Safety Method Statement Roofing
|
|
|
- Herbert Simmons
- 9 years ago
- Views:
Transcription
1 Description of Work and Location ROOF TILING A. Generally All materials shall be of a standard not lower than the requirements of the latest appropriate British Standard. The Contractor is advised that numerous types of tiled roofs exist throughout the Contract Area and that provision must be made for obtaining and stocking the requisite products and accessories, or compatible products, should the existing type be unobtainable this shall apply to all relevant roof types. Where compatible tiles/slates are, by necessity, used then they shall at all times comply with the relevant British Standard. B. AII tiles, slates and accessories laid or fitted shall be of a colour to match the existing and fixed in accordance with the manufacturer's instructions and current Codes of Practice. If the Codes of Practice have been altered since the original tiles or slates were fixed the Contract Administrator must be informed and the current Code of Practice conformed to. The whole of the roof tiling and slating shall be carried out in accordance with the recommendations of BS 5534: Part 1: 1997 and in accordance with the manufacturer's instructions and recommendations. C. The Contractor is to note that the Items and Prices in the Schedule of Rates together with any percentage adjustment thereto are deemed to allow for the reinstatement of any missing or defective battens and roofing felt when undertaking repairs. D.Concrete Roof Tiles and Fittings All concrete tiles and fittings are to comply with BS EN 490 and BS EN 491 and be equal to samples deposited with and approved by the Contract Administrator. E. Plain Clay Tiles Plain clay tiles are to comply with BS 402 and BS EN 538. F. Natural Slates and Fittings Natural slates and fittings are to comply with BS 680: Part 2: 1971 and shall be equal to samples deposited with and approved by the Contract Administrator. G. Fibre Cement Roof Slates and Fittings The roof slates and fittings for pitched roofs and tile hanging shall be Eternit slate or similar approved fixed in accordance with the manufacturer's instructions. Ridge tiles are to be 130 degrees internally socketed ridge tiles. H. Dry Ridge/Verge Dry ridge and dry verge works shall be installed to the approved manufacturer's instructions and will be compatible with existing dry ridge and dry verge installation and existing roof coverings. A. Underfelt The roof tile underfelt is to be reinforced bituminous felt to BS 747 Type IF weighing not less than 11 Kg/sqm, lapped 150mm at horizontal and vertical joints over adequately supporting members. The underfelt for copper, lead and zinc roofing shall be brown sheathing felt to BS 747 Type 4A (ii) (No. 1 inodorous). B. Battens The tile battens to be good quality deal, reasonably free from knots, clean and with no waney
2 edges in accordance with BS EN and impregnated with "Celcure", "Tanalith", "Treatim", or "Protim" wood preservative or equivalent approved before delivery to site, as specified under Woodwork. Battens to be fixed with staggered joints and square butt jointed.c. Wood Rolls Wood rolls for copper, zinc or aluminium roofing shall be wrot seasoned timber to the tapered profile shown in CP 143: Parts 12: 1970 and 15: Common rolls approximately 45 x40mm overall unless otherwise shown. Wood rolls for lead roofing shall be wrot seasoned timber to the smooth rounded profile shown in BS Common rolls approximately 45 x 45mm with 25mm wide flat base unless otherwise shown. D. Mortar The mortar for bedding and pointing to be cement mortar (1:3) as described in "Brickwork and Blockwork", but slightly tinted in colour to approval and specially mixed for the purpose. E. Nails The nails for underlay and battens shall comply with BS 1202: Part 1: 1974 for galvanised steel clout nails. Nails for battens shall be sized to give a secure fixing without splitting the batten. The nails for slates and tiles shall be aluminium alloy to BS 1202: Part 3: 1974, copper to BS 1202: Part 2: 1974, silicon bronze to BS 5534 or as recommended by the manufacturer and approved by the Contract Administrator. The nails for lead roofing shall be copper in accordance with BS 1202: Part 2: 1974, Table 2 jagged or ring shank not less than 20mm long with large flat heads. Where roofing slates or tiles are described as fixing with clips, the clips shall be of lead or copper, approx. 300mm long x 20mm wide and shall be fixed to the roof batten beneath the slate or tile to be fixed, bent up and over the bottom edge of the slate or tile. Clips for slates shall be aluminium alloy to BS 5534 or stainless steel to BS G. Fibre Cement Corrugated Roofing Sheets Shall be obtained from an approved manufacturer, be of a profile to match existing sheets and conform to BS 5427, BS 143 and BS H. Galvanised Steel Corrugated Roofing Sheets The sheets shall be hot dipped to BS 3083, Table 1, Coating type 350, 0.7mm thick with corrugations at 76.2mm pitch. A. Translucent Corrugated Roofing Sheets The sheets shall be glass fibre reinforced plastics to BS 4154 with fire exposure performance Category P60 to BS 476: Part 3: B. Steel Hook Bolts and Nuts The bolts for fixing corrugated sheets are to comply with BS 1494: Part 1 : 1965, cadmium or zinc coated and with plastic sleeves and washers. Bolt profile and size to suit sheets and roof members and the sheet manufacturer's recommendations. C. Steel Roofing Screws Roofing screws for corrugated sheets shall be galvanised and are to conform to BS 1494: Part 1 : 1965 and be complete with plastic washers. Length of nail shall suit the application and roof sheet manufacturer's recommendations.
