Transformer Short Circuit Current Calculation and Solutions
|
|
|
- Franklin Lyons
- 9 years ago
- Views:
Transcription
1 Transformer Short Circuit Current Calculation and Solutions Ling Song Bachelor s Thesis Electrical Engineering Vaasa 2013
2 BACHELOR S THESIS Author: Degree Programme: Specialization: Supervisor: Ling Song Electrical Engineering Electrical Power Lars Enström Title: Transformer Short Circuit Current Calculation and Solutions Date Number of pages Appendices 14 June pages 0 page Summary There are three goals for the thesis. The first one is to introduce types of short-circuits. The second one is to introduce the transformer short-circuit current calculations. And the last one is to find suitable reinforcement methods for the transformers which are running now. Using a comparative approach to analytic research, the advantages and disadvantages of different reinforcement methods can be analyzed. The result shows that the neutral reactor is the best choice to reinforce the S/C withstand capability: low cost, easy maintenance, high technique maturity and so on. Language: English Key words: short-circuit, transformer calculation methods, short-circuit withstand capability
3 Table of the contents 1 Background Introduction to the short circuit phenomenon Needs of transformer short-circuit current calculation Symmetrical components Different kinds of short circuits DC circuits AC circuits Single-phase circuits Three-phase circuits Development of short-circuit current Calculation methods for transformers Single transformer model Practical calculation methods The calculation by the impedance method The calculation in grid network using symmetrical components Reinforcement of S/C withstand capability Installation of neutral reactors Installation of current limitation series reactors Installation of fast switches with high capacity Installation of controllable Fault Current Limiters The comparison Practical work applications The conclusion References... 29
4 List of figures Figure 1. Sequence components to represent the three-phase electrical system... 4 Figure 2. The current in an inductor... 6 Figure 3. The fault types... 9 Figure 4. The simple S/C circuit... 错 误! 未 定 义 书 签 Figure 5. The currents continue symmetrically...11 Figure 6. The currents continue asymmetrically...12 Figure 7. The Dyn11 transformer circuit...13 Figure 8. Various S/C currents in calculation done according to the impedance method...16 Figure 9. Neutral earthing reactor made by Hilkar...19 Figure 10. The neutral reactor on three-winding transformer (in red cycle)...20 Figure 11. Neutral earthing reactor made by ABB...20 Figure 12. Core-and-coil assembly of a series reactor (made by Siemens)...22 Figure 13. The Is-limiter process...24 Figure 14. Superconducting FCL (35 kv/90 MVA) made in China...25 Figure 15. Series controllable FCL schematic...26
5 List of Tables Table 1. Transformer S/C accidents in China ( )... 2 Table 2. Transformer S/C accidents in China ( )... 3 Table 3. The S/C current influenced by neutral reactors in Lanting Substation Table 4. The reinforcement methods of transformers S/C withstand capability... 26
6 ABBREVIATIONS S/C AC DC Emf HV LV MV SGCC short circuit alternating current direct current electromotive force high voltage low voltage medium voltage State Grid Corporation of China
7 1 1 Background 1.1 Introduction to the short circuit phenomenon A short circuit (S/C) in an electrical circuit is a part of the circuit that for some reasons has become shorter than it should be. The current in an electrical circuit flows the easiest way and if two points in a circuit with different potentials are connected with low electrical impedance the current is taking a shortcut between the two points. The consequences of an S/C can be everything from just a minor malfunction to a disaster. The consequences are dependent of the system ś capacity for driving current in an S/C situation and how long time the S/C current is allowed to flow. In almost every electric circuit there has to be some kind of protection against S/C currents. When circuits are analyzed mathematically, an S/C is usually described by zero impedance between two nodes in the circuit. In reality it is impossible that the impedance should be zero and therefore the calculations will not give the real value but in most cases the highest possible value. To get right results of a calculation it is also important to know all parameters of the circuit. Especially in S/C situations the behavior of the circuits are strange and there is no linearity between the voltage of the system and the current flowing. A short circuit may lead to an electric arc if the current driving capacity of the system is enough and protecting devices don t disconnect the circuit. The arc is a channel of hot ionized plasma that is highly conductive. Even short arcs can remove significant amount of materials from the contacting points. The temperature of the electrical arc is very high causing the metal on the contact surfaces to melt. /1/ Even in circuits where no visible arcs appear the S/C current often causes excessive heating of some part of the circuit. Short circuits can produce very high temperatures due
8 2 to the high power dissipation in the circuit. A practical example of heating due to a short circuit is arc welding. The power supply for an arc welder can supply very high currents that flow through the welding rod and the metal pieces being welded. The point of contact between the rod and the metal surfaces gets heated to the melting point, fusing a part of the rod and both surfaces into a single piece. /2/ 1.2 Needs of transformer short-circuit current calculation Today more than ever before, the electricity grid is developing so quick ly the power plant capacity, the substation capacity and electricity loads, as well as load density, sustainably grow. Take China as an example. The number of 500 kv substations in the North China power grid is almost 2 times higher than in the past decade. The number has grown from 48 to 97; the substation capacity has increased from 52,069,000 kva to 157,960,000 kva. /3/ As a result, the short-circuit currents in the power grid increase year by year. Based on the statistical analysis of the State Grid Corporation of China (SGCC) /4/, /5/, the S/C current accidents of power transformers (Size 110 kv) happened 125 times. The total power capacity influenced by the S/C accidents is 7,996 MVA in 1995~1999. The number represents 37.5% of all power accidents and 44% of the transformers accidents. The details are shown in Table 1 and Table 2. Table 1. Transformer S/C accidents in China ( ) year Total Accident times S/C accident times The rate 49.2% 50% 38.2% 41.3% 40.8% 44%
