1 ASHRAE Std Update Where Are We Now? October 2012 Dennis A. Stanke Trane La Crosse, WI

2 ASHRAE Standard 62.1 What Is It? Title: Ventilation for Acceptable Indoor Air Quality Purpose: to specify minimum ventilation rates and indoor air quality that will be acceptable to human occupants and are intended to minimize adverse health effects. Scope: All commercial, institutional, and high-rise residential buildings 2

3 ASHRAE Standard 62.1 Why Care? Section 6 is the basis for many ventilation codes, include both US model codes (UMC and IMC) Compliance with Std (Sections 4 thru 7) is a LEED prerequisite for any credits Compliance with Std (Sections 4 thru 8) is required for compliance with: Std High Performance Green Buildings ENERGY STAR and beq energy label 4

4 what does Std 62.1 require? Must Comply With (Sect 4 and 5) Mandatory general requirements To reduce generation of indoor contaminants and introduction of outdoor contaminants (Sect 6) Ventilation requirements Prescribed rates to dilute indoor contaminants Performance rates to limit contaminant concentrations Natural ventilation provisions (Sect 7) Mandatory construction, startup reqmts (Sect 8) Mandatory operation, maintenance reqmts 5

5 Std Section 4 Outdoor Air Quality Project Team Regional Air Quality. Assess regional outdoor air (OA) quality to determine NAAQS compliance status Check for non-attainment for any EPA criteria contaminants Local Air Quality. Survey site for unusual local sources Visit the site, look around These assessments inform air cleaning decisions 6

6 Std Section 5 Systems and Equipment Mech Designer 5.1 Ventilation Air Distribution. Design to assure that ventilation air can get to occupied zones Provide means to adjust (balance) airflows Design to assure mixing in RA/OA mixing plenums Document assumptions and air balancing requirements Important in 100% OA systems should really duct OA to zone 7

7 Std Section 5 Systems and Equipment Mech Designer 5.2 Exhaust Duct Location. Prevent leakage of harmful exhaust contaminants into the building Design exhaust ducts to operate at negative pressure Room Duct Fan Outdoors 8

8 Std Section 5 Systems and Equipment Mech Designer 5.3 Ventilation System Controls. Design to assure minimum ventilation Provide controls to enable fan Provide controls to maintain minimum OA flow at any load or dynamic reset condition. VAV systems must include modulating dampers or injection fans 9

9 Std Section 5 Systems and Equipment Mech Designer 5.4 Airstream Surfaces. Reduce space contamination due to air distribution system Use duct materials that resist microbial growth per UL 181 Use duct materials that resist erosion per UL 181 Most matte-face finishes meet these requirements 10

10 Std Section 5 Systems and Equipment architect 5.5 Outdoor Air Intakes. Reduce contamination from outdoors Locate intake a minimum distance from outdoor sources, per Table 5.2. Examples sources/distances: Loading dock Dumpster Surface below intake Cooling tower exhaust 25 ft 15 ft 1 ft 25 ft Design to limit rain water penetration (using hood, proper velocity, etc.) or manage water that penetrates Use bird screens and prevent bird nesting at intake 11

11 Std Section 5 Systems and Equipment Mech Designer 5.6 Local Capture of Contaminants. Reduce recirculation of indoor contaminants Exhaust locally captured contaminants (from printers, for instance) directly to outdoors 5.7 Combustion Air. Reduce pollutants from combustion appliances Provide sufficient combustion air Provide sufficient air for removal of combustion products 12

12 Std Section 5 Systems and Equipment Mech Designer 5.8 Particulate Matter Removal. Reduce rate of dirt accumulation on HVAC devices Use at least a MERV 6 filter upstream of dehumidifying coils and other wet-surface devices (about 20% to 30% Dust Spot) 13

13 Std Section 5 Systems and Equipment Mech Designer 5.9 Dehumidification Systems. Design to reduce dampness in buildings during mechanical cooling By analysis, limit RH to 65% or less at design dew point condition without solar load Design so that intake exceeds exhaust airflow Basic constant volume systems with sensible-only thermostat might not comply with 65% limit 14

14 Std Section 5 Systems and Equipment Mech Designer 5.10 Drain Pans. Assure condensate drainage without flooding or carryover Slope drain pan at least 1/8 per foot Locate drain opening at lowest point of drain pan and size to prevent overflow under normal conditions Use P-trap or other seal to prevent ingestion of air while allowing complete drainage with fan on or off Size drain pan to limit carryover Proper P-trap design helps avoid common water carryover problems 15