3 D. Plywood Decking for Flat Roofs The plywood sheets shall be exterior quality bonding grade WBP conforming with BS E. Woodwool Slab Decking for Flat Roofs The woodwool slabs shall conform to BS 1105, Type B and where appropriate be reinforced with pressed steel channels all to the satisfaction of the Contract Administrator. Fixings for the slabs shall be galvanised steel large flat headed nails of a length to suit the application or steel clips galvanised to BS 729 or such other types of fixing as may be recommended by the manufacturer of the slabs. F. Wood Chipboard Decking for Flat Roofs Chipboard shall conform to BS 5669: Part 2: 1989 and be of an appropriate moisture resistant grade suitable for the purpose and be fixed with galvanised nails or screws conforming with BS 1202 and BS 1210 respectively each being of a size and gauge to suit the application. G.lnsulation Insulation shall comply with BS 5803: Part 1: 1985 and be obtained from an approved manufacturer. H. Lead The lead roof coverings, flashings, soakers, rainwater chutes, valley gutter linings, hips, ridges and the like are to be of best English milled lead in accordance with the Lead Development Association recommendations and in accordance with BS Tacks minimum 40mm wide of the same lead substance to be provided at not more than 1 metre centres to flashings. J. Self Adhesive Flashings Self adhesive flashings may only be used with the prior agreement of the Contract Administrator. Where self adhesive flashings are permitted they shall be fixed over existing flashings, filietsand the like in strict accordance with manufacturer's instructions, including applying recommended primer to ensure complete adhesion. A. Asphalt Roofing Asphalt roofing is to comply with BS 6925 Type R988, the isolating membrane shall be black sheathing felt to BS 747, Type 4A(i), bitumen based. Clean natural coarse sand passing a 600mm micron BS 470 test sieve is to be used as rubbing sand. Chippings shall be hard light coloured non absorbent natural stone graded 6 to 10mm. Solar reflective paint shall be used in accordance with manufacturer's recommendations. Asphalt roofing subject to traffic shall be to BS 6925 Type R988 undercoat with BS 1447, finishing coat. Isolating membrane for roofing subject to traffic shall be glass fibre tissue as recommended by the asphalt specialist. B. Building Paper Building paper used in roofing shall comply with BS 1521, Class B for temporary use and Class A of appropriate grade for permanent installation. C. Liquid Applied Waterproofing Liquid applied waterproofing shall be from an approved manufacturer and be used strictly in
4 accordance with the manufacturer's directions. D.Bitumen Felts for Felt Roofing Fine granule surfaced bitumen felt shall comply with BS 747, Type 2B, 3B and 5B, mineral surfaced bitumen felt shall comply with BS 747, Type 2E, 3E and 5E. E. High Performance Felt Roofing High performance felt roofing shall be from an approved manufacturer and applied strictly in accordance with the manufacturer's instructions to suit the relevant sub surface. F. High Performance 'Torch On" Felt Roofing High performance "torch on" felt roofing shall be prepared and applied strictly in accordance with the manufacturer's instructions to suit the relevant sub surface. G. Bitumen Primer Primer for felt roofing shall be cut back bitumen with a maximum volatile solvent 60% by weight. Viscosity to be Redwood No. 2 at 21 deg. C 25 sec maximum. A. Bitumen Compounds Bonding compound for felt roofing shall be oxidised bitumen having a penetration of 20/30 at 25 deg. C and a softening point & B) of 80/100 deg. C. Dressing compound forfeit roofing shall be cut back bitumen to BS 3690: Part 1: 1989 Grade 50 sec at 40 deg. C. Cold compounds dressing for bonding solar reflective chipping may be permitted but only at the sole discretion of the Contract Administrator. The bitumen coating for lead, copper or zinc roofing shall be a black coating solution to BS WORKMANSHIP B. Roof Tiling The roof tiling to be laid generally in accordance with BS 5534: Part 1: 1997, BS 8000: Part 6: 1990 and in even courses