IN-SERVICE PARTIAL DISCHARGE TESTING OF GENERATOR INSULATION
|
|
|
- Sheryl Blankenship
- 9 years ago
- Views:
Transcription
1 IN-SERVICE PARTIAL DISCHARGE TESTING OF GENERATOR INSULATION M. Kurtz and G. C. Stone, Ontario Hydro, Research Division Toronto, Canada IEEE Trans. Electr. Insul, Vol EI-14 No 2, April 1979 ABSTRACT Progressive degradation of high-voltage generator insulation, whether due directly to the erosive effects of internal or slot discharge or to other debilitating factors such as heat and vibration, may be detected and monitored as a function of time by in-situ partial-discharge tests. This paper describes new diagnostic test techniques for assessing the condition of generator insulation with a minimum of service interruption. An improved means of coupling or data acquisition is described, as well as a versatile single-channel pulse height analyzer with characteristics adequate for a field application of this type. Some typical test data are given. These studies were sponsored by the Canadian Electrical Association and are presented with their permission. are observed, together with a power-frequency trigger signal taken from one of the filter inputs, on an oscilloscope with a four-channel display as shown in Figure 2. The discharge patterns in Figure 3 are typical of a new and an old winding. Experience shows that as the magnitude of the highest partial discharge pulse increases, damage to the stator insulation also increases. INTRODUCTION Generator insulation systems, however perfect their initial state, inevitably degrade in service. Heat, thermal cycling, bar forces, vibration, mechanical shock, shrinkage of support structure such as wedges and spacers, and the presence of a high electric stress, act and interact to impair the integrity of the dielectric system. At some stage, partial discharges will start or begin to increase, providing an additional erosive aging factor. This usually occurs at abraded outer shielding, in cavities or delaminations, or in the end-turn structure. The number, magnitude and distribution of the partial discharge pulses can conceivably identify predominant aging mechanisms. Changes in these quantities, as a function of machine age, become a measure of cumulative insulation deterioration. CONVENTIONAL DIAGNOSTIC TEST A relatively inexpensive technique for the detection and display of partial-discharge pulses in generators has been developed and used by Ontario Hydro for over 20 years for the assessment of stator insulation condition [1]. In its present form, portable discharge-free coupling units, fabricated from approximately 2.5 m looped lengths of single conductor 27.6 kv concentric-neutral power cable are used, one for each phase of the generator as shown in Figure 1. The core conductors of the cables are connected to the generator s respective terminals at any conveniently accessible point on the machine side of the disconnecting switch. The cable shields, the low sides of these high voltage coupling capacitors, are respectively connected, via lengths of shielded coaxial cable, to three five-stage RC high pass filters with a cut-off at about 30 khz. After the machine is brought up to rated speed and voltage, the filter outputs Fig. 1: Cable-type portable partial-discharge coupling capacitors being connected to the three phase-conductors of a. machine prior to test. Fig. 2: Typical display showing the partial discharges from three phases of a machine and one power-frequency reference signal. Tests are usually done with the machine (a) isolated from the system, (b) synchronized at no load and (c) a full load. In many cases, a skilled operator can distinguish between pulses originating in the machine winding and external noise entering from the power (?). Large differences between the data for the (?) test modes may be caused by movement of bars in response to dynamic forces as the load changes. These movements result in a change in the contact resistance between the bar shielding paint and the iron in the (?). causing discharges in the slot to change. Such (?) are subject
2 to abrasion, cumulative damage to shielding, increasing slot discharge with further (?). more loosening, more movement and the beginning of a runaway condition to failure. The major limitations of conventional partial-discharge tests are: 1. Noise originating from external sources, whether from other equipment in the station, or from the power system in the synchronized-mode tests, tends to mask the desired information. Such external noise can be as much as an order of magnitude higher than the pulses related to discharges in the machine. The phase position and the general shape of the external noise pulses may be the same as the internal noise pulses. (The pulse shapes are indeed largely a characteristic of the generator, and the coupling and filtering equipment characteristics.) 2. The discharge pulses, with rise times in the nano-second range, usually do not recur at the same phase position in successive cycles of power frequency. Estimation of the highest pulse magnitude is difficult and test results tend to be highly subjective, i.e., different operators report different data. Capturing of the highest pulses with an oscilloscope camera, even with fast film, is uncertain and undependable. 3. Interruption to service is required. Though a Machine need not necessarily be at standstill, it is desirable, from safety considerations, to isolate the machine and open the field breaker before connecting or removing the portable coupling capacitors. 4. The portable couplers must be maintained in a safe condition. Periodic high-voltage testing is required to ensure that the couplers are discharge-free at 150% of Maximum operating voltage. To overcome these limitations the Canadian Electrical Association undertook the sponsorship of the development of a more objective technique making use of recent advances in digital methods. PULSE HEIGHT ANALYZER Examination of the oscilloscope displays of discharge pulses from different machines, insulated with a variety of systems subject to different kinds and degrees of damage, discloses subtle differences not easily characterized by quantities such as maximum pulse height and the like, and often not readily captured on film. There is clearly more information is the pulse pattern than even a trained eye can realize. A method of quantizing the data in the discharge pattern is required for future correlation with Insulation condition. A versatile dual-polarity single-channel pulse height analyzer has been built to study the characteristics of discharge pulses, particularly the uniqueness and repeatability of the pulse height distributions. This Generator Corona Analyzer (GCA) is designed specifically to accommodate the short rise time and high repetition rate (multiple sites) of these pulses and to be insensitive to ringing. The GCA receives data from the high-pass filter Mentioned above and counts the number of pulses during a one-second interval which fall in the window between lower and upper thresholds, manual 1 y variable from O.I to 1.4 V in 0.1 V steps, with a 0.1 V interval between the thresholds. (These values were selected after some experience with the first prototype circuit which permitted continuous independent variation of these thresholds.) A manual scan with a threshold selector switch permits a complete pulse height analysis in about 2 minutes. A phase window, adjustable in width and position relative to the power frequency cycle, allows pulse counts to be made in any desired portion of the cycle. Fig. 3: Partial discharge displays, one phase only, of asphaltic-mica insulated windings. These are from two identical machines. The upper trace is from a 3 year old winding, the lower from a 24 year old winding.
