Configurable s for APC Network Management Card
Table of Contents Silcon DP300E Series 3 Smart-UPS / Matrix 7 Symmetra 9 Symmetra 3-Phase 13 Environmental Monitor 21 Configurable s for APC Network Management Card Page 2 of 22
Silcon DP300E Series System: Coldstart. 0x0001 Severe System: Warmstart. 0x0002 Severe System: SNMP configuration change. 0x0003 Warning System: Detected an unauthorized user attempting to access the SNMP 0x0004 Informational System: Detected an unauthorized user attempting to access the Console 0x0005 Warning System: Detected an unauthorized user attempting to access the Web 0x0006 Warning System: Network service started. 0x0007 None System: Password changed. 0x0008 Warning System: File transfer started. 0x000C None System: File transfer started. 0x000D None System: File transfer failed. 0x000F None System: Console user logged in. 0x0014 None System: Web user logged in. 0x0015 None System: FTP user logged in. 0x0016 None System: Console user logged out. 0x001E None System: Web user logged out. 0x001F None System: FTP user logged out. 0x0020 None System: Reset to defaults. 0x0018 None System: Initializing data in the file. 0x0019 None System: Email information. 0x001A None System: Trace information. 0x0024 None System: Modem dial-out failed. 0x0025 Warning System: RMS CLI user logged in. 0x0026 None System: RMS CLI user logged out. 0x0027 None System: Network service information. 0x002A None System: Network service could not start. 0x002B None System: Network service stopped. 0x002C None UPS: Communications established. 0x1001 Informational UPS: Communications lost. 0x1002 Severe UPS: Sensed a load greater than 100 percent of rated capacity. 0x1003 Severe UPS: Overload condition cleared. 0x1004 Informational UPS: Passed internal self-test. 0x1005 Informational UPS: Failed internal diagnostic self-test. 0x1006 Severe UPS: Batteries discharged. 0x1007 Severe UPS: Battery discharge condition cleared. 0x1008 Informational UPS: Switched to battery backup power. 0x1009 Warning UPS: Returned from battery backup power. 0x100A Informational Configurable s for APC Network Management Card Page 3 of 22
Silcon DP300E Series (continued) UPS: Enabled SmartBoost; low incoming line voltage. 0x100B Warning UPS: Returned from SmartBoost. 0x100C Informational UPS: Enabled SmartTrim; high incoming line voltage. 0x100D Warning UPS: Returned from SmartTrim. 0x100E Informational UPS: Battery power is low and will soon be exhausted. 0x100F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational UPS: Turned on. 0x0113 Informational UPS: Turned off. 0x0114 Warning UPS: Entered sleep mode. 0x0115 Warning UPS: Returned from sleep mode. 0x0116 Informational UPS: Started reboot sequence. 0x0117 Warning UPS: Batteries need immediate replacement. 0x0119 Severe UPS: Bad battery condition cleared. 0x011A Informational UPS: In bypass due to an internal fault. 0x011B Severe UPS: In bypass due to user command via software or panel. 0x011C Warning UPS: In bypass initiated by user. 0x011D Warning UPS: Returned from bypass. 0x011E Informational UPS: Base module bypass power supply failure. 0x011F Severe UPS: Base module fan failure. 0x0120 Severe UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe UPS: Battery calibration test initiated. 0x0123 Informational UPS: Battery calibration complete. 0x0124 Informational UPS: Graceful shutdown in progress. 0x0125 Informational UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational UPS: Bad output voltage condition. 0x0128 Warning UPS: Bad output voltage condition cleared. 0x0129 Informational UPS: Battery charger failure. 0x012A Warning UPS: Battery charger failure cleared. 0x012B Informational UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational UPS: No batteries installed. 0x012F Warning UPS: No batteries installed cleared. 0x0130 Informational UPS: Power Module failure. 0x0201 Severe UPS: Power Module failure cleared 0x0202 Informational UPS: Intelligence Module failure. 0x0203 Severe UPS: Intelligence Module failure cleared. 0x0204 Informational UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational UPS: Battery failure. 0x0207 Severe Configurable s for APC Network Management Card Page 4 of 22
Silcon DP300E Series (continued) UPS: Battery failure cleared. 0x0208 Informational UPS: Load(kVA) alarm threshold violation. 0x0209 Severe UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational UPS: Redundancy lost. 0x020B Severe UPS: Redundancy returned. 0x020C Informational UPS: Redundancy below alarm threshold. 0x020D Severe UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range cleared; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational UPS: In bypass due to an internal fault 0x0215 Severe UPS: In bypass due to an internal fault cleared. 0x0216 Informational UPS: In bypass due to an overload. 0x0217 Severe UPS: In bypass due to an overload cleared. 0x0218 Informational UPS: In maintenance bypass. 0x0219 Severe UPS: In maintenance bypass cleared. 