By Narendra K. Gosain, Ph.D., P.E., Ray F. Drexler, P.E., and Dilip Choudhuri, P.E.
|
|
|
- Sharon Thomas
- 10 years ago
- Views:
Transcription
1 Structural Forensics investigating structures and their components Evaluation and Repair of Fire-Damaged Buildings By Narendra K. Gosain, Ph.D., P.E., Ray F. Drexler, P.E., and Dilip Choudhuri, P.E. A list of references is available in the online version of this article ( Bracketed numbers [x] within this text refer to the appropriate reference. Reinforced concrete and masonry structures are protected from fire by the cover that is present over the reinforcement, whereas steel structures are protected with externally applied fireresistive materials. All three of these types of structures must be properly evaluated after a fire to assess the nature and extent of the damage. A proper assessment of the structure after a fire event involves both field and laboratory work to determine the extent of fire damage, in order to design appropriate and cost effective repairs. This article presents an overview of how to conduct a forensic evaluation of a fire damaged structure. Two case studies are presented of fire damage evaluation and repair. Damaging Effects of Fire The heat associated with fires may vaporize trapped concrete pore water. The lack of continuous voids for pressure relief creates internal tensile stresses that are relieved by cracks and spalls extending to the surface. [1] Note that spalling may be explosive in higher strength concretes. Additionally, severe heat may cause chemical changes that lead to microcracking (visible only under magnification) and loss of strength and integrity. The effects of fire on concrete are significantly influenced by coarse aggregate type. Siliceous aggregate concrete retains approximately half its capacity at 1200 F while carbonate and lightweight aggregate concretes exhibit near full capacity at 1200 F [2,3]. The thermal protection of reinforcing steel is critical; testing indicates that bars heated beyond 932 º F lose significant amounts of yield strength and ultimate strength [4,5]. Both typical structural steel (A36 and A992) and high strength alloy steels retain approximately 90% of their strength to nearly 600ºF [5]. Significant dimensional changes and distortions occur at temperatures above 800ºF [6]. The heat associated with a fire can cause many types of changes to structural steel elements such as member deformation. Besides large deformations, other less obvious changes can occur at higher temperatures such as loss of normalized microstructure; stress relieving or sensitization of stainless steels; high residual stresses; or embrittlement due to rapid cooling [6] associated with fire fighting efforts. Table 1: Physical Effects of Temperature on Concrete [8] Temperature 0 to 550 F (0 to 290 C) 550 to 1100 F (290 to 590 C) 1100 to 1740 F (590 to 950 C) F (950+ C) Process The evaluation determines the nature and extent of the fire damage and whether repairs are required. This process involves (1) determining when to observe the fire-damaged structure (both before and after cleaning), (2) how to evaluate the post-fire conditions (visually, nondestructively, or destructively), and (3) assessing the structure to determine what, if any, repairs are required. Color Change Figure 1: Process Flow Chart The repair process involves (1) evaluating the options (remove and replace, salvage/ repair, or no action), (2) selecting the repair materials (concrete, steel, or fiber reinforced polymers), and (3) detailing the repairs (preparation, installation, and quality control). Figure 1 summarizes the process. Unless you are working with the fire department to fight the fire, no one should enter the structure until it is safe to do so. Fire damage to the structure is Changes in Physical Appearance and Benchmark Temperatures Concrete Condition None Unaffected Unaffected Pink to red Whitish Grey Buff Surface crazing: 570 F (300 C); Deep cracking: 1020 F (550 C); Popouts over chert or quartz aggregate: 1070 F (575 C) Spalling, exposing not more than 25% of reinforcing bar surface: 1470 F (800 C); Powdered, light colored, dehydrated paste: 1650 F (575 C) Extensive spalling Verify if Structure is Safe to Enter Perform Preliminary Site Visit - Identify Follow-up Areas - Note Temperature Indicators - Determine Cleaning Method Perform Detailed Evaluation - Visual - Non-Destructive Testing - Partially-Destructive Testing Analysis - Compare Allowable and Applied Stresses - Identify Extent of Repairs Design Repairs - Select Materials - Develop Details Sound but strength significantly reduced Weak and friable Weak and friable STRUCTURE 18 September 2008
