COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS
|
|
|
- Dayna Bridges
- 10 years ago
- Views:
Transcription
1 COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS Risto Kosonen, Panu Mustakallio Arsen Melikov 2, Marcin Duszyk 2 Oy Halton Group Ltd., Helsinki, Finland. 2 International Centre for Indoor Environment and Energy, DTU Civil Engineering, Technical University of Denmark, Lyngby, Denmark. Abstract Compared with convective systems radiant systems explore the advantage of influencing the mean radiant temperature for maintaining similar thermal conditions at lower room air temperature in heating mode and higher room air temperature in cooling mode. In some manufactures catalogues, the difference of the mean radiant temperature between radiant and convective systems is claimed to be as high as 2-3 o C. The difference between radiant system with ceiling installed pannels combined with mixing air distribution and convective system of chilled beams was studied with regard to the mean radiant temperature and radiant temperature asymmetry in a mock-up office at different internal load in both heating and cooling modes. The operative temperature and the radiant temperature asymmetry were measured at four locations and three heights in the occupied zone. The radiant temperature asymmetry was measured in three directions: vertical direction between floor and ceiling, and two horizontal directions respectively parallel to walls. The difference in operative temperature measured at. m height measured with the two systems under the same conditions and at same locations was insignificant (about.5 o C). The operative temperature was more or less uniform over the occupied zone and there was not any significant difference in the operative temperature measured with the two systems. The radiant asymmetry was lower than 5.5 o C in all measured cases. The difference in the radiant temperature asymmetry measured with the chilled beam system and the radiant panel system was also small. Keywords: thermal comfort, operative temperature, radiant panel, chilled beam Introduction Present standards (EN ISO 773) specify requirements with regard to general thermal comfort, operative temperature, vertical temperature gradient, radiant temperature asymmetry and draught discomfort for achieving thermally confortable environment in occupied zone of rooms. According to Babiak et al. (27) compared to the convective cooling system the radiant panel cooling system can achieve the same level of operative temperature at a higher room air temperature. In some manufactures catalogues, the difference of the mean radiant temperature between radiant and convective systems is claimed to be as high as 2-3 o C. The reported difference in the mean radiant temperature is based in measurements in empty room with maximum heating demand. However in modern offices, the situation is different when the heating and cooling demands are moderate and the surface temperature of the radiant panel is close to the room air temperature. In cooling applications, the radiant panel temperature can not decreased below 6-8 o C because of the condensation risk. For heating, the surface temperature of about 3 o C is high enough to cover the maximum heating demand. The difference between radiant and convective systems with regard to the mean radiant temperature and radiant temperature asymmetry was studied in a mock-up office at different internal load in both heating and cooling modes. The results are presented in this paper.
2 2 Methods Experiments were conducted in a mock up of an office room with dimensions 4.6 m x 2.8 m x 2.65 m (L x W x H). A chilled beam system ( 23 (L) x 3 (W)) and a radiant panel system ( 2 x 3 (L) x 6 (W)) were installed and studied. A radial air supply diffuser was installed between the radiant panels. In Fig., there is shown test arrangement in the simulated office. Figure. Set-up of the two systems studied. The performance of the systems was evaluated under winter and summer conditions in both maximum heating/cooling conditions and typical mid-season conditions in an office. The heat load used in the measurements comprised a PC (2 W), lighting (6 W) and a heated dummy (72 W) simulating an occupant. In the maximum cooling condition, heat gain from direct solar radiation was simulated by heating 3. m² area of the floor close to the window by electrically heated foil (2 W). The heat load from the window was 25 W (maximum cooling case) and 43 W (moderate cooling case) (surface temperatures of 32 o C and 3 o C). In the winter conditions, adjustable temperature of the simulated window was introduced. The window surface temperature was 5.2 o C in the cases without internal heat gains (heat loss 28 W). The transmission loss of the structure was 9 W. When the internal heat gains where introduced, the window surface temperature was decreased to 3.3 o C (heat loss 276 W). With the heat gains, the tramission loss was 99 W. In Fig.2, there is presented the locations of heat sources, the simulated window, radiant pannels, the supply valve, the chilled beams and the exhaust valve are indicated in Fig. and Fig. 2. The operative temperature and the radiant temperature asymmetry were measured at four locations in the occupied zone of the room. The operative temperature was measured at.,.6 and. m above the floor. The radiant asymmetry was measured in three directions: vertical direction between floor and ceiling, and two horizontal directions respectively parallel to walls. The locations of measurements sensors are presented in Fig. 3. The operative temperature was measured by Thermal Comfort Meter. The operative temperature measurement range is 5 4 C and the accuracy of operative measurement is ±.3 C. The radiant temperature asymmetry was measured by radiant asymmetry sensor with measurement accuracy ±2 C (in the range 3 C). The water flow rate was measured with Krohne
3 Electromagnetic Flowmeter IFC with accuracy less than ± % of the readings. The airflow rate was measured with differential pressure transmitter Furness Controls FCO33 with accuracy less than ±.5% of the readings. The air flow rate was measured with a measurement unit (MSD-). The experiments were conducted at winter and summer conditions. In the summer case the room air temperature was kept at 26 C in the reference point at the height level.3 m above the floor. In the winter case, the room air temperature measured was kept at 2 C. When supply air flow rate was introduced, it was in both radiant panel and active chilled beam cases 25 L/s (2. L/s per m 2 ). Figure 2. Locations of the heat sources, window and exhaust air diffuser in the room. Figure 3. Measurement locations and heights in the room.