to suit existing gauging and laps and be secured with the appropriate patent clips and or nails. Tiles shall be head nailed with two nails in every tile. Eaves shall be formed with double course of tiles. Verges shall be formed with tile and a half in alternate courses including any undercloak, or cut tiles if recommended by the manufacturer and pointed in cement mortar all to match existing. Exposed cut edges of tiles will not be permitted. C. Roof Slating Natural slate roofing shall be close jointed with horizontal and alternate vertical joints ranging through perfectly straight. Slates shall be head nailed with two nails to each slate every course. Slates to eaves, verges, ridges, hips, valleys and abutments shall be secured with two nails to each slate. Eaves shall be formed with double course of slates. Verges shall be formed with slates and slate and a half slates in alternate course including any undercloak and shall be bedded, jointed and pointed with mortar tinted to match colour of slates. Exposed cut edges of slates will not be permitted. Tile ridges and hips shall be of the type stated in the Schedule of Rates. Ridge and hip tiles shall be bedded, jointed and pointed with mortar tinted to match colour of tiles or slates. D. Fibre Cement Sheet Roofing Fibre cement sheet roofing shall be laid and fixed in accordance with BS 5247: Part 14: 1975,
5 Section 4, CPUS: Part 16: 1974 and as recommended by the manufacturer incorporating where appropriate end and side lap sealing strips. E.Galvanised Steel Lay galvanised corrugated sheeting in accordance with the general recommendations of CP 143: Part 10: 1973, Section 4 (Application) and generally as shown in Figures 1 to 3 inclusive of the Code. Allow slight movement between the structural frame and sheeting. Lap all sheets 150mm at ends and two corrugations at sides. A. Reinforced Plastics Where specified use reinforced corrugated plastic sheets in limited areas in association with roof sheeting of another material.lap at ends and sides as for the main roofing material and seal with approved woven fibre sealing strip. B. Fixing Sheets Secure sheets to steel with galvanised steel hook bolts and nuts, and to timber with galvanised steel roofing screws. Do not drill steelwork. C. Holing Sheets Drill sheet fixing holes through the crown of the corrugations 1.5mm larger in diameter than that of the bolt or screw shank. D. Safety Precautions Make arrangements to prevent unauthorised persons having access to the area below the roof whilst corrugated sheet roofing is under construction and do not allow any person to go on to roofing without using crawling boards. E. Insulation Insulation quilts shall be butt jointed and laid up to wall plates leaving sufficient space to ensure adequate ventilation of the roof space is maintained. Quilt to be laid under electrical cables and over horizontal pipes wherever possible. Quilt should not be laid under water storage tanks. Quilts to hatches should be bagged in polythene and securely fixed to hatch. F.General All debris resulting from roof works shall be cleared from all gutters. G. Leadwork Sheet lead shall be undertaken by skilled leadworkers and laid in accordance with Lead Development Association recommendations and in accordance with BS Solder shall not be used without the authority of the Contract Administrator. Close and open nailing shall be undertaken with copper nails at 25mm and 75mm centres respectively. Lengths of lead pieces used in leadwork shall not exceed 3.00m in length or 2.20m2 in area. All laps to finishing s shall not be less than 100mm. H. Lead Flashings Lead for flashings shall be milled sheet lead complying with BS and shall be in accordance with the classification recommendation in BS Lead flashings shall be dressed to the appropriate profiles without reducing the thickness of the lead sheet. The top edges of all cover flashings shall be turned 25mm into grooves chased or cut into brick, blockwork or other cladding material, securely wedged and pointed with cement mortar (1:3) in brick, block, masonry and concrete and in other cladding where appropriate.
