BY A.O. DESJARLAIS, J.P. SHEAHAN, AND P.C. GARRIGUS
|
|
|
- Leslie Baker
- 10 years ago
- Views:
Transcription
1 R RE ER RO OO OF F II N NG G O OV VE ER R F FA A II L LE ED D R RO OO OF FS S C CO ON N TA TA II N N II N NG G An ORNL/RCI/SPRI Collaborative Demonstration Project BY A.O. DESJARLAIS, J.P. SHEAHAN, AND P.C. GARRIGUS This paper was originally presented at the International Conference on Building Envelope Systems and Technologies (ICBEST 2001) held in June 2001 in Ottawa, Canada, and is reprinted here with permission. Abstract Although widely practiced within the roofing industry, roof re cover, particularly over failed roofs that contain significant amounts of moisture, remains a controversial issue. The key issues surrounding this debate are the drying of wetted insula tion, deck deterioration (dry rot of wood, disintegration of con crete, corrosion of metal), and fastener failures. To address these issues, a consortium made up of SPRI and its member compa nies the Roof Consultants Institute (RCI) and the Oak Ridge National Laboratory (ORNL) have initiated two demonstration projects to re cover failed roofing systems containing moisture and to monitor the performance of those roofing systems after the reroofing. In 1997, SPRI identified a building, the New Bethel Fellowship Church in Rossville, IL (approximately 100 miles south of Chicago) that satisfied criteria developed by SPRI for a satisfactory demonstration site. Representatives of SPRI, RCI, and Oak Ridge National Laboratory visited the building and, with the permission of the church, used this building for a demonstra tion project. The reroofing was performed in June The roof has been continuously monitored, and yearly visits to the building for inspection and sampling purposes have been undertaken. Evaluating the compressive properties of the original insulation has been used to monitor the adequacy of the existing roof as a substrate for the re cover roof. Fastener pullout testing has been employed to monitor the structural integrity of the September 2001 deck and the corrosion protection of the fasteners. Measuring the moisture content of the existing and re cover insulation examined whether the original roof is drying and whether the re cover roof was being compromised by water from the original roofing system. Moisture content data were also used to assess a computer model that has been developed to predict the drying rates of roofing systems containing wet insulation. Finally, the reflectance of the membranes was catalogued to determine how rapidly white membranes foul due to dirt accumulation and degradation and their impact on the drying process. This paper describes the building selection, reroofing process, data collection, and nondestructive analysis that have been per formed to determine if the old roofing system is drying and to assess whether the fasteners have been adversely affected by the wet insulation material. Computer simulations of the roof system have been performed to predict drying; these data are compared to actual core measurements and nondestructive test results to determine the drying rate of the re covered roof systems. Introduction Re covering roofs continues to be a popular method of reroof ing. The NRCA Annual Survey for 1998 indicates that re cover now represents approximately 1/3 of all roofing activity [1]. The same source reports that reroofing now represents over 3/4 of all U.S. low slope roof construction. The decision of whether to replace or re cover a roof occurs 75% of the time that the roofing industry is called upon to perform its job. Even with this renewed interest in reroofing, only conservative, unsub stantiated guidelines have been brought forward to aid the roof ing professional to make this everyday decision. Interface 7
2 Market forces and environmental issues have clearly led to the increased use of re cover. With increased emphasis on producing sustainable building systems, re cover offers the building owner the opportunity to reuse portions of the existing roof system, reducing the amount of construction and demolition waste generated by the roofing industry. Water is the universal concern in reroofing; a roof leak typically initiates the process of determining whether an existing roof system can be repaired or requires reroofing. Clearly, every roof should not be re covered. To successfully re cover an existing roof system that has failed and has water trapped within its cross section, the only means of removing that water in a timely fashion is to have it diffuse downward into the building interior. An estimate of the drying rate must be known to determine whether the components of the new and existing roofing systems can regain and maintain adequate physical properties to perform properly once the drying has been completed. Without this information, the roofing professional is simply guessing the best course of action. Experience in reroofing is helpful but limited because of the number of variables that impact the decision to reroof over wet insulation. He or she may choose the conservative route and require that every wetted portion of a roof be replaced. Given the business climate, he or she may gamble on winning an award by proposing to re cover that roof without sufficient information on the longterm effects of that proposal. A means of determining the correct course of action is computer simulation. Knowing the amount of moisture contamination, roofing system construction, location of the building, and the interior conditions, roofing systems can be modeled to quickly determine if they will dry within a reasonable period of time. However, most computer simulations require that simplifying assumptions be made and the roofing industry has traditionally resisted these techniques as decisionmaking