PowerNet SNMP Manager
|
|
|
- Anne Baldwin
- 9 years ago
- Views:
Transcription
1 PowerNet SNMP Manager for ManageWise User s Guide
2 2 PowerNet SNMP Manager for ManageWise - User s Guide 2 POWERNET MANAGER LICENSE STATEMENT The PowerNet Manager software is protected by both United States copyright law and international treaty provisions. Therefore, you must treat this software just like a book, with the following exception: American Power Conversion (APC) Corporation authorizes you to make archival copies of the software for the sole purpose of backing up our software and protecting your investment from loss. By saying just like a book, APC means, for example, that this software may be used by any number of people and may be freely moved from one computer location to another, as long as there is no possibility of it being used in one location while it is also being used in another. Just as a book cannot be read by two different people in two different places at the same time, neither can the software be used by two different people in two different places at the same time (unless, of course, APC s copyright has been violated). In addition, by using this package, you agree not to reverse engineer, reverse assemble, or reverse compile the software. Limited Warranty With respect to the physical diskette and physical material enclosed herein, APC warrants the same to be free of defects in materials and workmanship for a period of 60 days from the date of purchase. In the event of notification within the warranty period of defects in material or workmanship, APC will replace the defective diskette or material. If you need to return a product call the APC customer service department to obtain a Return Material Authorization (RMA) number. The remedy for breach of this warranty shall be limited to replacement and shall not encompass any other damages, including but not limited to loss of profit, and special, incidental, consequential or other similar claims. APC SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SOFTWARE, INCLUDING THE DISKETTES, DOCUMENTATION, AND CABLES. In no event shall APC be liable for any loss of profit or other commercial damage, including but not limited to special, incidental, consequential or other damages. Governing Law This statement shall be construed, interpreted and governed by the laws of the State of Rhode Island. LICENSES & TRADEMARKS APC, SNMP Adapter, PowerNet, PowerChute, Smart-UPS, v/s, Back-UPS Pro, Back-UPS, Matrix-UPS, Measure-UPS, SmartCell, SmartBoost, Symmetra, and Power Array are trademarks or registered trademarks of American Power Conversion Corporation. All other trademarks, product and corporate names are the property of their respective owners and used here for informational purposes only. Copyright American Power Conversion Corporation, All Rights Reserved. Reproduction in whole or in part without permission is prohibited. American Power Conversion Corporation APC Corporate APC Europe APC Ireland APC Japan P.O. Box 278 BR Gotanda 7th Floor 132 Fairgrounds Road 4 Rue St. Claire Deville Ballybrit Industrial Estates Nishi-gotanda West Kingston, RI Lognes F Galway Shinagawa-ku United States of America France Ireland Tokyo 141 Japan Toll Free: Toll Free: Toll Free: Free Dial: Telephone: Telephone: Telephone: Telephone: (81) (3) Fax: Fax: Fax: Fax: (81) (3) August, 1999 Online Version 1.3
3 3 PowerNet SNMP Manager for ManageWise - User s Guide 3 Contents About This Guide 5 Associated Documents... 5 How to Register Your Product... 5 Abbreviations... 5 APC Worldwide Support... 6 Chapter 1: PowerNet Manager Functions 7 To Monitor UPS Status and Power Quality... 7 To Control UPS Output Power... 7 To Test UPS Operation... 7 To Configure SNMP Agent and UPS Operating Parameters... 7 Chapter 2: How to Launch PowerNet Manager 8 Launch Procedure... 8 Discovery and APCUPS.INI How to Select a Maxi-Adapter UPS Network Errors Chapter 3: Main Screen 12 Menu Bar UPS Model Identification PowerNet Manager Status Line Tool Bar Polling Indicator Host Name/Address Access-Level Identification Chapter 4: Status Indicators 16 Line-Status Icons Load Icons Communication Icons Composite Status Indicator Error Message Screens... 23
4 4 PowerNet SNMP Manager for ManageWise - User s Guide 4 Chapter 5: Tool Bar Icons 24 Voltage Graph Window UPS Load Window Power Data Window UPS Batteries Window UPS Diagnostics Window Measure-UPS Window Chapter 6: How to Configure a UPS 33 SNMP Agent Parameters Dialog Box UPS Identification Parameters Dialog Box UPS Operating Parameters Dialog Box Reset UPS Parameters Dialog Box Site-Specific Notes Dialog Box Chapter 7: How to Control a UPS 43 Activate UPS Alarm Reboot the Attached Equipment Enter Sleep Mode Turn UPS Off and On Control Bypass Mode for a UPS Chapter 8: How to Test a UPS 47 Perform a UPS Self-Test Perform a UPS Runtime Calibration Simulate a Power Failure Index 49
5 5 PowerNet SNMP Manager for ManageWise - User s Guide 5 About This Guide This guide contains information about how to use American Power Conversion s (APC s) PowerNet Manager to manage (monitor, control, configure, and test) APC UPS systems. Associated Documents This guide explains how to use the PowerNet Manager application only. For information about installing PowerNet Manager, see your PowerNet Manager - Installation Guide; for information about your operating system, see the documentation for your operating system. Not all PowerNet Manager features are available with all APC UPS systems, PowerNet Adapters and PowerNet Agents. Refer to your APC UPS Owner s/user s Manual, PowerNet Adapter - User s Guide or PowerNet Agent - User s Guide for operational information about your UPS, Adapter or Agent. How to Register Your Product Please fill out and return the enclosed warranty card. This card allows you to provide us with feedback on how we can refine our products, and enables us to notify you about product updates and changes. Abbreviations APC refers to American Power Conversion; EEPROM refers to Electrically Erasable Programmable Read Only Memory; IP refers to internet protocol; NMS refers to network management station; SNMP refers to simple network management protocol; UPS refers to Uninterruptible Power Supply.
6 6 PowerNet SNMP Manager for ManageWise - User s Guide 6 APC Worldwide Support Technical support for this or any other APC product is available at no charge. You can contact APC Technical Support in any of the following ways: Use an APC web site. (Corporate Headquarters) Connect by links to APC web pages for specific countries and regions (North America, Japan, China, Korea, International, Latin America, France, Germany, Australia, Southeast Asia, and India), each of which provides technical support information. Submit technical support requests. Contact the APC representative or other distributor from whom you purchased your UPS or APC software application for information on how to obtain local technical support. Contact a local or regional APC Technical Support Center by telephone or . For addresses and local, country-specific, technical support telephone numbers worldwide, follow the links for Service and Support and Contact APC from the home page of APC s corporate web site, For addresses and technical support telephone numbers of major APC regional technical support centers, use the following list: APC Headquarters (U.S. and Canada): Latin America: Europe, Middle East, Africa: (toll free) (United States) [email protected] (Ireland) [email protected] Japan: [email protected]
7 7 PowerNet SNMP Manager for ManageWise - User s Guide 7 Chapter 1: PowerNet Manager Functions This chapter provides a brief overview of how you can use PowerNet Manager to do the following major tasks: TO MONITOR UPS STATUS AND POWER QUALITY TO CONTROL UPS OUTPUT POWER TO TEST UPS OPERATION TO CONFIGURE SNMP AGENT AND UPS PARAMETERS To Monitor UPS Status and Power Quality You can use the PowerNet Manager main screen, and five graphical display windows accessible through the main screen, to view a wide range of information about the UPS, its batteries, attached equipment, and input and output voltages. A sixth window provides access to environmental data when a Measure-UPS or SmartSlot Measure-UPS II connects with the UPS. To Control UPS Output Power You can use PowerNet Manager to control the power to the equipment being supported by the UPS. For example, you can turn a UPS off, reboot equipment attached to the UPS, or put a UPS into two different sleep modes. To Test UPS Operation You can use PowerNet SNMP Manager to perform a UPS self-test or a runtime calibration, and to verify that the UPS and PowerNet SNMP Manager are communicating properly. See PERFORM A UPS RUNTIME CALIBRATION in CHAPTER 8 for important information about the use of runtime calibrations. To Configure SNMP Agent and UPS Operating Parameters You can use PowerNet Manager to define parameters that affect UPS and SNMP operation. For example, you can adjust how a UPS reacts to power fluctuations and failures, or you can define the network management stations (NMSs) you want to use as trap receivers.
8 8 PowerNet SNMP Manager for ManageWise - User s Guide 8 Chapter 2: How to Launch PowerNet Manager This chapter describes how to begin managing a UPS with PowerNet Manager. Launch Procedure To launch PowerNet Manager: 1) From the Program Manager, load ManageWise. 2) From the Open option in the File menu, select Internetwork Map: You can also use the Segment Map... option to launch PowerNet Manager. 3) When the Internet map is displayed, double-click on the APC UPS SYSTEMS icon:
9 9 PowerNet SNMP Manager for ManageWise - User s Guide 9 5) The APC UPS systems map will now appear. This map will contain a battery-type icon for each UPS attached to the network: If 10 UPSs were attached, 10 battery-type icons would appear in the map. In the example given here, only two UPSs are attached to the network: 6) Double-click on any APC map icon to open the main screen for the UPS: Before the main screen appears, you can get two dialog boxes: One dialog box appears if you need to select between two UPS units which connect to the network through a PowerNet Maxi-adapter (see HOW TO SELECT A MAXI-ADAPTER UPS below); The other appears if the SNMP agent cannot communicate with PowerNet Manager (see NETWORK ERRORS later in this chapter). Silcon UPSs and the Web/SNMP Management Card When you have a Silcon UPS as part of your system, clicking on the Silcon battery icon launches the Web/SNMP Management Card. (If you have other web-based management cards connected, clicking on the associated battery icon launches a Web browser.) Instead of managing the UPS through the PowerNet Manager main screen, you will automatically be connected to the Web connection for your Silcon UPS where you can manage UPS properties on-line. For more information on managing UPS properties through the Web/SNMP Management Card, see the documentation provided with your Silcon UPS or select Help on the navigation bar of the Web interface.
