Cooling Tower Basics and Common Misconceptions
|
|
|
- Spencer Wilkinson
- 9 years ago
- Views:
Transcription
1 Cooling Tower Basics and Common Misconceptions Introduction In comparison with most other industrial equipments, the water cooling tower is a simple device, based on the direct contact of two of the earth s most common substances: air and water; yet a surprising number of misconceptions on its design, operation and behavior prevail. Cooling basics and important misconceptions are discussed herein, with the goal of helping to achieve the most economical and beneficial application, design, and operation of this important heat transfer device. Cooling Tower Fundamentals Heat Transfer: The basic principle of the cooling tower operation is that of evaporative condensation and exchange of sensible heat. The air and water mixture releases latent heat of vaporization which has a cooling effect on water by turning a certain amount of liquid into its gaseous state thereby releasing the latent heat of vaporization. This is more effectively demonstrated by wetting the back of your hand with water and blowing on it. This effect is what happens inside the cooling tower. The air stream releases latent heat of vaporization thereby dropping the temperature of the water on your skin. The liquid changing to its vaporous state consumes heat which is taken from the water remaining, thus lowering its temperature. There is a penalty involved, and that is loss of water which goes up to the cooling tower and is discharged into the atmosphere as hot moist vapor. Under normal operating conditions, this amounts to approximately 1.2% for each 10 o F cooling range. Sensible heat that changes temperature is also responsible for part of the cooling tower s operation. When water is warmer that the air, there is a tendency for the air to cool the water. The air then gets hotter as it gains the sensible heat of the water and the water is cooled as its sensible heat is transferred to the air. Approximately 25% of the sensible heat transfer occurs in the tower while the balance of the 75% cooling is due to the evaporative effect of latent heat of vaporization. Dry Bulb Temperature [DBT], Wet Bulb Temperature [WBT] and Relative Humidity [RH]: The temperature of air as read on the ordinary thermometer is called DBT. WBT is the reading when the bulb of a thermometer is covered with a wet cloth, and the instrument is whirled around in a sling. RH is the ratio of the quantity of water vapor present in a cubic feet of air to the greatest amount of vapor which that air could hold at a given temperature. When the relative humidity is 100%, the air cannot hold any more water and therefore, water will not evaporate in 100% humid air. When the RH is 100% the WBT is the same as the DBT, because the water cannot evaporate any more. But when the RH is less than 100%, the WBT will be less than the DBT and water will evaporate. The capability of the cooling tower is a measure of how close the tower can bring the water temperature to the WBT of the entering air. A larger cooling tower [i.e., more air and/or more fill] will produce a closer approach [colder leaving water] for a given heat load, flow rate and entering air condition. The lower the WBT, which indicates either cool air, low humidity or a combination of the two, the lower can the cooling tower can cool the water. The thermal performance of the cooling tower is thus affected by the entering WBT; the entering air DBT has an insignificant effect on thermal performance. In actual practice, the final cold water temperature will always be at least a few degrees above WBT, depending on design conditions. It is not customary in the cooling tower industry to guarantee any approach less than 5 o F. Jalal Engineering, [email protected] Page 1 of 6
2 Cooling Tower [Counter Flow] Theory Merkel Equation Figure 1 illustrates a drop of water falling through an upstream of unsaturated air at a wet bulb temperature of WBT with enthalpy ha, in a counter flow cooling tower. The drop of water is assumed to be surrounded by a film of saturated air at the water temperature WT with saturation enthalpy hw. As the drop travels downward, heat and mass transfer takes place from the interface air film to the upstream air, thereby cooling the water from HWT to CWT. This cooling process can best be explained on a Psychometric Chart. The process is shown in figure 2 known as the Driving Force Diagram. The air film is represented by the Water Operating Line on the Saturation Curve. The main air is represented by the Air Operating Line, the slope of which is the Water/Air [L/G] ratio. The cooling characteristic, a degree of difficulty to cooling is represented by the Merkel Equation: KaV / L = HWT CWT dt h W h The Merkel Equation primarily says that at any point in the tower, heat and water vapor are transferred into the air due [approximately] to the difference in the enthalpy of the air at the surface of the water and the main stream of the air. Thus, the driving force at any point is the vertical distance between the two operating lines. And