1 ASHRAE JOURNAL The following article was published in ASHRAE Journal, October Copyright 1997 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. The V in Classroom HVAC By Arthur E. Wheeler, P.E. Fellow ASHRAE C ommonly applied minimum outdoor air ventilation rates for school classrooms have evolved during the past hundred years from 30 cfm (15 L/s) per person down to 10 cfm (5 L/s) 1 per person in the mid-1920s. The rate dropped to half that some fifty years later with the onset of the energy crunch. Most recently it rose to 15 cfm (7.5 L/s) per person with ANSI/ ASHRAE Standard : Ventilation for Acceptable Indoor Air Quality 2. These shifts are the result of changes in the understanding of appropriate objectives and the nature of pollutants and their effects upon occupants. Conclusions have always been tentative due to difficulties in evaluating quantitatively the effectiveness of ventilation rates. The invariable presence of other environmental factors, some unrelated to air quality, confounds results. As always, non-environmental considerations, especially economics and energy use, continue to influence ventilation rate choices. The quest for more enlightened understanding of the role of ventilation continues. The current draft of the successor to Standard proposes a more finely delineated approach to establishing an outdoor ventilation rate for classrooms and other occupancy classifications. More than those of its predecessors, the draft strives to relate rates to the specific contaminants of concern, their sources, and the functional use and grade of the classroom. Microbe bearing particulates are given priority as a contaminant of concern. Dilution ventilation can reduce their concentration to a degree shown to provide a healthier environment. 4,5 The proposed standard recognizes that dilution of airborne particulate concentrations can be accomplished by both outdoor air (presumed to be virtually free of the microbes produced by the occupants) and recirculated air (from which particulates are removed by filtration). Following Standard , the proposed revision retains a minimum About the Author Arthur E. Wheeler, P.E., has nearly 50 years experience designing building refrigerating and air-conditioning systems. An ASHRAE Fellow and recipient of the Society s Distinguished Service Award, he has served on numerous standing, technical and standards committees, including the project committees for ASHRAE Standard and R. He is president of the Wheeler Engineering Company in Baltimore. Greater emphasis is placed upon satisfying occupants of classroom environments. Site Outdoor Summer Design: 90 F (32 C) db, 76 F (24 C) wb Indoor Summer Design: 75 F (24 C), 50% rh Classroom Floor & Roof Area: 810ft2 (75 m2) Wall Area: 270 ft 2 (25 m 2 ); Window Area: 81ft 2 (8 m 2 ) Lighting: 2 watts/ft2 (21.6 watts/m2) Normal Attendance: 23 Persons Fig. 1: Design parameters for classroom system evaluation. rate of 15 cfm (7.5 L/s) per person of outdoor air or recirculated air that is filtered to provide a dilution equivalent to the outdoor air based upon removal efficiency for three micron particles. The draft further prescribes a minimum rate of outdoor air required for dilution of non-filterable contaminants contributed by the two principle sources: occupants (and their activities) and building components. For the general classroom, the draft proposal establishes the minimum rate of outdoor air ventilation needed to dilute contaminants from these sources that is less than the current standard. 6 Two main reasons for this reduction are (1) the proposed standard considers the odor perception of adapted occupants as opposed to unadapted visitors, and (2) recognition that the rate of contaminants produced by the building on a per person basis is partially dependent upon occupancy density (persons per unit floor area). Standard prescribes outdoor air rates for classrooms that are greater than previous standards and ventilation codes. Especially in humid climates, this increase, coupled with the inherent limitations of commonly employed air-conditioning systems, has contributed to higher room humidity. Such occurrences frequently lead to extensive fungal growth and an indoor environment highly contaminated with spores and mycotoxins. The capabilities of an HVAC system to provide acceptable thermal conditions and air quality are often overlooked. Some systems dehumidify outdoor ventilation air only as an indirect result of cooling to maintain space temperature. When inadequately dehumidified outdoor air is supplied, the latent load and the humidity of the space are increased. Although higher See Wheeler, Page ASHRAE Journal October 1997