9 3 Table 2. Transformer S/C accidents in China ( ) year a Total Accident times S/C accident times The rate (%) 33.3% 32.1% 37.5% 39.6% 44.4% 36.6% a) The total number of transformers decreased in 2005 because of the reshuffle of the electrical enterprises. Some transformers weren t calculated in this table There are some examples of the transformer S/C accidents. The first one happened in Stone Road Substation in Hubei Province. The results are electricity power losses of kwh and direct economic losses of about 140,000 euros. /6/ A second accident happened in Riverside Substation in Kaifeng City, Henan Province in1998. The transformer in the S/C accident was 110 kv, S N =31500 kva. The S/C current which it encountered was 1288 A, about 1.3 ka /7/. Not only in China, but also in other countries, the percentage of S/C accidents is high. The transformers whose capacities are greater or equal to 2500k VA encounter 199 S/C accidents in the total 898 tests in high power laboratories in Korea, Sweden, Great Britain, Italy, Poland, Holland, Brazil, India, Rumania, South Africa, Russia, Mexico, the Czech Republic and Germany. The fail rate is 22%. In Canada, the rate of S/C accidents is 33 % of transformers whose capacities are 2501~4000 kva, the fail rate for transformers which are greater than 4000 kva is 25%. /8/ The S/C current is an important specification and standard for equipment and conductors in the power industry, and S/C current withstand capability of the main devices decides whether the grid could run more safely or not. So it s significant to calculate the S/C current and offer some possible solutions. The calculation can help us to 1) specify fault ratings for electrical equipment (e.g. short circuit withstand ratings) 2) help identify potential problems and weaknesses in the system and assist in system planning 3) form the basis for protection coordination studies /9/
10 4 So, it is not only the S/C calculation methods that are necessary but also the power transmission and the transformation devices should be equipped with better withstand ability for the higher S/C currents. 1.3 Symmetrical components In the practical work, engineers often use symmetrical components to analyze the three-phase power system. It was invented by a Canadian electrical engineer Charles L.Fortescue in Mr Fortescue s original purpose was to analyze the operation of the electrical motors. The theory was not used for the power system until The analytical technique was adopted and advanced by engineers at General Electric and Westinghouse and after World War II it was an accepted method for asymmetric fault analysis. Now it s a common tool used to analyze the faults of three-phase power system. /10/ The basic setting for the theory is that any unbalanced system quantities (current or voltage) could be decomposed into 3 symmetrical sets of balanced vectors: positive sequence components, negative sequence components and zero sequence components. Figure 1. Sequence components to represent the three-phase electrical system /11/ The positive sequence component of the current shown in Figure 1 is balanced in magnitude with a 120 degree phase separation and counter-clockwise rotation, just like the original balanced system. The negative sequence component of the current is
11 5 balanced in magnitude with a 120 degree phase separation, but has the opposite rotation, in this case, clockwise. The zero sequence components have equal magnitudes, but zero phase separation. Here, we denote the positive sequence with the subscript 1. Likewise, the negative sequence is denoted with the subscript 2 and the zero sequence is denoted with the subscript 0. Under a no fault condition, the power system is considered to be essentially a symmetrical system and therefore only positive sequence currents and voltages exist. At the time of a fault, positive, negative and possibly zero sequence currents and voltages exist. Using real world phase voltages and currents along with Fortescue s formulas, all positive, negative and zero sequence currents can be calculated. Protective relays use these sequence components along with phase current and/or voltage data as the input to protective elements. /12/
12 6 2 Different kinds of short circuits 2.1 DC circuits What circuit information is needed to do an S/C calculation for a DC circuit? In an electrical circuit the current is dependent of the electromotive force (emf), the electromagnetic field, and the total impedance of the circuit. In a battery the emf-value is dependent of the charge of the battery. The internal impedance of the battery is also a changing parameter and dependent of the charge, the temperature, and the age of the battery and so on. In a DC circuit the resistance is the current limiting factor together with the emf in steady-state which means after a while. In the beginning of a transient, like an S/C situation, also the inductance of the circuit is limiting. Any inductance in the circuit will smooth up the rise of the current. The current is increasing exponentially due to the relation between the inductance and the resistance of the circuit. Figure 2. The current in an inductor /13/ Direct current causes different problems from AC when trying to interrupt high value currents since the arc extinction is more difficult. AC passes through zero every half period thus helping the breaking of current. A circuit breaker for a certain AC current is usually not able to break the same magnitude of DC current. The difficulties of breaking a DC
13 circuit increases with the ratio of inductance versus resistance in the circuit. Inductances are always in opposition to changes of current AC circuits Alternating current circuits (AC) are more complex to solve than direct current circuits (DC). There are more parameters affecting the results and in fast changing situations the first values of current are strongly dependent of the phase of the active voltage source Single-phase circuits Most large power networks are three-phase but especially in low voltage systems most of the connected circuits are single-phase. When calculating S/C currents the situation is dependent on how near the generator or transformer the fault occurs. Not only due to the increasing impedance in the end of the network but also to the fact that generators and transformers are acting strange when they are not loaded symmetrically in all phases. In some cases the circuit may be fed from a single-phase transformer with a current carrying capacity that is not enough to make the three-phase system behave strange. The fact that the S/C current is easier to calculate far from a transformer or a generator is because the line impedances are playing an important role in the process and the impedances are often easier to know than the voltage in the beginning of the circuit. With longer lines the currents decreases and the voltage from the source will not change very much. In single-phase low voltage circuits that are commonly used in households the S/C currents must be disconnected for different reasons. One reason is because of the touch voltage that may occur during a contact between phase and protective earth. The protective earth in a circuit is used to prevent exposed conductive parts from getting a dangerous potential referred to earth. When a direct contact between phase and exposed conductive parts is established by a fault situation the potential will rise to a dangerous level for persons to touch and therefore the circuit must be disconnected by protection devices like fuses and circuit breakers. In household situations the maximum time for disconnection is normally 0.4 seconds.
