BILL OF QUANTITIES. 1.0 LOAD END SUBSTATION 69/22.9kV. Qty Unit Unit Cost Total Cost A. ELECTRICAL MATERIALS
|
|
- Morris Hawkins
- 7 years ago
- Views:
Transcription
1 1.0 LOAD END SUBSTATION 69/22.9kV BILL OF QUANTITIES DESIGN AND BUILD, FURNISHING, INSTALLING, TESTING, AND COMMISSIONING OF 230/69 KV SUBSTATION, 69/22.9 KV LOAD END SUBSTATION, AND 69 KV DOUBLE CIRCUIT TRANSMISSION LINE Qty Unit Unit Cost Total Cost A. ELECTRICAL MATERIALS A1. Power Transformer 100 MVA Two winding 3-Phase 2 sets Php Php 69kV delta-22.9kv ground wye with neutral earthing resistor class ONAN/ONAF/ONAF, complete with oil all appurtenances, and on-load tap changing mechanism 16 steps at 0.625% above and 16 steps at below normal. Low impedance and maximum of 250 kw loss at rated MVA A2. Power Circuit Breaker 69kV, 3-phase, 1200A, 20, ka 2 sets Php Php three pole operation, complete with the required and bushing current transformer (If dead tank type) A3. Ganged Disconnect Switch 69kV, 3-phase, 1200A, 2 sets Php Php 38KA equipped with earthing blades/switch, motor and manually group operated, complete with the required A4. Potential Transformer 69 kv, complete with the required 6 each Php Php A5. Surge Arresters 69 kv, station type, complete with the 6 each Php Php required A6. Substation Steel Structure including bolts, washer, etc 1 lot Php Php hot dipped galvanized complete with all the required A7. Installation Materials consisting of conductors 1 lot Php Php insulators, connectors, pole line hardwares and other A8. Grounding Materials complete with the required 1 lot Php Php materials for aerial and grounding mat A9. AC and DC Auxialiary Panels, indoor type, 3 phase lot Php Php VAC and 48 VDC complete main, tie, branch breakers with the required equipment, devices cables, conduits etc and A VDC Power Supply System, indoor type, complete 2 each Php Php with the required batteries and A VDC Battery Charger indoor type, complete with the 2 each Php Php required A12. PowerControl, Instrumentation and Protection 1 lot Php Php Cables, complete with insulated terminal lugs, glands, etc A13 Cable Trays (various type) hot dipped galvanized, 1 lot Php Php complete with supports, fittings, and other A14 Outdoor Lighting System complete with the required 1 lot Php Php fixtures, posts, conduits, conduit fittings, conductors foundations, etc A15 Metal Clad Swgr 22.9kV, 3-phase, 60 HZ, comprises of 2 each Php Php circuit breakers, current transformer with cubicle, 150KVA 22.9kv/230volts 3 phase station service transformer, potential transformer, digital ammeter with transfer switch, digital voltmeter with transfer switch, control switch, complete with the required, outdoor type, free standing
2 A16 Substation Control System Main Control Switchboard, 1 lot Php Php with all instrument, meters, indicators, control switches, annunciators, push buttons, LED indicating lamps, terminal blocks, wiring and miscellaneous auxiliary and accessory devices A17 Substation Protection System a. Transformer Protection (Main 1 and 2) complete 2 each Php Php with the required protective relays and b kv Feeder Protection System, complete with 2 each Php Php the required protective relays and A18 Spares, Spare parts and tools as per technical data data sheets; a. Power Transformer 1 lot