What to Consider When Evaluating Hot Aisle/ Cold Aisle Systems for Your Data Center. by Simplex Technical Staff
|
|
|
- Sandra Simpson
- 10 years ago
- Views:
Transcription
1 What to Consider When Evaluating Hot Aisle/ Cold Aisle Systems for Your Data Center by Simplex Technical Staff
2 What to Consider When Evaluating Hot Aisle/ Cold Aisle Systems for Your Data Center by Simplex Technical Staff Containment means partitioning off the hot and cold aisles, preventing the air from mixing and compromising the temperatures. Hot aisle and cold aisle positioning in the data center has been standard procedure for decades. But in recent years data center managers, seeking the opportunity for more efficiencies, have added the containment component to this formula. Containment means partitioning off the hot and cold aisles, preventing the air from mixing and compromising the temperatures. This has been a vast improvement in maintaining temperatures in the data center, providing maximum system stability and controlling energy costs. Data center managers report savings of as much as 30%, 40% and even 50% and more. Like any technology, though, results can be maximized by some planning and forethought. What follows are points of advice for data center managers as they make plans for hot aisle and cold aisle containment, and as they plan for data centers in general. 1. More Stable Cooling Means Increased Capacity. Think of your data center as a refrigerator. If you add more cooling, that's like turning up the cold setting on your refrigerator, but not having a door on it. The cold air is quickly diluted. It's an inefficient system. Put a door on the refrigerator, however, and you maintain the integrity of that cold air. Your food stays colder and there is less spoilage
3 Effective hot aisle/cold aisle containment is like putting a door on the refrigerator. You are maintaining the integrity of the cold air. This means lower, more stable temperatures in the data center. Data center managers can turn up the thermostat to save energy. The other benefit is the ability to increase Among the benefits to hot aisle/cold aisle containment is the additional capacity data center managers can get from the same space once temperatures are stabilized and better controlled. capacity. The need for more computing power and storage is only going to increase, and in some cases it is going to increase drastically. Thanks to advances in chip development, there is increased capacity in computing power and memory, and along with it comes more heat. Hot aisle/cold aisle containment means you can get additional capacity out of the same space. 2. New Construction vs. a Legacy Data Center. New construction data centers are brand new facilities. HVAC systems, the location of CRAC units, the layout of the data center--all of these things can be planned in advance to maximize the benefits of hot aisle and cold aisle containment. But there are thousands of data centers in operation that are already built, and some have been operating for many years. These are called legacy data centers. Legacy centers far outnumber new facilities, and this is where real energy savings can be accomplished. Hot aisle and cold aisle containment can be implemented in legacy data centers, but there are elements which need to be taken into consideration. Much of the infrastructure--specifically HVAC, raised floors, layout and electrical raceways--are already in place. The challenge in installing hot aisle and cold aisle containment in these data centers lies in effectively evaluating what already exists and careful planning to take maximum advantage of these conditions
4 3. Understand that Data Centers are Complicated. At a chapter meeting of AFCOM, Eugean Hacopians of ARNE Technologies pointed out that data centers today are like living organisms. They are very complicated and many components and factors are in play. "Changing airflow is one thing," said Hacopians, "but changing the behavior of the data center and the people running it--that's the holistic approach that gets more sustainable results." Eugean Hacopians of ARNE Technologies pointed out that data centers today are like living organisms. They are very complicated and many components and factors are in play. The micro processing capacity, the design of the racks, the layout of the room and even the age of the computers are just a few of the countless factors affecting temperatures not only in the room as a whole, but in specific areas. A frequent problem Hacopians cites is the uneven distribution of processor power within a row in a data center. One rack might be loaded up with six or seven kw worth of equipment, and the remaining racks have significantly less. This imbalance can create hot spots within the data center and challenges to cooling. "Look at the cost of running the data center in terms of both the capital expenditure and the cost of operation," said Hacopians. "Computer engineers look at compute cycles, memory usage, input and output, but they don't often look at the power used to run all of this." Hacopians has a suggestion for this: If you want to make your data center manager more cognizant of the operating costs of the data center, change his budget to include paying the energy bill for the data center. He'll start thinking holistically real quick. 4. Get Everyone--Especially Facilities Managers and Your Data Center Manager--on the Same Page. "We've come across a lot of companies where there is not a good relationship between IT and the facilities people," said Jake Stevenson of Enabled Energy. "The larger companies not so much, but especially in companies where there are growing pains, bridging this gap between IT and facilities accomplishes a lot." Eugean Hacopians has much the same opinion. "More often than not a solution is chosen based on a difference of opinion rather than a technology choice," said Hacopians. "Everyone needs to ask if the human factor or the politics of your environment are clouding a reasonable solution."