14 8 To access the clearance time under fault conditions the prospective fault current must be determined by measurement or calculation. It is the prospective current that will flow when the end of the cable being protected is connected to the protective earth conductor that is of concern. With long cable runs this prospective current can be found to be comparatively low. It should be remembered however that the first problem with long cable runs is the possibility of excessive voltage drop, and cables should be selected first for current rating, and then checked for voltage drop before determining the fault prospective. /14/ Three-phase circuits Three-phase electric power is a common method of AC electric power generation, transmission, and distribution. It is a type of poly-phase system and is the most common method used by electrical grids worldwide to transfer power. It is also used to power large motors and heavy loads. A three-phase system is usually more economical than an equivalent single-phase or two-phase system at the same voltage because it uses less conductor material to transmit electrical power. The three-phase system was independently invented by Galileo Ferraris, Mikhail Dolivo-Dobrovolsky and Nikola Tesla in the late 1880s. /15/ Most single-phase circuits are just a part of a three-phase network. In a three-phase system various types of S/C can occur. For example, S/C current can be phase-to-earth (80% of faults), phase-to-phase (15% of faults this type of fault often degenerates into a three-phase fault) and three-phase (only 5% of initial faults). These different short-circuit currents are shown in Figure 3. In China, there is another rough classification which is based on the number of the fault phase: three-phase fault, double-phase fault and single phase fault due to phase-to-earth fault which may happen for two phases. The primary characteristics of short-circuit currents are: 1) Duration: The current can be self-extinguishing, transient or steady-state 2) Origin: it may be caused by mechanical reasons (break in a conductor, accidental
15 9 electrical contact between two conductors via a foreign conducting body such as a tool or an animal), internal or atmospheric overvoltage, and insulation breakdown due to heat, humidity or a corrosive environment 3) Location (inside or outside a machine or an electrical switchboard) Figure 3. The fault types /16 / The consequences of S/C are depending on the type and duration of the fault and the short-circuit power available. Locally at the fault point there may occur electrical arcs causing damage to insulation, welding of conductors and fire. On the faulty circuit, electro dynamic forces may result in deformation of bus bars and cables and the excessive temperature rise may damage insulation. Other circuits in the network or in nearby networks are also affected by the short-circuit situation. Voltage drops occur in other networks during the time of S/C and shutdown of a part of a network may include also healthy parts of the network depending on the design of the whole network.
16 Development of short-circuit current A simplified AC network can be represented by a source of AC power, some kind of switching device, a total impedance Z N that represents all the impedances upstream of the switching point and a load, represented by its impedance (see figure 4). In a real network the total impedance Z N is made up of the impedances of all components upstream. The components are for example generators, transformers, wires, circuit-breakers and metering systems. When a fault with negligible impedance occurs between A and B a short-circuit current limited only by Z N flows in the circuit. The short-circuit current I sc develops under transient conditions depending on the relation between inductances and resistances in the whole circuit. If the circuit is mostly resistive the waveform of the current is following the waveform of the voltage but if there are inductances in the circuit the waveform of the current will differ from the waveform of the voltage during a transient time of the process. In an inductive circuit the current cannot begin with any value but zero. The influence of inductances is described by reactance X in AC circuits with a fixed frequency of the voltage. In low voltage systems where cables and conductors represent most of the impedance it can be regarded as mostly resistive. In power distribution networks the reactance is normally much greater than the resistances. Generally the total impedance Z in steady-state in an AC circuit is made up of the total resistance R and the total reactance X as the following relation shows. 2 2 Z R X
17 11 Figure 4. The simple S/C circuit In the simplified circuit above the voltage is constant and so is the total impedance. In faults far from generators and transformers where most of the impedance consists of impedances from wires the calculations can be done with a good result and the transient current is almost the same as if the current would flow for a longer time. The meaning of far from is not necessarily physical but means that generator or transformer impedances are less than the impedance of the elements from wires. The impedance elements from wires are constant at a constant temperature but the impedances of generators vary during a short-circuit and the impedances of transformers change if the transformers are asymmetrically loaded with high currents. Figure 5. The currents continue symmetrically Figure 5 shows the current in beginning of a short-circuit far from the generator. The short-circuit starts at a moment when the current normally is zero and continues symmetrically.
18 12 Figure 6. The currents continue asymmetrically Figure 6 shows the current when the short-circuit starts at a moment when the voltage is zero and the current is also starting from zero but asymmetrically during a transient time.
