PROFINET Installation Guideline for Cabling and Assembly
|
|
|
- Georgia Rich
- 10 years ago
- Views:
Transcription
1 PROFINET Installation Guideline for Cabling and Assembly Version 1.0 January 2009
2 PROFINET Installation Guideline for Cabling and Assembly Version 1.0 Jan 2009 Order No.: 8.072
3 PROFINET Order No: Identification: TC This document has been created by the working group Installation Guides (TC2 WG13) of the PROFIBUS User Organization (Profibus Nutzerorganisation, PNO). Published by: PROFIBUS Nutzerorganisation e.v. Haid-und-Neu-Str Karlsruhe Germany Phone: / Fax : / [email protected] All rights reserved, including the right to copy, to reproduce (photocopy, microfilm), to store in data processing systems, and to translate, either in part or completely. 2/99
4 Revision log Version Date Changes/History 1.0 January 31, 2009 first version for publishing 3/99
5 Table of contents 1. Laying PROFINET cables Routing PROFINET cables Copper cables Cable spacing Cable routing in switch cabinets Cable routing inside buildings Cable routing outside buildings Mechanical protection of PROFINET cables Laying copper PROFINET cables General Storage and transportation Temperature limits Tensile strength Using pulling aid and protecting connectors Attaching cable strain relief Pressure load Distortion Flexible PROFINET cables (distortion cables) Trailing and festoon cables Keeping to bending radii Avoiding loop formation Avoiding sharp edges Adding supplementary cables PROFINET copper cable Fiber optic (FO) cables Laying fiber optic PROFINET cables Protecting connectors against contamination Electromagnetic interference (EMI) Underground cables / Connecting building PROFINET cable assembly work PROFINET copper cable assembly work /99
6 2.1.1 General assembling information RJ45 insulation displacement technology M12 connector assembly M12 screwing clamp technology M12 insulation displacement technology Hybrid connectors Fiber optic cable assembly work Fiber optic harnesses handling precautions Protecting connectors against contamination and damage Optical face inspection Optical face cleaning Fiber optic cable Assembly and safety instructions SC-RJ connector M12-Fiber Hybrid connector Other FO connectors Grounding and equipotential bonding Protective ground Functional ground Equipotential bonding Connecting cable shields to the equipotential bonding conductor At the PROFINET node At the cabinet entry Establishing a connection between the cable shield and the equipotential bonding bar Connecting PROFINET nodes Electrostatic discharge (ESD) Connecting PROFINET nodes via plug connectors Terms and definitions /99
7 List of figures Figure 1: Cable distances...17 Figure 2: Laying cables outside buildings...42 Figure 3: Pin-assignment of RJ45 and M12 connectors...44 Figure 4: Connectors - Overview...45 Figure 5: Structure of PROFINET cable...46 Figure 6: Hybrid connectors...57 Figure 7: Quality of optical surface...61 Figure 8: SC-RJ and SC-RJ push-pull connectors...65 Figure 9: M12 Hybrid connectorm12 Hybrid Connector...69 Figure 10: BFOC (ST) Connector...72 Figure 11: Possible connections between shield and potential equipotential bonding bar...80 List of tables Table 1: Symbols indicating important text...13 Table 2: Use of expressions...13 Table 3: Minimum cable spacing according to IEC Table 4: Electrical PROFINET cable types...31 Table 5: Maximum FO cable lengths...39 Table 6: Marking of wire pairs...45 Table 7: Connector pin assignment...47 Table 8: Plastic fiber optic cable...63 Table 9: Glass fiber optic cable /99
8 Preface The aim of the PROFINET Installation Guideline is to support service technicians who have to install PROFINET cables, allowing them to professionally complete their job. The authors of this guideline have attempted to present the information in a simple way. Therefore, no previous knowledge of PROFINET installation is required. However, basic electrotechnical and optical knowledge are considered as useful. Moreover the fiber optic assembly requires specifics skills and it must be carried out by qualified persons. The PROFINET Installation Guideline does not cover basic operational principles of PROFINET. If such information is required, please see the appropriate documents e.g. PROFINET Cabling and Interconnection Technology (Order No: 2.252) available from the PROFIBUS User Organization or comparable technical literature. This document does not replace any previous documents. The previous PNO documents therefore continue to be valid. 7/99
9 Safety instructions The use of the PROFINET Installation Guideline for Cabling and Assembly may involve handling hazardous materials or tools or involve dangerous work. Due to the many and diverse applications of PROFINET, it is not possible to take all options or safety requirements into consideration. Each application makes different demands on the installer. In order to competently judge possible dangers, you must inform yourself about the safety requirements of the respective system before starting your work. Special attention must be paid to the laws and regulations of the respective country in which the system will be operated. You shall also observe general health and safety requirements, as well as the requirements of the company for which the system is being installed. In addition the manufacturer supplied documentation for the PROFINET components used must be considered. PROFINET manufacturers declaration Use only cables and connectors that are provided with a PROFINET manufacturer's declaration. These declarations can be obtained form the PROFINET web site at the following Link: 8/99
10 Power off for installation Make sure all cables and equipment is de-energized when installing electrical components. Touching energized wiring or equipment can cause severe or even fatal injuries. Short circuits can also cause serious and expensive damage to the components. Cable damage Always replace damaged or defective cables. 9/99
11 Liability exclusion The PROFIBUS User Organization has taken utmost care in the preparation of this document and compiled all information to the best of their knowledge. This document nevertheless has only informative character and is provided on the basis of liability exclusion. This document may be subject to change, enhancement or correction without any expressive reference. The PROFIBUS User Organization refuses all types of contractual or legal liability for this document, including the warranty for defects and the assurance of certain usage properties. Under no circumstances shall the PROFIBUS User Organization accept liability for any loss or damage caused by or resulting from any defect, error or omission in this document or from anybody using this document or relying on this document. 10/99
12 Referenced standards EN (2000) Information Technology Cabling Installation Part 2: Installation Planning and Practices Inside Buildings ; EN (2003) Information Technology Cabling Installation Part 3: Installation Planning and Practices Outside Buildings; IEC (2002) Electrical installation of buildings Part 5-54: Selection and erection of electrical equipment Earthing arrangements, protective conductors and protective bonding conductors IEC (2007) Industrial communication networks Installation of communication networks in industrial premises IEC (2007) Industrial communication networks Profiles Part 5-3: Installation of fieldbuses Installation profiles for CPF 3 11/99
13 Symbols This document contains various images. The images are supposed to help the reader understand the text. The images are usually in black and white. A green color is used to highlight important details. The field below shows the color used for this purpose. The following line style represents equipotential bonding and grounding conductors. The following symbol illustrates the connection to functional ground. Notice: Do not used functional ground as protective ground. Protective ground is illustrated using the following symbol: Protective ground is provided firstly to protect people against electrocution. It also provides protection for equipment against faults. Protective ground ensures that any fault currents are passed to ground, so causing the fuse to blow or a protection relay to trip thus de-energizing the system. 12/99
14 Additionally, the following symbols are used. These symbols draw the attention to particularly important text. Symbol Name Description Danger! This symbol indicates danger to life and health. It is extremely important to observe these instructions! Manufacturer instructions Caution! Manufacturer s instructions Notice Tip This symbol indicates a risk of damage to property. Observe these instructions to avoid such material damage. The symbol on the left indicates that you have to observe the manufacturer s instructions. In this case, instructions provided in the PROFINET Installation Guideline are additional information, only. This symbol indicates a risk of malfunctions. You shall observe this information to reduce the risk of malfunctions. Tips provide useful information on how to facilitate your work and improve the system configuration. Table 1: Symbols indicating important text Use of expressions "shall" "should" The use of the word shall in this guide indicates a mandatory requirement. The use of the word "should" in this document indicates flexibility of choice with a strongly preferred implementation. Table 2: Use of expressions 13/99
15 This page is intentionally left blank. 14/99
16 1. Laying PROFINET cables 15/99
17 Laying PROFINET cables 1.1 Routing PROFINET cables Copper cables In order to minimize pickup of electromagnetical interferences, PROFINET cables should be laid separately from other plant wiring. Parallel routing of PROFINET and other cables should be minimized and the distance between these different cables should be maximized. The minimum cable bend radius and tensile strength shall be observed whilst laying PROFINET cables. During installation, additionally observe the applicable national safety and installation regulations for data and power cables. The specifications provided in this guideline are based on applicable IEC standards. 16/99
18 Laying PROFINET cables Cable spacing Table 3 shows the minimum spacing required between PROFINET cables (shielded data cable) and other cables according to IEC The table also mentions two options with a separating web which can be used to separate data cables from power cables. as large as possible Figure 1: Cable distances Generally, the risk of disturbances (crosstalk) decreases when the spacing between the cables increases and when the parallel cable paths get shorter. 17/99
19 Laying PROFINET cables How to read the table To determine the required minimum separation distance between PROFINET cables and other electrical cables, proceed as follows: In the left column (PROFINET cables and cables for...) select which electrical cables you wish to lay in parallel with the PROFINET cables. In the right table area (Spacing), select the type of cable separation that you intend to use. See the column with the relevant cable separation type for the appropriate distance for each cable type. You shall also observe the regulations described below Table 3 for different installation areas. Spacing to PROFINET cable Without or with non-metal cutoff bridge Aluminum cutoff bridge Steel cutoff bridge Signal transmission cable Bus signals such as e.g. other PROFINET cables, PROFIBUS cables, Data cables for PCs, programming devices, printers Shielded analog inputs 0 mm 0 mm 0 mm Power supply cables Unshielded power supply cables 200 mm 100 mm 50 mm Shielded power supply cables 0 mm 0 mm 0 mm Table 3: Minimum cable spacing according to IEC /99
20 Laying PROFINET cables Cable routing in switch cabinets See Table 3 for the required minimum spacing between different categories of cables. In general, the risk of disturbances caused by interference pickup decreases as the spacing between the cables increases. Where cables in different categories have to cross, they should always cross at right angles. Try to avoid running cables in different categories in parallel even for short distances. 90 In case there is not sufficient space to achieve the required spacing between cables of different categories, the cables must be installed in separate, metallic, conducting ducts. Each duct should only carry cables of the same category. These channels can be arranged directly side by side. 19/99