5 This is the point where senior management needs to get involved, realizing that capital expenditures can be offset by immense savings down the line in energy costs paid from the operating budget, and also the extra productivity (or income, in the case of a colocation facility) from the added capacity. This is everyone's goal. 5. Contact Your Electrical Utility that is, if they have not already contacted you. There is a good chance that your utility has in place a system of rebates and incentives for companies that take proactive measures to decrease power usage in their data centers. Some of these rebates are sizable, and are provided as a credit against future bills. Some utilities, however, will provide a lump sum rebate at the conclusion of construction. That money will go a long way in defraying the cost of your data center. There is a good chance that your utility has in place a system of rebates and incentives for companies that take proactive measures to decrease power usage in their data centers. NetAPP, a large data storage company in Silicon Valley, installed data center curtains, as well as an array of other energy-saving measures, in one of their data centers in They received a $140,000 lump sum rebate up front from Pacific Gas & Electric! Engage your utility before you do anything in your data center in relation to hot aisle/cold aisle containment or other power savings measures, said Corban Lester, a program development manager for Lockheed Martin. Lester spends most of his time working on data center improvements. Many utilities offer rebate programs. Each one of them has its own flavor, but the one thing contacting the utility beforehand is true with nearly all of them. The utility might have certain stipulations in place such as approved contractors, approved equipment, and other requirements. Be aware of these requirements as you begin to plan. Becoming aware of them afterwards or during construction can be a headache. There are often specific time windows. These rebates are funded by grants and those moneys may run out, so verify if they are available and the limitations. Corban Lester recommends that you check out the websites for both The Green Grid ( and the Consortium for Energy Efficiency ( while you are still in the planning stages. These two nonprofit associations are working to bring data center managers, manufacturers and utilities together in order to promote better communication and standardization in the industry
6 There is not always a good transfer of information between all the parties involved in designing, building and approving data centers and the energy savings efforts involved, said Lester. The Green Grid and the Consortium for Energy Efficiency are working on improving that situation. Jon deridder, president of Enabled Energy, recommends making sure your accountant is familiar with IRS Section 179D. This section, which was created by the Energy Policy Act of 2005, allows for tax deductions for the costs of installing certain energy efficient systems in commercial structures. The deductions are as high as $1.80 per square foot, but there are stipulations. A lot of the rebates and tax credits available to companies are either not well understood, or just too hard to find, said deridder. Good consultants will assist you in reaping these benefits. 6. Contact Your Fire Marshal. "You have to know what [fire] jurisdiction you're in and what they accept." Those are the words of Chris Reimer, manager of business development for Facilities Protection Systems, a design/build fire protection contractor in Brea, CA. The firm specializes in data centers. "The fire marshal enforces the local codes/standards and will allow for alternative designs, so he needs to be involved with a project from the beginning," added Reimer. Almost all jurisdictions require that you have a sprinkler system for fire suppression. Sprinkler systems must have eighteen inches of clearance below sprinkler level to insure full dispersal of the water. Curtains or partitions that reach to the ceiling, or enclosures that cover the aisle with ceiling panels, limit the spray pattern and prevent water from reaching a fire. A solution for data center managers using hot aisle/cold aisle containment with curtains, or ceiling panels that cover the aisle, is to use mounting hardware with fusible Like the electrical utility, you need to involve the Fire Marshal in your region as soon as possible. They may have authorized providers and specific requirements for hot aisle/cold aisle containment. links that are held together with an alloy designed to melt at a temperature 15 to 20 degrees lower that the temperature at which fire sprinklers activate. When the fire sprinklers come on, the curtains will have already fallen away, allowing the sprinklers free operating range. An additional measure is to incorporate stainless steel wire lanyards to each mounting bar so that when the fusible links melt and the curtain mount falls away, the hardware will not fall to the floor, but sprinklers will have proper clearance. This allows fire personnel more room to maneuver
