(1) WALLS:- INSULATION IN CAVITY Ground Floor - Insulation above slab DETAIL 1.01a, 2011 AIR BARRIER - CONTINUITY THERMAL PERFORMANCE GENERAL NOTES

Size: px
Start display at page:

Download "(1) WALLS:- INSULATION IN CAVITY Ground Floor - Insulation above slab DETAIL 1.01a, 2011 AIR BARRIER - CONTINUITY THERMAL PERFORMANCE GENERAL NOTES"

Transcription

1

2

3 (1) WALLS:- INSULATION IN CAVITY Ground Floor - Insulation above slab DETAIL 1.01a, 2011 THERMAL PERFORMANCE CHECKLIST (TICK ALL) AIR BARRIER - CONTINUITY CHECKLIST (TICK ALL) Ensure partial fill insulation is secured firmly against inner leaf of cavity wall Floor insulation to tightly abut blockwork wall Ensure wall insulation is installed at least 225 mm below top of floor insulation 225 mm min Seal between wall and floor air barrier with a flexible sealant OR seal gap between skirting board and floor with a flexible sealant Seal all penetrations through air barrier using a flexible sealant Complying with checklist will help achieve design air permeability GENERAL NOTES The wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption Keep cavities clean of mortar snots and other debris during construction Detail applicable:- Ground-bearing floor; raft foundation; in-situ suspended ground floor slab; pre-cast suspended ground floor. Insulation above slab, with timber floor finish OPTION (TICK ONE) AIR BARRIER - OPTIONS Masonry inner leaf with wet-finish plaster, or Masonry inner leaf with scratch coat, and finished with plasterboard, or Inner leaf with plasterboard on dabs, with continuous ribbon of adhesive tape around all openings, along top and bottom of wall, and at internal and external corners, or Airtightness membrane and tapes ACCEPTABLE CONSTRUCTION DETAIL Ground Floor - Insulation above slab DETAIL 1.01a, 2011

4 (1) WALLS:- INSULATION IN CAVITY Ground Floor - Insulation above slab plus lightweight block DETAIL 1.01b, 2011 THERMAL PERFORMANCE CHECKLIST (TICK ALL) AIR BARRIER - CONTINUITY CHECKLIST (TICK ALL) Ensure partial fill insulation is secured firmly against inner leaf of cavity wall Floor insulation to tightly abut blockwork wall Ensure wall insulation is installed at least 225 mm below top of floor insulation Ensure block with a maximum Thermal Conductivity of.20 W/mK in the direction of heat flow is used and that block is suitable for use in foundations in all conditions. Block is to be installed so to avoid any effect of moisture on Thermal Conductivity 225 mm min Seal between wall and floor air barrier with a flexible sealant OR seal gap between skirting board and floor with a flexible sealant Seal all penetrations through air barrier using a flexible sealant Complying with checklist will help achieve design air permeability GENERAL NOTES The wall insulation installed below the wall DPC must be fit for purpose with regards to water absorption Keep cavities clean of mortar snots and other debris during construction Detail applicable:- Ground-bearing floor; raft foundation; in-situ suspended ground floor slab; pre-cast suspended ground floor. Insulation above slab, with timber floor finish OPTION (TICK ONE) AIR BARRIER - OPTIONS Masonry inner leaf with wet-finish plaster, or Masonry inner leaf with scratch coat, and finished with plasterboard, or Inner leaf with plasterboard on dabs, with continuous ribbon of adhesive tape around all openings, along top and bottom of wall, and at internal and external corners, or ACCEPTABLE CONSTRUCTION DETAIL Airtightness membrane and tapes Ground Floor - Insulation above slab DETAIL 1.01b, 2011

5

6

7

8 (1) WALLS:- INSULATION IN CAVITY Concrete Intermediate Floor within a dwelling DETAIL 1.04, 2011 THERMAL PERFORMANCE CHECKLIST (TICK ALL) AIR BARRIER - CONTINUITY CHECKLIST (TICK ALL) Ensure partial fill insulation is secured firmly against inner leaf of cavity wall Continue cavity wall insulation across floor abutment zone Seal gap between skirting board and floor with a flexible sealant Seal between the wall air barrier and the top and underside of the floor slab. (Dotted blue line is notional, to depict air barrier continuity through floor zone) Ensure continuous mortar bed between floor slab and top of blockwork wall Seal all penetrations through air barrier using flexible sealant Complying with checklist will help achieve design air permeability GENERAL NOTES Keep cavities clean of mortar snots and other debris during construction OPTION (TICK ONE) AIR BARRIER - OPTIONS Masonry inner leaf with wet-finish plaster, or Masonry inner leaf with scratch coat, and finished with plasterboard, or Inner leaf with plasterboard on dabs, with continuous ribbon of adhesive tape around all openings, along top and bottom of wall, and at internal and external corners, or ACCEPTABLE CONSTRUCTION DETAIL Airtightness membrane and tapes Concrete Intermediate Floor within a dwelling DETAIL 1.04, 2011