21 Laying PROFINET cables Metallic conductive cable ducts should be fastened every 50 cm to the cabinet frame or walls using screws. Make sure that there is low-resistance connection path between the duct and the cabinet frame. When using painted or coated switch cabinets, this can be achieved by using lock washers. Another option is to remove the coating or paint. However, any bare surfaces shall be protected against corrosion. 50 cm At the cabinet entry, connect the shields of all cables run into the cabinet to the equipotential bonding conductor. For this, the shields should be connected to operational ground across an area of appropriate size. Special installation components are available from various vendors for this purpose. The cables should be mechanically supported above the grounding clamp in order to avoid cable damage caused by cable movement. 20/99
22 Laying PROFINET cables Use a suitable cable entry to feed the cable into the cabinet, e.g. screwed cable glands. OK Do not run incoming external cables in parallel with internal PROFINET cables between the cabinet entry and the shield connector. The same applies to cables of the same category! No Cable routing inside buildings Observe the following when routing cables outside cabinets, but inside buildings: See Table 3 for the minimum spacing between two cables. In general, the risk of disturbances caused by crosstalk decreases when the spacing between the cables increases. 21/99
23 Laying PROFINET cables If the cables are laid in metallic cable ducts, the ducts can be placed directly next to each other. If a common metallic cable duct is used for all categories, observe the clearances specified in Table 3. In case there is insufficient space to do this, different cable categories must be separated by using metallic partitions. These partitions must be electrically connected to the channel over a large area. P R O F I N E T Where cables in different categories have to cross, they should always cross at right angles. Try to avoid running cables in different categories in parallel even for short distances /99
24 Laying PROFINET cables Connect metallic conductive cable trays or ducts to the equipotential bonding system of the building. Observe the instructions on equipotential bonding in chapter 2.3 of this document Cable routing outside buildings It is recommended that fiber optic cables are used for PROFINET links outside buildings. Fiber optic cabling has the following advantages over copper cabling: a) Total immunity to interference pickup. Thus fiber optic cables can be run along side to power cables without problems. b) Electrical isolation between the two ends. So there is no need for equipotential bonding between the two ends of the cable. c) Longer distances are possible with glass fiber cables than with copper. 23/99
25 Laying PROFINET cables Only use approved cables for installations outside buildings. This applies in particular to underground cables. The rules which apply for cable routing inside buildings also apply to disturbancefree routing of PROFINET cables outside buildings. In addition: Lay the cables on metallic conductive cable trays. Connect the joints of the cable trays using a large conductive area. Make sure that the connection is made of the same material as the cable track (no mix of materials). Connect the cable trays to ground. 24/99
26 Laying PROFINET cables Fiber optic (FO) cables are recommended for links between buildings or building parts. No equipotential bonding is required due to the fact that the optic cable is isolating. F O Plant part 1 Plant part 2 A media converter or switch is required as an interface between fiber optic cables and PROFINET copper cables (e.g. between outdoor and indoor systems). 25/99
27 Laying PROFINET cables This page is intentionally left blank. 26/99
28 Laying PROFINET cables 1.2 Mechanical protection of PROFINET cables Mechanical protection is intended to prevent wire/fiber breaks or short circuits on PROFINET cables and mechanical damage to the cable sheath/cladding and shield. Notice: The methods for mechanical protection described here apply to both electrical and FO cables. If the PROFINET cable cannot be laid in a cable tray, use a cable protection tube. In areas with heavy mechanical stress, lay the PROFINET cables in metalarmored conduits. In areas with light to medium stress, plastic conduits can be used instead. If there are 90 bends or building joints (e.g. expansion joints), the cable protection may have to be interrupted. In such cases, make sure that the minimum bend radius of the PROFINET cable is not exceeded. In addition to that make sure that the cable cannot be damaged, e.g. by falling parts. 27/99
29 Laying PROFINET cables In areas where people can step or climb, PROFINET cables should be run in metal armored conduits or cable trays. Notice: It is recommended to use FO cables for links between buildings to overcome the restrictions resulting from the maximum length of 100 m for PROFINET copper cables and for reasons of potential separation and interference immunity. 28/99
30 Laying PROFINET cables 1.3 Laying copper PROFINET cables General During installation be aware that PROFINET cables only have limited mechanical resilience. Cables can thus be damaged or destroyed by excessive tension or pressure. Twisting or sharp bending (kinking) of the PROFINET cable can also have the same effect. The following notes will help you to avoid damage resulting from the installation of PROFINET cables. Notice: Replace all PROFINET cables that may have been damaged or overstrained during installation Storage and transportation During transportation, storage and installation, PROFINET cables must be sealed at both ends using a shrink-fit cap. This prevents oxidation of individual wires and accumulation of moisture and dirt on the PROFINET cable. 29/99
31 Laying PROFINET cables Store and transport the cable reel according to the picture (side view), so that the coiled cable does not entangle Temperature limits The cable manufacturer usually specifies the minimum and maximum ambient temperatures for laying, operation and storage. The mechanical resilience of the cable will significantly decrease outside this temperature range. You will find these temperature specifications in the manufacturer data sheets. Some manufacturers even print the temperature specifications on the cable sheath. Max. temp. The typical temperature range for electrical PROFINET cable, that is installed and not subject to any movement, normally lies between 20 C and +70 C. However, some PROFINET cables have a deviating temperature range. Min. temp. 30/99
32 Laying PROFINET cables As soon as the cable is subject to mechanical stress caused by movement or during installation or when using it in drag chains, the temperature range is reduced significantly. Observe the manufacturers instructions Tensile strength The manufacturer specifies a maximum tensile strength for each cable type. The PROFINET cable can be damaged or even destroyed when this maximum tensile strength is exceeded. This is important because of the high mechanical stress when using drag chains or festoon attachment, or because of the tensile force generated when laying the cable. Please select from the table below the cable type best suited for each application: PROFINET cable Non-flexible (solid core) Flexible Permanent movement Suited for Stationary use without any motion Occasional motion or vibrations Special applications, e.g. permanent motion, vibrations or highly flexible Table 4: Electrical PROFINET cable types 31/99
33 Carefully unreel the PROFINET cable from the drum by hand, only. Laying PROFINET cables Do not apply force to pull it off. No Using pulling aid and protecting connectors Use cable stockings when pulling in PROFINET cables. If the PROFINET cable has already been pre-assembled, protect the connector by using a plastic or metal tube to cover the connector. 32/99
34 Laying PROFINET cables Attaching cable strain relief For all cables that are subject to tensile stress, attach a strain relief about 30 cm from the connection point. The shield connector at the cabinet entry does not provide sufficient strain relief! As the insulation has been removed in order to allow contact to the cable shield, the cable is sensitive to strain and torsion. Assembly components for strain relief are available from various vendors. Device 30 cm Pressure load Do not squash the PROFINET cable, e.g. by walking or driving over it. Avoid excessive loading of PROFINET cables through pressure, e.g. caused by squashing due to improper attachment. 33/99
35 Laying PROFINET cables Distortion Distortion, and in particular, twisting can degrade the electrical properties of PROFINET cables. Therefore, do not distort or twist PROFINET cables whilst unreeling or laying. Special distortionresistant PROFINET cables can be obtained from some manufacturers Flexible PROFINET cables (distortion cables) For PROFINET cables subject to frequent distortion, use flexible, distortion-resistant PROFINET cables. Robots are a typical application. 34/99
36 Laying PROFINET cables Trailing and festoon cables Use only those cables and attachments as trailing and festoon cables that have been approved for this application by the manufacturer. Appropriate components are available from various vendors. Make sure that trailing and festoon cables are not damaged or squashed by other components or cables when in motion. Make sure that the cables in drag chains are not crossed (use appropriate cutoff bridges). Otherwise the cables may be excessively stretched. Ensure that PROFINET cables are laid without distortion or twisting since this can cause damage or change the electrical properties of the cable. Please note that the PROFINET cable shall be capable for the type of usage. For example trailing cables are often not capable for usage as trailing cable. 35/99
37 Laying PROFINET cables Keeping to bending radii Keep to the minimum permissible bending radii. Falling below the minimum bending radius may damage the PROFINET cable. Please consult the manufacturer data sheets for bending radii specifications. Keep to minimum bending radius! For a single bend, the bending radius should typically not be smaller than 10 times the cable diameter. If multiple bending (>10 x) is expected, e.g. due to the connection and disconnection of PROFINET nodes, a larger bending radius is required (typically 20 times the cable diameter). When laying PROFINET cables they can be subjected to additional mechanical load caused by excessive tension. For that reason, larger bending radii are required during pulling than in the installed state. Pulling the PROFINET cable over a quoin can be particularly dangerous. It is therefore advisable to use guide pulleys. 36/99
38 Laying PROFINET cables Use whenever possible ducts or cable channels with radii or chamfers That helps to prevent a kink of the cables Avoiding loop formation Always unreel the PROFINET cable straight from the drum. Never unwind the cable without rotating the drum, since that can cause looping or kinking of the cable. The cable drum should always be mounted so as to rotate as the cable is pulled from the drum. This helps to avoid the formation of loops and associated cable kinks. In the case where a loop has been formed, The loop shall be carefully unwound to avoid twisting or distortion. Never simply pull or stretch the cable straight, since this can damage the PROFINET cable and/or change its electrical properties. 37/99
39 Laying PROFINET cables Avoiding sharp edges Sharp edges may damage the PROFINET cable. You should therefore de-burr sharp edges e.g. the cutting edges of cable ducts using a de-burring tool or file. Use plastic edge protectors to protect edges and angles. Use bends limiting parts in the direction of cable routing at the end of the duct or cable channel. That helps to prevent a kink of the cables Adding supplementary cables When laying additional cables, make sure that existing PROFINET cables and other system cables are not overstrained or damaged. This may happen e.g. in case the PROFINET cables are laid together with other cables on a joint cable tray (as long as permitted by electric safety). Take special care when installing new cables (for repair or upgrades). It is particularly critical to run several cables in one protection tube. This may cause damage to those cables already laid in the tube. Lay the PROFINET cable lastly when running it with other cables in the same cable duct. 38/99