Php Php b. 69 kv Power Circuit Breakers 1 lot Php Php c. 69 kv Ganged Disconnect Switches 1 lot Php Php d. 69 Kv Potential Transformers 1 lot Php Php e. 69 kv Surge Arresters 1 lot Php Php f. Metal Clad Switchgear 1 lot Php Php g. AC & DC Auxillary Switchboard 1 lot Php Php h. Storage Batteries 1 lot Php Php i. Battery Charger 1 lot Php Php j. Main Control Switchboard 1 lot Php Php k. Substation Protection System 1 lot Php Php A19 Current Transformer, 69 kv, 1200:5A Multi ratio, three 6 sets core, outdoor type oil filled, free standing complete with support structure and (Applicable if live tank) Item A SUB-TOTAL ELECTRICAL WORK 69/22.9kV B. FURNISHING OF LABOR, EQPT TOOLS AND MATERIALS FOR THE ERECTION, INSTALLATION, FIELD TESTING AND COMMISSIONING OF SUBSTATION EQUIPMENT AND IT'S ASSOCIATED CONTROL AND PROTECTION AND EQUIPMENT NECESSARY TO COMPLETE THE FOLLOWING ITEMS OF WORK: B1. Power Transformer 100 MVA 69/22.9 Kv 2 sets Php Php B2. Power Circuit Breaker 2 sets Php Php B3. Ganged Disconnect Switch 2 sets Php Php B4. Potential Transformer 6 each Php Php B5. Surge Arresters 6 each Php Php B6. Substation Steel Structures 1 lot Php Php B7. Installation Materials 1 lot Php Php B8. Grounding Materials 1 lot Php Php B9. AC and DC Auxialiary Panel 1 lot Php Php B volts DC Power Supply System 2 each Php Php B Volts DC Battery Charger 2 each Php Php B12. PowerControl, Instrumentation 1 lot Php Php
3 B13. Cable tray 1 lot Php Php B14. Outdoor Lighting System 1 lot Php Php B15. Metal Clad Swgr 22.9 kv 2 each Php Php B16. Substation Control System 1 lot Php Php B17. Substation Protection System 69kV and 22.9kV 2 each Php Php B18 Current Transformers 6 each Php Php Item B SUB TOTAL FURNISHING OF LABOR, EQPT, TOOLS, etc Php Php C. CIVIL WORKS COMPLETE DESIGN, FURNISH, INSTALL, CONSTRUCT, PLACE, APPLY AND / OR LAY, INCLUDING FURNISHING OF PLANT, LABOR, EQUIPMENT AND MATERIALS C1. 69/22.9 kv EQUIPMENT FOUNDATION Consisting of 1 lot Php Php concrete (211kg/cm²), Non-shirk Grout, Reinforcing Steel Bars (Grade 275), Excavation and backfill, Leveling Concrete (141 kg/cm²) and other incidentals required to complete a. Power Transformer 2 lot b. Power Circuit Breaker 2 lot c. Current Transformer 6 lot d. Voltage Transformer 6 lot e. Surge Arresters 6 lot f. Ganged Disconnect Switch 2 lot g. Metalclad Switchgear 2 lot C2. 69 kv Gantry Structure Consisting of concrete 1 lot Php Php (211kg/cm²), Non-shirk Grout, Reinforcing Steel Bars (Grade 275), Excavation and backfill, Leveling Concrete (141 kg/cm²) and other incidentals required to complete C3. Roadways, parking area, concrete curve & gutter 1 lot Php Php Construction of access road from the existing roadway to the transformer area, consisting of Concrete Pavement (211kg/cm²), Curb and Gutter (176kg/cm²) including dowels, Reinforcing steel bars (Grade 275, Aggregate sub-base and other incidentals required to complete the work C4. Drainage System - Consisting of different sizes of 1 lot Php Php RCDP, Drainage Appurtenances consisting of Concrete (176kg/cm²), Reinforcing steel bars Grade 275), Excavation and backfill, Miscellaneous Steel (ASTM A36), CHB including demolition/restoration works for the affected portion of the existing drainage appurtenances and other incidentals required to complete the work.