tools until they were validated with field experiments. Recognizing this need, a consortium made up of SPRI and its members, the Roof Consultants Institute (RCI), and Oak Ridge National Laboratory, planned, organized, and performed a whole roof re cover on the church building in Rossville IL. This paper summarizes that joint project. The Building Selection In 1992, the SPRI Re cover Subcommittee proposed that a whole building demonstration experiment be performed that would generate the necessary data to address concerns about roof re cover and developed specifications that the ideal test building should possess. The subcommittee was searching for a building that met the following criteria: The size of the building should be large enough to be considered representative of a typical building but small enough to control the cost. Ideally, the building should be between (3,000 and 10,000 ft 2 (280 and 930 m 2 ); The building should ideally be located in a northern climate and have a conditioned interior; Figure 1. The New Bethel Fellowship Church in Rossville, IL The roof system must be contaminated with an appreciable amount of water; The roof system must have the potential to dry downwardly (no vapor retarder); The roof system should be as typical as possible, i.e., have a metal deck, some insulation, and a traditional membrane; The deck must be structurally sound; Access to the roof, edge detailing, and all other aspects of the reroofing should be considered to minimize the overall project cost; The building owner must be willing to allow performance of an experiment on his building; and Ideally, the building should be owned by a nonprofit organization that would benefit from the reroofing project. The New Bethel Fellowship Church In 1997, SPRI identified a building, the New Bethel Fellowship Church in Rossville, IL (approximately 100 miles or 160 km south of Chicago), that satisfied most of the criteria developed by SPRI for a satisfactory demonstration site. The building is pictured in Figure 1. It was a one story structure that originally served as the town s market. The building had two roof planes and a total roof area of 11,000 ft 2 (1020 m 2 ). The main roof plane made up 95% of the entire roof area. The second roof plane covered a small service elevator at the rear of the building. The existing roof was comprised of an 18 gauge metal deck with 18 gauge metal panels welded to the underside, 39 mm or 1.5 inches of perlite insulation spot mopped with asphalt to the deck, and an aggregate surfaced, four ply organic felt and asphalt BUR. In addition, an asphalt base sheet with a liquid applied aluminum coating had been applied over the BUR in what appears to be a reroofing attempt. The roof had a 1:12 slope that peaked in the middle, equally dividing north and south on each side. The building owner informed us that the original roof was approximately 25 years old. The current owner had acquired the building in 1994, and it had been leaking since that time. The age of the attempted reroofing is unknown. Numerous ineffective temporary repairs were apparent, and the church was financially incapable of replacing the roof. Representatives of SPRI, RCI, and Oak Ridge National Laboratory visited the building in September During that visit, they met with church officials to discuss interest in their building, to assess their willingness in participating in the project, and to examine the roofing system. A visual inspection of the roof was performed and several core samples taken to verify the roof components and the absence of a vapor retarder. The core samples were also used to determine the amount of moisture in the roofing system. Fastener pullout tests were made to use as an indicator of the structural condition of the metal deck. Shortly after the visit, a nuclear densometer moisture survey was performed on the roof to determine the extent and location of 8 Interface September 2001
3 moisture contamination. In summary, the roof system satisfied most of the developed criteria. Permission was obtained from the owner to use the building as a test site and to proceed with the project. The Reroofing The reroofing was performed during the fourth week of June After removing any loose coated felt and brooming off any loose aggregate, 1/2 inch (13mm) wood fiberboard (WFB) in 4 by 8 ft. (1.2 by 2.4 m) sheets was mechanically attached from the eaves and the north and south sides approximately half way up to the peak, using fasteners with a compliance grade base coating that meets the minimum requirements of FM The remaining roof surface was insulated with 2 inch (51mm) polyisocyanurate foam (PIR) in 4 by 8 ft. (1.2 by 2.4 m) sheets attached in a similar manner as the wood fiberboard. Approximately half of the roof area was covered with a black or white thermoplastic olefin (TPO) single ply membrane. The membranes were mechanically attached. White membrane was used on the western half of the roof while black membrane was used on the eastern half. Since two manufacturers donated membrane, the roof was further split to accommodate the inclusion of their membranes. Figure 2 depicts the layout of the insulation and membranes. The flashings were redone, and new edge metal was applied around the roof perimeter. The building was reroofed in this manner because of the interest in examining the effects of roof color and re cover insulation R value on the drying rate of the roof system. The black and white ethylene/propylene membrane had as installed solar reflectances of approximately 0.05 and 0.8, respectively. These values of solar reflectance approximate the limits of membrane color used in roofing applications. When re covering a roofing system, a small quantity of insulation is typically used to separate the new membrane from the