3 Fig. 4: Simplified schematic of analyzer. of the output pulse from B Bust be set greater than the sum of A s output width and the signal rise time. This concept has been used elsewhere [2]. A cross-inhibit feature between the above positive-pulse channel and a similar negative-pulse channel, prevents either channel from functioning for 3 us after the first channel has been triggered, to avoid false counts due to opposite polarity voltage swings in the partial discharge pulse. (Individual partial discharge pulses are oscillatory, generally with a duration of less than 1 us. Observation of partial discharges on many different machines indicates that two consecutive pulses are rarely less than 10µs apart.) In practice, the circuit requires an overdrive of 20 mv for 25 ns to count a pulse, and pulses separated by 5 us or more can be resolved. Fig. 5: Sequence of analyzer s operation. Only pulses greater than the tower threshold produce trigger signals. The circuit uses two types of high-speed TTL 1C logic devices: fast comparators and non-retriggerable, edgetriggered monostables which can also be inhibited by an appropriate logic signal. The operation of the magnitude window for the positivepositive-pulse channel may be explained with reference to Figure 4. Monostables A and B are only triggered by a positive pulse. C is triggered only when both the inhibit signal is removed and a negative wave front appears at the trigger input. The sequence of operations for a pulse with a peak magnitude falling within the window is shown in Figure 5(a). The pulse triggers an output from comparator A only, while the inverted output from mono-stable B remains high since it was not triggered, thus failing to inhibit C. When A returns to the low level, monostable C is triggered by the negative front, its output activating a pulse counter. Until non-retriggerable monostable A returns to the low level, it cannot perceive input signals, thus ignoring ringing for a preselected time, in this case, 3µs. When the input pulse exceeds the upper threshold, as shown in Figure 5(b), both A and B are triggered. Since B s output is now low, C is inhibited from triggering when A s output drops; hence the counter is not activated. The width Fig. 6: Typical GCA Pulse Height Distribution, Mountain Chute GS, Unit 2, Blue Phase. It is interesting to note that the magnitudes of pulses in the 10 to 15 counts per second region correspond to the maximum pulse magnitudes observed in the conventional test. NOISE CORRECTION From basic considerations, partial discharges occurring during the rising portion of the applied high voltage wave, are detected as negative pulses, and vice versa. The GCA phase window may be adjusted so that in a sequence of pulse counts, one may record the distribution of positive and negative pulses in the rising and falling portions of the power frequency cycle, respectively. On the assumption that unwanted noise is more or less uniformly distributed in both half cycles, a net distribution may be derived which ore truly represents the discharge situation in the insulation system. Typical data obtained in this way are shown in Figures 6 and 7. A calibration procedure to be described later, permits conversion from a mv to a pc base. Correction for transient noise occurring at the time of measurement is achieved by a simultaneous display, renewed every second, of the count of a selected pulse polarity in both the rising and falling portions of the power frequency cycle, both counted in the same one second interval. This noise correction technique may be only partially effective because the external noise (discharges on the
4 incoming transmission lines, transformers, bus work) tends to be phase-oriented in exactly the same way as the generator insulation discharge pulses. Yet one invariably finds that the count in the expected polarity far exceeds the other. A more effective approach to noise elimination is described below. COUPLER CONSTRUCTION Essentially high-voltage power cable splice materials and techniques are employed. A sufficient thickness of selfamalgamating insulating tape to insulate for 4 kv (about 2 mm) is applied first over the jumper insulation for a length limited only by the local geometry (typically 20 cm). Over this insulation, a semi-conductive, self-amalgamating tape and tinned copper braid sandwich provides a discharge-free capacitor electrode. The capacitance of the coupler is adjusted to match symmetrical pairs to within about 2%. Depending on the jumper length, a typical coupler capacitance will be in the 70 to 90 pf range. The centre conductor of a coaxial cable (RGS8C/U) is soldered to the braid and securely fastened in place, as shown in Figure 9. The shield is removed to a point beyond the braid and left open at this end. Insulating tape is applied overall for mechanical security and a final finish layer similar to that normally used over jumpers may be used. Fig. 7: GCA Pulse Height Distribution, Barrett Chute GS, Unit 4, Red Phase. PERMANENT COUPLING CAPACITORS Permanent capacitive coupling devices may be installed in the winding itself, on the circuit ring