10 10 PowerNet SNMP Manager for ManageWise - User s Guide 10 Discovery and APCUPS.INI As shown in the APC UPS SYSTEMS map above, each icon has either a name, an IPX address (for a UPS which connects to the network through a PowerNet Agent running on a NetWare server), or an IP address (for a UPS which connects to the network through a PowerNet Adapter, or through a PowerNet Agent running on a non-netware server). The names and addresses are defined during the PowerNet Manager installation procedure (as described in the PowerNet SNMP Manager for ManageWise - Installation Instructions) and stored in the APCUPS.INI file. For the example APC UPS SYSTEMS map above, the file entries could look like this: ,private,user name,password Empty fields require a separation by commas. If the card is a web-based-only card and the you do not want to specify a username and password, the values might look like this: ,,, The APC Discovery program (apcdiscv.exe) inserts a record of the information stored in the APCUPS.INI file in the local map database. You can edit the APCUPS.INI file using any text editor to add (or remove) a networked UPS. Once you have edited the file, save it as a text file. Then close ManageWise and run Discovery (apcdiscv.exe), to reflect the changes in the local map database. How to Select a Maxi-Adapter UPS When you double-click an APC UPS icon that represents a PowerNet Maxi-adapter (AP9200, AP9201 and AP9203 Adapter models), this dialog box appears:
11 11 PowerNet SNMP Manager for ManageWise - User s Guide 11 Select the UPS you want to manage (select UPS 1 or UPS 2), then click OK. Network Errors Network error conditions can exist during two different situations: While attempting to launch PowerNet Manager. While using PowerNet Manager to monitor and control a UPS. In both cases, PowerNet Manager responds with the following dialog box: Click No, Exit PowerNet Manager to exit to the network map; click Yes, Keep Trying to continue attempts to establish (or reestablish) the link with the UPS. If the network error occurred while launching, the dialog box will remain displayed until you select an action. If the network error occurred while PowerNet Manager is linked with an SNMP agent, the dialog box remains until you select an action, or until communications with the SNMP agent is restored. In addition: The composite status indicator displays the following message: The four status icons report unknown status conditions: Utility Power Battery Load Communication All dials, controls and fields are disabled.
12 12 PowerNet SNMP Manager for ManageWise - User s Guide 12 Chapter 3: Main Screen The PowerNet Manager main screen has the following features which allow you to monitor, configure, control, and test a UPS: 1 MENU BAR 2 TOOL BAR 3 STATUS INDICATORS 4 UPS MODEL IDENTIFICATION 5 POWERNET MANAGER STATUS LINE 6 POLLING INDICATOR 7 HOST NAME/ADDRESS 8 ACCESS-LEVEL IDENTIFICATION
13 13 PowerNet SNMP Manager for ManageWise - User s Guide 13 Menu Bar The menu bar has seven options: File Menu A single option allows you can use to exit PowerNet Manager. You can also exit PowerNet Manager using Alt-F4. Edit Menu Allows you to use editing functions (Undo, Cut, Copy, Paste and Clear) when entering text in a dialog box. View Menu A single option allows you to enable or disable the display of the tool bar icons. See Chapter 5 for information on the windows you can access using the tool bar icons. Configuration Menu Allows you to modify SNMP agent, UPS identification, and UPS operating parameters, to record miscellaneous notes about the UPS, or to reset UPS parameters to factory-default settings. See CHAPTER 6 for more information on the Configuration menu. Control Menu Allows you to test the UPS alarm, reboot the devices attached to the UPS, put the UPS into sleep mode, turn off the UPS, or control the bypass mode for a Matrix-UPS or Symmetra Power Array. See CHAPTER 7 for more information about the Control menu. Diagnostics Menu Allows you to perform UPS self-tests, initiate runtime calibrations, or simulate power failures. See CHAPTER 8 for more information about the Diagnostics menu. Help Menu Allows you to access the online help, or PowerNet Manager s About display.
14 14 PowerNet SNMP Manager for ManageWise - User s Guide 14 Status Indicators The main screen has a composite status indicator and four status icons: The composite status indicator reports the overall status of the UPS, based on the operational conditions reflected by all four icons: Line status Battery status Load status Communication status See CHAPTER 4 for a complete description of the status indicators. When the UPS is on battery, a report about how long the UPS has been on battery appears to the right of the status icons. UPS Model Identification Identifies the type of UPS. PowerNet Manager Status Line Displays status messages about PowerNet Manager.
15 15 PowerNet SNMP Manager for ManageWise - User s Guide 15 Tool Bar The tool bar icons allow you to access windows which graphically display operational and environmental data: Voltage Graph Power Data UPS Battery UPS Load UPS Diagnostics Measure-UPS See CHAPTER 5 for a complete description of the tool bar icons and the associated windows. Polling Indicator When flashing, indicates PowerNet Manager is communicating with the UPS. Host Name/Address Identifies the SNMP agent s name, or network address (as shown), if the name is not known. Access-Level Identification Identifies the access level for the current user.
16 16 PowerNet SNMP Manager for ManageWise - User s Guide 16 Chapter 4: Status Indicators This chapter describes the following status indicators: INPUT-LINE ICONS BATTERY ICONS LOAD ICONS COMMUNICATION ICONS COMPOSITE STATUS INDICATOR Two error message screens can appear while using PowerNet Manager. The error message screens are described in the ERROR MESSAGE SCREENS section at the end of this chapter. Line-Status Icons Seven types of line status icons, shown below, report conditions relating to the incoming input voltage or voltage-related UPS operational states. INPUT-LINE OFF SLEEP BYPASS REBOOT SMARTBOOST/SMARTTRIM This icon indicates the SNMP agent cannot report status due to either a communication failure or the lack of data while PowerNet Manager is initializing a UPS connection.
17 17 PowerNet SNMP Manager for ManageWise - User s Guide 17 Input-Line Icons Two icons report on the status of the input voltage: The input voltage is within acceptable limits. The UPS is on battery due to an input power problem, or because it is executing a runtime calibration process. See PERFORM A UPS RUNTIME CALIBRATION in CHAPTER 8 for important information about the use of runtime calibrations. Sleep Icons You can use Put UPS to Sleep... in the Control menu to put the UPS into a sleep mode. Which icon appears depends on the sleep mode used: The UPS is sleeping for a defined period of time. The UPS is sleeping until the input voltage returns to acceptable limits. When the UPS is in sleep mode, it does not supply output power to its attached equipment. Reboot Icon The UPS is rebooting its attached equipment in response to using Reboot Load... in the Control menu. Off Icon
18 18 PowerNet SNMP Manager for ManageWise - User s Guide 18 The UPS is turned off, either manually, or in response to using Turn Off UPS... in the Control menu. Bypass Icon (Matrix-UPS and Symmetra Power Array Only) In bypass mode, a mode used for maintenance, the UPS cannot protect attached equipment from major power problems. A Matrix-UPS or Symmetra Power Array will automatically go into bypass mode when it detects certain types of internal failures. You can also manually place a Matrix-UPS or Symmetra Power Array into bypass mode using a bypass switch (at the rear panel of a Matrix-UPS, or front panel of a Symmetra Power Array) or by using Put UPS on Bypass in the Control menu. Caution: All maintenance activities must be completed before taking a UPS out of bypass mode. Either the switch at the UPS (switched bypass mode) or Put UPS on Bypass in the Control menu (software bypass mode) was used to put the UPS into bypass mode. The UPS is in bypass mode because of a hardware failure. Contact APC Technical Support, immediately, for corrective procedures. SmartBoost /SmartTrim Icons A Smart-UPS can increase (boost) or decrease (trim) the input voltage level without using battery power: Indicates the Smart-UPS is using SmartBoost: The UPS input voltage is at least as low as the Low Transfer Voltage, but not at least 12% (30% for a Smart-UPS 420 or Smart-UPS 620) lower than that Low Transfer Voltage value. If the input voltage goes higher than the Low Transfer Voltage value, the UPS resumes normal operation; If the input voltage goes at least 12% (30% for a Smart-UPS 420 or Smart-UPS 620) lower than the Low Transfer Voltage, the UPS will go on battery. Indicates the Smart-UPS is using SmartTrim: The UPS input voltage is at least as high as the High Transfer Voltage, but not at least 12% higher than that High Transfer Voltage value. If the input voltage goes lower than the High Transfer Voltage value, the UPS resumes normal operation; If the input voltage goes at least 12% higher than the High Transfer Voltage, the UPS will go on battery. Older Smart-UPS models do not have SmartTrim. See your Smart-UPS documentation for more detail. See the UPS Operating Parameters Dialog Box description (in CHAPTER 6) for
19 19 PowerNet SNMP Manager for ManageWise - User s Guide 19 information about how to define High and Low Transfer Voltage values. Battery Icons Three icons report on the UPS battery status: The UPS battery can support the attached equipment during a power failure. A low-battery condition exists and the UPS cannot use battery power to support its attached equipment if a power failure occurs. This icon appears during the following conditions: When the UPS completes a runtime calibration (the battery is deeply discharged during the calibration). See PERFORM A UPS RUNTIME CALIBRATION in CHAPTER 8 for important information about the use of runtime calibrations. When the Power Return Behavior parameter settings in the UPS Operating Parameters dialog box allow the UPS to come back on-line from a power failure before the UPS battery has recharged enough to support the attached equipment if another power failure occurs. For more information on the Power Return Behavior parameters, see UPS OPERATING PARAMETERS DIALOG BOX in CHAPTER 6. The SNMP agent cannot report the status because of either a communication failure, or the lack of available data while PowerNet Manager is initializing a UPS connection. Load Icons Three icons report on whether or not the UPS is within its normal, rated load tolerance: The load on the UPS from its attached equipment is within the rated load capacity for the UPS. The load on the UPS from its attached equipment exceeds the rated load capacity for the UPS. To correct, disconnect equipment from the UPS and perform a UPS self-test. If the UPS is still overloaded, contact APC Technical Support for help in correcting the problem. The SNMP agent cannot report the status because of either a communication failure, or the lack of available data while PowerNet Manager is initializing a UPS connection.
20 20 PowerNet SNMP Manager for ManageWise - User s Guide 20 Communication Icons Three icons report on the status of communication between the UPS and its SNMP Agent: The UPS and SNMP agent are communicating properly. A problem exists with the UPS-to-SNMP agent communications. The SNMP agent cannot report the status because of either a communication failure, or the lack of available data while PowerNet Manager is initializing a UPS connection. Composite Status Indicator The following is an alphabetical listing of messages the composite status indicator can display, along with brief descriptions, and recommended actions (where appropriate): A UPS internal fault has occurred. Contact APC Technical Support for corrective procedures. A UPS alarm test was initiated using Activate UPS Alarm in the Control menu. The battery is low, but acceptable input power is present. This message can appear at the end of a runtime calibration (a deep battery discharge is part of this UPS calibration process) or when the UPS comes back on line after supporting its attached equipment with battery power during an extended power failure. See PERFORM A UPS RUNTIME CALIBRATION in CHAPTER 8 for important information about the use of runtime calibrations. The UPS is on bypass due to detecting an internal hardware failure. Contact APC Technical Support for corrective procedures.