2 Advertisement in the print edition formerly in this space. October 1997 ASHRAE Journal 49

3 Wheeler, From Page 48 outdoor air ventilation rates may exacerbate humidity problems, lower rates may not cause them to disappear. Basis of Study This study examines and compares the performance capabilities of several HVAC systems popularly applied to general classrooms with respect to their ability to maintain space relative humidity and to control risk of microbial infection transmission. It also evaluates the effect of different outdoor ventilation rates upon classroom humidity during warm weather. The study examines a typical public school classroom located in central Maryland. Design parameters are given in Figure 1. Outdoor design conditions are selected for June or September, 2.5% frequency of occurrence. 7 Classroom orientation is a composite averaging north, east, south and west. Maximum attendance of 25 is discounted by two to account for normal absenteeism. The period of continuous occupancy is considered longer than three hours, therefore the variable occupancy provision contained in Standard is not applicable. Both occupied and unoccupied periods are analyzed to more fully evaluate system relative humidity control capabilities. Thermal loads are assumed to be steady state varying with outdoor air temperature as depicted in Figure 2, in which room sensible cooling load is plotted against outdoor air temperature. The room sensible load is the determinant of either the supply air temperature for a constant volume (CV) HVAC system or supply air flow rate, assuming a constant supply air temperature, for a variable air volume (VAV) system. The variable supply air temperature or flow is controlled to offset heat gain or loss. The study accounts for the effect of water vapor produced by the occupants upon space relative humidity; however, moisture entry due to infiltration, permeation and migration is not considered. These sources should be, but are not always, minimized by the building envelope design and construction. The systems compared are: Unit ventilators (UV) still probably the most popular throughout the country. VAV single duct for cooling, with controls that ensure a constant outdoor air ventilation supply even as total supply air flow changes as required by Standard VAV systems are more commonly selected for larger schools and those with both interior and perimeter classrooms. Single zone rooftop units (SZRT) with direct expansion cooling coils; one for each classroom. This system is often selected for single story buildings due to favorable capital cost. Performance with respect to ventilation and humidity control is similar to many self-contained and heat pump unit ventilators. Conditioned outdoor air supply system (COA+) supplemented by a room unit, such as a fan coil or heat pump. As well as being applied to new schools, the outdoor air supply system is being added as a remedial or upgrade measure employing existing unit ventilators with sealed outdoor air intakes. 8 Dual fan, dual duct (DFDD) supplying primary air for outdoor air ventilation and cooling through one duct system and secondary recirculated air, filtered and optionally heated through another duct system. The airstreams are blended in a terminal for each classroom to vary the supply temperature while holding the room supply rate constant. 9 While application of this system has been limited, it is receiving growing consideration for new schools. The systems are evaluated and compared for their capabilities to maintain classroom relative humidity, provide outdoor air ventilation, and to limit concentrations of airborne infectious particulates. Space relative humidity is analyzed coincident with three outdoor ambient conditions: 90 F (32 C) db 76 F (24 C) wb 112 grains/lb (16 g/kg) 52% rh 75 F (24 C) db 69 F (20 C) wb 98 grains/lb (14 g/kg) 75% rh 20 F (-6 C) db 17 F (-8 C) wb 10 grains/lb (1.4g/kg) 50% rh Outdoor design conditions do not always depict the seasonal humidity extremes encountered in many parts of the country, including Maryland. Partial load conditions, as represented by the second summer ambient, are not only more commonly encountered than those selected for design, but may test the systems humidity control more severely. Both occupied and unoccupied situations are examined during summer. To better understand the effects of different outdoor air ventilation rates, the rates of 5, 10 and 15 cfm (2.5, 5, 7.5 L/s) per person are compared for the unit ventilator system. Some school districts have adopted lower rates than the 15 cfm (7.5 L/s) per person recommended by Standard to ameliorate humidity conditions within the classrooms. The outdoor air rates are held constant during system operation except when an economizer control provides more outdoor air for the purpose of free cooling. Fig. 2: Cooling load plotted against outdoor air temperature. See Wheeler, Page ASHRAE Journal October 1997