19 13 3 Calculation methods for transformers In Chapter 1, the data show the importance of transformer S/C current calculations and introduce the symmetrical components theory briefly. Let s discuss the calculation methods on the basis of two single transformer models in Chapter Single transformer model In this section, I will begin with two examples: Figure 7. The Dyn11 transformer circuit Example 1: one transformer which has S N =100 kva, Dyn11 connection. The transformation rate is V/ 410 V. P 0 =220 W, P k =1485W, Z k =3.8%, Z 0 =3.8%. The calculation of its S/C current is as follows: The rated currents: I 1N =S N /( 3*U 1N ) = / (1.732*20500) = 2.82 A I 2N =S N /( 3*U 2N ) = / (1.732*410) = A The impedance: = 0.038* /100000=63.88 mω = 1485/ (3* )=24.97 mω Since we have,
20 14 = = 58.8 mω If U 1 =U 1N =20500V, the three-phase S/C at the terminals will be: = U 2N / ( * ) = 410/ (1.732*0.0639) = A 3700 A In the single phase fault accidents, the current will not change if it s the phase-neutral case. But the performance of the transformer will be abnormal. In special cases, the current may be greater (Yzn). If the transformer is Dyn connected, the single phase current will be less than the three-phase current. Example 2: a power transformer which has S N = 63 MVA. The transformation rate is 110 kv/ 21 kv. P 0 =32.0 kw, P k =210 kw, Z k =12%. Calculate the short-circuit current. The calculation of its S/C current is as follows: I 1N =S N /( 3*U 1N ) = 63*10 6 / (1.732*110k) = A I 2N =S N /( 3*U 2N ) = 63*10 6 / (1.732*21k) = 1732 A The impedance: = 0.12* (21*10 3 ) 2 /(63*10 6 )=23.05 Ω =0.12* (110*10 3 ) 2 /(63*10 6 )=0.840 Ω Short circuit current with nominal voltage (three-phase symmetrical) = U 1N / ( * ) = 110*10 3 / (1.732*23.05) = 2755 A = U 2N / ( * ) = 21*10 3 / (1.732*0.840) = 14.43k A There is always a voltage drop in the upstream network. That means that the voltage will be lower than the nominal voltage when the S/C accident happens.
21 Practical calculation methods The practical calculation methods are more complex than the simple model. There are two types: calculating S/C current by the impedance method and the calculation in grid network using symmetrical components The calculation by the impedance method The impedance method, reserved primarily for LV networks, was selected for its high degree of accuracy and its instructive value, given that virtually all characteristics of the circuit are taken into account. Figure 5 shows the various S/C currents. The three-phase S/C involves all three-phases. Short-circuit current I sc3 is equal to: I sc3 =U / 3/ Z sc, where U (phase-to-phase voltage) corresponds to the transformer no-load voltage which is 3 to 5% greater than the on-load voltage across the terminals. In fact, this is the positive-sequence impedance per phase in the symmetrical components theory. It is generally considered that three-phase faults offer the highest fault currents. Phase-to-phase S/C without earthing is the fault between two phases which is supplied with a phase-to-phase voltage U. The formula is: I sc2 =U / 2 Z sc.
22 16 Figure 8. Various S/C currents in a calculation done according to the impedance method The third fault type is Phase-to-neutral S/C without earthing. This is a fault between one phase and the neutral, supplied with a phase-to-neutral voltage: U f U 3 The calculation formula is: I sc1 = Z U f Z sc Ln. The final fault is Phase-to-earth fault (one or two phases). This type of fault brings the zero-sequence impedance Z 0 into play. Except when rotating machines are involved (reduced zero-sequence impedance), the S/C current I sc0 is less than that of a three-phase fault. Calculation of I sc0 may be necessary, depending on the neutral system (system earthing arrangement), in view of defining the setting thresholds for the zero-sequence (HV) or earth fault (LV) protection devices.
23 The calculation in grid network using symmetrical components A calculation using symmetrical components is particularly useful when a three-phase network is unbalanced. This is based on IEC (2001, c2002), "S/C currents in three-phase AC systems - Part 0: Calculation of currents" and uses the impedance method (as opposed to the per-unit method). /17/ Generally speaking, there are six general steps in the calculation: Step 1: Construct the system model and collect the relevant equipment parameters. Step 2: Calculate the short circuit impedances for all of the relevant equipment. Step 3: Refer all impedances to the reference voltage. Step 4: Determine the Thévenin equivalent circuit at the fault location. Step 5: Calculate balanced three-phase short circuit currents. Step 6: Calculate single-phase to earth short circuit currents. The relevant equipment parameters to be collected are as follows: 1) Network feeders: fault capacity of the network (VA), X/R ratio of the network; 2) Synchronous generators and motors: per-unit sub-transient reactance, rated generator capacity (VA), rated power factor (cosφ); 3) Transformers: transformer impedance voltage (%), rated transformer capacity (VA), rated current (A), total copper loss (W); 4) Cables: length of cable (m), resistance and reactance of cable (Ω/km); 5) Asynchronous motors: full load current (A), locked rotor current (A), rated power (W), full load power factor, starting power factor. 6) Fault limiting reactors: reactor impedance voltage (%), rated current (A). When we apply this way of calculating into the practical work to obtain accurate results, we must also consider the following factors: S/C currents of the substation bus, S/C currents of the short line fault (SLF: A short-line-fault is a fault that occurs on a line a
24 18 few hundred meters to several kilometers down the line from the circuit breaker terminal /18/ ), the marked data of the transformer and output of the power unit, even the temperature and the running style of the system(maximum load/ minimum load) and so on.