bus, or on suitable jumpers between coils or coil groups. Such couplers permit observation of the discharge condition in a machine in the presence of external noise, and with no interruptions to service, though some load variation during tests my be advantageous to search for loose bars. These may be fabricated quite simply, at least on hydraulic units, by applying a conductive layer over the bus or jumper insulation in a convenient location and providing for connection to detection equipment. If the permanent couplers are placed at corresponding points in a pair of parallels or splits, equidistant from the machine terminal, differential noise rejection is possible. (In cases where the circuit ring bus lengths are unequal, the difference may be compensated by suitable delay lines to the differential amplifiers.) A differential amplifier as shown in Figure S will eliminate not only external or common-mode noise, but also the power frequency and its harmonics, so that a filter with its associated signal distortion is no longer required. It may be noted that pulses from a third split, entering via the circuit ring bus, may be rejected like common-mode noise. Thus in order to survey a machine winding completely, every split must be equipped with a permanent coupler. Couplers were installed initially on the six splits in one phase of a 13.8 kv hydraulic machine. These were placed on coil group jumpers half way down the winding between line and neutral where the jumper conductor operates at about 4 kv to ground at 60 Hz Fig. 8: Schematic of permanent couplers in machine splits. The co-axial cables from all installed couplers are trained and secured to a common junction box, external to the machine, where each cable is terminated with a 50-ohm resistor and connected to a BNC connector. This resistor eliminates reflections and keeps the 60 Hz potential on the coupler and cable down to less than a volt. It is important to note that the cables from symmetrical coupler pairs must be matched in length to better than 1 m. PERMANENT COUPLER EVALUATION Tests on generators with permanent couplers demonstrated that pulses applied at the machine terminal were rejected in the differential mode and could not be detected. However, pulses injected near one of the couplers in a pair could be observed directly on an oscilloscope, chiefly because the difference in arrival time (50 ns) at the two couplers, and hence at the differential amplifier inputs, resulted in a net signal. Note that the polarity of an observed pulse depends on the source split as well as its phase relative to power frequency. Effective noise rejection and correlation with conventional
5 techniques were demonstrated with permanent couplers installed on four machines. Inherent in the Use of the permanent couplers on all splits is the capability, by observing pulse polarities, of identifying the location of the source of anomalously high pulses to within possibly a few coils at the line end of a single split. GCA. Some 60 machines have been tested with this technique to date, though the opportunity has not yet arisen to make measurements on a machine before and after maintenance, such as re-wedging or the like. Good correspondence has been noted between the new and the conventional test data. The conventional test, using portable couplers and the oscilloscope display, has correctly identified windings in the process of deterioration. Test data have ranged from 10 to 20 mv on machines considered to be in good running condition, to 50 mv to 500 mv (2000 to 5000 pc, depending on individual machine Vibrations) for machines in trouble. One large hydraulic generator suffering from severe ground wall erosion failed within a few months of the 50 mv measurement. Fig. 9: Unfinished permanent coupler installed on jumper in generator winding. Kote the co-axial cable attachment. CALIBRATION The conversion of test data in terms of millivolts of deflection on an oscilloscope screen, into apparent charge in picocoulombs is of paramount importance for rendering the data independent of the detection equipment parameters, machine size and the loading effects of connected bus, etc. For this purpose, it is necessary to inject a known charge at the machine terminals and to note the response on the detection equipment. A simple means of injecting such a pulse is achieved by isolating about 15 cm at one end of the shield on a portable discharge coupler by separating the concentric neutral conductors and cutting a I mm gap in the extruded shield of the cable. This provides a 30-pF high-voltage coupling capacitance through which a suitable square wave may be supplied via a length of co-axial cable, for calibration [3]. A 50-Q terminating resistor, connected to the co-axial cable at the coupling capacitor, limits the 60 Hz rise in potential of the HV cable shield to the order of 4 mv for a 13.8 kv generator winding, and eliminates reflections. A typical input square wave and output response is shown in Figure 10. A 200 ns rise time was selected since faster fronts produced unacceptable, ringing in the response. Typical calibrations obtained to date