Variable Frequency Drives for Water/Wastewater. Discussion on Pump Optimization Principles and Need to Know Drive Technology
|
|
- Reynold Reed
- 7 years ago
- Views:
Transcription
1 Variable Frequency Drives for Water/Wastewater Discussion on Pump Optimization Principles and Need to Know Drive Technology
2 Pumps in Water Wastewater 2
3 WWW Challenges: Drivers/Trends Demand for WWW Age of infrastructure Legislative compliance Reduced financial resources Energy efficiency awareness Energy use Typical wastewater process 0.3% 0.1% 1.4% 0.5% energy usage breakdown Aeration 3.2% 3.9% 8.1% Collection Anaerobic Digestion Lighting and Buildings 14.2% 14.3% 54.1% Belt Press Clarifiers Grit RAS Chlorination Process = 91.9% Gravity Thickening 3
4 Water energy use 71% of consumed electricity is used to turn motors 65% of this energy is used for fluid applications Wastewater energy use
5 Finnish Technical Research Center Report: Expert Systems for Diagnosis of the Condition and Performance of Centrifugal Pumps Evaluation of 1690 pumps at 20 process plants: Average pumping efficiency is below 40% Over 10% of pumps run below 10% efficiency Major factors affecting pump efficiency Throttled valves Pump over-sizing Seal leakage causes highest downtime and cost 5
6 System Curve Uncertainty Results in Uncertain Pump Operation - and higher costs 6
7 Pump Curves 7
8 Pumps System Overview and Fundamentals 8
9 Overview The pumping system: Components Pumps Motors, engines Piping Valves and fittings Controls and instruments Heat exchangers Tanks Others End-use Water treatment Wastewater treatment Water distribution Power generation Irrigation 9
10 Overview, continued Electric utility feeder Transformer Motor breaker/ starter Adjustable speed drive (electrical) System Approach Component optimization involves segregating components and analyzing in isolation System optimization involves studying how the group functions as one as well as how changing one component can help the efficiency of another Motor Coupling Pump Fluid System Served Process(es) 10
11 Pump Fundamentals There are two basic types of pumps: 1. Centrifugal 2. Positive Displacement (PD) Use a rotating impeller to increase velocity of a liquid and its stationary components direct discharge flow to convert velocity to increased pressure Types include axial, mixed flow, and radial Move a set volume of liquid and pressure is obtained as the liquid is forced through the pump discharge into the system Types include piston, screw, sliding vane, and rotary lobe 11
12 Pump Fundamentals, continued Centrifical Pumps Impart energy to the liquid by increasing its speed in the impeller and then converting the speed to pressure through diffusion in the volute. 12
13 Pump Fundamentals, continued PD Pumps Impart energy by applying mechanical force directly to the liquid through a collapsing volume 13
14 Energy Efficiency in Pumps Load Characteristics Water Wastewater Load Characteristics Variable Torque Constant Torque Constant Power Typical Applications Centrifugal Pumps and Blowers Positive Displacement Pumps, Blowers, Mixers, and Chemical Feed Pumps No applications Energy Savings Potential Substantial Potential Largest of all VFD applications Lowest Potential No Potential The Main Target ( first priority) The Next Step ( second priority) 14
15 Pump Fundamentals, continued Centrifical pumps are constant head devices, where head loss causes a pressure drop. Frictional head loss increases with the square of velocity change of the liquid in the pipe. Static head is the energy needed to overcome an elevation or pressure difference between the suction and discharge vessels. In most cases: 15
16 Pump Fundamentals, continued System Head Curve Produced by US DOE PSAT Software Friction Head Static Head 16
17 Pump Fundamentals, continued Friction May occur in pump systems due to irrecoverable hydraulic losses in: Piping Valving Fittings (e.g., elbows, tees) Equipment (e.g., heat exchangers) Used to control flow or pressure by: Automated flow and pressure control valves Orifices Manual throttling valves 17