4 Advertisement in the print edition formerly in this space. October 1997 ASHRAE Journal 51 (Circle No. 42 on Reader Service Card)

5 Wheeler, From Page 50 System Oa Vent/ Person Occupied UV 15 57% 68% Rh Range 1 Rh Ir 3 Unoccupied 63% F, 10 GR/# System Supply Air Flow CFM Cor V Db F Humidity Gr/# Fig. 3: Characteristics of each system studied. Filter Efficiency Dust Spot % Uv 1000 C <10 30 Vav 1000 V Cond. Oa+ 1345* C <10** 30** Single Zone 1000 C <10 30 Dfdd 1000 C *Oa + Recirculated Air ** Recirculated Air-thru Room Unit The study focuses upon particles three microns in size. Such particles are typical and roughly central to the size range of droplet nuclei carrying bacteria and viruses. These desiccated droplets produced by coughing or sneezing are able to remain in suspension because of their small size, generally ranging from one to five microns. 10 They are capable of being recirculated through air distribution systems unless removed by filtration or disinfection. To evaluate the effectiveness of filtration several levels of efficiency are compared. The comparison relies upon the use of the Infection Risk Index (I r ), based upon the Wells-Riley equation, both previously described in the ASHRAE Journal. 11 This empirically derived equation considers the strength of a discrete infection source or sources, the ventilation rate, and period of exposure. The dilution ventilation rate is considered to be outdoor air (assumed to be free of the occupant-produced droplet nuclei) plus the equivalent in filtered recirculated air, i.e. recirculated airflow times the three micron particulate efficiency. Source strength for inclusion to the Wells-Riley equation is chosen to be in the range of 20 to 40 quanta per hour. The risk comparison has been checked by mass balance equations (Standard 62:1989, p.23) based upon a generation rate of 425 colony forming units (CFU) per minute per person. 12 Only filters normally applicable to the systems are compared. These are identified by the ASHRAE Dust Spot Efficiency. 13 As they relate to a typical classroom, characteristics of each system studied are shown in Figure 3. The unit ventilator selected for the classroom is rated at 1000 cfm (500L/s), equipped with a four-row coil, supplied with chilled water for cooling and warm water for heating, with proportional water flow control by a room thermostat combined with Cycle II Control. 14 The 1 in. (0.025m) deep coarse fiber filter commonly employed is considered to have a dust spot efficiency less than 10% and neglible effectiveness for removal of three micron particles. The VAV system supply air temperature is slightly higher than for UV due to greater fan heat. 30% extended surface filters are assigned 60% removal efficiency for three micron particles 15 and for 85% filters, 98% removal efficiency for three micron particles. 16 The COA+ system supply air is close to temperature neutral. Following dehumidification of the airstream the temperature is increased to the level indicated by reheat or heat recovery to avoid overcooling. The filter efficiency indicated applies to the air recirculated through the room unit for determination of outdoor air equivalency. The SZRT direct expansion coil is controlled on/off by the classroom thermostat. Ventilation is continuous. Filters selected for both primary and secondary air paths of the DFDD system are the same as for the VAV system. Unlike the VAV system, the supply airflow to the classroom is held constant. Results For each of the five systems, the resultant space thermal conditions are calculated by psychrometric analysis based upon the selected parameters described in Figure 4. For all systems, room humidity is in some measure controlled indirectly as a consequence of room temperature control. The room humidity, during system operation, varies depending upon the magnitude of the room sensible load. For occupied perimeter classrooms this will vary largely depending upon the solar heat gain. When the space is unoccupied < % % 66% 60% 70% 36% % 63% 58% 65% >63% VAV 15 50% 54% 43% 4 24% Cond OA % 58% 47% 24% Single Zone Duel F & D 15 58% 75% 5 63% 75% 5 24% % 54% 43% 6 24% indoors, based upon 90 F db, 52%rh & 75 F, 75%rh outdoors; 2 indoors, occupied, no humidification; 3 infection risk index, based upon infectious particle removal from recirculated air; cfm min. supply air, reheat req d; 5 approximate; cfm min. primary air; Fig. 4: Psychrometric analysis of each system studied. with the system operating and the lights turned off, room sensible load is minimal. For some systems, the room humidity reaches its maximum during unoccupied periods. Humidity levels above 60% are conducive to mold growth. High relative humidity within the space is often indicative of the presence of moisture at the surfaces or substrates of the space envelope. Such moisture is a condition prone to cause rapid propagation of molds. Under such circumstances the effectiveness afforded by ventilation and filtration in reducing the space concentrations of fungal contaminants is likely to be quite limited. Spores and mycotoxins generated by molds can be odorous and cause adverse health effects. 17 The winter time room humidity is a consequence of both the moisture content of the See Wheeler, Page ASHRAE Journal October 1997