9 (1) WALLS:- INSULATION IN CAVITY Concrete Intermediate Floor between dwellings DETAIL 1.04a, 2011 THERMAL PERFORMANCE CHECKLIST (TICK ALL) AIR BARRIER - CONTINUITY CHECKLIST (TICK ALL) Ensure partial fill insulation is secured firmly against inner leaf of cavity wall Continue cavity wall insulation across floor abutment zone Seal gap between skirting board and floor with a flexible sealant Seal between the wall air barrier and the top and underside of the floor slab. (Dotted blue line is notional, to depict air barrier continuity through floor zone) Ensure continuous mortar bed between floor slab and top of blockwork wall Seal all penetrations through air barrier using flexible sealant Complying with checklist will help achieve design air permeability GENERAL NOTES Keep cavities clean of mortar snots and other debris during construction OPTION (TICK ONE) AIR BARRIER - OPTIONS Masonry inner leaf with wet-finish plaster, or Masonry inner leaf with scratch coat, and finished with plasterboard, or Inner leaf with plasterboard on dabs, with continuous ribbon of adhesive tape around all openings, along top and bottom of wall, and at internal and external corners, or ACCEPTABLE CONSTRUCTION DETAIL Airtightness membrane and tapes Concrete Intermediate Floor within a dwelling DETAIL 1.04a, 2011

10 (1) WALLS:- INSULATION IN CAVITY Timber Intermediate Floor Within a Dwelling DETAIL 1.05, 2011 THERMAL PERFORMANCE Ensure partial fill insulation is secured firmly against inner leaf of cavity wall Continue cavity wall insulation across floor abutment zone CHECKLIST (TICK ALL) AIR BARRIER - CONTINUITY CHECKLIST (TICK ALL) Mortar joints around built-in joists should be recessed or struck and carefully pointed with flexible sealant. Alternatively, joists may be fitted with proprietary shoes as they are installed. Seal shoe to blockwork face with a flexible sealant. (Dotted blue line is notional, to depict continuity of air barrier through floor zone) Seal between wall air barrier and blockwork, above and below the floor assembly Seal all penetrations through air barrier using a flexible sealant Complying with checklist will help achieve design air permeability GENERAL NOTES Keep cavities clean of mortar snots and other debris during construction Suspended timber floors may be laid in joist hangers rather than built in Where wall supports joists, thermal performance and airtightness of junction can be improved significantly by using joist hangers with shoes standing off the wall face For timber engineered joists, proprietary filler pieces must be fitted on both sides of the web between top and bottom flanges. (See manufacturer's details.) OPTION (TICK ONE) AIR BARRIER - OPTIONS Masonry inner leaf with wet-finish plaster, or Masonry inner leaf with scratch coat, and finished with plasterboard, or Inner leaf with plasterboard on dabs, with continuous ribbon of adhesive tape around all openings, along top and bottom of wall, and at internal and external corners, or Airtightness membrane and tapes ACCEPTABLE CONSTRUCTION DETAIL Timber Intermediate Floor Within a Dwelling DETAIL 1.05, 2011

11 (1) WALLS:- INSULATION IN CAVITY Timber Separating Floor Between Dwellings DETAIL 1.05a, 2011 THERMAL PERFORMANCE Ensure partial fill insulation is secured firmly against inner leaf of cavity wall Continue cavity wall insulation across floor abutment zone CHECKLIST (TICK ALL) AIR BARRIER - CONTINUITY CHECKLIST (TICK ALL) Mortar joints around built-in joists should be recessed or struck and carefully pointed with flexible sealant. Alternatively, joists may be fitted with proprietary shoes as they are installed. Seal shoe to blockwork face with a flexible sealant. (Dotted blue line is notional, to depict continuity of air barrier through floor zone) Seal between wall air barrier and blockwork, above and below the floor assembly Seal all penetrations through air barrier using a flexible sealant GENERAL NOTES Keep cavities clean of mortar snots and other debris during construction Suspended timber floors may be laid in joist hangers rather than built in Where wall supports joists, thermal performance and airtightness of junction can be improved significantly by using joist hangers with shoes standing off the wall face Detail is diagramatic only. Where floor is a separating floor, accoustic insulation should be provided. See TGD-E For timber engineered joists, proprietary filler pieces must be fitted on both sides of the web between top and bottom flanges. (See manufacturer's details.) ACCEPTABLE CONSTRUCTION DETAIL OPTION (TICK ONE) AIR BARRIER - OPTIONS Complying with checklist will help achieve design air permeability Masonry inner leaf with wet-finish plaster, or Masonry inner leaf with scratch coat, and finished with plasterboard, or Inner leaf with plasterboard on dabs, with continuous ribbon of adhesive tape around all openings, along top and bottom of wall, and at internal and external corners, or Airtightness membrane and tapes Timber Separating Floor Between Dwellings DETAIL 1.05a, 2011