0x021A Informational UPS: Input circuit breaker tripped open. 0x021B Severe UPS: Input circuit breaker tripped open cleared. 0x021C Informational UPS: System level fan failure. 0x021D Severe UPS: System level fan failure cleared. 0x021E Informational UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational UPS: No working Power Modules. 0x0223 Severe UPS: No working Power Modules cleared. 0x0224 Informational UPS: Load shutdown from bypass; input frequency or voltage outside 0x0225 Severe limits. UPS: Load shutdown from bypass cleared; input frequency or voltage 0x0226 Informational outside limits. UPS: Runtime below alarm threshold. 0x0227 Severe UPS: Runtime below alarm threshold cleared. 0x0228 Informational UPS: Extended Run Frame fault. 0x0229 Severe UPS: Extended Run Frame fault cleared. 0x022A Informational UPS: Output voltage out of range. 0x022B Severe UPS: Output voltage out of range cleared. 0x022C Informational UPS: Not synchronized fault 0x022D Severe UPS: Not synchronized fault cleared. 0x022E Informational Configurable s for APC Network Management Card Page 5 of 22
Silcon DP300E Series (continued) UPS: No batteries installed. 0x022F Severe UPS: No batteries installed cleared. 0x0230 Informational UPS: Battery voltage high. 0x0231 Severe UPS: Battery voltage high cleared. 0x0232 Informational UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe UPS: Non-specific fault cleared. 0x0234 Informational UPS: Site wiring fault. 0x0235 Severe UPS: Site wiring fault cleared. 0x0236 Informational UPS: Backfeed protection relay open. 0x0237 Severe UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register set cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0x0240 Informational UPS: Number of batteries increased. 0x0241 Informational UPS: Number of batteries decreased. 0x0242 Informational UPS: Number of Power Modules increased. 0x0243 Informational UPS: Number of Power Modules decreased. 0x0244 Informational UPS: Intelligence Module inserted. 0x0245 Informational UPS: Intelligence Module removed. 0x0246 Informational UPS: Redundant Intelligence Module inserted. 0x0247 Informational UPS: Redundant Intelligence Module removed. 0x0248 Informational UPS: Number of Extended Run Frames increased. 0x0249 Informational UPS: Number of Extended Run Frames decreased. 0x024A Informational Configurable s for APC Network Management Card Page 6 of 22
Smart-UPS / Matrix System: Coldstart. 0x0001 Severe System: Warmstart. 0x0002 Severe System: SNMP configuration change. 0x0003 Warning System: Detected an unauthorized user attempting to access the SNMP 0x0004 Informational System: Detected an unauthorized user attempting to access the Console 0x0005 Warning System: Detected an unauthorized user attempting to access the Web 0x0006 Warning System: Network service started. 0x0007 None System: Password changed. 0x0008 Warning System: File transfer started. 0x000C None System: File transfer started. 0x000D None System: File transfer failed. 0x000F None System: Console user logged in. 0x0014 None System: Web user logged in. 0x0015 None System: FTP user logged in. 0x0016 None System: Console user logged out. 0x001E None System: Web user logged out. 0x001F None System: FTP user logged out. 0x0020 None System: Reset to defaults. 0x0018 None System: Initializing data in the file. 0x0019 None System: Email information. 0x001A None System: Trace information. 0x0024 None System: Modem dial-out failed. 0x0025 Warning System: RMS CLI user logged in. 0x0026 None System: RMS CLI user logged out. 0x0027 None System: Network service information. 0x002A None System: Network service could not start. 0x002B None System: Network service stopped. 0x002C None UPS: Communication established. 0x0101 Informational UPS: Communication lost. 0x0102 Severe UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe UPS: Overload condition cleared. 0x0104 Informational UPS: Passed internal self-test. 0x0105 Informational UPS: Failed internal diagnostic self-test. 0x0106 Severe UPS: Batteries discharged. 0x0107 Severe UPS: Batteries discharge condition cleared. 0x0108 Informational UPS: Switched to battery backup power. 0x0109 Warning UPS: Returned from battery backup power. 0x010A Informational Configurable s for APC Network Management Card Page 7 of 22
Smart-UPS / Matrix (continued) UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning UPS: Returned from SmartBoost. 0x010C Informational UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning UPS: Returned from SmartTrim. 0x010E Informational UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational UPS: Turned on. 0x0113 Informational UPS: Turned off. 0x0114 Warning UPS: Entered sleep mode. 0x0115 Warning UPS: Returned from sleep mode. 0x0116 Informational UPS: Started reboot sequence. 0x0117 Warning UPS: Batteries need immediate replacement. 0x0119 Severe UPS: Bad battery condition cleared. 0x011A Informational UPS: In bypass due to an internal fault. 0x011B Severe UPS: In bypass due to user command via software or panel. 