6 Advertisement in the print edition formerly in this space. October 1997 ASHRAE Journal 53

7 Advertisement in the print edition formerly in this space. 54 ASHRAE Journal October 1997

8 VENTILATION Wheeler, From Page 52 outdoor air and the water vapor emanating from the occupants. An infection risk index of 1.0 is a value based solely on the dilution effect of 15 cfm (7.5 L/s) of outdoor air. Values other than 1.0 are comparative to this base condition. Mass balance analysis yielded higher changes in the risk indices for reductions in outdoor air ventilation than by Wells-Riley. This alternate approach indicates the risk for UV with <10% filters increases proportionally to the decrease in outdoor air, but with 30% filters the two methods of analysis were in close agreement. Discussion Unit ventilator system. Since the dew point of the supply air is regulated by the thermostat, reductions in room sensible load can result in high humidity conditions even when the occupant latent load is removed. Though not studied, face and bypass control in place of water flow control is likely to produce somewhat lower maximums. Room humidity would be even higher for humid outdoor ambient conditions in southern climates or during rainy summer periods elsewhere. 18 Reduced rates of outdoor air ventilation do not fully eliminate excursions of relative humidity in warm weather. It is also evident that in winter too little outdoor air can result in excessive humidity within the classroom as may be evidenced by condensation on the windows. The reduced infection risk attributed to 30% efficiency filters may understate the benefit of reducing buildup of nutrient (dirt) on the internals of the unit and the propagation of microbials from these locations. VAV system. The minimum supply air flow to the classroom will usually be greater than the minimum outdoor ventilation rate due to the turndown limitations of the volume control or the designers desire to maintain a greater supply of air for dilution and room air distribution. Airflow is projected to be at the minimum for many winter days. Both preheat and reheat may be necessary to avoid overcooling the space. Even with 85% efficiency filters, the infection risk index remains relatively high due to the reduced supply airflow occurring throughout most of the occupied period. Conditioned outdoor air supply plus recirculating room unit. The space is dehumidified both by the low dew point air supply and the room unit. Reduction in I r is solely the result of improved filtration of air recirculated through the room unit. Single zone rooftop. The high humidity conditions are due to humid outdoor air introduced through the unit with the cooling coil control indexed off in response to the space thermostat. Some of the moisture condensed on the coil during the cooling cycle is re-evaporated adding to the water vapor content of the supply air. Due to the variable periodicity of the cooling cycles, the upper end of the space humidity range as stated is approximate. Dual fan, dual duct. Analysis demonstrates equal or superior performance than the others in humidity control and the lowest infection risk index (using 85% efficiency filters). The mass balance analysis indicated even greater effectiveness at reducing the concentration of colony forming units (65% reduction) than that yielded by Wells-Riley. Concern has been voiced that ASHRAE recommended ventilation rates have contributed to indoor air quality problems by increasing room humidity. The comparisons demonstrate that HVAC system capabilities bear more significantly upon room humidity than outdoor air ventilation rates. Conclusions Too often the consequences of HVAC system selection upon both thermal conditions and air quality are overlooked. System selection is usually determined by the design engineer in collaboration with the architect and the school district staff whose chief concerns may be capital cost or past practice. Currently, greater emphasis is being placed upon satisfying occupants with the classroom environment. The capabilities of applicable systems to satisfy that goal deserves close attention. It s the engineer s responsibility to carefully examine the choices. Rather than recommending one system over others, this article offers a tool for thorough evaluation and provides designers with a means to influence others to select the provides HVAC system most likely to contribute to a suitable learning environment. References 1. Waters, T.J., Heating and ventilation of school buildings. Transactions of ASHVE, Vol 1, pp ANSI/ASHRAE Standard , Ventilation for Acceptable Indoor Air Quality. p Ibid., p Burge, H.A., Bioaerosols. CRC Press Inc., Boca Raton, FL. p Kuehn T.H Matching filtration to health requirements. ASHRAE Transactions 97(2). 6. BSR/ASHRAE Standard R. Public Review Draft August, p ASHRAE Handbook Fundamentals p Scofield, C.M., DesChamps, N.H. May HVAC design for classrooms: divide and conquer. Heating Piping & Air-Conditioning. Penton Publishing. Vol 65, No.5 9. Warden, D., January Dual fan dual duct: better performance and lower costs. ASHRAE Journal. Vol.38, No.1. p Riley R.L., Nardell, E.A Controlling transmission of tuberculosis in health care facilities: ventilation, filtration and ultraviolet air disinfection. Plant Technology and Safety Management Series. Oakbrook Terrace, IL. JCAHC Organization. Series No. 1. p Wheeler, A.E. June Better filtration, a prescription for healthier buildings. ASHRAE Journal. Vol 36, No.6. p Wheeler, A.E., Abend, A.C. Meeting the objectives of energy conservation & ventilation for acceptable IAQ in the classroom. Proceedings of IAQ 91 Healthy Buildings, ASHRAE, Atlanta,GA. 13. ANSI/ASHRAE Standard Gravimetric and Dust-Spot Procedures for Testing Air Cleaning Devices Used in General Ventilation for Removing Particulate Matter. 14. ASHRAE Handbook HVAC Application p Ibid., p Farr Co., Los Angeles, CA Bulletin B Miller, J.D. January, Fungi and indoor air quality. INvironment Professional. Vol. 3, No.1. p Bayer, C.W., Downing, C.C. Indoor Conditions in Schools with Insufficient Humidity Controls. Proceedings of IAQ 92, Environments for Buildings, ASHRAE. Please circle the appropriate number on the Reader Service Card at the back of the publication. Extremely Helpful Helpful Somewhat Helpful Not Helpful October 1997 ASHRAE Journal 55