6 A. Asphalt Roofing Asphalt shall be laid generally in accordance with BS 8218 and the recommendations and publications of the Mastic Asphalt Council and Employers Federation. Underlay shall be laid loose and with 50mm laps. Asphalt shall be laid in two coats with 150mm laps and shall be properly bonded to the edges of existing sound asphalt and unless otherwise directed all existing planes shall be maintained. Fillets 50mm on face shall be provided at all internal angles. The asphalt surface finish shall unless otherwise directed match the existing surface. B. Felt Roofing The felt roofing shall unless specified or directed otherwise comply with BS If on removing any defective felt the Contractor discovers that the base is defective or unsuitable in any way to receive the new felt and that repair of the base is outside the Contractor's remit featured on the Order, the Contractor shall immediately seek instruction from the Contract Administrator. When the Contractor has satisfied himself that the base is sound and generally complies with BS 8217 Clause 6, he can commence the repair works. Felts should be laid in the direction of the roof gradient with 75mm side and 100mm end laps, and breaking joints between layers. All concrete and screed base surfaces should receive a priming coat well brushed in and if the priority or period as the Order permits a period of 24 hours should be allowed to elapse before undertaking the felt laying. The first layer of felt should be partially or fully bonded to the base as directed, with bonding compound heated in thermostatically controlled kettles, to a temperature not exceeding 215 deg. Celsius, but sufficient to provide a 200 deg. Celsius laying temperature. A Partial Bonding System should be effected by spot, strip or frame bonding the first felt layer with hot bonding compound. The perimeter of the roof should be fully bonded fora width of 450mm, leaving 150mm wide ventilation channels at appropriate centres. A Fully Bonded System should be effected by applying a continuous even coating of hot bonding compound to the base at the rate of 1.5kg/m2 to which should be applied the first layer of felt to provide a complete bond excluding all air trapped air. Subsequent felt layers should be effectively bonded to match underlayer excluding all trapped air. Should any air bubbles become apparent in the work undertaken, the felt shall be cut back by the Contractor to the satisfaction of the Contract Administrator and renewed entirely at the Contractor's expense. C. Torch on Felt Roofing Torch on felt roofing shall be laid in accordance with the manufacturer's instructions. Ensure existing roof is clean and dry, cut out and patch blisters, nicks etc., and if necessary prime surface and allow to dry. Lay sheeting with 75mm side, 100mm end laps and apply flame to lower surface directing at the junction with the substrate so as to melt adhesive across roll width. Unroll felt onto part of molten bitumen and press down firmly. Seal laps with wide bladed scraper and seal plain finish (not mineral surface) by applying heat from above. Asphalt Coverings to Balconies and Walkways 1) Shall comply with BS 8218 and the Contractor shall ensure that the asphalt work isundertakenin accordance with BS 8218 and the publications of the Mastic Asphalt Council and Employers Federation 2) Asphalt for roofing subject to traffic shall comply with BS 6925 undercoat with BS1447, finishing coat 3) Isolating membrane for roofing subject to traffic shall be glass fibre tissue as recommended by the Contractor and to the approval of the Contract Administrator.
7
8 4) Metal lathing: Bitumen coated 'plain expanded' steel lathing to BS 1369, and minimum 26 swgandminimum 10 mm short way of mesh 5) Bonding primer: A high bond primer recommended by the asphalt specialist 6) Vapour barrier: BS 747 bitumen felt, BS 747, Type 3B bitumen felt glass fibre base 6) Primer for vapour barrier and general purposes: Cut back bitumen of suitable viscosity 7) Bitumen based bonding compound: For bonding vapour barriers and for general bonding purposes; oxidised bitumen suitable for applying hot 8) Rubbing sand: Clean natural coarse sand passing a 60 micron BS 470 test sieve 9) Chippings: Hard light coloured non absorbent natural stone graded 6 to 10 mm/nominal 14 mm single size 6 10) Dressing compound for chippings: Cut back bitumen to BS 3690 Grade 25 sec or a suitable cold applied bitumen based adhesive 11) Solar reflective paint: Shall be of a reputable proprietary brand and to the approval of the Contract Administrator 12) 190 Aluminium edging: A proprietary section profiled to suit asphalt manufactured from aluminium to BS 1474 HE9 TB or HE9 TF Supervision Pre-Site Preparation Work Site manager or competent forman to attend to site prior to works commencing to ensure safe and smooth operation. Work Operations Control of Operations Storage / Materials I Handling Materials only to be stored on site when necessary, otherwise transported as required. Inspection / Monitoring Works to be inspected during and on completion of works by site manager or competent foreman. Competence of Operatives All operatives are fully trained and qualified within the their trades. Apprentices may be used where required.
9 Accompanying Assessments Risk assesments to be compelted for all woks and associated works. Plant & Equipment All plant and equipment whether belonging to or hired, will be regularly tested. Safety of 3rd Parties All precautions will be taken in keeping with the safety of any third parties being the occupiers or general public. PPE Requirements All relevant PPe equipment will be used according to works involved. First Aid Requirements First aid kits supplied to all vehicles. Emergency Procedure Environmental Issues All waste and debris to be removed using registered waste carriers (skips) Contractor. Signed. Date.