0x011C Warning UPS: In bypass initiated by user. 0x011D Warning UPS: Returned from bypass. 0x011E Informational UPS: Base module bypass power supply failure. 0x011F Severe UPS: Base module fan failure. 0x0120 Severe UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe UPS: Battery calibration test initiated. 0x0123 Informational UPS: Battery calibration complete. 0x0124 Informational UPS: Graceful shutdown in progress. 0x0125 Informational UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational UPS: Bad output voltage condition. 0x0128 Warning UPS: Bad output voltage condition cleared. 0x0129 Informational UPS: Battery charger failure. 0x012A Warning UPS: Battery charger failure cleared. 0x012B Informational UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational UPS: No batteries installed. 0x012F Warning UPS: No batteries installed cleared. 0x0130 Informational UPS: Scheduled shutdown initiated. 0x0131 Informational UPS: Scheduled shutdown failed. 0x0132 Warning UPS: Scheduled shutdown deleted. 0x0133 Informational Configurable s for APC Network Management Card Page 8 of 22
Symmetra System: Coldstart. 0x0001 Severe System: Warmstart. 0x0002 Severe System: SNMP configuration change. 0x0003 Warning System: Detected an unauthorized user attempting to access the SNMP 0x0004 Informational System: Detected an unauthorized user attempting to access the Console 0x0005 Warning System: Detected an unauthorized user attempting to access the Web 0x0006 Warning System: Network service started. 0x0007 None System: Password changed. 0x0008 Warning System: File transfer started. 0x000C None System: File transfer started. 0x000D None System: File transfer failed. 0x000F None System: Console user logged in. 0x0014 None System: Web user logged in. 0x0015 None System: FTP user logged in. 0x0016 None System: Console user logged out. 0x001E None System: Web user logged out. 0x001F None System: FTP user logged out. 0x0020 None System: Reset to defaults. 0x0018 None System: Initializing data in the file. 0x0019 None System: Email information. 0x001A None System: Trace information. 0x0024 None System: Modem dial-out failed. 0x0025 Warning System: RMS CLI user logged in. 0x0026 None System: RMS CLI user logged out. 0x0027 None System: Network service information. 0x002A None System: Network service could not start. 0x002B None System: Network service stopped. 0x002C None UPS: Communications established. 0x0101 Informational UPS: Communications lost. 0x0102 Severe UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe UPS: Overload condition cleared. 0x0104 Informational UPS: Passed internal self-test. 0x0105 Informational UPS: Failed internal diagnostic self-test. 0x0106 Severe UPS: Batteries discharged. 0x0107 Severe UPS: Battery discharge condition cleared. 0x0108 Informational UPS: Switched to battery backup power. 0x0109 Warning UPS: Returned from battery backup power. 0x010A Informational Configurable s for APC Network Management Card Page 9 of 22
Symmetra (continued) UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning UPS: Returned from SmartBoost. 0x010C Informational UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning UPS: Returned from SmartTrim. 0x010E Informational UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational UPS: Turned on. 0x0113 Informational UPS: Turned off. 0x0114 Warning UPS: Entered sleep mode. 0x0115 Warning UPS: Returned from sleep mode. 0x0116 Informational UPS: Started reboot sequence. 0x0117 Warning UPS: Batteries need immediate replacement. 0x0119 Severe UPS: Bad battery condition cleared. 0x011A Informational UPS: In bypass due to an internal fault. 0x011B Severe UPS: In bypass due to user command via software or panel. 0x011C Warning UPS: In bypass initiated by user. 0x011D Warning UPS: Returned from bypass. 0x011E Informational UPS: Base module bypass power supply failure. 0x011F Severe UPS: Base module fan failure. 0x0120 Severe UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe UPS: Battery calibration test initiated. 0x0123 Informational UPS: Battery calibration complete. 0x0124 Informational UPS: Graceful shutdown in progress. 0x0125 Informational UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational UPS: Bad output voltage condition. 0x0128 Warning UPS: Bad output voltage condition cleared. 0x0128 Informational UPS: Battery charger failure. 0x012A Warning UPS: Battery charger failure cleared. 0x012B Informational UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational UPS: No batteries installed. 0x012F Warning UPS: No batteries installed cleared. 0x0130 Informational UPS: Scheduled shutdown initiated. 0x0131 Informational UPS: Scheduled shutdown failed. 0x0132 Warning UPS: Scheduled shutdown deleted. 0x0133 Informational UPS: Power Module failure. 0x0201 Severe UPS: Power Module failure cleared. 0x0202 Informational UPS: Intelligence Module failure. 0x0203 Severe UPS: Intelligence Module failure cleared. 0x0204 Informational Configurable s for APC Network Management Card Page 10 of 22