12

13 (1) WALLS:- INSULATION IN CAVITY THERMAL PERFORMANCE CHECKLIST (TICK ALL) Masonry Partition Wall AIR BARRIER - CONTINUITY CHECKLIST (TICK ALL) DETAIL 1.07, 2011 Ensure partial fill insulation is secured firmly against inner leaf of cavity wall Continue cavity wall insulation across abutment zone Seal between air barrier on external wall and the blockwork, to the partition wall. (Dotted blue line is notional, to depict air barrier continuity through partition, depending on whether partition toothed into external wall or braced with ties) Seal all penetrations through air barrier using a flexible sealant Complying with checklist qualifies builder to claim! value in Table 3 of IP 1/06 and Table K1 of DEAP 2006 GENERAL NOTES Keep cavities clean of mortar snots and other debris during construction Read this detail in conjunction with detail G-02, Blockwork Partition Head OPTION (TICK ONE) AIR BARRIER - OPTIONS Complying with checklist will help achieve design air permeability Masonry inner leaf with wet-finish plaster, or Masonry inner leaf with scratch coat, and finished with plasterboard, or Inner leaf with plasterboard on dabs, with continuous ribbon of adhesive tape around all openings, along top and bottom of wall, and at internal and external corners, or ACCEPTABLE CONSTRUCTION DETAIL Masonry Partition Wall Airtightness membrane and tapes DETAIL 1.07, 2011

14 (1) WALLS:- INSULATION IN CAVITY THERMAL PERFORMANCE CHECKLIST (TICK ALL) Stud Partition Wall AIR BARRIER - CONTINUITY CHECKLIST (TICK ALL) DETAIL 1.08, 2011 Ensure partial fill insulation is secured firmly against inner leaf of cavity wall Install external air barrier before stud; or install barrier before partition lining and seal all gaps between air barrier and stud with flexible sealant. (Dotted blue line depicts air barrier continuity through partition stud member) Continue cavity wall insulation across abutment zone Seal all penetrations through air barrier using a flexible sealant Complying with checklist qualifies builder to claim! value in Table 3 of IP 1/06 and Table K1 of DEAP 2006 GENERAL NOTES Detail applicable to timber stud and metal stud partitions Keep cavities clean of mortar snots and other debris during construction Read this detail in conjunction with details G-03, Timber Stud Partition Head, or G-04, Metal Stud Partition Head as appropriate OPTION (TICK ONE) AIR BARRIER - OPTIONS Complying with checklist will help achieve design air permeability Masonry inner leaf with wet-finish plaster, or Masonry inner leaf with scratch coat, and finished with plasterboard, or Inner leaf with plasterboard on dabs, with continuous ribbon of adhesive tape around all openings, along top and bottom of wall, and at internal and external corners, or Airtightness membrane and tapes ACCEPTABLE CONSTRUCTION DETAIL Stud Partition Wall DETAIL 1.08, 2011

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37

Contents. APA Construction Details. Full fill cavity walls 2-13. Partial fill cavity walls 14-25. Solid externally insulated walls 26-37 Contents Pages Full fill cavity walls 2-13 Partial fill cavity walls 14-25 Solid externally insulated walls 26-37 Appendix (BRE confirmation of Ψ and y-values) 38-40 Page 1 of 40 APA Construction Details

More information

Introduction & Principles Issued in support of Junction Details, Parts 1 to 5

Introduction & Principles Issued in support of Junction Details, Parts 1 to 5 Accredited Construction Details (Scotland) 2010 For the limitation of thermal bridging and air infiltration in low and medium rise domestic buildings Introduction & Principles Issued in support of Junction

More information

Rockwool Flexi Insulation Application Guide

Rockwool Flexi Insulation Application Guide Pitched roof Rafters InterMediate floors INTERNAL partitions external Framed walls separating floors Separating Walls Rockwool Flexi Insulation Application Guide Ground floor The perfect fit for any framed

More information

TGD L 2011. Limiting Thermal Bridging and Air Infiltration. Acceptable Construction Details. Introduction

TGD L 2011. Limiting Thermal Bridging and Air Infiltration. Acceptable Construction Details. Introduction TGD L 2011 Limiting Thermal Bridging and Air Infiltration Acceptable Construction Details Introduction Government of Ireland 2015 1 INTRODUCTION This guide to Acceptable Construction Details (ACDs) is

More information

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.

Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01. Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice

More information

Manual lifting and handling

Manual lifting and handling Manual lifting and handling When installing British Gypsum products and systems care should be taken to ensure that appropriate methods of handling and lifting are adopted. The following guidance details

More information

Module 3.7. Thermal bridging

Module 3.7. Thermal bridging Module 3.7 Thermal bridging Learning Outcomes On successful completion of this module learners will be able to - Describe construction details which influence thermal bridging. 2 Introduction to thermal

More information

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003) NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:

More information

DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP

DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP CONTENTS WHAT IS RISING DAMP STEP 1 SURVEY STEP 2 METER READINGS STEP 3 CONCLUSION STEP 4 PREPARATION FOR TREATMENT STEP 5 TYPE OF TREATMENT STEP 6

More information

The right solutions. However, it is inevitable that with the introduction of any new construction system the question arises How does it compare?