21 21 PowerNet SNMP Manager for ManageWise - User s Guide 21 The UPS battery, which has been supplying output power to the attached equipment, has reached its runtime shutoff point and acceptable input voltage remains unavailable. The SNMP agent has lost communication with the UPS. Check the UPS-to-agent cable connections. No response from the SNMP agent due to one of three possible causes: A loose network cable. Check and tighten all network connections. An incorrect community name. Check the SNMP agent s community name to make sure it matches the name specified by the NMS. The SNMP agent is no longer functioning. Reboot the agent: In most cases, this will solve the problem. The UPS is turned off, either manually, or in response to using Turn Off UPS... in the Control menu. The UPS is supplying battery power to attached equipment. The UPS is using the input voltage to generate the output voltage to its attached equipment. The UPS rated-load capacity is exceeded. Reduce the UPS load and perform a UPS self-test. If still overloaded, contact APC Technical Support for help in correcting the problem. The UPS is rebooting its attached equipment in response to using Reboot Load... in the Control menu. The UPS has determined the battery is no longer usable. If the battery is not user-replaceable, contact APC Technical Support.
22 22 PowerNet SNMP Manager for ManageWise - User s Guide 22 A runtime calibration has been initiated using Initiate Run Time Calibration in the Diagnostics menu. See PERFORM A UPS RUNTIME CALIBRATION in CHAPTER 8 for important information about the use of runtime calibrations. The UPS is undergoing a self-test, either initiated by the UPS, or in response to using Initiate UPS Self Test in the Diagnostics menu. The UPS is sleeping until input voltage returns to an acceptable level in response to using Put UPS to Sleep... in the Control menu. A test of the ability of the UPS to switch to battery in the event of a power failure has been initiated using Simulate Power Failure in the Diagnostics menu. The Smart-UPS is using SmartBoost to boost a low input voltage to an acceptable level. The Smart-UPS is using SmartTrim to reduce a high input voltage to an acceptable level. SmartTrim is not available on older Smart-UPS models. The Matrix-UPS or Symmetra Power Array is in bypass in response to using Put UPS On Bypass in the Control menu, or from the UPS front panel. The Matrix-UPS or Symmetra Power Array is in bypass in response to using the switch located at the UPS. The UPS is sleeping for a user-defined period of time in response to using Put UPS to Sleep... in the Control menu. Either PowerNet Manager is initializing contact with the UPS, or an error condition, which cannot be reported by another message, has occurred.
23 23 PowerNet SNMP Manager for ManageWise - User s Guide 23 Error Message Screens In addition to the Network Errors Encountered message screen (described in Chapter 2), two other error message screens can appear while you are using PowerNet Manager: Command failed - This screen appears when an attempt is made to execute a command to which the UPS cannot respond. Typically, this is due to a problem with the SNMP agent s community name: Set failed - This screen appears when an attempt is made to apply an incomplete or inaccurate value to a UPS or SNMP parameter: The set-failed message will also appear if the UPS uses a PowerNet Agent with a 5.x version of PowerChute plus, and you try to use the UPS Diagnostics window to change the self-test schedule. PowerChute plus 5.x applications have a feature which schedules self-tests, shutdowns, and runtime calibrations.
24 24 PowerNet SNMP Manager for ManageWise - User s Guide 24 Chapter 5: Tool Bar Icons The tool bar has six icons which, when clicked, open windows which display UPS operational, site power or environmental data, as follows: VOLTAGE GRAPH POWER DATA UPS BATTERIES UPS LOAD UPS DIAGNOSTICS MEASURE-UPS Voltage Graph Window The Voltage Graph and UPS Batteries windows are automatically displayed when PowerNet Manager begins monitoring a UPS. This icon opens the Voltage Graph window, if it is closed.
25 25 PowerNet SNMP Manager for ManageWise - User s Guide 25 Once PowerNet Manager begins monitoring a UPS, the Voltage Graph window continuously records the input and output voltages. However, only the last 12 hours of recorded voltages, from a single PowerNet Manager session, can be viewed using the Voltage Graph window. The Voltage Graph window has the following functional elements: GRAPH WINDOW AREA SCALE BUTTONS GRAPH POSITION SCROLL BARS CURRENT VOLTAGE REPORT LAST TRANSFER CAUSE MESSAGE LINE Graph Display Two lines appear in the graph display: A red line tracks the input voltage to the UPS; A green line tracks the UPS output voltage. The overall scale range for the graph data is Volts. How much of that scale is displayed depends on the settings of the zoom in/zoom out buttons and the graph positioning scroll bars. Scale Buttons Two buttons allow you to adjust the scale used by the graph display: Use this button to see a section of the displayed voltage range in more detail. Use this button to see a larger section of the displayed voltage. The graph can display 5V, 10V, 20V, 40V, 80V, 160V, or 320V high slices of the input/output voltage range. Graph Position Scroll Bars Two scroll bars allow you to position the voltage data within the display: The vertical position scroll bar, located to the left of the graph window, selects what part of the voltage range is displayed. The horizontal scroll bar, located below the graph window, selects what part of the running input/output voltage history is displayed. Current Voltage Report This area reports the current input and output voltage values.
26 26 PowerNet SNMP Manager for ManageWise - User s Guide 26 Last Transfer Cause Message Line This line, located just above the PowerNet Manager status line at the bottom of the window, identifies the cause of the last transfer to battery power by the UPS. The UPS can transfer to battery for any of the following reasons: High input line voltage (the input voltage level was too high to be safely used by the UPS for output power) Brownout (input voltage was present, but at a level that was too low to be used by the UPS for output power) Blackout (the input voltage was absent or almost absent) Small, momentary power sag (the input voltage decreased slightly for a short period of time) Small, momentary power spike (the input voltage increased slightly for a short period of time) Deep momentary power sag (the input voltage decreased significantly for a short period of time) Large momentary power spike (the input voltage increased significantly for a short period of time) An unrecorded event (the SNMP agent is unable to report why the last transfer occurred) UPS Load Window This icon opens this window: The UPS Load window has two dials: Power Load (% Volt-Amps): Displays the UPS load as a percentage of the maximum UPS load capacity (the higher the load, the less runtime available). Current (Amperes): Reports the current, in amperes, for Matrix-UPS and Symmetra Power Array models.
27 27 PowerNet SNMP Manager for ManageWise - User s Guide 27 Power Data Window This icon opens this window: The Power Data window provides information about the following input and output power categories: Now The input and output AC voltages Min The minimum input voltage detected since PowerNet Manager began monitoring the UPS Max The maximum input voltage detected since PowerNet Manager began monitoring the UPS Current The input and output current, in amperes Frequency The input and output voltage frequencies, in Hertz Phase The phase of the input and output voltages The current value is reported for Matrix-UPS and Symmetra Power Array models. Current values are N/A (not applicable) for other UPS models.
28 28 PowerNet SNMP Manager for ManageWise - User s Guide 28 UPS Batteries Window The UPS Batteries and Voltage Graph windows are automatically displayed when PowerNet Manager begins monitoring a UPS. This icon opens the UPS Batteries window, if it is closed: This UPS batteries window uses the following major functional elements to provide data about the battery: BATTERY CAPACITY (%) DIAL INTERNAL UPS TEMPERATURE (DEG C) DIAL STATUS BOX Battery Capacity (%) Dial This dial identifies what percentage (%) of the normal battery capacity is available. To perform a runtime calibration, the UPS battery capacity must be at 100%. See PERFORM A UPS RUNTIME CALIBRATION in CHAPTER 8 for important information about the use of runtime calibrations.
29 29 PowerNet SNMP Manager for ManageWise - User s Guide 29 Internal UPS Temperature (deg C) Dial This dial identifies the temperature inside the UPS casing,, in degrees Celsius. Temperature readings will vary depending on battery conditions: If the battery is fully charged, the UPS temperature will be around 40 C (104 F). If the battery is charging heavily, the UPS temperature can be as high as 50 C (122 F). Following a heavy-load discharge, the UPS temperature can be as high as 65 C (149 F). Caution: A temperature higher than 75 C (167 F) indicates a UPS malfunction, such as a failed fan or blocked ventilation. Correct the condition immediately to avoid damage to the UPS or its attached equipment. Call APC Technical Support if the problem persists. Status Box The status box has the following elements: Runtime Remaining identifies how long the UPS can support its load on battery power. The greater the UPS load, the lower the runtime available. Battery Last Replaced On field allows you to track battery changes: Type the date in mm/dd/yy format and click Apply. Total Battery Pack(s) and Bad Battery Pack(s) fields, which are only active when the UPS is a Matrix-UPS, Symmetra Power Array, or a Smart-UPS XL (UPS models that can have multiple attached external batteries), identify how many battery packs are attached, and how many packs need replacing.
30 30 PowerNet SNMP Manager for ManageWise - User s Guide 30 UPS Diagnostics Window This icon opens this window: This UPS Diagnostics window reports the status of the last self-test and runtime calibration and allows you to schedule self-tests. When the UPS uses a PowerNet Agent, the last self-test and runtime calibration reports include the dates each was performed. The example above shows the reports given by a PowerNet Adapter or Web/SNMP Management Card. See PERFORM A UPS RUNTIME CALIBRATION in CHAPTER 8 for important information about the use of runtime calibrations. To change when the UPS performs a self-test: 1) Select when you want self-tests to occur: Never Disable UPS-initiated self-tests. At UPS Turn On Perform a self-test whenever the UPS is turned on. Weekly Perform a self-test on a weekly basis. Bi-Weekly Perform a self-test every two weeks. The Bi-Weekly setting is not available when the UPS uses a PowerNet Agent. In addition, if the UPS connects with a machine that uses a 5.x version of PowerChute plus to monitor that UPS, you can use PowerChute plus to schedule self-tests, but you cannot use the UPS Diagnostics window to change the self-test schedule. 2) Click Apply. APC recommends you perform self-tests on a weekly basis to ensure the UPS is free of faults that can be detected by a self-test.