Symmetra (continued) UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational UPS: Battery failure. 0x0207 Severe UPS: Battery failure cleared. 0x0208 Informational UPS: Load(kVA) alarm threshold violation. 0x0209 Severe UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational UPS: Redundancy lost. 0x020B Severe UPS: Redundancy returned. 0x020C Informational UPS: Redundancy below alarm threshold. 0x020D Severe UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range cleared; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational UPS: In bypass due to an internal fault. 0x0215 Severe UPS: In bypass due to an internal fault cleared. 0x0216 Informational UPS: In bypass due to an overload. 0x0217 Severe UPS: In bypass due to an overload cleared. 0x0218 Informational UPS: In maintenance bypass. 0x0219 Severe UPS: In maintenance bypass cleared. 0x021A Informational UPS: Input circuit breaker tripped open. 0x021B Severe UPS: Input circuit breaker tripped open cleared. 0x021C Informational UPS: System level fan failure. 0x021D Severe UPS: System level fan failure cleared. 0x021E Informational UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational UPS: No working Power Modules. 0x0223 Severe UPS: No working Power Modules cleared. 0x0224 Informational UPS: Load shutdown from bypass; input frequency or voltage outside 0x0225 Severe limits. UPS: Load shutdown from bypass cleared; input frequency or voltage 0x0226 Informational outside limits. UPS: Runtime below alarm threshold. 0x0227 Severe UPS: Runtime below alarm threshold cleared. 0x0228 Informational UPS: Extended Run Frame fault. 0x0229 Severe UPS: Extended Run Frame fault cleared. 0x022A Informational UPS: Output voltage out of range. 0x022B Severe Configurable s for APC Network Management Card Page 11 of 22
Symmetra (continued) UPS: Output voltage out of range cleared. 0x022C Informational UPS: Not synchronized fault. 0x022D Severe UPS: Not synchronized fault cleared. 0x022E Informational UPS: No batteries installed. 0x022F Severe UPS: No batteries installed cleared. 0x0230 Informational UPS: Battery voltage high. 0x0231 Severe UPS: Battery voltage high cleared. 0x0232 Informational UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe UPS: Non-specific fault cleared. 0x0234 Informational UPS: Site wiring fault. 0x0235 Severe UPS: Site wiring fault cleared. 0x0236 Informational UPS: Backfeed protection relay open. 0x0237 Severe UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0X0240 Informational UPS: Number of batteries increased. 0X0241 Informational UPS: Number of batteries decreased. 0X0242 Informational UPS: Number of Power Modules increased. 0X0243 Informational UPS: Number of Power Modules decreased. 0X0244 Informational UPS: Intelligence Module inserted. 0X0245 Informational UPS: Intelligence Module removed. 0X0246 Informational UPS: Redundant Intelligence Module inserted. 0X0247 Informational UPS: Redundant Intelligence Module removed. 0X0248 Informational UPS: Number of Extended Run Frames increased. 0X0249 Informational UPS: Number of Extended Run Frames decreased. 0X024A Informational Configurable s for APC Network Management Card Page 12 of 22
Symmetra 3-Phase System: Coldstart. 0x0001 Severe System: Warmstart. 0x0002 Severe System: SNMP configuration change. 0x0003 Warning System: Detected an unauthorized user attempting to access the SNMP 0x0004 Informational System: Detected an unauthorized user attempting to access the Console 0x0005 Warning System: Detected an unauthorized user attempting to access the Web 0x0006 Warning System: Network service started. 0x0007 None System: Password changed. 0x0008 Warning System: File transfer started. 0x000C None System: File transfer started. 0x000D None System: File transfer failed. 0x000F None System: Console user logged in. 0x0014 None System: Web user logged in. 0x0015 None System: FTP user logged in. 0x0016 None System: Console user logged out. 0x001E None System: Web user logged out. 0x001F None System: FTP user logged out. 0x0020 None System: Reset to defaults. 0x0018 None System: Initializing data in the file. 0x0019 None System: Email information. 0x001A None System: Trace information. 0x0024 None System: Modem dial-out failed. 0x0025 Warning System: RMS CLI user logged in. 0x0026 None System: RMS CLI user logged out. 0x0027 None System: Network service information. 0x002A None System: Network service could not start. 0x002B None System: Network service stopped. 0x002C None UPS: Communications established. 0x0101 Informational UPS: Communications lost. 0x0102 Severe UPS: Sensed a load greater than 100 percent of rated capacity. 0x0103 Severe UPS: Overload condition cleared. 0x0104 Informational UPS: Passed internal self-test. 0x0105 Informational UPS: Failed internal diagnostic self-test. 0x0106 Severe UPS: Batteries discharged. 0x0107 Severe UPS: Battery discharge condition cleared. 0x0108 Informational UPS: Switched to battery backup power. 0x0109 Warning UPS: Returned from battery backup power. 0x010A Informational Configurable s for APC Network Management Card Page 13 of 22