2 not always obvious. By entering as soon as practical, the engineer can uncover hidden distress and observe the collateral damage to finishes and contents. If the engineer observes contents that are not burned beyond use, the steel is not expected to be damaged. Collateral damages frequently provide good indications of maximum fire temperatures. Evaluation The three stages of evaluation are visual assessment, non-destructive testing, and partiallydestructive testing. STAGE 1 Visual Assessment Cleaning Soot hides most cracks, spalls, and distortions in the structure. The structure may be cleaned by means of dry ice blasting, grit blasting, water blasting, or chemical washing. Chemical wiping or dry ice blasting tends to generate the least collateral damage to the structure. Grit blasting tends to produce large amounts of blasting medium. Water blasting can cause collateral damage to finished areas below the fire (beyond the firefighting water damage). Visual Assessment Coloration Fires consume timber based construction materials from the outside in; the charred exterior material helps protect the interior material. The presence or absence of charred/ burned timber can help determine the fire s temperature and duration. Intense heat may cause chemical reactions that form crystals or change the properties/ color of the matrix and/or aggregates in concrete [8,9]. Table 1 summarizes the changes in concrete (color, surface appearance, and condition) by temperature and can be used to estimate the effect of the fire. Additionally, the rapid cooling of the concrete by firefighting water can cause thermal cracking and superficial surface spalls. Proper evaluation of steels subjected to fire typically requires estimating the temperature and duration of the fire. For clean unpainted steel, a yellowish brown color indicates a temperature of ºF while a blue color indicates a temperature of ºF, other tempering colors are provided in the referenced API document [6]. Visual Assessment Deformation Deformation of structural members and associated materials (coatings, pipes, et cetera) can provide valuable information to develop a heat intensity map. Table 2 provides common temperature indicators. STAGE 2 Non-Destructive Testing Concrete The extent of delamination can be determined by means of chain dragging for large horizontal areas such as slabs, and by means of hammer Table 2: Physical Effects of Temperatures on Various Materials [6,7] Material Examples Condition Temperature Polystyrene Polyethylene Vinyl-based paints UHMW / HD Polyethylene pipe Lead Zinc Aluminum Molded glass Sheet glass Foam insulation; light shades; handles Curtain hooks; radio containers Softens Melts and flows 120 to 140 F (50 to 60 C) 250 F (120 C) Bags; film Shrivels 120 F (49 C) Bottles; buckets Softens and melts 150 F (66 C) Structural steel paint Water and waste pipes Plumbing lead; flashing; storage batteries Plumbing fixtures; flashing; galvanized surfaces Small machine parts; brackets; toilet fixtures; cooking utensils Glass block; jars and bottles; tumblers; solid ornaments Window glass; plate glass; reinforced glass Melts, flows, bubbles, or burns Melts, flows, bubbles, or burns Drops Drops Softened or adherent Rounded Thoroughly flowed Softened or adherent Rounded Thoroughly flowed 250 F (120 C) 375 F (190 C) 550 to 650 F (300 to 350 C) 750 F (400 C) 1200 F (650 C) 1300 to 1400 F (700 to 750 C) 1400 F (750 C) 1450 F (800 C) 1300 to 1400 F (700 to 750 C) 1450 F (800 C) 1500 F (850 C) Silver Jewelry; tableware; coins Drops 1750 F (950 C) Brass Bronze Door knobs; furniture knobs; locks; lamp fixtures; buckles Window frames; art objects sounding for vertical and overhead surfaces. Impulse response can be used to rapidly screen large areas for potential damage. Impact echo testing can also be used to determine the depth and extent of internal fractures. Finally, rebound hammers are frequently used to compare the surface hardness of concrete to locate potential damage. continued on next page 1650 to 1850 F (900 to 1000 C) 1850 F (1000 C) STRUCTURE 19 September 2008
3 examination of dyed concrete thin sections to determine aggregate and paste mineralogy and microstructure. Petrography provides information on cracking such as orientation and location, changes in color, carbonation, paste-aggregate bond, water/cement ratio, air content, desiccation, and depth and extent of damage. Figure 2: Slab separation and joist spalling. Figure 3: Heat damage of seats at level above fire. Non-Destructive Testing Steel Non-destructive evaluation techniques for steel structures include distortion measurements, plumbness or straightness checks, and hardness testing. If the member distortion is minor, it is unlikely the member was exposed to a temperature of more than 1200ºF for any length of time and therefore no consequential metallurgical changes will occur [11]. Measurements of distortion, such as buckling of restrained plates and out-of-plumbness, can provide an indication of maximum temperature reached. Visual inspection of connections that are to remain is critical since connections may have fractured due to the fire event [11]. Weld inspection techniques such as ultrasonic testing, magnetic particle testing, and dye penetrant testing may also be useful in determining the integrity of welded connections. Hardness testing aids in determining the loss of tensile strength in cold and structural carbon steels and, to a lesser extent changes in ductility and toughness. ASTM A370-05, Standard Test Methods and Definitions for Mechanical Testing of Steel Products, provides guidelines for correlating hardness numbers with approximate tensile strengths [12]. Scaling of carbon steels typically begins above 1000 º F and can affect hardness readings [6]. Above 1200ºF the surface will develop a coarse, eroded surface markedly different from mill scale [13]. Partially-Destructive Testing Concrete The primary destructive tests for concrete are compressive strength testing and petrography. The compressive testing gives a general indication of whether or not the concrete meets the design requirements. Strength tests should be correlated with petrographic examinations of nearby cores. The initial heating effects of the fire dessicate the concrete and may cause a moderate increase in the breaking strength of cylinders. The internal condition of fire damaged concrete needs to be evaluated by petrography. This involves both macro and microscopic SAW-CUT SLAB 3 WIDE TO ALLOW DOWEL PLACEMENT. PATCH WITH POLYMER MORTAR AFTER REBAR IS INSTALLED. 