7 An alternative to fuse links that melt at high temperatures are electronic fuse links. Electronic fuse links are typically connected to smoke sensors that, when activated, trip the links in the specific area of your data center where the fire is located. Data center managers planning to use partitions as opposed to curtains and are dealing with a sprinkler-based fire suppression system also need to consider the implications. You may need to budget for sprinkler piping in all the aisles of the data center because designing the partitions to fall way in a fire is not an option. Clean-agent fire-suppression systems use HFC (such as FM -200 TM or ECARO-25TM) or inert gas (such as ProInert, Argonite, or Inergen ). These are clean agents dispersed throughout the room to extinguish the fire once smoke has been detected. The individual molecules of these gases are very small. Combined with the velocity at which the gas is dispersed, it will spread throughout the data center quickly. "As long as you are using a clean agent gas that permeates, the gas will be instantaneously homogeneous," added Reimer. "The gas is going to make its way in, up, around and through equipment. It will mix throughout the room and extinguish the fire and allow for anyone remaining within the protected space to breath safely and easily." If you choose to use curtains in your data center, you might all get to demands from the Fire Marshal to source curtain materials that are flame resistant. Simplex recently released an exclusive vinyl material--flexsim --that is the first domestically produced clear flexible curtain vinyl to meet the stringent ASTM E-84 Class 1 rating for flame and smoke generation. FlexSim also meets or exceeds requirements for NFPA-701 and UL Title 19 for compliance with the California Fire Marshal. Fire suppression in the data center is complicated and involved. It is always good policy to check with the Fire Marshal while still in the planning stages and employ the services of an expert. As Chris Reimer points out, the investment you make initially in fire suppression for your data center is worth it, considering the ramifications of fire damage, downtime and lost information in the event of a mishap later. An additional measure is to incorporate stainless steel wire lanyards to each mounting bar so that when the fusible links melt and the curtain mount falls away, the hardware will not fall to the floor, but sprinklers will still have proper clearance. This allows fire personnel more room to maneuver
8 Modular designs, like the AirBlock DCT mounting system from Simplex, allow you to design containment that fits your data center--and make changes when you need to. 7. Realize that Things Change and Base your Purchase of Components on that Reality. You are eventually going to have to make changes in the data center to accommodate growth or reconfigure the layout. This is why it makes sense to look for mounting hardware for curtains and partitions that are modular in design, allowing you to make quick changes. 8. Pay Attention to the Location of A/C or CRAC units. Best practice is to get all the air running in one direction. Optimum placement of the cabinets is perpendicular to CRAC units. This affords a more direct path for hot air to run back to CRAC units. If the cabinets are parallel to the CRAC units it means hot air has to go around or through the racks, which takes more energy to pull it and could cause hot spots throughout the room. Generally best practices call for positioning the CRAC unit directly at the end of the hot aisle. This gives the hot air a straight path back to the unit. You can lose efficiency if you set it up any other way. 9. Your Data Center Does Not have to be Homogenous. In the magazines and on the Internet we see photos of data centers with rows and rows of racks, all