The right solutions. However, it is inevitable that with the introduction of any new construction system the question arises How does it compare? Value assessment. The right solutions. We Believe We believe that Porotherm offers both short and long term value to all involved in the building process - from bricklayer to client and everyone in between.

More information

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with

Section 4.3. Separating Floors. Timber frame floor with I-Beams. Upgrading existing timber floor with new ceiling. Timber frame floor with Section Separating Floors Timber frame floor with I-Beams Product: Earthwool Acoustic Roll and Floorfoam Easy Edge Strip Timber frame floor with solid timber joists Product: Earthwool Acoustic Roll and

More information

Improving the flood resistance of your home. Advice sheet 4: Flood-resilient walls.

Improving the flood resistance of your home. Advice sheet 4: Flood-resilient walls. Improving the flood resistance of your home Advice sheet 4: Flood-resilient walls. This sheet provides guidance on identifying different types of wall, and reducing the flow of floodwater through them

More information

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS

SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS NOISE TECHNICAL FACT SHEET FACT SHEET 5 SOUND INSULATION FOR EXTERIOR WALLS AND FACADE SYSTEMS The sound insulation of exterior walls and roof-ceiling systems refers to their ability to reduce external

More information

NRG 75 CRF NRG GREENBOARD WALL SYSTEM

NRG 75 CRF NRG GREENBOARD WALL SYSTEM NRG GREENBOARD WALL SYSTEM NRG Energy Efficient Building Systems is pleased to announce a revolution in lightweight cladding systems. NRG Building Systems is the first and only company to achieve CodeMark

More information

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.

INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength. INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal

More information

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in REV 1-12.12.11/TB002 Technical Bulletin Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in conjunction with TRADA Technology and is intended to provide the reader with introductory

More information

Good Craftsmanship Guide. Carpentry and Joinery- Carcassing

Good Craftsmanship Guide. Carpentry and Joinery- Carcassing Good Craftsmanship Guide Carpentry and Joinery- Carcassing Introduction This Good Craftsmanship Guide highlights key problems with the major elements of Carpentry and Joinery - Carcassing, and gives guidance

More information

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1

Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1 Top plate Stud Soffit lining 45mm min nog Fix scotia bead Building underlay/james Hardie rigid air barrier Soffit Detail Building underlay/james Hardie rigid air barrier Bottom plate 25mm wide cant strip.

More information

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing Substrate, structural panel, bonded waterproofing The universal substrate for tiles Perfect covering No matter whether you work with mosaics or large format tiles, an absolutely level substrate with straight

More information

Extension. for. Pretend Customer 123 A Road HA7 9BP. at: 123 A Road HA7 9BP

Extension. for. Pretend Customer 123 A Road HA7 9BP. at: 123 A Road HA7 9BP for Pretend Customer at: Pretend Customer Site address: Monday, 23 November 2015 Dear Pretend Customer, Subject: Thank you for your valued enquiry and instructions to quote for the above project. We are

More information

Section 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining

Section 3.1.2. Timber Frame Walls. Single layer between studs. Single layer between studs with service void. Between studs with insulated lining Section Timber Frame Walls Single layer between studs Product: Earthwool FrameTherm Rolls and Slabs Tf01 Single layer between studs with service void Product: Earthwool FrameTherm Rolls and Slabs Tf02

More information

The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES

The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES The Scottish Building Standards TECHNICAL HANDBOOK CONSERVATORIES Crown copyright 2006 Cover designed and produced by Astron Text pages

More information

Energy Company Obligation (ECO): Technical Monitoring Questions

Energy Company Obligation (ECO): Technical Monitoring Questions Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified

More information

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD

VA25014B0516 VA CINCINNATI PROJECT NO. 539-328 INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION 09 29 00 GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board, vapor retarder and air and moisture barrrier. 1.2 RELATED WORK A. Installation

More information

Installation Guide. Bath and Wall Surrounds SERIES 7104 1021861-2-B

Installation Guide. Bath and Wall Surrounds SERIES 7104 1021861-2-B Installation Guide and Wall Surrounds SERIES 7104 1021861-2-B Thank You For Choosing Sterling We appreciate your commitment to Sterling value. Please take a few minutes to review this manual before you

More information

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS

More information

Building Regulations for the Conservation of Fuel and Power

Building Regulations for the Conservation of Fuel and Power Insulation CI/SfB Rn7 M2 First Issue April 2014 Building Regulations for the Conservation of Fuel and Power ENGLAND EXISTING DWELLINGS 2013 EDITION Low Energy Low Carbon Buildings Contents Page Introduction

More information

A practical guide to building airtight dwellings

A practical guide to building airtight dwellings A practical guide to building airtight dwellings A practical guide to building airtight dwellings June 2009 NHBC Foundation Buildmark House Chiltern Avenue Amersham Bucks HP6 5AP Tel: 01494 735394 Fax:

