The Evolution of Requirements for Supervising Station Alarm Systems
|
|
|
- Claire Gilmore
- 10 years ago
- Views:
Transcription
1 The Evolution of Requirements for Supervising Station Alarm Systems Fire Marshal s Association of Colorado January 18, 2013 Warren Olsen, CFPS CBCO FSCI [email protected] 1
2 Disclaimer: The comments and opinions made during the presentation of this session are solely those of the presenter and do not reflect an official position of the National Fire Protection Association, its employees, or any of its technical committees. 2
3
4 Overview 4 NFPA 72 Recent Significant Document Changes When is supervising station monitoring required NFPA 72 Definitions affecting Supervising Station Alarm Systems Supervising Station Alarm Systems general chapter review Differences in Supervising Station levels of service Communication method requirements for Supervising Station Alarm Systems
5 NFPA 72 Recent Significant Document Changes 2007 Edition 11 Chapters - Did not address MNS 2010 Edition Renamed National Fire Alarm and Signaling Code 2010 Edition Mostly eliminated the word fire proceeding alarm system 2010 Edition Provided numbered chapters 1 29 for future expansion 2010 Edition Added 3 new chapters including Circuits and Pathways, Emergency Control Functions, and Emergency Communications Systems (MNS, EVAC, Radio Enhancement) 2013 Edition Added new chapter on Documentation 2016 Edition Begins its cycle in June
6 When is Supervising Station monitoring required International Fire Code Definitions Approved. Acceptable to the fire code official. Supervising Station. A facility that receives signals and at which personnel are in attendance at all times to respond to these signals. 6
7 When is Supervising Station monitoring required International Fire Code 7 Monitoring Sprinkler Systems Monitoring. Alarm, supervisory and trouble signals shall be distinctively different and shall be automatically transmitted to an approved supervising station* or, when approved by the fire code official, shall sound an audible signal at a constantly attended location. * 2006 and previous editions indicated approved central station, remote supervising station, or proprietary supervising station Monitoring Fire Alarm Systems Monitoring. Fire alarm systems required by this chapter or by the International Building Code shall be monitored by an approved supervising station in accordance with NFPA 72.
8 When is Supervising Station monitoring required Life Safety Code Definitions Approved. Acceptable to the authority having jurisdiction. Supervising Station. A facility that receives signals and at which personnel are in attendance at all times to respond to these signals. Emergency Forces Notification Where fire department notification is required by another section of this Code, the fire alarm system shall be arranged to transmit the alarm automatically via any of the following means acceptable to the authority having jurisdiction and shall be in accordance with NFPA 72, National Fire Alarm Code. (2) Central station fire alarm system (3) Proprietary supervising station fire alarm system (4) Remote supervising station fire alarm system 8
9 NFPA 72 Definitions affecting Supervising Station Alarm Systems Definitions Section Approved. Acceptable to the authority having jurisdiction. Section 3.3.XXX Supervising Station. A facility that receives signals from a protected premises fire alarm system and at which personnel are in attendance at all times to respond to these signals. Section 3.3.XXX - Runner. A person... available for prompt dispatching, when necessary, to the protected premises. 9 Section 3.3.XXX Runner Service. The service provided by a runner at the protected premises, including restoration, resetting and silencing of all equipment transmitting signals to an offpremises location.