4 The experimental conditions during the experiments are listed in Table. The cooling capacity was varied between 35 W/m 2,floor - 5 W/m 2,floor. In the cooling mode a reference case with radiant cooling panels but without supply of ventilation air was measured. In heating mode, the heating capacity was varied between 7-24 W/m 2,floor. With radiant panel system, for the case with the maximum heating capacity (24 W/m 2,floor) measurements without supply of ventilation air were performed as well. Table : Measured cases and experimental conditions (RP= radiant panel, CB=chilled beam and WSA= without supply air). Case Water Temperature in/out, C Water Flow rate kg/s Temperature of supply air, C RP 29 W/m 2 WSA Cooling: 4/ Specified Heat gain profile Maximum internal load Note: 265 W (24 W/m2) transmission loss through the walls RP 5 W/m 2 Cooling: 4/ Maximum internal load RP 35 W/m 2 Cooling: 4/8. 7 Part load RP 24 W/m 2 WSA Heating: 33.5/ No internal load RP 24 W/m 2 Heating: 33.5/ No internal load RP 7 W/m 2 Heating: 33.5/ Maximum internal load CB 5 W/m 2 Cooling: 6.8/ Maximum internal load CB 35 W/m 2 Cooling: 2.4/ Part load CB 24 W/m 2 Heating: 33./ No internal load CB 7 W/m 2 Heating: 29.6/ Maximum internal load 3 Results In Fig 4, the difference between the air temperature and operative temperature measured at the. m at the locations A, B, C and D (Fig. 3) in the occupied zone in the cooling mode case is shown. In the comparison of the operative and room air temperatures, the reference room air temperature is calculated from the closest air temperature sensors from the relevant operative temperature measurement point. The used reference room air temperatures calculation are marked with red circles around the operative sensors in Fig. 3. With the radiant panel system (RP), the room air temperature was in average.3 ºC higher than operative temperature in the case of maximum cooling load condition (5 W/m 2 ). Close to the dummy (at point C), the room air temperature was.35 ºC higher than the operative temperature. With lower heat gains (35 W/m 2 ), the room air temperature was at the measured points was either higher or lower than the operative temperature. On an average, the room temperature was.3 ºC lower than the room air temperature. The difference increased (up to.7 ºC) in the case with radiant panels when ventilation air was not supplied. With the chilled beam system (CB), the room air temperature was in average.5 o C lower than the operative temperature in the case with maximum cooling load (5 W/m 2 ). Close to the dummy, there was not any difference and the room air temperature was the same as the operative temperature. With lower cooling load (35 W/m 2 ), there was on average.2 ºC difference between the room air and operative temperatures. Thus, the radiant panel gave on average.5 ºC lower operative temperature than the chilled beam systems. Close to the dummy, there was higher difference: radiant panel system gave.35 ºC lower operative temperature than the chilled beam system. In Fig. 5, the difference between room air temperature and operative temperature in heating mode is shown. With the radiant panel system combined with mixing air distribution, the room air
5 temperature was on average higher.6 ºC than operative temperature in the maximum heat demand condition (7 W/m 2 ). With the chilled beam system, in the maximum heat condition, the difference was about the same level (. ºC). Respectively, with lower heat demand case (7 W/m 2 ), the difference was.6 ºC with the radiant panel system and.25 ºC with the chilled beam system. The temperature difference in the case with radiant panels increased (up to.4 ºC) when the ventilation air was not used (Case RP 24 W/m 2 WSA). Both in heating and cooling mode when the supply air flow rate was introduced with the radiant panel system, the difference between the room air and operative temperatures reduced. This indicates that the jet and convection loads mixed the room space and influenced on the surface temperature of the walls.,8 Temperature difference?c,6,4,2 -,2 RP 29 W/m2 WSA RB 5 W/m2 RP 35 W/m2 CB 5 W/m2 CB 35 W/m2 -,4 -,6 Figure 4. Difference between room air temperature and operative temperature measured at A, B, C, D at. m level above the floor in cooling mode cases. (WSA=without supply air),8 Temperature difference?c,6,4,2 -,2 RP 24 W/m2 WSA RP 24 W/m2 RP 7 W/m2 CB 24 W/m2 CB 7 W/m2 -,4 Figure 5. Difference between room air temperature and operative temperature measured at locations A, B, C, D at. m level above the floor in heating mode cases (WSA=without supply air).
