RECOMMENDATIONS FOR REPAIR OF SPRAY POLYURETHANE FOAM (SPF) ROOF SYSTEMS DUE TO HAIL AND WIND DRIVEN DAMAGE



Similar documents
THERMAL BARRIERS FOR THE SPRAY POLYURETHANE FOAM INDUSTRY

RECOATING AND RENEWING SPF ROOFING SYSTEMS

The Renewal of Spray Polyurethane Foam and Coating Roof Systems

Spray Polyurethane Foam Systems for Cold Storage Facilities Operating Between - 40 o C and + 10 o C (- 40 o F and + 50 o F )

COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE

Specifying SPF Roofing Systems

Roof Restoration System. For building owners, property management firms and facility managers. seamless possibilities

NEOGARD. Preventive Maintenance Manual

SPECIFICATIONS FOR SEWER PIPE AND LINING INSERTION - TRENCHLESS; GENERAL GUIDELINES (As Provided by NASSCO)

Roof Condition Analysis

Ball Peen Hammer Test

Building Owners Guide to a Duro-Last System!

Get Rid of Roof Problems for Good. How spray foam roofing can protect your building and make you money

APPENDIX B. I. Background Information

INDUSTRY RECOMMENDATIONS for Sanding, Sealing Court Lining, Finishing & Resurfacing of Maple Gym Floors

Selecting Vinyl Flooring

CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS

CA-48 TECHNICAL SPECIFICATION

SMOOTHMOVE INSTRUCTIONS FURNITURE VAN EPOXY FLOOR FINISH KIT VOC-FREE - NO SOLVENT GENERAL INFORMATION KEY 87269AB

Minor Cracks in Horizontal Surfaces

PHOENIX Product Data Sheet (Updated on 14-Jan-2012)

Business area System/product family System/product Exterior restore group. Sto restore Advanced Restoration for Building Façades

Colorado State University. Durrell Center Roof Repair

PART E SPECIFICATIONS

Glulam Appearance Classifications for Construction Applications

Look out for the reviews before you happen to finalize the siding replacement service

StuccoSpec Moisture Testing Inspection

UNIVERSITY OF CHICAGO ELEVATOR PIT LEAK REPAIR

Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION CONCRETE BONDING COMPOUND.

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

Tiled Shower Pan Leaks - Investigation And Repair FAQ

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

External Wrapping of Steel Riser Pipe. Case Study HJ3 CS200902

WATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION

Oil and Gas Pipeline Design, Maintenance and Repair

bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls

SCHWARTZ WATER-BASE WOOD FLOOR SEALER AND WATER-BASE PREMIIUM WOOD FLOOR FINISH

NAPCA BULLETIN APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE

Secondary Containment Comparison ATI Ultra COAT vs HDPE

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

Roof Inspection. Summary Report

Evaluating Composition Shingles

ROOF INSPECTION & MAINTENANCE

A. Work on this project shall consist of, but is not limited to, the following:

Commercial Roof Management

REPLACE YOUR ROOF TO VISUALLY INSPECT YOUR ROOF REGULARLY SO YOU CAN DISCOVER PROBLEMS WHILE THEY ARE STILL MINOR AND CAN BE REPAIRED.

Williamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, (68 pages)

STANDARD SPECIFICATIONS SECTION SEWER MAIN AND LATERAL CONNECTION SEALING BY CHEMICAL GROUT

SPF ROOFING. Tomorrow's Roof Today

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

DRAFT MAINTAINING HOUSTON S STREETS REPAIR, REHABILITATION, RECONSTRUCTION. Using the Full Range of Tools for a Challenging Job

BLACK JACK ALL WEATHER ROOF COATING

The AQUAFIN Approach to Concrete Repair

What Can I Expect from Synergy?

The Perfect Fit For Metal Retrofit

INSTALLATION INSTRUCTION - INSTRUCCIONES DE INSTALACION FOR DOUBLE-HUNG VENT REPLACEMENT WINDOW

DIVISION: PLUMBING SECTION: DOMESTIC WATER PIPING REPORT HOLDER: CURAFLO IP LLC 4035 E. OASIS STREET MESA, AZ 85215

Document Library TS Data Sheet

PAINT REMOVAL SYSTEM PAINT REMOVAL SPECIFICATION SAFE WORK METHOD STATEMENT FOR LEAD PAINT REMOVAL

Metropolitan Builders Association Masonry & Concrete Standard

Rehabilitation of an Aging Concrete Reservoir Adit Tower

Owner s Manual & Safety Instructions

POLYURETHANE LINING AND COATING ON PIPE RAW WATER

!!! !!!! !!! !!! !!! !!! !!!!!!!!! Table of Contents! Section 1: Most Common Types of Flat Roofing! Section 2: Better Understand Your Flat Roof!