4 C5. Oil/Water Separator - Consisting of concrete 1 lot Php Php (211kg/cm²), Reinforcing Steel Bars (Grade 275), Excavation and backfill, Miscellaneous Steel, Galvanized Steel pipe, B.I. Pipe, including its tapping to the nearest drainage system and other incidentals required to complete the work. C6. Concrete Firewall - Between transformers consisting of 1 lot Php Php Concrete (211kg/cm²), Reinforcing Steel Bars (Grade 275), Excavation and Backfill, Levelling Concrete (141kg/cm²) and other incidentals required to complete the work. C7. Cable Trenches - Consisting of Concrete (211kg/cm²) 1 lot Php Php Reinforcing Steel Bars (Grade 275), Excavation, levelling Concrete (141kg/cm²), Checkered Steel Plate Cover, Stiffener, Embedded Metals, Steel angle, pits, Discharge Pipes including demolition/restoration and connection to PSPC trenches, contractor to coordinate with PSPC. C8. Cable Pipe Crossing Roadways - Consisting of 1 lot Php Php Concrete (211kg/cm²), Reinforcing Steel Bars (Grade 275), Excavation, Sand and Gravel bedding, upcv Pipes,Discharge Pipes and other incidentals required to complete C9. Switchyard Gravel Surfacing - Gravel surfacing on the 1 lot Php Php bays where the equipment will be installed with the lines and extent as directed by the owner. C10. Seclusion Fence and Gate - Endorsing the 69kV and 1 lot Php Php 22.9kV switchyard consisting of Hot Dipped Galvanized Wire Mesh Gauge #10, G.I. Pipes Schedule 40, Miscellaneous Steel (ASTM A36), Concrete (211 kg/cm²) Reinforcing Steel Bars (Grade 275), Excavation and Baclfill, and other incidentals required to complete the work. ITEM C SUB-TOTAL CIVIL WORKS D. ARCHITECTURAL WORKS D1. Control House (160 sq m) Reinforced concrete 1 lot Php Php structure, complete with the required civil/structural/sanitary, electrical and mechanical (HVAC & Domestic water supply) system E. OCCUPATIONAL HEALTH & SAFETY IN CONSTRUCTION E1. Personal Protective eqpt 1 lot Php Php E2. Clinical Materials 1 lot Php Php E3. Sinages and Barricades 1 lot Php Php E4. Salary and wages of health and safety personnel 1 lot Php Php Item E SUB-TOTAL OHSC Php Php SUB-TOTAL 69/22.9 Kv LOAD END S/S Php Php
5 2.0 CLARK SUBSTATION 230/69kV A. ELECTRICAL WORKS A1. Power Transformer 100 MVA Three winding autotransformer 2 sets Php Php type 3-Phase 230kV wye/13.8 delta/69kv ground wye with neutral earthing resistor class ONAN/ONAF/ONAF, complete with oil all appurtenances, and on-load tap changing mechanism with taps of 16 steps at 0.625% above and 16 steps at 0.625% below normal, Cupper winding, Impedance equal to existing transformer, low Impedance and 230KW power loss at MVA rating, should be able to operate parallel with existing. A2. Power Circuit Breaker 230kV, 3-phase, 1200A, 20, ka three pole operation, complete with the required and bushing current transformer (If dead tank type) poles 2 sets Php Php 3 poles 6 sets Php Php A3. Power Circuit Breaker 69kV, 3-phase, 1200A, 20, ka 4 sets Php Php three pole operation, complete with the required and bushing current transformer (If dead tank type) A4. Ganged Disconnect Switch 230kV, 3-phase, 1200A, 14 sets Php Php 38KA equipped with 460 vac 3 phase motor and manually group operated, complete with the required A5. Disconnect Switch 69kV, 3-phase, 1200A, 38 ka 8 sets Php Php equipped with earthing blades, motor and manually group operated, complete with the required A6. Potential Transformer 230 kv, complete with the 6 each Php Php required A7. Surge Arresters 230 kv, station type, complete with the 6 each Php Php required A8. Substation Steel Structure including bolts, washer, etc 1 lot Php Php hot dipped galvanized complete with all the required A9. Installation Materials consisting of conductors 1 lot Php Php insulators, connectors, pole line hardwares and other A10. Grounding Materials complete with the required 1 lot Php Php materials for aerial and grounding mat A11. AC and DC Auxialiary Panels, indoor type, complete 1 lot Php Php with the required equipment, devices and A12. Distribution Board 125 VDC complete with enclosure, 2 each Php Php main, tie branch breakers,and for installation. Number of breakers to supply four (4) additional bays A13. Distribution Board 3 Phase 460/230 VAC with 2 each Php Php enclusure, main, tie, and branch circuit and fot Accessories for installation. Number of circuit breaker to include 4 additional bays A14. PowerControl, Instrumentation and Protection 1 lot Php Php Cables, complete with insulated terminal lugs, glands, etc. A15. Cable Trays (various type) hot dipped galvanized, 1 lot Php Php complete with supports, fittings, and other A16. Switchyard Lighting System complete with the 1 lot Php Php required fixtures, posts, conduits, conduit fittings, conductors foundations, etc