therefore, the performance demanded from the cooling A ENTHALPY [Btu/lb] 1/[Hw - Ha 1 / [ hw ha ] Performance Demand [KaV/L] is area under curve. SATURATED AIR FILM, Enthalpy: h W Jalal Engineering, [email protected] Page 2 of 6 WBT AIR, Enthalpy: ha WATER DROPLET Water Operating Line, h w Enthalpy Driving Force: h w -h A Saturation Curve Air Operating Line, h A AIR, Enthalpy: ha θ Tan θ = L/G FIG TEMPERATURE [F] FIG TEMPERATURE [F] FIG. 3 tower is the inverse of this difference. The solution of the Merkel Equation can be represented by the Performance Demand Diagram shown in figure 3. The KaV/L value is equal to the area under the curve. An increase in the entering WBT moves the Air Operating Line towards the right and upward to establish equilibrium. Both the CWT and HWT increases, while the approach decreases. The curvature of the saturation line is such that the approach decreases at a progressively slower rate as the WBT increases. An increase in the heat load increases the cooling ranges and increases the length of the Air Operating Line. To maintain equilibrium, the line shifts to the right increasing the HWT, CWT, and CWT HWT
3 approach. The increase causes the hot water temperature to increase considerably faster than does the cold water temperature. In both these cases, the KaV/L should remain constant. However, a change in L/G will change the KaV/L value. Cooling Tower Designing On the basis of the above discussion, it is clear that there are five parameters that in combination dictate and define the performance of a cooling tower: 1. Hot Water Temperature HWT, 2. Cold Water Temperature CWT, 3. Wet Bulb Temperature WBT, 4. Water Flow Rate L, 5. Air Flow Rate G. The first four data are the ones, which are given by the user. The fifth one [G], is selected by the cooling tower designer. Once these five data are available, the tower characteristic [KaV/L], can be calculated through the Merkel Equation. The first step in cooling tower designing is the generation of a Demand Curve. In this curve, the KaV/L values are plotted against varying the L/G ratios. The next step is to superimpose fill characteristics curves and demand curves.[cooling Technology Institute has tested a variety of fill configurations and generated fill characteristic curves for each type; CTI s Technical Paper TP88 05 can be referred to in this regard.] Cooling Tower designing is basically an iterative process. The factors that effect the selection of design L/G and consequently the fill height are: cell dimensions, water loading, air velocities across various cooling tower sections and pressure drops, and fan selection. Please refer to figure 5 below, which is a screen print of Jalal Engineering s cooling tower designing program. COOLING TOWER DESIGNING GPM-US WBT- o F Heat Load -Ton[R] Number of Cells: Cell Model: 4250 HWT- o F R- o F CWT- o F A- o F 5.4 o C 3 16S 4,781.3 o C GPM / Cell: Cell Area-sft.: Water Loading-GPM/sft: Design Point Demand Curve 4FT/ 700FPM 4FT/ 500FPM 4FT/ 300FPM 2FT/ 700FPM 2FT/ 500FPM 2FT/ 300FPM L/G: 1.00 L -lb/min: [per Cell] 11,800.8 KaV/L: G -lb/min: [per Cell] Louver Height -ft Free Area-% 6.5 Louver Length-ft 97.0 Louver Velocity-FPM KaV/L CFM / Cell: 181, Air Velocity Across Fill -FPM: Fill Height Required -ft: 3 Fill Height to be Installed -ft: 4 Fill Safety Factor 1.3 KaV/L per ft.: 0.52 Fill Designation M L/G Fill Characteristic Lines of Velocity [M19060/ M-Nozz.(B&C)] vs. Demand Curve at Design Approach QUICK Fill Ht. -ft.: 3.01 CHECK Air FPM: 660 Air Properties Enthalpy-Btu/lb Specific Volume-ft 3 /lb Wet-Bulb Temp.- o F CT Designing Standard: Inlet 89.6 L/G: 1.00 Fill F./ft.: 0.52 Rain: 5.5 GPM: Outlet CTI Technical Paper TP88-05 Macro OK No. of Fans per Cell: 1 CFM per Fan: 181,978 Fan Diameter -ft: 12 Hub Seal Diameter -ft: 5 CT Static Press. -in. WC 0.40 CT Vel. Press. -in. WC [w/ o vel. recovery] Fan Efficiency -% 75 Fan Shaft Power -HP Motor Shaft Power -HP: 23.8 Gear Eff.-% Input Power -HP: 25.9 Motor Eff. -% JALAL Jalal Engineering [email protected] Customer Name: OMV Pakistan Ltd. Run Date: FIG. 4 Jalal Engineering, [email protected] Page 3 of 6
4 Common Misconceptions ʺMy Tower is Cooling the Water 20 ʺ Many people have been guilty at one time or another of defining what a cooling tower is doing in terms of range (HWT CWT). Often, this is accepted as a level of performance of the cooling tower. Nothing could be further from the truth. The equation for heat load is as follows: Heat Load [Btu/hr] = 500 x Water Flow Rate [GPM] x Range [ o F] Now, heat load, of course, is supplied by the unit being served by the cooling tower. The tower itself is neither a heat source nor a heat sink. In the usual circulating system the heat load is independent of the cooling tower. The number 500 is a constant, therefore is independent of the cooling tower. The circulating water flow is determined by the number of pumps running and the pressure drop in the overall circulating water system. Therefore, it likewise is independent of the cooling tower. If heat load, the constant, and the circulating water flow are all