18 VFD Benefits with Pumps 18
19 Energy Efficiency in Pumps Motor Costs 19
20 Energy Efficiency in Pumps Energy Wastes How your money is wasted! Car example : try to regulate the speed of your car keeping one foot on the accelerator the other on the brake. Pump example : try to adjust the pump output running the motor at full speed control the flow with a throttle valve Still one of the most common control methods in industry.. with a considerable waste of energy 20
21 VFD Benefits with Pumps Physical Laws for Centrifugal Loads Its Pure Physics: Due to the laws that govern centrifugal pumps, the flow of water decreases directly with pump speed Affinity laws of centrifugal loads : Flow = f (motor speed) Pressure = f (motor speed) 2 Power = f (motor speed) 3 21
22 VFD Benefits with Pumps Physical Laws for Centrifugal Loads A motor running at 80% of full speed requires 51% of the electricity of a motor running at full speed. 22
23 VFD Benefits with Pumps Physical Laws for Centrifugal Loads A motor running at 50% of full speed requires 12.5% of the electricity of a motor running at full speed. 23
24 VFD Benefits with Pumps Physical Laws for Centrifugal Loads A small reduction in speed produces a significant reduction in power Relevant applications : Pumps The resisting torque of centrifugal pumps varies with the square of the speed : T = kn² Power is a cubed function P = kn³ EX 50HP 10Hrs/day, 250 With 15% average speed reduction ATL = $7,460 VFD = $4,188 Savings = $3,272 Today, less than 10% of these motors are controlled with Variable Speed Drives 24
25 Efficiency of Pumping Systems 25
26 Efficiency of Pumping Systems Equations for efficiency Pump Energy Usage Pump Efficiency Measurement ( Q* H ) kw 16,667 kw kw = = * MGD (5308* η * η * η ) Q Motor Pump Drive Q = Flow( gpm) H = Head( ft) η = efficiency For Water Wastewater PSI conversion to ft = PSI * 2.31 η η Motor * η Wire to water Pump * η Drive ( Q * H ) = (5308* kw ) ( Q * H ) = (5308* kw ) 26
27 Sample Pump Calculations Actual Pump Data Single Pump Running Measurement Measured VFD Speed 54.1 Hertz Measured Power 32.3 kw Measured flow 716 GPM Measured head 74.5 PSI The image cannot be displayed. Your computer may not have enough memory to open the image, or the image may have been corrupted. Restart your computer, and then open the file again. If the red x still appears, you may have to delete the image and then insert it again. Two Pumps Running Measurement Measured VFD Speed 48 Hertz Measured Power 82.5 kw Measured flow 1452 GPM Measured head 75 PSI Three Pumps Running Measurement Measured VFD Speed?? Hertz Measured Power kw Measured flow 5125 GPM Measured head 79.4 PSI 27
28 Sample Pump Calculations FREQ KW PSIG TDH GPM GPM X TDH KW X 5308 EFFICIENCY? The image cannot be displayed. Your computer may not have enough memory to open the image, or the image may have been corrupted. Restart your computer, and then open the file again. If the red x still appears, you may have to delete the image and then insert it again. PUMP QTY three pumps two pumps one pump FREQ KW GPM KW X EFFICIENCY kw/mgd PUMP QTY? three pumps two pumps one pump 28
29 VFD Benefits with Pumps Other Benefits In addition to Energy Saving, using a VFD has many other advantages: Less mechanical stress on motor and system Less mechanical devices - Less Maintenance Process regulation with PID regulators, load management functions Reduce noise, resonance avoidance Performance and flexibility, range settings, above base operations Easier installation and settings, drive mechanics Can be controlled with Automation, Communication networks 29
30 Steps to Obtain Pump Optimization 30