10 NFPA 72 Definitions affecting Supervising Station Alarm Systems Definitions Section Central Supervising Station. A supervising station that is listed for central station service and that also commonly provides less stringent supervising station services such as remote supervising station services. Section Central Station Service. The use of a system or group of systems including the protected premises fire alarm system(s) in which the operation of circuits and devices are signaled to, recorded in, and supervised from a listed central station that has competent and experienced operators who, upon receipt of a signal, take such action as required by this Code. Related activities at the protected premises, such as equipment installation, inspection, testing, maintenance, and runner service, are the responsibility of the central station or a listed alarm service local company. Central station service is controlled and operated by a person, firm, or corporation whose business is the furnishing of such contracted services or whose properties are the protected premises. Section 26.3 Specific requirements for Central Station Service 10
11 NFPA 72 Definitions affecting Supervising Station Alarm Systems Definitions Section Proprietary Supervising Station. A supervising station under the same ownership as the protected premises fire alarm system(s) that it supervises and to which alarm, supervisory, or trouble signals are received and where personnel are in attendance at all times to supervise operation and investigate signals. Section Proprietary Supervising Station Service. The use of a system or group of systems including the protected premises fire alarm system(s) in which the operation of circuits and devices are signaled to, recorded in, and supervised from a supervising station under the same ownership as the protected premises that has competent and experienced operators who, upon receipt of a signal, take such action as required by this Code. Related activities at the protected premises, such as equipment installation, inspection, testing, maintenance, and runner service, are the responsibility of the owner. Proprietary supervising station service is controlled and operated by the entity whose properties are the protected premises. 11 Section 26.4 Specific requirements for Proprietary Supervising Station Service
12 NFPA 72 Definitions affecting Supervising Station Alarm Systems 12 Definitions Section Remote Supervising Station. A supervising station to which alarm, supervisory, or trouble signals or any combination of those signals emanating from protected premises fire alarm systems are received and where personnel are in attendance at all times to respond. Section Remote Supervising Station Service. The use of a system including the protected premises fire alarm system(s) in which the operations of circuits and devices are signaled to, record in, and supervised from a supervising station that has competent and experienced operators who, upon receipt of a signal, take action as required by this Code. Related activities at the protected premises, such as equipment installation, inspection, testing, and maintenance, are the responsibility of the owner. Section 26.5 Specific requirements for Remote Supervising Station Alarm Systems
13 Supervising Station Alarm Systems General Chapter Review Chapters 8 (07 ed.) or 26 (10, 13 eds.) - Supervising Station (07-Fire) Alarm Systems When is the Chapter Applicable? Section 26.1 Application. The performance, installation, and operation of alarm systems at a continuously attended supervising station and between the protected premises and the continuously attended supervising station shall comply with the requirements of this chapter. 13
14 Supervising Station Alarm Systems General Chapter Review Chapters 8 (07 ed.) or 26 (10, 13 eds.) - Supervising Station (07-Fire) Alarm Systems When does a Protected Premises a alarm system become a Supervising Station Alarm System? 2007/2010 eds. Section 8.1.1/ Where a protected premises fire alarm system has its signals sent to a supervising station, the entire system shall become a supervising station alarm system ed. Section Where any system regulated by this Code sends signals to a supervising station, the entire system shall become a supervising station alarm system. 14
15 Supervising Station Alarm Systems General Chapter Review Chapters 8 (07 ed.) or 26 (10, 13 eds.) - Supervising Station (07-Fire) Alarm Systems What other chapters may apply? 2007 ed. Section The requirements of Chapters 4 (Fundamentals), 6 (Protected Premises) and 10 (Testing and Maintenance) shall also apply unless in conflict with this chapter ed. Section Revised the existing chapters to 10 (Fund.), 14 (T & M), and 23 (PP) and added 12 (Circuits and Pathways) 2013 ed. Section Also added chapter 7 (Documentation) 15
16 Supervising Station Alarm Systems General Chapter Review Chapters 8 (07 ed.) or 26 (10, 13 eds.) - Supervising Station (07-Fire) Alarm Systems How are alarm signals to be handled? 2007/2010 eds. Section 8.2.1/ Alarm Signal Disposition. Except as permitted by / , all fire alarm signals received by a supervising station shall be immediately retransmitted to the public fire service communications center ed. Section Same basic requirement exists, but now allows for Alarm Signal Pre-Verification and Alarm Signal Verification. 16