existing roof system. If the existing roof system has little or no insulation, the reroofing may include an appreciable amount of insulation. These two extremes were captured with the two types and thicknesses of insulation installed. Because of the interest in modeling the roof system, instrumentation was installed in the roof system during the reroofing. Figure 2.Schematic of re cover insulation, membrane, and instrumentation layout. Six temperature sensors were installed directly under the membrane while two sets of temperature and relative humidity sensors were installed inside the building. These sensors would be used as the boundary conditions of the modeling efforts; the sensors below the membrane would effectively define the climate side of the roofing system while the sensors below the deck would monitor the indoor conditions. All of the instrumentation was connected to a data acquisition system (DAS) installed in the building. The DAS sampled the output of each sensor every minute and computed 15 minute averages that were stored in memory for subsequent analysis. When the re cover was completed, the roof was marked off in a grid pattern on 5 ft. (1.5m) centers. Each intersection of the gridlines was given a two number ID; the two numbers identified the location of all the intersections from the southwest corner of the roof. The first digit identified the intersection s distance (in feet) from the southwest corner in the north south direction while the second digit identified the same parameter in the eastwest direction. A nuclear densometer moisture survey was then performed on the roof. This survey would be used as the baseline to determine the drying rate of the roof. Based on this survey, seven locations were identified on the roof that covered the range of outputs measured by the nuclear densometer. 2 inch or 51mm diameter core cuts were taken at these locations and the moisture content of the existing perlite and re cover insulations from the core cuts were determined gravimetrically. These data were used to calibrate the nuclear densometer and the moisture reading at each intersection of the roof grid was converted to moisture content. Field Sampling After the Reroofing In October 1998, four months after reroofing, the research team returned to perform another nuclear densometer moisture survey. The roof was revisited in June 1999 for more extensive sampling. During this second visit, 450mm or 18 inch square sections of the roof were removed at each of the seven locations sampled in At each location, the membrane was cut to expose an insulation fastener. After verifying that the fastener was tight, the fastener plate was cut off, and foam around the fastener was cut away so a fastener withdrawal test could be performed. After testing the existing fasteners, a 12 in. (300 mm) square section was cut out of the BUR and existing perlite insulation. Specimens of the re cover insulation, perlite, and membrane were coded, placed into plastic bags, and shipped to laboratories for subsequent testing. New fasteners were installed into the deck and pullout tests performed as an indicator of the deck s integrity. All of the pullout tests yielded results in excess of 3100 N (700 lbs.); this pullout force is well in excess of the required holding power of the fasteners and indicates that the aged and previously wetted 18 gauge deck is sufficiently robust. The insulation specimens removed from the test cuts were sent to the laboratory of one of the project participants. Measurements of compressive resistance and R value were 10 Interface September 2001
4 Table 1: Thermophysical properties of existing and re cover insulation materials twelve months after reroofing. performed prior to and after drying the specimens to constant weight. These results are presented in Table 1. The specimens of the re cover membrane removed from the test cuts were forwarded to another participant s laboratory to assess their solar reflectance; results from these tests are summarized in Table 2. To successfully re cover an existing roof, the existing insulation material must be capable of providing a rigid, stable base for the reroofing system. A measure of the existing insulation s capability to provide a satisfactory base is the compressive resistance of the insulation. There is no consensus standard on what percentage of initial properties is required to consider that insulation can be reused [2]. The average compressive resistance of the perlite specimens containing appreciable amounts of water (17/37, 22/67, and 12/102) is 103 kpa (14.9 psi). After drying, the average compressive resistance of these specimens was 105 kpa (15.2 psi). Similarly, the average compressive strength of specimens removed from dry locations before and after drying was 286 and 265 kpa (41.6 and 38.5 psi), respectively. Water clearly degrades the compressive properties of the perlite insulation; even after drying, the compressive strength does not approach the values of the specimens removed from dry areas. Without existing standards or industry consensus, it is unclear whether the wet WFB has maintained adequate mechanical strength to support a roof re cover. The SPRI Re cover Subcommittee has published recommended guidelines to assess the suitability of a roofing system for recover. They state that unless otherwise recommended by the insulation and membrane manufacturer, insulation that has a compressive resistance of less than 100 kpa (15 psi) for mechanicallyattached re cover systems or 70 kpa (10 psi) for ballasted re cover systems should be removed and replaced with new insulation [3]. If this guideline had been followed, perlite insulation located near Grid 12/102 should have been replaced prior to reroofing. ASTM C , Standard Specification for Perlite Thermal