25 19 4 Reinforcement of S/C withstand capability There are many methods applied to reinforce the S/C withstand capability of the transformers: improvement of the materials, reforming of the design and good maintenance in the operation process and so on. However, what I want to mentioned here is methods for the transformers which are in use and those which are hard to modify or expensive to modify. 4.1 Installation of neutral reactors Usually, the probability of power systems encountering single phase S/C accidents is much higher than the probability of power systems encountering three-phase S/C accidents. The reinforcement of the S/C withstand capability for the transformers can, to a great degree, reduce the ruin of an S/C accident. The single phase S/C current is affected by the positive sequence impedance and zero sequence impedance. One effective way to change the zero sequence impedance is changing the earthing methods of transformer neutral points, or installing the neutral grounding reactor. /19/ Figure 9. Neutral earthing reactor made by Hilkar Neutral grounding reactors are used for low-impedance grounding of the neutral point of three-phase networks in order to limit the fault current in the event of a phase-to-ground S/C (fault current will be limited to the level of the phase-to-phase S/C current). One reactor terminal is connected to the neutral of the network and the other terminal is
26 20 grounded. During normal operation of the power system the current flow through the reactor is almost zero, since it is only driven by the imbalance of the thre e-phase network. Figure 10. The neutral reactor on three-winding transformer (in red cycle) /20/ The ordinary installation place of the neutral reactor is in the compensation equipment called HV shunt reactor. In China, people often use the star connection for the HV shunt reactor, and then add a reactor in series at the neutral point of the star connection. That s so called high-voltage reactor grounding through small reactance at the neutral point. The functions of reactors here are to compensate the phase to phase capacitor and grounding capacitor, speed up the termination of the secondary arc current and to make it easier to adopt the single-phase reclosers. /21/ Figure 11. Neutral earthing reactor made by ABB /22 / One application example happened in 2004, in Ningbo City, Zhejiang Province,China. Engineers installed little reactors which are 15 Ω as the neutral earthing reactor for a 500kV transformer in Lanting Substation. The S/C current decreased. The details are shown in Table 3
27 21 Table 3. The S/C current influenced by neutral reactors in Lanting Substation Single phase S/C current 3 phase S/C current without reactor (ka) with reactor(ka) When the neutral points connect with reactors, the zero sequence impedance will change. The grounding S/C current of double phases may be larger than that of the single phase. So it s necessary to check both the single phase S/C and double phases S/C after the installation of a neutral reactor. 4.2 Installation of current limitation series reactors The series reactor is a high-voltage electrical apparatus designed to limit the current of a short circuit and maintain adequate voltage on the buses of distribution switchgear during a short circuit in a network. It consists of an inductance coil. Such reactors are also used to compensate reactive power in order to improve the transmission capacity of power lines. /23/ The use of reactors is a traditional and commonly used method for the limitation of the S/C current. The reactors are usually installed at the areas where the short-line-fault may happen and connect in series in the circuits which require a limit to the S/C current. The principle is decreasing S/C currents by increasing the impedance of the circuits. The advantage is that it s easier to install and run in safe and reliable ways. The disadvantage is that the reactor will increase the losses of power. It may influence the stability of the power system. /24/
28 22 Figure 12. Core-and-coil assembly of a series reactor (made by Siemens) The current limitation series reactor is usually applied at outlets of the LV side, and can also be applied at the 35 kv medium side in 220 kv transformer. This method is suitable for both three phase S/C and single phase S/C. The example is ABB. They build a series reactor for the Metro Grid project which transfers the power from Sydney South to Haymarket Substation in Australia. It s the biggest reactor made by ABB Installation of fast switches with high capacity The representatives of fast switches with high capacity are Is-limiter (made by ABB), Pyristor (made by Ferraz) and C-Lip (made by G&W) /26/. This kind of switches can protect electric devices from larger S/C current shocks and prevent large-area electricity black-outs caused by the destruction of main equipment due to overcurrent. It has several advantages in the technical field: 1) Fast cut off ability (less than 2ms); 2) Fast limitation of the large S/C current: Is-limiter is capable of detecting and limiting an S/C current at the first rise, i.e. in less than 1ms /27/.
29 23 3) Less occupied space 4) Easy to install and maintain It is a fault current limiting device that uses chemical charges and current-limiting fuses to interrupt the fault current within the first quarter to half cycle (i.e. before the first peak). In a typical Is-limiter design, the device is composed of two current paths connected together in parallel one path is an element rated for the full load current (which can have high continuous current ratings, e.g A), and the other path provides the current limiting function via a current-limiting fuse (which typically has a continuous current rating of <300 A at 15 kv). /28/ The work principle can be described as follows: when the S/C happens, the current transformer module detects the signal and transfers it to the control module. Then the control module is triggered and turns the disconnector on to move the S/C current into the fuse module at the instant. Here, the current is cut off. The interesting thing and special feature is that the device uses the explosive to get the rapid cut-off ability. It can limit both S/C currents of single phase and three-phase. /29/ Figure 11. ABB Is-limiter insert holder with insert for 12 kv, 2000 A The working process can be described as follows:
30 Figure 13. The Is-limiter process 24
31 Installation of controllable Fault Current Limiters Fault Current Limiter (FCL) is also called S/C Current Limiter (SCCL). There are several different types: Superconducting Fault Current Limiter (SFCL), the one we mentioned in section 4.3, and the controllable Fault Current Limiter which is based on electronic technology and so on. /30/ Figure 14. Superconducting FCL (35 kv/90 MVA) made in China The shortcomings of a superconducting fault current limiter are 1) The working environment is quite harsh: the high-temperature superconductor needs liquid nitrogen (N 2 ). The critical temperature is 77 K (about -196 ). And the low-temperature superconductor needs liquid nitrogen liquid helium (He). The critical temperature is 4 K (about ). Once the working temperature is over the critical temperature, the SFCL will not able to keep the superconductor character. 2) The technique is not mature enough. In China, there are only two prototypes running. The number of SFCLs which are running in Switzerland, Germany, Great Britain and USA is less than 20. So it s not suitable to be applied for modifying the transformers that are running now. However, the controllable Fault Current Limiter based on electronic technology is more mature than SFCL. There are two types: series and parallel. The operation principle is: use the electronic apparatuses to break or connect the circuit with high speed. Then the capacitor, the resistance, or the inductance in series or in parallel at bypass works immediately to increase impedance of the circuit in order to limit the S/C current. /31/
32 26 As an example, see the figure below: Figure 15. Series controllable FCL schematic The controllable FCL shown is the series type. It consists of the capacitor (C), the inductance (L) and a bypass switch (K). Normally, the switch doesn t work and it s open. L and C work on the series resonance condition. The impedance could be regarded as zero, compared with the total impedance. So the influence of FCL could be acceptable. When accidents are detected, K receives the command and closes to take C away instantly. The inductance (L) begins to limit the current at the moment, so that the fault current is limited. The advantages are: 1) no influence on the protection solution being used; 2) no influence on the stability of the current; 3) Less occupied space. The weaknesses are high cost and the maintenance. 4.5 The comparison The table below is the comparison of 4 methods: Table 4. The reinforcement methods of transformers S/C withstand capability neutral reactors series reactors fast switches Controllable FCLs The cost low normal low high Project time short short short normal The limitation objects only single phase both both both Technical maturity high high normal low Space little little quite little large Maintenance easy easy easy hard
33 Practical work applications Based on the above materials, the technical handbooks (GB , GB and GB ) and the experience of electrical engineers of SGCC, some practical work applications are offered. In the practical work, the risk of three-phase S/C accidents at the MV side of 500 kv and 220 kv transformers is quite little; the main risk is the single phase accident. The reinforcement of S/C withstand capability of the single phase or the limitation of the S/C current at the single phase can reduce the number of transformer S/C accidents significantly. In Table 4, we can find that the new devices work more effectively and respond much faster, but they are defeated by the traditional ways in the economy, the reliability, the maturity and the maintenance experience. So the best selection is to install the neutral reactor. If there does exist the need for three-phase protection, we can install the fast switch or FCL. For the LV side accident, people can opt to install current limitation series reactors, or fast switches if the space is limited.
34 28 5 The conclusion The thesis introduces the definition and the importance of S/C current calculations. Chapter 2 introduces the type of the fault circuits and calculation methods from basic DC circuits to AC circuits. In Chapter 3, I discuss transformers S/C calculation methods. In Chapter 4, based on the comparison of different breakers, I offer some reinforcement methods for the transformers which are running now. The deficiency of the work is the lack of knowledge of practical calculation methods, especially in the symmetrical components field. For this reason, Chapter 4 is not that satisfactory. The reinforcement methods of the S/C withstand capability only mention the devices for the working transformers. In fact, good maintenance can also reduce the number of S/C accidents.
35 29 6 References /1/ Short circuit (n.d.) (retrieved: 22 February 2013) /2/ What is a short circuit?(n.d.) (retrieved: 09 June 2013) /3/ North China Power Grid achieved double growth in "Eleventh Five-Year"(2011) (retrieved: 02 March 2013) /4/ Wang,M,Y. (2001) Fault Statistics & Analysis All Transformer Types in China. Electrical Equipment, 49(1), p /5/ Wang,M,Y. (2006) Fault Statistics & Analysis All Transformer Types in China. Electrical Devices, 37(2), p.4-13 /6/ the analysis of two transformers S/C accidents (retrieved: 12 June 2013) /7/ Wang,M,Y. (2001) Fault Statistics & Analysis All Transformer Types in China. Electrical Equipment, 49(1), p /8/ Zhang,K,L. (2001). Improve the ability of large power transformer short-circuit resistance measures. FUJIAN DIANLI YU DIANGONG, 1(3), p.8. /9/ According to the IEC (n.d.) _calculation.3f (retrieved: 06 May 2013) /10/ Symmetrical components (n.d.) (retrieved: 06 April 2013) /11/ Lee,L. (2012). Symmetrical Components. Phdengineer (retrieved: 06 April 2013) /12/ Protection Basics: Introduction to Symmetrical components (n.d.) (retrieved: 20 April 2013) /13/ Ac_theory_module 4 (n.d.) (retrieved: 11 June 2013) /14/ Another step in electrical safety (n.d.) (retrieved: 10 June 2013) /15/ Three-phase electric power(n.d.) (retrieved: 10 June 2013)