17 Supervising Station Alarm Systems General Chapter Review Chapters 8 (07 ed.) or 26 (10, 13 eds.) - Supervising Station (07-Fire) Alarm Systems What is Pre and Alarm Signal Verification? 2013 ed. Section Alarm Signal Pre-Verification. Where alarm signal verification is required by the responsible fire department, the supervising station shall immediately notify the communications center that a fire alarm signal has been received and verification is in process ed. Section Verification shall meet the requirements of ed. Section Alarm Signal Verification. supervising station personnel shall attempt to verify alarm signals prior to reporting them to the communication center where all of the following conditions exist: 17
18 Supervising Station Alarm Systems General Chapter Review Chapters 8 (07 ed.) or 26 (10, 13 eds.) - Supervising Station (07-Fire) Alarm Systems What steps are required during the alarm signal verification (ASV) process? (1) ASV is required by the fire department for a specific protected premises (2) The fire department must provide documentation of the ASV requirement to the supervising station and protected premises (3) If the ASV requirement changes, the fire department must provide documentation to the supervising station and protected premises (4) The ASV shall not take longer than 90 seconds from the time the alarm signal is received at the supervising station until the time that retransmission of the verified alarm signal is initiated 18
19 Supervising Station Alarm Systems General Chapter Review Chapters 8 (07 ed.) or 26 (10, 13 eds.) - Supervising Station (07-Fire) Alarm Systems What steps are required during the alarm signal verification (ASV) process? (5) ASV is only permitted from authorized personnel within the protected premises (6) Verified alarm signals are immediately retransmitted to the communication center and include information that the signal was verified at the protected premises to be an emergency (7) Alarm signals where verification is not conclusive are immediately retransmitted to the communications center (8) Alarm signals that are verified as nuisance alarms are not dispatched and are handled in accordance with * * Alarm signals not reported to the communications center shall be reported to the responsible fire department in a manner and at a frequency specified by the responsible fire department. 19
20 Supervising Station Alarm Systems General Chapter Review Chapters 8 (07 ed.) or 26 (10, 13 eds.) - Supervising Station (07-Fire) Alarm Systems What is required when someone changes a supervising station service provider? 2007/2010 eds. Section / Requires supervising station customers or clients be notified within 30 days of any scheduled change in service which results in signals going to a different supervising station facility. Effective 2013 ed. The AHJ must also be notified of the change or termination! 07 ed and /10 ed and /13 ed and Requires that all zones, points, and signals be tested from the protected property (either by the supervising station or prime contractor) Definition: Prime Contractor. The one company contractually responsible for providing central station services to a subscriber as required by this Code. The prime contractor can be either a listed central station or a listed alarm service-local company. 20
21 Differences in Supervising Station levels of service Sections 8.3 and 26.3 Central Station Service Basic requirements have not changed: Installation of alarm transmitters Monitoring of all signals Retransmission of signals Associated record keeping and reporting Testing and maintenance Runner service Signed contract covering all of the above through the listed Central Station and/or Listed Alarm Service - Local Company Conspicuously posted indication of system compliance from an approved organization (UL, FM, ETL, etc.) 21
22
23
24 Differences in Supervising Station levels of service Sections 8.4 and 26.4 Proprietary Supervising Station Alarm Systems Basic requirements have not changed: Examples Wal-Mart (Monitoring all of their stores from their Bentonville, Arkansas supervising station) Walgreens (Monitoring all of their stores from their Deerfield, Illinois supervising station) 24
25 Differences in Supervising Station levels of service Sections 8.5 and 26.5 Remote Supervising Station Alarm Systems Basic requirements have not changed Some changes of note that did occur: 2010 ed. Section Indication of Remote Station Service. Requires that the owner of a remote supervising station alarm system provide annual documentation to the AHJ identifying the party responsible for the I.T.&M. of the system. Documentation requirements indicated in the code ed. Section Now requires the representative of the service provider to sign the documentation 25
26 Communication Method Requirements for Supervising Station Alarm Systems 26
27 Reconfiguration of Communication Methods Item/Edition Application General Communication Methods Active Multiplex, McCulloh, Directly Connected Non-Coded, Private Microwave, Other Trans Tech , , , , Specifically Named General Covers Anything Not Specifically Covered Performance-Based Tech. Covers Anything Not Specifically Covered DACTs Way RF Radio Way Private Radio
28 Communication Method Requirements for Supervising Station Alarm Systems 2007 ed./ eds. Section 8.6/26.6 Communication Methods for Supervising Station Alarm Systems 8.6.1/ Application. This section covers: The transmitter located at the protected premises The transmission channel between the protected premises and the supervising station or subsidiary station If used, any subsidiary station and its communication channel The signal receiving, processing, display, and recording equipment at the supervising station 28