Insulation Board [4], specifies a minimum R value requirement for perlite roof insulation of 19.0 m K/W (2.73 hr ft 2 F/Btu in.). The average "as received" R values for the wet and dry perlite locations are 12.3 and 15.8 m K/W (1.8 and 2.3 hr ft 2 F/Btu in.), respectively. After drying, these R values increase to 17.8 and 17.3 m K/W (2.6 and 2.5 hr ft 2 F/Btu), respectively. After drying, the perlite insulation R values are within 10 percent of the ASTM requirements indicating that thermal performance loss due to having been wet is not a permanent or significant problem. The solar reflectance of the white membranes from Manufacturers 1 and 2 decreased from 0.82 and 0.78 to 0.71 and 0.67, respectively, after being exposed for one year on the test roof. When the membranes were cleaned, the solar reflectance increased to 0.82 and 0.76, respectively. The data suggest that the reductions in solar reflectance are primarily due to dirt buildup. The reflectance of the black membranes has not exhibited any significant changes, maintaining their initial solar reflectances of 0.07 and 0.04+/ 0.02 after the twelve month exposure. Table 2. Solar reflectance of white and black TPO membrane materials. Moisture Measurements and Analysis A major goal of this project was to determine how rapidly the existing roof would dry after it had been re covered. To assess the drying rate of the roof system, it was essential to accurately determine the initial concentration and distribution of moisture in the existing roof. In June 1998, just after the reroofing, one of the project participants performed a nuclear densometer moisture survey of the entire roof on a grid with nodes 5 ft. (1.5 m) apart. Seven core samples were taken at the same time and were used to calibrate the output of the nuclear densometer. The relationship between the output of the nuclear densometer and the moisture content of the core samples (determined gravimetrically) was obtained by linearly regressing the data. Coefficients of fit for these regressions exceeded Separate relationships were developed for the different re cover insulation areas; those relationships were then employed to determine the moisture content for each location sampled with the nuclear densometer. The average moisture content for the total roof system was determined by an area weighted sum. Additionally, area weighted moisture contents of the roof areas covered by 12 Interface September 2001
5 Table 3. Moisture contents of various roof areas as a function of time after roof re cover. different re cover insulations and different membrane colors were also determined. Nuclear densometer surveys were repeated 4, 12, and 25 months after reroofing. These data are presented in Table 3. A combined heat and mass transfer model [5] was used to predict the drying rate of the re covered roof system. References [5, 6, 7, 8, and 9] have described, validated, and used this model on low slope roof systems. The model requires as input the geometry and material properties of the components of the roofing system as well as hourly indoor and climatological data. The instrumentation installed in the roofing system was used to define the hourly exterior roof temperature and the indoor vapor pressure and temperature. Hourly values of the roof surface temperatures and monthly averages of the measured interior conditions are used as inputs for the model. A comparison of the measured drying data and model predictions for the perlite insulation re covered with white and black membrane areas are presented in Figure 3. The model overpredicts the drying rate of the perlite insulation and does not appear to capture the impact of membrane color. Possible explanations for these variations include the lack of sensitivity of the nuclear densometer at lower levels of moisture content or the permeance of the metal deck. The fact that we are averaging a number of locations that range from relatively dry to saturated and the average is not similar to the sum of the range of moisture contents present certainly contributes to the differences noted. Areas that are already relatively dry will dry no further, and the Figure 3. Comparison of measured and modeled moisture contents of perlite insulation. nuclear densometer will simply detect no change in moisture content for these locations. These areas, averaged with areas that are drying, will yield an average change in moisture content that is less than the situation where all of the locations contain the same (average) amount of moisture. The model does not predict any significant seasonal variations in the drying rate of the perlite insulation. This result is consistent with our expectations because the wetted insulation layer is relatively protected from seasonal temperature fluctuations by the re cover insulation. However, the model does a fair job at estimating how long the perlite insulation must be exposed to reach an average moisture content that was less than saturation. The model predicted times ranging from 9 13 months while the test data indicates that 12 months were needed. Conclusions This full scale re cover demonstration project has supplied a significant amount of data regarding the hydrothermal performance of re cover roofing systems. It complements another recover demonstration project in a warmer climate that has been previously reported [10]. The following recommendations have been developed from the work completed thus far: The existing roof system cross section should be verified by means of core cuts; Core cuts should also be taken from suspect areas to determine the extent of damage. If areas of insulation are wet, their ability to support the new roofing system should be analyzed. Unless otherwise recommended by the insulation and membrane manufacturer, insulation, after