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
Technology at its best. Benefits
Protecting what s under your roof from the elements is simplicity itself with Ruberoid Roofing Shingles. Roofing Shingles make ideal roofing; they are attractive, easy to install and are perfect for use
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035
Decra Plus Drawing no DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 Description Shown In Decra Brochure Most Commonly Used Detail t~êã=oççñ=b~îéë=aéí~áä=b~îéë=lîéêü~åö=táíü=fåëìä~íéç=c~ëåá~=~åç=pçññáí
Your guide to home maintenance. Flat Roofs
Your guide to home maintenance Flat Roofs Your guide to home maintenance is a series of information leaflets that gives you all the information you need to keep your home in tiptop condition. Flat Roofs
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
The formation of roof waterproofing details calls for
3.5 BUILT-UP ROOFING DETAIL DESIGN INTRODUCTION The formation of roof details calls for a combination of the skills of the designer and the roofer. There are many different approaches to detail design
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
CHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
CI SfB. (4-) Nn2. Onduline. Mini Profile. Onduline Garden Roof Range. Onduline Building Products Ltd
CI SfB (4-) Nn2 Onduline Mini Profile Onduline Garden Roof Range Onduline Building Products Ltd Onduline Garden Roof Range Onduline Mini Profile The new Onduline Mini Profile sheets have been designed
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
Including. Rubershield-Pro. Breather Membrane
Including RubershieldPro Breather Membrane 2 Ruberoid produces a wide range of underslating membranes, primarily to be installed below tiles, slates or metal roofing providing a secondary barrier against
Cupa Natural Slate Roofing design and fixing guide
Cupa Natural Slate Roofing design and fixing guide Cupa Natural Slate synonymous with quality Currently the Spanish slate industry is the undisputed market leader in natural slate production, with 90%
Rooflight INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS Rooflight These instructions should be used for: Installing Permanent Trickle Ventilation: Constructing & Waterproofing a Timber Upstand Curb: Installing & Waterproofing Proprietary
3 BUILT-UP ROOFING THE RUBEROID BLUE BOOK
3 BUILT-UP ROOFING 3.1 MATERIALS 3.2 APPLICATION TECHNIQUES 3.3 SURFACE PROTECTION 3.4 TYPICAL SPECIFICATIONS 3.5 BUILT-UP ROOFING DETAIL DESIGN 3.6 TYPICAL DETAILS 3.1 MATERIALS INTRODUCTION Bituminous
Bituminous Sheet Flat Roofs: Their repair and maintenance
Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and
Energy Company Obligation (ECO): Technical Monitoring Questions
Energy Company Obligation (ECO) Technical Monitoring Questions v1 30/05/2013 Energy Company Obligation (ECO): Technical Monitoring Questions Under ECO suppliers are required to instruct suitably qualified
Ubiflex. Non-lead flashing system
Ubiflex Non-lead flashing system Ubiflex non-lead flashing Ubiflex is a non-lead waterproof flashing material which can be used in most applications where lead is traditionally used to provide a weatherproof
Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.
CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,
Linea Weatherboard DIRECT FIX CONCRETE SLAB AND SOFFIT FIGURE 1
Top plate Stud Soffit lining 45mm min nog Fix scotia bead Building underlay/james Hardie rigid air barrier Soffit Detail Building underlay/james Hardie rigid air barrier Bottom plate 25mm wide cant strip.
How To Build A Gambrel Roof And A Gable End Roof
Dutch Gable or Gambrel Roof and The Scotch Valley The folowing pages are an extract from Carp 12 text TAFE NSW Construction and Transport Division 71 HIP and VALLEY ROOFING GAMBREL / DUTCH GABLE The effect
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
G VYCOR DECK PROTECTOR
G VYCOR DECK PROTECTOR Self-Adhered Flashing Contractor s Guide DECKS AND DETAIL AREAS For longer lasting decks, install Grace Vycor Deck Protector. FROM THE MAKERS OF G Ice & Water Shield What Self-Adhered
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
Multi-layer Insulation Blanket for Roofs
Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof
CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application 9 - 1 -
CONTENTS General conditions Material requirements 3 Terms 4 Estimating shingle requirements 4 Roof preparation 6 Shingle application 9 Shingle Shingle application application guide guide - - b a 3a 3b
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 16 BRIDGE DECK WATERPROOFING. 16.1 General...16-1. 16.2 Materials...16-1. 16.3 Equipment...
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 16 BRIDGE DECK WATERPROOFING TABLE OF CONTENTS 16.1 General...16-1 16.2 Materials...16-1 16.3 Equipment...16-1 16.4 Installation...16-2 16.4.1 Traffic Restrictions...16-2
After reading this lesson you will be able to: 12.3 IMPORTANCE OF ROOF 12.4 TYPES OF ROOF IN A HOUSE
86 :: Certificate in Construction Supervision (CIVIL) 12 ROOF 12.1 INTRODUCTION The structure provided to cover the house surface (floor) is known as roof. For different situation and requirement, it is
Site Inspection Report
Site Inspection Report Project Title: 1 Canada Square Location: 1 Canada Square, Canary Wharf, London Date of Inspection: 16/05/12 System / Products: TBA (suggested flame free application) Attendees: G
Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing
Substrate, structural panel, bonded waterproofing The universal substrate for tiles Perfect covering No matter whether you work with mosaics or large format tiles, an absolutely level substrate with straight
NRG 75 CRF NRG GREENBOARD WALL SYSTEM
NRG GREENBOARD WALL SYSTEM NRG Energy Efficient Building Systems is pleased to announce a revolution in lightweight cladding systems. NRG Building Systems is the first and only company to achieve CodeMark
GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS
GENERAL SPECIFICATION FOR CIVIL ENGINEERING WORKS SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS 13.1 13.2 2006 Edition SECTION 13 WORK FOR ELECTRICAL AND MECHANICAL INSTALLATIONS GENERAL
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
Triflex system: Triflex ProDetail. Solution type: Roof detail and repair waterproofing. Application: Overlay of existing substrate
CAD details Triflex ProDetail Triflex system: Triflex ProDetail Solution type: Roof detail and repair waterproofing Application: Overlay of existing substrate CAD details CAD S: CAD details Triflex ProDetail
STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2
STANDARD for Plumbing, Heating, Hot Water, Cold Water & Electrical work undertaken by owners within the building known as Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers
Western Red Cedar Shingles Product Guide
Western Red Cedar Shingles Product Guide Western Red Cedar Shingles & Shakes from John Brash are a truly renewable and sustainable roofing and cladding material; with one of the lowest carbon footprints
VM ZINC : standing seam Guidelines for specification and installation
VM ZINC : standing seam Guidelines for specification and installation Junglim Architecture - QUARTZ-ZINC Roofing and cladding system in VM ZINC Roofs from a 3 pitch and facades Freedom with shape and appearance
RB271 06/07 R807.1 RB272 06/07 R807.1. Public Hearing: Committee: AS AM D Assembly: ASF AMF DF. Proponent: Rick Davidson, City of Hopkins, MN
3. The use of asphalt shingles and other roof coverings has been successful over these composite insulation panels, so the extra details about vapor retarders, etc. can be eliminated. RB271 06/07 R807.1
Detached accessory structures that contain no conditioned floor area are exempt.
RESIDENTIAL ROOFING PERMITS: A roofing permit is required for roofing of residential dwellings and garages in accordance with Section R105 of the International Residential Code. Updated 11/2013 City of
FUNCTIONAL REQUIREMENTS
FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS 7.9 ROOF COVERINGS TRADITIONAL SLATE AND TILES Workmanship i. All workmanship must be within the tolerances defined in Chapter 1 of this Manual. ii. All
SHINGLE APPLICATION GUIDE
SHINGLE APPLICATION GUIDE CONTENTS 01. General conditions 01. Material requirements 02. Terms 07. Estimating shingle requirements 08. Roof preparation 10.Shingle application E version 2006 GENERAL CONDITIONS
RIW SHEETSEAL 226 BENEFITS APPLICATIONS APPLIED TO. CI/SfB TN6 L6813. November 2013. l Water and water vapour barrier. l Factory controlled thickness
CI/SfB TN6 L6813 November 2013 RIW SHEETSEAL 226 is a cold applied, high density polyethylene film, coated with a bitumen/rubber self adhesive layer with a removable reinforced silicone paper. Primer is
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
PRODUCT SHEET 1 MIDLAND LEAD MANUFACTURERS LTD S CAST LEAD SHEET
CI/SfB (49) Mh8 Midland Lead Manufacturers Ltd Kiln Way Woodville Swadlincote Derbyshire DE11 8ED Tel: 01283 224555 Fax: 01283 550284 e-mail: [email protected] website: www.midlandlead.co.uk Agrément
High Performance Solutions and Compounds for Roofing and Structural Waterproofing
High Performance Solutions and Compounds for Roofing and Structural Waterproofing IKO is a worldwide group of companies with extensive experience and specialist technical knowledge. IKO is a leader in
Steel-framed Walls. Insulation
Insulation A4/8 SF AW1192 Issue 4 Nov 2012 Steel-framed Walls Insulation guide Helps achieve a 6-star house energy rating Rigid and flexible Kingspan AIR-CELL solutions available Vapour barrier or vapourpermeable
CHAPTER 6 ASPHALT ROLL ROOFING
CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed
BUILD A CARPORT. 2 - Planning the carport. 3 - Designing the carport
BUILD A CARPORT You only need basic DIY and woodworking skills to build a carport. The most important part of the job is setting the supporting posts truly vertical - a job for which another pair of hands
BILL OF QUANTITY FOR THE WORK OF "REPAIRING OF CIVIL & PLUMBING WORKS INSIDE AND OUTSIDE OF THE WORKSHOP"
BILL OF QUANTITY FOR THE WORK OF "REPAIRING OF CIVIL & PLUMBING WORKS INSIDE AND OUTSIDE OF THE WORKSHOP" Sl. 1 DISMANTLING WORK 1.1 Stripping off worn out plaster (outside and inside) and raking out joints
H2 Opening Statement Asbestos
H2 Opening Statement Asbestos Every year there are thousands of asbestos related deaths. Asbestos fibres accumulate in the lungs, therefore several diseases can occur, among these are two main types of
Under Tile and Slate Undersheeting System
CI Sf (4-) Nn2 Under Tile and Slate Undersheeting System One system providing a weatherproof barrier, ventilation and insulation A RITISH OARD OF AGREMENT CERTIFICATE NO. 94 / 3055 2 Under Roofing System
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Services Enclosures and Protected Shafts - Maintaining Compartmentation
Introduction When a fire resisting element is used to provide fire compartmentation, every opening that allows services to pass through the element must be adequately protected by sealing, or fire stopping
WATERPROOFING OF WET ROOMS
WATERPROOFING OF WET ROOMS Waterproofing under tiles For longterm enjoyment of a wetroom area a complete and resistant waterproofing system is an important precondition. Most tiles are by themselves waterproof
System 5000 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY
CI/SfB Oct 12 (47) Ln Uniclass L524 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY Bailey Flame-free felt roofing Bailey
BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS.
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance
INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles
INSTALLATION RECOMMENDATIONS Outdoor Rubber Tiles Prior to Installation: The Outdoor Rubber Tiles and accessory transition pieces intended for this installation have been shipped to you via a freight carrier
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
FLASHMAN WINDOW AND DOOR FLASHING SYSTEM. Product. Scope. Appraisal No. 573 [2013]
FLASHMAN WINDOW AND DOOR FLASHING SYSTEM This Appraisal replaces BRANZ Appraisal No. 573 (2007). Amended 05 February 2016. BRANZ Appraisals Technical Assessments of products for building and construction.
Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5
Cl Sfb (27-9) Rn7 M2 December 2004 Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Fesco, Fesco S, Retrofit, Retrofit S, Fesco Fillet, PF,
USER GUIDE Easier, Safer, Betta! www.gripsetbetta.com WATERPROOFING
USER GUIDE Easier, Safer, Betta! www.gripsetbetta.com WATERPROOFING Welcome to Gripset Betta, Over the past 3 decades through the tireless commitment to improve and enhance the way buildings are waterproofed,
Roofers Guide to Underslating Membranes
Roofers Guide to Underslating Membranes IKO is a worldwide enterprise, with more than 3000 employees, and manufacturing plants in Canada, the United States, United Kingdom, Belgium, Holland, France and
ICOPAL POUR AND ROLL ROOF WATERPROOFING ICOPAL POWER ELASTOMERIC ROOF WATERPROOFING SYSTEM
Icopal Limited Barton Dock Road Stretford Manchester M32 0YL Tel: 0161-865 4444 Fax: 0161-864 8433 e-mail: [email protected] website: www.icopal.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL
Barewood Octagon and Elongated Windows Installation Instructions
Step-by-step instructions to a beautiful window. Measuring and Installation of your new window from Century Specialty Windows couldn't be easier with our step-by-step instructions. Quality, function and
16 2 10.3 Materials and Colors
16 2 10.3 Materials and Colors To create a harmonious and coherent image for each development, building designs shall pay close attention to choice of materials and colors. Building construction shall
PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS
Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING
DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP
DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP CONTENTS WHAT IS RISING DAMP STEP 1 SURVEY STEP 2 METER READINGS STEP 3 CONCLUSION STEP 4 PREPARATION FOR TREATMENT STEP 5 TYPE OF TREATMENT STEP 6
Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors
Improving the flood resistance of your home Advice sheet 6: Flood-resilient This sheet provides guidance on identifying different types of floor, assessing the routes floodwater may enter, and describes
How to Install Hardwood Flooring Over a Sub Floor
How to Install Hardwood Flooring Over a Sub Floor Installation Preparation Instructions Read the entire instructions before starting your project. 1) INSPECT EACH PLANK (see fig. a) Wood is a natural product
REDLAND DRY BONDING GUTTER. Installation Instructions for Redland Dry Bonding Gutter
REDLAND DRY BONDING GUTTER Installation Instructions for Redland Dry Bonding Gutter 1 Introduction 1.1 TECHNICAL DATA Dimensions: 3 m long x 210 mm wide Material: Glass-fibre/polyester composite. Pitch
Herringbone Pattern Flooring
Herringbone Pattern Flooring If it s not marked NOFMA, it s not certified. Handling, Storage, Installation and Tips Herringbone is generally manufactured from 3/4 x 2 ¼ or ¾ x 1-1/2 standard tongue & groove
Epdm Flat Roofing Systems
Epdm Flat Roofing Systems EDPM can be fully bonded, loose laid and ballasted or mechanically attached depending on the existing roof and its proposed usage. This applies to roofs to be refurbished and
Preformed Metal Roofing and Siding
Page -1-1. GENERAL 1.1. Description This specification along with the drawings covers the furnishing of all material, products, equipment, accessories, tools, services, transportation, labor and supervision
Extension. for. Pretend Customer 123 A Road HA7 9BP. at: 123 A Road HA7 9BP