15 Drain Seals Mech Designer total trap height T = D + H where H = air-handler casing pressure + 1 in. wg D = trap depth = ½ H + d d = drain pipe diameter 16

16 Std Section 5 Systems and Equipment Mech Designer 5.11 Finned Tube Coils and Heat Exchangers. Select to reduce water droplet carryover Limit coil pressure drop to 0.75 in.wc.@ 500 fpm Exception: No pressure drop limit when design provides access to both faces for cleaning 5.12 Humidifiers and Water Spray Systems. Reduce water-borne contaminants and design to reduce carryover Use potable water No downstream devices within absorption distance 17

17 Std Section 5 Systems and Equipment Mech Designer 5.13 Access for Inspection, Cleaning and Maintenance. Reduce dirt accumulation in air distribution system Design system with adequate clearance around ventilation equipment Provide access doors/panels for ventilation equipment (air handlers, terminal units) Provide access doors/panels for devices in air distribution system (air plenums, coils, air cleaners, drain pans, fans, humidifiers) 18

18 Std Section 5 Systems and Equipment Architect 5.14 Building Envelope and Interior Surfaces. Reduce intrusion of water and water vapor and uncontrolled condensation Use a weather barrier within the building envelope Use a vapor retarder within the building envelope (typically on the warm side, but it really depends on wall design) Seal all envelope seams, joints and penetrations Insulate pipes, ducts and other cold surfaces 19

19 Std Section 5 Systems and Equipment Architect 5.15 Buildings with Attached Parking Garages. Reduce infiltration of vehicular exhaust Maintain garage pressure below adjacent occupied space Or, use a vestibule Or, otherwise design to minimize air migration from garage to occupied space 20

20 Std Section 5 Systems and Equipment Mech Designer 5.16 Air Classification and Recirculation. Reduce recirculation of dirty air to cleaner spaces Designate air from each space/location (see Table 6.1) Class 1: Low contaminant concentration (office) Class 2: Mild concentration (dining room) Class 3: Significant concentration (daycare sick room) Class 4: Highly objectionable/potentially harmful Design to limit air recirculation as follows: Class 1 to any space or location Class 2 to self, other Class 2 or Class 3 Class 3 to self Class 4 to outdoors only 21

21 Std Section 5 Systems and Equipment Project Team 5.17 Buildings Containing ETS Areas and ETS-Free Areas. Reduce level of ETS in ETS-free areas Classify each area as ETS or ETS-free Pressurize ETS-free areas with respect to ETS areas Separate ETS/ETS-free areas with solid walls, doors, etc (or engineer to assure airflow into ETS areas Maintain transfer airflow paths Don t recirculate from ETS to ETS-free at air handler Exhaust from ETS areas Post sign: This area may contain ETS 22

22 what does Std 62.1 require? Must Comply With (Sect 4 and 5) Mandatory general requirements To reduce generation of indoor contaminants and introduction of outdoor contaminants (Sect 6) Ventilation requirements Prescribed rates to dilute indoor contaminants Performance rates to limit contaminant concentrations Natural ventilation provisions (Sect 7) Mandatory construction, startup reqmts (Sect 8) Mandatory operation, maintenance reqmts 23

23 Std Section 6.0 Procedures Mech Designer 6.1 General. Find minimum zone and intake OA flow using either the VRP, the IAQP, or the NVP Ventilation Rate Procedure (VRP). Prescribes procedures and OA rates, assuming typical space contaminant sources and source strengths IAQ Procedure (IAQP). Requires analysis of contaminants ( performance ) based on sources and target concentrations to find minimum OA rates Natural Ventilation Procedure (NVP). Prescribes opening areas, and requires mechanical ventilation in most climates (mixed-mode ventilation) 24

24 Std Section 6.2 Ventilation Rate Procedure Mech Designer 6.2 Ventilation Rate Procedure. Find OA intake flow (Vot) using prescribed zone OA rates & system intake calculation procedures in this section 25