More information

INSTALLATION OF WYKAMOL MEMBRANE PRODUCTS

INSTALLATION OF WYKAMOL MEMBRANE PRODUCTS Wykamol Group Unit 3 Boron Court Network 65 Business Park Hapton Burnley Lancs BB11 5TH Tel: 0845 400 6666 INSTALLATION OF WYKAMOL MEMBRANE PRODUCTS CM8 & KONTRACT 8 1.1 PREPARATION Wykamol wall membrane

More information

FIRE RATED GLAZING System Guide

FIRE RATED GLAZING System Guide SYSTEM GUIDE Issue date: 05-05-2015 Expiry date: 31-12-2016 System Guide Introduction Pyropanel Developments are specialists in fire rated glazing solutions, and our systems are designed for easy installation

More information

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit R-H-DI1 INSULATION BATT NR-E-IB1 Avoid Using Batt Insulation With Metal Framing Batt insulation should not be used with metal framing systems. Although it is common to see fiberglass batt insulation installed

More information

House building is changing fast NHBC unveils new Standards Chapters on curtain walling and cladding, and light steel framed walls and floors

House building is changing fast NHBC unveils new Standards Chapters on curtain walling and cladding, and light steel framed walls and floors W42_Stand_Extra_32 15/3/05 9:17 am Page 2 NHBC s technical newsletter April 2005 Issue 32 This edition includes: 2 House building is changing fast NHBC unveils new Standards Chapters on curtain walling

More information

Residential Refurbishment. September 2012. ThermoShell Internal Wall Insulation System Design Guide

Residential Refurbishment. September 2012. ThermoShell Internal Wall Insulation System Design Guide Residential Refurbishment September 2012 ThermoShell Internal Wall Insulation System Design Guide The importance of wall insulation in houses Buildings account for 40% of our energy consumption and in

More information

IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN. 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION

IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN. 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION IRISH BUILDING CONTROL INSTITUTE HOTEL COURT HOTEL BALLYCONNELL CO CAVAN 26 th MARCH 2009 TIMBER FRAME CONSTRUCTION Bill Robinson BSc. C. Eng. M. I. Struct. E. Timber Design Services 1 IS440 Timber frame

More information

Issue of the Guidelines on Prevention of Water Seepage in New Buildings

Issue of the Guidelines on Prevention of Water Seepage in New Buildings graphic: Buildings Department Your REF 來 函 檔 號 :. OUR REF 本 處 檔 號 :.BD GR/1-55/173 FAX 圖 文 傳 真 :..28400451 TEL 電 話 :..2626 1717 www.info.gov.hk/bd To : All Authorized Persons 7 March 2005 Registered Structural

More information

PRODUCT GUIDE. Building the future with Ytong autoclaved aerated concrete. low tolerances high quality

PRODUCT GUIDE. Building the future with Ytong autoclaved aerated concrete. low tolerances high quality Building the future with Ytong autoclaved aerated concrete PRODUCT GUIDE low tolerances high quality XEL0002_Productguide_versie januari 2016.indd 1 11-01-16 13:03 This is Xella Xella is a leading manufacturer

More information

0331 Brick and block construction

0331 Brick and block construction 0331 BRICK AND BLOCK CONSTRUCTION This worksection has been written for Class 1 and 10a buildings that fully conform to the scope of AS 4773.1. If the works include isolated structures, (totally separate

More information

This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover

This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover Dow Construction Products Thermal Insulation of Floors This seminar covers the principles, design and installation of ground bearing and suspended insulated floors. You will discover Why a floor should

More information

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details

Installation Details. D1 General D2 Walls D3 Ceilings D4 Reference. D Installation Details D Installation Details D1 General D2 Walls D3 Ceilings D4 Reference D Installation Details D Contents D1 General Installation and Fastening Sequence for Steel Studs D1.1 Fastener Selection D1.3 D2 Walls

More information

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................

More information

Innovation - High performance roof, wall and floor insulation board. delivering better performance

Innovation - High performance roof, wall and floor insulation board. delivering better performance 2010 VERSION 1 IRL High performance roof, wall and floor insulation board Innovation - delivering better performance PRODUCT SPECIFICATION INSTALLATION GUIDE I ve worked with Xtratherm for years, they

More information

7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME

7. Installation. installation 7.1.1. CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME 7. Installation Window involves the fixing of window frame at an earlier construction stage and subsequent of the window sashes. This is a highly workmanship dependent process. Only trained and approved

More information

Rochdale Building Control Guide. Approved Document C. Site preparation and resistance to contaminants and moisture

Rochdale Building Control Guide. Approved Document C. Site preparation and resistance to contaminants and moisture Rochdale Building Control Guide Approved Document C Site preparation and resistance to contaminants and moisture Dampness is often misdiagnosed within buildings, the approved document deals with prevention

More information

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,

More information

C05. S03. P02 P08 FireWall. Including C05. S01. P02 Specialist partitions introduction