40 Laying PROFINET cables 1.4 PROFINET copper cable The connection between two PROFINET nodes is callled PROFINET channel. In most cases PROFINET channels consist of PROFINET copper cables. The maximum length of a copper cable PROFINET channel is 100 m. 1.5 Fiber optic (FO) cables Because fiber optic cables do not carry electrical currents or voltages they are totally immune to electromagnetic interference. Therefore the routing of fiber optic cables is less critical than for copper cables. However, mechanical protection must be provided for fiber optic cables. In addition minimum bend radius and tensile strength of the cable must be observed. Depending on the distance FO cables with different types of fiber are available. The different types of fiber allow different maximum distances to be covered. Table 5: Maximum FO cable lengths shows the maximum cable lengths for the common types of fiber used. A fiber optic cable requires a connector at each end. However, sometimes additional connectors can be used in a single run of fiber. These additional connectors introduce additional attenuation of the signal and so can reduce the allowable cable length. Table 1: Symbols indicating important text shows the effect of additional connectors on the maximum cable length. Fiber No One Two additional additional additional connectors connector connectors Plastic Optical Fiber (POF) 50 m 43.5 m 37 m Plastic Cladded Fiber (PCF) 100 m 100 m 100 m Multimode fiber 2000 m 2000 m 2000 m Monomode fiber m m m Table 5: Maximum FO cable lengths 39/99
41 Laying PROFINET cables Laying fiber optic PROFINET cables When exceeding the tensile strength, the fibers may be overstreched, may cause higher attenuation, may reduce the lifespan or/and may be permanently damaged. This will cause sporadic or continuous data communication errors. A failure may occur some time later, e.g. several years later, after the installation. Special attention needs to be paid to adhere to the minimum bending radii of the cables. The minimum bending radius of a PROFINET cable is usually 15 times the diameter of the cable. Please observer the data sheets of the manufacturers Protecting connectors against contamination Connectors of fiber optic cables are sensitive to contamination. Attach the provided dust protection caps to protect unused connectors and jacks. Clean the end face of the connector prior to connecting it to a device. Use a lint-free tissue soaked with isopropyl alcohol. Lay the tissue on an even and not too hard surface. In oder do clean the connector move it in one direction over the tissue. Repeat the procedure if necessary at a different spot on the tissue. Inspect the end face with a microscope to ensure the cleaning was effective. 40/99
42 Laying PROFINET cables Electromagnetic interference (EMI) Fiber optic cables are immune to EMI! It is therefore no problem to jointly lay fiber optic cables and copper cables. However take care when re-pulling or replacing fiber optic cables. Do not exceed the maximum tensile load. When using FO cables with steel reinforcement, the reinforcement shall be connected to the equipotential grounding conductor in order to avoid interference Underground cables / Connecting building Cables to be laid in the ground must be of particularly rugged design. When laying cables directly in the ground, exclusively use cables explicitly approved by the manufacturer for this application. Observe the following for direct ground installation: Install the cable in a trench approx. 80 cm below ground level. Observe the applicable local specifications. 80 cm PROFINET Protect the cable against mechanical damage, e.g. using a plastic tube. Place cable warning tape on top. Caution cable 41/99
43 Laying PROFINET cables If copper PROFINET cables are laid in the same trench as other categories of cable, observe the clearances as per Table 3. You can, for example, use bricks as spacers. Because fiber optic cables are immune to interference pickup, these can be laid next to other categories of cable without problems. Watch out for hints to other cables or devices (e.g. cable warning tape) when digging a trench. Damage to other cables or devices (e.g. power cables, gas pipes) may not only result in material damage, but also endangers persons life and health. Switch / Media converter Caution Cable Plastic pipe PROFINET cable Figure 2: Laying cables outside buildings 42/99
44 2 PROFINET cable assembly work 43/99
45 PROFINET cable assembly work 2.1 PROFINET copper cable assembly work There are several types of connectors to connect PROFINET copper cables to a PROFINET node: The 8-pin RJ45 and the M12 connector.. RJ45, multipin, male RJ45, multipin, female M12,multipin, M12, multipin, 4 4 male female Figure 3: Pin-assignment of RJ45 and M12 connectors For an IP20 environment in a cabinet the RJ45 connector is used. In case of increased requirements with respect to the ingress protection (IP65/67) the RJ45- connector with a push pull housing or an M12 connector (D-coding) is used. 44/99
46 PROFINET cable assembly work Push Pull RJ45 (IP65/67) RJ45 (IP20) M12 (IP65/67 Figure 4: Connectors - Overview Hint: The connector type is determined by the interface of the PROFINET node. Select a suitable PROFINET connector type which fits the connector at the device and fulfills your requirements with respect to assembly. For all connectors the way how the cable is connected to the connector differ from manufacturer to manufacturer. Therefore it is not possible to generally describe the assembly of the connectors. The PROFINET cable considered here is a 4-wire round cable. The wires are arranged to form a so-called star-quad. Table 6 shows the color codes of the wire pairs. Pair 1 (Transmitted Data) 2 (Received Data) Wire A Yellow (TD+) White (RD+) Wire B Orange (TD-) Blue (RD-) Table 6: Marking of wire pairs 45/99
47 PROFINET cable assembly work Note that the two opposite wires in the cable create a pair that is used together, to reduce susceptibility to electromagnetic interference. I.e. always use Yellow and Orange together as a pair and White and Blue together as a pair. All wire pairs are enclosed by a plastic-covered aluminum foil and a braid consisting of tinned copper wires. The exact structure may vary depending on the manufacturer. Please observe the manufacturer's specifications. Use only PROFINET cables and connectors that are provided with a PROFINET manufacturer's declaration. Figure 5: Structure of PROFINET cable 46/99
48 PROFINET cable assembly work Signal Function Wire color Pin assignment RJ45 M12 TD+ TD- RD+ RD- Transmit Data + Transmit Data - Receive Data + Receive Data Yellow 1 1 Orange 2 3 White 3 2 Blue 6 4 Table 7: Connector pin assignment Note that to ensure that the screen is effective at high frequencies, the cable screen must always be connected to the local earth at each device. This is normally done through the connector. In addition to that the device should also be locally earthed General assembling information When using connectors with insulation displacement technology observe the following instruction: In case connectors are removed and mounted again, the end of the cable shall be cut off and stripped off again. Otherwise there is a danger that contact might not be fully established. 47/99
49 PROFINET cable assembly work PROFINET Insulation displacement technology usually consists of a compatible system of connectors, cable and stripping tool. You shall only use components that are part of the manufacturer's system in order to avoid problems. The stripping tools for different cable types are in some cases identical in appearance. However, there are often differences in the knife cartridge that is installed in the stripping tool. The knife cartridge must be suited to the PROFINET cable/connector that is being used. Using the incorrect cartridge can result in defective connection of the data wires or screen. Make sure that the shield is properly connected when mounting the connector. Shield and signal wires shall not have any connection to each other Please close the connector carefully.otherwise the wires can be damaged and short circuits can occur. Make sure to use only those PROFINET cables that have been approved by the connector manufacturer for use with the relevant connector. This applies in particular to the use of insulation displacement technology. For IP65 applications make sure that the cable diameter matches the connector housing. This is mandatory to ensure correct sealing between connector and cable RJ45 insulation displacement technology Manuf. instructions Read the instructions from the connector manufacturer. The instructions provide valuable information on the connector design which can vary from one manufacturer to another. 48/99
50 PROFINET cable assembly work PROFINET Insulation displacement technology usually consists of a compatible system of connectors, cable and stripping tool. You shall only use components that are part of the manufacturer's system in order to avoid problems. This type of connector is available from different manufacturers in various styles. The next section shows as an example the principal steps to assemble such a kind of connector. The exact Dprocedure might differ from vendor to vendor. Please observe the manufacturer's instuctions. Open the connector Strip off the cable by using a stripp off tool. This tool is sold suiting to the diameter of the cable. Make sure that you adhere to the given lengths for the shield and the wires. When using the genuine stripping tool for PROFINET cable, this is automatically the case. Insert the wires into the tansparent retainer. Match the color of the wire to the color code of the retainer 49/99
51 Push down the retainer. PROFINET cable assembly work Close the housing. Ensure proper contact between the cable shield and the connector housing. Lock the housing For insulation displacement technology there are appropriate stripping tools for each manufacturer's system. These tools not only strip the insulation, but also prepare the cable shield ready for good connection. They considerably facilitate the assembly of connectors and reduce the assembly time. 50/99
52 PROFINET cable assembly work M12 connector assembly The 4-pin M 12 connector is also an important type of connector for PROFINET. It is frequently used in rugged industrial environments outside the switching cabinet. The connection technology varies depending on the manufacturer. The next section will focus on field assembly connectors for PROFINET. The following connection technologies are available for field-assembly PROFINET cables: Screwed clamp technology Insulation displacement technology M12 screwing clamp technology Manuf. instructions Manufacturer instructions: Read the instructions from the connector manufacturer. The instructions provide valuable information of the connector design. The following description reflects the basic procedure, but by no means does it replace the manufacturer's instructions. Notice: M12 connectors usually consist of several parts. The IP protection type may vary depending on the connector type. After opening the package, check whether all parts are included. The general steps are: 51/99
53 Open the connector. PROFINET cable assembly work Slide the cap, seal and other required housing parts onto the PROFINET cable. Strip the PROFINET cable sheath, ensuring that the stripped cable and shield dimensions fit the connector being used (see the manufacturer s specifications). Strip the cable and the individual cores to fit the connector. Insert the stripped wires into the opened contact clamps. Make sure to correctly assign the wire color codes to the clamps. 52/99