2 ½ 2 ½ C L STEM 1 CLR. 1 CLR. ABRASIVE BLAST EXISTING CONC. TO ROUGHEN SURFACE AND REMOVE SOOT. REMOVE ALL DUST WITH COMPRESSED AIR. Partially-Destructive Testing Steel The primary destructive tests for steel are tensile tests to determine yield and ultimate tensile strength. Microscopic examination of fracture surfaces are not commonly per for fire damage evaluations. Engineering Analysis The assessment phase compares the findings of the evaluation phase (damage plots, temperature plots, and allowable stresses based on nondestructive and/or destructive testing) with the analysis findings to determine if the applied stresses in the various elements exceed allowable levels. This then determines the extent, if any, of required removals, replacements, and/or repairs. Based on the results of the assessment, repair materials can be selected, details developed, and repairs installed. Fire Damage Repairs Typically, repair materials are similar to the original construction materials. Timber structures may be repaired with new timbers or composites of steel and timber members, and steel structures are normally repaired with steel. Both concrete and masonry structural elements are frequently repaired with fiber reinforced polymers (FRP) or externally bonded steel members using epoxy adhesive. 6 1 CLR. TYP. 4 TYP Figure 4: Repair detail for slab-joist separation. EPOXY GROUT 10 #5 DOWELS 7 AT CL OF JOIST STEM. SEE PLAN FOR SPACING. #3 BARS BETWEEN 15 O.C. #3 15 O.C. DRILL HOLES THROUGH BRIDGING FOR INSTALLATION OF BARS. #3 O.C. 2 - #7 CONT. REMOVE ALL LOOSE CONCRETE PRIOR TO SHOTCRETING. DO NOT REMOVE EXISTING REBAR. MAINTAIN REBAR IN POSITION. C L STEM EPOXY INJECT CRACK BETWEEN STEM AND FLANGE. NEW SHOTCRETE. SHOTCRETE SHALL TEST 6000 PSI AT 28 DAYS. STRUCTURE 20 September 2008
4 Concrete structures are occasionally repaired with shotcrete as well. Selecting the appropriate repair material is a critical step in the repair process. The repair material must be compatible with the base material, project needs, technical resources available, financial constraints, and multiple other project specific criteria. Case Studies Two case studies are presented to illustrate various types of structural damage and repairs worked on by the authors [10]. The first summarizes the assessment and repair for arson damage to a reinforced concrete stadium structure. The second addresses the evaluation and repair of damage to a steel framed office building. Case Study 1: Stadium Fire An arson fire occurred on an elevated level of a reinforced concrete stadium structure. After the fire department approved the area for entry, initial observations were made. The fire severely damaged the concrete in an area approximately 25 feet by 25 feet above the fire; the concrete joists were deeply spalled, the slab separated from the joists, and severe cracking was present (Figure 2). The fire was intense to the extent that the seating area directly above the fire suffered heat damage (Figure 3). Destructive testing indicated that the strength of reinforcing steel and some concrete above the fire was compromised. Repairs were designed to rebond the slab and joists using L-shaped dowels to hook the slab and joist webs together. The load carrying capacity of the effected slabs and joists were repaired by means of encasing external reinforcement (bars and stirrups) with shotcrete applied to an intentionally cleaned and roughened surface (Figure 4). continued on next page Figure 5: Interior damage due to fire. References 1. Chiang, Chih-Hung and Tsai, Cho-Liang, Time-Temperature Analysis of Bond Strength of a Rebar after Fire Exposure, Cement and Concrete Research, V. 33, No. 10, Oct pp Neville, A.M., Properties of Concrete, 4 th Edition, Pearson Education Limited. 1995, 844 pp. 3. Abrams, M.S., Compressive Strength of Concrete at Temperatures to 1600 F, Temperature and Concrete, SP 25, American Concrete Institute, Farmington Hills, MI, 1971, pp Edwards, William T. and Gamble, William L., Strength of Grade 60 Reinforcing Bars After Exposure to Fire Temperatures, Concrete International, V.8, No. 10, Oct. 1986, pp National Codes and Standards Council of the Concrete and Masonry Industries, Assessing the Condition and Repair Alternatives of Fire-Exposed Concrete and Masonry Members, Fire Protection Planning Report, Aug. 1994, 14 pp. 6. American Petroleum Institute Publication, API RP 579 Fitness-For-Service, 1st Edition, January Erlin, B; Hime, W.G.; and Kuenning, Fire Damage to Concrete Structures, Concrete Construction, V. 17, No. 4, Apr. 1972, 6 pp. 8. Yüzer, N., Aköz, F. and Öztürk, L.D., Compressive Strength Color Change Relation in Mortars at High Temperature, Cement and Concrete Research, V. 34, No. 10, Oct. 2004, pp Tovey, A.K., Assessment and Repair of Fire-Damage Concrete Structures--an Update, Evaluation and Repair of Fire Damage to Concrete, SF-92, T.Z. Harmathy, ed., American Concrete Institute, Farmington Hills, MI, 1986, pp Gosain, Narendra K., Effects of Fire on Concrete, Concrete International, April 2006, pp Tide, R. H. R., Integrity of Structural Steel After Exposure to Fire, AISC Engineering Journal, First Quarter 1998, pp ASTM International Publication, A , Standard Test Methods and Definitions for Mechanical Testing of Steel Products, Current edition approved May 1, Figure 6: Buckled metal deck. Note separation of concrete from metal deck through exploratory opening. 