29 Communication Method Requirements for Supervising Station Alarm Systems 2007 ed./ eds. Section / Alternate Methods The code does not prohibit the use of listed equipment using alternate communications methods that provide a level of reliability and supervision consistent with the requirements of Chapter 4 (07 ed.)/10 (10,13 eds.) and the intended level of protection. 29
30 Communication Method Requirements for Supervising Station Alarm Systems Sections in the three different editions try to deal with technologies not specifically covered by the Code ed. Section Other Transmission Technologies 2010 ed. Section General 2013 ed. - Section Performance-Based Technologies 30
31 Communication Method Requirements for Supervising Station Alarm Systems 2007 ed. Section Other Transmission Technologies Communications Integrity Any technology pathway failure has to be annunciated at the supervising station within 5 minutes If a signal can t be sent to the supervising station, then a signal has to be annunciated at the protected premises If the technology pathway cannot be supervised, a redundant path, which can be monitored, is needed If there is a redundant path, the failure of either pathway has to be annunciated at the supervising station within 24 hours That s it in the 2007 ed.! 31
32 Communication Method Requirements for Supervising Station Alarm Systems 2010 ed. Section General 2013 ed. Section Performance-Based Technologies Communications Integrity Must monitor the integrity of the transmission technology and the communications path. 32
33 Communication Method Requirements for Supervising Station Alarm Systems 2010 & 2013 eds. General & Performance-Based Technologies 2010 ed Single Communications Technology failure of the communication pathway shall be annunciated at the supervising station within 5 minutes of the failure ed Single Communications Path Unless prohibited by the AHJ a single transmission path shall be permitted path shall be supervised at an interval of not more than 60 minutes failure of the path shall be annunciated at the supervising station within not more than 60 minutes failure to complete a signal transmission shall be annunciated at the protected premises in accordance with Section (200 seconds). 33
34 Communication Method Requirements for Supervising Station Alarm Systems 2010 & 2013 eds. General & Performance-Based Technologies 2010 ed Multiple Communications Technologies (1) Must monitor for integrity each communications path (2) Must annunciate the failure of any communications path at the supervising station and at the protected premises within 24 hours of the failure 2013 ed Multiple Communications Paths (1) Must supervise each path (2) The failure of any path shall be annunciated at the supervising station within not more than 6 hours (3) The failure to complete a signal transmission shall be annunciated at the protected premises within 200 seconds 34
35 Communication Method Requirements for Supervising Station Alarm Systems 2010 & 2013 eds. General & Performance-Based Technologies 2010 ed Sharing Communications Equipment On-Premises If the fire alarm transmitter is sharing on-premises communications equipment, the shared equipment shall be listed ed Sharing Communications Equipment on Premises shall be listed as communications or information technology equipment. 35
36 Communication Method Requirements for Supervising Station Alarm Systems 2010 & 2013 eds. General & Performance-Based Technologies 2010 ed Secondary Power Secondary power capacity in accordance with shall be provided for all equipment necessary for the transmission and reception of alarm, supervisory, trouble, and other signals located at the protected premises 2013 ed Secondary Power (1) Fire alarm transmitters not requiring shared communications equipment must meet the requirements of (2) If fire alarm transmitters share on-premises communications equipment the shared equipment must have a secondary power capacity of 24 hours 36
37 Communication Method Requirements for Supervising Station Alarm Systems Digital Alarm Communicating Transmitters (DACT) 2007 and 2010 eds. No significant changes 2013 ed. - Changes DACTs shall employ one telephone line/number (not a party line) and (1) one-way private radio (2) two-way RF radio (3) transmission means complying with
38 Communication Method Requirements for Supervising Station Alarm Systems Digital Alarm Communicating Transmitters (DACT) Additional 2013 ed. - Changes (1) Supervision of each communication channel shall not exceed an interval of 6 hours (24 hours in previous code eds.) (2) Each transmission means shall automatically initiate and complete a test signal transmission sequence to its associated receiver at least once every 6 hours (3) A successful transmission of any other signal within the same 6 hour period satisfies the test requirement 38
39 Communication Method Requirements for Supervising Station Alarm Systems Radio Systems Two-Way Radio Frequency (RF) Multiplex Systems Radio Telemetry One-Way Private Radio Alarm Systems Keltron, AES radio networks No major changes 39
40 Questions? Warren Olsen, CFPS CBCO FSCI 40
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
UL s Perspective on IP Signaling Larry Shudak Principal Engineer Signaling and Security Control Equipment Underwriters Laboratories Inc.