54 PROFINET cable assembly work Tighten the contact clamps using a screw driver (observe torque). Observe torque! Connect the shield. For this, you usually fold back the cable braid over a metal sleeve. Insert a gasket into the sleeve in order to seal the connector. Make sure that the shield wires to not touch the gasked. Ensure there is no shortcircuit between the shield and the data wires. Close and tighten the connector, making sure that the wires inside the connector are not twisted as the screwed housing is assembled 53/99
55 PROFINET cable assembly work M12 insulation displacement technology Manuf. instructions Manufacturer instructions: Read the connector manufacturer s instructions. These instructions provide valuable information on the connector design. The following description reflects the basic procedure, but by no means does it replace the manufacturer's instructions. The main advantage of insulation displacement technology is quicker and simpler assembly procedure. The general steps are: Open the connector. 54/99
56 PROFINET cable assembly work Slide the cap, seal and other required housing parts like seals or contact springs onto the PROFINET cable. Strip the PROFINET cable sheath, ensuring that the stripped cable and shield dimensions fit the connector being used (see the manufacturer s specifications). Do not strip the insulation of thei individual wires. Connect the cable shield. Ensure there is no short-circuit between the shield and the data wires. Insert the wires in the open contact clamps. Make sure that the color of the wires fits the color coding of the contact clamps 55/99
57 Push the two parts of the connector together PROFINET cable assembly work Ensure that the cable strain relief and cable seal are correctly fitted. Close and tighten the connector, making sure that the wires inside the connector are not twisted as the screwed housing is assembled. For insulation displacement technology there are appropriate stripping tools for each manufacturer's system. These tools not only strip off the insulation, but also expose the shield. They considerably facilitate the assembly and reduce the assembly time. Notice: The stripping tools for different cable types are in some cases identical in appearance. However, there are often differences in the knife cartridge that is installed in the stripping tool. The knife cartridge must be suited to the PROFINET cable/connector that is being used. Using the incorrect cartridge can result in defective connection of the data wires or screen. 56/99
58 2.1.6 Hybrid connectors PROFINET cable assembly work Figure 6: Hybrid connectors Hybrid connectors use the same connector for the power supply of the PROFINET nodes and for the connection of the PROFINET cable. This reduces the installation work. Installation can be simplified significantly by using ready-made cables that are available from the cable manufacturers in various lengths. Where connectors have to be assembled on site due to deviating cable lengths or repair work, the manufacturer s instructions shall be observed. The contacts of hybrid connectors are usually crimped. Crimping tools are provided by the connector manufacturers. Use only crimping tools specified by the manufacturer of the connector. Correctly crimped connections are mandatory for a permanent, high-quality connection. 57/99
59 PROFINET cable assembly work 2.2 Fiber optic cable assembly work Manuf. instructions Manufacturer instructions: The specifications of the FO cable components can be found in the data sheets. Always observe this information. The assembly of ready-made fiber optic cables depends on the fiber and connector types. In general, assembly requires a higher precision and higher tool cost with decreasing diameter of the fiber core Fiber optic harnesses handling precautions The following sections describe the generic procedures for harness and installation of fiber optic cables Protecting connectors against contamination and damage Connectors of fiber optic cables are sensitive to contamination. Attach the provided dust protection caps to protect unused connectors and jacks. Do not remove protective cap until ready to mate. If cap is displaced, inspect and recap the connector end. 58/99
60 PROFINET cable assembly work CAUTION Even though the optical connector is protected by dust caps, the connector can be soiled. A soiled optical surface of a connector can reduce the reliability and the quality of the signal transmission. Clean the optical surface ot the connecotre prior to connecting it to a PROFINET device. The process of inspecting and cleaning the face ferrules depend on the kind of fibers used: multimode, single-mode, PCF or POF. The following instructions are general. 59/99
61 PROFINET cable assembly work Optical face inspection Manuf. instructions Manufacturer instructions: Refer to the manufacturer s optical inspection instructions. The following steps can be used as a guideline: Make sure that the fiber link to be examined is not actively transmitting. This is accomplished by physically detaching the connectors from the transmitter or turning off the power of all interface equipment. Protect equipment against re-connection or power on during inspection. Serious eye injury can occur during the inspection of a connector if an active transmitter is connected to the fiber Always verify that the connector under inspection is not attached to a transmitting source. Notice that the wavelengths 850nm and 1300nm, used for the optical transmission, are not visible for the human eye! 60/99
62 PROFINET cable assembly work Use a fiber optic video probe or a hand held fiber microscope to inspect the optical face for contamination, chips, pits, scratches in the core and in the cladding. If dirt, debris or other surface contamination is identified then proceed to the following paragraph for cleaning procedures. The following figures show the basic aspect defaults. Good Pits Bad Debris Bad Scratches Bad Figure 7: Quality of optical surface Optical face cleaning Manuf. instructions Manufacturer instructions: Refer to the manufacturer s cleaning instructions. The following steps can be used as a guideline: 61/99
63 PROFINET cable assembly work The next steps describe the generic steps for optical face cleaning of connectors Use a lint free wipe moistened with isopropyl alcohol or optical quality cleaning fluid to clean the end faces. Rub lightly the ferule on the wipe. Always wipe in one direction not back and forth. Re-inspect the end faces with a fiber optic video probe or a hand held fiber optic microscope and verify that the contamination has been removed. Refer to the former paragraph about inspection. If the contamination is still present, after repeated attempts to clean the ferrules have failed, the contacts must re-polished or replaced. Polishing is a delicate step. It must be made by qualified persons. Contact the connector manufacturer Fiber optic cable Glass or plastic fiber optic cables have a number of outstanding properties: Total immunity to electromagnetic interference. Total electrical isolation of connected devices. Largely tap-proof. Extremely low attenuation when using glass fibers, therefore longer transmission distances. Due to these properties, they are particularly well suited for: Cabling outside of buildings Long distances Environments subject to heavy electromagnetic interference The following categories exist Glass fiber optic cables: single mode (SM) and multi mode (MM) Plastic Cladded Fiber (PCF)) Plastic Optical Fiber (POF) 62/99
64 PROFINET cable assembly work The following commercial cable types are used for industrial applications (Table 8 and Table 9): Plastic Optical Fibre (POF) or Plastic Cladded Fiber (PCF) Installation type stationary or flexible highly flexible Cable marking type B + fiber type type B + fiber type Sheath color green application-specific Wire color orange + black orange + black Maximum attenuation at 650 nm 10 db/km Plastic Optical Fiber 160 db/km (POF) Plastic Cladded Fiber 10 db/km (PCF) Table 8: Plastic fiber optic cable Single Mode(SM) or Multi Mode(MM) Installation type stationary or flexible highly flexible Cable marking type B + fiber type type B + fiber type Sheath color green application-specific Wire color orange + black orange + black Maximum attenuation at 1300 nm (IEC /41) MM: 1.5 db/km SM: 0,6 db/km Table 9: Glass fiber optic cable Manuf. instructions Manufacturer instructions: The selection of a suitable connector (SC-RJ or SC-RJ-Push-Pull or M12 Hybrid Connector) depends on the device to be connected, on the requirements concerning dust and water protection (IP protection type) and on the cable used. 63/99
65 PROFINET cable assembly work For multimode fibers the types 50/125µm and 62,5/125 µm are commonly used. Please observe: When connecting a transmission line from different section, that only section of the same type are put together. Otherwise you will experience additional connection loss at the joints due to the different diameter of the core of the fiber Assembly and safety instructions The assembly of the thin glass fibers requires a high degree of precision that can only be obtained using special tools and training. When glass FO cables are used only occasionally, it is normally more cost effective to use ready-made cables. These are available from the cable manufacturers in various lengths. When using glass FO cables more frequently, connector manufacturers can often advise on tools and training for their connectors. Do not leave the waste of glass fiber assembly scattered around. The thin wires of the fiber optic cable may cause injuries. Dispose of all glass fiber waste safely. Insert the connector into the PROFINET device only after having completed the cable assembly. An unfinished connector assembly can damage the optical interface of any device to which it is connected. Before mating an optical connector examine the optical contact end face with the appropriate tool: the surface must be clean. This means no scratches, pits or debris. Such defects could damage the PROFINET device interface and/or degrade the communications. Special tools are required for the assembly of glass FO cables. These tools are always optimized for a specific connector type and can only be used with this type. Suitable tools, so-called assembly packages, are offered by the connector manufacturers. Training is also required. 64/99
66 PROFINET cable assembly work SC-RJ connector For PROFINET fiber optic networks (glass and plastic), SC-RJ type connectors are commonly used. The SC-RJ connector is a duplex connectore. The two elements of the connector for receiving and transmitting data are hold in place by a frame and are connected and disconnected always as a unit. The base version of this connector is specified for use in cabinets or electronic rooms (protection class IP 20). For harsh environmental conditions or applications requiring IP65/68 protection, the SC-RJ Push/Pull variant can be used. Figure 8: SC-RJ and SC-RJ push-pull connectors Manuf. instructions The manufacturer s instructions shall always be read and followed. By carefully observing the manufacturers instructions and by using the specified tools you will be able to produce optical connections with high quality. The following example shows the typical steps to assemble a connector for a plastic optical fiber. For an optical fiber made of glass, a cleave tool to cut (break) off the fiber is needed. 65/99
67 PROFINET cable assembly work Strip the FO cable sheath. Separate the two wires of the twin wire fiber optic cable with a sharp knife (do not pull apart, since this can break the fibers). Strip the fiber optic cable (observe the correct stripping diameter). Push the connector components onto the optical fiber. The fiber sticks out of the ferrule. Insert the fiber by screwing or crimping into the connector housing. (Use crimp tool specified by the manufacturer of the connectore) 66/99
68 PROFINET cable assembly work Cut off the fiber, sticking out of the ferrule. In case of a glass fiber, use special cleave tool. Polish optical fiber cable in minimal two steps (rough and then fine polish) according the termination instruction. Use a polishing holder to align the connector to the polishing pad and polish it with movements in a shape 8. Remove all traces of abrasive material. Check the quality of the optical surface with a portable Inspection microscope. Make sure that the surface is free of dirt, debris or damage. Good Surface Check the correct mounting of the connector by measuring the attenuation of the cable with the assembled connectors. (Se PROFINET Commissioning 67/99