31 Pump Optimization Complete a detailed Pump Assessment Pumps are usually consuming more energy than necessary: The pump is oversized and has to be throttled to deliver the right amount of flow. Energy is lost in the valve. Pumps that are not running close to their best efficiency points (BEP) operate at lower efficiency. Throttled pumps usually fall into this category. Pumps are running with by-pass, or recirculation, lines open. Pumps are running although they could be turned off. The pump is worn and the efficiency has deteriorated. The pump/system was installed or designed incorrectly (piping, base plate etc.) 31
32 Pump Optimization Complete a detailed Pump Assessment To determine whether these reasons apply, some basic information is needed: Actual system demand (flow and pressure) Operational flow rate as a function of time (the duration curve) Flow controls The pump curve Where the pump operates on the curve 32
33 Process Energy Optimization Automation is the Key Develop consistent and appropriate milestone and deliverable expecta4ons Standardize program schedule tracking requirements Establish key energy management performance metrics Produce meaningful reports that allow for clear and concise decision- making Install addi4onal monitoring equipment as needed 33
34 Considerations for Variable Frequency Drives for Water and Wastewater 34
35 VFD Topics Type(s) Enclosure / Environment / Packaging Harmonics/ Harmonic Mitigation IEEE 519 Accessability Sustainability 35
36 VFD Considerations The industry has standardized on PWM 6 pulse drives. Where 6 Pulse refers to the Front end of the Drive and a bridge of 6 diodes converting incoming AC to DC power. A DC Bus (capacitor) Insulated Gate Bipolar Transistors (IGBT) as the output components. The output of which generates a simulated RMS waveform with a constant V/Hz ratio. 36
37 One of These 37
38 Packaging Open Enclosed MCC 38
39 Harmonics Reduction This continues to be a big topic for us in Water and Wastewater The Motor loads on VFD s are a large percentage of the total load. Many Consultants have standardized on designs by HP requiring Line reactors or Multipulse Drives (typically 18 pulse). There are multiple sloutions One size does not fit all. Schneider Electric offers as standard 18 pulse VFD, Matrix Filter VFD and Active Harmonic Mitigation. 39
40 18 Pulse Drive Using the same 6 Pulse Inverter STD 6 Pulse Inverter Line Reactor 18 pulse Diode Bridge Phase Shifting XFMR 40
41 Matrix Filter Drive using the same 6 pulse Inverter STD 6 Pulse Drive Matrix Filter 41
42 Matrix Filter Drive Matrix Filter Drive Harmonic Mitigation as good or better than 18 pulse. Better Mitigation given Voltage Imbalance Footprint of Drive is Typically smaller than 18 Pulse. Efficiency of Drive is better than 18 Pulse Losses of 18 Pulse bridge + Transformer + Line Reactor > Matrix Filter. Cost is Typically Lower than 18 Pulse Output to the Motor is Identical. What s Not To Like? 42
43 Data on side by side comparisons of 18 Pulse and Matrix Filter. 43
44 Accusine used with one or many 6 pulse drives 44
45 The Variable Frequency Drive for W/ WW The Altivar 61 is our Standard 6 pulse inverter for variable speed applications used in centrifugal pump and fan / blower applications offering the highest level of features, functions, and flexibility. This same inverter is the heart of our configured enclosed applications, 18 Pulse Drives, Motor Control Centers and our new Matrix Filter Drive.. All the Inverter parts, programming, troubleshooting, wiring, interfacing, etc is common. 45
46 Other Drive/System Application Considerations Enclosed Drive or Packaged Drive Short Circuit Current Rating. SE = 100k amps as standard Power Loss Ride Through especially for pump stations. SE meets Semi F47 standards Communication Capabilities SE offers Modbus Serial and 11 additional Protocols as options. Built in Web Server and diagnostic web displays with Ethernet. 46
47 Appendix 47
48 Standard Six Pulse Inverter in 6 pulse Drive Drive in MCC 18 Pulse Matrix Filter Drive 48
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
More informationCENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.
CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As
More informationSpecifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
More informationVariable Frequency Drives and Energy Savings
Variable Frequency Drives and Energy Savings It s more than just fan and pump applications www.sea.siemens.com by: Stephen Prachyl www.usa.siemens.com/energysavings When discussing energy savings and variable
More informationUnidrive M Energy Savings
Unidrive M Energy Savings Why is this important? Some Data: Money, Lots of Money >13.5m electric motors 1Hp or greater installed in US industrial process operations. Industry spends >$33b annually on electricity
More informationThe Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction
The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V.
More informationAdditional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:
Variable Frequency Drives (or VFDs) are becoming almost standard part of aquatics equipment room packages. Most VFDs are fairly simple to install and operate however, they are quite complex with respect
More informationPump Maintenance - Repair
Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.
More informationVARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION..........................2
More informationPump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps
Pump ED 101 Positive Displacement Pumps Part I Reciprocating Pumps Joe Evans, Ph.D http://www.pumped101.com There are many pump designs that fall into the positive displacement category but, for the most
More informationCENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES
CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES 4.0 PUMP CLASSES Pumps may be classified in two general types, dynamic and positive displacement. Positive displacement pumps
More informationDATA COLLECTION AND PUMP ENERGY SAVING OPPORTUNITIES. Presented By: Rick Rumsey, P.E.
DATA COLLECTION AND PUMP ENERGY SAVING OPPORTUNITIES Presented By: Rick Rumsey, P.E. Data Collection Customer Information Pump Motor Information Pump Information Irrigation System Information Historic
More information32VFD Variable Frequency Drives for Centrifugal Chillers
32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to
More informationUnderstanding Variable Speed Drives
Understanding Variable Speed Drives April 1, 1997 Solomon S. Turkel, Solomon S. When applied properly, the variable frequency drive (VFD) is the most effective motor controller in the industry today. Modern
More informationHVAC Applications. VFD considerations for HVAC systems...
HVAC Applications VFD considerations for HVAC systems... 1 COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES)
More informationEnergy Audits Waste Water Treatment Plants
Energy Audits Waste Water Treatment Plants Ohio Water Environment Association Conference June 20, 2012 Presented by: Samuel J. Morgan, P.E., LEED AP CT Consultants, Inc. World Energy Trend US Total Energy
More informationPump Selection and Sizing (ENGINEERING DESIGN GUIDELINE)
Guidelines for Processing Plant Page : 1 of 51 Rev 01 Feb 2007 Rev 02 Feb 2009 Rev 03 KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru. (ENGINEERING DESIGN GUIDELINE)
More informationFundamentals of Inverter Fed Motors
Fundamentals of Inverter Fed Motors Technical Manual 10/02 MN780 Contents Page The Growing Use Of Inverters.................................................................. 1 How Inverters Affect Motors....................................................................
More informationSAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
More informationPumps SELECTION OF A PUMP
Pumps SELECTION OF A PUMP A water system needs to move the water produced from the source to its customers. In almost all cases in Minnesota, the source is at a lower elevation than the user so the water
More informationLine Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
More informationPUMPS TYPE OF PUMP PRESSURE/FLOW RATING CHARACTERISTICS. Centrifugal Low Pressure/High Flow Flow changes when
PUMPS Pumps provide the means for moving water through the system at usable working pressures. The operation and maintenance of these pumps are some of the most important duties for many water utility
More informationSECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
More informationTOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?
KNOWLEDGE: K1.01 [3.3/3.5] P21 Which one of the following contains indications of cavitation in an operating centrifugal pump? A. Low flow rate with low discharge pressure. B. Low flow rate with high discharge
More informationDiscover the power of e-learning! The Quick Guide to AC Variable Frequency
The Quick Guide to AC Variable Frequency This ebook is meant as an easy guide to any electrical or electronic engineer or technician, who would like to know how modern ac variable frequency drives work.