Symmetra 3-Phase (continued) UPS: Enabled SmartBoost; low incoming line voltage. 0x010B Warning UPS: Returned from SmartBoost. 0x010C Informational UPS: Enabled SmartTrim; high incoming line voltage. 0x010D Warning UPS: Returned from SmartTrim. 0x010E Informational UPS: Battery power is low and will soon be exhausted. 0x010F Severe UPS: Returned from a Low-Battery condition. 0x0110 Informational UPS: Turned on. 0x0113 Informational UPS: Turned off. 0x0114 Warning UPS: Entered sleep mode. 0x0115 Warning UPS: Returned from sleep mode. 0x0116 Informational UPS: Started reboot sequence. 0x0117 Warning UPS: Batteries need immediate replacement. 0x0119 Severe UPS: Bad battery condition cleared. 0x011A Informational UPS: In bypass due to an internal fault. 0x011B Severe UPS: In bypass due to user command via software or panel. 0x011C Warning UPS: In bypass initiated by user. 0x011D Warning UPS: Returned from bypass. 0x011E Informational UPS: Base module bypass power supply failure. 0x011F Severe UPS: Base module fan failure. 0x0120 UPS: External battery pack communications established. 0x0121 Informational UPS: External battery pack communications lost. 0x0122 Severe UPS: Battery calibration test initiated. 0x0123 Informational UPS: Battery calibration complete. 0x0124 Informational UPS: Graceful shutdown in progress. 0x0125 Informational UPS: SmartBoost or SmartTrim relay failure. 0x0126 Warning UPS: SmartBoost or SmartTrim relay failure cleared. 0x0127 Informational UPS: Bad output voltage condition. 0x0128 Warning UPS: Bad output voltage condition cleared. 0x0129 Informational UPS: Battery charger failure. 0x012A Warning UPS: Battery charger failure cleared. 0x012B Informational UPS: Internal battery temperature threshold violation. 0x012C Warning UPS: Internal battery temperature threshold violation cleared. 0x012D Informational UPS: No batteries installed. 0x012F Warning UPS: No batteries installed cleared. 0x0130 Informational UPS: Scheduled shutdown initiated. 0x0131 Warning UPS: Scheduled shutdown failed. 0x0132 Informational UPS: Scheduled shutdown deleted. 0x0133 Severe UPS: Power Module failure. 0x0201 Severe UPS: Power Module failure cleared. 0x0202 Informational UPS: Intelligence Module failure. 0x0203 Severe UPS: Intelligence Module failure cleared. 0x0204 Informational Configurable s for APC Network Management Card Page 14 of 22
Symmetra 3-Phase (continued) UPS: Redundant Intelligence Module failure. 0x0205 Severe UPS: Redundant Intelligence Module failure cleared. 0x0206 Informational UPS: Battery failure. 0x0207 Severe UPS: Battery failure cleared. 0x0208 Informational UPS: Load(kVA) alarm threshold violation. 0x0209 Severe UPS: Load(kVA) alarm threshold violation cleared. 0x020A Informational UPS: Redundancy lost. 0x020B Severe UPS: Redundancy returned. 0x020C Informational UPS: Redundancy below alarm threshold. 0x020D Severe UPS: Redundancy below alarm threshold cleared. 0x020E Informational UPS: Bypass not in range; either frequency or voltage. 0x020F Severe UPS: Bypass not in range; either frequency or voltage. 0x0210 Informational UPS: Bypass contactor stuck in bypass position. 0x0211 Severe UPS: Bypass contactor stuck in bypass position cleared. 0x0212 Informational UPS: Bypass contactor stuck in on-line position. 0x0213 Severe UPS: Bypass contactor stuck in on-line position cleared. 0x0214 Informational UPS: In bypass due to an internal fault. 0x0215 Severe UPS: In bypass due to an internal fault cleared. 0x0216 Informational UPS: In bypass due to an overload. 0x0217 Severe UPS: In bypass due to an overload cleared. 0x0218 Informational UPS: In maintenance bypass. 0x0219 Severe UPS: In maintenance bypass cleared. 0x021A Informational UPS: Input circuit breaker tripped open. 0x021B Severe UPS: Input circuit breaker tripped open cleared. 0x021C Informational UPS: System level fan failure. 0x021D Severe UPS: System level fan failure cleared. 0x021E Informational UPS: Redundant Intelligence Module in control. 0x021F Severe UPS: Redundant Intelligence Module in control cleared. 0x0220 Informational UPS: IIC inter-module communications failure. 0x0221 Severe UPS: IIC inter-module communications failure cleared. 0x0222 Informational UPS: No working Power Modules. 0x0223 Severe UPS: No working Power Modules cleared. 0x0224 Informational UPS: Load shutdown from bypass; input frequency or voltage outside 0x0225 Severe limits. UPS: Load shutdown from bypass cleared; input frequency or voltage 0x0226 Informational outside limits. UPS: Runtime below alarm threshold. 0x0227 Severe UPS: Runtime below alarm threshold cleared. 0x0228 Informational UPS: Extended Run Frame fault. 0x0229 Severe UPS: Extended Run Frame fault cleared. 0x022A Informational UPS: Output voltage out of range. 0x022B Severe Configurable s for APC Network Management Card Page 15 of 22