25 Std Section 6.2 Ventilation Rate Procedure Mech Designer Outdoor Air Treatment. If OA is unacceptable per Section 4.1 assessment, must use air cleaning PM10. Where PM10 exceeds the NAAQS (nonattainment areas), use MERV 6 filter PM2.5. Where PM2.5 exceeds the NAAQS (non-attainment areas) use MERV 11 filter Ozone. Where ozone greatly exceeds the NAAQS (very high non-attainment area) use 40% efficient ozone air cleaner NAAQS: the most recent three-year average annual fourthhighest daily maximum eight-hour average ozone concentration exceeds ppm (209 μg/m3) 26

26 Std Section 6.2 VRP Zone Calculaitons Mech Designer Zone Calculations. To assure reasonable breathing-zone dilution for each zone: Use Table 6.1 rates (cfm/per and cfm/sf) and Equation 6-1 to find breathing zone outdoor airflow: Vbz = Rp*Pz + Ra*Az Use Table 6.2 defaults to find zone air distribution effectiveness, Ez (typically 1.0 for cooling) Use Equation 6-2 to find zone outdoor airflow: Voz = Vbz/Ez 30

27 ventilation rate procedure Minimum Ventilation Rates Mech Designer Table 6-1: Minimum breathing-zone rates for 63 categories Std Std Rp Ra Rp Ra Occupancy category cfm/p cfm/ft² cfm/p cfm/ft² Office Classroom (ages 5-8) Lecture classroom Retail sales Auditorium Prescribes both per-person and per-area rates 31

28 ventilation rate procedure Effective Minimum Rates Mech Designer Comparison of breathing-zone OA flow Std Std Occupancy category (default density/1000 ft²) Vbz cfm Effective cfm/p Vbz cfm Effective cfm/p Office (5p) Classroom (ages 5-8) (25p) Lecture classroom (65p) Retail sales (20p) Auditorium (150p) % of OA rates drop; 30% stay same or rise 32

29 Std Section 6.2 VRP System Calculations Mech Designer Single-Zone Systems. For ventilation systems with one air handler per zone: Find system-level outdoor air intake flow: Vot = Voz % Outdoor Air Systems. For ventilation systems with one air handler supplying only outdoor air to many zones. Find system-level outdoor air intake flow: Vot = S Voz 33

30 Std Section 6.2 VRP System Calculations Mech Designer Multiple-Zone Recirculating Systems. For ventilation systems with one AHU serving many zones: Find outdoor air intake flow (Vot) using prescribed equations and procedure to account for system ventilation efficiency (Ev): Vot = Vou/Ev outdoor air intake flow Vou = D* S Rp*Pz + S Ra*Az OA used in zones D = Ps/ S Pz population diversity factor Ev = min(evz) system vent efficiency Evz = 1 + Xs Zpz zone vent efficiency Xs = Vou/Vps average OA fraction Zpz = Voz/Vpz zone primary OA fraction 34

31 Std Section 6.2 VRP System Calculations Mech Designer For design, Vpz = Vpz-exp, where Vpz-exp is the lowest expected primary airflow at the design condition. I use the Multiple-Zone Recirculating Systems. For reheat minimum airflow setting, Vpzm; it s easy but very ventilation systems with one AHU serving many zones: conservative. Find outdoor air intake flow (Vot) using prescribed equations and procedure to account for system ventilation efficiency (Ev): For design, Vps = Vps-exp, where Vps-exp is the highest expected system primary airflow value at the Vot = Vou/Ev outdoor air intake flow design Vou condition. = D* S Rp*Pz I use + fan S Ra*Az block airflow OA used Vps-des: in zones it s easy and usually D = Ps/ worst-case. S Pz population diversity factor Ev = min(evz) system vent efficiency Evz = 1 + Xs Zpz zone vent efficiency Xs = Vou/Vps average OA fraction Zpz = Voz/Vpz zone primary OA fraction 35

32 Std Section 6.2 OA Calculation Example Do we have time for an example? No But, I found total OA intake for a 6-zone school, using different systems and methods: One RTU per zone (six single-zone systems), both in cooling and heating One FC per zone, and a 100% OA system, with both CV and VAV ventilation airflow A reheat VAV (single-path multiple-zone) system using both default Ev and calculated Ev A series fan-powered VAV (dual-path multiple-zone) system using calculated Ev 36