13. Dill, F. H., Structural Steel After a Fire, Proceedings of National Steel Construction Conference, May 5-6, Denver, CO, American Institute of Steel Construction, Chicago, IL STRUCTURE 21 September 2008
5 ADVERTISEMENT - For Advertiser Information, visit Figure 7: Collateral damage to plastics. Figure 8: Structural repairs to limit floor slab displacements. Case Study 2: Occupied Steel High Rise Fire Fire occurred in an occupied space of a The assessment concluded that the steel frame steel framed high rise. The steel framing did not require repairs. However, to prevent was protected by a sprayed fire resistive material. displacements of the separated concrete slab The exposed metal deck supports a above the metal deck, structural repairs were composite concrete floor system. (Figure 5, required (Figure 8). The repairs included page 21). Heat from the fire caused some adding new beams to support the metal deck buckling of the metal decks near the fire and the addition of grout to fill the voids (Figure 6, page 21) and deformation of plastic between the concrete and metal deck. racks (Figure 7) in an adjacent room not directly exposed to the fire. Conclusions The evaluation effort included steel hardness All structures subjected to fire should be readings of the structural steel framing evaluated in a systematic manner to determine members. In addition, concrete cores were the extent, if any, of required repairs. The extracted from the floor slab where the fire intensity and duration of the fire can be estimated occurred and in the deck directly above the by observing the collateral damage; fire for compression testing. No testing was a variety of testing methods and tools are considered necessary in the adjacent room available to evaluate the effects of the fire on with de plastic due to the low temperature both the materials and structural elements. indication. Test results confirmed that These evaluations, combined with an engineer- steel Thank hardness you for was reviewing in the expected this ad range proof for to indicate the upcoming analysis, issue allow of STRUCTURE effective and Magazine. economical To ensure minimal that heat the damage proper to advertisement the steel frame. for your repair company details is run, to be please developed print out and this installed Concrete document, cores fill out indicated the information that compressive below and fax as it needed. to us at: strengths exceeded design requirements. Yes, the ad looks fine. The authors are part of the Structural Diagnostics Services Group (SDSG) at Walter P Moore. No, we require the following changes: Narendra K. Gosain, Ph.D., P.E., is a senior principal and SDSG s executive director. Dr. Gosain can be reached at [email protected]. Dilip Choudhuri, P.E., is a principal and can be reached at [email protected]. Ray F. Drexler, P.E., is a senior associate and can be reached at [email protected]. If we recieve no fax within 48 hours of this , we will assume that there is no change necessary and will run the ad as presented here. Thank you for your assistance. STRUCTURE 22 September 2008
Structural Failures Cost Lives and Time
Structural Failures Cost Lives and Time Recent failures of storage bins, silos and other structures highlight the need to increase awareness of hazards associated with these structures. Since 2010, one
Chapter. Restoration of Damaged Structures
5 Chapter Restoration of Damaged Structures Bringing back a damaged structure to its pre-earthquake state and original strength is called restoration. This is the first step of building rehabilitation.
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
Fire and Concrete Structures
Fire and Concrete Structures Authors: David N. Bilow, P.E., S.E., Director, Engineered Structures, Portland Cement Association 5420 Old Orchard Road, Skokie, IL 60077,Phone 847-972-9064, email: [email protected]
Evaluating. A Case Study
A Case Study Evaluating by Richard B. Stoddard, Washington State Department of Transportation In December 2002, a railroad tanker collision caused a fire under a prestressed concrete girder bridge crossing
Rehabilitation of an Aging Concrete Reservoir Adit Tower
Rehabilitation of an Aging Concrete Reservoir Adit Tower Raymond S. Tombaugh, Senior Coatings Consultant KTA-Tator, Inc. and Mongkol Mahavongtrakul, P.E. Corrosion Control Contract Manager San Francisco
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM
STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM Installed in Pre-engineered Steel Buildings Provides Lowest Cost Construction Method for CORROSIVE AND WET Environments PREFERRED SOLUTIONS, INC.