6 A17. Bay Control Unit with provision for integration to existing 1 lot Php Php Micro Processor Base Control complete with necessary A18. Substation Protection System a. Transformer Protection (Main 1 and 2) complete 2 sets Php Php with the required protective relays and b. 69 kv Feeder Protection System, complete with 2 sets Php Php the required protective relays and A20. Spares, Spare parts and tools a. Power Transformer 1 lot Php Php b. 230 kv Power Circuit Breakers 1 lot Php Php c. 230 kv Ganged Disconnect Switches 1 lot Php Php d. 230 Kv Potential Transformers 1 lot Php Php e. 230 kv Surge Arresters 1 lot Php Php g. AC & DC Auxillary Switchboard 1 lot Php Php h. Main Control Switchboard 1 lot Php Php i. Substation Protection System 1 lot Php Php A21 Current Transformer, 230 kv, 1200:5A Multi ratio, three 48 sets Php Php core, outdoor type oil filled, free standing complete with support structure and (Applicable if live tank) A22 Ganged Disconnect Switch 230kV, 3-phase, 1200A, 2 sets Php Php 38KA equipped with earthing blades, 460 vac 3 phase motor and manually group operated, complete with the required A23 Periperal unit for the expansion of existing bus protection 1 lot Php Php compatible to the existing unit A24 Current Transformer 13.8 kv, 1500:5A with resistor by 3 sets Php Php contractor to design the size. A25 Breaker Fail Protection relay 8 sets Php Php B. Item A SUB-TOTAL ELECTRICAL MATERIALS 230/69 Kv Php Php FURNISHING OF LABOR, EQPT TOOLS AND MATERIALS FOR THE ERECTION, INSTALLATION, FIELD TESTING AND COMMISSIONING OF SUBSTATION EQUIPMENT AND IT'S ASSOCIATED CONTROL AND PROTECTION AND EQUIPMENT NECESSARY TO COMPLETE THE FOLLOWING ITEMS OF WORK: B1. Power Transformer 100 MVA 230/69 Kv 2 sets Php Php B2. Power Circuit Breaker 8 sets Php Php B3. Ganged Disconnect Switch 16 sets Php Php B4. Voltage Transformer 6 each Php Php B5. Surge Arresters 6 each Php Php B6. Substation Steel Structure 1 lot Php Php B7. Installation Materials 1 lot Php Php B8. Grounding Materials 1 lot Php Php
7 B9. AC and DC Auxialiary Panel 1 lot Php Php B10 PowerControl, Instrumentation 1 lot Php Php B11. Cable tray 1 lot Php Php B12. Switchyard Lighting System 1 lot Php Php B16. Bay control unit 1 lot Php Php B17. Substation Protection System 2 each Php Php B19 Current Transformer 48 each Php Php Item B SUB TOTAL FURNISHING OF LABOR, EQPT, TOOLS etc Php Php C. CIVIL WORKS COMPLETE DESIGN, FURNISH, INSTALL, CONSTRUCT, PLACE, APPLY AND / OR LAY, INCLUDING FURNISHING OF PLANT, LABOR, EQUIPMENT AND MATERIALS C1. EQUIPMENT FOUNDATION Consisting of concrete 1 lot Php Php (211kg/cm²), Non-shirk Grout, Reinforcing Steel Bars (Grade 275), Excavation and backfill, Leveling Concrete (141 kg/cm²) and other incidentals required to complete a. Power Transformer 2 lot Php Php b. Power Circuit Breaker 8 lot Php Php c. Current Transformer 6 lot Php Php d. Voltage Transformer 6 lot Php Php e. Surge Arresters 6 lot Php Php f. Ganged Disconnect Switch 18 lot C kv Gantry Structure Consisting of concrete 1 lot Php Php (211kg/cm²), Non-shirk Grout, Reinforcing Steel Bars (Grade 275), Excavation and backfill, Leveling Concrete (141 kg/cm²) and other incidentals required to complete C3. Roadways, parking area, concrete curve & gutter 1 lot Php Php Construction of access road from the existing roadway to the transformer area, consisting of Concrete Pavement (211kg/cm²), Curb and Gutter (176kg/cm²) including C4. dowels, Reinforcing steel bars (Grade 275, Aggregate Sub base and other incidentals required to complete the work. Drainage System - Consisting of different sizes of RCDP, Drainage Appurtenances consisting of Concrete 1 lot Php Php (176kg/cm²), Reinforcing steel bars Grade 275), Excavation and backfill, Miscellaneous Steel (ASTM A36), CHB including demolition/restoration works for the affected portion of the existing drainage appurtenances and other incidentals required to complete C5. Oil/Water Separator - Consisting of concrete 1 lot Php Php (211kg/cm²), Reinforcing Steel Bars (Grade 275), Excavation and backfill, Miscellaneous Steel, Galvanized Steel pipe, B.I. Pipe, including its tapping to the nearest drainage system and other incidentals required to C6. complete the work Concrete Firewall - Between transformers consisting of Concrete (211kg/cm²), Reinforcing Steel Bars (Grade 3 lots Php Php 275), Excavation and Backfill, Levelling Concrete (141kg/cm²) and other incidentals required to complete the work.