31 31 PowerNet SNMP Manager for ManageWise - User s Guide 31 Measure-UPS Window A Measure-UPS is an environment and contact status monitoring instrument that continuously measures ambient temperature, humidity and external contact closures from sources, including smoke, heat, water, and motion detectors. When a Measure-UPS is used with a UPS and PowerNet Manager, it forms a complete remote, environmental- and physical-monitoring system. Three Measure-UPS models are available: AP9503 Measure-UPS - An external, self-contained model which can use a temperature probe or a temperature and humidity probe. The AP9503 cannot be used with a UPS that has an Adapter installed in its SmartSlot. AP9612T SmartSlot Measure-UPS II - Has a temperature probe only, and mounts in a UPS SmartSlot, or in a SmartSlot expansion chassis. AP9612TH SmartSlot Measure-UPS II - Has a temperature and humidity probe, and mounts in a UPS SmartSlot, or in a SmartSlot expansion chassis. If a Measure-UPS is attached, this icon opens this window:
32 32 PowerNet SNMP Manager for ManageWise - User s Guide 32 The Measure-UPS window uses the following elements to provide environmental data: AMBIENT TEMPERATURE (DEG C) DIAL RELATIVE HUMIDITY (%) DIAL CONTACT DEFINITIONS Ambient Temperature (deg C) Dial A Measure-UPS monitors the temperature of an environment in Celsius. If a Fahrenheit temperature reading is needed, you can use the following formula to convert the Ambient Temperature (deg C) dial s Celsius reading: F = (9C)/ (where F equals Fahrenheit and C equals Celsius) Relative Humidity (%) Dial When a Measure-UPS uses a probe which can monitor humidity, this dial reports the relative humidity as a percentage (%) value. This dial is inactive when a Measure-UPS uses a probe which can only monitor temperature. Contact Definitions A Measure-UPS has four contact inputs. Each contact allows a Measure-UPS to monitor an external alarm condition. Each can be configured as either normally open or normally closed. Contacts do not come with a Measure-UPS, but are ordered separately. To set a contact as either normally open or normally closed, see the documentation which came with your Measure-UPS or SmartSlot Measure- UPS II. The Measure-UPS window has a set of identical elements for each of four contacts: A text box which allows you to use up to 15 characters to identify a contact s function: Type in the identification and click Apply. A box which identifies the contact s normal setting (Open or Closed). A status box which reports whether the contact senses a Faulted or Not Faulted condition. For example, you can use a Measure-UPS contact to monitor the security of a wiring closet by setting the contact to sense whether the closet door is normally open or normally closed. If the contact is set for Closed, and the closet door is opened, the Measure-UPS window reports that the door is open by reporting a Faulted condition for that contact.
33 33 PowerNet SNMP Manager for ManageWise - User s Guide 33 Chapter 6: How to Configure a UPS The Configuration menu options allow access to dialog boxes you can use to tailor various UPS and SNMP Agent parameters, reset UPS parameters to their factory-default values or record notes and observations: SNMP AGENT PARAMETERS DIALOG BOX UPS IDENTIFICATION PARAMETERS DIALOG BOX UPS OPERATING PARAMETERS DIALOG BOX RESET UPS PARAMETERS DIALOG BOX When the UPS uses a PowerNet Agent, the Reset UPS Parameters to Factory Defaults... option in the Configuration menu is inactive. SITE-SPECIFIC NOTES DIALOG BOX The configuration values used in this chapter are not specific to any particular UPS. These values can vary, primarily due to differences in the operating voltages used by different UPS models. Refer to your UPS documentation for details about your specific UPS.
34 34 PowerNet SNMP Manager for ManageWise - User s Guide 34 SNMP Agent Parameters Dialog Box Selecting Modify SNMP Agent Parameters... opens this dialog box: This dialog box has the following sections: TRAP RECEIVERS PARAMETERS MIB-II AGENT IDENTIFICATION PARAMETERS The Trap Receivers values can be changed only when the UPS uses a PowerNet Adapter. Trap Receiver Parameters When the UPS uses a PowerNet Adapter, this section allows you to define up to four trap receivers. Each trap receiver definition has the following fields: Field None of the Trap Receiver parameters can be modified for PowerNet Agents. Description Receiver IP Address Community Name Trap Type(s) You must use this field to identify the IP address of a specific NMS you want to use as a trap receiver. The default, , indicates the trap receiver is undefined, and no traps will be sent. Defines an up to eight-character community name for traps sent to the NMS defined in the Receiver IP Address field. Typically, this value remains in its default setting (public). Defines whether the PowerNet Adapter sends PowerNet MIB Only traps, RFC1628 Only traps, or Both, to the defined NMS.
35 35 PowerNet SNMP Manager for ManageWise - User s Guide 35 MIB-II Agent Identification Parameters This section allows you to specify the sysname (System Name), syslocation (Location) and syscontact (Contact) MIB-II variables for the SNMP agent. The Site-Specific Notes dialog box has an identical MIB-II Agent Identification section. Changes made to MIB-II information in either dialog box are reflected in both. Modifying Parameters To change any SNMP agent parameter except for Trap Type(s), type in the new definition and click Apply; to change a Trap Type(s) setting, select the trap type (PowerNet Only, RFC1628 Only, or Both) from the drop-down menu and click Apply. In both cases, you must click Apply, before using OK to exit the dialog box, to save the change. UPS Identification Parameters Dialog Box Selecting Modify UPS Identification Parameters... opens this dialog box:
36 36 PowerNet SNMP Manager for ManageWise - User s Guide 36 This dialog box has the following sections: UPS IDENTIFICATION BOX UPS NAME PARAMETER ATTACHED DEVICE PARAMETERS UPS Identification Box This box contains information which is set at the factory and cannot change: UPS Model (UPS model name) Rev. (UPS firmware revision) Mfg. on (date the UPS finished the manufacturing process) Serial # (UPS serial number) UPS Name Parameter This parameter allows you to use up to eight characters to define a name for the UPS. Attached Devices Parameters This section allows you to identify up to four devices that connect to the UPS, and to specify the power requirements for each device: Use the left-hand field to define the device name. Use the right-hand field to identify the power requirements for the device. The Total VA field is automatically calculated based on the power requirements defined for each device. The value is provided as a convenience only, to help a user make sure the attached equipment does not exceed the load capacity of the UPS; PowerNet Manager does not use this value. Modifying Parameters To change the UPS Name or Attached Devices values, type in the new value and click Apply before using OK to exit the dialog box.
37 37 PowerNet SNMP Manager for ManageWise - User s Guide 37 UPS Operating Parameters Dialog Box Selecting Modify UPS Operating Parameters... opens this dialog box: The drop-down menus are disabled for a Smart-UPS that has rear-panel dip-switches and does not have all switches set to 1, or when the SNMP agent used by the UPS to connect to the network has its write community name inaccurately recorded at the PowerNet Manager NMS. This dialog box has the following sections: ON-LINE BEHAVIOR PARAMETERS ON-BATTERY BEHAVIOR PARAMETERS POWER RETURN BEHAVIOR PARAMETERS FRONT-PANEL ACCESS PASSWORD PARAMETER Some parameter values depend on the operating voltage used by the UPS. See your UPS documentation for information about the settings available for your UPS.
38 38 PowerNet SNMP Manager for ManageWise - User s Guide 38 Front-Panel Password Parameter This parameter (located in the Other section of the dialog box) applies to a Matrix-UPS or Symmetra Power Array only. It lets you define a 4-character password that helps prevent unauthorized users from using the UPS front panel to reprogram the UPS. To define a password, type in the 4-character password and click Apply before using OK to exit the dialog box. On-Line Behavior Parameters This section s parameters allow you to affect the on-line operation of the UPS. Parameter settings can vary, depending on the operating voltage a UPS uses. Parameter Rated Output Voltage High Transfer Voltage Description Defines the output voltage the UPS passes on to its attached equipment when on battery. For a 120 VAC UPS, this listed value cannot change from 115 volts. For a UPS model with a variable output, this value can be changed. Defines the upper limit for on-line operation: if the input voltage equals or exceeds this value, the UPS either goes on battery or, if the UPS is a newer model Smart-UPS, begins using SmartTrim. The settings for a 120-VAC Smart-UPS are 129, 132, 135, 138. A Smart-UPS which has SmartTrim can lower the input voltage to a level acceptable for output to the attached equipment without requiring the UPS to go on battery. Low Transfer Voltage Defines the lower limit for on-line operation: if the input voltage is less than, or equal to, this value, the UPS either goes on battery or, if the UPS is a Smart-UPS, begins using its SmartBoost feature. The settings for a 120-VAC Smart-UPS are 97, 100, 103, 115. The Low Transfer Voltage setting cannot be changed for a Matrix-UPS or a Symmetra Power Array. For a Smart-UPS, SmartBoost allows the UPS to raise the input voltage to a level acceptable for output to the attached equipment without requiring the UPS to go on battery. Sensitivity This parameter defines how sensitive the UPS will be to distortion in the input voltage before it switches to battery. The settings for a 120-VAC Smart-UPS are Low, Medium and High. Matrix-UPS and Symmetra Power Array models also have an Automatic setting.
39 39 PowerNet SNMP Manager for ManageWise - User s Guide 39 On-Line Behavior Parameters Special Considerations The following should be taken into account when selecting settings for the High Transfer Voltage, Low Transfer Voltage and Sensitivity parameters: The High Transfer Voltage and Low Transfer Voltage values are best used in areas with chronically high or chronically low voltages. With attached equipment which can tolerate a wide voltage range you can increase the High Transfer Voltage setting and decrease the Low Transfer Voltage setting to create a wider voltage window for the UPS, thus reducing the number of times the UPS must run on battery to maintain acceptable voltages. The primary benefit of a wider voltage window is the UPS battery gets used less than if it has to respond to frequent high or low voltage conditions. This keeps the battery at a higher capacity for more serious power fault conditions. If the equipment attached to the UPS is particularly sensitive to power disturbances, the Sensitivity setting should be High (its factory-default setting). If the UPS frequently transfers to battery due to the High setting for Sensitivity, setting the value to Low or Medium may solve the problem. On-Battery Behavior Parameters This section s parameters allow you to affect the on-battery operation of the UPS. Parameter Audible Alarm Description Defines when the UPS will generate an alarm: Never Disables alarms. At Low Battery When a low-battery condition occurs. On Battery When a power failure occurs. On Battery +30s When a power failure that lasts 30 seconds occurs. If power failures occur frequently, selecting On Battery +30s will reduce the number of alarms. Low Battery Runtime UPS Turn Off Delay Allows you to define when a low-battery condition will occur: How many seconds of runtime will remain before the battery becomes unable to provide power to the attached equipment. The selections are 120, 300, 420, and 600. Allows you to set the time difference, in seconds, between when the UPS is commanded to turn off and when it actually turns off its outlets. This allows the attached equipment to perform an orderly shutdown before the UPS turns off power. The selections are 20, 180, 300, and 600.