C05. S03. P02 P08 FireWall. Including C05. S01. P02 Specialist partitions introduction C05. S03. P02 P08 Including C05. S01. P02 Specialist partitions introduction C05 Specialist partitions Introduction Specialist partitions This section details specialist lightweight systems where high-security,

More information

UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS

UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS Executive Summary: There is a proposal at the Joint Committee on Administrative

More information

12.1 Schlüter -KERDI-BOARD

12.1 Schlüter -KERDI-BOARD I n n o v a t i v e p r o f i l e s 12.1 Schlüter -KERDI-BOARD S u b s t r a t e U N I V E R S A L S T R U C T U R A L P A N E L, B O N D E D W A T E R P R O O F I N G Application and Function Schlüter

More information

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill

ENERGY STAR Qualified New Homes Thermal Enclosure Checklist. Water Management Checklist. Eli Caudill ENERGY STAR Qualified New Homes Thermal Enclosure Checklist & Water Management Checklist Eli Caudill ENERGY STAR Version 3 Tighter Standards Whole Home Approach Better, More Sustainable Construction Surpasses

More information

Multi-layer Insulation Blanket for Roofs

Multi-layer Insulation Blanket for Roofs Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof

More information

The Pocket Guide To Insulation August 2013

The Pocket Guide To Insulation August 2013 The Pocket Guide To Insulation August 2013 Introduction Knauf Insulation is the UK s leading manufacturer of insulation products, including: Earthwool glass and rock mineral wool Polyfoam ECO extruded

More information

Mold Preventing I nterior System

Mold Preventing I nterior System interior insulation and renovation boards A system of components that have been designed to work perfectly together to repair damage caused by mold. The system consists of boards, insulation wedges, reveal

More information

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION SIPS SCREWS WITH MINIMUM 1" PENETRATION IN WOOD MEMBER IN SIP WALL PANEL CONNECTED TO @ 24" O.C. MAXIMUM OUTSIDE SKIN EACH SIDE OF FRAMING TYP. AS RECOMMENDED BY FOAM CORE AS EACH SIDE OF FRAMING TYP.

More information

Rev 1-12.2013. Code of Practice. SIP Technology. www.uksips.org

Rev 1-12.2013. Code of Practice. SIP Technology. www.uksips.org Rev 1-12.2013 Code of Practice SIP Technology www.uksips.org What are Structural Insulated Panels (SIPS)? SIPS are prefabricated, high performance, lightweight, building panels that can be used in floors,

More information

plumbing products guide

plumbing products guide plumbing products guide radiator pipe guide & seals A significant development in the drive to reduce air leakage and heat loss. Installations such as that shown are all too common. The detail is poorly

More information

Chapter 3 Pre-Installation, Foundations and Piers

Chapter 3 Pre-Installation, Foundations and Piers Chapter 3 Pre-Installation, Foundations and Piers 3-1 Pre-Installation Establishes the minimum requirements for the siting, design, materials, access, and installation of manufactured dwellings, accessory

More information

- Version 2 Total R-value calculations for typical building applications

- Version 2 Total R-value calculations for typical building applications - Version 2 Total R-value calculations for typical building applications - Version 2 Total R-value calculations for typical building applications Acknowledgements Version Date Description 1 Nov 2010 Initial

More information

The WANZ Guide to Window Installation

The WANZ Guide to Window Installation The WANZ Guide to Window Installation as described in E2/AS1 Amendment 5 Ver. 1.1 Page 2 of 74 Contents Overview Page 5 Objective Page 5 Scope Page 5 Opening Preparation Page 7 Step P1 Preliminary Check

More information

Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses (Revised 19 th Jan 2011)

Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses (Revised 19 th Jan 2011) Technical Guide Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses (Revised 19 th Jan 2011) ASSESSMENT OF DAMAGE Prior to any assessments or repairs being commenced, a licensed

More information

LAYING BLOCK AND BRICK

LAYING BLOCK AND BRICK LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct

More information

Chapter 5.4. Waterproofing of basements and other below ground structures

Chapter 5.4. Waterproofing of basements and other below ground structures Chapter Waterproofing of basements and other below ground structures Waterproofing of basements and other below ground structures CONTENTS SCOPE DESIGN Clause Page D1 Design standards D1 2 D2 Statutory

More information

INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS

INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS Introduction This inspection guide is organized to follow the EIF System's Installation Guide.

More information

PRODUCT GUIDE lower tolerances high quality

PRODUCT GUIDE lower tolerances high quality Building the future with Ytong autoclaved aerated concrete PRODUCT GUIDE lower tolerances high quality Introduction Distinctive building with aerated concrete Ytong blocks are a well known global name

More information

Lintel Product Selector

Lintel Product Selector Uniclass L325:P4142 Cl/Sfb October 2014 EPIC F631:X442 (31.9) Hh2 www.catnic.com Lintel Product Selector October 2014 Care has been taken to ensure that the contents of this publication are accurate, but

More information

Installation An Industry Guide to the Correct Installation of Windows and Doors

Installation An Industry Guide to the Correct Installation of Windows and Doors An Industry Guide to the Correct of Windows and Doors Background Foreword The Australian Window Association is pleased to produce this Industry Guide for the of Windows and Doors as part of its commitment

More information

WATERPROOFING OF WET ROOMS

WATERPROOFING OF WET ROOMS WATERPROOFING OF WET ROOMS Waterproofing under tiles For longterm enjoyment of a wetroom area a complete and resistant waterproofing system is an important precondition. Most tiles are by themselves waterproof

More information

GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS.

GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS. GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS. This leaflet provides guidance on how to attain compliance with The Building (Amendment) Regulations (Northern Ireland) 2006, Part

More information

PB301 July 2009. Lightweight Building Solutions. Bushfire Protection. www.boral.com.au/bushfireprotection

PB301 July 2009. Lightweight Building Solutions. Bushfire Protection. www.boral.com.au/bushfireprotection PB301 July 2009 Lightweight Building Solutions Bushfire Protection www.boral.com.au/bushfireprotection Attached or adjacent within 6m roofed structures such as garages, carports, verandas and the like,

More information

Internal wall insulation in existing housing

Internal wall insulation in existing housing Energy Efficiency Best Practice in Housing Internal wall insulation in existing housing A guide for specifiers and contractors Cost-effective External wall appearance maintained Easier to install and maintain

More information

Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses

Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses Technical Guide Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses ASSESSMENT OF DAMAGE Prior to any assessments or repairs being commenced, a licensed electrician must undertake

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

Contents. Who is Premier Guarantee? Your Structural Warranty. What to look out for in your New Home. Running in your New Home. DIY and Maintenance

Contents. Who is Premier Guarantee? Your Structural Warranty. What to look out for in your New Home. Running in your New Home. DIY and Maintenance Homeowners Handbook Contents Who is Premier Guarantee? Your Structural Warranty What to look out for in your New Home Running in your New Home DIY and Maintenance Structural Warranty Cover This booklet

More information

Squash Court Design general points

Squash Court Design general points Squash Court Design general points Contents: Contents:... 1 1. Squash Court Dimensions... 2 2. CourtTech Walls... 3 3. Dimensional requirements for courts with CourtTech Walls... 3 4. Loading of CT System

More information

How To Repair A Boat Landing Deck With A Boat Bed

How To Repair A Boat Landing Deck With A Boat Bed RESIDENTIAL INSULATED SHEATHING INSTALLATION GUIDE Residential Insulated Sheathing Installation Guide ROXUL COMFORTBOARD IS Table of Contents Slab-on-grade-to Above Grade Wall...1 Foundation Wall at Footing

More information

R E S I D E N T I A L H O U S I N G

R E S I D E N T I A L H O U S I N G HL 252 Rev. April 1997 R E S I D E N T I A L H O U S I N G CONTROLLING EXTERNALWATER PROBLEMS FOR RESIDENCES I II III IV V Lot Drainage Gutter Water Management Foundation Waterproofing Floor Slab Waterproofing

More information

Avoiding Air Barrier Pitfalls

Avoiding Air Barrier Pitfalls Avoiding Air Barrier Pitfalls Design & Durability November 2013 Air barriers, when correctly installed, help buildings achieve high levels of energy efficiency by decreasing heat loss. For example, great

More information

European Organisation for Technical Approvals

European Organisation for Technical Approvals Warrington Certification Limited, Holmesfield Road, Warrington, WA1 2DS Tel. +44 (0) 1925-646777 Fax +44 (0) 1925-646667 Member of EOTA Authorised and notified according to Article 10 of the Council Directive

More information

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery

Part 3 Ancillary technologies. Chapter 3.2. Mechanical ventilation with heat recovery Part 3 Ancillary technologies Chapter CONTENTS SCOPE Clause Page DESIGN Design standards D1 1 Statutory requirements D2 1 System design D3 1 Building integration D4 2 Noise D5 2 Access and controls D6

More information

Window Installation Instructions

Window Installation Instructions Caution The correct installation methods of windows in full frame or insert applications is critical towards achieving the tested performance of the window and longterm enjoyment and energy savings for

More information

Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM

Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 2 below and above ground V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V The flexible, fast and cost-effective answer

More information

Conventions for U-value calculations

Conventions for U-value calculations Conventions for U-value calculations 2006 edition Brian Anderson BRE Scotland BRE is committed to providing impartial and authoritative information on all aspects of the built environment for clients,

More information

BER Assessors Dwellings Technical Bulletin

BER Assessors Dwellings Technical Bulletin BER Assessors Dwellings Technical Bulletin Issue No. 2/12 April 2012 Contents: 1. SUPPLEMENTARY ELECTRIC WATER HEATING IN SUMMER... 2 2. PITCHED ROOF U-VALUE CALCULATIONS... 8 2.1. PITCHED ROOF, INSULATED