Moisture Control. It s The Dew Point. Stupid! Its not the humidity.

Moisture Control. It s The Dew Point. Stupid! Its not the humidity. Moisture Control Its not the humidity. It s The Dew Point Stupid! Mike Schell EpiphanyTec Inc. Santa Barbara, CA mschell@epiphanytec.com 805 687-3175 Matching great technology to market need! Topics SHR

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality

Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality Camfil Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality Most non-practitioners notice the HVAC system when it is too hot, or too cold, or in other ways not working

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

Hospital Application Guide. Cost-effective climate control for hospitals

Hospital Application Guide. Cost-effective climate control for hospitals Hospital Application Guide Cost-effective climate control for hospitals Munters is the world leader in dehumidification Munters is the largest manufacturer of dehumidifiers in the world. Since developing

More information

Whole House Dehumidification for Occupant Comfort and Energy Savings

Whole House Dehumidification for Occupant Comfort and Energy Savings Downloaded from www.rsrews.com. Since 1968, RS Andrews has proudly served Atlanta's Heating, Air Conditioning & Plumbing Needs. Whole House Dehumidification for Occupant Comfort Energy Savings June 2009

More information

Innovent LASER Packaged Fresh Air Conditioning Units

Innovent LASER Packaged Fresh Air Conditioning Units LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent

More information

To provide good indoor air quality

To provide good indoor air quality Conditioning Ventilation Air for Improved Performance and Air Quality The practice of using a mixing chamber for mixing outdoor and return in a single system should be replaced by a technique with two

More information

Minimizing Indoor Mold Problems through Management of Moisture in Building Systems