33 VRP 6-zone school example OA Intake Flow Summary Ventilation System OA Intake (2001 Vot) OA Intake (2010 Vot) % Chg Single-Zone Clg 12,600 8, Single-Zone Htg 15,800 11, % OA CV 12,600 8, % OA VAV 8,800 7, MZS-VAV Default Ev 10,900 10,800-1 MZS-VAV Calc Ev 10,900 8, MZS-VAV Series FP 10,900 7,

34 Std Section 6.2 VRP Dynamic Reset Mech Designer Dynamic Reset. To assure outdoor airflow meets requirement for ventilation load, without over-ventilating, optional controls may: Reset zone minimum OA flow based on variations in occupancy, i.e., demand controlled ventilation (DCV) Reset OA intake flow based on variations in ventilation efficiency (ventilation reset control) Reset VAV zone minimum airflow based on variations in outdoor air fraction due to free cooling or exhaust-air make-up operation This Section includes operating control options, (rather than design requirements) 43

35 Std Section 6.3 IAQ Procedure Mech Designer 6.3. Indoor Air Quality (IAQ) Procedure Find breathing zone OA flow (Vbz) and system OA intake flow (Vot) based on performance Compliance addresses Contaminant sources Contaminant concentration Perceived indoor air quality Design approach Combined IAQP and VRP Documentation 44

36 Std Section 6.3 IAQ Procedure Mech Designer Contaminant Sources. Must identify contaminants of concern including mixtures, sources, source strengths Contaminant Concentration. Must specify target concentration, for each C of C Perceived IAQ. Must specify target perceived air quality in terms of percent satisfied Requires designer judgment to identify contaminants/mixtures of concern, source and source strength for each, targets concentrations. Judgment = Risk 45

37 Std Section 6.3 IAQ Procedure Mech Designer Design Approaches. Find highest required zone and system OA flow rates using: Mass balance analysis AND Subjective evaluation, either after construction, OR using OA needed in a substantially similar zone Combined IAQP and VRP. May use VRP to find minimum OA and IAQP to find additional OA (or air cleaning required) Documentation. Must document assumptions and calculations. IAQP meets Std 62.1 but does NOT meet Std or LEED requirements 46

38 Std Section 6 Natural Ventilation Project Team 6.4 Natural Ventilation Procedure. Use NV with mechanical ventilation in most climates: Perimeter areas must be within defined distance from OA opening with free area at least 4% of floor area Interior areas must be within defined distance from OA opening, and interior-perimeter opening with free area at least 8% of interior floor area, but not less than 25 ft 2 Defined distance depends on window location and ceiling height (2H for single-side, 5H for doubleside) Mixed mode controls must coordinate operation of NV and MV systems 47

39 Std Section 6.5 Exhaust Ventilation Mech Designer Exhaust Ventilation. To assure minimum removal of local contaminants, some zones require exhaust rates prescribed in Table 6.4. Examples of more than 20 zones listed: Art classroom 0.70 cfm/ft2 Beauty and nail salons 0.60 Kitchenettes 0.30 Locker/dressing rooms 0.25 Copy, printing rooms 0.50 Toilet public 50 (cont.) or 70 (cyc.) cfm/wtr closet 48

40 what does Std 62.1 require? Must Comply With (Sect 4 and 5) Mandatory general requirements To reduce generation of indoor contaminants and introduction of outdoor contaminants (Sect 6) Ventilation requirements Prescribed rates to dilute indoor contaminants Performance rates to limit contaminant concentrations (Sect 7) Mandatory construction, startup reqmts (Sect 8) Mandatory operation, maintenance reqmts 49

41 Std Section 7 Construction/Start-Up Project Team 7.1 Construction Phase. Must reduce IAQ problems introduced during construction. For example: Install unit filters before operating fans Protect materials from rain and moisture. Don t install materials with visible microbial growth Reduce transfer of construction contaminants into occupied areas Construct ducts per SMACNA standards 50

42 Std Section 7 Construction/Start-Up Project Team 7.2 System Start-Up. Must reduce potential for IAQ problems prior to occupancy. For example: Balance air flows Test (or certify) drain pan drainage Clean air distribution system before start up Test OA dampers for proper operation Provide ventilation system documentation (HVAC controls information, air balance report, design criteria and assumptions, drawings, etc.) to owner or owner s agent 51

43 Std Section Operation & Maintenance Project Team 8.2 Operations and Maintenance Manual. Develop a building operations and maintenance manual 8.3 Ventilation System Operation. Operate it whenever spaces are expected to be occupied 8.4 Ventilation System Maintenance. Maintain it in accordance with Manual Compliance with Section 8 is required by Std but not by LEED 52