Experimental assessment of concrete damage due to exposure to high temperature and efficacy of the repair system
MATEC Web of Conferences 6, 06002 (2013) DOI: 10.1051/matecconf/20130606002 C Owned by the authors, published by EDP Sciences, 2013 Experimental assessment of concrete damage due to exposure to high temperature
EAST LYME HIGH SCHOOL
Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805
CEMEX USA - Technical Bulletin 2.1 Proper use of the Rebound Hammer Updated to reflect the changes to ASTM C805 The Rebound Hammer has been around since the late 1940 s and today is a commonly used method
738-B-297 POLYMERIC CONCRETE BRIDGE DECK OVERLAY. (Adopted 02-20-14)
POLYMERIC CONCRETE BRIDGE DECK OVERLAY (Adopted 02-20-14) Description The polymeric concrete bridge deck overlay shall consist of an epoxy polymer that acts together with special aggregate to form an overlay
PRE INSTALLATION MANUAL
REINFORCED CONCRETE PIPE PRE INSTALLATION INSPECTION & REPAIR MANUAL Kentucky Transportation Cabinet Kentucky Department of Highways Division of Materials 1227 Wilkinson Boulevard Frankfort, KY 40601 (502)
Concrete Repair. Applications and Procedures
Concrete Repair Applications and Procedures Objectives Identify what surface preparation is needed Identify typical modes of failure and testing methods How to choose the correct material for the repair
CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS
AN ERGONARMOR COMPANY TECHNICAL INFORMATION SPECIFICATION FOR INSTALLATION 07/11 SUPERSEDES 04/00 PAGE 1 OF 6 CORROSION ENGINEERING RESIN-BASED POLYMER CONCRETES AND GROUTS 1. SCOPE 1.1 This specification
Garver Feed Mill Condition Evaluation
Garver Feed Mill Condition Evaluation OUTLINE Brick masonry overview Condition assessment & methodology Project overview Existing conditions Stabilization Probable costs Summary BRICK MASONRY OVERVIEW
Fire Damage Evaluation. Concrete Garage. Vehicular fires in parking garages are not an
Fire Damage Evaluation and Repair of Precast Concrete Garage By Alfredo E. Bustamante and Michael W. Lee Vehicular fires in parking garages are not an infrequent event. Research by the authors indicates
External Wrapping of Steel Riser Pipe. Case Study HJ3 CS200902
External Wrapping of Steel Riser Pipe Case Study HJ3 CS200902 Introduction Refineries process a wide variety of petroleum products. As part of the process, they rely on cooling towers, which recycle water
Chapter 5 Bridge Deck Slabs. Bridge Engineering 1
Chapter 5 Bridge Deck Slabs Bridge Engineering 1 Basic types of bridge decks In-situ reinforced concrete deck- (most common type) Pre-cast concrete deck (minimize the use of local labor) Open steel grid
UBC Plant Operations Asbestos Work Procedures April 2004
UBC Plant Operations Asbestos Work Procedures April 2004 These Procedures are for use by UBC Plant Operations, Utilities, Housing & Conferences, and IT Services only and are not intended for use by other
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training
Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline
Detailing of Reinforcment in Concrete Structures
Chapter 8 Detailing of Reinforcment in Concrete Structures 8.1 Scope Provisions of Sec. 8.1 and 8.2 of Chapter 8 shall apply for detailing of reinforcement in reinforced concrete members, in general. For
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
the runnerless types of molds are explained post molding operations are described the basic methods of applied decoration methods are examined
Training Objectives After watching the video and reviewing this printed material, the viewer will gain knowledge and understanding of the various plastic finishing processes used in industry and their
Fire-Damage or Freeze-Thaw of Strengthening Concrete Using Ultra High Performance Concrete
Fire-Damage or Freeze-Thaw of Strengthening Concrete Using Ultra High Performance Concrete Ming-Gin Lee 1,a, Yi-Shuo Huang 1,b 1 Department of Construction Engineering, Chaoyang University of Technology,Taichung
Common Perils of Ceramic Floor Tile Systems. Parkway, Suite 220, Plano, Texas 75093; PH (469) 429-9000; email: bbarrett@architecturalengineers.
Common Perils of Ceramic Floor Tile Systems Bart B. Barrett, P.E. 1 and James M. Falls, E.I. 2 1 Central Florida Branch Director, Nelson Architectural Engineers, Inc., 2740 Dallas Parkway, Suite 220, Plano,
Asbestos Management Program
Asbestos Management Program Facilities and Operations Revision #4: February 17, 2012 Page IMPORTANT Asbestos related incidents must be reported IMMEDIATELY to your supervisor Emergency Contacts During
INDUSTRIAL FLOORING INSTALLATION CHALLENGES. James C. Ziegler, ArmorSeal Product Manager Sherwin Williams Cincinnati, Ohio, USA
INDUSTRIAL FLOORING INSTALLATION CHALLENGES James C. Ziegler, ArmorSeal Product Manager Sherwin Williams Cincinnati, Ohio, USA Abstract: Specifier's and contractors not only need to properly evaluate the
SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION 623.10 CONCRETE BONDING COMPOUND.
SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION 623.10 CONCRETE BONDING COMPOUND. 623.10.1 Description. This work shall consist of preparing the surface,
The mechanical properties of metal affected by heat treatment are:
Training Objective After watching this video and reviewing the printed material, the student/trainee will learn the basic concepts of the heat treating processes as they pertain to carbon and alloy steels.
Successful Approach to the Repair of Reinforced Concrete Support Structures in Delayed Coking Units
Successful Approach to the Repair of Reinforced Concrete Support Structures in Delayed Coking Units Thomas Kline Director- Concrete Repair Solutions STRUCTURAL TECHNOLOGIES, LLC Houston, Texas USA November
University of Missouri Hospitals and Clinics. Structural Repair and Protection of Post-tensioned Parking Garage
University of Missouri Hospitals and Clinics Structural Repair and Protection of Post-tensioned Parking Garage 1 University of Missouri Project The University of Missouri Health Care Patient and Visitor
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES
AIR RELEASE, CLEANOUT, AND SEWER MANHOLES **From Hartford IM BLDG(10) DESCRIPTION. This work shall consist of the construction of air release, cleanout, and sanitary sewer manholes; and the furnishing
A Study on the Flexural and Split Tensile Strengths of Steel Fibre Reinforced Concrete at High Temperatures
A Study on the Flexural and Split Tensile Strengths of Steel Fibre Reinforced Concrete at High Temperatures 1 P. Jyotsna Devi, 2 Dr. K. Srinivasa Rao 1,2 Dept. of Civil Engg, Andhra University, Visakhapatnam,
Basement Window Installation Guide Hopper and Sliding
Basement Window Installation Guide Hopper and Sliding americancraftsmanwindows.com Project Requirements: Installation must comply with all applicable building codes. Existing window frame, wall and weatherresistant
Preservation, Repair and Rehabilitation of Concrete Bridges, Pavements and Tunnels in Virginia
Preservation, Repair and Rehabilitation of Concrete Bridges, Pavements and Tunnels in Virginia International Concrete Repair Institute Spring Convention Reno, Nevada March 20, 2014 Michael Sprinkel, PE.,
SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront
PART 1 GENERAL 1.01 Work Included SECTION 08 41 1 ALUMINUM FRAMED ENTRANCES and STOREFRONTS System 402 Flush-Glazed Screw Spline Storefront A. Furnish and install aluminum architectural storefront system
necessary for years of satisfactory service. SmartBlock insulating form concrete walls share the
Chapter 7 PLUMBING AND ELECTRICAL 7.1 Introduction to Plumbing and Electrical Consideration of support services such as plumbing and electrical systems from the preliminary schematics phase through final
September 1, 2003 CONCRETE MANUAL 5-694.900 CONCRETE PAVEMENT REHABILITATION 5-694.900
September 1, 2003 CONCRETE MANUAL 5-694.900 5-694.901 GENERAL CONCRETE PAVEMENT REHABILITATION 5-694.900 Concrete Pavement Rehabilitation is an extremely valuable tool of the Minnesota Department of Transportation
RACQUETBALL, HANDBALL OR SQUASH COURTS AND GYMNASIUM WALL SURFACES
1807 Elmwood Avenue, Suite 275 Buffalo, New York 14207 (800) 543-5155 RACQUETBALL, HANDBALL OR SQUASH COURTS AND GYMNASIUM WALL SURFACES Fiberesin Wall System Provide materials and labor to complete courts
Bonding Agents: The Good, the Bad, and What Works. Bond with Your Concrete
Bonding Agents: The Good, the Bad, and What Works Bond with Your Concrete Jose DonJuan Graduate Research Assistant Kyle A. Riding, Ph.D., P.E. Associate Professor Department of Civil Engineering Kansas
LAYING BLOCK AND BRICK
LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct
Structural Audit of Buildings
International Journal of Civil Engineering Research. ISSN 2278-3652 Volume 5, Number 4 (2014), pp. 411-416 Research India Publications http://www.ripublication.com/ijcer.htm Structural Audit of Buildings
North American Stainless
North American Stainless Long Products Stainless Steel Grade Sheet 2205 UNS S2205 EN 1.4462 2304 UNS S2304 EN 1.4362 INTRODUCTION Types 2205 and 2304 are duplex stainless steel grades with a microstructure,
Materials. Estimating Steel. Players. Materials. Shop Drawings. Detailing Process. Standard shapes. Fabricated members, Built-up sections
Materials Standard shapes W sections, C channels, Structural T, Angles, Pipes, Tubes, Rods and Plates Fabricated members, Built-up sections Adding plates to beam flanges, Stiffeners to beam webs Built
UX-30 PERFORMANCE TESTING SUMMARY REPORT Revision 0
UX-30 PERFORMANCE TESTING SUMMARY REPORT Revision 0 Prepared By: Patrick L. Paquin, EnergySolutions Date Reviewed By: Mirza I. Baig, EnergySolutions Date Approved By: Thomas F. Dougherty, Columbiana Hi
Page & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
INDEX. Sec. No. Items Page Nos.