the same brand, shape and size. We wish it were that simple. For legacy data centers in particular, as you have expanded and reconfigured the data center, combined facilities, added additional processing power and removed damaged racks, your rack census may consist of three of four different racks and countless sizes. How is one hot aisle and cold aisle containment system going to accommodate all this variation? Make sure AC and CRAC units in the data center are positioned the move through the racks as efficiently as possible. AirBlock data center curtains from Simplex are designed especially for such applications. Versatile mounting systems can be reconfigured to match your changing needs. You can even accommodate offset rows. Curtains of various sizes and lengths are used for racks of varying height, and easily attached expandable filler panels are used to cover gaps for racks that have been temporarily moved
9 10. Keep Ergonomics in Mind. You will install doors and other features to make the data center easier to work in, and to move racks and other items in and out. Think about doors--sliding doors, hinged doors, strip curtains. Think about which way you want the door to open. Look for issues of clearance and traffic. The more sophisticated data center containment systems give you a choice of door configurations that best fit the traffic patterns and other needs of your data center. 11. Isolating the Aisle Means Sealing Everything. Data center managers can spend a lot of energy, time and money making sure they have sealed off the wide open walls in a data center, but they will overlook the small area above a rack or wiring loom, or the hole in a Plexiglas wall through which wires and cables pass. But air is like fluid in a data center. It will take the path of least resistance and you will Good containment design means that hot air and cold are prevented from mixing in all locations, especially over the tops of the racks. experience serious leaks in these overlooked areas as cool air comes rushing through to mix with the warm air. Specially designed short curtains and brush seals can be used to close off these areas. Jake Stevenson at Enable Energy also points out the gaps that exist when racks are moved out of a data center, even temporarily, or when racks of a different type or brand are placed next to each other. Even racks in which one or more of the U s are empty offer a significant enough gap for hot air to travel through the rack back into the cold air aisle. Expandable filler panels like those from Simplex, used to fill the gap between racks when one is removed, guard against this, as do interior rack blanking panels used to fill in a partially empty rack
10 12. Hot Aisle Containment versus Cold Aisle Containment. There is a huge discussion in the industry about whether it makes more sense to isolate the hot aisle or the cold aisle. Different data center experts advocate different theories. The reality is your decision on this question, especially in a legacy data center, is largely decided by your existing infrastructure. Where is the cold air coming from? Where does the warm air have to go in order to be exhausted from the data center or rerouted back into the HVAC or CRAC units? Certain factors will dictate whether you isolate the hot aisle for the cold aisle. Every case is site specific. 13. Consult an Expert Every Step of the Way. Remember the words of Eugean Hacopians: Data centers are very complicated and many components and factors come into play. Every element figures into how your data center is going to react not only to hot aisle/cold aisle containment, but increases in processing capacity, positioning of racks and everything else. The money you spend on a knowledgeable consultant will pay off in lower energy bills and increased stability later on. Founded in 1979, Simplex Isolation Systems designs and manufactures custom cleanrooms that are modular and expandable, as well as a number of products for use in process isolation and contamination control. Simplex is also a prominent name in the data center industry for hot aisle and cold aisle isolation. Their innovative products and materials offer significant advantages. Simplex has worked with some of the leading names in data centers in the U.S., including ebay, AT&T, Walt Disney Studios, Caltech, Oracle and many more Miller Ave. Fontana, CA Toll-free: Fax: [email protected] 10
Product Bulletin. thousands of dollars in excess energy.