6 Radiant temperature asymmetry was measured in three directions: between floor and ceiling, and direction respectively parallel to walls and 2 and walls 3 and 4 (Fig. 2). In Figs. 6 and 7 radiant temperature asymmetry between floor and ceiling and between wall (with heated window) and wall 2 is shown in the heating and cooling conditions respectively. In the cooling mode, the radiant symmetry between floor and ceiling was below 5.5 o C in all measured cases (Fig. 6). The radiant temperature difference was less than 2 o C for all measured locations except location C which most probably was influenced by the heated dummy. Between the floor and the ceiling the radiant temperature asymmetry was below 2.5 o C (Fig. 6). In heating mode, the radiant asymmetry was below 3 o C in all studied cases (Fig. 7) ΔT,?C 3 2 RP29 W/m2 WSA RB 5 W/m2 CB 5 W/m2 RP 35 W/m2 CB 35 W/m2 6 ΔT,?C RP29 W/m2 WSA RB 5 W/m2 CB 5 W/m2 RP 35 W/m2 CB 35 W/m2 Figure 6. Radiant temperature asymmetry measured in the cooling mode cases (Table ). Upper figure: asymmetry between wall and wall 2; Lower figure: asymmetry between floor and ceiling (WSA=without supply air).
7 6 5 4 ΔT,?C 3 2 RP29 W/m2 WSA RB 5 W/m2 CB 5 W/m2 RP 35 W/m2 CB 35 W/m ΔT,?C 3 2 RP29 W/m2 WSA RB 5 W/m2 CB 5 W/m2 RP 35 W/m2 CB 35 W/m2 Figure 7. Radiant temperature asymmetry measured in the heating mode cases (Table ). Upper figure: asymmetry between wall and wall 2; Lower figure: asymmetry between floor and ceiling (WSA=without supply air). 4 Discussion The results of the present study do not validate the reported in the literature advantage of radiant cooling systems in providing operative temperature 2-3 o C lower than air temperature in comparison with mixing air distribution systems. The results of this study showed that the difference between the operative temperature and the air temperature was much lower. In the cooling mode the maximum difference for the radiant panel system combined with mixing air distribution was.35 o C and an average difference was only.2 o C. Results showed also small difference between room air temperature and operative temperature with the chilled beam system. Thus, there was no significant difference on the operative temperatures with the radiant panel and chilled beam system. The stated in some manufactures catalogues relatively large difference of 2-3 between operative temperature and air temperature in rooms with radiant cooling/heating panels has been obtained without presence of heat sources and airflow introduced by mechanical ventilation. In occupied spaces
8 thermal plumes and the ventilation flow influence substantially the air distribution and promote air mixing which has an impact on the mean radiant temperature and thus on the operative temperature. The present results show that air mixing is also achieved in rooms without mechanical ventilation due to the thermal plumes generated by heat sources. In the room with radiant panels and without heat sources and flow generated by mechanical ventilation the difference between the room air and operative temperature is higher. This however is not the case in occupied spaces. In the measurements of the present study were performed with the highest heat load of 5 W/m 2 floor. In case of higher heat load (7-9 W/m 2 floor) for radiant cooling systems, the difference between the operative temperature and the air temperature may be higher. The office layout will affect the air distribution and thus may have effect on the performance of the radiant cooling systems and in general on occupants thermal comfort. In open layout concepts, the results could be different. 5 Conclusions The average difference in operative temperature measured with the radiant panel and chilled beam systems under the same conditions and the same location in the occupied zone were small (less than.35 o C). The operative temperature was more or less uniform over the occupied zone. The difference between the operative temperature and the air temperature in the case of radiant cooling panels combined with mixing ventilation was not much different than in the case of chilled beams. The radiant temperature asymmetry was lower than 5.5 o C in all measured cases. That fulfils the demands of present 6 Acknowledgement The study is supported by Technology Agency of Finland (TEKES). 7 References Babiak, J., Olesen, B.W., Petras, D. (27) Low temperature heating and high temperature cooling, Rehva guidebook no 7, Finland, ISBN , p. 4-5 International standard ISO 7726:998 Ergonomics of the thermal environment- Instruments for measuring physical quantities, International Organization of Standardization ISO, November 28, Geneva, Switzerland, p. 6-7, 49-5 International standard ISO 773:25 Moderate thermal environments-determination of the PMV and PPD indices and specification of the conditions for thermal comfort, International Organization of Standardization ISO, November 25, Geneva, Switzerland