Symmetra 3-Phase (continued) UPS: Output voltage out of range cleared. 0x022C Informational UPS: Not synchronized fault. 0x022D Severe UPS: Not synchronized fault cleared. 0x022E Informational UPS: No batteries installed. 0x022F Severe UPS: No batteries installed cleared. 0x0230 Informational UPS: Battery voltage high. 0x0231 Severe UPS: Battery voltage high cleared. 0x0232 Informational UPS: Non-specific fault; Access UPS keyboard for details. 0x0233 Severe UPS: Non-specific fault cleared. 0x0234 Informational UPS: Site wiring fault. 0x0235 Severe UPS: Site wiring fault cleared. 0x0236 Informational UPS: Backfeed protection relay open. 0x0237 Severe UPS: Backfeed protection relay open cleared. 0x0238 Informational UPS: Bit 28 of the abnormal condition register set. 0x0239 Severe UPS: Bit 28 of the abnormal condition register cleared. 0x023A Informational UPS: Bit 29 of the abnormal condition register set. 0x023B Severe UPS: Bit 29 of the abnormal condition register cleared. 0x023C Informational UPS: Bit 30 of the abnormal condition register set. 0x023D Severe UPS: Bit 30 of the abnormal condition register cleared. 0x023E Informational UPS: Bit 31 of the abnormal condition register set. 0x023F Severe UPS: Bit 31 of the abnormal condition register cleared. 0x0240 Informational UPS: Number of batteries increased. 0x0241 Informational UPS: Number of batteries decreased. 0x0242 Informational UPS: Number of Power Modules increased. 0x0243 Informational UPS: Number of Power Modules increased. 0x0244 Informational UPS: Intelligence Module inserted. 0x0245 Informational UPS: Intelligence Module removed. 0x0246 Informational UPS: Redundant Intelligence Module inserted. 0x0247 Informational UPS: Redundant Intelligence Module removed. 0x0248 Informational UPS: Number of Extended Run Frames increased. 0x0249 Informational UPS: Number of Extended Run Frames decreased. 0x024A Informational UPS: Number of System Power Supplies increased. 0x024B Informational UPS: Number of System Power Supplies decreased. 0x024C Informational UPS: External Switch Gear Q001 closed. 0x024D Informational UPS: External Switch Gear Q001 opened. 0x024E Informational UPS: External Switch Gear Q002 closed. 0x024F Informational UPS: External Switch Gear Q002 opened. 0x0250 Informational UPS: External Switch Gear Q003 closed. 0x0251 Informational UPS: External Switch Gear Q003 opened. 0x0252 Informational UPS: External Switch Gear Q004 closed. 0x0253 Informational UPS: External Switch Gear Q004 opened. 0x0254 Informational Configurable s for APC Network Management Card Page 16 of 22
Symmetra 3-Phase (continued) UPS: External Switch Gear failure. 0x0A01 Severe UPS: External Switch Gear failure cleared. 0x0A02 Informational UPS: External Transformer over temperature. 0x0A03 Severe UPS: External Transformer over temperature cleared. 0x0A04 Informational UPS: External DC Circuit Breaker tripped. 0x0A05 Severe UPS: External DC Circuit Breaker closed. 0x0A06 Informational UPS: System Power Supply failure. 0x0A07 Severe UPS: System Power Supply failure cleared. 0x0A08 Informational UPS: Battery Monitor Card failure. 0x0A09 Severe UPS: Battery Monitor Card failure cleared. 0x0A0A Informational UPS: Battery Monitor Card removed. 0x0A0B Severe UPS: Battery Monitor Card inserted. 0x0A0C Informational UPS: XR Communication Card failure. 0x0A0D Severe UPS: XR Communication Card failure cleared. 0x0A0E Informational UPS: XR Communication Card removed. 0x0A0F Severe UPS: XR Communication Card inserted. 0x0A10 Informational UPS: External Switch Gear Monitoring Card failure. 0x0A11 Severe UPS: External Switch Gear Monitoring Card failure cleared. 0x0A12 Informational UPS: External Switch Gear Monitoring Card removed. 0x0A13 Severe UPS: External Switch Gear Monitoring Card inserted. 0x0A14 Informational UPS: Internal DC Circuit Breaker tripped. 0x0A15 Severe UPS: Internal DC Circuit Breaker closed. 0x0A16 Informational UPS: Static Bypass Switch failure. 0x0A17 Severe UPS: Static Bypass Switch failure cleared. 0x0A18 Informational UPS: System EEProm removed. 0x0A19 Severe UPS: System EEProm inserted. 0x0A1A Informational UPS: System EEProm failure. 0x0A1B Severe UPS: System EEProm failure cleared. 0x0A1C Informational UPS: UPS is in forced bypassed. 0x0A1D Severe UPS: UPS returned from forced bypassed. 0x0A1E Informational UPS: Bit 15 of the second abnormal condition register set. 0x0A1F Severe UPS: Bit 15 of the second abnormal condition register cleared. 0x0A20 Informational UPS: Bit 16 of the second abnormal condition register set. 0x0A21 Severe UPS: Bit 16 of the second abnormal condition register cleared. 0x0A22 Informational UPS: Bit 17 of the second abnormal condition register set. 0x0A23 Severe UPS: Bit 17 of the second abnormal condition register cleared. 0x0A24 Informational UPS: Bit 18 of the second abnormal condition register set. 0x0A25 Severe UPS: Bit 18 of the second abnormal condition register cleared. 0x0A26 Informational UPS: Bit 19 of the second abnormal condition register set. 0x0A27 Severe UPS: Bit 19 of the second abnormal condition register cleared. 0x0A28 Informational UPS: Bit 20 of the second abnormal condition register set. 0x0A29 Severe Configurable s for APC Network Management Card Page 17 of 22