independent of the cooling tower, then by mathematical deduction the range is likewise completely independent of the cooling tower. Therefore, the range is the same whether there is a two cell tower or a four cell tower. The range would be the same if the fans were on full speed, half speed, or turned off. Consequently, such a statement as ʺMy tower is not performing because I bought it to cool 20, and it is only cooling the water 10 ʺ has no validity whatsoever. Likewise, the converse is true. Someone who has a cooling tower which is ʺcooling the water 30 ʺ whereas it was only designed to cool 20, may not be in such a fortunate position as he might think. Both these cases show no indication whatsoever of actual thermal capability of the cooling tower. What then is a measure of the thermal capability of the cooling tower? It is not the amount of heat being rejected, rather it is the level at which this heat is rejected. The measure of performance of the cooling tower is the resultant cold water temperature or even more specifically, the approach (CWT WBT) under given conditions. Cold water temperature is the primary dependent variable, and vividly indicates cooling tower capability. Approach Approach is CWT minus WBT. Another misconception that constantly crops up in cooling tower work is concerning approach. One will say, ʺI bought a tower to make a 10 approach, yet I have a 15 approach today. Therefore, the cooling tower is not working in accordance with its design.ʺ As the WBT goes down, the CWT also goes down. However, this is not a one to one relationship. It is more nearly a two to one relationship. That is, for each 2 F drop in WBT, the CWT will drop approximately 1 F. Therefore, if the WBT is 10 below design WBT, then by definition the approach will be increased 5 above that specified as design. Of course, the converse is also true: as wet bulb increases above design, then the cold water temperature will increase roughly one degree for each two degree increase in wet bulb. These are rough approximations and can be changed somewhat by different L/G ratios. Therefore, when attempting to determine whether or not performance appears to be satisfactory at other than design conditions, it is wiser to utilize the cooling tower performance curves or the CTI Blue Book [with cooling tower characteristic curves] rather than to just compare the actual approach to the design. Drift Loss Today, we see more and more interest in low drift loss cooling towers. This increased interest has been brought about by several factors. The major factor is continual insistence by the regulatory bodies that drift loss be minimized to reduce ecological effects. A second factor is an attempt to reduce water costs and treating costs by reducing water Jalal Engineering, [email protected] Page 4 of 6
5 consumption. However, let us now look at the basic concept reducing drift loss reduces water consumption. Water is lost out of a cooling tower in the following ways: drift, evaporation, blowdown and windage. Drift loss is a loss of water due to physical entrainment of liquid droplets in the air stream. This places water, with its attendant dissolved solids, in liquid form in the atmosphere. Windage is of a similar nature but usually much smaller in quantity. Windage is the sometimes loss of water through the louvered area of the tower due to wind blowing through the tower. This occurs more often with operation of the fans at half speed or off. For the purposes of this discussion, we will consider windage a portion of drift loss. The fact that drift leaves the cooling tower as liquid water, thereby containing its proportionate share of dissolved solids, is the important factor to remember. In order to maintain a proper total dissolved solids content level in a cooling tower, it is necessary to continuously blow down or throwaway a portion of circulating water. This is done to prevent the tower from accumulating excessive amounts of total dissolved solids which would cause severe scale and/or corrosion problems. This loss of water from the system is absolutely essential and cannot be avoided for the successful operation of the cooling tower. Therefore, drift is more properly defined as ʺinvoluntary blowdown.ʺ It now becomes readily apparent that any decrease in the drift loss from the cooling tower will result in an equivalent increase necessary in the blowdown in order to prevent excessive solids buildup. When viewed in this manner, it is evident that lowering drift loss does not reduce water consumption and consequently does not save anything in basic water cost or chemical treating costs. Another common misconception occurs when large clouds of ʺfogʺ emanate from cooling towers under certain atmospheric conditions. Many people assume that drift is a major contributing factor. However, this ʺfogʺ is quite different from drift as this water leaves the system in the vapor state and recondenses to small liquid droplets after encountering the relatively colder ambient air. The fog itself does not carry with it the dissolved solids and consequently does