drying, that has a compressive resistance of less than 100 kpa (15 psi) for mechanically attached re cover systems or 70 kpa (10 psi) for ballasted re cover systems should be removed and replaced with new insulation. The top surface of the structural deck can also be examined from the openings created by the core cuts. If deck corrosion is present, the structural integrity of the deck should be checked (see below); The design professional should inspect the deck to determine the extent of replacement or repair required, if any. A complete underside (as well as a topside) examination in questionable areas should be undertaken; Fastener pullout tests should be conducted to verify the structural integrity of the deck, regardless of the method of attachment of the re cover application. This is particularly important when using non penetrating fasteners that are specifically designed for lightweight decks such as cementitious wood fiber and gypsum; The re cover system should be comprised of materials that will not degrade during the drying interval; and The moisture content of the insulation should be measured. Using a simulation tool or an accepted alternate, an estimate of the length of time that is required to dry the insulation should be performed. Insulation that requires 14 Interface September 2001
6 an excessive length of time to dry may create other conditions that lead to roof component failures and should be removed. The length of time to dry varies from roofing system to roofing system. Roofing systems that have been wet for an extended period of time prior to reroofing or contain moisture sensitive components must be dried more rapidly than roofing systems that have just recently failed or contain moisture tolerant materials. References 1. Annual Market Survey, National Roofing Contractors Association, Rosemont IL Sheahan, J.P., and Desjarlais, A.O. Insulation Reuse in Low Slope Roofing: An Industry Survey Proceedings from the Fourth International Symposium on Roofing Technology, Nat ional Roofing Contractors Association, Rosemont IL Flexible Membrane Roofing, A Professional s Guide to Specifications, SPRI, Needham, MA, ASTM C , Standard Specification for Perlite Thermal Insulation Board, Vol , Annual Book of ASTM Standards, American Society for Testing and Materials, West Conshohocken, PA Pedersen, C. (name changed to Rode, C.). Combined Heat and Moisture Transfer in Building Constructions. Technical University of Denmark, Thermal Insulation Laboratory Ph.D. thesis Rode, C., and Courville, G.E. A Computer Analysis of the Annual Thermal Performance of a Roof System with Slightly Wet Fibrous Glass Insulation under Transient Conditions, Thermal Insulation, vol. 15., pp Desjarlais, A.O.; Christian, J.E.; Kyle, D.M.; and Rode, C. Moisture: Its Effects on the Thermal Performance of a Low Slope Roof System. ASHRAE Transactions, 99(2), American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta GA. pp Desjarlais, A.O.; Kyle, D.M.; and Christian, J.E. The Simulated Impact of Climate on the Drying Times of a Wetted Low Slope Roof System. Thermal Insulation, vol. 16, pp Kyle, D.M., and Desjarlais, A.O. Assessment of Tech nologies for Constructing Self Drying Low Slope Roofs. Oak Ridge National Laboratory Report ORNL/CON 380, Oak Ridge TN Patten, J.C.; Sheahan, J.P.; Garrigus, P.C.; Desjarlais, A.O.; and Choiniere, S. The Pembroke Project: A Full Scale Demonstration of Roof Re cover. Proceedings from the Fourth International Symposium on Roofing Technology, National Roofing Contractors Association, Rosemont IL ABOUT THE AUTHORS André Desjairlais is Program Manger for the Building Envelope and Materials Research Programs at the Oak Ridge National Laboratory (ORNL) in Oak Ridge, Tennessee. Desjarlais has been involved in materials research for over 25 years, first as a consultant, and for the last nine years with ORNL. He particiates in ASHRAE, ASTM (as an officer), SPRI (as a director and techni cal chairman), RICOWI (as a director), ANDRÉ DESJARLAIS the Federal Roofing Committee (as past chairman), the National Fenestration Rating Council, and the Building Thermal Envelope Coordinating Committee (as a director). His areas of expertise include building envelope and mater ial energy efficiency, moisture control, and durability. J.P. Sheahan is a past president of RCI. From 1959 to 1978, Jim gained experience in many facets of the con struction industry primarily in water proofing and insulation through his work with Dow Chemical Co. In 1979, he formed J.P. Sheahan & Associates Inc. in Midland, Michigan. He is a Registered Roof Consultant and has been a member of the Cellular Plastics J.P. SHEAHAN Division of the Society of Plastic Industries (SPI), of CSI, ASTM D 08, and BTECC. Jim holds 15 patents on roof related products. Peter Garrigus has worked for TRUFAST Corporation for two years as Vice President of Product Engineering. He is responsible for research and development of fastening systems for the Roofing and Metal Construction Divisions. Previously, Mr. Garrigus man aged the Applications and Engineering Department for a roofing manufacturer. He has extensive background in build ing codes, testing, and design work. PETER GARRIGUS Peter has a Bachelor of Science degree in mechanical engineering from Northeastern University. He is currently chairman of the Single Ply Roofing Institute Recover Subcom mittee, a member of RCI, and former director of SPRI and CRRC. 16 Interface September 2001
Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY
Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Low-slope reroofing guidelines
Low-slope reroofing guidelines by Thomas Bollnow and Joan P. Crowe, AIA The NRCA Roofing and Waterproofing Manual, Fifth Edition, contains reroofing guidelines for steep- and low-slope roofing. The August