Symmetra 3-Phase (continued) UPS: Bit 20 of the second abnormal condition register cleared. 0x0A2A Informational UPS: Bit 21 of the second abnormal condition register set. 0x0A2B Severe UPS: Bit 21 of the second abnormal condition register cleared. 0x0A2C Informational UPS: Bit 22 of the second abnormal condition register set. 0x0A2D Severe UPS: Bit 22 of the second abnormal condition register cleared. 0x0A2E Informational UPS: Bit 23 of the second abnormal condition register set. 0x0A2F Severe UPS: Bit 23 of the second abnormal condition register cleared. 0x0A30 Informational UPS: Bit 24 of the second abnormal condition register set. 0x0A31 Severe UPS: Bit 24 of the second abnormal condition register cleared. 0x0A32 Informational UPS: Bit 25 of the second abnormal condition register set. 0x0A33 Severe UPS: Bit 25 of the second abnormal condition register cleared. 0x0A34 Informational UPS: Bit 26 of the second abnormal condition register set. 0x0A35 Severe UPS: Bit 26 of the second abnormal condition register cleared. 0x0A36 Informational UPS: Bit 27 of the second abnormal condition register set. 0x0A37 Severe UPS: Bit 27 of the second abnormal condition register cleared. 0x0A38 Informational UPS: Bit 28 of the second abnormal condition register set. 0x0A39 Severe UPS: Bit 28 of the second abnormal condition register cleared. 0x0A3A Informational UPS: Bit 29 of the second abnormal condition register set. 0x0A3B Severe UPS: Bit 29 of the second abnormal condition register cleared. 0x0A3C Informational UPS: Bit 30 of the second abnormal condition register set. 0x0A3D Severe UPS: Bit 30 of the second abnormal condition register cleared. 0x0A3E Informational UPS: Bit 31 of the second abnormal condition register set. 0x0A3F Severe UPS: Bit 31 of the second abnormal condition register cleared. 0x0A40 Informational UPS: Bit 32 of the second abnormal condition register set. 0x0A41 Severe UPS: Bit 32 of the second abnormal condition register cleared. 0x0A42 Informational UPS: Bit 33 of the second abnormal condition register set. 0x0A43 Severe UPS: Bit 33 of the second abnormal condition register cleared. 0x0A44 Informational UPS: Bit 34 of the second abnormal condition register set. 0x0A45 Severe UPS: Bit 34 of the second abnormal condition register cleared. 0x0A46 Informational UPS: Bit 35 of the second abnormal condition register set. 0x0A47 Severe UPS: Bit 35 of the second abnormal condition register cleared. 0x0A48 Informational UPS: Bit 36 of the second abnormal condition register set. 0x0A49 Severe UPS: Bit 36 of the second abnormal condition register cleared. 0x0A4A Informational UPS: Bit 37 of the second abnormal condition register set. 0x0A4B Severe UPS: Bit 37 of the second abnormal condition register cleared. 0x0A4C Informational UPS: Bit 38 of the second abnormal condition register set. 0x0A4D Severe UPS: Bit 38 of the second abnormal condition register cleared. 0x0A4E Informational UPS: Bit 39 of the second abnormal condition register set. 0x0A4F Severe UPS: Bit 39 of the second abnormal condition register cleared. 0x0A50 Informational UPS: Bit 40 of the second abnormal condition register set. 0x0A51 Severe UPS: Bit 40 of the second abnormal condition register cleared. 0x0A52 Informational Configurable s for APC Network Management Card Page 18 of 22
Symmetra 3-Phase (continued) UPS: Bit 41 of the second abnormal condition register set. 0x0A53 Severe UPS: Bit 41 of the second abnormal condition register cleared. 0x0A54 Informational UPS: Bit 42 of the second abnormal condition register set. 0x0A55 Severe UPS: Bit 42 of the second abnormal condition register cleared. 0x0A56 Informational UPS: Bit 43 of the second abnormal condition register set. 0x0A57 Severe UPS: Bit 43 of the second abnormal condition register cleared. 0x0A58 Informational UPS: Bit 44 of the second abnormal condition register set. 0x0A59 Severe UPS: Bit 44 of the second abnormal condition register cleared. 0x0A5A Informational UPS: Bit 45 of the second abnormal condition register set. 0x0A5B Severe UPS: Bit 45 of the second abnormal condition register cleared. 0x0A5C Informational UPS: Bit 46 of the second abnormal condition register set. 0x0A5D Severe UPS: Bit 46 of the second abnormal condition register cleared. 0x0A5E Informational UPS: Bit 47 of the second abnormal condition register set. 0x0A5F Severe UPS: Bit 47 of the second abnormal condition register cleared. 0x0A60 Informational UPS: Bit 48 of the second abnormal condition register set. 0x0A61 Severe UPS: Bit 48 of the second abnormal condition register cleared. 0x0A62 Informational UPS: Bit 49 of the second abnormal condition register set. 0x0A63 Severe UPS: Bit 49 of the second abnormal condition register cleared. 0x0A64 Informational UPS: Bit 50 of the second abnormal condition register set. 0x0A65 Severe UPS: Bit 50 of the second abnormal condition register cleared. 