This article appeared in a journal published by Elsevier. The attached copy is furnished to the author for internal non-commercial research and
This article appeared in a journal published by Elsevier. The attached copy is furnished to the author for internal non-commercial research and education use, including for instruction at the authors institution
Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE
TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically
Energy Efficient HVAC-system and Building Design
Energy Efficient HVAC-system and Building Design Maija Virta 1, Harri Itkonen 1, Panu Mustakallio 1, Risto Kosonen 1 1 Halton Oy, Finland Corresponding email: [email protected] SUMMARY This paper
CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND?
Topic B3: Control of indoor environment CAN DEMAND CONTROLLED VENTILATION REPLACE SPACE HEATING IN OFFICE BUILDINGS WITH LOW HEATING DEMAND? Axel CABLE 1,*, Mads MYSEN 1,2, Kari THUNSHELLE 1 1 SINTEF,
COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS -
pcoolingandheating COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - Bjarne W. Olesen, Ph.D. D. F. Liedelt "Velta" Summary Due to intensive use of
Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE
Life cycle cost comparison of TAB vs. other HVAC (UK) TECHNICAL BROCHURE 3 213 2 2 UPONOR LIFE CYCLE COST COMPARISON OF TAB VS. OTHER HVAC Contents Introduction... 4 Base building... 5 System and tested
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling
Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling Panu Mustakallio and Risto Kosonen Halton Oy, Haltonintie 1-3, 47400 Kausala, Finland E-mail: [email protected]
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of
Kan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13
Kan behovsstyrt ventilasjon erstatte lokal varme? Axel Cablé, SINTEF Seminar 19.11.13 1 Kan behovsstyrt ventilasjon erstatte lokal varme? Principles Challenges VABAT Project 2 Principles Increased envelope
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 REHVA
Radiant Panels and Chilled Sails. www.price-hvac.com
Radiant Panels and Chilled Sails www.price-hvac.com Radiant Panels and Chilled Sails Introduction Radiant panels use thermal radiation to modify surface temperatures in order to provide sensible cooling
HDA -----------------------------------------------------------
----------------------------------------------------------- Lightstrips ---------------------------------------------------------------------- Ceiling system for heating and cooling LIGHTSTRIPS LIGHTSTRIPS
Adaptive strategies for office spaces in the UK climate
International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
Federation of European Heating, Ventilation and Air-conditioning Associations
Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu [email protected] Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of
Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015
EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW
School Performance Specifications. SPACES Engineering Technical Meeting 22 September 2015
School Performance Specifications SPACES Engineering Technical Meeting 22 September 2015 EFA Facilities Output Specification: Introduced in 2013 to promote: well-integrated and simple buildings that benefit
Air distribution effectiveness with stratified air distribution systems
Lee, K.S., Jiang, Z., and Chen, Q. 2009 Air distribution effectiveness with stratified air distribution systems, ASHRAE Transactions, 115(2). Air distribution effectiveness with stratified air distribution
How To Design A Room Air Conditioning System
Comparison of HVAC Technology in Buildings Conventional HVAC Technology Bauer Optimising Technology The Differences Room environment (Occupant Comfort) Energy Consumption Architecture Air flows in a room
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics
Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics A Presentation of Work in Progress 4 October 2006 in the Intelligent
ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS.