Rudder Repair and refinish

Know the Code: Using Spray Foam Insulation In Attics and Crawl Spaces

Aerial Infrared Roof Moisture Surveys

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012

High Performance PSA in Sheet Membrane in Water Protection

Baton Rouge Foundation Repair

TECHNICAL REQUIREMENTS AND SPECIFICATIONS

METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES

Sun Vinyl New Construction Windows Homeowner's Warranty

SIDE SEWER CONDITION ASSESSMENT AND REPAIR RECOMMENDATIONS

In the Fall 2002 issue of HHE News I examined

SANITARY GRAVITY SEWER LINE TESTING. B. Section CCTV Inspection of Gravity Sewer Lines

WATERPROOFING FOR CONCRETE STRUCTURES

Fluid-Applied Roofing for Repair and Renovation FACILITIES & MAINTENANCE PRIVATE UNIVERSITY PRODUCTS AND NEWS JULY 2015

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

SECTION 311 PLACEMENT AND CONSTRUCTION OF CEMENT TREATED SUBGRADESOIL CEMENT BASE COURSE

SECTION WATER STORAGE TANK PAINTING

1. (1) Random Orbital Sander 2. (1) Angle Polisher, (Rated at approx RPM), with 4.75 inch diameter hook backup

ASBESTOS MANAGEMENT PROGRAM

The Ultimate in Weathersealing Versatility. Dow Corning 123 Silicone Seal

Document Library TS Data Sheet M Windo-Weld Super Fast Urethane. Data Sheet. Public

Low-slope reroofing guidelines

SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide

Sewer Rehabilitation Design Requirements

Bituminous Sheet Flat Roofs: Their repair and maintenance

TARRANT COUNTY DETAIL STANDARDS

Nondestructive Evaluation of USCG Hawkins Pt. Road Curtis Bay, MD Provided by: HurleyIR

A. This Section includes rubberized asphalt sheet membrane waterproofing systems.

Eric Six Heath Consultants Incorporated

Code of Standard Practice for Timber Frame Structures

(800) (562) A Subsidiary of the International Code Council *Revised April 2014

Roofing Signs that Your Roof Needs Repair/Replacement

Transcription:

RECOMMENDATIONS FOR REPAIR OF SPRAY POLYURETHANE FOAM (SPF) ROOF SYSTEMS DUE TO HAIL AND WIND DRIVEN DAMAGE RECOMMENDED DESIGN CONSIDERATIONS AND GUIDE SPECIFICATIONS Spray Polyurethane Foam Alliance Copyright January 2003 To order copies of this publication, call 800-523-6154 and request SPFA Stock Number AY-139 1

TECHNICAL COMMITTEE Mission Statement The mission of the Technical Committee is to provide a wide range of technical service to the Spray Polyurethane Foam industry such as, but not limited to: 1. Review existing documents and serve as a clearing house to ensure the Continuity of Value of technical information published by SPFD and others concerning the products and services to our industry; 2. Review, research, develop and issue documents concerning new products, systems and services AND 3. To identify, explore, develop and communicate an understanding of technical issues facing our industry. Technical Committee Members Roger Morrison, Chairman North Carolina Foam Industries Mary Bogdan Honeywell John Courier Equipment & Coatings Technology John Hatfield Penta Engineering Group, Inc. Tim Leonard ERSystems Jack Moore West Roofing Systems, Inc. Robert Smith KoSa Brad Beauchamp Stepan Co. Jim Calkins Dow Chemical John Ewell Dallas/Ft. Worth Urethane, Inc. Larry Smiley Poly-Tek. John Stahl Preferred Solutions, Inc. Bruce Schenke BASF Dennis Vandewater Sadler Coatings Systems AD HOC MEMBER: Laverne Dalgleish CUFCA This brochure was developed to aid specifiers in choosing spray-applied polyurethane foam systems. The information provided herein, based on current customs and practices of the trade, is offered in good faith and believed to be true, but is made WITHOUT WARRANTY, EITHER EXPRESS OR IMPLIED, AS TO FITNESS, MERCHANTABILITY, OR ANY OTHER MATTER. SPFA DISCLAIMS ALL LIABILITY FOR ANY LOSS OR DAMAGE ARISING OUT OF ITS USE. Individual manufacturers and contractors should be consulted for specific information. Nominal values which may be provided herein are believed to be representative, but are not to be used as specifications nor assumed to be identical to finished products. SPFA does not endorse the proprietary products or processes of any individual manufacturer, or the services of any individual contractor. 2

RECOMMENDATIONS FOR REPAIR OF SPRAY POLYURETHANE FOAM (SPF) ROOF SYSTEMS DUE TO HAIL AND WIND DRIVEN DAMAGE OBJECTIVE Research has indicated the damage caused by wind driven missiles typically does not cause a spray polyurethane foam (SPF) roof to leak. This damage can usually be repaired economically and does not require the roof to be replaced. This document provides a means to evaluate information collected from the investigation of an SPF roof system after damage has occurred and to make recommendations for the rehabilitation and/or repair of the damaged areas. Ascertain the degree of the damage through a detailed on-site inspection (visual, physical analysis, drawings, reports) and determine which category of damage has occurred. CAUSE OF DAMAGE Typical causes of damage and detailed descriptions of types of damage are described below. 1) Mechanical damage due to wind driven missiles 2) Hail During high wind events a wide variety of objects can potentially impact a roof and produce damage to the protective coating and SPF. This damage may be isolated to small areas of the roof or cover large areas. Substrate and structural damage may or may not have occurred and should be thoroughly investigated. The type of repairs required will depend on the size and severity of the damage and should be consistent with SPFA s Guideline AY-122, The Renewal of Spray Polyurethane Foam and Coating Roof Systems. Hail can damage both the surface coating and the underlying foam in an SPF roof system. 3