Product Bulletin on Data Center Curtains PolySim Our NFPA and ASTM fire-rated material. See page 3 AirBlock Data Center Curtains: Maximize Cooling Efficiency Increase Data Center Capacity Insure System
Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs
WHITE PAPER Reducing Room-Level Bypass Airflow Creates Opportunities to Improve Cooling Capacity and Operating Costs By Lars Strong, P.E., Upsite Technologies, Inc. 505.798.000 upsite.com Reducing Room-Level
AirBlock Data Center Doors
Data Center Doors AirBlock Data Center Doors What makes AirBlock the best? Works with your existing hot aisle/cold aisle isolation system. Doors accommodate different racks within the same data center;
AirBlock Data Center Doors
Data Center Doors AirBlock Data Center Doors What makes AirBlock the best? Works with your existing hot aisle/cold aisle isolation system. Doors accommodate different racks within the same data center;
IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
- White Paper - Data Centre Cooling. Best Practice
- White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION
Cooling a hot issue? MINKELS COLD CORRIDOR TM SOLUTION The heat load in data centers is increasing rapidly, the adaptation of a cooling strategy is often necessary. Many data centers and server rooms use
APC APPLICATION NOTE #112
#112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
Best Practices for Wire-free Environmental Monitoring in the Data Center
White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com [email protected] Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Data Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Data Center Rack Systems Key to Business-Critical Continuity. A White Paper from the Experts in Business-Critical Continuity TM
Data Center Rack Systems Key to Business-Critical Continuity A White Paper from the Experts in Business-Critical Continuity TM Executive Summary At one time, data center rack enclosures and related equipment
Greening Commercial Data Centres
Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential
TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com
MODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS
MODELING THE PERFORMANCE OF FIRE PROTECTION SYSTEMS IN MODERN DATA CENTERS Richard W. Bukowski. P.E., FSFPE and Ralph Transue, P.E. Rolf Jensen and Associates, Chicago, IL 60661 USA Data Centers Society
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
Data Center Cooling. 1-800-693-0351 www.dpstele.com. A guide from: Your partners in UPS Monitoring Systems
Data Center Cooling A guide from: Your partners in UPS Monitoring Systems The air in your server room, especially nearest the processors in your equipment, will rise to dangerous temperatures quickly if
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Raised Floor Data Centers Prepared for the Future
Raised Floor Data Centers Prepared for the Future Raised Floors Protect My Investment by Providing a Foundation for Current and Future Technologies. Creating the Future Proof Data Center Environment The
Great Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
Containment Solutions
Containment Solutions Improve cooling efficiency Separate hot and cold air streams Configured to meet density requirements Suitable for commercial and SCEC endorsed cabinets Available for retrofit to SRA
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360
Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
Driving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
Measure Server delta- T using AUDIT- BUDDY
Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because
Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200
Data Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
Top 5 Trends in Data Center Energy Efficiency
Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,
What to Know When Considering a Cleanroom. by Simplex Technical Staff
What to Know When Considering a Cleanroom by Simplex Technical Staff What to Know When Considering a Cleanroom by Simplex Technical Staff Does your business plan include the development of an area in your
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Server Room Thermal Assessment
PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...
abstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
Cabinets 101: Configuring A Network Or Server Cabinet
Cabinets 101: Configuring A Network Or Server Cabinet North, South and Central America White Paper May 2012 www.commscope.com Contents Background Information 3 What is a network or server cabinet? 3 What
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency
Five Strategies for Cutting Data Center Energy Costs Through Enhanced Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Executive Summary As electricity prices and IT
Thermal Optimisation in the Data Centre
Thermal Optimisation in the Data Centre Best Practices for achieving optimal cooling performance and significant energy savings in your data centre 1. Thermal analysis 2. Cold-Aisle-Containment 3. Seal
Enclosure and Airflow Management Solution
Enclosure and Airflow Management Solution CFD Analysis Report Des Plaines, Illinois December 22, 2013 Matt Koukl- DECP Mission Critical Systems Affiliated Engineers, Inc. Contents Executive Summary...