not fit into the category of involuntary blow down. Furthermore, it cannot be stopped by reducing drift loss. Therefore, one should not specify more stringent drift loss requirements to reduce fogging. Energy and money would be expended for absolutely no benefit. The only real justification for reduction of drift loss is based on the nature of the area where the drift falls and its affects on the mechanical equipment of the cooling tower. If the dissolved solids in the drift are being deposited on sensitive areas then it is important to keep drift loss as low as practicable. If a cooling tower is of induced draft design, excessive drift will certainly erode the mechanical equipment. Therefore, one should be certain as to the desired effect to be accomplished prior to making very restrictive and costly requirements in reduction of drift loss. Evaporation The most common misconception concerning evaporation is that competing tower manufacturers and designs can accomplish widespread differences in the amount of water being evaporated in a cooling tower. The truth of the matter is that the large majority of heat exchange in a cooling tower is accomplished by the evaporation of a portion of the circulating water. This removes heat from the remainder of the circulating water by removing the latent heat of vaporization necessary to accomplish this phase change. Inasmuch as evaporating water is the basic function of the cooling tower, one is mislead to believe that a cooling tower can operate successfully without the proper evaporation. There are a few design features that can have a minor effect on the evaporation rate. For example, cooling towers with identical duties, but operating at different L/G ratios, will have slightly different evaporation rates. The normal ʺrule of thumbʺ for determination of evaporation is 0.1 % 1 o F the circulating water flow for every 1.0 F range. Jalal Engineering, [email protected] Page 5 of 6
6 The ʺMore Waterʺ Syndrome The ʺmore waterʺ fallacy is important and worthy of inclusion here. This situation commonly occurs in an operating cooling tower when, in the heat of summer, the temperature begins to rise on, say, a shelland tube exchanger in a refinery unit. Operation calls for more water in order to hold the temperature of the cooled process stream. Additional water is pumped over the tower, and this results in a decrease in the towerʹs performance capabilities, thereby raising the CWT. The raising of the CWT going to the exchanger in some cases more than offsets the effect of increased heat transfer coefficient in the exchanger due to increased water flow. Therefore, the situation becomes worse and again ʺmore waterʺ is demanded. It takes a well trained operator to recognize the fact that, when trouble is occurring temperature wise, less water rather than ʺmore waterʺ is often necessary to bring the temperatures down. Of course, situations can exist where the increase in velocity through an exchanger occasions a better overall heat transfer, even though the temperature of the water through the unit is rising. This trade off must be looked at very carefully rather than just assuming that more water is the cure all to summertime operating cooling problems. Power Considerations Often the effect of fan power on cooling tower thermal capability is misunderstood. For instance, it is quite often thought that a 10% increase in power by increasing fan pitch will accomplish a 10% increase in the capacity of the cooling tower. A quick check of the fan laws will reveal that this is far from the truth. If we are near design fan power and are operating at an essentially constant fan efficiency, air flow rate (and hence, cooling tower capability), will increase in proportion to the cube root of the power increase. For example, if the horsepower were increased to 110% of its original value, the air flow and thermal performance capability of the tower would only be increased approximately 3.2%. Conclusion This article demonstrates rather pointedly that cooling tower performance and operation are not so straightforward as they many times are thought to be. These misconceptions and inadequate knowledge of cooling tower design can cost you money in all phases of dealing with cooling towers. Purchase of a new tower will cost more in the long run if plant operations do not run efficiently due to an ill designed cooling tower. Tower operation, in terms of energy cost, will be more expensive if utilization of fan power is misunderstood. Upgrading an existing tower may turn out to be futile because tower performance was viewed in terms of range. It is necessary to have a working knowledge of the performance of cooling towers, without misconception, in order to purchase and operate them to the best advantage for maximum production at minimum cost. Jalal Engineering, [email protected] Page 6 of 6
AIR CONDITIONING TECHNOLOGY
AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air
THE PSYCHROMETRIC CHART AND ITS USE
Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
How do I measure the amount of water vapor in the air?