INDEX Sec. No. Items Page Nos. 1. Types of Pipe............... MSSP- 2 2. Concrete Pipe............... MSSP- 2 thru MSSP-3 3. ABS and PVC Truss Pipe............... MSSP- 3 4. ABS and PVC Solid Wall Pipe...............
LOWELL REGIONAL WASTEWATER UTILITY SPECIFICATIONS FOR THE LOWELL MA CONCRETE FLOODWALL REPAIRS
Concrete Repairs LOWELL REGIONAL WASTEWATER UTILITY SPECIFICATIONS FOR THE LOWELL MA CONCRETE FLOODWALL REPAIRS PART 1 - GENERAL 1.01 DESCRIPTION OF WORK A. The work will occur within the City of Lowell
SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS
Fracture Mechanics of Concrete Structures Proceedings FRAMCOS-3 AEDIFICA TIO Publishers, D-79104 Freiburg, Germany SEISMIC RETROFITTING TECHNIQUE USING CARBON FIBERS FOR REINFORCED CONCRETE BUILDINGS H.
Heat Exchanger Thin Film Foul Release Applications Corrosion Resistant Protective Coatings Grit Blast Surface Prep of Tubular Equipment
Heat Exchanger Thin Film Foul Release Applications Corrosion Resistant Protective Coatings Grit Blast Surface Prep of Tubular Equipment Non-Destructive Examination Heat Exchanger Mechanical Repair Services
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION
PR11 Plastic Repair, Adhesive
Uniform Procedures For Collision Repair PR11 Plastic Repair, Adhesive 1. Description This procedure describes methods for making adhesive repairs to most types of exterior and interior automotive plastics.
Minor Cracks in Horizontal Surfaces
Cracks, chips and broken or flaking areas in concrete are not only unsightly, they can lead to further deterioration of the surface. The result is a costly replacement project as opposed to a simple repair.
Seismic Retrofitting for School Buildings in Japan Nonstructual Seismic Retrofitting
Seismic Retrofitting for School Buildings in Japan Nonstructual Seismic Retrofitting for School Buildings in Japan 8 January 2009 Koichi Shinpo Director, Educational Facilities Research Center National
High Performance PSA in Sheet Membrane in Water Protection
High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is
PC-Concrete Injectable Concrete Anchoring and Repair System
PC-Concrete Injectable Concrete Anchoring and Repair System DESCRIPTION: PC-Concrete is a two component (1:1 ratio), 100% solids, high modulus, structural epoxy paste. PC-Concrete is a solvent free, no
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors
Improving the flood resistance of your home Advice sheet 6: Flood-resilient This sheet provides guidance on identifying different types of floor, assessing the routes floodwater may enter, and describes
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Strength of Concrete
Strength of Concrete In concrete design and quality control, strength is the property generally specified. This is because, compared to most other properties, testing strength is relatively easy. Furthermore,
SECTION 33 12 19 FIRE HYDRANTS
SECTION 33 12 19 FIRE HYDRANTS PART 1: GENERAL 1.01 SCOPE A. Fire hydrants. B. Adjustment of fire hydrants and gate valves. 1.02 SUBMITTALS A. Conform to requirements of Section 01 33 00 - Submittals.
VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10
VOLUME V GUIDELINES FOR DESIGN CONSULTANT TABLE OF CONTENTS APPENDIX B: MASTER CONSTRUCTION SPECIFICATIONS AND PREPARATION GUIDE, DIVISIONS 0-10 SECTION B1: PREPARATION GUIDE B1.1 INTRODUCTION... B1-1
Technical Data Sheet February 2014
Scotch-Weld Technical Data Sheet February 2014 Product Description s are high performance, two-part acrylic adhesives that offer excellent shear, peel, and impact performance. These toughened products
The AQUAFIN Approach to Concrete Repair
Concrete Repair Building Product Systems Waterproofing & Concrete Restoration Decorative Coatings Moisture Vapor Remediation & Flooring Injection Grouting The AQUAFIN Approach to Concrete Repair www.aquafin.net
Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing
1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize
STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA
STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael
Draft Table of Contents. Building Code Requirements for Structural Concrete and Commentary ACI 318-14
Draft Table of Contents Building Code Requirements for Structural Concrete and Commentary ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318 14) Chapter 1 General 1.1 Scope of ACI 318
ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES
ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES PART 1 - GENERAL 1.1 SCOPE OF WORK SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS PULTRUDED SQUARE TUBE LADDER
SPECIAL NOTE FOR ASPHALT WATERPROOFING MIX FOR BRIDGE-DECK OVERLAYS AND ADJACENT APPROACHES
SPECIAL NOTE FOR ASPHALT WATERPROOFING MIX FOR BRIDGE-DECK OVERLAYS AND ADJACENT APPROACHES 1. DESCRIPTION. Asphalt Waterproofing Mix (AWM) is a highly elastomeric, polymermodified, impermeable asphalt
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
Section 02702 SEWER PIPE INSTALLATION AND TESTING
PART 1 - GENERAL Section 02702 SEWER PIPE INSTALLATION AND TESTING 1-1. SCOPE. This section covers the installation and testing of all sewer pipe furnished under the following specification sections: Concrete