More informationC. starting positive displacement pumps with the discharge valve closed.
KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the
More informationA BRIEF INTRODUCTION TO CENTRIFUGAL PUMPS
A BRIEF INTRODUCTION TO CENTRIFUGAL PUMPS figure below is a cross section of a centrifugal pump and shows the two basic parts. Joe Evans, Ph.D IMPELLER This publication is based upon an introductory, half
More informationRotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com
13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer tsi@mbesi.com Rotating Machinery Diagnostics & Instrumentation
More informationAgricultural Pumping Efficiency Improvements
APPLICATION NOTE An In-Depth Examination of an Energy Efficiency Technology Agricultural Pumping Efficiency Improvements Summary...1 How This Technology Saves Energy...2 Types of Energy Efficiency Measures...4
More informationMinor losses include head losses through/past hydrants, couplers, valves,
Lecture 10 Minor Losses & Pressure Requirements I. Minor Losses Minor (or fitting, or local ) hydraulic losses along pipes can often be estimated as a function of the velocity head of the water within
More informationProduct Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
More informationDrives and motors. A guide to using variable-speed drives and motors in retail environments
Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility
More informationTransformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
More informationBasic Nameplate Information
Basic Nameplate Information General Information: Most equipment nameplates will have some common items of information. Many of these are self explanatory, and include: Manufacturer Manufacturerʼs address
More informationInverter technology. bulletin
Inverter technology application bulletin What is the inverter component? The inverter is an electronic power component that continuously varies the electricity supply frequency of an electric motor. The
More informationData Bulletin Variable Frequency Drives and Short-Circuit Current Ratings
Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203 03/2013 Retain for future use. Introduction Short-circuit current s (SCCRs) for variable frequency drives (VFDs) is
More informationSta-Rite Industries Basic Training Manual
LOW SPEED BOOSTER PUMP HIGH SPEED FILTER PUMP AUX 1 AUX 2 1915 0895 Sta-Rite Industries Basic Training Manual THIRD EDITION Hydraulics Pumps Motors Filtration Heaters 2668 0397NF 2003 Sta-Rite Industries,
More informationHarmonic Distortion and Variable Frequency Drives
Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation
More informationVariable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
More informationChapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
More informationSECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
More informationTECHNICAL INFORMATION Bulletin
Peerless Pump Company 2005 Dr. M.L. King Jr. Street, P.O. Box 7026, Indianapolis, IN 46207-7026, USA Telephone: (317) 925-9661 Fax: (317) 924-7338 www.peerlesspump.com www.epumpdoctor.com TECHNICAL INFORMATION
More informationIrrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County
Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology Public Utility District No. 1 of Chelan County This paper describes how to calculate energy saved by installing a variable
More informationDescription of the Water Conserv II Facility
Description of the Water Conserv II Facility Introduction The Water Conserv II (WCII) Water Reclamation Facility provides service to a majority of the southwest section of Orlando. The WCII facility has
More informationPumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic energy).
HYDRAULIC MACHINES Used to convert between hydraulic and mechanical energies. Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic
More informationUNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
More informationPrinciples of Adjustable Frequency Drives
What is an Adjustable Frequency Drive? An adjustable frequency drive is a system for controlling the speed of an AC motor by controlling the frequency of the power supplied to the motor. A basic adjustable
More informationPumps 101: Operation, Maintenance and Monitoring Basics
White Paper Pumps 101: Operation, Maintenance and Monitoring Basics Daniel Kernan Manager Monitoring and Control Group, ITT Executive Summary Pumps are at the heart of most industrial processes, and the
More informationUnderstanding Delta Conversion Online "Output Power Factor Ratings" - Part 7
Application Note #45 Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7 Introduction This application note is the seventh in a series on delta conversion theory of operation.
More informationSlide 1. Slide 2. Slide 3 288,817,200,000. Thank you for attending the session on Hot Water Re-Circulation.