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers
Power and Cooling Guidelines for Deploying IT in Colocation Data Centers White Paper 173 Revision 0 by Paul Lin and Victor Avelar Executive summary Some prospective colocation data center tenants view
NAISSUS THERMAL MANAGEMENT SOLUTIONS
NAISSUS THERMAL MANAGEMENT SOLUTIONS HIGH PERFORMANCE CLOSED LOOP WATER COOLING SYSTEM NTMS30 30kW SYSTEM Cool the servers, not the room! NAISSUS THERMAL MANAGEMENT SOLUTIONS HIGH PERFORMANCE CLOSED LOOP
Creating Order from Chaos in Data Centers and Server Rooms
Creating from in Data Centers and Server Rooms By Dennis Bouley White Paper #119 Executive Summary Data center professionals can rid themselves of messy racks, sub-standard under floor air distribution,
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE
DATA CENTRES UNDERSTANDING THE ISSUES TECHNICAL ARTICLE Molex Premise Networks EXECUTIVE SUMMARY The term data centre usually conjures up an image of a high-tech IT environment, about the size of a football
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
V RICONDITION C OOLING SOLUTIONS. Next Generation Cold Corridor. Takes modular thinking in energy-efficient data centre design to a new level
V RICONDITION C OOLING SOLUTIONS Next Generation Cold Corridor Takes modular thinking in energy-efficient data centre design to a new level In 2006, Minkels became the first data centre supplier in Europe
Using CFD for optimal thermal management and cooling design in data centers
www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27 Tom Brey, IBM perations Work Group 1 Virtualization Two Steps WP #19 USING VIRTUALIZATIN T IMPRVE DATA CENTER EFFICIENCY
How Row-based Data Center Cooling Works
How Row-based Data Center Cooling Works White Paper 208 Revision 0 by Paul Lin and Victor Avelar Executive summary Row-based data center cooling is normally regarded as a cold air supply architecture that
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
RVH/BCH Data Centres Proposals for Surge Protection and Ventilation
REPORT Proposals for Surge Protection and Ventilation BELFAST HEALTH AND SOCIAL CARE TRUST ROYAL GROUP OF HOSPITALS GROSVENOR ROAD BELFAST BT12 6BA Rev. 01 6th September 2013 Table of Contents 1.0 Ventilation
Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems
NER Data Corporation White Paper Thermal Monitoring Best Practices Benefits gained through proper deployment and utilizing sensors that work with evolving monitoring systems Introduction Data centers are
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Airflow Management Solutions
Data Center Products Airflow Management Solutions Switch N to Eaton. Computational Fluid Dynamics (CFD) model of an optimized data center illustrating cold-aisle isolation and Eaton s Heat Containment
Strategies for Deploying Blade Servers in Existing Data Centers
Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
Data Center Cooling & Air Flow Management. Arnold Murphy, CDCEP, CDCAP March 3, 2015
Data Center Cooling & Air Flow Management Arnold Murphy, CDCEP, CDCAP March 3, 2015 Strategic Clean Technology Inc Focus on improving cooling and air flow management to achieve energy cost savings and
Data Centers and Mission Critical Facilities Operations Procedures
Planning & Facilities Data Centers and Mission Critical Facilities Operations Procedures Attachment A (Referenced in UW Information Technology Data Centers and Mission Critical Facilities Operations Policy)
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
AIR-SITE GROUP. White Paper. Green Equipment Room Practices
AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider
Rack Hygiene. Data Center White Paper. Executive Summary
Data Center White Paper Rack Hygiene April 14, 2011 Ed Eacueo Data Center Manager Executive Summary This paper describes the concept of Rack Hygiene, which positions the rack as an airflow management device,
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Energy Efficiency and Availability Management in Consolidated Data Centers
Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal
Liebert CRV Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment. Precision Cooling For Business-Critical Continuity
Liebert Row-Based Cooling Intelligent Precision Cooling For Data Center Equipment Precision Cooling For Business-Critical Continuity The Intelligent Data Center Cooling Solution: Liebert Trust the industry
Upgrading the PRS datacentres: space requirement. S. S. Mathur, GM-IT, CRIS
Upgrading the PRS datacentres: space requirement S. S. Mathur, GM-IT, CRIS PRS / UTS scenario: then and now Year 2000 PRS: 600 locations UTS: 0 locations Year 2008 PRS 1600 locations E-ticketing Passengers
Energy Efficiency. Bars & RestauRants. www.energia.ie
Energy Efficiency Bars & RestauRants www.energia.ie 2 Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could