How do I measure the amount of water vapor in the air? Materials 2 Centigrade Thermometers Gauze Fan Rubber Band Tape Overview Water vapor is a very important gas in the atmosphere and can influence many
THE HUMIDITY/MOISTURE HANDBOOK
THE HUMIDITY/MOISTURE HANDBOOK Table of Contents Introduction... 3 Relative Humidity... 3 Partial Pressure... 4 Saturation Pressure (Ps)... 5 Other Absolute Moisture Scales... 8 % Moisture by Volume (%M
UNDERSTANDING REFRIGERANT TABLES
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
Humidity, Condensation, Clouds, and Fog. Water in the Atmosphere
Humidity, Condensation, Clouds, and Fog or Water in the Atmosphere The Hydrologic Cycle Where the Water Exists on Earth Evaporation From the Oceans and Land The Source of Water Vapor for the Atmosphere
Centrifugal Fans and Pumps are sized to meet the maximum
Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
This chapter discusses: 1. Definitions and causes of stable and unstable atmospheric air. 2. Processes that cause instability and cloud development
Stability & Cloud Development This chapter discusses: 1. Definitions and causes of stable and unstable atmospheric air 2. Processes that cause instability and cloud development Stability & Movement A rock,
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation
ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation Ohio Medical Corporation 1111 Lakeside Drive Gurnee, IL 60031 Phone: (800) 448-0770 Fax: (847) 855-6304 [email protected]
Because here you can see a simple an elementary direct evaporative cooling system this is called as a single stage system you can see from the
Refrigeration and Air Conditioning Prof M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 38 Air Conditioning Systems Welcome back in the last lecture
Temperature and Humidity
Temperature and Humidity Overview Water vapor is a very important gas in the atmosphere and can influence many things like condensation and the formation of clouds and rain, as well as how hot or cold
Air Water Vapor Mixtures: Psychrometrics. Leon R. Glicksman c 1996, 2010
Air Water Vapor Mixtures: Psychrometrics Leon R. Glicksman c 1996, 2010 Introduction To establish proper comfort conditions within a building space, the designer must consider the air temperature and the
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
By: Jaap Hoogland SPX Cooling Technologies GmbH. CW /Jaap Hoogland/ 16-10-2007 Seawater Cooling Tower Circuits 1
By: Jaap Hoogland SPX Cooling Technologies GmbH CW /Jaap Hoogland/ 16-10-2007 Seawater Cooling Tower Circuits 1 SUMMARY Seawater recooling systems Technique required for seawater cooling towers Heat calculation
Recover Heat from Boiler Blowdown Water
Prepared for California Energy Commission (CEC) Prepared By: Southern California Gas Company (A Sempra Energy Utility) E3M Inc. May 2012 i Disclaimer The CEC and its contractor, Southern California Gas
Refrigeration Manual. Part 3 - The Refrigeration Load
Refrigeration Manual Part 3 - The Refrigeration Load FOREWORD The practice of refrigeration undoubtedly goes back as far as the history of mankind, but for thousands of years the only cooling mediums were
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
1. The Kinetic Theory of Matter states that all matter is composed of atoms and molecules that are in a constant state of constant random motion
Physical Science Period: Name: ANSWER KEY Date: Practice Test for Unit 3: Ch. 3, and some of 15 and 16: Kinetic Theory of Matter, States of matter, and and thermodynamics, and gas laws. 1. The Kinetic
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Evaporative Cooling System for Aquacultural Production 1
Fact Sheet EES-100 March 1993 Evaporative Cooling System for Aquacultural Production 1 C. D. Baird, R. A. Bucklin, C. A. Watson and F. A. Chapman 2 INTRODUCTION Florida aquaculture sales totaled $54 million
VAV Laboratory Room Airflow The Lowdown on Turndown
Technology Report March, 2003 VAV Laboratory The Lowdown on Turndown Turndown comparison of these two turndown ratios. Note the small actual airflow difference between them. control ranges are normally
COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers
COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.
Principles of Rice Drying How does rice dry?
Principles of Rice Drying James F. Thompson June 30, 1998 How does rice dry? Rice gains or loses moisture based on its moisture and the humidity of the air around it. If the humidity is low, high moisture
Specific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.
Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of
How To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX
Cooling Systems Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX Cooling Water Systems Water is used for cooling because of its capacity to remove and store heat and availability. Cooling water is used in
a comprehensive approach to the analysis of cooling tower performance
thermal SCIENCE a comprehensive approach to the analysis of cooling tower performance DONALD R. BAKER HOWARD A. SHRYOCK Introduction The generally accepted concept of cooling tower performance was developed
Partnerships Implementing Engineering Education Worcester Polytechnic Institute Worcester Public Schools
Partnerships Implementing Engineering Education Worcester Polytechnic Institute Worcester Public Schools Supported by: National Science Foundation Weather: 4.H.3 Weather and Classical Instruments Grade
Humidity the story for teachers
Humidity the story for teachers As we have learned earlier, water may exist as a gas (water vapour). Even in the driest desert there is some water vapour in the air. Water vapour is the most important
HVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla
Helsinki University of Technology Department of Mechanical Engineering Energy Engineering and Environmental Protection Publications Steam Boiler Technology ebook Espoo 2002 Boiler Calculations Sebastian
Wet Bulb Temperature and Its Impact on Building Performance
Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?
Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside.
Lab Exercise: Dew Point and Relative Humidity Purpose: To determine the dew and point and relative humidity in the classroom, and find the current relative humidity outside. Relative humidity is a measure
Chapter 18 Temperature, Heat, and the First Law of Thermodynamics. Problems: 8, 11, 13, 17, 21, 27, 29, 37, 39, 41, 47, 51, 57
Chapter 18 Temperature, Heat, and the First Law of Thermodynamics Problems: 8, 11, 13, 17, 21, 27, 29, 37, 39, 41, 47, 51, 57 Thermodynamics study and application of thermal energy temperature quantity
UNIT 2 REFRIGERATION CYCLE
UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression
High Altitude HVAC. Silvertip Integrated Engineering Consultants [email protected] www.silvertipconsultants.com
Presentation to: Rocky Mountain ASHRAE 2013 Tech Conference April 19, 2013 High Altitude HVAC Design Considerations by: Michael D. Haughey, PE, HBDP, CEM, LEED TM AP 2013 Silvertip Integrated Engineering
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas
Increasing Natural Gas Boiler Efficiency by Capturing Waste Energy from Flue Gas Mark Schiffhauer, ATSI Engineering Services Cameron Veitch, Combustion and Energy Systems Scott Larsen, New York State Energy
Vogt Valves The Connection Bulletin for Forged Steel Flow Control Valves CB 15
The Connection Bulletin for Forged Steel Flow Control Valves CB 15 Flow Control Division Forged Steel Flow Control Valves GRADUATED DIAL AND INDICATOR FULLY GUIDED V-PORT THROTTLING DISC AND INTEGRAL HARD
Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Relative Humidities RH% 49.4. 0.
Psychrometrics Psychrometric Chart Relative Humidities RH% 49.4 100% 80% 0.030 Enthalpies 70% H btu/lb 46.5 0.028 85 Not to Scale 0.026 Humidity Numbers and Values 43.7 60% Ratios are approximate 0.024
Name: OBJECTIVES Correctly define: WEATHER BASICS: STATION MODELS: MOISTURE: PRESSURE AND WIND: Weather
Name: OBJECTIVES Correctly define: air mass, air pressure, anemometer, barometer, cyclone, dew point, front, isobar, isotherm, meteorology, precipitation, psychrometer, relative humidity, saturated, transpiration
Greenhouse Glazing Effects on Heat Transfer for Winter Heating and Summer Cooling
Greenhouse Glazing Effects on Heat Transfer for Winter Heating and Summer Cooling David R. Mears, Ph.D. Bioresource Engineering Department of Plant Biology and Pathology Rutgers University 20 Ag Extension
Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2
Instruction Manual Dew Point Tester The CVS Dew Point Tester is a chilled mirror apparatus, which operates by attaining the conditions necessary by the definition of dew point. When a gas is cooled out
ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE
ES 106 Laboratory # 6 MOISTURE IN THE ATMOSPHERE 6-1 Introduction By observing, recording, and analyzing weather conditions, meteorologists attempt to define the principles that control the complex interactions
How To Understand And Understand Psychrometrics
Air Conditioning Psychrometrics Course No: M05-005 Credit: 5 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774 [email protected]
Waste Heat Recovery through Air Conditioning System
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn : 2278-800X, www.ijerd.com Volume 5, Issue 3 (December 2012), PP. 87-92 Waste Heat Recovery through Air Conditioning
Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle
INL/CON-05-00740 PREPRINT Evaluation Of Hybrid Air- Cooled Flash/Binary Power Cycle Geothermal Resources Council Annual Meeting Greg Mines October 2005 This is a preprint of a paper intended for publication
An Approach for Water Cost of Cooling Water System in Oil Refinery
CHEMICAL ENGINEERING TRANSACTIONS Volume 21, 2010 Editor J. J. Klemeš, H. L. Lam, P. S. Varbanov Copyright 2010, AIDIC Servizi S.r.l., ISBN 978-88-95608-05-1 ISSN 1974-9791 DOI: 10.3303/CET1021018 103
CHEMICAL ENGINEERING LABORATORY 3, CE 427 DRYING OF SOLIDS
Revised 10/00 CHEMICAL ENGINEERING LABORATORY 3, CE 427 DRYING OF SOLIDS Introduction Material covered here pertains to Chapter 24 of M,S&H. Please read relevant sections of this chapter. Drying involves
UNIT VII--ATMOSPHERIC STABILITY AND INSTABILITY
UNIT VII--ATMOSPHERIC STABILITY AND INSTABILITY The stability or instability of the atmosphere is a concern to firefighters. This unit discusses how changes in the atmosphere affect fire behavior, and
Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409
Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam
Fundamentals of Climate Change (PCC 587): Water Vapor
Fundamentals of Climate Change (PCC 587): Water Vapor DARGAN M. W. FRIERSON UNIVERSITY OF WASHINGTON, DEPARTMENT OF ATMOSPHERIC SCIENCES DAY 2: 9/30/13 Water Water is a remarkable molecule Water vapor
Greenhouse Cooling. Why is Cooling Needed?