More information

Building Control Guidance Note

Building Control Guidance Note Elements Renovation / Replacement. Issued 25/01/13 Rev a Page 1 of 9 (Applies to both Domestic and Non-Domestic Premises) Works relating to thermal elements can arise in building an extension, a material

More information

Simplifying design and construction. Alan Tovey, Director The Basement Information Centre

Simplifying design and construction. Alan Tovey, Director The Basement Information Centre Simplifying design and construction Alan Tovey, Director The Basement Information Centre Simplifying design and construction Grades of construction Construction options Design and waterproofing issues

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

Sports Buildings: budget costs for the Flood Relief Fund

Sports Buildings: budget costs for the Flood Relief Fund Sports Buildings: budget costs for the Flood Relief Fund The list below provides typical costs for flood insurance works, typically required by sports clubs or facilities. The list is not exhaustive but

More information

British Gypsum Guide to Timber Frame Construction. March 1998

British Gypsum Guide to Timber Frame Construction. March 1998 British Gypsum Guide to Timber Frame Construction March 1998 Timber frame construction has a centuries long tradition in the UK, however, over the last 80 years it has continuously evolved to meet the

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

CI/SfB 2- Rj7 December 2010

CI/SfB 2- Rj7 December 2010 Engineered Timber Systems CI/SfB 2- Rj7 December 2010 STANDARD DETAILS Contents Wall Details W1 Typical wall section. W2 a Sectional elevation through soleplate fixing detail. Ground bearing slab. W2 b

More information

Knauf Aquapanel Interior. Tile Backing. Cement board for wet areas. Will not deteriorate in water. Easy to score and snap

Knauf Aquapanel Interior. Tile Backing. Cement board for wet areas. Will not deteriorate in water. Easy to score and snap Tile Backing Will not deteriorate in water Easy to score and snap Resistant to mould and mildew Knauf Aquapanel Interior Cement board for wet areas Knauf Aquapanel Interior Cement Board Drywall for Wet

More information

Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses (Revised 2 nd Feb 2013)

Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses (Revised 2 nd Feb 2013) Technical Guide Guide to Assessment and Repair of Flood Damaged Timber and Timber Framed Houses (Revised 2 nd Feb 2013) ASSESSMENT OF DAMAGE Prior to any assessments or repairs being commenced, a licensed

More information

2014 British Columbia Building Code Changes

2014 British Columbia Building Code Changes District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most

More information

PART 1 GENERAL 1.1 SECTION INCLUDES

PART 1 GENERAL 1.1 SECTION INCLUDES J-1 Section 09110 Long Form Specification INTERIOR METAL STUD FRAMING This section includes lightweight, usually 0.036 inch (0.9 mm) thick or lighter, non-axial load bearing metal stud framing including

More information

CHAPTER 6: SUBSTRUCTURE

CHAPTER 6: SUBSTRUCTURE CHAPTER 6: SUBSTRUCTURE Technical Manual V7: TS-011a-7.00-180814 CHAPTER 6: SUBSTRUCTURE CONTENTS 6.1 BASEMENTS 6.2 WALLS BELOW GROUND 6.3 DAMP PROOFING 6.4 GROUND FLOORS 89 CHAPTER 6 FUNCTIONAL REQUIREMENTS

More information

Airtight Intelligence

Airtight Intelligence VARIO - Airtight Intelligence The multitasking membrane The Vario System keeps heat in Airtight Intelligence Vario-System keeps draughts out beats present and future regulations saves energy Introducing

More information

DEFAULT HEAT LOSS COEFFICIENTS

DEFAULT HEAT LOSS COEFFICIENTS DEFAULT HEAT LOSS COEFFICIENTS SECTION A101 GENERAL REQUIREMENTS A101.1 Scope. The following defaults shall apply to Chapter 4 of both the (RE) and (CE) sections of the IECC. This chapter includes tables

More information

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION REPORT HOLDER: CERTAINTEED CORPORATION 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-3758 Reissued 04/2016 This report is subject to renewal 04/2017. DIVISION: 07 00 00 THERMAL

More information

Domestic Extensions. Monmouthshire County Council. Building control guidance document

Domestic Extensions. Monmouthshire County Council. Building control guidance document Monmouthshire County Council Building control guidance document Domestic Extensions Building Regulations 2010 (with 2013 amendments) For use in Wales May 2013 Edition Guidance produced for Monmouthshire

More information

WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204

WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 Structural Inspection Report Client: CSArch Architecture Engineering Construction Management 19 Front Street, Newburgh,

More information

Annex of the certificate (Page 1/6) Accreditation Scope

Annex of the certificate (Page 1/6) Accreditation Scope As a Testing Laboratory Annex of the certificate (Page 1/6) Accreditation Scope Address: Küçük Çiğli Mh. 8780/1 Sk. No:5 Çiğli 35681 İZMİR / TÜRKİYE Phone : 0 232 376 24 25 Fax : 0 232 386 33 98 E-Mail

More information