0x0A66 Informational UPS: Bit 51 of the second abnormal condition register set. 0x0A67 Severe UPS: Bit 51 of the second abnormal condition register cleared. 0x0A68 Informational UPS: Bit 52 of the second abnormal condition register set. 0x0A69 Severe UPS: Bit 52 of the second abnormal condition register cleared. 0x0A6A Informational UPS: Bit 53 of the second abnormal condition register set. 0x0A6B Severe UPS: Bit 53 of the second abnormal condition register cleared. 0x0A6C Informational UPS: Bit 54 of the second abnormal condition register set. 0x0A6D Severe UPS: Bit 54 of the second abnormal condition register cleared. 0x0A6E Informational UPS: Bit 55 of the second abnormal condition register set. 0x0A6F Severe UPS: Bit 55 of the second abnormal condition register cleared. 0x0A70 Informational UPS: Bit 56 of the second abnormal condition register set. 0x0A71 Severe UPS: Bit 56 of the second abnormal condition register cleared. 0x0A72 Informational UPS: Bit 57 of the second abnormal condition register set. 0x0A73 Severe UPS: Bit 57 of the second abnormal condition register cleared. 0x0A74 Informational UPS: Bit 58 of the second abnormal condition register set. 0x0A75 Severe UPS: Bit 58 of the second abnormal condition register cleared. 0x0A76 Informational UPS: Bit 59 of the second abnormal condition register set. 0x0A77 Severe UPS: Bit 59 of the second abnormal condition register cleared. 0x0A78 Informational UPS: Bit 60 of the second abnormal condition register set. 0x0A79 Severe UPS: Bit 60 of the second abnormal condition register cleared. 0x0A7A Informational UPS: Bit 61 of the second abnormal condition register set. 0x0A7B Severe Configurable s for APC Network Management Card Page 19 of 22
Symmetra 3-Phase (continued) UPS: Bit 61 of the second abnormal condition register cleared. 0x0A7C Informational UPS: Bit 62 of the second abnormal condition register set. 0x0A7D Severe UPS: Bit 62 of the second abnormal condition register cleared. 0x0A7E Informational UPS: Bit 63 of the second abnormal condition register set. 0x0A7F Severe UPS: Bit 63 of the second abnormal condition register cleared. 0x0A80 Informational Configurable s for APC Network Management Card Page 20 of 22
Environmental Monitor Environment: Contact 1 fault. 0x0301 Severe Environment: Contact 1 fault cleared. 0x0302 Informational Environment: Contact 2 fault. 0x0303 Severe Environment: Contact 2 fault cleared. 0x0304 Informational Environment: Contact 3 fault. 0x0305 Severe Environment: Contact 3 fault cleared. 0x0306 Informational Environment: Contact 4 fault. 0x0307 Severe Environment: Contact 4 fault cleared. 0x0308 Informational Environment: Low temperature threshold violation on probe 1. 0x0309 Severe Environment: Low temperature threshold violation on probe 1 cleared. 0x030A Informational Environment: High temperature threshold violation on probe 1. 0x030B Severe Environment: High temperature threshold violation on probe 1 cleared. 0x030C Informational Environment: Low humidity threshold violation on probe 1. 0x030D Severe Environment: Low humidity threshold violation on probe 1 cleared. 0x030E Informational Environment: High humidity threshold violation on probe 1. 0x030F Severe Environment: High humidity threshold violation on probe 1 cleared. 0x0310 Informational Environment: Low temperature threshold violation on probe 2. 0x0311 Severe Environment: Low temperature threshold violation on probe 2 cleared. 0x0312 Informational Environment: High temperature threshold violation on probe 2. 0x0313 Severe Environment: High temperature threshold violation on probe 2 cleared. 0x0314 Informational Environment: Low humidity threshold violation on probe 2. 0x0315 Severe Environment: Low humidity threshold violation on probe 2 cleared. 0x0316 Informational Environment: High humidity threshold violation on probe 2. 0x0317 Severe Environment: High humidity threshold violation on probe 2 cleared. 0x0318 Informational Environment: Communications established. 0x0319 Informational Environment: Communications lost. 0x031A Severe Environment: Integrated contact fault. 0x031B Severe Environment: Integrated contact fault cleared. 0x031C Informational Environment: Low temperature threshold violation on integrated probe. 0x031D Severe Environment: Low temperature threshold violation on integrated probe 0x031E Informational cleared. Environment: High temperature threshold violation on integrated probe. 0x031F Severe Environment: High temperature threshold violation on integrated probe 0x0320 Informational cleared. Environment: Low humidity threshold violation on integrated probe. 0x0321 Severe Environment: Low humidity threshold violation on integrated probe cleared. 0x0322 Informational Environment: High humidity threshold violation on integrated probe. 0x0323 Severe Environment: High humidity threshold violation on integrated probe cleared. 0x0324 Informational Environment: Integrated relay output fault. 0x0325 Warning Environment: Integrated relay output fault cleared. 0x0326 Warning Configurable s for APC Network Management Card Page 21 of 22