Minimizing Indoor Mold Problems through Management of Moisture in Building Systems Minimizing Indoor Mold Problems through Management of Moisture in Building Systems Position Document Approved by ASHRAE Board of Directors June 30, 2005 AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING

More information

Molds and mildew are fungi that grow

Molds and mildew are fungi that grow Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate

More information

Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy

Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy Liabilities of Vented Crawl Spaces, Their Impacts on Indoor Air Quality in Southeastern U.S. Homes and One Intervention Strategy Jonathan Coulter 1 ABSTRACT This paper documents the influences vented crawl

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Using Wet-Bulb Economizers. Data Center Cooling

Using Wet-Bulb Economizers. Data Center Cooling The following article was published in ASHRAE Journal, August 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Dedicated Outdoor Air Systems (D.O.A.S.)

Dedicated Outdoor Air Systems (D.O.A.S.) Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

IEQ-15 Air Distribution System

IEQ-15 Air Distribution System AIM OF CREDIT To encourage and recognise the design and maintenance of air distribution systems that minimise the risk of particulate and microbial contamination to the internal air supply. CREDIT CRITERIA

More information

Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes

Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes Liabilities of Vented Crawl Spaces And Their Impacts on Indoor Air Quality in Southeastern U.S. Homes Jonathan Coulter, Bruce Davis, Cyrus Dastur, Melissa Malkin-Weber and Tracy Dixon Advanced Energy,

More information

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air 0 Optimal Air Quality: Critical to Hotels Provides comfortable environment for guests no overcooling Protects building, carpets

More information

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng. HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains

More information

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.

LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc. LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start

More information

By Tom Brooke PE, CEM

By Tom Brooke PE, CEM Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature

More information

Flexibility, Efficiency In San Antonio Arena

Flexibility, Efficiency In San Antonio Arena 2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 9, September 2005). This article may not

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

HVAC Simplified Approach Option

HVAC Simplified Approach Option HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than

More information

Radford University. Indoor Air Quality Management Plan

Radford University. Indoor Air Quality Management Plan Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings

More information

3/29/2012 INTRODUCTION HVAC BASICS

3/29/2012 INTRODUCTION HVAC BASICS INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is

More information

Biological Contamination in the HVAC System

Biological Contamination in the HVAC System Biological Contamination in the HVAC System by Chin S. Yang, Ph.D. P & K Microbiology Services, Inc. Cherry Hill, New Jersey The heating, ventilating, and air-conditioning system (HVAC) in a building is

More information

Ventilation Standard For Health Care Facilities

Ventilation Standard For Health Care Facilities The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

INDOOR AIR QUALITY ASSESSMENT. Dennett Elementary School 80 Crescent Street Plympton, Massachusetts

INDOOR AIR QUALITY ASSESSMENT. Dennett Elementary School 80 Crescent Street Plympton, Massachusetts INDOOR AIR QUALITY ASSESSMENT Dennett Elementary School 80 Crescent Street Plympton, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Assessment Emergency

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment

Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment AT-01-7-3 Selecting the Supply Air Conditions for a Dedicated Outdoor Air System Working in Parallel with Distributed Sensible Cooling Terminal Equipment Kurt M. Shank Student Member ASHRAE Stanley A.

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

How To Control Humidity With A Humidifier

How To Control Humidity With A Humidifier Control of ventilation and air conditioning plants Building Technologies s Contents.Temperature control in air treatment systems 2. Humidity controls 3. Recirculated air mixing. Internal heat sources 6.2

More information

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH PEOSH Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview Eric Weren, MSIH Public Employees Occupational Safety and Health Unit IAQ Asthma-Friendly

More information

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.

Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0. Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024

More information

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!

Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere

What is LEED? Why pursue LEED accreditation? How does LEED accomplish these goals? Sustainable sites Water efficiency Energy and Atmosphere Green AAON for What is LEED? Sustainability and green have recently become terms used within the building industry (and others) to refer to a construction project that has low environmental impact, or

More information

FLORIDA SOLAR ENERGY CENTER

FLORIDA SOLAR ENERGY CENTER FLORIDA SOLAR ENERGY CENTER Creating Energy Independence Since 1975 Impact of Energy-Efficiency Parameters on Home Humidity Rob Vieira Florida Solar Energy Center A Research Institute of the University

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System

Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning

More information

Controlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY

Controlling Condensation On CWP Insulation BY ED LIGHT, MEMBER ASHRAE; JAMES BAILEY, P.E., MEMBER ASHRAE; AND ROGER GAY This article was published in ASHRAE Journal, Decemeber 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without

More information

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 The Fundamentals of HVAC: What Shapes the Storage Environment Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013 Introduction Presenter Jeremy Linden, Preservation

More information

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

HVAC Characteristics. Test Space HVAC Characteristics

HVAC Characteristics. Test Space HVAC Characteristics HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd mart@energysoft.com EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal

Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)

More information

School HVAC. Design Manual. Application Guide AG 31-004. Air Cooled Chiller. Chilled Water Pumps. Expansion Tank CHWR CHWS. Make up Water Line Boiler

School HVAC. Design Manual. Application Guide AG 31-004. Air Cooled Chiller. Chilled Water Pumps. Expansion Tank CHWR CHWS. Make up Water Line Boiler Application Guide AG 31-004 School HVAC Design Manual Chilled Water Pumps Air Cooled Chiller CHWR HWR Make up Water Line Boiler Expansion Tank CHWS Hot Water Pumps CHWR HWR CHWS HWS CHWR HWR CHWS Unit

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

Building Energy Systems. - HVAC: Heating, Distribution -

Building Energy Systems. - HVAC: Heating, Distribution - * Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center

More information

Simulation of hygroscopic materials in the HVAC system of an office building

Simulation of hygroscopic materials in the HVAC system of an office building Simulation of hygroscopic materials in the HVAC system of an office building IEA/ECBCS Annex 41 Porto Meeting Melanie Fauchoux, Carey Simonson and David Torvi Department of Mechanical Engineering, University

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

ECHO System for Basements

ECHO System for Basements ECHO System for Basements Homeowners looking for more space are all too familiar with the cold, damp and dingy basement. Now, the Enclosure Conditioned Housing (ECHO) System TM, winner of the Ottawa-Carleton

More information

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels

AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels AIR SYSTEMS ENERGY SERIES Energy Recovery Wheels APPLICATION GUIDE Supercedes: Nothing Form 102.20-AG6 (305) INTRODUCTION As fossil fuel reserves are depleted, the cost of energy continues to rise. According

More information

VAV Laboratory Room Airflow The Lowdown on Turndown

VAV Laboratory Room Airflow The Lowdown on Turndown Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally

More information

Comfort Conditioning & Indoor Air Quality

Comfort Conditioning & Indoor Air Quality This article was published in ASHRAE Journal, May 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.newellinstruments.com.

More information

Residential HVAC System Sizing

Residential HVAC System Sizing Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: goss@acad.umass.edu SUMMARY Heating, ventilating and air-conditioning (HVAC)

More information

Humidity Control in School Facilities

Humidity Control in School Facilities Humidity Control in School Facilities By John C. Fischer Member ASHRAE Charlene W. Bayer, PhD. Member ASHRAE Consulting engineers who design school facilities are challenged with controlling space humidity

More information

NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS

NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

Pool Dehumidification Basics

Pool Dehumidification Basics Copyright 2009 Wescor. All rights reserved. Permission granted to reproduce for personal and educational use only. When energy costs were low, many pool owners considered only first cost when choosing

More information

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST

FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST FIRST RADIANT COOLED COMMERCIAL BUILDING IN INDIA CRITICAL ANALYSIS OF ENERGY, COMFORT AND COST Guruprakash Sastry, Senior Manager Green Initiatives Infosys Limited, Bangalore, INDIA ABSTRACT Radiation

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Design Options for HVAC Distribution Systems

Design Options for HVAC Distribution Systems Design Options for HVAC Distribution Systems Course No: M06-017 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877)