44 Std Summary The 2010 version has a few new requirements It s continually improved (next version in 2013) It s VRP rates and procedures are required by IMC and UMC and by LEED It s required by reference in Std 189.1, which is one of two IgCC project compliance paths We re out of time! 53

45 Questions? ASHRAE 62.1 update: Where are we now?

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical

More information

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng. HVAC Systems and Indoor Air Quality Douglas K. Spratt, M.Sc., P.Eng. The 5 Senses Architecture Electrical Structural Mechanical Hearing Seeing Smelling Feeling Tasting HVAC Systems are Dynamic Heat Gains

More information

engineers newsletter live Course Outline

engineers newsletter live Course Outline engineers newsletter live Course Outline ASHRAE Standards 62.1 and 90.1 and VAV Systems These days many designers want to comply with both Standard 62.1 and Standard 90.1. Requirements from both standards

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Dedicated Outdoor Air Systems (D.O.A.S.)

Dedicated Outdoor Air Systems (D.O.A.S.) Commercial and Industrial Climate Control Systems Dedicated Outdoor Air Systems (D.O.A.S.) AMDOAS-1 What is it? Why use one? What are my options? Selection considerations Design steps What is it? A separate

More information

CHAPTER 4 VENTILATION AIR SUPPLY

CHAPTER 4 VENTILATION AIR SUPPLY CHAPTER 4 VENTILATION AIR SUPPLY 401.0 General. 401.1 Applicability. This chapter contains requirements for ventilation air supply, exhaust, and makeup-air requirements for occupiable spaces within a building.

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

Radford University. Indoor Air Quality Management Plan

Radford University. Indoor Air Quality Management Plan Radford University Indoor Air Quality Management Plan Spring 2015 Introduction Concerns with Indoor Air Quality (IAQ) have increased since energy conservation measures were instituted in office buildings

More information

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015

Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015 for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097

More information

NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS

NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS NADCA GENERAL SPECIFICATIONS FOR THE CLEANING OF COMMERCIAL HEATING, VENTILATING AND AIR CONDITIONING SYSTEMS National Air Duct Cleaners Association 1518 K Street, N.W. Suite 503 Washington, DC 20005 (202)

More information

for K-12 School Buildings

for K-12 School Buildings Advanced Energy Design Guide for K-12 School Buildings HVAC Section John Murphy Applications Engineer, LEED AP Trane La Crosse, Wisconsin [email protected] www.trane.com AEDG-K12 HVAC Subcommittee John

More information

Technical Investigation Elizabeth C. Krauss Mechanical Option September 18, 2013

Technical Investigation Elizabeth C. Krauss Mechanical Option September 18, 2013 Technical Investigation Elizabeth C. Mechanical Option September 18, 2013 State Institute of Rehabilitation T e c h n i c a l R e p o r t I 1 Technical Investigation... 0 Executive Summary... 2 Mechanical

More information

Glossary of HVAC Terms

Glossary of HVAC Terms Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other

More information

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP Construction Indoor Air Quality Management Plans for LEED Matt Gregg, PE, LEED AP Agenda What is a Construction IAQ Management Plan? What are the LEED Requirements? What is the Mechanical Contractor s

More information

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Methods for Effective Room Air Distribution Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Agenda Overview LEED issues and Update Perimeter Acoustics Thermal Comfort IAQ / Standard 62.1 Update

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

Indoor Environmental Quality Checklist Including Background Information in Comment Section

Indoor Environmental Quality Checklist Including Background Information in Comment Section Department of Employee Relations Indoor Environmental Quality Checklist Including Background Information in Comment Section Building Description Original construction date Renovation dates Number of floors

More information

Indoor Air Quality. A Guide to Understanding ASHRAE Standard 62-2001

Indoor Air Quality. A Guide to Understanding ASHRAE Standard 62-2001 Indoor Air Quality A Guide to Understanding ASHRAE Standard 62-2001 Preface This guide reviews and explains the provisions of ASHRAE Standard 62-2001, Ventilation for Acceptable Indoor Air Quality. It

More information

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE APPLICATION NOTE TI-138 TSI s IAQ-CALC TM Indoor Air Quality Meter and TH-CALC TM Thermohygrometer calculate Percent Outdoor Air (%OA). In order to take