40 40 PowerNet SNMP Manager for ManageWise - User s Guide 40 Power Return Behavior Parameters This section s parameters allow you to affect how a UPS which shut down due to an extended power failure responds when the input voltage returns to an acceptable range. Parameter (Battery Capacity) Description Defines the minimum percentage of full battery capacity the UPS must have available before the UPS can return from a low-battery shutdown condition when the input voltage returns to an acceptable voltage range: The UPS cannot supply power to its attached equipment until the battery capacity equals or exceeds this parameter s value. The available values depend on the UPS model. A setting of 0 (the default) ensures the UPS goes back on line almost immediately (once the delay specified by the Power Return Delay (Time) value expires). However, with the setting set at 0, it is possible that if another power failure occurs soon after the UPS goes back on line, the UPS may not have enough battery capacity available to allow its attached equipment enough time for an orderly shutdown before the UPS must turn off. Delay (Time) Defines a delay, in seconds, to occur between the time the UPS battery capacity equals or exceeds the value defined by the Power Return (Battery Capacity) parameter (described below) and the time the UPS provides power to its attached equipment. The selections are 0, 60, 180, and 300. The Power Return Delay (Time) value is also used during a reboot (see REBOOT ATTACHED EQUIPMENT in CHAPTER 7) and before the UPS wakes from a timed-sleep (see ENTER SLEEP MODE in CHAPTER 7). Modifying Parameters Except for the password parameter (described separately), all parameters in the UPS operating parameters dialog box use drop-down menus: Select the new setting from the menu and click Apply, to save the change, before using OK to exit the dialog box.
41 41 PowerNet SNMP Manager for ManageWise - User s Guide 41 Reset UPS Parameters Dialog Box Selecting Reset UPS Parameters to Factory Defaults..., an option available only when the UPS uses a PowerNet Adapter, opens this confirmation box: Clicking Yes resets all the UPS operating parameters (except Front Panel Access Password, which has no default value) to their factory-default settings: Factory-default values are stored in the UPS EEPROM. Most of these values depend on the UPS model and its operating voltage. Audible Alarm High Transfer Voltage Low Battery Runtime Low Transfer Voltage Power Return Delay (Capacity) Power Return Delay (Time) Rated Output Voltage Sensitivity UPS Name UPS Turn Off Delay Also, the self-test scheduling setting in the UPS Diagnostics window, and the Battery Last Replaced On date in the UPS Batteries window, are reset to their EEPROM-defined values.
42 42 PowerNet SNMP Manager for ManageWise - User s Guide 42 Site-Specific Notes Dialog Box Selecting Site-Specific Notes... opens this dialog box: A large text box provides space for recording notes about the UPS; A MIB-II Agent Identification section allows you to specify System Name, Location and Contact (MIB-II sysname, syslocation and syscontact variables) values for the SNMP agent. To save changes, click Apply before using OK to exit the dialog box. The SNMP Agent Parameters dialog box has an identical MIB-II Agent Identification section. Changes made to this MIB-II information in either dialog box is reflected in both boxes.
43 43 PowerNet SNMP Manager for ManageWise - User s Guide 43 Chapter 7: How to Control a UPS The Control menu options allow you to do the following: ACTIVATE UPS ALARM REBOOT THE ATTACHED EQUIPMENT ENTER SLEEP MODE TURN UPS OFF AND ON CONTROL BYPASS MODE FOR A UPS When the UPS uses a PowerNet Agent, you cannot use Reboot Load... or Put UPS to Sleep... In addition, although you can use Turn Off UPS..., you cannot use PowerNet Manager to turn the UPS back on: The UPS will need to be turned on using its on/off switch. Activate UPS Alarm Selecting Activate UPS Alarm causes the following to occur: The UPS emits an audible alarm (beeps) and briefly turns on its front panel lights (a Matrix-UPS has no lights; a Symmetra Power Array has no lights and does not beep). The composite status indicator briefly displays this message:
44 44 PowerNet SNMP Manager for ManageWise - User s Guide 44 Reboot the Attached Equipment Selecting Reboot Load... opens this confirmation box: Reboot Load... is unavailable when the UPS uses a PowerNet Agent. Clicking Yes causes the following to occur: The UPS cycles its output power off and then back on. During the reboot, PowerNet Manager displays the following: Composite status indicator message Line-status icon Enter Sleep Mode Selecting Put UPS to Sleep... opens the following dialog box: Put UPS to Sleep... is unavailable when the UPS uses a PowerNet Agent. As shown, unless the UPS is on-battery, the Until Power Returns selection is inactive.
45 45 PowerNet SNMP Manager for ManageWise - User s Guide 45 This dialog box allows you to define two different sleep modes, either turn off the UPS until input voltage returns to an acceptable level (sleeping awaiting power return) or for a defined period of time (timed sleep), as follows: 1) Select the sleep mode: Click Until Power Returns to conserve battery power during a power failure by putting the UPS to sleep until the input voltage returns to normal. When input voltage returns to normal, the UPS will wait until two UPS operating parameter values, Power Return Delay (Time) and Power Return (Battery Capacity), are satisfied before turning the UPS on. See POWER RETURN BEHAVIOR PARAMETERS in CHAPTER 6. While in this sleep mode, PowerNet Manager displays the following: Composite status indicator message Line-status icon Click For to define the sleep time, in minutes. The defined time must be a multiple of 6 (6, 12, 18, 60, etc.): Any other value will be rounded up or down by PowerNet Manager. Once the defined sleep time passes, the UPS will wait for the time defined by the UPS operating parameter, Power Return Delay (Time), to pass before turning the UPS on. See POWER RETURN DELAY PARAMETERS in CHAPTER 6. While in this sleep mode, PowerNet Manager displays the following: Composite status indicator message Line-status icon When you put the UPS into a timed sleep, Put UPS to Sleep... changes to Wake Up Sleeping UPS, an option you can use to wake the UPS before the defined time passes. 2) Click OK to put the UPS to sleep. The return of power following the sleep mode can be affected by two UPS operating parameters. See POWER RETURN BEHAVIOR PARAMETERS in CHAPTER 6.
46 46 PowerNet SNMP Manager for ManageWise - User s Guide 46 Turn UPS Off and On Selecting Turn Off UPS... opens this confirmation box: Clicking Yes causes the following to occur: The UPS waits until the time defined by the UPS operating parameter, UPS Turn Off Delay, passes before it turns off power to its attached equipment. If the UPS uses a PowerNet Adapter, Turn Off UPS... becomes Turn On UPS, an option you can use to turn the UPS on again. However, you will need to use the on/off switch at the UPS to turn the UPS on again if either of the following is true: - The PowerNet Adapter loses power when you use Turn Off UPS... - The UPS uses a PowerNet Agent (Turn Off UPS... does not change to Turn On UPS). While the UPS remains off, PowerNet Manager displays the following: Composite status indicator message Line-status icon Control Bypass Mode for a UPS Selecting Put UPS On Bypass, an option available only with a Matrix-UPS or Symmetra Power Array, immediately puts the UPS into software bypass. You can use the bypass switch at the Matrix-UPS or Symmetra Power Array to put the UPS into switched bypass. A Matrix-UPS or Symmetra Power Array can also go into a hardware-failure bypass mode. See BYPASS ICON (MATRIX-UPS AND SYMMETRA POWER ARRAY) in CHAPTER 4 for more information on the bypass modes. While in software bypass, the following occurs: The UPS cannot protect its attached equipment from power problems. Put UPS On Bypass changes to Return UPS from Bypass, an option which allows you to take the UPS out of software bypass when the UPS is ready to go back on line. PowerNet Manager displays the following: Line-status icon Composite status indicator message
47 47 PowerNet SNMP Manager for ManageWise - User s Guide 47 Chapter 8: How to Test a UPS The Diagnostics menu options allow you to do the following to test the UPS batteries and operation: PERFORM A UPS SELF-TEST PERFORM A UPS RUNTIME CALIBRATION SIMULATE A POWER FAILURE When the UPS uses a PowerNet Agent, the Initiate Run Time Calibration option is unavailable. Perform a UPS Self-Test Selecting Initiate UPS Self Test causes the UPS to perform a self-test. During this self-test, the UPS switches briefly to battery power and performs internal diagnostics. At the end of the test, PowerNet Manager posts the test result in the UPS Diagnostics window (see CHAPTER 5). During a self-test, the composite status indicator displays this message: The UPS can initiate self-tests. See the UPS Diagnostics window description in CHAPTER 5 for more information on UPS-initiated self-tests.