range from 10 to 35 pc per mv, depending on the machine size. A pulse generator at a repetition frequency of 5 khz, capable of driving 50 Ω to 20 V, has been built into the GCA and may also be used to check its operation. TEST RESULTS Pulse height distribution data is being collected using the Fig. 10: Calibration of pulse voltage magnitudes into picocoulombs. The lower trace shows the front of a negative square wave which is applied through a 50 pf ideating capacitor. The response through the filter is shown in the upper trace. The injected charge, about 200 pc, yields a calibration in this case, of 20 pc/mv. For several machines, maximum pulse height has been decreased by an order of magnitude following treatment such as slot wedge tightening, re-finishing of semi-conductive slot paint, injection of semi-conductive silicone rubber in slot sides, etc. [4]. CONCLUSIONS AND FUTURE WORK The goal of a more objective and reliable test method with reduced system cost and independence from the interfering effects of external noise has been achieved. Further refinement and time reduction for the test is possible using a multichannel analyzer. A commercial analyzer has been modified to accept pulses at intervals down to about 10 us, yielding test curves identical to those obtained with the single-channel Generator Corona Analyzer, but in a much shorter time. A prototype system has been demonstrated using a programmable calculator and a fast digitally controllable counter for the permanent installation and continuous pre-programmed periodic monitoring of discharge pulse distribution as a function of load and time. Now that data may be obtained in a consistent and repeatable manner, the enormous task remains of collecting data from the field and establishing correlations with
6 observed insulation damage in service as a function probably of the type of insulation system in question. When such correlations are confirmed, early warning of incipient problems will hopefully be obtainable so that suitable repair and maintenance work may be scheduled. REFERENCES [1] M. Kurtz, A Partial Discharge Test for Generator Insulation, Ontario Hydro Research Quarterly, Vol. 23, No 4, 1973, pp 1-4. [2] H. A. Cole, A Differential Pulse Height Discriminator, Nuclear Instrumentation and Methods, Nov. 1976, p 551. [3] Detection and Measurement of Discharge (Corona) Pulses in Evaluation of Insulation Systems, ASTM , Part 39. [4] M. Kurtz and J. F. Lyies Generator Insulation Diagnostic Testing, IEEE Paper So. F7918S-0, PES Winter Meeting, New York, N. Y., Feb This paper was presented at the 1978 International Symposium on Electrical Insulation, Philadelphia, June Manuscript was received 11 August 1378, in revised form 30 November 1978.
Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives
Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives G.C. Stone, I. Culbert, H.G. Sedding Qualitrol-Iris Power Mississauga, Ontario, Canada Abstract On-line partial discharge
DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
Charged cable event. 1 Goal of the ongoing investigation. 2 Energy sources for the CDE. Content
Charged cable event David Pommerenke, [email protected], 916 785 4550 Last update: Feb.23, 2001 Content Goal Energy sources, which may lead to CDE. Complexity of the different discharge modes. Possible
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
DDX 7000 & 8003. Digital Partial Discharge Detectors FEATURES APPLICATIONS
DDX 7000 & 8003 Digital Partial Discharge Detectors The HAEFELY HIPOTRONICS DDX Digital Partial Discharge Detector offers the high accuracy and flexibility of digital technology, plus the real-time display
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
GLOLAB Two Wire Stepper Motor Positioner
Introduction A simple and inexpensive way to remotely rotate a display or object is with a positioner that uses a stepper motor to rotate it. The motor is driven by a circuit mounted near the motor and
GenTech Practice Questions
GenTech Practice Questions Basic Electronics Test: This test will assess your knowledge of and ability to apply the principles of Basic Electronics. This test is comprised of 90 questions in the following
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,
Troubleshooting accelerometer installations
Troubleshooting accelerometer installations Accelerometer based monitoring systems can be tested to verify proper installation and operation. Testing ensures data integrity and can identify most problems.
Operational Amplifier - IC 741
Operational Amplifier - IC 741 Tabish December 2005 Aim: To study the working of an 741 operational amplifier by conducting the following experiments: (a) Input bias current measurement (b) Input offset
EXPERIMENT NUMBER 5 BASIC OSCILLOSCOPE OPERATIONS
1 EXPERIMENT NUMBER 5 BASIC OSCILLOSCOPE OPERATIONS The oscilloscope is the most versatile and most important tool in this lab and is probably the best tool an electrical engineer uses. This outline guides
Current Probes. User Manual
Current Probes User Manual ETS-Lindgren L.P. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS. What Is Tan δ, Or Tan Delta?