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature
Thermal Values Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature relative to changing exterior temperatures. By reducing interior temperature
Nondestructive Evaluation of USCG. 2401 Hawkins Pt. Road Curtis Bay, MD 21226. Provided by: HurleyIR
Nondestructive Evaluation of USCG 2401 Hawkins Pt. Road Curtis Bay, MD 21226 Provided by: HurleyIR On Tuesday May 20 th 2014, HurleyIR provided a nondestructive evaluation for Ruff Roofers of the USCG
COMMERCIAL BUILDING APPLICATIONS
EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that
ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction...2. 2.0 Methodology...2
Standard Practice f Table of Contents 1.0 Introduction...2 2.0 Methodology...2 Appendix A...7 Insulation Board Fastening Patterns 4 feet 4 feet Boards Adhered Membranes...8 Insulation Board Fastening Patterns
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Durapax Coal Tar BUR Application Guide
400 Old Reading Pike, Suite 304 Pottstown, PA 19464 Tel: 610-579-9075 Fax: 610-323-0115 www.durapax.com Durapax Coal Tar BUR Application Guide DESIGN CONSIDERATIONS The proper specifications of any roof
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
07 21 19 Guide Specification STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
07 21 19 STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM 7819 Broadview Road Cleveland, OH 44131 800-522-4522 February, 2011 SPEC NOTE: This guide specification is intended for use when specifying
Nondestructive Evaluation of. Outback Steakhouse/Bertucci s Building at. 2207 Forest Drive, Annapolis, MD. Provided by: HurleyIR
Nondestructive Evaluation of Outback Steakhouse/Bertucci s Building at 2207 Forest Drive, Annapolis, MD Provided by: HurleyIR On Monday, June 2, 2014, HurleyIR provided a nondestructive evaluation for
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
September 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction
T e c h n i c a l n o t e Water Vapor Permeance of Wood Structural Panels and Wood Wall Construction Number J450 February 2009 Controlling against moisture damage in structures depends upon proper system
Get Rid of Roof Problems for Good. How spray foam roofing can protect your building and make you money
Get Rid of Roof Problems for Good How spray foam roofing can protect your building and make you money What is a Spray Foam Roofing System? 300 MILLION Board feet of roofing spray foam installed annually
FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association
FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING Roofing Manufacturers Association Why is a built-up roof considered a multi-ply roof? ARMA defines a built-up roofing system as a roof where multiple
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
Roof Repair Project Report. Fairbank Complex 40 Fairbank Road Sudbury, Massachusetts. February 14, 2014. RBA Project No. 2014007.00.
Report Fairbank Complex 40 Fairbank Road RBA Project No. 2014007.00 Prepared by: 33 Center Street, 2 nd Floor Burlington, MA Tel: 781-273-1537 Fax: 781-273-1695 TABLE OF CONTENTS Roof Repair Project Report...
Article. Protecting the Building Envelope from Water Damage. MemBrain Smart Vapor Retarder & Air Barrier Film
Article Protecting the Building Envelope from Water Damage Vapor Retarders Play a Crucial Role in Moisture Management Whether we like it or not, moisture in the form of water vapor diffusion and humid
Roofing Systems. New Applications / Re-Roofing / Maintenance
Roofing Systems New Applications / Re-Roofing / Maintenance New Roof Installation In terms of the design and installation of an original roofing system (in conjunction with the construction of a new building),
Roof Insulation Building. Energy. Environment friendly e-library
Roof Insulation Building Codes & Energy Efficiency Environment friendly e-library Building Code Driver Buildings consumer almost 50% of all energy. Experts believe that a 30% increase in building efficiency
Presented by: Jennifer Doyle, P.E., RRC, LEED AP
Presented by: Jennifer Doyle, P.E., RRC, LEED AP Moisture Gas: Molecules are spread out "Vapor" suspended in air forms a mixture, present everywhere Liquid: Molecules are closer Rain Condensation Pipes
Crescent Valley High School Roof Investigation
Crescent Valley High School Roof Investigation Project: Corvallis School District Crescent Valley High School Roof Date: July 26, 2011 Report By: Rowell Brokaw Architects: Mark Young, AIA, Chris Andrejko
Thermal Performance of Vegetative Roofing Systems
Thermal Performance of Vegetative Roofing Systems Andre O. Desjarlais, Abdi Zaltash, and Jerald A. Atchley Oak Ridge National Laboratory, and Michael Ennis, SPRI Published in Proceedings of 25 th RCI International
Roof Condition Analysis
Roof Condition Analysis Prepared for: J.W. Nelson John Evans Middle School - Gym Dome 2900 15th Avenue Greeley, Colorado Prepared by: Gregory Ham Coastal Specified Products 5252 Sherman Street Denver,
Georgia State University. Urban Life Building Roof Replacement
ENGINEERING AND ENVIRONMENTAL 140 DECATUR STREET SE, ATLANTA, GA 30303 GEORGIA STATE UNIVERSITY - FACILITIES DESIGN & CONSTRUCTION 34 BROAD STREET, SUITE 100 ATLANTA, GA 30303 DRAWING INDEX A-0 PROJECT
Roof Condition Report. Academy International School 8550 Charity Drive. Colorado Springs, Colorado
Roof Condition Report Academy International School 8550 Charity Drive Colorado Springs, Colorado FOR Mr. Robert Thompson Academy School District 20 10221 Lexington Drive Colorado Springs, Colorado July
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION
HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION ADVANCED TECHNOLOGY FROM OWENS CORNING TRUMBULL ASPHALT TruLo Lo Odor and TruLo Max asphalt raising the roof on asphalt performance.
COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
Avoiding the Landfill: The Recycling of Vinyl Roof Membranes
Avoiding the Landfill: The Recycling of Vinyl Roof Membranes With its European counterparts blazing the trail, the North American vinyl (PVC) roofing industry has entered a new phase in its commitment
Open-cell spray foam & what every contractor
Open-cell spray foam & what every contractor should know Overview Open-cell or Closed-cell? The age old question that many stumped - from industry bloggers to homeowners - is whether to choose opencell
Bituminous Sheet Flat Roofs: Their repair and maintenance
Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and
Natatorium Building Enclosure Deterioration Due to Moisture Migration
Buildings 2012, 2, 534-541; doi:10.3390/buildings2040534 OPEN ACCESS buildings ISSN 2075-5309 www.mdpi.com/journal/buildings/ Case Study Natatorium Building Enclosure Deterioration Due to Moisture Migration
PIMA Technical Bulletin #115. The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing. What is a High R Roof?
PIMA Technical Bulletin #115 The High R Roof: Guidelines for Energy-Efficient Roofing and Re-Roofing About Polysio Insulation Polyiso is a rigid foam insulation used in over 70% of commercial roof construction,
ROXUL COMMERCIAL ROOFING. Understanding Climate Requirements That Drive Performance. roxul.com
ROXUL COMMERCIAL ROOFING Understanding Climate Requirements That Drive Performance High Performance Roofing Insulation Products ROXUL /ROCKWOOL commercial roofing products have been available globally
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping
BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes
*Trademark of The Dow Chemical Company A business unit of The Dow Chemical Company and its subsidiaries Copyright 2003 The Dow Chemical Company.
Dow Chemical is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members.
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Laboratory Report P12850.03.09. Simulated Wind Uplift Testing of Adhered Single-Ply Roofing Systems in accordance with FM Standard 4470, Appendix C
Simulated Wind Uplift Testing of Adhered Single-Ply Roofing Systems in accordance with FM Standard 4470, Appendix C Prepared for: 2100 River Edge Parkway, Suite 175 Atlanta, GA 30328 Date of Issuance:
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS
EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS 1. SCOPE 1.1 This specification covers the type, physical properties and dimensions of Expanded Polystyrene Insulation Board intended for use
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
Best Practices in Roof Design: Sustainable Energy Efficient Reroofing
Best Practices in Roof Design: Sustainable Energy Efficient Reroofing Best Practice Roof Design: Sustainable Energy Efficient Reroofing Presented by Edis Oliver, PE Principal 9511 Lake Creek Parkway Austin,
Fiberglas, Exterior Wall Thermal Insulation
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
FIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012
RACKING AND ATTACHMENT CRITERIA FOR EFFECTIVE MEMBRANE ROOF SYSTEM INTEGRATION Public Version 1: July 9, 2012 Commercial rooftops represent the most available, sustainable and secure real estate for new
Aerial Infrared Roof Moisture Surveys
Aerial Infrared Roof Moisture Surveys INTRODUCTION IR P/PM (infrared predictive/preventive maintenance) is not limited to annual infrared surveys of electrical switchgear. For instance, infrared thermography
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
10DBMC International Conference On Durability of Building Materials and Components LYON [France] 17 20 April 2005
10DBMC International Conference On Durability of Building Materials and Components Wall Cladding System Durability Lessons Learned from the Premature Deterioration of Wood-Framed Construction Clad with
The existing roof angle change terminations and flashings when sound and intact can be reused.
January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing
03/05/14 REVISOR RSI/JC RD3945
1.1 Department of Commerce 1.2 Proposed Permanent Rules Relating to Commerce; Thermal Insulation Standards; 1.3 Materials and Installation 1.4 7640.0100 AUTHORITY; PURPOSE; INCORPORATIONS BY REFERENCE.