Coating damage can appear as gouges, cracks, and punctures. Hail induced coating cracks often form patterns shaped like crow s feet or semi-circles. Depending on hail stone size, shape, and hardness, the underlying foam may be dented, cracked, or gouged. Depressions in SPF dented by hail stones may be 1/8-inch to 3/4-inch deep. Hail damage can be isolated to small areas or cover the entire roof surface. The repair technique is determined from the severity (size and depth of damage) and extent (number of hail hits per unit area) of the hail damage. For example, fifteen 3-inch diameter hail dents on a 1000 square foot roof may be easier to repair than hundreds of 3/4-inch diameter dents. Occasionally, hail damage may not be discovered for months or years after a hail event. In these circumstances, the repairs may be more extensive because of UV degradation and/or moisture intrusion due to breached coating and damaged foam cell structure. 3) Foam and coating abrasion Abrasion occurs when the wind blows sand/debris at a velocity sufficient to erode the protective coating over the SPF. Abraded coated SPF roofs are repaired by re-coating the affected areas and should be consistent with the SPFA s Guideline AY-122. 4

INSPECTION PROCEDURES The first step in making an evaluation and repair recommendation of a damaged SPF roof is a thorough inspection. Follow the SPFA AY-122, The Renewal of Spray Polyurethane Foam and Coating Roof Systems. Wind driven damage may not be readily visible from all directions. Check for the specific following items: Damage causing roof leaks. Flashing and termination point damage. Splits and other impact damage. Abraded coating. Substrate or structural damage. Moisture intrusion in the SPF. Determine severity and extent of hail damage by using a grid method (See Table 1). DEGREES OF HAIL OR MISSILE DAMAGE AND REPAIR RECOMMENDATIONS After obtaining information from the roof inspection, repair recommendations can be developed specific to the damage sustained based on Table 1. The degree of damage may vary in different areas of the roof. Repair procedures shall vary accordingly. Consult the manufacturer for specific recommendations before commencing repairs. 5

TABLE 1 The following chart can help classify the mechanical damage and provide repair recommendations. Damage extent in this chart is categorized as less than 10 or more than 20 defects per 100 ft 2. Recommended repairs for damage extents between 10 and 20 defects per 100 ft 2 will require judgement based on manufacturer s recommendations. Degree of Damage Light Size & severity Extent per 100 ft² Recommended repair 1/2"diameter or less less than 1/8 deep Less than 10 cracks, cuts and/or dents Caulk and coat dents, cuts and cracks. Note: Re-coat should be considered based on remaining service life of coating More than 20 cracks, cuts or dents Re-coat as required to fill in cracks Note: Some caulking may be required to seal deeper cracks Less than 10 cracks/dents Coat/caulk cracks Moderate 1/2" to 3/4" diameter less than 1/4" deep More than 20 cracks, cuts or dents Recoat as required to seal cracks Note: Some caulking may be required to seal deeper cracks Heavy 3/4" to 1-1/2 1/4 to 1/2" deep Less than 10 cracks/dents More than 20 cracks/dents Remove damaged SPF: Caulk holes and recoat as required Scarify 1/2" of roof surface: Re-foam and coat Severe 1-1/2 or larger 1/2" or deeper Less than 10 crack/dents More than 20 cracks/dents Remove damaged SPF: Caulk holes: Recoat as required Scarify 3/4" of roof surface: Re-foam and coat DEGREES OF COATING ABRASION AND REPAIR RECOMMENDATIONS 6

Wind driven sand, dirt, and other small particles can abrade and scour the coating and SPF systems. The degree of damage will vary in different areas of the roof. Repair procedures will vary accordingly. Different coatings will have different resistance to abrasion and thicker coating layers will provide protection for longer periods of time. Light and moderate abrasion will remove and roughen the coating surface exposing small areas of SPF. This type of damage can be repaired by renewing the coating system with additional compatible coating. Consult the coating manufacturer for specific recommendations. Heavy and severe abrasion will remove much of the coating system, expose the SPF, and possibly erode the SPF as well. This will leave depressions and pits in the surface. Severe abrasion can be repaired by scarifying or removing the damaged foam and coating surface, reapplying SPF, and applying the coating system in the area affected. Repairs for this type of damage can sometimes be made by applying a mixture of fillers and coating to cover the rough SPF and coating surface followed by a finish coat. Consult the manufacturer for specific recommendations. Spray Polyurethane Foam Alliance 4400 Fair Lakes Court. Suite 105 Fairfax, VA 22033 www.sprayfoam.org 7