TAN δ (DELTA) CABLE TESTING OVERVIEW AND ANSWERS TO FREQUENTLY ASKED QUESTIONS What Is Tan δ, Or Tan Delta? Tan Delta, also called Loss Angle or Dissipation Factor testing, is a diagnostic method of testing
A Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
CHAPTER 11: Flip Flops
CHAPTER 11: Flip Flops In this chapter, you will be building the part of the circuit that controls the command sequencing. The required circuit must operate the counter and the memory chip. When the teach
Use and Application of Output Limiting Amplifiers (HFA1115, HFA1130, HFA1135)
Use and Application of Output Limiting Amplifiers (HFA111, HFA110, HFA11) Application Note November 1996 AN96 Introduction Amplifiers with internal voltage clamps, also known as limiting amplifiers, have
Application Note AN- 1095
Application Note AN- 1095 Design of the Inverter Output Filter for Motor Drives with IRAMS Power Modules Cesare Bocchiola Table of Contents Page Section 1: Introduction...2 Section 2 : Output Filter Design
Power-factor testing of rotating machinery is another valuable test
Feature Power-Factor Testing of Stator Winding Insulation: Understanding the Test Technique and Interpretation of Results Power-factor testing of rotating machinery is another valuable test technique providing
RADIANT PLASMA 4700 Plasma Spark Generator
RADIANT PLASMA 4700 Plasma Spark Generator Installation Guide / User Manual A S P A R K O F F R E S H A I R Aquapulser.com Contents 1 Introduction 2 1.1 About the Product....................................
ECEN 1400, Introduction to Analog and Digital Electronics
ECEN 1400, Introduction to Analog and Digital Electronics Lab 4: Power supply 1 INTRODUCTION This lab will span two lab periods. In this lab, you will create the power supply that transforms the AC wall
4 SENSORS. Example. A force of 1 N is exerted on a PZT5A disc of diameter 10 mm and thickness 1 mm. The resulting mechanical stress is:
4 SENSORS The modern technical world demands the availability of sensors to measure and convert a variety of physical quantities into electrical signals. These signals can then be fed into data processing
Amplifier for Small Magnetic and Electric Wideband Receiving Antennas (model AAA-1B)
Amplifier for Small Magnetic and Electric Wideband Receiving Antennas (model AAA-1B) 1. Description and Specifications Contents 1.1 Description 1.2 1.2 Specifications 1.3 1.3 Tested parameters in production
ABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
Balanced vs. Unbalanced Audio Interconnections
Revised 7/2/08 Balanced vs. Unbalanced Audio Interconnections In discussing the characteristics and performance of various interconnect systems; two points should be kept in mind. Balance is defined in
Design of Bidirectional Coupling Circuit for Broadband Power-Line Communications
Journal of Electromagnetic Analysis and Applications, 2012, 4, 162-166 http://dx.doi.org/10.4236/jemaa.2012.44021 Published Online April 2012 (http://www.scirp.org/journal/jemaa) Design of Bidirectional
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection
Wide Bandwidth, Fast Settling Difet OPERATIONAL AMPLIFIER
Wide Bandwidth, Fast Settling Difet OPERATIONAL AMPLIFIER FEATURES HIGH GAIN-BANDWIDTH: 35MHz LOW INPUT NOISE: 1nV/ Hz HIGH SLEW RATE: V/µs FAST SETTLING: 24ns to.1% FET INPUT: I B = 5pA max HIGH OUTPUT
High Voltage Power Supplies for Analytical Instrumentation
ABSTRACT High Voltage Power Supplies for Analytical Instrumentation by Cliff Scapellati Power supply requirements for Analytical Instrumentation are as varied as the applications themselves. Power supply
MODEL 2202IQ (1991-MSRP $549.00)
F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR
1. Oscilloscope is basically a graph-displaying device-it draws a graph of an electrical signal.
CHAPTER 3: OSCILLOSCOPE AND SIGNAL GENERATOR 3.1 Introduction to oscilloscope 1. Oscilloscope is basically a graph-displaying device-it draws a graph of an electrical signal. 2. The graph show signal change
WIRE AND CABLE ENGINEERING GUIDE
Excerpt From Prysmian s WIRE AND CABLE ENGINEERING GUIDE Page 1 of 8 CABLE TESTING Testing represents an integral part in the life of a cable. A cable will be subjected to multiple tests in its lifetime
A Perspective on On-line Partial Discharge Monitoring to Assess the Insulation Condition of Rotating Machine Stator Winding Insulation
A Perspective on On-line Partial Discharge Monitoring to Assess the Insulation Condition of Rotating Machine Stator Winding Insulation G.C. Stone Iris Power-Qualitrol Mississauga, Canada [email protected]
GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS
1/5/2006 Page 1 of 6 GENERAL POWER SYSTEM WIRING PRACTICES APPLIED TO TECNADYNE DC BRUSHLESS MOTORS 1. Introduction The purpose of this application note is to describe some common connection and filtering
Essential Electrical Concepts
Essential Electrical Concepts Introduction Modern vehicles incorporate many electrical and electronic components and systems: Audio Lights Navigation Engine control Transmission control Braking and traction
Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist.
Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist. Abstract. I have been asked to put together a detailed article on a SWR meter. In this article I will deal
Single Channel Loop Detector
Single Channel Loop Detector Model - LD100 Series The LD100 is a single channel inductive loop detector designed for parking and access control applications. The detector is connected to an inductive loop
IEC 1000-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays
IEC 00-4-2 ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays Application Note July 1999 AN9612.2 Author: Wayne Austin The SP720, SP721, SP723, and SP724 are protection
Type SA-1 Generator Differential Relay
ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes
Errors Due to Shared Leadwires in Parallel Strain Gage Circuits
Micro-Measurements Strain Gages and Instruments Errors Due to Shared Leadwires in Parallel Strain Gage Circuits TN-516 1. Introduction The usual, and preferred, practice with multiple quarterbridge strain
Episode 126: Capacitance and the equation C =Q/V
Episode 126: Capacitance and the equation C =Q/V Having established that there is charge on each capacitor plate, the next stage is to establish the relationship between charge and potential difference
Bridgeless PFC Implementation Using One Cycle Control Technique
Bridgeless PFC Implementation Using One Cycle Control Technique Bing Lu Center for Power Electronics Systems Virginia Polytechnic Institute and State University 674 Whittemore Hall Blacksburg, VA 24061
PCM Encoding and Decoding:
PCM Encoding and Decoding: Aim: Introduction to PCM encoding and decoding. Introduction: PCM Encoding: The input to the PCM ENCODER module is an analog message. This must be constrained to a defined bandwidth
A Multichannel Storage Capacitor System for Processing of Fast Simultaneous Signals. Atsushi Ogata. IPPJ-T-16 Oct. 1973
A Multichannel Storage Capacitor System for Processing of Fast Simultaneous Signals Atsushi Ogata IPPJ-T-16 Oct. 1973 A Multichannel Storage Capacitor System for Processing of Fast Simultaneous Signals
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 46 2007. Test Method for AC to DC Power Supplies
ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE 46 2007 Test Method for AC to DC Power Supplies NOTICE The Society of Cable Telecommunications Engineers (SCTE)
employed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
S/PDIF D/A Converter. User Manual. Rev.B, December 2011 Audial d.o.o Belgrade, Serbia www.audialonline.com, [email protected]
S/PDIF D/A Converter User Manual Rev.B, December 2011 Audial d.o.o Belgrade, Serbia www.audialonline.com, [email protected] IMPORTANT PRECAUTIONS 1. Do not expose this device to rain or moisture,
Technical Note Series
Technical Note Series SKIN CONDUCTANCE SENSOR (SA9309M) S TN0 0 0 8-0 0 S k i n C o n d u c t a n c e S e n s o r Page 2 IMPORTANT OPERATION INFORMATION WARNING Type BF Equipment Internally powered equipment
Output Ripple and Noise Measurement Methods for Ericsson Power Modules
Output Ripple and Noise Measurement Methods for Ericsson Power Modules Design Note 022 Ericsson Power Modules Ripple and Noise Abstract There is no industry-wide standard for measuring output ripple and
Frequency Response of Filters
School of Engineering Department of Electrical and Computer Engineering 332:224 Principles of Electrical Engineering II Laboratory Experiment 2 Frequency Response of Filters 1 Introduction Objectives To
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
Subject: Glenair MIL-PRF 24758 Conduit Surface Transfer Impedance Test
Lothar O. Hoeft, Ph.D. Consultant, Electromagnetic Effects 5012 San Pedro Ct., NE Albuquerque, New Mexico 87109-2515 Phone: (505)-889-9705 E-mail: [email protected] 1 February 24, 2006 Subject: Glenair
Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge
, Firenze, Italy Electrical tests on PCB insulation materials and investigation of influence of solder fillets geometry on partial discharge A. Bulletti, L. Capineri B. Dunn ESTEC Material and Process
BSNL TTA Question Paper-Instruments and Measurement Specialization 2007
BSNL TTA Question Paper-Instruments and Measurement Specialization 2007 (1) Instrument is a device for determining (a) the magnitude of a quantity (b) the physics of a variable (c) either of the above
Low Cost Pure Sine Wave Solar Inverter Circuit
Low Cost Pure Sine Wave Solar Inverter Circuit Final Report Members: Cameron DeAngelis and Luv Rasania Professor: Yicheng Lu Advisor: Rui Li Background Information: Recent rises in electrical energy costs
ARRL Morse Code Oscillator, How It Works By: Mark Spencer, WA8SME
The national association for AMATEUR RADIO ARRL Morse Code Oscillator, How It Works By: Mark Spencer, WA8SME This supplement is intended for use with the ARRL Morse Code Oscillator kit, sold separately.