UL s Perspective on IP Signaling Larry Shudak Principal Engineer Signaling and Security Control Equipment Underwriters Laboratories Inc. 2011 Underwriters Laboratories Inc. Transmission methods Historically,
Loop Start or Ground Start?
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Loop Start or Ground Start? by Dean K. Wilson, P.E. Question: The new telephone system installed in our office building has telephone voice mail. To signal
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
INSPECTION AND TESTING OF FIRE ALARM SYSTEMS
Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.
rpsa FIRE PROTECTION ENGINEERS
R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Understanding Supervision of Fire Protection Systems by Robert P. Schifiliti,
Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems
Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
Alarm Systems Using Wireless or Other Transmission Technology as a Single Path of Communication. Purpose. References. Description of Code Reference
TOWN OF BRIGHTON Office of the Fire Marshal 2300 Elmwood Avenue Rochester, New York 14618 (585) 784-5220 Office (585) 784-5207 Fax Alarm Systems Using Wireless or Other Transmission Technology as a Single
Fire Prevention Coffee Break Training. November 2015
Fire Prevention Coffee Break Training November 2015 Agenda Changes in the Pire Prevention Bureau FM Lund Tags FM Lund System priorities for the FD FM Lund Transmission Technologies- Phelan Questions and
Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply
FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
Approval Standard for Central Station Service for Fire Alarms and Protective Equipment Supervision
Approval Standard for Central Station Service for Fire Alarms and Protective Equipment Supervision Class Number 3011 April 1999 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification
BASIC FIRE ALARM TRAINING
BASIC FIRE ALARM TRAINING What is a fire alarm system? Per the defini+on in NFPA 72 A system or por+on of a combina+on system that consists of components and circuits arranged to monitor and annunciate
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
TITLE 9-1 BURGLAR AND HOLDUP ALARM USERS REGISTRATION; FALSE ALARM
CHAPTER 1 BURGLAR AND HOLDUP ALARM USERS REGISTRATION; FALSE ALARMS SECTION: 9-1-1: Purpose 9-1-2: Definitions 9-1-3: Automatic Dialing Service; lnterconnection to Primary Trunklines 9-1-4: Testing Equipment
CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013
CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013 Alan Cavers, Engineering Manager Underwriters Laboratories of Canada Dec. 2013 Copyright 1995-2007 Underwriters'
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14
City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the time of the inspection or test. It shall be permitted to modify this form
The Jefferson County Board of Supervisors does ordain as follows:
ORDINANCE NO. 18 The Jefferson County Board of Supervisors does ordain as follows: 18.01 TITLE. This ordinance shall be known as the Jefferson County Alarm Systems Ordinance. 18.02 DECLARATION OF PURPOSE.