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
Lighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: [email protected] Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
APPENDIX C MOISTURE GUIDELINES & MOISTURE TESTING
APPENDIX C MOISTURE GUIDELINES & MOISTURE TESTING Appendix C Moisture Guidelines Determining moisture content is an essential part of quality control within the flooring installation process. Flooring
T R A N S F E R A B L E F U L LY
HSTOPS A WALL OF WATER 22 FT. HIG! F U L LY T R A N S F E R A B L E RESISTS10 PSI ! 1 F U L LY T R A N S F E R A B L E HSTOPS A WALL OF WATER 22 FT. HIG RESISTS10 PSI Guaranteed To Stop Water Even Under
INVESTIGATING AND REMEDIATING LEAKS IN BELOW GRADE STRUCTURES AND UNDER PLAZAS
INVESTIGATING AND REMEDIATING LEAKS IN BELOW GRADE STRUCTURES AND UNDER PLAZAS JUSTIN HENSHELL, FAIA, FASTM HENSHELL & BUCCELLATO, RED BANK, NJ B U I L D I N G E N V E L O P E T E C H N O L O G Y S Y M
APE T CFRP Aslan 500
Carbon Fiber Reinforced Polymer (CFRP) Tape is used for structural strengthening of concrete, masonry or timber elements using the technique known as Near Surface Mount or NSM strengthening. Use of CFRP
The Original Carbon Fiber Reinforced Polymer System
Infrastructure The Original Carbon Fiber Reinforced Polymer System Phone: 52.292.39 Toll Free: 866.38.269 Fax: 52.48.5274 282 E. Fort Lowell Rd. Tucson, AZ 8576 www.dowaksausa.com Test results are supported
HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS
HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS Shiwei William Guan, Ph.D. Vice President, R&D and International Business Madison Chemical Industries Inc. 490
How To Run A Test Lab In Rourkela
TESTING LABORATORY ROURKELA 1. Background: Keeping in view of the growing demand of quality of the products of the industries, Govt. has established Testing Laboratory, Rourkela, under the Directorate
Strengthening and Repair of Reinforced Concrete Structures. Ian Wienholt Business Development Manager
Strengthening and Repair of Reinforced Concrete Structures Ian Wienholt Business Development Manager 34 years of Concrete Repair and Strengthening Experience Over 12,000 Repair Project Over 25,000 PT Projects
Experimental Study on Non Destructive Testing Techniques (NDTT)
Experimental Study on Non Destructive Testing Techniques (NDTT) G.Lalitha 1, K.Bala Showry 2 1 G.Lalitha Assistant Prof, Civil Engineering, BVRIT, TS, India 2 Dr.K.Bala Showry Professor, Mechanical Engineering,
SECTION 03300 CAST-IN-PLACE CONCRETE
SECTION 03300 PART 1 GENERAL 1.01 DESCRIPTION This section describes materials and methods for formwork, reinforcement, mixing, placement, curing and repairs of concrete, and the use of cementations materials
ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES. July 1, 2008 Revision 2
ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES 1 PART 1 - GENERAL 1.0 GENERAL 1.1 REFERENCES: SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS PULTRUDED FIBERGLASS
2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award George Washington University Ross Hall Façade Restoration
2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award George Washington University Ross Hall Façade Restoration 2006 ICRI Baltimore Washington Chapter Outstanding Repair Project Award
Protecting Your Pools Crack Treatments
1 Protecting Your Pools Crack Treatments Scuba Pool Repair Inc. 800 Cristich Lane Campbell, CA 95008 Phone: 408-866-1945 Fax: 408-866-1931 Email: [email protected] www.scubapoolrepair.com Scuba
ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING. January 24, 2014 06610-1
ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING January 24, 2014 06610-1 SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS MOLDED GRATING PART 1 - GENERAL 1.1 SCOPE OF WORK A. The CONTRACTOR
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin
Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin americancraftsmanwindows.com Project Requirements: Failure to follow these instructions may void product
If you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
Part and tooling design. Eastman Tritan copolyester
Part and tooling design Eastman Tritan copolyester Part and tooling design Process Part design Tooling design High cavitation considerations Process Process Project development flow chart Concept OEM generates
CA-48 TECHNICAL SPECIFICATION
CA-48 TECHNICAL SPECIFICATION SafeLane surface overlay Pavement Substrate A Cargill Deicing Technology Product Providing customers with deicing solutions that save lives and enhance commerce. Helping to
Wastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
Autobody/Collision and Repair Technology/Technician CIP 47.0603 Task Grid
1 Secondary Task List 100 ORIENTATION 101 Identify opportunities in the auto body field. 102 Identify basic auto body construction. 103 Identify program rules and policies. 104 Identify government agencies
SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS
1 SECTION 05 7360 ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and