Greenhouse Cooling Why is Cooling Needed? Solar radiation is the heat input for the earth can radiate as much as 277 Btu/ft 2 /hr onto the surface of the earth on summer s day in coastal and industrial
5.2. Vaporizers - Types and Usage
5.2. Vaporizers - Types and Usage 5.2.1. General Vaporizers are constructed in numerous designs and operated in many modes. Depending upon the service application the design, construction, inspection,
SECOND GRADE 1 WEEK LESSON PLANS AND ACTIVITIES
SECOND GRADE 1 WEEK LESSON PLANS AND ACTIVITIES WATER CYCLE OVERVIEW OF SECOND GRADE WATER WEEK 1. PRE: Exploring the properties of water. LAB: Experimenting with different soap mixtures. POST: Analyzing
UNIT 6a TEST REVIEW. 1. A weather instrument is shown below.
UNIT 6a TEST REVIEW 1. A weather instrument is shown below. Which weather variable is measured by this instrument? 1) wind speed 3) cloud cover 2) precipitation 4) air pressure 2. Which weather station
Akton Psychrometric Chart Tutorial and Examples
Akton Psychrometric Chart Tutorial and Examples December 1999 Akton Associates Inc. 3600 Clayton Road, Suite D Concord, California 94521 (925) 688-0333 http://www.aktonassoc.com Copyright 1999 Akton Associates
COOLING TOWERS. This section briefly describes the main features of cooling towers.
COOLING TOWERS 1. INTRODUCTION...1 2. TYPES OF COOLING TOWERS...4 3. ASSESSMENT OF COOLING TOWERS...7 4. ENERGY EFFICIENCY OPPORTUNITIES...9 5. OPTION CHECKLIST...14 6. WORKSHEETS...15 7. REFERENCES...17
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
C. starting positive displacement pumps with the discharge valve closed.
KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the
Atmospheric Stability & Cloud Development
Atmospheric Stability & Cloud Development Stable situations a small change is resisted and the system returns to its previous state Neutral situations a small change is neither resisted nor enlarged Unstable
Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"
Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A" Takahiro OUE *1, Kazuto OKADA *1 *1 Refrigeration System & Energy Dept., Compressor Div., Machinery Business Kobe Steel has developed an air-sourced
We will study the temperature-pressure diagram of nitrogen, in particular the triple point.
K4. Triple Point of Nitrogen I. OBJECTIVE OF THE EXPERIMENT We will study the temperature-pressure diagram of nitrogen, in particular the triple point. II. BAKGROUND THOERY States of matter Matter is made
Ground Source Heat Pumps The Fundamentals. Southington, Connecticut 860 628 4622 John F. Sima III P.E.
Ground Source Heat Pumps The Fundamentals Southington, Connecticut 860 628 4622 John F. Sima III P.E. Winter/Spring 2010 Ground Source Heat Pumps The Fundamentals TOPICS: Heat Pump Terminology Basic Physics
Temperature affects water in the air.