69 Guideline for further details PROFINET cable assembly work Protect the assembled connector by attaching dust caps Mate the two parts of the SC-RJ connector into the frame to create the duplex connector. Observe the manufacturers instruction how to place the transmitting and the receiving part of the connector into the frame. As a support the PROFINET FO cable has indicators printed on the cable, that show the transmission direction. Kodiernase 68/99
70 PROFINET cable assembly work M12-Fiber Hybrid connector The M12 Fiber Hybrid connector provides two optical connections (for data) and two optional electrical connections (for device power supply, AWG 20). M12 Fiber Optic Connectors are available for Multimode, Single-mode, POF and PCF fibers. Figure 9: M12 Hybrid connectorm12 Hybrid Connector Manuf. instructions The manufacturer s instructions shall always be read and followed. By carefully observing the manufacturers instructions and by using the specified tools you will be able to produce optical connections with high quality. The following example shows the typical steps to assemble a Hybrid connector. For an optical fiber made of glass, a cleave tool to cut (break) off the fiber is needed. Cable preparation Slide the cap, seal and other required housing elements onto the cable. 69/99
71 PROFINET cable assembly work Strip the external jacket and the 2.4mm fiber jacket. Strip of the insulation of the fibers according to the instructions of the manufacturer Gluing Insert the glue inside the contact using a syringe. Glue Insert the fiber into the contact and protect the exceed fiber with a cap. - Polymerize (cure) the glue. NOTE: For POF, if you wish a quick installation and if the optical budget can accept higher insertion loss, the gluing and polishing step can be replaced by a cutting step. Mounting Score the exceed fiber. Insert the contacts into the plugs ensuring that the fibers are crossed over between the two connectors 70/99
72 PROFINET cable assembly work Note: The crossover requires that a fiber pair shall be crossed over in the cable. The crossover ensures that the transmitter at one end of the cable is connected to the receiver at the other end. A fool proofing (keying) system within the plug and socket ensure the crossover is maintained when connection is made. As additional support the wires of the PROFINET cable carry indicators that indicate the direction of the data flow Screw the housing elements to close and seal the connector. Polishing Place the ferrule and plug in the polishing tool. Polish by pressing the plug and moving the tool onto polishing paper in 2 steps: coarse and fine polishing. An automated polishing process can be used for volume production. End face inspection Inspect the end face with an inspection microscope to be sure that no dirt, no debris or other surface contaminations are present and that the surface is free of scraces. Perfect face 71/99
73 PROFINET cable assembly work Optical measurement Measure the attenuation of cable and connectors to ensure that al mountingsteps have been made correctly. (Se PROFINET Commissioning Guideline ) Other FO connectors For fiber optic connection in existing plants in many cases a connector BFOC/2,5 is still in use. The connector is also know under the trade mark "ST -Connector". This connector has been in use as industrial grade connector for many years and is available for all PROFINET fiber types (plastic as well as glass) Figure 10: BFOC (ST) Connector The ST connector is a single wire connector with bayonet latch. As both fibers of a connection are connected individually, special attention has to be taken for the correct assignment of sending and receiving fiber. The mounting of the connector is comparable to the mounting of the SC-RJ connector. 72/99
74 PROFINET cable assembly work 2.3 Grounding and equipotential bonding Good grounding and equipotential bonding are vital to the resistance of PROFINET networks to electromagnetic interference. Grounding of the PROFINET cable screen shall be done at both ends of every cable (i.e. at each device) to reduce the impact of electromagnetic interference. Equipotential bonding ensures that the ground potential is identical throughout the entire PROFINET network, so providing protection against equipotential bonding currents which could otherwise flow through the PROFINET cable shield. Basic information on the installation of grounding and equipotential bonding is given below: Manuf. instructions Manufacturer instructions: Read and observe the manufacturer s instructions. These instructions provide important information on how to best connect the PROFINET node to ground and to the equipotential bonding conductor Protective ground Protective ground is principally provided to protect people against electrocution in the case of a fault. The protective ground also protects devices, machines and plant equipment against more serious damage in the case of faults. The frame, case or cabinet of electrical equipment shall be connected to protective ground via ground wire that can carry the full fault current. Protective ground is illustrated by the following symbol: 73/99
75 PROFINET cable assembly work As protective ground is part of the general electrical system, it is not described in more detail in this document. Always observe the applicable standards and regulations! Notice: Some PROFINET nodes are equipped with a protective ground connector. These are mainly PROFINET nodes with an additional, higher-voltage power supply. Establish a protective ground connection in compliance with the applicable regulations for these devices Functional ground Functional ground is used to divert electromagnetic interference voltages to ground. This improves the interference resistance of data transmission. The functional ground is used to earth the screen of the cable and device case so diverting any interference pickup to ground. Manuf. instructions Manufacturer instructions: The manufacturer s documentation will generally provide important information on how to best connect the PROFINET node to ground and to the equipotential bonding conductor. Some PROFINET nodes are equipped with a functional ground connector terminal. This terminal is marked with the symbol for functional ground. Connect the functional ground terminal of the PROFINET node to the functional ground connector of the system using a large cross-section cable which is as short as possible. In many cases, the entire metal construction of the system is used as functional ground. Other devices use the installation mounting as functional ground. You shall therefore connect the DIN rails of the system to functional ground. 74/99
76 PROFINET cable assembly work For grounding the PROFINET nodes, use a copper cable with appropriate crosssection (at least 2.5 mm²). Grounding cables usually have a green-yellow insulation. The green-yellow marking is mandatory in some countries (green only in the USA). Functional ground is represented using the following symbol: Functional ground symbol Equipotential bonding Equipotential bonding is intended to provide identical grounding potential throughout the entire system. Therefore no equalizing currents will flow through the PROFINET cable shield. Use a copper cable or a tinned grounding rod as the equipotential bonding conductor for equipotential bonding in the system and between the system components. Connect the equipotential bonding conductor to the grounding clamp or bar across a sufficiently sized surface. 75/99
77 PROFINET cable assembly work Interconnect all shields and ground connectors (if any). As the name suggests, equipotential bonding ensures that the potential is equal in all plant parts. This avoids equipotential bonding currents across the PROFINET cable shields. PROFINET Plant Equipotential bonding Functional ground Connect the mounting area (for example top-hat rails) with the equipotential bonding conductor. Connect the plant equipotential bonding system with the building's equipotential bonding system as many times as possible. Plant Building s equip. bond. If components are coated, remove the coating from the contact areas before establishing the connection. After installation, any exposed contact areas shall be protected against corrosion, for example by applying a zinc-based, paint or varnish coating. 76/99
78 PROFINET cable assembly work All equipotential bonding connections shall be protected against corrosion. This protection can be achieved using special anti-corrosive compounds or by varnishing or painting the contact areas after assembly. Use self-locking screw or clamp connections. Make sure that the connection will not disengage inadvertently. Use crimped wire end sleeves or cable lugs for flexible equipotential bonding cables. Do not tin the cable ends (this is no longer permissible). Install the equipotential bonding as close as possible to the PROFINET cable. Equipotential bonding cond. PROFINET Interconnect the individual parts of all metal cable trays. Use special connecting elements that are available from the manufacturer for this purpose. Make sure that the connecting elements are of the same material as the trays. 77/99
79 PROFINET cable assembly work Connect the metal cable trays to the equipotential bonding system as often as possible. Equipotential bonding system Use flexible grounding straps at expansion joints or articulated joints. Grounding straps are normally available from the cable manufacturers. When fiber optic cables are used for interconnections between buildings or parts of buildings. No equipotential bonding is required due to the immunity of fiber optic cables to electromagnetic interference, as long as the cable is free of metal Connecting cable shields to the equipotential bonding conductor The shield is an important part of the PROFINET copper cable. It shields the data wires in the cable against electromagnetic interference coming from the environment. To make sure that the shield can properly provide this function, it must be connected to the plant s equipotential bonding system. The general principles of connecting the PROFINET copper cable shield to the equipotential bonding system follow: 78/99
80 PROFINET cable assembly work At the PROFINET node Equipotential bonding is realized via the relevant connectors as well as by connecting the cable to the equipotential bonding bar. OK At the cabinet entry At the cabinet entry, connect the PROFINET cable shield to the equipotential bonding conductor across a large area and as close as possible to the point of entry. This prevents interference acting on the PROFINET cable outside the cabinet from being conducted into the cabinet. Install an equipotential bonding bar behind the strain relief at the cabinet entry. Chapter shows how to connect the shield to the equipotential bonding bar. 79/99
81 PROFINET cable assembly work Establishing a connection between the cable shield and the equipotential bonding bar There are several ways for connecting the cable shield and the equipotential bonding conductor over a large area. The figure below illustrates three connection options. These approaches have proven to be successful in daily operation. Figure 11: Possible connections between shield and potential equipotential bonding bar Make sure that the PROFINET cable is not squashed by the connection between the shield and the equipotential bonding bar. Use a shield clamp that is appropriate for the cable diameter. Any distortion can deteriorate the electrical properties of the PROFINET cable. 80/99
82 PROFINET cable assembly work Observe the following when establishing the shield connection: Remove the PROFINET cable sheath only for the required connection length. The PROFINET cable is susceptible to mechanical damage in the area where the sheath has been removed. OK No Be careful not damage the shield when stripping off the PROFINET cable sheath. 81/99