48 48 PowerNet SNMP Manager for ManageWise - User s Guide 48 Perform a UPS Runtime Calibration Selecting Initiate Run Time Calibration, an option which is active only if the UPS uses a PowerNet Adapter or Web/ SNMP Management Card, starts a runtime calibration. This calibration process allows the UPS to compute its onbattery runtime, given its specific load. APC recommends that you do not perform runtime calibrations on a routine basis. The runtime calibration is a lengthy process which results in a deep discharge of the battery (down to 25% of available battery power). This typically results in the battery being unable to support the attached equipment, should a power failure occur. In addition, repeated deep discharges can have an adverse affect on the life of the UPS battery. Therefore, unless it is critical to your specific situation that you know the exact amount of runtime available, you should only perform a runtime calibration when the amount of equipment (UPS load) connecting to the UPS for power has been significantly changed, either by permanently unplugging some equipment, or by plugging in new equipment. You can also perform a runtime calibration on a periodic basis, but no more often than every six months, since as a battery ages, the runtime can be effected. To begin a runtime calibration, the UPS battery capacity must be at 100%. During the runtime calibration: The composite status indicator displays this message: Initiate Run Time Calibration changes to Cancel Run Time Calibration, an option which allows you to cancel the process at any time. The value shown in the Battery Capacity (%) dial in the UPS Batteries window decreases as the calibration progresses because the runtime calibration process will discharge the UPS battery. When the runtime calibration process finishes, the following runtime calibration status indicator will be replaced by the following composite status indicator message: Simulate a Power Failure Selecting Simulate Power Failure tests the ability of the UPS to switch to battery power when a power failure occurs. Although the UPS goes on battery during the simulation, the SNMP agent for the UPS will not send an onbattery trap. During the simulation, the composite status indicator displays this message:
49 49 PowerNet SNMP Manager for ManageWise - User s Guide 49 Index A Abbreviations 5 Abnormal message 20 About this guide 5 Access-level identification, PowerNet Manager 15 Activate UPS Alarm 43 Address MIB-II location 35, 42 Receiver IP 34 Agent Parameters 33 MIB-II variables 35 SNMP 33 syscontact 35 syslocation 35 sysname 35 Trap receivers 34 SNMP 16, 19, 20, 21, 35, 42 Alarm test message 20 Ambient temperature (deg C) dial 32 APC Discovery program 10 APCUPS.INI file 10 Associated documents 5 B Bad battery pack(s) 29 Battery Capacity (%) dial 28 Last replaced on 29 Status icons. See Status icons Values 28 Blackout 26 Brownout 26 Bypass mode and icons 18 C Calibration Cancel runtime 48 Initiate runtime 48 Cancel Runtime Calibration 48 Celsius-to-Fahrenheit conversion formula 32 Communication-status icons. See Status icons Community name 21 Composite status indicator 14, Abnormal 20 Alarm test 20 Discharged battery 20 Hardware fail bypass 20 Lost serial communication 21 Low battery 21 Network error 21 Off 21 On battery 21 Online 21 Overload 21 Rebooting 21 Replace battery 21 Runtime calibration 22 Self test 22 Simulated power fail 22 Sleeping awaiting power return 22 SmartBoost 22 SmartTrim 22 Software bypass 22 Switched bypass 22 Timed sleep 22 Unknown 22 Configuration menu 13, 33 Modify SNMP Agent Parameters UPS Identification Parameters UPS Operating Parameters Reset UPS Parameters to Factory Defaults Site-Specific Notes... 35, 42 Configuring the UPS. See Configuration menu Control menu 13, 43 Activate UPS Alarm 43 Put UPS On Bypass 46 to Sleep Reboot Load Take UPS Off Bypass 46 Turn Off UPS On UPS 46 Wake Up Sleeping UPS 45 Controlling the UPS. See Control menu Controlling UPS output power 7 D Diagnostics menu 47 Cancel Runtime Calibration 48 Initiate Run Time Calibration 48 UPS Self Test 47, 48 Reboot Load Dialog box Put UPS to Sleep Reboot Load Reset UPS Parameters to Factory Defaults Site-specific notes 42 MIB-II variables 42 Notes area 42 syscontact 42 syslocation 42 sysname 42 SNMP agent parameters 34 MIB-II variables 34 Receiver IP address 34 syscontact 35 syslocation 35 sysname 35 Trap receivers 34 Turn off UPS UPS identification parameters 35 Attached devices 36 Mfg. on 36 Rev. 36 Serial # 36 UPS identification box 36 UPS model 36 UPS name 36 UPS operating parameters 37 Audible alarm (on-battery) 39 High transfer voltage 38 Low battery runtime 39 Low transfer voltage 38 Matrix-UPS or Symmetra password 38 On-battery behavior 39 On-line behavior 38 Other (Matrix-UPS or Symmetra password) 38 Power return (battery capacity) 40 Power return behavior 40 Power return delay (time) 40 Rated output voltage 38 Sensitivity 38 Special considerations 39 UPS turn off delay 39 Discharged battery message 20 Discovery program 10 E Edit menu 13 EEPROM, resetting to factory defaults 41 F File menu Exit 13 Shutdown server 13 Formula, Celsius-to-Fahrenheit 32 Frequency 27 Functions 7 H Hardware fail bypass message 20 Help menu 13 High Input voltage 26 Transfer voltage 38 Host Name/IP Address 15 I Icons Smart-UPS SmartBoost (line status) 18 SmartTrim (line status) 18 Status. See Status icons Tool bar. See Tool bar icons Identification parameters Initiate Run Time Calibration 48 UPS Self Test 47 Input-line status icons 17 Internal UPS temperature (deg C) dial 29
50 50 PowerNet SNMP Manager for ManageWise - User s Guide 50 L Last transfer cause 26 Launching PowerNet Manager 8 Line-status icons. See Status icons Load-status icons. See Status icons Lost serial communication message 21 Low Battery message 21 Transfer voltage 38 M Main screen 12 Configuration menu. See Configuration menu Control menu. See Control menu Diagnostics menu. See Diagnostics menu Features 12 File menu Exit 13 Shutdown server 13 Host Name/IP address 15 Menu bar 13 Polling indicator 15 Status Icons. See Status icons Indicator. See Composite status indicator Tool bar. See Tool bar icons UPS model identification 14 Matrix-UPS Bad battery pack(s) 29 Bypass icons and mode 18 Front-panel password 38, 41 Measure-UPS Tool bar icon 24 Window Ambient temperature (deg C) 32 Contacts definitions 32 Relative humidity (%) 32 Menu bar. See Menus Menus Configuration. See Configuration menu Control. See Control menu Diagnostics. See Diagnostics menu Edit 13 File 13 Help 13 View 13 MIB-II Agent identification parameters 34, 42 Variables syscontact 35, 42 syslocation 35, 42 sysname 35, 42 Modifying SNMP agent parameters 35 UPS Identification parameters 36 Operating parameters 40 Momentary power problems 26 N Network error Composite status message 21 Message screen 10 Network view APC UPS icons 8-11 Node/server name 15 O Off Composite status message 21 Line-status icon 17 On battery Composite status message 21 Line-status icon 17 Online Composite status message 21 Line-status icon 17 Operating parameters 13, 33, 37 Overload message 21 P Phase 27 Polling indicator 15 Power Data window Current Frequency Max Min Now Phase Tool bar icon 24 Load (% volt-amps) 26 Return Battery capacity Behavior Delay time Sleeping awaiting power return message 22 Sag 26 Spike 26 PowerNet Manager Access-level identification 15 Composite status indicator messages. See Composite status indicator Functions Configuring SNMP and UPS parameters 7 Controlling UPS output power 7 Main screen. See Main screen Status Icons. See Status icons Indicator. See Composite status indicator Line 14 PowerNet Manager Verifying operation 10 Put UPS On Bypass 46 to Sleep R Rated output voltage 38 Reboot 7 Load Rebooting message 21 Receiver IP address 34 Relative humidity (%) dial 32 Replace battery message 21 Reset UPS Parameters to Factory Defaults Runtime Calibration Composite status message 22 Remaining 29 S Self-test message 22 Sensitivity 39 Simulated power fail message 22 Site-specific notes... See Dialog box, sitespecific notes Sleep Awaiting power return icon 17 Mode 7 Timed icon 17 Sleeping awaiting power return message 22 Smart-UPS Line-status icons SmartBoost 18 SmartTrim 18 SmartBoost feature 22 SmartTrim feature 22 SmartBoost Composite status message 22 Line-status icon 18 Smart-UPS feature 22 SmartTrim Composite status message 22 Line-status icon 18 Smart-UPS feature 22 SNMP Agent 35, 42 MIB-II variables 35, 42 Parameters. See Dialog box, SNMP agent parameters Receiver IP address 34 syscontact parameter 35 syslocation parameter 35 sysname parameter 35 Software bypass message 22 Status Composite status indicator 14, Icons Battery 14, Bypass (line status) 18 Communication 14, Input line (line status) 17 Line 14, 16 Load 14, Off (line status) 17 Sleeping awaiting power return (line status) 17 SmartBoost (line status) 18 SmartTrim (line status) 18 Unknown communication 20 Unknown line 16 Unknown load 19 PowerNet Manager status line 14 Switched bypass message 22 System Contact 35, 42 Location 35, 42 Name 35, 42
51 51 PowerNet SNMP Manager for ManageWise - User s Guide 51 T Take UPS Off Bypass 46 Testing the UPS Alarm test 43 Self-test 47 Timed sleep message 22 Tool bar 15 Icons Measure-UPS 31 Power data 27 UPS batteries 28 UPS diagnostics 30 UPS load 26 Voltage graph 24 Windows. See Tool bar icons Total battery pack(s) 29 Transfer to battery 26 Trap Receiver parameters 34 Type(s) 35 Turn Off UPS On UPS 46 U Unknown Composite status message 22 Status Communication-status icon 20 Line-status icon 16 Load-status icon 19 UPS Acronym definition 5 Batteries window Battery capacity (%) 28 Internal UPS temperature (deg C) 29 Status box 29 Tool bar icon 24 Diagnostics window At UPS turn on Bi-weekly Never Tool bar icon 24 Weekly Identification parameters. See Dialog box, UPS identification parameters Load window Current (amperes) 26 Power load (% volt-amps) 26 Tool bar icon 24 Model identification Operating parameters. See Dialog box, UPS operating parameters V Verifying operation 10, 11 View menu 13 Voltage graph Tool bar icon 24 Window Current voltage report 25 Graph display 25 Last transfer cause 26 Positioning scroll bars 25 Scale adjustment buttons 25 W Wake Up Sleeping UPS 45 Window Measure-UPS. See Measure-UPS window Power data. See Power data window UPS batteries. See UPS batteries window UPS diagnostics. See UPS diagnostics window UPS load. See UPS load window Voltage graph. See Voltage graph window
PowerNet SNMP. Management Information Base (MIB) v3.0.0. Reference Guide. Title Page
PowerNet SNMP Title Page Management Information Base (MIB) v3.0.0 Reference Guide PowerNet SNMP Management Information Base (MIB) v3.0.0: Reference Guide POWERNET MIB V3.0.0 2 PowerNet SNMP Management
Title Page. Installation Guide. PowerChute plus Version 5.0.1. for Windows 95
Title Page PowerChute plus Version 5.0.1 for Windows 95 Notice Page : PowerChute plus for Windows 95 version 5.0.1 PowerChute plus License Statement This software is protected by both United States copyright
Addendum: PowerNet SNMP Management Information Base (MIB)
Reference Guide TitlePage Addendum: PowerNet SNMP Management Information Base (MIB) for Version 3.3.0 ADDENDUM TO REFERENCE GUIDE: POWERNET SNMP MANAGEMENT INFORMATION BASE (MIB) MIB VERSION 3.3.0 AMERICAN
Title Page Web/SNMP Management SmartSlot Card
Title Page Web/SNMP Management SmartSlot Card AP9606 User s Guide Thank You! Thank you for selecting the APC Web/SNMP Management SmartSlot Card. It has been designed for many years of reliable, maintenance-free
PowerNet SNMP Management Information Base (MIB)
TitlePage PowerNet SNMP Management Information Base (MIB) Version 3.2.0 REFERENCE GUIDE: POWERNET SNMP MANAGEMENT INFORMATION BASE (MIB) MIB VERSION 3.2.0 AMERICAN POWER CONVERSION CORPORATION - SOFTWARE
Network Management Card. Installation and Quick Start Manual
Network Management Card Installation and Quick Start Manual Radio frequency interference Changes or modifications to this unit not expressly approved by the party responsible for compliance could void
PowerNet Management Information Base (MIB)
PowerNet Management Information Base (MIB) Version 3.4.4 Reference Guide REFERENCE GUIDE: POWERNET MANAGEMENT INFORMATION BASE (MIB), VERSION 3.4.4 AMERICAN POWER CONVERSION CORPORATION - SOFTWARE LICENSE
Configurable Events for APC Network Management Card
Configurable s for APC Network Management Card Table of Contents Silcon DP300E Series 3 Smart-UPS / Matrix 7 Symmetra 9 Symmetra 3-Phase 13 Environmental Monitor 21 Configurable s for APC Network Management
Operation Manual. Smart-UPS C. Uninterruptible Power Supply. Tower 1000/1500 VA. 120/230 Vac. su0813a
Operation Manual Smart-UPS C Uninterruptible Power Supply Tower 1000/1500 VA 120/230 Vac su0813a Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power
Before You Start 1 Overview 2 Supported Devices 4 Public (User LAN) and Private (APC LAN) Networks 5. Initial Configuration Requirements 6
Contents Introduction 1 Before You Start 1 Overview 2 Supported Devices 4 Public (User LAN) and Private (APC LAN) Networks 5 Initial Configuration Requirements 6 Overview 6 Setup Wizard 7 Status, Alarm,
Installation and Operation Back-UPS 1250, 1300, 1500
Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with
Environmental Monitoring Unit
Environmental Monitoring Unit AP9312TH AP9312THi User s Guide Contents Environmental Monitoring Unit Managing the Unit............................ 1 Introduction.................................. 1 Available
Back-UPS Pro 1300/1500 Installation and Operation
Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a
CAUTION. CAUTION indicates a potentially hazardous situation which, if not avoided, can result in equipment damage and minor or moderate injury.