1 ENERGY SAVINGS BY CHANGING CONSTANT AIR VOLUME SYSTEMS (CAV) TO VARIABLE AIR VOLUME SYSTEMS (VAV) IN EXISTING OFFICE BUILDINGS. - EXPERIENCE FROM A PLANT RECONSTRUCTION BASED ON A NEW SUPPLY AIR TERMINAL
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
Lesson 36 Selection Of Air Conditioning Systems
Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section
Subtropical Cities September 2006. Design for Energy Efficiency in Commercial Buildings in Queensland
Subtropical Cities September 2006 Design for Energy Efficiency in Commercial Buildings in Queensland Contents Typical Building Constraints & Requirements Understanding Energy Consumption in Buildings HVAC
Alternative to the Conventional Heating and Cooling Systems in Public Buildings
Paper received: 01.12.2009 UDC 628.8:697.353:069 Paper accepted: 02.03.2010 Alternative to the Conventional Heating and Cooling Systems in Public Buildings Mitja Košir * - Aleš Krainer - Mateja Dovjak
Thermal environments. www.swema.com [email protected] Tel. +46 8 94 00 90
ISO 7730 Moderate Thermal Environments Thermal environments Swema equipment for the measurement of Moderate Thermal Environments is designed to comply with the standards: ISO7726 - Thermal environments
Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures
Comparison of two calculation methods used to estimate cooling energy demand and indoor summer temperatures Kai Sirén and Ala Hasan Helsinki University of Technology, Finland Corresponding email: [email protected]
Radiant Floor Heating In Theory and Practice
The following article was published in ASHRAE Journal, July 02. Copyright 02 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes only.
Halton - Achieving Energy Efficiency in School Design
Halton - Achieving Energy Efficiency in School Design Enabling Wellbeing Halton Design Tools Drive Energy Efficient Kitchen Ventilation and Comfort Today, nutritional guidelines for school foodservice
Displacement ventilation
General The displacement ventilation principle is the oldest form of ventilation and can be achieved without the use of fans. Air movement occurs by means of the density differences between supply air
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN
COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN Umesh Atre Innovative Design Inc 850 W Morgan St Raleigh, NC 27603 [email protected]
CEN/TC 156. pren 15251. Date: 2006-07-31 CEN/TC 156. Secretariat: BSI ICS: Descriptors:
CEN/TC 156 Date: 2006-07-31 pren 15251 CEN/TC 156 Secretariat: BSI Indoor environmental input parameters for design and assessment of energy performance of buildingsaddressing indoor air quality, thermal
Active & Passive Beams
Active & Passive Beams Active & Passive Beams Introduction Beam systems are an alternative to traditional all-air conditioning systems. Beams use water to move energy through a building and service the
AIR DISTRIBUTION FOR COMFORT AND IAQ
AIR DISTRIBUTION FOR COMFORT AND IAQ Heating Piping and Air Conditioning March 1998 Dan Int-Hout Chief Engineer KRUEGER EXCELLENCE IN AIR DISTRIBUTION Modern environmentally controlled spaces consume significant
A NODAL MODEL FOR DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEMS IN OFFICE SPACES
A NODAL MODEL FOR DISPLACEMENT VENTILATION AND CHILLED CEILING SYSTEMS IN OFFICE SPACES Simon J. Rees and Philip Haves School of Mechanical & Aerospace Engineering, Oklahoma State University, Stillwater,
CFD ANALYSIS CHALLENGES IN BUILDING SIMULATION FOR SIMBUILD2004 CONFERENCE. Ferdinand Schmid and Galen Burrell Architectural Energy Corporation
CFD ANALYSIS CHALLENGES IN BUILDING SIMULATION FOR SIMBUILD2004 CONFERENCE Ferdinand Schmid and Galen Burrell Architectural Energy Corporation ABSTRACT This paper discusses the capabilities and challenges
We have been working in an ideal climate for thirty years.