Laboratory 4: Feedback and Compensation
Laboratory 4: Feedback and Compensation To be performed during Week 9 (Oct. 20-24) and Week 10 (Oct. 27-31) Due Week 11 (Nov. 3-7) 1 Pre-Lab This Pre-Lab should be completed before attending your regular
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
THE STRAIN GAGE PRESSURE TRANSDUCER
THE STRAIN GAGE PRESSURE TRANSDUCER Pressure transducers use a variety of sensing devices to provide an electrical output proportional to applied pressure. The sensing device employed in the transducers
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Contents. Document information
User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB
Zero voltage drop synthetic rectifier
Zero voltage drop synthetic rectifier Vratislav Michal Brno University of Technology, Dpt of Theoretical and Experimental Electrical Engineering Kolejní 4/2904, 612 00 Brno Czech Republic [email protected],
Precision, Unity-Gain Differential Amplifier AMP03
a FEATURES High CMRR: db Typ Low Nonlinearity:.% Max Low Distortion:.% Typ Wide Bandwidth: MHz Typ Fast Slew Rate: 9.5 V/ s Typ Fast Settling (.%): s Typ Low Cost APPLICATIONS Summing Amplifiers Instrumentation
+5 V Powered RS-232/RS-422 Transceiver AD7306
a FEATURES RS- and RS- on One Chip Single + V Supply. F Capacitors Short Circuit Protection Excellent Noise Immunity Low Power BiCMOS Technology High Speed, Low Skew RS- Operation C to + C Operations APPLICATIONS
Fundamentals of Signature Analysis
Fundamentals of Signature Analysis An In-depth Overview of Power-off Testing Using Analog Signature Analysis www.huntron.com 1 www.huntron.com 2 Table of Contents SECTION 1. INTRODUCTION... 7 PURPOSE...
Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox
HOME APPLICATION NOTES Iron Powder Cores for Switchmode Power Supply Inductors by: Jim Cox Purpose: The purpose of this application note is to cover the properties of iron powder as a magnetic core material
ON-LINE PARTIAL DISCHARGE MEASUREMENTS ON TURBINE GENERATORS. EXPERIENCE WITH STATER SLOT AND BUS COUPLER MEASUREMENTS
ON-LINE PARTIAL DISCHARGE MEASUREMENTS ON TURBINE GENERATORS. EXPERIENCE WITH STATER SLOT AND BUS COUPLER MEASUREMENTS H.G.SEDDING, Ontario Hydro; G.C STONE, Iris Power Engineering (Canada); A.PENAZIEV,
SINGLE-SUPPLY OPERATION OF OPERATIONAL AMPLIFIERS
SINGLE-SUPPLY OPERATION OF OPERATIONAL AMPLIFIERS One of the most common applications questions on operational amplifiers concerns operation from a single supply voltage. Can the model OPAxyz be operated
ELECTRON SPIN RESONANCE Last Revised: July 2007
QUESTION TO BE INVESTIGATED ELECTRON SPIN RESONANCE Last Revised: July 2007 How can we measure the Landé g factor for the free electron in DPPH as predicted by quantum mechanics? INTRODUCTION Electron
HIGH RELIABILITY POWER SUPPLY TESTING
HIGH RELIABILITY POWER SUPPLY TESTING Dale Cigoy Keithley Instruments, Inc. The reliability of a power supply must match or exceed the rest of the system in which it is installed. Generally, this requires
ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EEM 102 INTRODUCTION TO ELECTRICAL ENGINEERING EXPERIMENT 9: DIODES AND DC POWER SUPPLY OBJECTIVE: To observe how a diode functions
Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES APPLICATIONS PRODUCT OVERVIEW FUNCTIONAL BLOCK DIAGRAM
Isolated AC Sine Wave Input 3B42 / 3B43 / 3B44 FEATURES AC averaging technique used to rectify, amplify, and filter 50 Hz to 400 Hz sine-wave signals. Accepts inputs of between 20 mv to 550 V rms to give
www.jameco.com 1-800-831-4242
Distributed by: www.jameco.com 1-800-831-4242 The content and copyrights of the attached material are the property of its owner. LF411 Low Offset, Low Drift JFET Input Operational Amplifier General Description
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables
Two different types of cables are used in primary airfield lighting circuits: - unshielded cables and - shielded cables Classically both cables have a single AWG 8 copper conductor or a cross section of
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
Measuring Impedance and Frequency Response of Guitar Pickups
Measuring Impedance and Frequency Response of Guitar Pickups Peter D. Hiscocks Syscomp Electronic Design Limited [email protected] www.syscompdesign.com April 30, 2011 Introduction The CircuitGear
Application Note. So You Need to Measure Some Inductors?
So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),
Electrical Resonance
Electrical Resonance (R-L-C series circuit) APPARATUS 1. R-L-C Circuit board 2. Signal generator 3. Oscilloscope Tektronix TDS1002 with two sets of leads (see Introduction to the Oscilloscope ) INTRODUCTION
Cable Solutions for Servo and Variable Frequency Drives (VFD)
Cable Solutions for Servo and Variable Frequency Drives (VFD) Electric drive systems with continuous torque and speed control are widespread today. They allow an optimal adjustment of the drive with respect
Op-Amp Simulation EE/CS 5720/6720. Read Chapter 5 in Johns & Martin before you begin this assignment.