KEY CONCEPT Most clouds form as air rises and cools. BEFORE, you learned Water vapor circulates from Earth to the atmosphere Warm air is less dense than cool air and tends to rise NOW, you will learn How
SAMPLE CHAPTERS UNESCO EOLSS
STEAM TURBINE OPERATIONAL ASPECTS R.A. Chaplin Department of Chemical Engineering, University of New Brunswick, Canada Keywords: Steam Turbines, Operation, Supersaturation, Moisture, Back Pressure, Governing
OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa
OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a
A heat pipe heat recovery heat exchanger for a mini-drier
A heat pipe heat recovery heat exchanger for a mini-drier A Meyer Department of Mechanical Engineering, University of Stellenbosch, Stellenbosch R T Dobson Department of Mechanical Engineering, University
7613-1 - Page 1. Weather Unit Exam Pre-Test Questions
Weather Unit Exam Pre-Test Questions 7613-1 - Page 1 Name: 1) Equal quantities of water are placed in four uncovered containers with different shapes and left on a table at room temperature. From which
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
HVAC Made Easy - Overview of Psychrometrics
PDHonline Course M135 (4 PDH) HVAC Made Easy - Overview of Psychrometrics Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088
A Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
FUNDAMENTALS OF ENGINEERING THERMODYNAMICS
FUNDAMENTALS OF ENGINEERING THERMODYNAMICS System: Quantity of matter (constant mass) or region in space (constant volume) chosen for study. Closed system: Can exchange energy but not mass; mass is constant
6 th Grade Science Assessment: Weather & Water Select the best answer on the answer sheet. Please do not make any marks on this test.
Select the be answer on the answer sheet. Please do not make any marks on this te. 1. Weather is be defined as the A. changes that occur in cloud formations from day to day. B. amount of rain or snow that
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
Chapter 14. At temperatures below the critical temperature, the gas GAS VAPOR MIXTURES AND AIR-CONDITIONING. Objectives
Chapter 14 GAS VAPOR MIXTURES AND -CONDITIONING At temperatures below the critical temperature, the gas phase of a substance is frequently referred to as a vapor. The term vapor implies a gaseous state
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Vapor Chambers. Figure 1: Example of vapor chamber. Benefits of Using Vapor Chambers
Vapor Chambers A vapor chamber is a high-end thermal management device that can evenly dissipate heat from a small source to a large platform of area (see Figure 1). It has a similar construction and mechanism
Tim Facius Baltimore Aircoil
Presented By: Tim Facius Baltimore Aircoil Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for the benefit of
Desuperheater Online Program Sizing Guidance
Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without
Energy savings in commercial refrigeration. Low pressure control
Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary
How To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
To measure the solubility of a salt in water over a range of temperatures and to construct a graph representing the salt solubility.
THE SOLUBILITY OF A SALT IN WATER AT VARIOUS TEMPERATURES 2007, 1995, 1991 by David A. Katz. All rights reserved. Permission for academic use provided the original copyright is included. OBJECTIVE To measure
Stability and Cloud Development. Stability in the atmosphere AT350. Why did this cloud form, whereas the sky was clear 4 hours ago?
Stability and Cloud Development AT350 Why did this cloud form, whereas the sky was clear 4 hours ago? Stability in the atmosphere An Initial Perturbation Stable Unstable Neutral If an air parcel is displaced
Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans
Energy Savings With Adjustable Frequency Drives for Centrifugal Fans 2 Centrifugal Fans Centrifugal Fan Fans are designed to be capable of meeting the maximum demand of the system in which they are installed.
7. COOLING TOWER. 7.1 Introduction
7. COOLING TOWER Syllabus Cooling Tower: Types and performance evaluation, Efficient system operation, Flow control strategies and energy saving opportunities, Assessment of cooling towers 7.1 Introduction
STEAM TURBINE 1 CONTENT. Chapter Description Page. V. Steam Process in Steam Turbine 6. VI. Exhaust Steam Conditions, Extraction and Admission 7
STEAM TURBINE 1 CONTENT Chapter Description Page I Purpose 2 II Steam Turbine Types 2 2.1. Impulse Turbine 2 2.2. Reaction Turbine 2 III Steam Turbine Operating Range 2 3.1. Curtis 2 3.2. Rateau 2 3.3.
CGC1D1: Interactions in the Physical Environment Factors that Affect Climate
Name: Date: Day/Period: CGC1D1: Interactions in the Physical Environment Factors that Affect Climate Chapter 12 in the Making Connections textbook deals with Climate Connections. Use pages 127-144 to fill
The Ideal Gas Law. Gas Constant. Applications of the Gas law. P = ρ R T. Lecture 2: Atmospheric Thermodynamics
Lecture 2: Atmospheric Thermodynamics Ideal Gas Law (Equation of State) Hydrostatic Balance Heat and Temperature Conduction, Convection, Radiation Latent Heating Adiabatic Process Lapse Rate and Stability
Natural Air Drying Corn Paul E. Sumner University of Georgia Biological and Agricultural Engineering Department
Natural Air Drying Corn Paul E. Sumner University of Georgia Biological and Agricultural Engineering Department Many small farmers prefer to dry crops using unheated or natural air drying in bins in layers
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem