INDOOR MEDIUM VOLTAGE SWITCHGEAR UP TO 24kV
|
|
|
- Henry Wheeler
- 9 years ago
- Views:
Transcription
1 INDOOR MEDIUM VOLTAGE SWITCHGEAR UP TO 24kV TRANSMISSION & DISTRIBUTION MV SWITCHGEAR
2 SBV range of products Prior to 1980, Alstom s indoor switchgear business centered around J&P designed AG and Statter designed ACO ranges of bulk oil circuit breaker equipment. A requirement for modern technology switchgear was identified in the mid- 1970s and in 1976, equipment based on the B-Vac fixed pattern vacuum circuit breaker was introduced. This equipment however, was not well accepted on the local market and by 1978 had made no significant inroads into the modern technology business. In 1978 it was realised that a more cost-effective range of draw-out pattern switchgear would have to be introduced. At that time no suitable designs in GEC distribution switchgear were available and the decision that would lead to the development of Alstom s SBV range of switchgear was taken. SBV vacuum switchgear The SBV equipment was designed to meet virtually all known customer requirements. It includes single and double busbar units. Integral circuit (cable) earthing is offered as a option. Busbar earthing via the circuit breaker is also an available option. SBV equipment is designed for horizontal isolation and withdrawal, offering inter alia, the following advantages: Natural venting of the circuit breaker compartments is permitted and, subsequently, higher continuously rated currents. Pressure relief vents, fitted as a standard to all equipment, are accommodated at the top of the circuit breaker panels. The purpose of the relief vents is to open and relieve over-pressure that will result from the unlikely event of an internal arc fault Freestanding SBV 5 capacitor feeders. thus affording inherent operator safety. In the case of the duplicate busbar compartment, venting of the lower busbar compartment is effected at the longitudinal end of the switchboard. Vacuum interrupters are employed as a switching medium. The advantages of switching in vacuum are considerable. They include: Small interrupter gaps (as low as 6 mm for applications) result in low-energy mechanisms, ensuring long mechanism life. Low-peak arc voltages result in very low arc energy which in turn ensures a long electrical life for the vacuum interrupter and a no-maintenance device. In 1965 three outdoor, fixed-type vacuum circuit breakers, fitted with auto-reclose facilities, were installed on Great Britain s Eastern Electricity Board 11kV networks to assess their performance. Five arduous years of service were insufficient to evaluate the contact wear and loss of vacuum integrity, as none could be detected. The current chopping level of vacuum arc switching is the lowest of all switching media. Of the four switching media (air, oil, SF6 and vacuum), vacuum has by far the best dielectric recovery properties after short-circuit interruption. Vacuum arc switching produces no adverse environmental products, precluding harmful characteristics either towards people or materials. Increased safety due to the absence of oil products in the equipment make-up. Tests The relevant international and national type tests applicable to the Alstom range of switchgear have been carried out by accredited testing authorities such as KEMA and the SABS. Copies of these tests are available on request. It can be stated that, among South African manufacturers of indoor switchgear, ALSTOM Switchgear has been a leader in implementing internal arc testing and actively promotes internal arc testing of switchgear. SBV switchgear has been internally arc tested at 25 ka for 200 milliseconds, as per Eskom requirements. TYPES OF SWITCHGEAR Type SBV 3 & SBV 3E This version is available in single or duplicate busbar arrangements. Circuit and busbar earthing via the circuit breaker are available options. The operating mechanism allows for hand charged spring or motor charged spring application. The mechanism design allows for the following optional features: second shunt trip facility under voltage (no-volt) trip facility direct acting (series) trip facility
3 including A to and including 40 ka for 3 seconds BIL: 95 kv Type SBV4 & SBV4E The SBV4 equipment is available in single busbar configuration only and is of low-profile construction, permitting overall height reduction of the switchgear. Circuit and busbar earthing via the circuit breaker are available options. The operating mechanism allows for hand charged spring or motor charged spring application. The mechanism design allows for the provision of the following optional features: second shunt trip facility under voltage (no-volt) trip facility direct acting (series) trip facility including A to and including 31,5 ka for 3 seconds BIL: 95 kv Type SBV5 & SBV5E The SBV 5 circuit breaker was designed for utilisation in the low-profile SBV4 housings and is interchangeable with the SBV4 circuit breaker and vacuum contactors. Circuit and busbar earthing via the circuit breaker are available options. The operating mechanism is of the magnetic actuator type, using closing and tripping coils with the plunger Medium voltage switchboard undergoing preparations for acceptance testing. being held magnetically in the closed or open positions by permanent magnets. The material used for the magnets is neodymium-iron-boron, the field strength of which is almost twice that of samarium cobalt and up to 280 times that of steel. The circuit breaker has been type tested in excess of no-load mechanical operations without discernable component wear. The combination of magnetic actuators with long-life vacuum interrupters has resulted in circuit breaker life that was previously not possible. Further features include a low component count, reliability and minimal maintenance. including A to and including 25 ka for 3 seconds BIL: 95 kv Type SBV24 This version is for 22 kv indoor utilisation and is of single busbar configuration. Circuit and busbar earthing via the circuit breaker are available options. The operating mechanism allows for hand charged spring or motor charged spring application. The mechanism design allows for the provision of the following features: second shunt trip facility under voltage (no-volt) trip facility direct acting (series) trip facility. 24 kv including A to and including 25 ka for 3 seconds. BIL: 125 kv Type SBV-C These are fused vacuum contactors mounted on withdrawable carriages and are extensible on SBV3 and SBV4 switchgear. A manually operated cable discharge switch is an available option. Operating mechanisms are electrically held or mechanically latched options. Mechanical life of the vacuum contactors is in excess of 3 x 10 6 operations; electrical endurance in excess of 10 6 operations. Fused contactors have an advantage over circuit breakers in that the fuses greatly limit the magnitude and duration of short-circuit currents. Where the equipment is used in switching of motors, cables can be sized to carry load and starting currents only. Possible fault damage to motors can thus be restricted. (of contactor unit only) including 400 A Rated short circuit capability: 4 ka BIL: 75 kv
4 Internal arc testing of MV switchgear A major hazard of electrical medium voltage installations is the danger of an internal arc fault. The most common causes of an internal arc fault are tools left on the busbars after the initial installation or during maintenance, and binding wire used during commissioning tests, not having been removed prior to energising. An internal arc condition constitutes a potentially dangerous situation for the operator. Internal arc testing requirements were initiated by the German PHELA organisation. A procedure for internal arc testing was then developed, resulting in Appendix A of the IEC standard. Arc duration of 0,1 second is considered sufficient to prove the operation of pressure relief devices. Internal arc faults are normally simulated by a thin copper wire of approximately 0,5 mm in diameter stretched across two or more phases inside the various switchgear compartments, and in the case of segregated phase conductors, SBV3 double busbar switchpanel after internal arc test. between one phase and earth. All the relevant compartments must be individually tested to ensure the integrity of the complete switch panel, not just one particular section. For the effects of the explosion to be monitored under actual conditions, two walls, a ceiling and the floor are required to be simulated. As operator safety is of prime importance, indicators are positioned both horizontally and vertically in metal racks 300 mm from the switchgear being tested. The above indicators are positioned front and sides, facing all the points where gas is likely to be emitted, and positioned in such a way that hot gas escaping in slant directions can be monitored. These indicators consist of metal frames covered with black cretonne cloth of 150 g/m². To successfully complete the internal arc tests the equipment needs to meet the criteria set out in IEC Appendix A as repeated below: 1 Whether correctly secured doors, covers, etc, do not open. 2 Whether parts (of the metal-enclosed switchgear and control gear), which may cause a hazard, do not fly off - including large parts or those with sharp edges, e. g. inspection windows, pressure relief flaps, cover plates, etc, made of metal or plastic. 3 Whether arcing does not cause holes to develop in the accessible external parts of the enclosure as a result of burning or other effects. 4 Whether the indicators arranged vertically do not ignite. Indicators that ignite as a result of paint or stickers burning are excluded from this assessment. 5 Whether the indicators arranged horizontally do not ignite. Should they start burning, the assessment criterion may be regarded as having been met if proof is established that the ignition was caused by glowing particles rather that hot gases. Highspeed camera pictures should be produced in evidence. 6 Whether all the earthing connections are still effective. It is advisable to record the tests in a high-speed video of up to frames per second in order to analyse the physical phenomena. The ever increasing safety needs call for switchgear manufacturers to comply with international and national standards. Internal arc fault testing in accordance with IEC The design of the SBV range of vacuum switchgear commenced in Even at that early stage the importance of internal arc fault venting and safety was recognised. The design of the horizontal withdrawable switchgear was chosen so as to incorporate top venting. Following Alstom s success at KEMA in 1997 when the SBV4 was successfully internal arc fault tested for 20 ka at for 0,1 second, more onerous tests were carried out at the SABS high power laboratory. The tests provided for side access in addition to front access and the internal arc was for 25 ka with a duration of 0,2 sec. Internal arc classification in accordance with IEC The introduction of IEC and internal arc classification (IAC) lead to Alstom enhancing its proven SBV range of circuit breakers (i.e. SBVE). The SBVE range is presently classified as BFL-AR 25 ka 0.2 sec in accordance with IEC Development and testing with SBVE is ongoing, ensuring safer and more reliable products. 5
5 SBV3 switchgear fitted with amp busbar trunking to fit through fire wall 2 SBV4 switchboard with A incomers 3 SBV5 circuit breaker carriage 4 Special purpose busbar trunking 5 SBV4/SBV4C switchboard during inspection 6 SBV24 switchboard being commissioned on site. 6
6 ALSTOM SWITCHGEAR Head office 2 Magnet Road Knights 1413 P O Box Knights 1413 Tel: (011) Fax: (011) [email protected] BRANCH OFFICES BLOEMFONTEIN PRETORIA CAPE TOWN 20 Lombard Street 449 Skilder Street 12 Hawkins Avenue Hilton 9300 Silvertondale Epping Industria No 1, 7460 P O Box 914 P O Box 1304 P O Box 276 Bloemfontein 9300 Silverton 0127 Eppindust 7475 Tel: (051) Tel: (012) Tel: (021) Fax: (051) Fax: (012) Fax: (021) PORT ELIZABETH DURBAN WELKOM 200 Kempston Road 70 Edwin Swales VC Drive th Street Sidwell Rossburgh 4094 Voorspoed 9459 P O Box 3503 P O Box 922 P O Box 515 North End 6056 Durban 4000 Welkom 9460 Tel: (041) Tel: (031) Tel: (057) Fax: (041) Fax: (031) Fax: (057) NELSPRUIT POLOKWANE JOHANNESBURG C/0 Kragbron & Bester Street 115 Blaawburg Street 4 Branch Road Nelspruit 1201 Ladine 0750 Driehoek Germiston 1401 P O Box 785 P O Box 5908 PO Box 678 Nelspruit 1200 Polokwane 0750 Germiston 1400 Tel: (013) Tel: (015) Tel: (011) Fax: (013) Fax: (015) Fax: (011) STEELPOORT Building 1 Tweefontein Farm Steelpoort Ext 10 PO Box 786 Nelspruit 1200 Tel: (013) Fax: (013) RUSTENBURG Ruby Sands Road Memorial Park Rustenburg PO Box Protea Park Rustenburg 0300 Tel: (082) Fax: (012)
7 Alstom Medium Voltage Switchgear 2 Magnet Road, Knights, 1413 P O Box 13024, Knights, 1413 Tel: (011) Fax: (11) [email protected]
INDOOR MEDIUM VOLTAGE SWITCHGEAR - UP TO 24kV. A division of ACTOM Pty Ltd
INDOOR MEDIUM VOLTAGE SWITCHGEAR - UP TO 24kV A division of ACTOM Pty Ltd ACTOM Indoor Medium Voltage Switchgear SBV range of products Prior to 1980, ACTOM s indoor vacuum arc switching is the switchgear
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection
Session Eleven: Development of Standards for MV Switchgear Rated for Arc Protection Bryan Johnson Product Group Manager, MV Switchgear ABB South Africa Contents Introduction... 3 What is an internal arc
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Advantages of Fixed Circuit Breaker Switchgear
Advantages of Fixed Circuit Breaker Switchgear by Lionel Mackay, EDF Energy, and Mike Adams, Schneider Electric Ltd Introduction The purpose of this paper is to review the advantages of fixed circuit breaker
Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated lightning impulse withstand voltage [kv] 75 125
Standards and Regulations IEC 62271-200 ; VDE 0671-200 ; BS EN 62271-200 Technical Data MC3-12 MC3-24 Voltage Rated operating voltage [kv] 12 24 Rated power frequency withstand voltage [kv] 28 50 Rated
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV
MEDIUM VOLTAGE SUBSTATION PRACTICES MEDIUM VOLTAGE SUBSTATION PRACTICES Medium Voltage (MV) is defined as: 1000V< MV 44kV MEDIUM VOLTAGE SUBSTATION PRACTICES This presentation covers some safety aspects
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy
Our brand A strong brand for strong products: The ENERGOLINE brand represents our product portfolio of INDUSTRIAL SWITCHGEAR SYSTEMS. Our products are characterized by a high degree of safety, flexibility
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
Session Four: Internal Arc Safety in New and Existing Switchgear
Session Four: Internal Arc Safety in New and Existing Switchgear Richard Blakeley RPS SWITCHGEAR LIMITED 1. INTRODUCTION Commercial pressures are increasing on organisations to maximise their plant utilisation,
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
Low Voltage Switchboards The Best Technical Solution for Your Ship
The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Safe and secure distribution of medium voltage with AX1
Safe and secure distribution of medium voltage with AX1 The intelligent switchgear AX1 is a modern, air-insulated switchgear that lies at the very front line of safety and security safety for operating
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac
New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges
Switchgear and Metal-Enclosed Bus
Section 18 Switchgear and Metal-Enclosed Bus 180. SWITCHGEAR ASSEMBLIES 180A. General Requirements for All Switchgear. This rule covers general requirements for all switchgear. Examples of switchgear found
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN
e 2 ALPHA Medium Voltage Switchgear Data Sheet K-1.1.2 EN We create ideas with power! ELEKTROMETAL ENERGETYKA SA is a new Polish company providing solutions for electrical power engineering. Our services
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY
2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY Thomas P. McNamara, P.E. Manager, Development Engineering ABB Inc. Power Technologies Medium
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
MEDIUM VOLTAGE SWITCHGEAR AND CONTROLGEAR MODEL MS-E. IEC 62271-200 7.2 /12 /15 kv 25, 31.5, 40 ka
SWITCHGEAR AND CONTROLGEAR MODEL MS-E IEC 6227- /2 /5 kv,, ka The MS-E conforms to IEC 6227- standard and is designed and manufactured utilising Mitsubishi Electric state-of-the-art technology, fully taking
Power-Zone 4 Arc Resistant Low Voltage Switchgear
Power-Zone 4 Arc Resistant Low Voltage Switchgear with ArcBlok Technology Make the most of your energy SM Workplace safety 2 I Power-Zone 4 Arc Resistant Low Voltage Switchgear Five to ten arc flash explosions
Masterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Design of a New Generation of Internal Arc Resistant Switchgear
Design of a New Generation of Internal Arc Resistant Switchgear Nirmal Deb Patrick Bailly Thierry Tricot Leslie T Falkingham AREVA T&D AREVA T&D AREVA T&D AREVA T&D Switzerland France France UK Abstract
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV. tgood.com. Energy. Fast.
METAL-CLAD AND METAL-ENCLOSED SWITCHGEAR 3.6KV~40.5KV tgood.com Energy. Fast. TGOOD produces over 5000 switchgear units annually for projects around the globe PRODUCT OVERVIEW Integral substation component
UFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
Emirates Aluminium starts up World s first fully integrated power distribution system from ABB
Reprint from Aluminium World 2009, Volume 2 Emirates Aluminium starts up World s first fully integrated power distribution system from ABB Emirates Aluminium (EMAL), a joint venture between Abu Dhabi s
Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation
Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
Type-Tested Power Distribution Board 8PT with Rear Busbars. sivacon
Type-Tested Power Distribution Board 8PT with Rear Busbars sivacon The Obvious Solution for Global Challenges SIVACON Type-testing is one of today s important issues for low-voltage technology and will
P System Cubicles. Certified for more safety
P System Cubicles Prisma Plus LV Switchboards Certified for more safety Prisma Plus, an offer thought out for greater professionalism With the Prisma Plus P system, Schneider Electric proposes high-performance
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV
Installation, Operation and Maintenance Instructions Uniflex ABB PTMV SAFETY FIRST! For safe and correct usage note the following recommendations: Only install switchgear and switchboards in enclosed rooms
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011
SOLUTIONS FOR INTERNAL ARC PROTECTION ACC. IEC 62271-200 WITH PRESSURE RELIEF INTO THE SWITCHGEAR ROOM FOR GAS AND AIR INSULATED MEDIUM VOLTAGE SWITCHGEARS Harethe El Ouadhane Mario Haim Helmut Spitzer
Regulation IO-6.0: Electrical Safety Regulations
Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5
Contents. Description. Product Selection Guide
.1 Medium Voltage Switchgear Introduction Indoor Type VCP-W Metal-Clad Switchgear Assembly (5/15 kv shown) Product Selection Guide Product Offering Chart Metal-Enclosed Contents Description Notes Additional
Switchboard system. NorLine 800
Switchboard system NorLine 800 NorLine 800 SWITCHBOARD SYSTEM 2 NorLine 800 Switchboard system Table of contents Subject Page Table of contents 2 Overview 2-3 NorLine 800 technical specifications 4 Structural
Overview Brochure Integrated Power Distribution. Medium Voltage Assembly Solutions
Overview Brochure Integrated Power Distribution Medium Voltage Assembly Solutions Medium voltage assembly solutions Eaton, a premier leader in manufacturing power distribution and power protection equipment
8146/5 Series Breaker Panelboards
8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division
Modular Systems wind portfolio overview Power Collection and Grid Connection products
Modular Systems wind portfolio overview Power Collection and Grid Connection products Slide 1 Modular Systems wind portfolio Wind power - definition A wind turbine is a device that converts kinetic energy
Extend the Life of Existing Switchgear
Extend the Life of Existing Switchgear January 2011/1910DB1002 by Hal Theobald, Product Manager Schneider Electric USA, Inc. Make the most of your energy SM Summary Introduction... p 3 Maintenance Requirements...
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS
DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS ABSTRACT Data Centers are a critical part of the world economic systems. Billions of electronic transactions happen
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
Nothing s BetterThan the Original MODAN Power Distribution Systems
MODAN www.eaton.com Nothing s BetterThan the Original MODAN Power Distribution Systems Modan Modular switchboard system Controlling and Distributing Power Safely Thinking further. Questioning the well-established
OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.
OVERCURRENT & EARTH FAULT RELAYS Objective: To study the protection of equipment and system by relays in conjunction with switchgear. Theory: The function of a relay is to detect abnormal conditions in
8. Switchgear and switchgear installations for high voltage up to and including 52 kv (medium voltage)
8 ABB_11_E_08 13.08.2007 9:07 Uhr Seite 379 8. Switchgear and switchgear installations for high voltage up to and including 52 kv (medium voltage) 8.1 Switchgear apparatus (< 52 kv) This voltage range
Medium voltage indoor circuit breakers ANSI/IEC solutions
Medium voltage indoor circuit breakers ANSI/ solutions Table of contents Introduction... 3 Vmax/A... 4 ADVAC... 6 AMVAC... 8 Vmax... 10 VD4... 12 VM1... 16 HD4... 19 V-Contact VSC... 22 2 Medium voltage
Securing your electrical installations Prisma,
Securing your electrical installations Prisma, an optimised solution for type tested low voltage switchboards up to 3200 A Table of contents Developing installation safety 4 Prisma P * Electrical switchboards
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
Engineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Interior
01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
Choosing for tranquility
Medium voltage switchgear with withdrawable circuit breakers MCset Choosing for tranquility Web enabled Power & Control Building a New Electric World Innovation at every level Busbar compartment This section
Addendum #2 Contract UK-11-13
Addendum #2 Contract UK-11-13 Utilities Kingston Purchase and Replacement of Switchgear at Kingston Hydro Substation MS11 March 25, 2011 Delivered to: All RFP recipients Total number of pages: Nine (9)
Enhancing Personnel Safety with Arc Resistant Equipment
Enhancing Personnel Safety with Arc Resistant Equipment Carl Christian Power LV Offer Marketing Nashville, TN Sponsored by the Water Wastewater Competency Center 1 Enhancing Personnel Safety 5-10 Five
Engineering Specification
Engineering Specification Electrical 33KV AC INDOOR SWITCHGEAR NON-WITHDRAWABLE Owner: Approved by: Chief Engineer, Electrical Neal Hook Chief Engineer Electrical Authorised by: Version 2.1 Issued May
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
SENTRON Switching and Protection Devices Air Circuit Breakers
Siemens AG 9 SENTRON Switching and rotection Devices Air Circuit reakers 5 5/ Introduction 3WL Air Circuit reakers 3WL Air Circuit reakers/ Non-Automatic Air Circuit reakers up to 63 A (AC) 5/6 General
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
SIVACON The Versatile Low-Voltage Switchboard
s SIVACON The Versatile Low-Voltage Switchboard Type-Tested Power Distribution Board 8PT The Obvious Solution for Global Challenges SIVACON Type testing in low-voltage switchgear is increasingly becoming
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
Medium Voltage Switchgear
Uniswitch Medium Voltage Switchgear 12 kv, 17.5 kv, 24 kv 630 A and 1250 A Operation and TABLE OF CONTENTS 1 Summary...1 1.1 General...1 1.2 Standards and specifications...2 1.3 Service conditions...3
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application
Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application by Reza Tajali, P.E. Square D Company ABSTRACT In modern data centers, Uninterruptible Power Supplies (UPS)
Disconnectors and Earthing Switches 36 kv up to 800 kv
Power Transmission and Distribution Disconnectors and Earthing Switches 36 kv up to 800 kv Ruhrtal & Siemens: A strong and successful team We manufacture high quality high-voltage disconnectors and earthing
Fusible Disconnect Switch
Circuit Breakers Circuit breakers are used in panelboards and switchboards to provide circuit protection and provide a means of energizing and de-energizing a circuit. Siemens Sentron molded case circuit
RE-3 : SOLID TOP RANGE RANGE TOP ONLY
VULCAN ELECTRIC SOlid top oven range MODEL: RE-3 - SOLID TOP oven Range RE-3T - SOLID range top only ON CABINET BASE RE-3 : SOLID TOP RANGE Model Re-3T : Solid TOP RANGE TOP ONLY Index: General Data 2
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS
A USERS GUIDE TO ARC RESISTANT LOW VOLTAGE SWITCHGEAR & MOTOR CONTROL ANALYTICAL COMPARISON VS ARC FLASH TEST RESULTS By: Gabriel Arce, ABB, San Luis Potosi, Mexico Casey McCollum, ABB, Houston, TX John
3/2-way Solenoid Valve, direct-acting, NC or NO
3/2-way Solenoid Valve, direct-acting, NC or NO Electrical connection cable plug, Form A With or without manual override as standard Threaded port and sub-base s Impulse optional Type 6014 can be combined
GE Power Controls. MiniFORM Switchboards
GE Power Controls MiniFORM Switchboards MiniFORM MiniFORM MiniFORM switchboards Arrangement Modules Arrangement modules 1-6 6 Arrangement modules 7-12 7 Arrangement modules 12-14 8 Arrangement modules
Intertek Cleeve Road, Leatherhead, Surrey KT22 7SB UK
Intertek Cleeve Road, Leatherhead, Surrey KT22 7SB UK [email protected] +44 1788 578435 www.uk.intertek-etlsemko.com Author: Craig Diack-Evans Senior International Business Development Manager ASTA
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services
Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services Introduction Power Distribution Equipment is a term generally used to describe any apparatus used for the generation,
High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance
Annex I To Loughborough University (LU) Facilities Management (FM) Health and Safety Policy High Voltage (HV) Electricity System Safety Rules and Associated Safety Guidance 1. Introduction a. These Safety
employed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
IEC 61439-1 & 2 standard. The reference for safe and reliable LV switchboards
IEC 61439-1 & 2 standard The reference for safe and reliable LV switchboards IEC61439-1 & 2 The power of a standard adapted to your needs IEC standards are today legal or market references. The new IEC
SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A
s SICONT Limit Switches Type 3SE3 upto 500 VAC, 600 VDC, 10A Introduction The technical and descriptive information on the function, construction and selection of the new types of 3SE3 limit switches is
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear
Medium voltage products UniSec for Smart Grid Air-insulated medium-voltage secondary distribution switchgear Index 3 Overview 4 Standard Levels 6 Monitoring & Control 7 Measurements 8 Protection & Logic
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
How To Build A Germany Power Plant
Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA
MRO Modularne Razdelilne Omare d.o.o. ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 2, 000 Ljubljana, LOVENIA MC GENERAL When to use? MC - modular switchgear cabinets are type-tested, factory built switchgears,
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS
ARC FLASH CALCULATIONS & LABELING REQUIREMENTS Presented by: Edmund Elizalde EYP Mission Critical Facilities, Inc. Slides by: Lonnie Lindell SKM Systems Analysis, Inc. 1 Agenda NEC 110.16 NFPA 70E IEEE
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80