Op-Amp Simulation EE/CS 5720/6720 Read Chapter 5 in Johns & Martin before you begin this assignment. This assignment will take you through the simulation and basic characterization of a simple operational
DIGITAL-TO-ANALOGUE AND ANALOGUE-TO-DIGITAL CONVERSION
DIGITAL-TO-ANALOGUE AND ANALOGUE-TO-DIGITAL CONVERSION Introduction The outputs from sensors and communications receivers are analogue signals that have continuously varying amplitudes. In many systems
LM 358 Op Amp. If you have small signals and need a more useful reading we could amplify it using the op amp, this is commonly used in sensors.
LM 358 Op Amp S k i l l L e v e l : I n t e r m e d i a t e OVERVIEW The LM 358 is a duel single supply operational amplifier. As it is a single supply it eliminates the need for a duel power supply, thus
TIMING SIGNALS, IRIG-B AND PULSES
TIMING SIGNALS, IRIG-B AND PULSES Document No. PD0043200B July 2013 Arbiter Systems, Inc. 1324 Vendels Circle, Suite 121 Paso Robles, CA 93446 U.S.A. (805) 237-3831, (800) 321-3831 http://www.arbiter.com
Impedance Matching and Matching Networks. Valentin Todorow, December, 2009
Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines
An Ethernet Cable Discharge Event (CDE) Test and Measurement System
An Ethernet Cable Discharge Event (CDE) Test and Measurement System Wei Huang, Jerry Tichenor ESDEMC Technology LLC Rolla, MO, USA [email protected] Abstract A Cable Discharge Event (CDE) is an electrostatic
Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter
NTE2053 Integrated Circuit 8 Bit MPU Compatible A/D Converter Description: The NTE2053 is a CMOS 8 bit successive approximation Analog to Digital converter in a 20 Lead DIP type package which uses a differential
Transistor Amplifiers
Physics 3330 Experiment #7 Fall 1999 Transistor Amplifiers Purpose The aim of this experiment is to develop a bipolar transistor amplifier with a voltage gain of minus 25. The amplifier must accept input
Eatman Associates 2014 Rockwall TX 800-388-4036 rev. October 1, 2014. Striplines and Microstrips (PCB Transmission Lines)
Eatman Associates 2014 Rockwall TX 800-388-4036 rev. October 1, 2014 Striplines and Microstrips (PCB Transmission Lines) Disclaimer: This presentation is merely a compilation of information from public
MEASUREMENT SET-UP FOR TRAPS
Completed on 26th of June, 2012 MEASUREMENT SET-UP FOR TRAPS AUTHOR: IW2FND Attolini Lucio Via XXV Aprile, 52/B 26037 San Giovanni in Croce (CR) - Italy [email protected] Trappole_01_EN 1 1 DESCRIPTION...3
AS2815. 1.5A Low Dropout Voltage Regulator Adjustable & Fixed Output, Fast Response
1.5A Low Dropout oltage Regulator Adjustable & Fixed Output, Fast Response FEATURES Adjustable Output Down To 1.2 Fixed Output oltages 1.5, 2.5, 3.3, 5.0 Output Current of 1.5A Low Dropout oltage 1.1 Typ.
Lab 1: The Digital Oscilloscope
PHYSICS 220 Physical Electronics Lab 1: The Digital Oscilloscope Object: To become familiar with the oscilloscope, a ubiquitous instrument for observing and measuring electronic signals. Apparatus: Tektronix
Yamaha Power Amplifier. White Paper
Yamaha Power Amplifier White Paper August 2008 Table of Contents 1. About EEEngine...2 1.1. Introduction...2 1.2. Explanation of different amplifier topologies...2 2. Yamaha technology...5 2.1. Dual mono-amplifier
1. Learn about the 555 timer integrated circuit and applications 2. Apply the 555 timer to build an infrared (IR) transmitter and receiver
Electronics Exercise 2: The 555 Timer and its Applications Mechatronics Instructional Laboratory Woodruff School of Mechanical Engineering Georgia Institute of Technology Lab Director: I. Charles Ume,
KNX Powerline PL 110. KNX Association
KNX Powerline PL 110 Table of Contents 1 Introduction...3 2 Standardisation...3 3 Transmission Process...4 3.1 Phase Coupling...5 3.2 Telegram Transmission...6 3.2.1 Training Sequence...6 3.2.2 Preamble
A wave lab inside a coaxial cable
INSTITUTE OF PHYSICS PUBLISHING Eur. J. Phys. 25 (2004) 581 591 EUROPEAN JOURNAL OF PHYSICS PII: S0143-0807(04)76273-X A wave lab inside a coaxial cable JoãoMSerra,MiguelCBrito,JMaiaAlves and A M Vallera