8 C7. Cable Trenches - Consisting of Concrete (211kg/cm²) 1 lot Php Php Reinforcing Steel Bars (Grade 275), Excavation, levelling Concrete (141kg/cm²), Checkered Steel Plate Cover, Stiffener, Embedded Metals, Steel angle, pits, Discharge Pipes including demolition/restoration and works for the affected portion of the existing cable trench to connect the new trench and other incidentals required to complete C8. Cable Pipe Crossing Roadways - Consisting of 1 lot Php Php concrete (211kg/cm²), Reinforcing Steel Bars (Grade 275) Excavation, Sand and Gravel bedding, upcv Pipes, Discharge Pipes and other incidentals required to complete C9. Switchyard Gravel Surfacing - Gravel surfacing on the 1 lot Php Php bays where the equipment will be installed with the lines and extent as directed by the owner. C10. Seclusion Fence and Gate - Endorsing the 230kV and 1 lot Php Php 69kV switchyard consisting of Hot Dipped Galvanized Wire Mesh Gauge #10, G.I. Pipes Schedule 40, Miscellaneous Steel (ASTM A36), Concrete (211 kg/cm²) Reinforcing Steel Bars (Grade 275), Excavation and Backfill and other incidental to complete the work. C11. 69kV Gantry Structure Consisting of concrete 1 lot Php Php (211kg/cm²), Non-shirk Grout, Reinforcing Steel Bars (Grade 275), Excavation and backfill, Leveling Concrete (141 kg/cm²) and other incidentals required to complete ITEM C SUB-TOTAL CIVIL WORKS Php Php D. OCCUPATIONAL HEALTH AND SAFETY IN CONSTRUCTION D1. Personal Protective eqpt 1 lot Php Php D2. Clinical Materials 1 lot Php Php D3. Signage's and Barricades 1 lot Php Php D4. Salary and wages of health and safety personnel 1 lot Php Php Item D SUB-TOTAL OHSC Php Php SUB-TOTAL 230/69kV Substation Php Php C. 69 Kv TRANSMISSION LINE From Clark S/S to STS Double Circuit (1 x 410 TASCR) on Concrete pole, clearance over roadway as per PEC, IEC, ANSI, NESC, maximum span is 67 meters on 70 foot concrete poles D. Load End Metering System Multi ratio 1200:5A 0.3 accuracy class, Burden B-0.1 to 0.9 Weather proof enclosure, Voltage transformer 0.3 accuracy, with Billing meter for electronic billing system. 4.8 KM Php Php 2 sets Php Php E Reconfiguration/ Parameterazation/ Data Base 1 lot Php Php Configuration of existing MBSC System complete with Bay Control Units, Cables,, periperal, etc to conform with the new set-up of Clark S/S F DESIGN COST Php Php TOTAL PROJECT COST Php Php
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
More informationFundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
More information2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
More informationSECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
More informationINDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions
More informationELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F
ELECTRICAL ENGINEERING DESIGN CRITERIA APPENDIX F TABLE OF CONTENTS Appendix F - Electrical Engineering Design Criteria F.1 Introduction...F-1 F.2 Codes and Standards...F-1 F.3 Switchyard and Transformers...F-1
More informationCustomer Substation Manual 08/05/02
Customer Substation Manual Table of Contents Section Page 2 of 85 Description 0 Preface 010.00 General 010.10 Information Required for the Review of New Customer Substations 010.20 New Customer Substation
More informationQUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
More informationSubmit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationMEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
More informationIRRIGATION PUMPING Table of Contents - Section 900
IRRIGATION PUMPING Table of Contents - Section 900 PARAGRAPH 900.1 GENERAL 1 900.2 METERING REQUIREMENTS 1 900.3 CUSTOMER S CONTROL EQUIPMENT 2 900.4 SERVICE CONDUCTOR REQUIREMENTS 2 900.5 RECOMMENDATIONS