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

AG-TQS-IAQ-00 March 4, 2002. Application Guide. TQS with IAQ Inlet

AG-TQS-IAQ-00 March 4, 2002. Application Guide. TQS with IAQ Inlet Application Guide TQS with IAQ Inlet Table of Contents Introduction 2 ASHRAE Standard 62 2 Outdoor Air Requirements For Ventilation For Commercial Buildings 3 EPA Report Energy Costs and IAQ Performance

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Dehumidification Frequently Asked Questions

Dehumidification Frequently Asked Questions Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful

More information

Mechanical and Natural Ventilation

Mechanical and Natural Ventilation BBSE3006: Air Conditioning and Refrigeration II http://www.hku.hk/bse/bbse3006/ Mechanical and Natural Ventilation Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:

More information

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems

APPLICATION GUIDE. Moisture Management in Waterborne Climate Systems APPLICATION GUIDE Moisture Management in Waterborne Climate Systems Contents Introduction 3 WBCS Concept 3 Condensation 4 Moisture Sources in the Space 4 Impact of a High Moisture Load 5 Designing to Manage

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Indoor air quality Workers and students spend about half their waking hours at work or school. Therefore, maintaining adequate indoor air quality

More information

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates

Causes of High Relative Humidity Inside Air Conditioned Buildings. Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates Causes of High Relative Humidity Inside Air Conditioned Buildings Roger G.Morse AIA, Paul Haas CSP, CIH Morse Zehnter Associates S. FLORIDA AVE. AMBIENT 91 F db / 78 F wb 16,000 HOURS ANNUALLY THAT wb

More information

CHAPTER 4 VENTILATION

CHAPTER 4 VENTILATION CHAPTER 4 VENTILATION SECTION 1 GENERAL 1.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. Mechanical exhaust systems, including exhaust systems serving

More information

SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING

SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION SYSTEM CLEANING SECTION 23 01 30.51 HVAC AIR-DISTRIBUTION PART 1 - GENERAL 1.1 SUMMARY A. Section includes cleaning of interior surfaces of HVAC equipment. The HVAC equipment cleaning work includes the following: 1. Air

More information

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis Components HVAC General System Selection Life Cycle Cost Analysis Outdoor Air Design Values Indoor Air Design Values Outdoor Air Ventilation Welding Ventilation Temperature Control Systems Ductwork HVAC

More information

VENTILATION CHAPTER 4

VENTILATION CHAPTER 4 CHAPTER 4 VENTILATION SECTION 1 GENERAL 1.1 Scope. This chapter shall govern the ventilation of spaces within a building intended to be occupied. This chapter does not govern the requirements for smoke

More information

IECC Compliance Guide for Homes in Virginia

IECC Compliance Guide for Homes in Virginia IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,

More information

Mechanical Technical Assignment One ASHRAE Standard 62.1 and Standard 90.1 Evaluation

Mechanical Technical Assignment One ASHRAE Standard 62.1 and Standard 90.1 Evaluation Mechanical Technical Assignment One ASHRAE Standard 62.1 and Standard 90.1 Evaluation Prepared for: Dr. James D. Freihaut Department of Architectural Engineering The Pennsylvania State University Prepared

More information

Minimizing Indoor Mold Problems through Management of Moisture in Building Systems

Minimizing Indoor Mold Problems through Management of Moisture in Building Systems Minimizing Indoor Mold Problems through Management of Moisture in Building Systems Position Document Approved by ASHRAE Board of Directors June 30, 2005 AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING

More information

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com

Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is

More information

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH PEOSH Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview Eric Weren, MSIH Public Employees Occupational Safety and Health Unit IAQ Asthma-Friendly

More information

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA.