Product Description The APC by Schneider Electric Smart-UPS is a high performance uninterruptible power supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts,
User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply
User Manual English APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC Tower Uninterruptible Power Supply 990-1587A 12/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent
Release Notes: PowerChute plus for Windows 95 and Windows 98
: PowerChute plus for Windows 95 and Windows 98 These release notes supplement the User s Guide: PowerChute plus, Version 5.0.2, for Windows 95 and Windows 98 (pc98ug.pdf) and the Installation Guide: PowerChute
User Manual. English. APC Smart-UPS 1000/1500 VA 100/120/230 VAC 750/1000XL VA 120/230 VAC. Tower Uninterruptible Power Supply
User Manual English APC Smart-UPS 1000/1500 VA 100/120/230 VAC 750/1000XL VA 120/230 VAC Tower Uninterruptible Power Supply 990-1074C 06/2012 Introduction American Power Conversion Corporation (APC) is
User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed
PowerPanel Business Edition USER MANUAL
USER MANUAL Rev. 0.9 2007/10/26 Copyright 2006-2007 Cyber Power Systems, Inc. All rights reserved. PowerPanel Business Edition USER S MANUAL PowerPanel Business Edition provides power management Services.
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
SNMP Web card. User s Manual. Management Software for Uninterruptible Power Supply Systems
SNMP Web card User s Manual Management Software for Uninterruptible Power Supply Systems Table of Contents 1. Overview... 3 1.1 Introduction... 3 1.2 Features... 3 1.3 Overlook... 3 1.4 Installation and
Ambient Temperature In Range Probe X
List of Events This section lists all events that are written to the Event Log. Some of these events can be configured through the Configuring Events to Take Actions page, and these are listed in the first
ViewPower. User s Manual. Management Software for Uninterruptible Power Supply Systems
ViewPower User s Manual Management Software for Uninterruptible Power Supply Systems Table of Contents 1. ViewPower Overview... 2 1.1. Introduction...2 1.2. Structure...2 1.3. Applications...2 1.4. Features...2
Out-of-Band Management Card
Out-of-Band Management Card AP9608 Installation Manual Related Documents For information on using the Out-of-Band Management Card after installation and startup, see the online User s Guide specific to
Operation Manual. Smart-UPS X Uninterruptible Power Supply
Operation Manual Smart-UPS X Uninterruptible Power Supply Low Voltage (100-127 V) SMX2000RMLV2U SMX2200RMLV2U SMX3000RMLV2U SMX3000RMLV2UNC SMX3000RMJ2U High Voltage (200-240 V) SMX2200RMHV2U SMX3000RMHV2U
How To Install A Power Supply (Uplast) With A Battery Pack
APC Smart-UPS RT SURTA48XLBP/SURTA48XLBPJ External Battery Pack User Manual Introduction/Before Installation About this Manual The APC Smart-UPS RT external battery pack (SURTA48XLBP or SURTA48XLBPJ) connects
Triple Expansion Chassis
Triple Expansion Chassis AP9604 Installation Manual Contents Introduction............................. 1 Installation.............................. 2 Power Considerations...................... 5 Operations..............................
Back-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
SentryPlus. Shutdown Management Software for Windows. User s Manual
SentryPlus Shutdown Management Software for Windows User s Manual Table of Contents Introduction...3 SentryPlus Features...3 SentryPlus Installation...4 SentryPlus Setup...4 SentryPlus Service...5 SentryPlus
Network Management Card
Network Management Card AP9617 AP9618 AP9619 Installation and Quick-Start Manual How to Avoid Equipment Damage Disconnect UPS power You do not need to turn off a Symmetra or a Silcon model UPS to install
Product Description... 1 Internal Management Features... 3 Front Panel... 5 Watchdog Features... 7
Contents Introduction--1 Product Description.................................. 1 Internal Management Features........................... 3 Front Panel........................................ 5 Watchdog
User s Manual Network Management Card
User s Manual Network Management Card RMCARD202 Intelligent Network Management Card allows a UPS system to be managed, monitored, and configured Version 1.0 E-K01-SNMP005-0 TABLE OF CONTENTS Introduction
Sentry Bulldog Shutdown Management Software (For UNIX Series)
Sentry Bulldog Shutdown Management Software (For UNIX Series) User Manual Table of Contents Introduction...4 Sentry Bulldog Installation...5 Sentry Bulldog Services...6 Sentry Bulldog Monitor...7 Networking...8
FXM Communication Manual
Operator s Manual 017-201-B1 9/06 EFFECTIVE: September, 2006 Alpha Technologies Power Alpha Technologies 1 Introduction to FXM Computer Communication There are several ways to connect a computer to the
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial MODEL NUMBER: SMART2200RM2U Highlights 2.2kVA / 2200VA / 1920W line interactive 2U
Network Management Station (NMS) Reference Guide
Network Management Station (NMS) Reference Guide Network Management Station (NMS) - Reference Guide 2 Network Management Station (NMS) - Reference Guide 2 All rights reserved. No part of this reference
How To Log On... 13 Main Screen... 16 Control Console Menus... 19
Contents Introduction 1 Product Description.......................................... 1 Internal Management Features.................................. 4 How to Recover from a Lost Password...........................
SSL-Manager (SNMP-SSL Management Software)
SSL-Manager (SNMP-SSL Management Software) User s Manual Table of Contents Chapter 1 Introduction... 3 Chapter 2 Installation... 4 Chapter 3 SSL-Manager Menus... 8 Chapter 4 Setup... 11 Chapter 5 Operation...
Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system
Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system Model #: SMART500RT1U 500VA line interactive 1U rack/tower UPS 7 outlets with 1 switchable load bank Simultaneous
APC UPS Management Solutions
APC UPS Management Solutions Award-winning software and accessories for network administrators providing UPS manageability and safe system shutdown for desktops, workstations, and servers protected by
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMARTINT3000VS Highlights 3kVA / 3000VA / 2250W line interactive tower UPS system 230V
Network Management Card. User Manual
User Manual 1 Contents Contents 2 Chapter 1 Overview 3 1.1 NMC package contents 4 1.2 NMC CD Resources 4 1.3 Features 4 1.4 NMC Applications 5 Chapter 2 NMC parameters setting via serial COM port 6 2.1
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U SURT192RMXLBP2 SURT192RMXLBP2J English 990-2485B 02/2009 Introduction About this UPS The American Power Conversion (APC ) SURT192RMXLBP2 external
Document Number: 13004.25-4.5.2-6/15/2012
Mobile Android App User Guide Copyright 2012 icontrol Networks, Inc. All rights reserved. No reproduction in whole or in part without prior written approval. icontrol Networks, icontrol, and icontrol logo
User s Manual UPS SERIES. Network Interface Card UPS-IPCARD. I-00453 Rev B
User s Manual UPS SERIES Network Interface Card UPS-IPCARD I-00453 Rev B TABLE OF CONTENTS INTRODUCTION............................................................. 3-4 INSTALLATION GUIDE.......................................................
Using the UPSMON-Plus Monitoring Software
Using the UPSMON-Plus Monitoring Software With UPSMON-Plus UPS Monitoring software, you can: Monitor battery level, load level, input and output current. Schedule daily, weekly, or monthly battery self
Operation Manual. Smart-UPS UPS. 750/1000/1500/2200 VA Rack-mount 2U 120/230 VAC. 3000 VA Rack-mount 2U 120/208/230 VAC
Operation Manual Smart-UPS UPS 750/1000/1500/2200 VA Rack-mount 2U 120/230 VAC 3000 VA Rack-mount 2U 120/208/230 VAC Contents Overview... 1 Product Description....................................... 1
Mobile Android App User Guide
Mobile Android App User Guide Mobile Android App User Guide Copyright 2012 icontrol Networks, Inc. All rights reserved. No reproduction in whole or in part without prior written approval. icontrol Networks,
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications
Monitoring Network DMN
Monitoring Network DMN User Manual Table of contents Table of contents... 2 1. Product features and capabilities... 3 2. System requirements... 5 3. Getting started with the software... 5 3-1 Installation...