36 30 /16/ Calculation of short-circuit currents (n.d.) gineering/electrical-know-how/low-voltage-minus-1kv/ect158.pdf (retrieved: 21 May 2013) /17/ According to the IEC (n.d.) Methodology (retrieved: 08 May 2013) /18/ Short-line-fault (n.d.) (retrieved: 22 May 2013) /19/ Zhang,F,J. & Wu,Z,Y. (2009). Application actualities and development of short-circuit limiting technique for power system. Guangdong Electric Power, 22(2), p /20/ the neutral reactor (n.d.) (retrieved: 16 May 2013) /21/ Han,L.&Qiu,W,D.& Xiao,Zh,L.(2009). Overview on measures of short-circuit limiting technique on power system. Electric Power Technologic Economics, 21(3), p /22/ Neutral Earthing reactor (n.d.) (retrieved: 08 June 2013) /23/ Series Reactor (n.d.) (retrieved: 15 May 2013) /24/ Lin,Y. (2010) Application of short-circuit current limitation technologies for 500kV power system in Guangdong Grid. North China Electric Power, Mechanical & Electrical Engineering Techbology, 39(9), p /25/ ABB_Australia. (2006). ABB Capability Guide 451ece31b4c482573ea001f8711/$FILE/AUABB%20Capability%20Guide_LR.pdf (retrieved: 18 May 2013) /26/ Zhang,L. & Guo,Q. & Zeng,L,D& Dai,C. (2011). High-Capacity Explosive High-Speed Interrupted Mechanism for Independent Power System. Journal of Naval Aeronautical and Astronautical University.26 (5), p /27/ Is-Limiter (n.d.) 8e083/$file/2493%20Is-Limiter%20GB.pdf (retrieved: 20 May 2013) /28/ IS Limiter (n.d.) (retrieved: 18 May 2013) /29/ Han,G. & Han,L. & Wu,L. (2010) Application and development of methods on limiting power grid s short-circuit current. Power System Protection and Control, 38(1), p /30/ He,Zh,Q. & Gao,W,L. (2010). Analysis on restrictive measures against short-circuit current of 220kV Chongqing power grid. Central China Electric Power, 23(2), p
37 /31/ Electric Power Research Institute of China(2011). The Principle of FCLs and Applications Controllable FCLs. Electric Power Research Institute Internal document 31
SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS
Bachelor's Thesis Electrical Engineering June 2014 SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS MD FARUQUL ALAM SALMAN SAIF HAMID ALI School of Engineering Blekinge Tekniska
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
7. Reactive energy compensation
593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical
Power transformers. Special transformers Railway
Power transformers Special transformers Railway A leader in railway systems Our compact and low-weight transformers fully comply with the customer s specifications. The products are developed together
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Power Quality Paper #3
The Effect of Voltage Dips On Induction Motors by: M D McCulloch 1. INTRODUCTION Voltage depressions caused by faults on the system affect the performance of induction motors, in terms of the production
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
AMSC s Superconductor Cable Technologies for Electric Utilities
International Workshop 2014 AMSC s Superconductor Cable Technologies for Electric Utilities Michael Ross, P.E. Managing Director of Superconductor Power Systems AMSC Corporate Facts Headquartered in MA,
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Transformers. Special transformers Reactors products
Transformers Special transformers Reactors products Reactors Custom designed, custom built ABB Oy Transformers has extensive experience and numerous references from different reactor applications, having
TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer
168-08 TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE APPARATUS A three-phase outdoor oil-immersed distribution transformer DESIGNATION 1000 kva SERIAL No. 1-08-112-01-0001 Rated power Rated voltage
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
How To Understand And Understand The Theory Of Electricity
DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating
MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 20 24 Apr $3,750 Dubai, UAE In any of the 5 star
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the
Electrical network protection. Protection guide. Guide
Electrical network protection Protection guide Guide A new path for achieving your electrical installations A comprehensive offer The Protection Guide completes the perfectly coordinated offer of products
HIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
Permissible ambient temperature Operation Storage, transport
The Sitras PRO combined DC protective unit and controller is used in the power supply for DC railways in mass transit and main-line systems up 3,000 V DC. It protects DC switch gear and contact line systems
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS
SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS Claudio S. Mardegan [email protected] www.engepower.com Phone: 55 3579-8777
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
The Intelligent AX1 Switchgear for Medium Voltage
The Intelligent AX1 Switchgear for Medium Voltage Leif Lundin, Manager of Research and Development, Division Medium Voltage and Compact Substations, ABB Distribution, Sweden Abstract The newly launched
DIRECT CURRENT GENERATORS
DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle
Critical thin-film processes such as deposition and etching take place in a vacuum
WHITEPAPER INTRODUCING POWER SUPPLIES AND PLASMA Critical thin-film processes such as deposition and etching take place in a vacuum SYSTEMS chamber in the presence of a plasma. A plasma is an electrically
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to
Electrical network protection. Protection guide. Guide 2003 51G 51G 51G 51G 51G. network protection solutions
Electrical network protection Protection guide Guide 2003 5 A H G G 4 D3 D2 D1 G G G 3 network protection solutions Protection guide Contents 0 Presentation 2 Power-system architecture Selection criteria
DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION
ÿþ üûúùø öõöôùóùõò CT Dimensioning DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION Application note GER3973 1 CT Dimensioning ÿþ üûúùø öõöôùóùõò GER-3973 Application note ÿþ üûúùø öõöôùóùõò
INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
Lab 14: 3-phase alternator.
Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
How To Understand The Electrical Power Supply Of A Power Supply System
17 Circuit diagram symbols E 18 CIRCUIT DIAGRAM SYMBOLS electrical network elements three-phase line or cable single-phase line or cable short circuit earth electrode outgoing feeder supply incoming feeder
IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution
IEC and IEEE Standards for High-Voltage Switchgear and Controlgear Present Situation and Future Evolution Denis Dufournet Chairman IEC TC 17 & SC17A Fellow IEEE Senior Expert Areva T&D Mumbai, January,
Introduction to Short Circuit Analysis
www.pdhcenter.com PDH Course E04 www.pdhonline.org Introduction to Short Circuit Analysis Course Content A short circuit is a low-resistance connection established by accident or intention between two
SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS
Sawsan Henein AIT Austrian Institute of Technology Electric Energy Systems Research Group SIMULATING HYBRID ENERGY GRIDS IN SMART CITIES FOCUS ON ELECTRIC ENERGY SYSTEMS Sustainable Places 2015 Savona,
Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards
Guide to the electrical parameter classifications of IEC 60950 and IEC 62368 safety standards Abstract This Guide is an informative listing of selected terms and definitions found in IEC Glossary entry
Hyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
Cahier technique no. 158
Collection Technique... Cahier technique no. 158 Calculation of short-circuit currents B. de Metz-Noblat F. Dumas C. Poulain Building a New Electric World "Cahiers Techniques" is a collection of documents
21 st Century Facilities
Electrical Testing 21 st Century Facilities Facility Owners face tough challenges 24 X 7 reliability needed Non linear loads cause harmonics VFD Computers Switching transients disrupt operations Less customer
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
Fuse Selection Guide
Fuse Selection Guide Although care is taken to properly design electrical and electronic circuits; overcurrents in the form of short-circuits and overload can occur. The sole purpose of fuses and circuit
A Practical Guide to Dielectric Testing
Chroma Systems Solutions, Inc. A Practical Guide to Dielectric Testing 19032 Series Electrical Safety Analyzer & 19050 Series Hipot Tester AC/DC/IR/SCAN Keywords: Dielectric tests, insulation resistance
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
Lab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE
Appendix B-2 - Electrical Safety In Design Final Report TECHNOLOGIES THAT REDUCE LIKELIHOOD OF INJURY FROM ELECTRICAL HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE The following are technologies that reduce
Experiment #3, Ohm s Law
Experiment #3, Ohm s Law 1 Purpose Physics 182 - Summer 2013 - Experiment #3 1 To investigate the -oltage, -, characteristics of a carbon resistor at room temperature and at liquid nitrogen temperature,
Resistors in Series and Parallel
Resistors in Series and Parallel Bởi: OpenStaxCollege Most circuits have more than one component, called a resistor that limits the flow of charge in the circuit. A measure of this limit on charge flow
DESCRIPTION DWG DESCRIPTION DWG
DESCRIPTION DWG DESCRIPTION DWG Ferroresonance 3451/1 3451/2 3451/3 Electro-magnetic Fields (EMF) 3462/1 HV & LV Insulators (Links) 3463/1 A ORIGINAL ISSUE B 14.07.09 APPROVED DATE J. Brooks 25.02.03 INDEX
13. Electrical network design methodology and application example
873 13. Electrical network design methodology and application example 874 13. ELECTRICAL NETWORK DESIGN METHODOLOGY AND APPLICATION EXAMPLE The profitability of an industrial installation is directly linked
Electrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
Engineering innovation
Eaton's Electrical Engineering Services & Systems Solutions Focus Seamless Solutions for Reliable, Efficient and Safe Power Systems Engineering innovation Progressive solutions for today s power systems
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings
Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203 03/2013 Retain for future use. Introduction Short-circuit current s (SCCRs) for variable frequency drives (VFDs) is
Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation
Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage
Application Note. So You Need to Measure Some Inductors?
So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),
Guidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions
Superconducting and Solid-State Electronic Fault Current Limiter Technologies The shift from demonstration projects to Business-as-Usual solutions Dr. Detlev Kirsten & Herbert Piereder Solid State SSFCL
Instrument Transformers Application Guide
Instrument Transformers Application Guide Edited by ABB AB High Voltage Products Department: Marketing & Sales Text: Knut Sjövall, ABB Layout, 3D and images: Mats Findell, ABB SE-771 80 LUDVIKA, Sweden
Agilent Technologies. Troubleshooting Three-Phase AC Motors with U1210 Series Handheld Clamp Meters. Application Note
Agilent Technologies Troubleshooting Three-Phase AC Motors with U1210 Series Handheld Clamp Meters Application Note INTRODUCTION In today s world, the three-phase AC induction motors are widely used in
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface
Eðlisfræði 2, vor 2007
[ Assignment View ] [ Print ] Eðlisfræði 2, vor 2007 30. Inductance Assignment is due at 2:00am on Wednesday, March 14, 2007 Credit for problems submitted late will decrease to 0% after the deadline has
Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring web.itu.edu.tr/yumakk. Distance Protection
Distance Protection Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you are strongly advised to study this note regarding to the pre-study questions
Modeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB
Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/ Course Learning Outcome (CLO) Upon completion of this course, students should be able to: Apply the principles of three phase systems,
National Craft Assessment and Certification Program S P E C I F I C A T I O N S
National Craft Assessment and Certification Program S P E C I F I C A T I O N S INDUSTRIAL ELECTRICIAN V4 ELEC26_O4 Released September 2013 Focus Statement An Industrial Electrician must be able to interpret
Voltage Unbalance and Motors
Voltage Unbalance and Motors Background Voltage unbalance occurs when the RMS line voltages on a poly-phase system are unequal. Voltages are seldom perfectly balanced between phases, but when this unbalance
DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR
1 DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING Constructional details Types of rotors EE2302 - ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR PART A 1.
Protection from Short-circuit
Protection from Short-circuit Back-up Fuse-Link with ÜLA (controlled power dissipation) Test device for tripping device Special version with threat High-voltage Fuse-Link for voltage transformers (HSW)
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
Residual Current Circuit Breaker
Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID
Tension (kv) Impedance (Ohms) EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID frequency (Hz) Simon DESCHANVRES Yannick VERNAY RTE, CNER, Substations Department t (ms) EMTP-RV Users Group
Type SA-1 Generator Differential Relay
ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes
EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION
EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION INTERNATIONAL ELECTROTECHNICAL COMMISSION EFFICIENT ELECTRICAL ENERGY TRANSMISSION AND DISTRIBUTION 1 EFFICIENT ELECTRICAL ENERGY TRANSMISSION
Current transformer selection guide
The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
TDMS Test & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley
Alternating Current and Direct Current
K Hinds 2012 1 Alternating Current and Direct Current Direct Current This is a Current or Voltage which has a constant polarity. That is, either a positive or negative value. K Hinds 2012 2 Alternating
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61
FUSES Catalogue CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61 INTRODUCTION The main function of current limiting fuses is to protect electrical apparatus, such as distribution transformers, motors
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION
Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
3-Phase AC Calculations Revisited
AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who