1. Certification: Employ an ASCS certified by NADCA on a full-time basis. 2. Supervisor Qualifications: Certified as an ASCS by NADCA. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

Basics of HVAC Cleaning

Basics of HVAC Cleaning Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1

Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1 Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1 Background: The past 10 years have seen a dramatic change in the design and function of air handlers, due in

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2 providing insights for today s hvac system designer Engineers Newsletter volume 42 2 Understanding Single-Zone VAV Systems Single-zone variable-air-volume (VAV) is not a new concept, but due to new energy

More information

MULTIZONE APPLICATION OF SOLUTION UNITS

MULTIZONE APPLICATION OF SOLUTION UNITS MULTIZONE APPLICATION OF SOLUTION UNITS APPLICATION GUIDE Supersedes: 102.20-AG12 (206) Form: 102.20-AG12 (307) GENERAL Multi-zone heating and air conditioning units offer design and application advantages

More information

DRYER VENTING SPECIFICATIONS DRYER SAFETY

DRYER VENTING SPECIFICATIONS DRYER SAFETY DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting

More information

Molds and mildew are fungi that grow

Molds and mildew are fungi that grow Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate

More information

HVAC Systems in Schools & Commercial Buildings and Radon

HVAC Systems in Schools & Commercial Buildings and Radon HVAC Systems in Schools & Commercial Buildings and Radon References US EPA Radon Prevention in the Design and Construction of Schools and Other Large Buildings http://www.epa.gov/ordntrnt/ord/nrmrl/pubs/1993/air/

More information

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems

More information

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1

More information

DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE

DESERT RESEARCH INSTITUTE MOLD ASSESSMENT AND REMEDIATEION PROCEDURE 1.0 Introduction DESERT RESEARCH INSTITUTE This Desert Research Institute (DRI) Mold Assessment and Remediation Procedure was established to assure that consistent and uniform information is provided to

More information

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW

PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,

More information

Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance

Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

HVAC Characteristics. Test Space HVAC Characteristics

HVAC Characteristics. Test Space HVAC Characteristics HVAC Characteristics Information on the characteristics of the heating, ventilation, and air conditioning (HVAC) system(s) in the entire BASE building including types of ventilation, equipment configurations,

More information

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained).

This permit does not include replacement or upgrading of the existing electrical panel or service (a separate electrical permit must be obtained). CITY OF MILPITAS Building & Safety Department 455 E. Calaveras Blvd. Milpitas, CA 95035 408-586-3240 www.ci.milpitas.ca.gov RESIDENTIAL AIR CONDITIONING, REPLACEMENT 1. PERMIT INFORMATION: The replacement

More information

ECHO System for Basements

ECHO System for Basements ECHO System for Basements Homeowners looking for more space are all too familiar with the cold, damp and dingy basement. Now, the Enclosure Conditioned Housing (ECHO) System TM, winner of the Ottawa-Carleton

More information

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN

HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN HOSPITAL ISOLATION ROOM HVAC SYSTEM DESIGN Presented to: ASHRAE YEA Illinois Chapter Specialty Environment Design Conference March 24, 2014 Jean O. Gibbons, PE, LEED AP Senior Vice President Grumman/Butkus

More information

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design

More information

Why is my air conditioner dripping on my customers?

Why is my air conditioner dripping on my customers? De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These

More information

Green Built Texas Protocol v3 Project Summary and Checklist, One and Two Family New Construction

Green Built Texas Protocol v3 Project Summary and Checklist, One and Two Family New Construction Date of Application Path Project Identification Project Address Owner Identification Architect Identification Contractor Identification Third Party Provider Green Built Texas Protocol v3 Project Summary

More information

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons

HIGH EFFICIENCY RTU. www.reznorhvac.com HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING. DX System IEER> 13.2 Gas Heat Efficiency > 92% Capacities Tons Capacities 10-25 Tons 100-400 MBH HIGH EFFICIENCY, PACKAGED SPACE CONDITIONING DX System IEER> 13.2 Gas Heat Efficiency > 92% HIGH EFFICIENCY RTU 30-120 kw 3,000-11,550 CFM Comfort Comfort is determined

More information

HVAC Simplified Approach Option

HVAC Simplified Approach Option HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than

More information

Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality

Camfil. Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality Camfil Technical Services Bulletin Tools for Schools Filtration for Improved Indoor Air Quality Most non-practitioners notice the HVAC system when it is too hot, or too cold, or in other ways not working

More information

Walkthrough Inspection Checklist

Walkthrough Inspection Checklist Walkthrough Inspection Checklist This checklist is to aid during an IAQ Walkthrough of the school. The checklist includes considerations both inside and outside the school building: Instructions: 1. Read

More information

Comparing Energy Savings of Different VAV Systems

Comparing Energy Savings of Different VAV Systems Comparing Energy Savings of Different VAV Systems Prepared By: Martyn Dodd [email protected] EnergySoft LLC 1025 5th Street, Suite A Novato, CA 94945 415-897-6400 www.energysoft.com Last Modified: March