Slide 1 Thank you for attending the session on Hot Water Re-Circulation. Hot Water Re-Circulation National Conference Center Lansdowne, VA March 25 th & 26 th, 2010 Slide 2 AGENDA Water Waste Statistics
More informationVariable Speed Drive (VSD) for Irrigation Pumping
United States Department of Agriculture NATURAL RESOURCES CONSERVATION SERVICE Engineering Technical Note No. MT-14 January 2010 Variable Speed Drive (VSD) for Irrigation Pumping Pumping water for irrigation
More informationModelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor
International Journal of Engineering Inventions e-issn: 78-7461, p-issn: 319-6491 Volume 3, Issue 5 (December 013) PP: 36-41 Modelling, Simulation and Performance Analysis of A Variable Frequency Drive
More informationWIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
More informationVARIABLE FREQUENCY DRIVES THEORY, APPLICATION, AND TROUBLESHOOTING
VARIABLE FREQUENCY DRIVES THEORY, APPLICATION, AND TROUBLESHOOTING BY HOWARD W. PENROSE UNIVERSITY OF ILLINOIS AT CHICAGO ENERGY RESOURCES CENTER 851 SOUTH MORGAN STREET ROOM 1213, SEO, MC156 CHICAGO,
More informationHPT High Speed Boiler Feedwater Pumps
HPT High Speed Boiler Feedwater Pumps The Heart of Your Process Types of Boiler Feedwater Pumps Diffuser Casing Segmental Ring Volute Casing Horizontal Split Diffuser Casing High Speed Barrel Casing HPT
More informationHow To Save Energy On A Power Supply
Technical Note: Using EC Plug Fans to Improve Energy Efficiency of Chilled Water Cooling Systems in Large Data Centers A Technical Note from the Experts in Business-Critical Continuity Introduction A U.S.
More informationEnergy Efficiency Best Practice Guide Pumping Systems
6 Energy Efficiency Best Practice Guide Contents 1 Introduction 4 2 Business benefits of efficient pumping systems 5 3 What is your opportunity? 7 4 Solution 1 Improve the efficiency of your existing system
More informationDrive Solutions for Electric Utilities
Drive Solutions for Electric Utilities metals cranes mining testing oil & gas solar inverters utilities cement About TMEIC A Global network TMEIC is built on the combined and proud heritage of Toshiba
More informationCommercial & Municipal Retrofit 2015 VFD Rebate
2015 VFD Rebate Section A: MEMBER INFORMATION Member Name Electric Account Number Rate Number Facility Address City State Zip Code Service Location Identification Email Mailing Address (if different from
More informationFault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1
Fault codes DM1 Industrial engines DC09, DC13, DC16 Marine engines DI09, DI13, DI16 03:10 Issue 5.0 en-gb 1 DM1...3 Abbreviations...3 Fault type identifier...3...4 03:10 Issue 5.0 en-gb 2 DM1 DM1 Fault
More informationPOSITIVE DISPLACEMENT BLOWERS & VACUUM PUMPS. Water & Wastewater Treatment Solutions
POSITIVE DISPLACEMENT BLOWERS & VACUUM PUMPS Water & Wastewater Treatment Solutions Water & Wastewater Treatment Solutions Gardner Denver understands the complex needs and challenges of the water and wastewater
More informationUnit 24: Applications of Pneumatics and Hydraulics
Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 1 HYDRAULIC PUMPS The material needed for outcome 2 is very extensive so there
More informationPEERLESS PUMP COMPANY SYSTEM ANALYSIS FOR PUMPING EQUIPMENT SELECTION
PEERLESS PUMP COMPANY SYSTEM ANALYSIS FOR PUMPING EQUIPMENT SELECTION Peerless Pump Company 005 Dr. Martin Luther King Jr. Street P.O. Box 706 Indianapolis, Indiana 4607-706 Phone: (317) 95-9661 Fax: (317)
More informationModule 9: Basics of Pumps and Hydraulics Instructor Guide
Module 9: Basics of Pumps and Hydraulics Instructor Guide Activities for Unit 1 Basic Hydraulics Activity 1.1: Convert 45 psi to feet of head. 45 psis x 1 ft. = 103.8 ft 0.433 psi Activity 1.2: Determine
More informationA.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
More informationOffshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
More informationWe will discuss common industrial applications with guides for the proper use of electric motors on these.
INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which
More information26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
More informationMaterial taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001
Pressure Control Chapter 3 Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Introduction Pressure control is a key element in the design of any circuit. Used correctly, it can
More informationWhat Is Regeneration?
What Is Regeneration? Braking / Regeneration Manual Regeneration Overview Revision 1.0 When the rotor of an induction motor turns slower than the speed set by the applied frequency, the motor is transforming
More informationCompressed Air Systems
Efficiency Vermont Guide to Savings Helping Vermont businesses save energy and money Compressed Air Systems 888-921-5990 www.efficiencyvermont.com 1 Save money and optimize system performance Air compressors
More informationABB drives for water Medium voltage drives for energy savings and life-cycle improvements
ABB drives for water Medium voltage drives for energy savings and life-cycle improvements 2 ABB drives for water Water Increasing demand for a limited resource Freshwater is one of the world s most important
More informationBOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.
SUBMERSIBLE PUMP selection A submersible pump consists of the following basic elements: < Bowl Assembly < Motor < Cable < Drop Pipe < Surface Plate (with)(without) discharge elbow DATA REQUIRED FOR SELECTION
More informationEnergy audit methodology of thermal systems Training Programme Energy Conservation in Foundry Industry
Energy audit methodology of thermal systems Training Programme Energy Conservation in Foundry Industry 11-13 August 2014 Indore Energy audits - TERI s experience Pioneered energy audits in India Highly
More informationDrives and motors. A guide to using variable-speed drives and motors in data centres
Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers
More informationMATHEMATICS FOR WATER OPERATORS
MATHEMATICS FOR WATER OPERATORS Chapter 16: Mathematics The understanding of the mathematics of water hydraulics (flows, pressures, volumes, horsepower, velocities) and water treatment (detention time,
More informationMARINE ELECTRICAL TRAINING CENTER
MARINE ELECTRICAL TRAINING CENTER SPLIT - CROATIA Introduction: Our recognized course instruction teaches electrical maintenance, testing, power studies and safety skills.withcourseslastingnomorethanfewdays,wespecializeinfast,effectiveelectricalskillstraining.
More informationHORIZONTAL PUMPING SYSTEM
HORIZONTAL PUMPING SYSTEM BORETS U.S. INC. PERFORMANCE TECHNOLOGY INNOVATION Horizontal Pumping System What is HPS? HPS classification, Pumps, Stages, Impellers, Curves/Performance, Components Why use
More informationPulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques
Drives AC Drives Using PWM Techniques Power Conversion Unit The block diagram below shows the power conversion unit in Pulse Width Modulated (PWM) drives. In this type of drive, a diode bridge rectifier
More informationMultimeter measurements on variable frequency drives using the new Fluke 289 DMM
Multimeter measurements on variable frequency drives using the new Fluke 289 DMM Application Note Editor s note: For similar instructions using the Fluke 87V DMM, reference Fluke article 12345. In the
More informationAppendix S Pump Station Evaluation
Appendix S Pump Station Evaluation Technical Memorandum Date: October 12, 2001 To: Re: Orange County Utilities Task 6.4 Raw Wastewater Pump Stations 1.0 Summary In accordance with Task 6.4 of the Orange
More informationPower Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.
Power Electronics Prof. K. Gopakumar Centre for Electronics Design and Technology Indian Institute of Science, Bangalore Lecture - 1 Electric Drive Today, we will start with the topic on industrial drive
More informationDrives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)
Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to
More informationEET272 Worksheet Week 9
EET272 Worksheet Week 9 answer questions 1-5 in preparation for discussion for the quiz on Monday. Finish the rest of the questions for discussion in class on Wednesday. Question 1 Questions AC s are becoming
More informationPacific Pump and Power
Pacific Pump and Power 91-503 Nukuawa Street Kapolei, Hawaii 96707 Phone: (808) 672-8198 or (800) 975-5112 Fax: (866) 424-0953 Email: sales@pacificpumpandpower.com Web: www.pacificpumpandpower.com Pumps
More informationUnit 24: Applications of Pneumatics and Hydraulics
Unit 24: Applications of Pneumatics and Hydraulics Unit code: J/601/1496 QCF level: 4 Credit value: 15 OUTCOME 2 TUTORIAL 3 HYDRAULIC AND PNEUMATIC MOTORS The material needed for outcome 2 is very extensive
More information7. Pumps and Motors. be downloaded free from the U.S. Department of Energy at: http://www.oit.doe.gov/bestpractices/pdfs/pumplcc_1001.
89 7. Pumps and Motors The focus of this publication is to identify best practices in energy efficiency for the chemical industry. While there are some standard approaches that are almost universally beneficial
More informationProduct Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
More informationBSM MOTOR DRIVEN CENTRIFUGAL PUMPS
PRINCIPLE OF OPERATION A hydraulically and dynamically balanced impeller with raised vane sections discharges liquid as a result of the centrifugal force developed in rotation. The head developed is entirely
More informationHarmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
More informationPulse Width Modulated (PWM)
Control Technologies Manual PWM AC Drives Revision 1.0 Pulse Width Modulated (PWM) Figure 1.8 shows a block diagram of the power conversion unit in a PWM drive. In this type of drive, a diode bridge rectifier
More informationCDX. EBARA PUMPS EUROPE S.p.A. CENTRIFUGAL PUMPS. Page - CONTENTS 100
CONTENTS Page - CONTENTS 100 - SPECIFICATIONS 200 SELECTION CHARTS 201 PERFORMANCE CHART 70 202 PERFORMANCE CHART 90 203 PERFORMANCE CHART 120 204 PERFORMANCE CHART 200 205 - CONSTRUCTIONS 300 SECTIONAL
More informationZ1000 HVAC Drive. 3 HP to 500 HP Fan and Pump Applications. Specifications
Z1000 HVAC Drive 3 HP to 500 HP Fan and Pump Applications The Z1000 variable speed drive is designed for building automation applications such as fans, pumps, and cooling towers through 500 HP. The Z1000
More informationNEW ADVANCES IN PULSE WIDTH MODULATED SLIP POWER RECOVERY DRIVES FOR PUMPS
NEW ADVANCES IN PULSE WIDTH MODULATED SLIP POWER RECOVERY DRIVES FOR PUMPS Stephan Bondy Douglas Phares Manish Verma Bill Horvath Oil & Gas segment leader Market leader, Global Drives Sales Application
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationEMI in Electric Vehicles
EMI in Electric Vehicles S. Guttowski, S. Weber, E. Hoene, W. John, H. Reichl Fraunhofer Institute for Reliability and Microintegration Gustav-Meyer-Allee 25, 13355 Berlin, Germany Phone: ++49(0)3046403144,
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationFREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
More informationPower Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER. www.ep2000.com 800.500.
Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER Introduction Heat in the System The modern facility has been revolutionized by advancements
More informationEnergy Efficiency in Pumping Systems: Experience and Trends in the Pulp & Paper Industry
Energy Efficiency in Pumping Systems: Experience and Trends in the Pulp & Paper Industry Vestal Tutterow, Lawrence Berkeley National Laboratory ABSTRACT Approximately two-thirds of all US industrial electricity
More information