conductivity calculations and semi-empirical models. In the following, two simple examples are first presented to illustrate the comparison Figure 1. Geometry of single-conductor cable As this case is a simple calculation of radial heat conduction, it can be assumed that the calculated results will coincide with the simulation. The equations shown here are taken from the standard calculation. The first step for calculation of the ampacity is to determine the thermal resistance of the individual cable layers using Eq. (1). (1) The temperature differences between the individual layers are determined using Eq. (2):

The heat flow is calculated by way of the power loss in the conductor, namely in accordance with Eq. (3) and (4): (2) (3) (4) Both convective cooling and ambient heat radiation are assumed at the surface of the cable. To describe the corresponding heat flow, separate heat transfer coefficients are determined for the convection and radiation components and then combined into a thermal resistance relating to the ambient temperature. The convective heat transfer coefficient is calculated with: (4) The constants k 1, s, k 2,s are calculated using the following empirically determined models: (5) (6) The heat transfer coefficient to take into account the radiation is calculated using the emission coefficient ε and the Stefan Boltzmann constant σ in the equation: The arising temperature difference between the conductor surface and the cable surface thus amounts to: (9) By way of Eq. (2), it is then also possible to determine the temperatures of the individual layers. To calculate the ampacity, a maximum conductor temperature is specified, and the corresponding maximum permissible current is determined by iteration. To compare the calculation model based on the aforementioned equations with a COMSOL simulation, a corresponding model can be established in COMSOL. Figure 1 shows the first model. To calculate the ampacity, the Heat Transfer in Solids mode is used. To this end, a Heat Source is defined in the conductor in accordance with Eq. (3) and (4). Equivalently to the IEC model, a Convective Cooling boundary condition is also applied at the cable surface, based on Eq. (4) and (7). For iteration of the ampacity, an additional global constraint is set to specify the maximum temperature in the conductor. Table 1 provides an overview of the parameters used. Table 1: Values used for single-conductor cable r 1 7.5 mm 1 400 W/(m² K) r 2 15 mm 2 0.3 W/(m² K) r 3 35 mm 3 44 W/(m² K) r 4 38 mm 4 0.3 W/(m² K) These factors are converted into a thermal resistance relative to the environment: (7) (8) R 20 0.125 /km T max 90 C As was to be expected, the resultant values and temperatures coincide in this case. Figure 2

shows the temperatures for the individual layers of the cable, referring in each case to the outer radius of the layer concerned. Figure 2. Temperatures in single-conductor cable 2.2 Three-conductor cable The next step is now to show that, when dealing with models which, although still simple, nevertheless display increasing complexity, the differences between a standard calculation and the COMSOL simulation increase accordingly. To this end, a configuration comprising a bundle of three single-conductor cables in air was chosen. In the IEC model, the bundling of three single-conductor cables is taken into account by incorporating an additional factor into the thermal resistance calculation. The equation is thus modified as follows: (11) The values of f ks and f rs change in accordance with the configuration and layout of the different cables [1]. Furthermore, the additional conductors are taken into account in Eq. (3) and (4) by way of the additionally generated heat flow. Here, too, as in the previous case, an equivalent model is implemented in COMSOL. Figure 3 shows the calculated geometry, for which a Convective Cooling boundary condition is again defined at the cable surface in accordance with Eq. (11). A Heat Source is calculated for the conductors in accordance with Eq. (3) and (4). Figure 3. Geometry of single-conductor cable Table 2: Values used for three bundled singleconductor cables r 1 7 mm 1 400 W/(m² K) r 2 14 mm 2 0.3 W/(m² K) r 3 18.5 mm 3 0.3 W/(m² K) R 20 0.125 /km T max 90 C Iteration of the ampacity with the two models already results in differences. The standard calculation produces a current value of 541 A, whereas COMSOL indicates an ampacity of 563 A. Figure 4 reveals also the different temperatures for the individual layers. This can be explained by the fact that the simple assumptions from the IEC calculation model, which are here again based on the calculation of radially symmetrical cables, no longer apply properly for this configuration.

is here necessary to take into account also the losses in the shield and the armouring. Furthermore, the cable is surrounded by an air-filled cylinder. Figure 6 shows a partially extruded cylinder with cable. The full extrusion is not depicted for the sake of clarity; the total height is typically over 20 m. Figure 4. Temperatures of three bundled singleconductor cables 3. Calculation of a more complex configuration with COMSOL 3.1 COMSOL model On the basis of the assumptions from the previous section, this section describes a model to determine the ampacity of an increasingly more complex configuration, as used in offshore wind farms, for example. The cable shown here is a multiple-core high-voltage cable which runs vertically through an air-filled metal cylinder. Such cylinders are typically used to route the cable to the generator in a wind turbine. The critical point for this application in respect of the maximum temperature is that the cables here hang free in air, whereas they are elsewhere typically routed over the sea bed and are thus adequately cooled. Figure 6. Extruded geometry of cable in cylinder, blue shows air domain For this case, it is necessary to investigate not only the heat conduction, but also the flows attributable to free convection in the cylinder. To this end, the Conjugate Heat Transfer mode is applied. To model the arising air flow, a gravitational force was defined for the air. For the heat conduction at the outer jacket, the boundary conditions Convective Cooling and Surface to Ambient Radiation were selected. Figure 7 shows the arising flow for a stationary load case with a constant current flowing through the conductors. The resultant temperature difference between the cable and the environment produces a free convection flow in the air-filled cylinder. Figure 5. Geometry of high-voltage three-conductor cable Figure 5 shows the cross-section of a cable. In addition to the heat losses in the conductors, it

Figure 7. Velocity in cable casing 7. Conclusions It was possible to demonstrate that COMSOL Multiphysics can be used to calculate cable ampacity. As presumed, increasingly more complex cable configurations lead to differences between the standard calculation and the simulation. As the standard calculation cannot take into account complex geometries, it incorporates additional safety margins which are in part not required in the simulation. In a further step, a complete model for temperature calculation with a high-voltage cable suitable to connect an offshore wind turbine was determined. This model enabled explicit investigation and evaluation of the influence of the cable periphery. 8. References 1. L. Heinhold, R. Stubbe, Kabel und Leitungen für Starkstrom, MCD Verlag, (1999)