83 PROFINET cable assembly work Do not use the shield connection as a strain relief. This would impair the contact between the shield and the equipotential bonding bar. Exception: installation elements specifically designed for this application. No strain relief! Secure the PROFINET cable before and after the position of shield application. The PROFINET cable which is sensitive in this region can thus be protected against buckling and bending. Pay particular attention to strain relied when the cable is subjected to movement,. Use only connection elements that are appropriate for the diameter of the stripped cable. Do not attach the equipotential bonding bar to coated surfaces. Galvanized or chromed surfaces, for example, are well suited. Use tinned, galvanized or otherwise galvanically treated installation material. This is protected against corrosion and establishes permanent, good contact. 82/99
84 PROFINET cable assembly work Establish the connection between the shield and the equipotential bonding bar only via the braided shield. PROFINET cables are also equipped with an additional foil screen. This must not be used for connection. For improved stability, it is usually plastic-coated on one side. This plastic coating has an insulating effect. OK No 83/99
85 This page is intenionally left blank 84/99
86 3 Connecting PROFINET nodes 85/99
87 Connecting PROFINET nodes Electrostatic discharge (ESD) Electronic components are however extremely sensitive to high voltages. In the case where the electrostatic discharge passes to an electronic component or circuit, the component may be destroyed. PROFINET nodes include sensitive electronic circuitry which can be damaged by electrostatic discharge. Therefore, when handling PROFINET components, you shall observe the following precautions in order to protect them from being damaged. Touch a grounded metal part before handling any PROFINET components or devices. This will cause your body to be discharged. Do not touch the plug or screw contacts of the component. Only touch the housing when handling connectors. 86/99
88 Connecting PROFINET nodes Disconnect the PROFINET cable from all PROFINET nodes before starting to work on any PROFINET cable. Completely assemble the PROFINET cable with connectors on each side before connecting it to a PROFINET node. PROFINET node PROFINET PROFINET node If cables are directly connected, touch the insulation, not the wires Connecting PROFINET nodes via plug connectors PROFINET nodes are usually equipped with copper cables with 8-pin RJ45 or M12 plug connectors. This is a very simple type of connection. A ready-made PROFINET cable can be connected by fitting together the connector plugs. In the same way, the PROFINET cable shield is connected to the PROFINET. The following instructions apply for all types of plug connections for copper cables. The displayed plug connectors only have symbolic meaning. 87/99
89 Connecting PROFINET nodes Due to its design, it is normally impossible to turn a plug connection out of position. However, before joining the components nevertheless check how the socket and connector fit together. You can thus avoid damage to the connectors. This is of special importance when using round connectors, e.g. M12. Only touch the housing of plug connections If cables are directly connected, touch the insulation, not the wires. 88/99
90 Connecting PROFINET nodes Do not apply excessive force when establishing a plug connection. If the connectors do not fit smoothly, check them for possible defects. A connector pin may be deformed. In such a case, replace the defective connector /99
91 This page is intentionally left blank 90/99
92 4 Terms and definitions 91/99
93 Terms and definitions Glossary Communication In the case of PROFINET, the electronic transfer of digital data from one network user to another. DIN Deutsches Institut für Normung (German Standardization Institute) ( ) EN (European Standard) European Standard acknowledged and applied by all European countries. Many of the IEC Standards have been adopted as EN European standard. Hazard IEC Potential source of hazard. The term includes hazards to persons which arise within a short period (e.g. fire and explosions) also those which have a long-term effect on the health of a person (e.g. toxic waste). Glass fiber / optical fiber Transmission line made of glass or plastic to guide light waves. Optical Fibers are, other than copper cable, immune against electromagnetic interference and can cover larger distances. IEC International Electrotechnical Commission (headquartered in Geneva, CH) 92/99
94 Terms and definitions IP protection types by housing (IP-Code) The IP identifier according to IEC designates the protection class provided by the housings of electrical devices, e.g. IP 67. The first figure indicates the protection of persons against the intrusion of dangerous parts and protection of internal parts against the intrusion of solid foreign material. 0 No protection 1 Protection against solid bodies >50 mm, e.g. hands 2 Protection against solid bodies >12 mm, e.g. fingers 3 Protection against solid bodies >2.5 mm, e.g. tools and wires 4 Protection against solid bodies >1 mm, e.g. tools, wires and thin wires 5 Protection against dust (limited intrusion permitted) 6 Protection against dust (total) The second figure indicates the protection of the internal components against the dangerous intrusion of water. 0 No protection 1 Protection against vertically falling water (condensate) 2 Protection against splash water deviating from the vertical by 15 3 Protection against splash water deviating from the vertical by 60 4 Protection against splash water from all directions 5 Protection against low pressure water jet from all directions (limited intrusion permitted) 6 Protection against high pressure water jet from any direction (limited intrusion permitted), e.g. for use on the deck of ships 7 Protection against water up to an immersion depth between 15 cm and 100 cm 8 Protection against water if immersed under pressure 93/99
95 Terms and definitions Optical transmission ISO/IEC (100BASE-FX): Physical transmission with the following properties: Optical fiber made of quartz (glass) or plastics Long distances, independent of transmission speed Immunity to electromagnetic interference Electrically isolated stations Star, ring, line and mixed cable topologies Possibility to connect to electrical network segments Possible optical fiber types (multi-mode glass fiber, single-mode glass fiber, plastic fiber, PCF glass fiber) PROFINET Is a standard for industrial Ethernet in automation technology. It exists in two different versions or types: PROFINET CBA (Component Based Automation) for networking of distributed systems PROFINET IO (Input Output) for controlling sensors and actors using a central control system in production engineering PROFINET cable Cable for digital data transmission, designed as copper cable or optical fiber cable. PROFINET components All components of a PROFINET network (e.g. cables, connectors, controller/device interfaces, repeaters, etc.) PROFIBUS Nutzerorganisation e.v. (PNO, PROFIBUS User Organization) PNO is the regional German organization of PROFIBUS & PROFINET International (PI). PI has authorized the PROFIBUS Nutzerorganisation e.v. (PNO Germany) to install Technical Committees (TC) and Work Groups (WG) in order to define and maintain the manufacturer-independent PROFIBUS/-NET standard. The PNO has 94/99
96 Terms and definitions been founded in The PNO is a non-profit organization headquartered in Karlsruhe, Germany. Members of PROFIBUS & PROFINET International are entitled to participate in the technical committees and work groups of PNO. Members can take an active role in the maintenance and development of PROFIBUS/-NET. This way, the PROFIBUS/-NET technology is guaranteed to be open and manufacturer-independent. You will find more detailed information at or PROFINET-Node Device which communicates with other devices via the PROFINET cable (controller, device) Programming device Adapted to the size of the programmable logic controller (PLC) there a many types of programming devices and / or software offered by the manufacturer. Single-command programming device: This programming device is useful for small modifications of existing programs Specific computer hardware and software provided by the manufacturer of special programming languages, such as Ladder Logic, include special functions for automation applications or for industrial environments. These programming devices are upgraded to development tools so that all commissioning steps can be performed. PC-compatible software to ensure the use of a normal, standard PC or notebook as a programming device. Special hardware, for example a PROFINET interface, is required in order to upgrade this system to a development tool. Switch A device operating as active star point to connect PROFINET devices. Switches analyze the inbound data packets and route them to the port where the receiver is registered. For additional PROFINET terms, please visit the PI glossary at searching for "Glossary". 95/99
97 Alphabetic index C Connecting PROFINET nodes...85 Plug...87 E electrostatic discharge...86 Equipotential bonding...73, 75 Cabinet entry...79 connect cable shield...80 Connecting PROFINET node...79 Functional ground...74 Protective ground...73 F Fiber optic cable assembly work BFOC(ST)...72 M12 Fiber Hybrid connector...69 SC-RJ connector...65 G Grounding...See Equipotential bonding L Laying PROFINET cables...15 Adding cables...38 Bending radii /99
98 Cable routing in switch cabinets...19 Cable routing inside buildings...21 Cable routing outside buildings...23 Cable spacing...17 connecting buildings...41 Copper cables...16 Distortion...34 Electrical cables...29 Fiber optic cables...25, 39, 40 Flexible PROFINET cables...34 FO cable connectors...40 FO cable connectors, optical face cleaning...61 FO cable connectors, optical inspection...60 FO cable EMI...41 Loop formation...37 Mechanical protection of PROFINET cables...27 Pressure load...33 Protection FO cable connectors...58 Pulling aids...32 Routing PROFINET cables...16 Sharp edges...38 Storage and transportation...29 Strain relief...33 Temperature limits...30 Tensile strength...31 Trailing and festoon cables...35 Underground cables... See Cable routing outside buildings Underground cables...41 M M12 plug connection Insulation displacement technology...54 M12 screwing clamp technology technology /99
99 P Plug connection Insulation displacement technology...48 PROFINET cable assembly work...43 assembly Fiber optic cables...64 Connecting cable shield to equipotential bonding conductor...78 Fiber optic cable...58, 62 Fiber optic harnesses handling precaution...58 Hybrid connector...57 Insulation displacement technology...54 Insulation Displacement technology...48 M M12 connector...51 M12 Fiber Hybrid connector...69 M12 screwing clamp technology...51 Marking of wire pairs...45 Pinbelegung...44 PROFINET copper cable...44 Properties Fiber optic cables...62 Push Pull RJ RJ safety instructions for fiber optic cable...64 Steckverbinder...44 Structure of PROFINET cable /99
100 Addresses PI Competence Center The international Competence Center (PICC), accredited by PNO, are qualified partners for all questions regarding PROFINET and located all over the world. The services offered by the PICCs range from a telephone hotline, support for field device development, troubleshooting in systems through the organization of specific, problem-oriented workshops. These impart not only the fundamental principles of PROFINET, facilitating entry to the technology, but also detailed information that provides developers with information on how to develop field devices. The current contact addresses can be obtained at area support. Copyright by PROFIBUS Nutzerorganisation.e.V. Haid-und-Neu-Str Karlsruhe Germany Phone: / Fax: / [email protected] 99/99
101 Order No.: /2009 Copyright by: PROFIBUS Nutzerorganisation e.v. Haid-und-Neu-Str Karlsruhe Germany Phone: Fax: [email protected] http: //
PROFINET. Design Guideline
PROFINET Design Guideline Version 1.04 November 2010 PROFINET Design Guideline Version 1.04 November 2010 Order No: 8.062 Page 1 / 190 Introduction PROFINET Order No: 8.062 Identification: TC2-10-0002
Subminiature Load Cell Model 8417
w Technical Product Information Subminiature Load Cell 1. Introduction... 2 2. Preparing for use... 2 2.1 Unpacking... 2 2.2 Using the instrument for the first time... 2 2.3 Grounding and potential connection...
Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection
w Technical Product Information Precision Miniature Load Cell with Overload Protection 1. Introduction The load cells in the model 8431 and 8432 series are primarily designed for the measurement of force
Unarmored Variable Frequency Drive (VFD) Cable Termination Guide
Authorized Distributor Unarmored Variable Frequency Drive (VFD) Cable Termination Guide Be Certain with Belden A Step-by-Step Look at the Connection/Termination of Unarmored VFD Cables Terminating Unarmored
Items Supplied. Frequency. Designation Description / Delivery Unit Order Number
Fiber Optic Cleaver D6 For Single- and Multimode Fibers Diamond blade for highest cleave quality and long life (typically > 10,000 cleaves) Fiber cleave length: 3.5 to 15 mm Fiber diameter: 125 µm nominal
Juice Box Stages 1&2 135&335 Installation Guide 5/10/08
Tools Required: 8mm socket or nut driver Small flat head screwdriver Electrical tape, masking tape, or shrink tube Pep talk: Although the install looks daunting at first, once you get the learning curve
Operating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
Why Expanded Beam types are essential in military and other harsh environment applications
White paper Fiber Optic Connectors Bliek 18 4941 SG RAAMSDONKSVEER NEDERLAND Telephone: +31 162 518 208 Fax: +31 162 518 216 E-mail: [email protected] Website: www.mcap.nl ABN-AMRO: 52.14.96.500 IBAN: NL28ABNA0521496500
PROFINET Cabling and Interconnection Technology
PROFINET Cabling and Interconnection Technology Guideline for PROFINET Version 2.00 March 2007 Order No: 2.252 Document Identification: TC2-06-0010 File name: PN-Cabling-Guide_2252_V200_May07 Prepared
Structured Cabling, Earthing & Equipotential Bonding
White Paper Information and Communication Technology Structured Cabling, Earthing & Equipotential Bonding English Rev. 1.0.1 / 2012-06-01 1 Abstract All Dallmeier network products (PoE cameras, recorders,
Installation and safety instructions for AC/DC built-in devices
The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further
Best Practices for Ensuring Fiber Optic System Performance. David Zambrano
Best Practices for Ensuring Fiber Optic System Performance David Zambrano Inspect Before You Connect Optical Connectors in our Networks Contamination and Signal Performance Sources of Contamination Process
Cat7/Class F New Installation Concept New infrastructure. Handbook
Cat7/Class F New Installation Concept New infrastructure Handbook contents 1 Introduction 3 2 What is the Cat7/Class F installation concept 3 3 Distribution centre 3 3.1 Patch Modules 3 4 How to handle
HARTING Ethernet Cabling 4-poles Overview
Ethernet Cabling 4-poles Overview RJ45 Connectors [on page 8] System cables [on page 10] Distribution modules and Outlets [on page 20] Connectors [on page 22] System cables [on page 24] Panel feed-throughs
Reasons for reissue are in Section 6, REVISION SUMMARY.
Figure 1 This instruction sheet covers the application of OPTIMATE FSMA Fiber Optic Connector Types 905 and 906 for data and telecommunications applications. Base part numbers which apply to each type
01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS
. HARTING RJ INDUSTRIAL ETHERNET CONNECTORS Ethernet is is coming up to standard industrial interface. Therefore, automation devices such as controllers, sensors and actuators feature possess on one or
HARTING Ethernet Cabling 8-poles Overview
Ethernet Cabling 8-poles Overview RJ45 Connectors [on page 8] System cables [on page 12] Distribution modules and Outlets [on page 17] Connectors [on page 20] System cables [on page 26] Panel feed-throughs
ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01
ABB Drives User s Manual Pulse Encoder Interface Module RTAC-0 Pulse Encoder Interface Module RTAC-0 User s Manual 3AFE 64486853 REV A EN EFFECTIVE:.5.00 00 ABB Oy. All Rights Reserved. Safety instructions
Universal Vehicle Power Supply 9007AX01. Installation Instructions
Universal Vehicle Power Supply 9007AX01 Installation Instructions Disclaimer Honeywell International Inc. ( HII ) reserves the right to make changes in specifications and other information contained in
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS
BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE
RLH 2 Wire Digital Phone Fiber Link Card System
RLH Industries, Inc. The leader in rugged fiber optic technology. USER GUIDE! Unconditional Lifetime Warranty U-008 2014C-0924 RLH 2 Wire Digital Phone Fiber Link Card System CARD INSTALLATION INFORMATION
RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
Specifying an IT Cabling System
Specifying an IT Cabling System This guide will help you produce a specification for an IT cabling system that meets your organisation s needs and gives you value for money. You will be able to give your
Ethernet Patch Cord Wiring
Ethernet Patch Cord Wiring C ONTENTS Ethernet Patch Cords & RJ-45 Connectors... 2 Ethernet Patch Cords and UTP Cabling... 3 What s all the twisting about?... 4 Ethernet Applications... 5 568A & 568B Wiring
MOUNTING AND OPERATING INSTRUCTIONS
MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall
HARTING Ethernet Cabling 4-poles Overview
Overview RJ45 Connectors [on page 8] System cables [on page 10] Distribution modules and Outlets [on page 20] HARTING PushPull Connectors [on page 22] System cables [on page 24] Panel feed-throughs [on
USER GUIDE. 2 Channel POTS Mux DIN Fiber Link System. Introduction SYSTEM INSTALLATION INFORMATION. The leader in rugged fiber optic technology.
The leader in rugged fiber optic technology. USER GUIDE! Lifetime Warranty U-04 015A-01 Channel POTS Mux DIN Fiber Link System SYSTEM INSTALLATION INFORMATION Introduction The Channel POTS Mux DIN Fiber
Micrio WS1 Replacement Wind Speed Sensor and WC1 Replacement Wind Compass Sensor for Raymarine ST50 and ST60 Wind Instruments. Rev 4.
Micrio WS1 Replacement Wind Speed Sensor and WC1 Replacement Wind Compass Sensor for Raymarine ST50 and ST60 Wind Instruments. Rev 4.1 The Micrio WS1 Wind Speed Sensor and WC1 Compass Sensor are direct
Power Supply Cables and Connectors
Power Supply Cables and Connectors Often during the excitement of designing a challenging new system, some of the more mundane engineering aspects get overlooked. This is especially true of connections
AMPSEAL* Automotive Plug Connector and Header Assembly
AMPSEAL* Automotive Plug Connector and Header Assembly Application Specification 24 SEP 97 Rev E All dimensions are given in millimeters unless otherwise specified. All dimensional tolerances are +0.2
When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description
Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only
Chapter 4 Connecting to the Internet through an ISP
Chapter 4 Connecting to the Internet through an ISP 1. According to Cisco what two things are essential to gaining access to the internet? a. ISPs are essential to gaining access to the Internet. b. No
White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection
White paper SACE Tmax XT Circuit-Breaker Terminals and Connection Circuit-Breaker Terminals and Connections Index Introduction... 2 1. Components used for wiring... 3 1.1. Electrical...3 1.2. Flexibility
Fiber Optic Cable Installation
Quick Guide Fiber Optic Cable Installation Introduction Fiber optic cables can be easily damaged if they are improperly handled or installed. It is imperative that certain procedures be followed in the
PROFIBUS cable. for PROFIBUS-PA and -DP 10/63-6.46 EN
for PROFIBUS-PA and -DP 10/63-6.46 EN CPN 080/CPE 080-Ex PROFIBUS-PA basis cable AWG 18, 0.88 mm 2 Use For fixed installation indoor and outdoor, on racks and in conduits. Application Fieldbus cable for
4RU High Density Shelf Installation Instructions
4RU High Density Shelf Installation Instructions Table of Contents General Product Information... 1.0 Safety Precautions... 2.0 Tools Required... 3.0 Package Contents... 4.0 Installing the Product Unpacking...
SC, FC and ST * Hot Melt Fiber Optic Connectors
SC, FC and ST * Hot Melt Fiber Optic Connectors Instructions September 1998 78-8073-7873-8 2 Contents 1.0 Safety and Helpful Hints...4 2.0 Field Termination Kit Contents...4 3.0 STÑInstallation on 900
Infrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
Technical Data. Dimensions
0102 Model Number Features 15 mm quasi flush Usable up to SIL2 acc. to IEC 61508 Accessories BF 30 Mounting flange, 30 mm V1-G-N-2M-PUR Female cordset, M12, 2-pin, NAMUR, PUR cable V1-W-N-2M-PUR Female
Optocore Guideline for Fiber Optical Cabling in Permanent Installations
Optocore Guideline for Fiber Optical Cabling in Permanent Installations This guideline is designed to assist Optocore customers with basic information and principles for fiber optical cabling in permanent
CamSplice Assembly Manual
Corning Cable Systems SRP-006-038 Issue 9, September 2000 Page 1 of 6 CamSplice Assembly Manual Table of Contents 1. General... 1 2. Precautions... 1 3. Tools and Materials... 2 4. Cable and Fiber Preparation...
Installation Instructions
READ BEFORE INSTALLING UNIT For Slider Casement Air Conditioners To avoid risk of personal injury, property damage, or product damage due to the weight of this device and sharp edges that may be exposed:
Achat 115MA full-range speaker. user manual
Achat 115MA full-range speaker user manual Musikhaus Thomann Thomann GmbH Hans-Thomann-Straße 1 96138 Burgebrach Germany Telephone: +49 (0) 9546 9223-0 E-mail: [email protected] Internet: www.thomann.de
ELEVATOR TRAVELING CABLE - DESIGN EVOLUTION
ELEVATOR TRAVELING CABLE - DESIGN EVOLUTION by Richard Laney Introduction Elevator traveling cable is a vital link between the elevator car and controller. In conventional elevators, all power and signal
UniStream CPU-for-Panel
UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic
Module Connectors and Cable Specifications
Module Connectors, page 1 Cables and Adapters, page 2 Cleaning the Fiber-Optic Connectors, page 6 Module Connectors RJ-45 Connector The RJ-45 connector is used to connect a Category 3, Category 5, Category
Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1
Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader
Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family
Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family Part of the Kiva Lighting Family Custom Lighting and Fans Since 1992 1312 12th St NW Albuquerque,
Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement
Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement This work instruction describes the methods and means for which to remove and reinstall optional scanner cable configurations
PURE : REliable planning of data center cabling
PURE : REliable planning of data center cabling THE PURE EFFEct: TWICE AS MANY CONNEctionS AND 15 METERS MORE CHannEL LEngtH * PreCONNECT PURE is a milestone in the development of high-end IT cabling for
Cable Preparation and Pulling Procedure Best Practices for Fiber Optic Indoor Tight-Buffered Cable
Cable Preparation and Pulling Procedure Best Practices for Fiber Optic Indoor Tight-Buffered Cable Panduit Corp. 2009 BEST PRACTICES PN447B \ Table of Contents 3 2.0 Preparation Notes Tools and Material
5800 Temperature Sensor Cable Assembly
5800 Temperature Sensor Cable Assembly Removal and Replacement Instruction Sheet #60-4702-070 Revision D, January 14, 2013 Overview The 5800 has two refrigeration temperature sensors, one attached to the
XL PREMIUM OIL COOLER KIT
-J05 REV. 0-0-0 XL PREMIUM OIL COOLER KIT GENERAL Kit Number 0008 Models For model fitment information, see the P&A Retail Catalog or the Parts and Accessories section of www.harley-davidson.com (English
Reasons for reissue of this instruction sheet are provided in Section 5, REVISION SUMMARY.