Underfloor cooling We have been working in an ideal climate for thirty years. A climate that has brought us to a position of leadership in Italy in the field of radiant heating and cooling. RDZ was the
Instructions for designing heating systems.
Instructions for designing heating systems. In order to obtain the required effect, a lower consumption, a smaller quantity of impurities and improved comfort, heat and domestic hot water installations
Thermal environment in indoor spaces with under-floor air distribution systems: 1. Impact of design parameters (1522-RP)
Lee, K.S., Xue, G., Jiang, Z., and Chen, Q. 0. Thermal environment in indoor spaces with under-floor air distribution systems:. Impact of design parameters (5-RP), HVAC&R Research, 8(6), 8 9. Thermal environment
Software Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
2013 Code_Saturne User Group Meeting. EDF R&D Chatou, France. 9 th April 2013
2013 Code_Saturne User Group Meeting EDF R&D Chatou, France 9 th April 2013 Thermal Comfort in Train Passenger Cars Contact For further information please contact: Brian ANGEL Director RENUDA France [email protected]
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
BUILDING ENERGY DEMAND AGGREGATION AND SIMULATION TOOLS A DANISH CASE STUDY
BUILDING ENERGY DEMAND AGGREGATION AND SIMULATION TOOLS A DANISH CASE STUDY P. Gianniou; A. Heller; C. Rode Department of Civil Engineering, Technical University of Denmark, Kgs. Lyngby ABSTRACT Nowadays,
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
Air-water systems for efficient air conditioning
Air-water systems for efficient air conditioning The art of handling air System overview Passive cooling systems Induction units Façade ventilation units Page 4 Page 6 Page 10 Passive Chilled ceiling Undersill
THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING. R.M.J. Bokel
THE EFFECT OF WINDOW POSITION AND WINDOW SIZE ON THE ENERGY DEMAND FOR HEATING, COOLING AND ELECTRIC LIGHTING R.M.J. Bokel Department of Architecture, Delft Technical University, Delft, The Netherlands,
Diego Ibarra Christoph Reinhart Harvard Graduate School of Design
Building Performance Simulation for Designers - Energy DesignBuilder // EnergyPlus Tutorial #2 Load Schedules GEOMETRY LOADS RESULTS Diego Ibarra Christoph Reinhart Harvard Graduate School of Design OVERVIEW
DESIGN OF NATURAL VENTILATION WITH CFD CHAPTER SEVEN. Qingyan Chen. difficult to understand and model, even for simple
CHAPTER SEVEN L. Glicksman and J. Lin (eds), Sustainable Urban Housing in China, 116-123 2006 Springer. Printed in the Netherlands. DESIGN OF NATURAL VENTILATION WITH CFD Qingyan Chen INTRODUCTION As the
Center for the Built Environment UC Berkeley
Center for the Built Environment UC Berkeley Peer Reviewed Title: Analysis of a hybrid UFAD and radiant hydronic slab HVAC system Author: Raftery, Paul, National University of Ireland Galway Lee, Kwang
Energy Efficiency HOSPITALITY. www.energia.ie
Energy Efficiency HOSPITALITY www.energia.ie Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could make a real
HEATING-COOLING WALL PANELS SYSTEM IN SLOVENE ETHNOGRAPHIC MUSEUM
01-147 The 2005 World Sustainable Building Conference, HEATING-COOLING WALL PANELS SYSTEM IN SLOVENE ETHNOGRAPHIC MUSEUM Aleš KRAINER Prof. Dr. 1 Rudi Perdan 2 Gal Krainer 3 1 2 Faculty of Civil Engineering,
Air Conditioning in Green Office Buildings?