January 1, 2013. RE: TG-7FS Sole Path Cellular Alarm Communicator. To whom it may concern:
January 1, 2013 RE: TG-7FS Sole Path Cellular Alarm Communicator To whom it may concern: In November 2009, the National Fire Protection Association (NFPA) released the newest addition to the NFPA 72, National
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group
OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group Course Title: Rev Date Agenda Introduction to Underwriters Laboratories
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
CHAPTER. Fire Alarm Systems APPROVAL AND ACCEPTANCE. Shop Drawings
Fire Alarm Systems CHAPTER 2 The information contained in this chapter is intended to assist the registered design professional (RDP), commissioning agent, authority having jurisdiction (AHJ), and the
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
Approval Standard for Fire Alarm Signaling Systems
Approval Standard for Fire Alarm Signaling Systems Class Number 3010 December 2014 Copyright 2014 by FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify
INSPECTION AND TESTING FORM
INSPECTION AND TESTING FORM SERVICE ORGANIZATION PROPERTY NAME (USER) DATE: 08-04-15 TIME: 8:00 Name: Siemens Industries Inc. Name: Kcvtcs Madisonville Tech, School Bldg. Address: 2700 Stanley Gault Pkwy
Austin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
UL Fire Door Inspection Service. UL Fire Alarm Certification Program. A valuable but misunderstood resource for jurisdictions
2013 Issue 2 2 A Strong Foundation 3 Introducing UL Fire Door Inspection Service 6 Enhanced UL Marks Coming Your Way Soon UL Fire Alarm Certification Program A valuable but misunderstood resource for jurisdictions
Fire Alarm System Monitoring, a Primer for the Property Owner David Duggan, 2005
Fire Alarm System Monitoring, a Primer for the Property Owner David Duggan, 2005 Problem: How does a property owner / manager know when a fire alarm system is required for his premises, and just as important,
Central Station Interface with Fire Alarm and the Relevant Codes & Standards
Central Station Interface with Fire Alarm and the Relevant Codes & Standards By: Kim Caron Director of Business Development Communication Paths History Panel Testing Requirements ULC Listed Station requirements
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
Wireless Mesh Networks and Applications in the Alarm Industry. A Technology Overview. Presented by
Wireless Mesh Networks and Applications in the Alarm Industry A Technology Overview Presented by Wireless Mesh Networks and Applications in the Alarm Industry Table of Contents Page 1.0 What is Wireless
AETNA FIRE ALARM SERVICE CO., INC.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the inspection or test. It shall be permitted to modify this form as needed
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014 1.1 To acquire an installation
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal [email protected] Fax (631) 224-5458
OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal [email protected] Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for
221.01 PURPOSE AND GENERAL POLICY...221-1 221.02 DEFINITIONS...221-1. 221.03 ALARM PERMITS...221-1 (1) Permit Fees...221-2
TABLE OF CONTENTS ALARMS ORDINANCE 221.01 PURPOSE AND GENERAL POLICY...221-1 221.02 DEFINITIONS...221-1 221.03 ALARM PERMITS...221-1 (1) Permit Fees...221-2 221.04 CENTRAL ANSWERING STATION ALARM...221-2
PASSED AND APPROVED BY THE PRESIDENT AND BOARD OF TRUSTEES
VILLAGE OF NORTH RIVERSIDE 1 ORDINANCE NO. 91-0-10 AN ORDINANCE REGARDING BURGLAR. HOLDUP. AND FIRE ALARM SYSTEMS PASSED AND APPROVED BY THE PRESIDENT AND BOARD OF TRUSTEES OF THE VILLAGE OF NORTH RIVERSIDE
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST All fire alarm system plan submittals must include this Fire Alarm System Plan Submittal Checklist. PLAN APPROVAL - No work shall be performed until plans are
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
White Paper. Why Cellular as a Single Transmission Path meets the Requirements of NFPA 72. The Gradual Demise of POTS
White Paper Why Cellular as a Single Transmission Path meets the Requirements of NFPA 72 The purpose of this white paper is to provide documentation supporting the use of cellular as a single communication
Peter Lowitt President Lowitt Alarms and Security Systems, Inc. Chairman CSAA Public Sector Liaison Committee
Peter Lowitt President Lowitt Alarms and Security Systems, Inc. Chairman CSAA Public Sector Liaison Committee Joint IAFC CSAA Committee - False Dispatch Reduction - - Agenda - How we got here Peter Lowitt
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
AlarmNet Commercial Fire. We ve Got You Covered
AlarmNet Commercial Fire We ve Got You Covered When seconds count...that s when AlarmNet s got Thousands of fires occur in offices every year, resulting in injuries, deaths and over $2.6 billion in direct
Chapter 4. Regulation of Alarm Systems
Chapter 4 Regulation of Alarm Systems 5-4-1 Title 5-4-2 Declaration of Purpose 5-4-3 Definitions 5-4-4 Administrative Rules 5-4-5 Automatic Dialing Devices 5-4-6 Direct Connections to the Police Department
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
What Should I Expect From My Alarm Monitoring Station?