Reasons for reissue of this instruction sheet are provided in Section 5, REVISION SUMMARY. Air Pressure 586.1 min 689.5 kpa max [85 min 100 psi max] Air Displacement 721,000 mm 3 [44 in. 3 ] Figure 1 Weight
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
Quick start guide smart.power smart.power smart.power
Quick start guide Intended use: smart.power is a universal charging device for charging (in absence of other charging options) your mobile phone, your TEASI-navigation system or other devices with a 5V
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
- power windows - alarm system - electric door mirror control - door warning light - central locking - seat memory
Door Wiring Harness Plug Connections Binder -, Electrics Vehicle Type: (86) Model Year: 7 (V) Concern: Door wiring harness plug connections X11 / X12. Information: The rubber boot for the door connector
Networks. The two main network types are: Peer networks
Networks Networking is all about sharing information and resources. Computers connected to a network can avail of many facilities not available to standalone computers: Share a printer or a plotter among
K E E P E TH T I H S I MA M N A U N A U L A FO F R
Quad-C LED Moving Wash Pro SI-055 User Manual KEEP THIS MANUAL FOR FUTURE NEEDS 1. Unpacking Thank you for choosing Color Imagination s Quad-C LED Moving Wash Pro. For your own safety, please read this
Model 1756 Test Lead Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you
Mounting instructions. Junction box VKK2R-8 DIGITAL. A1145-1.0 en
Mounting instructions Junction box VKK2R-8 DIGITAL VKK2R-8 DIGITAL 3 Contents Page Safety instructions... 4 1 Introduction and appropriate use... 7 2 Mechanical construction... 8 2.1 Mounting... 9 3 Electrical
Cable Guide. Cables, Connectors & Tools for installation of quality networks. TRIAX - your ultimate connection
Cable Guide Cables, Connectors & Tools for installation of quality networks TRIAX - your ultimate connection A Selection of the best Triax TX Cable range optimised for digital reception Simplification
Operating Instructions
Important information: These instructions contain safety information, read and follow them carefully. Dialight will not accept any responsibility for injury, damage or loss which may occur due to incorrect
Installation Instructions For Slider Casement Air Conditioners
Installation Instructions For Slider Casement Air Conditioners NOTE: These instructions describe installation in a typical wood framed window with a wood SLIDE-BY sash, or installation in a metal CASEMENT
LocoNet, the Digitrax Difference
LocoNet, the Digitrax Difference LocoNet is Digitrax's method of communication between LocoNet compatible devices on a model railroad layout. LocoNet Compatible devices are designed to work together on
Addendum to the Operating Instructions
Drive Technology \ Drive Automation \ System Integration \ Services Addendum to the Operating Instructions MOVIMOT with AS-Interface and AC Motor DT/DV Unit Replacement MOVIMOT MM..C -> MM..D with MLK3A
FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK
FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK Field busses are industrial control systems using Programmable Logic lers (PLC) to control and manage field devices found in industrial environments. The communication
DIVISION 26 - ELECTRICAL SECTION 26 05 20 CABLES FOR INSTRUMENTATION
DIVISION 26 - ELECTRICAL PART 1 - GENERAL 1.01 SUMMARY A. Section Includes 1. Instrumentation Cables 1.02 SUBMITTALS A. Submit in accordance with requirements of Section 01 33 00. B. Product Data: Submit
WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS
CONDUCTORS Conductors are needed to complete the path for electrical current to flow from the power source to the working devices and back to the power source. Special wiring is needed for battery cables
5 in 1 Cable Tester RTK-T05 User Manual
1. INTRODUCTION The 5 in 1 Cable Tester tests 5 common LAN and Computer cables. It tests installed cables or patch cords with RJ-45, RJ-11, 1394, USB and BNC connectors. It is intended to test cables with
Safety & Environmental Protection Services Guidance Note
Safety & Environmental Protection Services Guidance Note A STEP-BY-STEP GUIDE TO VISUAL INSPECTION OF ELECTRICAL EQUIPMENT Why Inspect? The Health and Safety at Work etc Act 1974 and the Electricity at
Cable management for rack-mounted systems
Cable management for rack-mounted systems technology brief, 2 nd edition Abstract... 2 Introduction... 2 Cable routing guidelines... 3 Separation of power and data cables... 3 Retention of excess cable...
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
EMC Engineering Guidelines For Automation Systems PS 4 PS 416 04/97 AWB 27-1287-GB
EMC Engineering Guidelines For Automation Systems PS 4 PS 416 1st edition 04/97 Moeller GmbH, Bonn Author: Werner Albrecht Editors: Klaus Krüger, Thomas Kracht Translator: Chris Baker, Terence Osborn Contents
Installation & Weatherproofing Guide for ENCOM Broadband Radios
Installation & Weatherproofing Guide for ENCOM Broadband Radios Read the following instructions before proceeding with your ENCOM Wireless Radio installation. Keep these instructions in safe location for
Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters
S&C Vista SD Underground Distribution Switchgear Pad-Mounted and Vault-Mounted Style Outdoor Distribution (17.5 kv and 29 kv) With Visi-Gap Load Interrupter Switches and Visi-Gap Fault Inetrrupters Replacement
PRELIMINARY MANUAL STAGE COLOR 48. Preliminary User Guide. Official version will follow soon on: WWW.BRITEQ-LIGHTING.COM TABLE OF CONTENTS
STGE COO 48 Preliminary User Guide Official version will follow soon on: WWW.BITEQ-IGHTIG.COM TBE OF COTETS 1. Safety Instruction 2. Technical Specification 3. How To Set The Unit 4. How To Control The
Standards Affecting a Premise T-1 Installation
Standards Affecting a Premise T-1 Installation The T-carrier system originated many years ago as a technology developed by AT&T. The intended use of the scheme was to increase the voice channel capacity
Congratulations! Thank you!
TM-47 ORDERCODE D1370 Congratulations! You have bought a great, innovative product from DAP Audio. The DAP Audio Microphone range brings excitement to any venue. Whether you want simple plug-&-play action
7.4 3M No Polish Connector
Cap Fibre Splice Element Description 3M No Polish Connector (NPC) enables fast, on-site installation of 250μm and 900μm connections utilizing a one piece, pre-assembled design. The SC compatible connector
AC and DC Drive System Installation Information
Purpose This document contains the Parker SSD Drives recommendations for installing drive systems. These instructions must be followed for safe and reliable operation. Instructions CODES AND REGULATIONS
CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions
Printing 3 March 2008 CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions This instruction is intended for CP2 cable pedestal installations and replacements. The following tools will be
Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
PRODUCT: WASHER / WASHER-DRYER COMBO MODEL: AW 120 / AW 122 / AW 125 AWD 120 / AWD 121 / AWD 129
PRODUCT: WASHER / WASHER-DRYER COMBO MODEL: The information included in this Splendide Repair Manual may change without notice. Please see our web site www.splendide.com/service/docs.html for updates,
HIROSE ELECTRIC U.S.A. Fiber Optic VAR July, 2015
HIROSE ELECTRIC U.S.A. Fiber Optic VAR July, 2015 Fiber Optic VAR Program Hirose Launches Fiber Optic Cabling VAR Program to provide a complete fiber optic cable assembly and wire harness solutions to
RAUFOSS EXPLOSIVE COMPRESSION FITTINGS
INSTRUCTION MANUAL FOR RAUFOSS EXPLOSIVE COMPRESSION FITTINGS Box 7 2831 Raufoss Norway Tlf.: +47 61 15 17 87 Fax: +47 61 15 25 56 25 January 2013, rev 2 Available on www.vpmetall.no Page 1 CONTENTS GENERAL
Outdoor Use Waterproof I/O Connectors (Optical / Modular / Electrical) FO-BH, FO-BC, NT5, JN2 / W Series
COMPONENTS PRODUCT INFORMATION RoHS Compliant NEW Outdoor Use Waterproof I/O Connectors (Optical / Modular / Electrical) FO-BH, FO-BC, NT5, JN2 / W Series Optical FO-BH Series (Compact Type) CONNECTOR
Rutenbeck Network Connection Box Cat. 5, shielded. Cable installation. UAE Connection Box Cat. 5 Operating Instructions.
Rutenbeck Network Connection Box Cat. 5, shielded 1-gang, 1 x 8-pole Order No.: 0180 00 2-gang, 2 x 8-pole Order No.: 0178 00 1-gang, (especially for channel construction) Order No.: 0802 00 2-gang, (especially
PROFINET Diagnostics Software and Tools
PROFINET Diagnostics Software and Tools Dr. Xiu Ji Static wiring test, diagnostics Live system diagnostics Basics of PROFINET Content PROFINET Diagnostics by Dr. Xiu Ji, Page 2 What is PROFINET? PROFINET
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
ETHERLINE Ethernet Cable, Connectors & Tools
Ethernet Cable, ors & Tools 2 Pair 242 4 Pair 249 Industrial Ethernet ors & Tools 256 Ethernet Cable, ors & Tools ETHERNET CABLE, CONNECTORS & TOOLS Quick Select Chart 240 2 Pair 2 Pair: CAT.5/5e; Stationary
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html TECHNICAL SERVICE DEPARTMENT Removal, Cleaning, & Reinstallation of the Burner Assembly For models 74 & GT199 Required tools -
HARAX circular connector
Show navigation HARAX circular connector Technical characteristics Specifications IEC 60 352-4 IEC 60 9475-2 Approvals HARAX M8-S/M12-S Rated voltage Rated current Diameter of individual strands Conductor
SELF INSTALLATION GUIDE
Ultrafast Fibre-optic Broadband SELF INSTALLATION GUIDE Gigaclear install permission July2012 v1.0 Before you begin Please make sure you have the correct length of cable. Bear in mind that you may need
Reasons for reissue are provided in Section 6, REVISION SUMMARY.
Reasons for reissue are provided in Section 6, REVISION SUMMARY. The FRONT OF TOOL has the AMP marking on the link. The BACK OF TOOL (Wire Side), into which the wire is inserted, has the wire size marked
We hope that every customer sets up CC-Link system easily by reading this documentation.
This documentation describes items to consider in advance, how to select devices, points to keep in mind and procedure in order to set up cable wiring. Abstract of contents Chapter 1: Procedure for cable
The Do s and Don ts of Pressure Transducers
The Do s and Don ts of Pressure Transducers ABSTRACT When specifying a pressure transducer for a process measurement, a number of items have to be considered. Some of the more important ones are discussed