for Pretend Customer at: Pretend Customer Site address: Monday, 23 November 2015 Dear Pretend Customer, Subject: Thank you for your valued enquiry and instructions to quote for the above project. We are
TR21. I n s u l a t i o n. Low Energy Low Carbon Buildings
I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Fourth Issue March 2011 TR21 INSULATION FOR FLAT ROOFS WATERPROOFED WITH PARTIALLY BONDED BUILT UP FELT AND MASTIC ASPHALT High performance rigid thermoset insulation
How to build a Pizza Oven in 4 days
How to build a Pizza Oven in 4 days Preparation day (slab) 1. Foundation 1500 deep x 1300 wide x 75mm deep Required 20 bags cement pre mix. If you already have a concrete base, you save this prep day DAY
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
ALUMASC ROOF WATERPROOFING MEMBRANES EUROROOF MASTERGOLD ROOF WATERPROOFING MEMBRANE
Alumasc Exterior Building Products Ltd White House Works Bold Road Sutton St Helens Merseyside WA9 4JG Tel: 01744 648 400 e-mail: [email protected] website: www.alumascroofing.co.uk APPROVAL
CI/SfB (Ff3) January 2011. Roofing design guide. Showing you the way. Redefining traditional products
CI/SfB (Ff3) January 2011 Roofing design guide Showing you the way Redefining traditional products Contents 2-3 General information Eaves detailing 4 Traditional eave 4 Hardrow slates eave Verge detailing
HOW-TO LAY HARDBOARD OR PLYWOOD FLOOR OVERLAY
HOW-TO HOW-TO LAY HARDBOARD OR PLYWOOD FLOOR OVERLAY Most floor coverings, if laid over uneven wooden floors, will wear unevenly and look unsightly. The answer is to cover the old boards with hardboard
INSTALLATION OF A BAY WINDOW
INSTALLATION OF A BAY WINDOW Installation of a Bay Window These instructions relate to the replacement of an existing bay window or replacement of a straight window with a new bay window, in an opening
Low Energy Low Carbon Buildings
I n s u l a t i o n CI/Sfb (27.9) Rn7 M2 Eighth Issue March 2011 TR27 LPC/FM INSULATION FOR FLAT ROOFS WATERPROOFED WITH FULLY ADHERED SINGLE PLY, PARTIALLY BONDED BUILT UP FELT, MASTIC ASPHALT AND COLD
K2 STONE NATURAL VENEER
INTRODUCTION WHAT IS K2 NATURAL THINSTONE VENEER? Natural K2 Stone veneer is real stone, cut 1 inch thick, making it light enough to be installed as a veneer. Sometimes referred to as thin veneer, thin
THE REDLAND GUIDE TO BS 5534
THE REDLAND GUIDE TO BS 5534 HELPING YOUR COMPANY TO GET ONE STEP AHEAD www.redland.co.uk Enforcement is via authorities such as the National House Building Council (NHBC) and Local Authority Building
Construction. Pre-Bagged Structural Waterproofing System. Product Description. Product Data. Tests. Form
Construction Product Data Sheet Edition 15/07/2013 Identification no: 01 07 05 04 001 0 000001 Sika 1 Pre-Bagged Structural Waterproofing System Product Description Pre-Bagged Structural Waterproofing
Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..
Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
Shingle Installation Guide
Shingle Installation Guide Getting Started Dedicated to improving the environment, NewTech manufactures roofing tiles that are composed of up to 90% recycled post-industrial plastic. The manufacture of
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-900* Reissued March, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION:
House building is changing fast NHBC unveils new Standards Chapters on curtain walling and cladding, and light steel framed walls and floors
W42_Stand_Extra_32 15/3/05 9:17 am Page 2 NHBC s technical newsletter April 2005 Issue 32 This edition includes: 2 House building is changing fast NHBC unveils new Standards Chapters on curtain walling
Shower and Floor Gullies Channel Drain and Tile Drain SECTION
Shower and Floor Gullies Channel Drain and Tile Drain SECTION 2 Shower and Floor Gullies, Channel Drain and Tile Drain 29 General Information Shower and Floor Gullies McAlpine has responded to market conditions
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
TECHNOELAST ROOF WATERPROOFING MEMBRANES TECHNOELAST APP EPP AND TECHNOELAST APP EKP ROOF WATERPROOFING MEMBRANES
TechnoNicol-Vyborg Ltd Ruberoidnaya St 7 Leningradskaya Region Vyborg 188804 Russia Tel: 007 81378 39090 Fax: 007 81378 39091 e-mail: [email protected] website: www.tn-europe.com APPROVAL INSPECTION TESTING