More information

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1

DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 1 by Roger M Hensley, CMS TYPES OF SUPPLY DUCT SYSTEMS There are several basic

More information

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work?

newsletter Let s take a high-level look at airside economizing: what it is, what it requires, and how it s done. How does economizer cooling work? engineers volume 35 2 newsletter providing insights for today s hvac system designer keeping cool with outdoor air Airside Economizers from the editor For the denizens of commercial buildings, comfort

More information

DOAS UNITS. www.reznorhvac.com MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR. Kitchens Hotel Corridors Laboratories. Paint Booths. Capacities Tons MBH

DOAS UNITS. www.reznorhvac.com MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR. Kitchens Hotel Corridors Laboratories. Paint Booths. Capacities Tons MBH MAKEUP AND VENTILATION AIR 100% OUTSIDE AIR Kitchens Hotel Corridors Laboratories Conference CENTERS Schools Paint Booths Malls/Shopping Centers DOAS UNITS Capacities 5-35 Tons 50-800 MBH 30-120 kw 650-9,000

More information

SAM HOUSTON STATE UNIVERSITY

SAM HOUSTON STATE UNIVERSITY PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

Integrating Kitchen Exhaust Systems with Building HVAC

Integrating Kitchen Exhaust Systems with Building HVAC Design Guide 3 Improving Commercial Kitchen Ventilation System Performance Integrating Kitchen Exhaust Systems with Building HVAC This design guide provides information that may help achieve optimum performance

More information

KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS

KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS By Jerome E. Spear, CSP, CIH Effective January 1, 2005, consultants who prepare mold management plans for buildings located in Texas must be licensed

More information

Specification. Indoor Air Quality Management

Specification. Indoor Air Quality Management GREENGUARD Environmental Institute 2211 Newmarket Parkway, Suite 110 Marietta, GA 30067 1.800.427.9681 Specification Indoor Air Quality Management This Master Specification section is intended for use

More information

Building Performance Solutions HVAC Design Guide, 2007

Building Performance Solutions HVAC Design Guide, 2007 Building Performance Solutions HVAC Design Guide, 2007 HVAC sizing, system design, layout, and installation shall be sized according to (Air Conditioning Contractor of America), ACCA manual J8, 8 th edition,

More information

Preliminary Final Proposal

Preliminary Final Proposal 1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient

More information

Answers to Your Questions from the Webinar

Answers to Your Questions from the Webinar 2008 Desert Aire and USA Swimming. Used by permission. Desert Aire & USA Swimming - Aquatics Webinar - Answers to Your Questions Answers to Your Questions from the Webinar Thank you for your interest in

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida

Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes

More information

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

bout your HOUSE before you start Renovating Your Basement Moisture Problems

bout your HOUSE before you start Renovating Your Basement Moisture Problems A bout your HOUSE before you start Renovating Your Basement Moisture Problems CE 28 c Condensation of cold surfaces, efflorescence Water leak in corner on floor Mold and decay on floor joists and sill

More information

Air Conditioning Clinic

Air Conditioning Clinic Air Conditioning Clinic Introduction to HVAC Systems One of the Systems Series February 2012 TRG-TRC018-EN Introduction to HVAC Systems One of the Systems Series A publication of Trane Preface Introduction

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

bout your house before you start Renovating Your Basement Moisture Problems

bout your house before you start Renovating Your Basement Moisture Problems A bout your house CE 28c before you start Renovating Your Basement Moisture Problems Mold and decay on floor joists and sill plates Stuffy air, high humidity, poor air circulation Water draining in from

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

To provide good indoor air quality

To provide good indoor air quality Conditioning Ventilation Air for Improved Performance and Air Quality The practice of using a mixing chamber for mixing outdoor and return in a single system should be replaced by a technique with two

More information

24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by

24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by 24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL ENERGY CONSERVATION CODE (1) The Department of Labor and Industry adopts and incorporates by reference the International Code Council's International

More information

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition

IEQ Management Plan. Denver Museum of Nature and Science ECF Addition IEQ Management Plan GH Phipps Construction Companies 5995 Greenwood Plaza Blvd., Suite 100 Greenwood Village, Colorado 80111-4710 303.571.5377 PHONE www.ghphipps.com Denver Museum of Nature and Science

More information