NRCA s steep-slope manual is thoroughly revised for 2013
Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA
Predictive Service Life Tests for Roofing Membranes
Predictive Service Life Tests for Roofing Membranes ABSTRACT C.G. Cash, D.M. Bailey, A.G. Davies, Jr., A. H. Delgado, D.L. Niles, R.M. Paroli Simpson Gumpertz & Heger Inc, Waltham, MA USA U.S. Army Corps
High Performance PSA in Sheet Membrane in Water Protection
High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
Water Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
Site Inspection Report
Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G
RECOATING AND RENEWING SPF ROOFING SYSTEMS
RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the
Window Sill Details for Effective Drainage of Water
Construction Technology Update No. 76 Window Sill Details for Effective Drainage of Water By M.A. Lacasse and M.M. Armstrong Satisfactory window performance demands a good product and proper installation.
GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS
GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS 1.0 STATEMENT OF POLICY The overall performance of a roofing system can be affected by factors other than the roof system installation. Henry
ABSeam Panel Overview and Installation Instructions
82 Garden Spot Road Ephrata, PA 17522 717-445-6885 35 Ridge Road Newville, PA 17241 717-776-5951 ABSeam Panel Overview and Installation Instructions Applications: The ABSeam panel is an architectural panel
EPDM System Repair and Cleaning
EPDM single-ply roof systems have represented a third of the volume of the low-sloped commercial market for close to twenty years. The majority of these roofs were installed to receive the manufacturer
CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS
TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes
TECH BULLETIN. Roofing No. Impact of Temperature on Polyiso R-value. Subject: Impact of Temperature on the R-value for Polyisocyanurate Insulation
TECH BULLETIN Roofing No. 3016 Subject: Impact of erature on the R-value for Polyisocyanurate Insulation Date: February 2014 (Revised May 2015) The blowing agents used in polyisocyanurate (polyiso) foam
bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls
A bout your HOUSE before you start Repairing And Replacing Materials Exterior Walls CE 28 h Exterior finish materials are expected to protect the house from the elements while providing an attractive appearance.
Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage
The Science of Rough Opening Preparation and Window Installation to Minimize Air Leakage Sam Hagerman, Hammer and Hand [email protected] Florian Speier, Zola Windows [email protected] Paul Grahovac,
Dollars & Sense of Compliance!
CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors
Proven roofing SyStemS
Proven Roofing Systems Above all. Roofing challenges are never over our heads At GenFlex, we live to tackle and solve the toughest challenges in roofing. The result is a full line of proven, durable roofing
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 41 13 METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC
0 ICC ES Report ICC ES (800) 423 687 (62) 699 043 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3422 Reissued 09/201 This report is subject to renewal 09/2016. DIVISION: 07 00 00 THERMAL AND
CRS Sales & Marketing
TPO - Technology CRS Sales & Marketing Presenter: Gena Miller Thank you AIA, Sign In Sheet (1 Hour CEU-HSW) Division of CRS, Inc. (Commercial Roofing Specialties) 5 Locations (4 state of GA, 1 state of
research highlight Highly Energy Efficient Building Envelope Retrofits for Houses
research highlight June 2012 Technical Series 12-103 Highly Energy Efficient Building Envelope Retrofits for Houses introduction In Canada approximately 30% of all energy is consumed in buildings, with
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
CHAPTER 6 ASPHALT ROLL ROOFING
CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed
JM s Commitment to Meeting Your Single Ply Roofing Needs. JM PVC with DuPont Elvaloy KEE (Ketone Ethylene Ester) Single Ply Systems
JM s Commitment to Meeting Your Single Ply Roofing Needs Johns Manville Roofing Systems helps you defy the elements with the industry s most comprehensive portfolio of commercial roofing solutions. Our
EcoTouch Insulation with PureFiber Technology
PROJECT ENGINEER RESPONSIBILITY: This is a general specification guide, intended to be used by experienced construction professionals, in conjunction with good construction practice and professional judgment.
keep moisture in check by getting fairly hot and facilitating downward time the sun came out, Then, after installation roof no longer got very
Cool Roofs Cause Condensation Fact or Fiction? by Phil Dregger, PE, RRC, Technical Roof Services, Inc. (Editor s Note: Phil Dregger is a professional engineer, registered roof consultant, author, and fellow
Weather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group
Weather Resistive Barriers: Building Science Makes a Case for Two Layers by Dave Olson Technical Services Manager, Fortifiber Building Systems Group Since water intrusion is among the most damaging problems
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING
SECTION 07720 PREFORMED METAL STANDING SEAM ROOFING PART ONE GENERAL DESCRIPTION This section includes pre-formed standing seam metal roofing and related flashings, closures, trim and accessories including,
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT.
INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT. awipanels.com From freezing, sub-zero temperatures to Contents dry heat or high humidity, Mother Nature continually tests the limits of building envelopes. That's