Air Conditioning in Green Office Buildings? How to implement Demand Controlled Ventilation Stuttgart Rechte allein bei ICEBO 08 10.10.2008 CI / DrRo 1 Air Conditioning in Green Office Buildings ventilation
Information paper 20. Prepared by: David Clark. book:
Information paper 20 Ventilation rates in offices and natural mechanical Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information
ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests
ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests DesignBuilder Version 1.2.0 (incorporating EnergyPlus version 1.3.0) - June 2006 1.0 Purpose The ANSI/ASHRAE Standard 140-2004
Sustainable construction criteria to evaluate the thermal indoor climate - further development of the BNB assessment tool and practical implementation
Fraunhofer Institute for Building Physics IBP Directors Univ. Prof. Dr. Ing. Gerd Hauser Univ. Prof. Dr. Ing. Klaus Sedlbauer Holzkirchen Branch Fraunhoferstrasse 10 83626 Valley / Germany IBP-Abstract
BBD 2015 Presentation HVAC, Control, and Plumbing Systems for Thermos Bottle Buildings Roy Swain, P.E. February 5, 2015
BBD 2015 Presentation HVAC, Control, and Plumbing Systems for Thermos Bottle Buildings Roy Swain, P.E. February 5, 2015 Thermos Bottle Buildings are now popular and practical. However, they have thermal
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM
ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,
RESNET National Rater Test Study Guide Outline
RESNET National Rater Test Study Guide Outline The RESNET national home energy rating standard spells out a listing of the knowledge base and skills set for Home Energy Ratings. Trainers and Rating Quality
How To Make A Building Energy Efficient
An Introduction to Chilled Beams and Ceilings July 2012 Version 1 DISCLAIMER All rights reserved. Apart from any fair dealing for the purposes of private study or research allowed under applicable copyright
Elegance SC. Solar Control
Elegance SC Solar Control Sapa Building System Building Understanding In an age of global warming, the reduction of carbon emissions is a key factor when both selecting materials for a building and how
Mistrale. Fusion Terminal
Mistrale Fusion Terminal PUBLICATION NATURAL VENT. 1 SEPT 2015 Features - Slimline energy efficient ventilation solution - Standard and high capacity terminals provide 128 or 256 L/s capacity - Compliant
Fläkt Woods Building Future
Energy, Expertise and Environment with Fläkt Woods Fläkt Woods Building Future Saving energy in building ventilation You must save 20% on energy before 2020. Following the Kyoto protocol the European Union
Condensing Boiler Efficiency
Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2
UNDERFLOOR AIR DISTRIBUTION
FINAL REPORT NCEMBT-080801 UNDERFLOOR AIR DISTRIBUTION AN EXPERIMENTAL COMPARISON OF AIR DIFFUSION PERFORMANCE BETWEEN UNDERFLOOR AIR DISTRIBUTION AND CONVENTIONAL OVERHEAD AIR DISTRIBUTION SYSTEMS AUGUST
SELECTIVE GLAZING FOR SUN CONTROL
SUN CONTROL GLAZING SELECTIVE GLAZING FOR SUN CONTROL Sun Factor 1st level performance for direct solar energy Solar energy control Solar control coating Only if the glass is exposed to sun rays! 2nd level
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS
CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS by Dr. Bing Chen and Prof. John Bonsell Passive Solar Research Group University of Nebraska-Lincoln Omaha campus and Richard
LindabAtriumPlana. Heating and cooling panels. lindab atrium plana. lindab we simplify construction
lindab we simplify construction LindabAtriumPlana Heating and cooling panels 052016 Lindab Ventilation All forms of reproduction without written permission are forbidden is the registered trademark of
Energy savings in the residential area are essential in
Overheating and insufficient heating problems in low energy houses up to now call for improvements in future Requirements for improved energy performance have shifted major focus on energy calculations
Optimum Solar Orientation: Miami, Florida
Optimum Solar Orientation: Miami, Florida The orientation of architecture in relation to the sun is likely the most significant connection that we can make to place in regards to energy efficiency. In
Under sill units. Type FSL-B-ZAS
.1 X X testregistrierung Under sill units Type, heat recovery Centrifugal fan Adaptive heat recovery damper HYGIENISCH GETESTET V DI 022 Tested to VDI 022 Secondary air unit for supply air and extract
Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas
Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update
CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER
International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)
HYDRONIC DESIGNER / INSTALLER MODULE DESCRIPTIONS
HYDRONIC DESIGNER / INSTALLER MODULE DESCRIPTIONS PIP301: Blueprint Reading This module covers the basic skills required for interpreting information provided by drawings. These skills are essential in
3-D Modeller Rendered Visualisations
Recognised energy Dynamic Simulation Modelling (DSM) software DesignBuilder is a user interface to the EnergyPlus DSM. EnergyPlus builds on the most popular features and capabilities of BLAST and DOE-2
Combi Unit Genius. The energy efficient Building Service Centre
Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Combi Unit Genius The energy efficient Building Service Centre systemair Central Building Services
Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers
Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial
Problem Statement In order to satisfy production and storage requirements, small and medium-scale industrial facilities commonly occupy spaces with ceilings ranging between twenty and thirty feet in height.