What Should I Expect From My Alarm Monitoring Station? When the alarm goes off... What actions will the operators take? When will they dispatch the authorities? What actions do I need to take? Monitoring
FIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
Life Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
Section 1: Definitions
ARTICLE XIV: REGISTRATION AND ENFORCEMENT OF ALARM SYSTEMS Section 1: Definitions A. Alarm Company is a person or business that sells, provides, monitors, maintains, services, repairs, alters, replaces,
Chapter 67 ALARM SYSTEMS
Chapter 67 ALARM SYSTEMS 67-1. Title. 67-2. Declaration of purpose. 67-3. Definitions. 67-4. Administrative rules. 67-5. Automatic dialing devices. 67-6. Direct connections to the Police Department. 67-7.
Fire Alarm Log Book. Any activity regarding this system must be documented in writing.
CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
CHAPTER 8. Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13)
CHAPTER 8 Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13) Section Title Number 5-8-1 Title 5-8-2 Declaration of Purpose 5-8-3 Definitions 5-8-4 Administrative Rules 5-8-5 Supervised Fire
AlarmNet Network Overview
AlarmNet Network Overview AlarmNet is a family of communications services designed specifically for the security industry. AlarmNet is designed to be a cost effective alternative or backup to the transmission
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
Phone Company or Phony Company? Part 2 by Dean K. Wilson, P.E.
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 question: Phone Company or Phony Company? Part 2 by Dean K. Wilson, P.E. In the March/April 2008 edition of, I attempted to answer the following Question:
SOLUTION BRIEF. Motorola FSA4000. How to Achieve Near 100% Fire Station Alerting Reliability
SOLUTION BRIEF Motorola FSA4000 How to Achieve Near 100% Fire Station Alerting Reliability CONTENTS 2 Abstract 2 Introduction 2 Rapid Response Depends on Reliable Dispatch and Alerting Systems 3 Most Approaches
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
ARTICLE 735. Emergency Alarm System
ARTICLE 735 Emergency Alarm System 735.01 Definitions 735.02 Approved Alarm Companies 735.03 Registration Required; Transferability; False Statements; And Registration for Apartment Complexes 735.04 Alarm
University Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
VILLAGE OF DOWNERS GROVE REPORT FOR THE VILLAGE COUNCIL MEETING FEBRUARY 4, 2014 AGENDA
ITEM ORD 00-05473 VILLAGE OF DOWNERS GROVE REPORT FOR THE VILLAGE COUNCIL MEETING FEBRUARY 4, 2014 AGENDA SUBJECT: TYPE: SUBMITTED BY: Wireless Alarms Resolution Ordinance Motion Discussion Only James
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
ORDINANCE REGARDING ALARMS IN THE TOWN OF PLAINVILLE
ORDINANCE REGARDING ALARMS IN THE TOWN OF PLAINVILLE SECTION I. PURPOSE AND INTENT. The purpose of this ordinance is to encourage Alarm Users and Alarm Businesses to maintain the operational reliability
C. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
Fire Station IP Alerting System
SCOPE OF SERVICES Fire Station IP Alerting System The County desires to acquire a Fire Station Alerting System ( System ) that will interface with the County s Motorola CAD system (Premier CAD v7, formally