More informationDigital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
More informationDesign Criteria Additions Related To PJM IPP R02 project
Design Criteria Additions Related To PJM IPP R02 project GENERAL DESCRIPTION OF THE PPL ELECTRIC UTILTIES 500 KV SYSTEM Existing System: This document describes the design details of the EXISTING 500 kv
More informationTop Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
More informationHow To Get A Power Line Extension
GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs
More information261000 Medium Voltage Electrical Distribution
Sections Included In This Standard: 1.1 General 1.2 Underground Cable 1.3 Medium Voltage Switches 1.4 Transformers 1.5 Electrical Manholes 1.6 Switch Vaults 1.7 Distribution Switchgear/Switchboards This
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More informationANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
More informationMEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
More informationBASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
More information3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
More informationELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
More informationSan Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS
San Antonio Water System Standard Specifications for Construction ITEM NO. 854 SANITARY SEWER LATERALS 854.1 DESCRIPTION: This item shall govern sanitary sewer laterals installed in accordance with these
More informationwww.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
More informationTS 813 GROUNDING AND BONDING TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET GROUNDING
TORONTO TRANSPORTATION January 2012 TS 813 GROUNDING AND BONDING TABLE OF CONTENTS 1. DRAWINGS TTD 813.001 TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD 813.005 CONTROLLER CABINET
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationAsset Management Plans
November 213 Introduction Table of Contents Page # ACS Buildings & Grounds 2 Purpose and Scope ACS Buildings & Seismic 3 The purpose of these ( Plans ) is to demonstrate how we intend to deliver on the
More informationUnified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
More informationSWITCHGEAR. EGP Switchgear
SWITCHEA EP Switchgear Cat generator set paralleling switchgear has been designed to integrate with Cat EMCP3 generator set controls. Now you can get greater efficiency, reliability and dependability all
More informationPower Plant Electrical Distribution Systems
PDH Course E184 Power Plant Electrical Distribution Systems Gary W Castleberry, PE 2008 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
More informationApproved Meter Sockets and Cabinets
Single Unit Residential Guide 1 PHASE, 120/240 VOLT S METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to center of meter ± 100 mm ( 4
More informationUNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
More informationSCOPE OF WORK - SUBSTATION
SCOPE OF WORK - SUBSTATION VI - i TABLE OF CONTENTS 4.2 SCOPE OF WORK - SUBSTATIONS... 1 4.2.1 General... 1 4.2.2 Standard Substation... 2 4.2.3 33 kv Switchgear GIS Type... 2 4.2.3.1 Transformer Bay...
More informationEmirates Aluminium starts up World s first fully integrated power distribution system from ABB
Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s
More informationSWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
More informationTECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT
TECHNICAL SPECIFICATIONS & SPECIAL CONDITIONS OF CONTRACT FOR ELECTRICAL WORKS CHAPTER 1 SPECIAL CONDITIONS OF CONTRACT 1.1 General 1.1.1 These Special Conditions of Contract supplement the General Instructions.
More informationEARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
More informationSelecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
More informationStep Voltage Regulators
Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions
More information3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
More informationMOBILE HOME SERVICE REQUIREMENTS GAS
ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS
More informationSimple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
More informationFusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
More informationHow To Plan Out An Array Of Solar Panels
CITY OF DOWNEY COMMUNITY DEVELOPMENT, BUILDING AND SAFETY 11111 Brookshire Avenue Downey, CA 90241 562.904.7142 (www.downeyca.org) B SECTION 01/01/2011 EFFECTIVE DATE PHOTOVOLTAIC 032 FORM NUMBER 2013
More informationTable of Contents. TransformerIQ FAQs 1
[12/12] FAQs Table of Contents FAQ 1. What size transformer will TransformerIQ monitor?... 2 FAQ 2. Are there different TransformerIQ versions?... 2 FAQ 3. How are the units powered?... 2 FAQ 4. What is
More informationMTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS
Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT
More informationAMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationCustomer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances
Page 50 of 100 Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances (Replaces A-190556) THIS CUSTOMER REFERENCE SPECIFICATION (CRS) IS PART OF THE RULES FOR
More informationCONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION
CONSOLIDATED EDISON CO. OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT SUBSTATION & EQUIPMENT SECTION SPECIFICATION EO-5023 REVISION 3 MARCH 2003 REQUIREMENTS FOR
More informationLightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
More informationSpecification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
More informationPower transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
More informationA. Shop Drawing submittals shall include, but not be limited to, the following:
SECTION 26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical
More informationCATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)
CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) Fig1. CPTR SMART CONTROL PRECISION CUSTOMIZED MANUAL OR AUTO SCR OR DIODE DRY TYPE SWITCH MODE DRY TYPE SCR OR DIODE OIL TYPE 1 INDEX PAGE 1. Cover 2. Index
More informationInstallation Guide (Typical) For Micro-Comm Radio Telemetry And Control Systems
Installation Guide (Typical) For Micro-Comm Radio Telemetry And Control Systems Project: Location: Micro-Comm Project Manager: NOTE: This Installation Guide is intended to be a Typical Installation reference
More informationHomeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
More informationDead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
More informationThree-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
More informationProduct brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms
Product brochure Multi Functional Switchgear PASS M00 72.5 kv Flexible and compact switchgear solutions for windfarms The future of Wind Farms As offshore wind farms move towards deploying higher capacity
More informationSECTION 02221 SELECTIVE DEMOLITION
SECTION 02221 PART 1 -GENERAL 1.01 DESCRIPTION This section includes all material, labor, machinery and supervision required to demolish and remove the following items where applicable and as noted on
More informationDESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: -
PROPOSED KISUMU HOUSING 3 BEDROOM-TYPE 1 ELECTRICAL INSTALLATION -SITE 01 DESCRIPTION UNIT QTY RATE TOTAL (KSHS) Supply and install the following: - 1.0 Final sub-circuit from Consumer Unit to lighting
More informationServices. Three Phase Service
Services Primary Service vs Secondary Service Overhead vs Underground Common Service Types Three Phase Wye Closed Open Delta Corner Grounded Center Tapped Open Single Phase Three Phase Service Wye Delta
More information270526-TC Grounding and Bonding for Telecommunications Systems
270526-TC Grounding and Bonding for Telecommunications Systems Part 1 - General Related Documents The following related sections of the OT standards shall also be applicable to this section. OT Engineer
More informationSecondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
More informationGROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
More informationTECHNICAL SPECIFICATIONS
1. Standards BOS Item / System I ii iii TECHNICAL SPECIFICATIONS Applicable BIS /Equivalent IEC Standards / Applicable MNRE Specifications Standard Description Standard Number Crystalline Silicon Terrestrial
More informationUnderground Commercial Electric Service
Underground Commercial Electric Service SCANA Corporation 2013 Revised: June 2013 Table of Contents SECTION PAGE I. Specification and Requirements 2 A. General B. Definition of Terms C. Company and Developer
More informationEARTHING SYSTEM CALCULATION
BAZIAN STEAL FACTORY S/S 132/11kV, 1x30/40MVA EARTHING SYSTEM CALCULATION Kurdistan Region Sulaimani May 2011 Bazian Steal Factory S/S 132/11kV, 1x30/40 MVA Contents: 1. Introduction... 3 2. List of references
More informationELECTRIC SERVICE HANDBOOK
ELECTRIC SERVICE HANDBOOK Revised July 2006 Table of Contents Electric Construction Title: Electric Service Handbook Page No. TOC Rev. July-06 Section 1: Introduction...1-010 Section 2: DP&L Offices...2-010
More informationPower Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
More informationSOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
More informationDefinition AC Power Distribution
COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility
More informationAUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
More informationListed are common requirements that apply to existing solar installations when altered, added to or reconfigured.
SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation
More informationBUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE
BUILDERS AND CONTRACTORS GUIDE FOR ELECTRIC SERVICE Toll Free Telephone Numbers Residential Services 800.454.3853 Commercial Services 800.653.5307 Utility Locating Company N.C. 800.632.4949 S.C. 888.721.7877
More informationElectrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
More informationGROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
More informationCustomer Metering and Services Guide
This document is an uncontrolled copy and may not be the most current copy. The most current copy is available at www.atcoelectric.com. This document is the property of ATCO Electric and may be updated
More informationCurrent Transformers Ratio / Polarity / Types
CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s
More informationCAPACITOR BANK TESTING SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for testing Capacitor Banks including capacitors, tuning reactors and inrush limiting reactors.
More informationFW-X240 AUTO TRANSFORMER Installation Manual
FW-X240 AUTO TRANSFORMER Installation Manual 1 FW-X240 Auto Transformer About OutBack Power Systems OutBack Power Systems is a leader in advanced energy conversion technology. Our products include true
More informationCurrent Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
More informationLearning Module 13: Panelboards and Switchboards. 101 Basic Series
Learning Module 13: Panelboards and Switchboards 101 Basic Series What You Will Learn We ll step through each of these topics in detail: Introduction 4 Definitions 4 Similarities Between Panelboards and
More informationENERGY NETWORKS ASSOCIATION. Electricity Industry EMF Measurement Protocol for High Field Areas
ENERGY NETWORKS ASSOCIATION Electricity Industry EMF Measurement Protocol for High Field Areas Contents 1 Introduction 1.1 Background 1.2 High Field Areas 2 High Field Area - Generation Businesses 2.1
More informationREQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE
BC Hydro Distribution Standards REQUIREMENTS FOR CUSTOMER-OWNED PRIMARY SERVICES SUPPLIED AT 4 kv TO 35 kv PRIMARY GUIDE JUNE 2010 Changes Visible Edition This document shows all changes that have been
More informationTransmission Company Of Nigeria Project Management Unit. March, 2014
Transmission Company Of Nigeria Management Unit Status Report on On-going s Presentation to The Honourable Minister Of State For Power Mohammed Wakili March, 2014 World Bank Intervention in Energy Sector
More informationCable/Conduit Conversion
Cable/Conduit Conversion Busway can be used in many applications where cable and conduit are more commonly used. The question arises, Why use busway instead of conventional cable and conduit? Benefits
More informationEngineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
More information(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS
(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS IS 12729:2004 IEC 60694(2002) 1.1 Scope This International Standard applies to a.c. switchgear and controlgear,
More informationNATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
More informationUnit Price Averages Reports
Unit Price Averages Reports 12/7/2015 UNIT PRICE AVERAGES REPORT Disclaimer The information provided in the following Unit Price Averages Report is only for the use of Alberta Infrastructure & Transportation
More informationSF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
More informationASCO SERIES 185 Power Transfer Switches
ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from
More informationPressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
More informationThree-phase AC circuits
Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
More informationChecklist Testing and inspection without interconnection
Shams Dubai Checklist Testing and inspection without interconnection Version.0 AUGUST 205 TABLE OF CONTENTS Scope...5. PV PLANT AND INSPECTION DATA... 6 2 TESTING EQUIPMENT...7 3 DOCUMENTS... 8 3. Reference
More informationSub-Bid Contractor Update Statement. Tab A - Invitation for Bids. Tab B - Instructions to Bidders
INTRODUCTORY INFORMATION TABLE OF CONTENTS 00 0101 PROJECT TITLE PAGE PROCUREMENT REQUIREMENTS (PROJECT MANUAL) Tab A - Invitation for Bids Tab B - Instructions to Bidders Tab C Bid Form for General Bids
More information