More information

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015 Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements By Michael O. Davis, PE, November 2015 Advised by Heat Pipe Technology Background: HVAC systems are often designed

More information

Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators

Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators Mark J. Mendell, Richard C. Diamond, William J. Fisk Environmental

More information

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Dedicated Outdoor Air-Dual Wheel System Control Requirements

Dedicated Outdoor Air-Dual Wheel System Control Requirements 4428 Dedicated Outdoor Air-Dual Wheel System Control Requirements Stanley A. Mumma, Ph.D., P.E. Fellow ASHRAE ABSTRACT The central thrust of this paper is to develop a clear understanding of the performance

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

Rev. No. 0 January 5, 2009

Rev. No. 0 January 5, 2009 ENERGY & ENVIRONMENTAL ENERGY ISSUES COMMITTEE 415 Main Building Telephone (574) 631-6666 Notre Dame, Indiana Facsimile (574) 631-5883 46556 USA Energy Conservation Plan For HVAC Systems Rev. No. 0 January

More information

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow

HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation. Richard Lord Carrier Fellow HVAC Technologies for Building Energy Efficiency Improvements 2013 National Symposium on Market Transformation Richard Lord Carrier Fellow HVAC Industry Challenges and Issues Ozone Deletion Global Warming

More information

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,

More information

Role of Economizers in Dedicated Outdoor Air Systems

Role of Economizers in Dedicated Outdoor Air Systems Introduction: Role of Economizers in Dedicated Outdoor Air Systems A question that frequently arises when a dedicated outdoor air system (DOAS) (Mumma, 2001) is discussed, particularly when the parallel

More information

INDOOR AIR QUALITY ASSESSMENT

INDOOR AIR QUALITY ASSESSMENT INDOOR AIR QUALITY ASSESSMENT Massachusetts Criminal Justice Training Council at the Boylston Town Offices Building 221 Main Street Boylston, Massachusetts Prepared by: Massachusetts Department of Public

More information

Matching the Sensible Heat Ratio of Air Conditioning Equipment with the Building Load SHR

Matching the Sensible Heat Ratio of Air Conditioning Equipment with the Building Load SHR Matching the Sensible Heat Ratio of Air Conditioning Equipment with the Building Load SHR Final Report to: Airxchange November 12, 2003 Report prepared by: TIAX LLC Reference D5186 Notice: This report

More information

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s

More information

Indoor air quality monitoring made easy

Indoor air quality monitoring made easy Indoor air quality monitoring made easy with the Fluke 985 Particle Counter Application Note Introduction Energy savings is top of facilities owners agenda. HVAC system tends to be the largest contributor

More information

Answers to Your Questions from the Webinar

Answers to Your Questions from the Webinar 2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in

More information

The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings

The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings 4276 The Impact of Demand-Controlled and Economizer Ventilation Strategies on Energy Use in Buildings Michael J. Brandemuehl, Ph.D., P.E. Member ASHRAE James E. Braun, Ph.D., P.E. Member ASHRAE ABSTRACT

More information

Risk Bulletin. Mold Prevention and Control for Mechanical and HVAC Contractors. XL Group Insurance

Risk Bulletin. Mold Prevention and Control for Mechanical and HVAC Contractors. XL Group Insurance XL Group Insurance Risk Bulletin Mold Prevention and Control for Mechanical and HVAC Contractors Mechanical contractors have an inherent risk of mold claims arising out of the heating, ventilation, and

More information

HVAC Calculations and Duct Sizing

HVAC Calculations and Duct Sizing PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An

More information

AG-TQS-IAQ-00 March 4, 2002. Application Guide. TQS with IAQ Inlet

AG-TQS-IAQ-00 March 4, 2002. Application Guide. TQS with IAQ Inlet Application Guide TQS with IAQ Inlet Table of Contents Introduction 2 ASHRAE Standard 62 2 Outdoor Air Requirements For Ventilation For Commercial Buildings 3 EPA Report Energy Costs and IAQ Performance

More information

Using Time-of-Day Scheduling To Save Energy

Using Time-of-Day Scheduling To Save Energy The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.

More information