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
USER S GUIDE. network management card. Contents. Introduction--1. Control Console--13
Contents Introduction--1 Product Description.................................. 1 Functionality 1 Initial set-up 2 Network management features 3 Internal Management Features........................... 5
How to Obtain an OPC License--5. Creating a System Code 5 Entering an Authorization Code 6. Getting Started with SNMP Editor--7
Contents Introduction--1 Product definition 1 Implementing SNMP 2 Integrating SNMP into the user interface 3 Components of OPC SNMP Gateway 4 How to Obtain an OPC License--5 Creating a System Code 5 Entering
Symmetra LX. Operations Guide
Symmetra LX Operations Guide For use with Symmetra LX UPS Models: 200 V, 4 8 kva 208/240 V, 4 8 kva 220/230/240 V, 4 8 kva 200 V, 4 16 kva 208/240 V, 4 16 kva 220/230/240 V, 4 16 kva Symmetra LX Rack-mount
Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
Prisma II Software Upgrade Program (SOUP) Installation Guide
Prisma II Software Upgrade Program (SOUP) Installation Guide Overview The Prisma II Software Upgrade Program (SOUP) is a user-friendly utility that allows users to perform firmware upgrades on Prisma II
NEC Express5800 Series NEC ESMPRO AlertManager User's Guide
NEC Express5800 Series NEC ESMPRO AlertManager User's Guide 7-2006 ONL-4152aN-COMMON-128-99-0606 PROPRIETARY NOTICE AND LIABILITY DISCLAIMER The information disclosed in this document, including all designs
User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer
User s Manual PowerPanel Shutdown Service Graceful Shutdown and Notification service to ensure power protection of your computer Revision 1.1 TABLE OF CONTENTS INTRODUCTION... 1 INSTALLATION GUIDE... 2
PowerPanel Personal Edition User Manual. User Manual. PowerPanel Personal Edition. Rev. 6 2012/02/24
User Manual PowerPanel Personal Edition Rev. 6 2012/02/24 ELECTRONIC END USER LICENSE AGREEMENT FOR CYBERPOWER POWERPANEL PERSONAL EDITION NOTICE TO USER: THIS IS A CONTRACT. BY INSTALLING THIS SOFTWARE
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS, Sine
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SMART1000RM1U Description Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line interactive,
Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
PowerPanel Personal Edition User Manual. User Manual. PowerPanel Personal Edition. Rev. 9 2015/12/2
User Manual PowerPanel Personal Edition Rev. 9 2015/12/2 ELECTRONIC END USER LICENSE AGREEMENT FOR CYBERPOWER POWERPANEL PERSONAL EDITION NOTICE TO USER: THIS IS A CONTRACT. BY INSTALLING THIS SOFTWARE
Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System
Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System MODEL NUMBER: HTR05-1U Description Tripp Lite's HTR05-1U AVR Series intelligent, Automatic Voltage Regulated
USER S GUIDE. network management card. Contents. Introduction--1. Control Console--13
Contents Introduction--1 Product Description.................................. 1 Features 1 Initial set-up 2 Network management features 3 Internal Management Features........................... 4 Overview
CompleteView Alarm Client User s Manual. Version 3.8
CompleteView Alarm Client User s Manual Version 3.8 Table Of Contents Introduction... 1 Overview... 2 System Requirements... 2 Configuration... 3 Starting the Alarm Client... 3 Menus... 3 File Menu...
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 Getting Started Getting Started with the Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 You only need a few minutes to get started
eco PDU PE Series SNMP Settings User Instructions
eco PDU PE Series SNMP Settings User Instructions www.aten.com NRGence User Help User Information Online Registration Be sure to register your product at our online support center: International North
750VA/1000VA/1500VA 100/120/230VAC 2U
User s Manual English Smart-UPS 750VA/1000VA/1500VA 100/120/230VAC 2U Rack Mount Uninterruptible Power Supply 990-1194 5/02 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent
CompleteView Alarm Client User Manual. CompleteView Version 4.3
CompleteView Alarm Client User Manual CompleteView Version 4.3 Table of Contents Introduction...1 Overview... 2 System Requirements... 2 Configuration...3 Starting the Alarm Client... 3 Menus... 3 File
User Manual. English. APC Smart-UPS. 2200 VA 120/230 Vac. 3000 VA 100/120/208/230 Vac. 2U Rack Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS 2200 VA 120/230 Vac 3000 VA 100/120/208/230 Vac 2U Rack Mount Uninterruptible Power Supply 990-1352A 11/2003 Introduction The APC Uninterruptible Power Supply (UPS) is
Liebert MultiLink. User Manual - Fundamental & Advanced
Liebert MultiLink User Manual - Fundamental & Advanced TABLE OF CONTENTS 1.0 WHAT IS LIEBERT MULTILINK?..............................................2 1.1 How Does Liebert MultiLink Work?.............................................
User s Manual. Remote Management Card RMCARD202. Intelligent Remote Management Card allows a UPS system to be managed, monitored, and configured
User s Manual Remote Management Card RMCARD202 Intelligent Remote Management Card allows a UPS system to be managed, monitored, and configured Version 1.2 TABLE OF CONTENTS Introduction 1 Installation
hp embedded web server for hp LaserJet printers
hp embedded web server for hp LaserJet printers user guide Trademark Credits Microsoft is a U.S. registered trademark of Microsoft Corporation. Netscape is a U.S. trademark of Netscape Communications Corporation.
Automation License Manager
s Contents Product Overview 1 Installation 2 Working with the Automation License Manager 3 Glossary Manual Index 12/2008 A5E02389428-01 Legal information Warning notice system This manual contains notices
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual
Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS
User Manual. Humidity-Temperature Chart Recorder. Model RH520
User Manual Humidity-Temperature Chart Recorder Model RH520 Introduction Congratulations on your purchase of the Extech RH520 Temperature + Humidity Chart Recorder. The RH520 measures and displays Temperature,
NETWORK PRINT MONITOR User Guide
NETWORK PRINT MONITOR User Guide Legal Notes Unauthorized reproduction of all or part of this guide is prohibited. The information in this guide is subject to change without notice. We cannot be held liable
Smart-UPS On-Line 230 V
Smart-UPS On-Line 230 V Unity output power factor single-phase, double-conversion online UPS with advanced management features A versatile UPS developed for unstable power conditions worldwide Smart-UPS
User Manual. English. APC Smart-UPS RT. 3000/5000/6000 VA 200-240 VAC Tower/Rack Mount 3U Uninterruptible Power Supply
User Manual English APC Smart-UPS RT 3000/5000/6000 VA 200-240 VAC Tower/Rack Mount 3U Uninterruptible Power Supply 990-1289D 03/2006 Introduction The APC Smart-UPS RT is a high-performance, uninterruptible
To use PowerChute Web Device Manager, the Smart-UPS must connect to your network through one of the following types of servers or workstations:
PowerChute Web Device Manager, Version 2.0.0: Entire contents copyright 2000, American Power Conversion. All rights reserved; reproduction in whole or in part without permission is prohibited. PowerChute
OWNERS MANUAL. Status Monitor. for Windows 95, 98, ME, NT 4, 2000 & XP. SIGNALCRAFTERS TECH, INC. www.signalcrafters.com
OWNERS MANUAL Status Monitor for Windows 95, 98, ME, NT 4, 2000 & XP SIGNALCRAFTERS TECH, INC. www.signalcrafters.com 57 Eagle Rock Avenue, East Hanover, NJ 07936 Tel: 973-781-0880 or 800-523-5815 Fax:
Spectra T50e Flash (SD) Card Installation Instructions
Spectra T50e Flash (SD) Card Installation Instructions PN 90970021 Revision A Notices Notices Except as expressly stated herein, Spectra Logic Corporation makes available this Spectra library and associated
Environmental Management System
Contents Introduction--1 Product Description.................................. 1 Access Procedures................................... 3 How to Recover from a Lost Password..................... 6 Upgrading
Dell Network Management Card. User's Guide. w w w. d e l l. c o m s u p p o r t. d e l l. c o m
Dell Network Management Card User's Guide w w w. d e l l. c o m s u p p o r t. d e l l. c o m Notes and Warnings NOTE: A NOTE indicates important information that helps you make better use of your software.
Foglight Experience Monitor and Foglight Experience Viewer
Foglight Experience Monitor and Foglight Experience Viewer Quest Software, Inc. April 2008 Using the Dell Remote Access Controller Copyright Quest Software, Inc. 2008. All rights reserved. This guide contains
User's Reference Guide for PowerAlert UPS Management Software Version 10.2 for Windows
User's Reference Guide for PowerAlert UPS Management Software Version 10.2 for Windows 1111 W. 35th Street Chicago, IL 60609 USA (773) 869-1234 www.tripplite.com Table of Contents A QUICK GUIDE TO POWERALERT
Welch Allyn Connex VM data management system. Directions for use
Welch Allyn Connex VM data management system Directions for use 2011 Welch Allyn. All rights are reserved. To support the intended use of the product described in this publication, the purchaser of the
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS,
Installation and Operation
Installation and Operation Smart-UPS ΤΜ SR1 Uninterruptible Power Supply SR18KXIET SR110KXIET 220/230/240 Vac Tower suo0759b Smart-UPS TM SR1 Uninterruptible Power Supply 8000/10000 VA 220/230/240 Vac
PowerChute Business Edition. Getting Started
PowerChute Business Edition Getting Started Contents Getting Started Guide 1 PowerChute Business Edition Components 2 Installation Procedure 3 STEP 1: Install the PowerChute Business Edition Agent 3 STEP
User Manual. Smart-UPS. Uninterruptible Power Supply 750/1000/1500 VA. 100/120/230 Vac. Rack Mount 2U
User Manual Smart-UPS Uninterruptible Power Supply 750/1000/1500 VA 100/120/230 Vac Rack Mount 2U Smart-UPS TM Uninterruptible Power Supply 750/1000/1500 VA 100/120/230 Vac Rack-Mount 2U EN 990-1194E 08/2014
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
Belkin Bulldog Plus. Shutdown Management Software for Windows. User s Manual
Belkin Bulldog Plus Shutdown Management Software for Windows User s Manual Table of Contents INTRODUCTION...5 Bulldog Plus features:...5 BULLDOG PLUS INSTALLATION...5 Bulldog Plus Setup:...6 BULLDOG PLUS
Network Management Card
Network Management Card AP9617 AP9618 AP9619 Installation and Quick-Start Manual This manual is available in English on the enclosed CD. Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.
APC Smart-UPS 2400/3000 VA 100/110-120 VAC 3U. Uninterruptible Power Supply
User Manual English APC Smart-UPS 2400/3000 VA 100/110-120 VAC 3U Tower/Rack Mount Uninterruptible Power Supply 990-2233A 02/2005 Introduction/Before Installation Introduction/Before Installation About
Internet Office UPS System Standby UPS for PCs, workstations and more
Internet Office UPS System Standby UPS for PCs, workstations and more Model #: INTERNETOFFICE500 500VA standby tower UPS system Offers battery-derived AC output during blackouts and brownouts starting