Comparison between Decentralised and Centralised Air Conditioning Systems
Comparison between De and Centralised Air Conditioning Systems (Summary) FassadenSystemLüftung FassadenSystemLüftung Telephone +49/ 28 45/ 2 02-711 GmbH & Co KG Telefax +49/28 45/2 02-2 25 Heinrich-Trox-Platz
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
INDOOR ENVIRONMENT OF A CLASSROOM IN A PASSIVE SCHOOL BUILDING WITH DISPLACEMENT VENTILATION. Applied Energy Research, Munich, Germany
INDOOR ENVIRONMENT OF A CLASSROOM IN A PASSIVE SCHOOL BUILDING WITH DISPLACEMENT VENTILATION Yang Wang 1,2, Jens Kuckelkorn 1, Fu-Yun Zhao 3,4 and Hartmut Spliethoff 2,1 1 Division of Technology for Energy
Energy Efficiency. Bars & RestauRants. www.energia.ie
Energy Efficiency Bars & RestauRants www.energia.ie 2 Your chance to reduce your business energy usage by as much as 20%! 20% is a significant figure and reducing your energy bill by this amount could
Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...
Solar air collectors for industry and larger halls N S Ø Efficient dehumidification and air heating for free... This booklet contains information about SolarVenti Industrial air solar system. The system
Crawl space heat and moisture behaviour
Crawl space heat and moisture behaviour Miimu Airaksinen, Dr., Technical Research Centre of Finland, VTT [email protected], www.vtt.fi KEYWORDS: crawl space, moisture, evaporation from ground, ground
Basic Selection & Proper Application of Overhead Air Distribution Devices
Basic Selection & Proper Application of Overhead Air Distribution Devices GRD Selection & Application Terms Selection Throw Sound Installation Variations affect Performance Inlet Effects Basics Return
DSRQ - DSRSQ - DSRSQ-THERM
DSRQ - DSRSQ - DSRSQ-THERM Specification item: Variable geometry diffuser on 597x597 mm panel developed for rooms with high ceilings where a long throw and a high induction ratio are required. Made up
Essam E. Khalil [email protected]
AIR-CONDITIONING SYSTEMS DEVELOPMENTS IN HOSPITALS: COMFORT, AIR QUALITY, AND ENERGY UTILIZATION Essam E. Khalil [email protected] PROFESSOR OF MECHANICAL ENGINEERING, CAIRO UNIVERSITY, EGYPT Abstract
DEVELOPMENT OF CONVECTIVE HEAT TRANSFER MODELS FOR HUMAN BODY SEGMENTS FOR THE CASE OF DISPLACEMENT VENTILATION IN ROOMS
DEVELOPMENT OF CONVECTIVE HEAT TRANSFER MODELS FOR HUMAN BODY SEGMENTS FOR THE CASE OF DISPLACEMENT VENTILATION IN ROOMS S. R. Bolineni 1, S. Stratbücker 1, and C. van Treeck 2 1 Fraunhofer Institute for
CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL BUILDING
2000 Elsevier Science Ltd. All rights reserved., Air Distribution in Rooms, (ROOMVENT 2000) Editor: H.B. Awbi 767 CFD AND MULTI-ZONE MODELLING OF FOG FORMATION RISK IN A NATURALLY VENTILATED INDUSTRIAL
How To Model With Cfd Using Phoenics
The Use and Application of CFD in the Air Conditioning and Fire Protection Industry AIRAH NSW February 2008 The Use and Application of CFD in the Air Conditioning and Fire Protection Industry An Introduction
EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS
EVALUATION OF PHOENICS CFD FIRE MODEL AGAINST ROOM CORNER FIRE EXPERIMENTS Yunlong Liu and Vivek Apte CSIRO Fire Science and Technology Laboratory PO Box 31 North Ryde, NSW 167, Australia TEL:+61 2 949