TRANSFORMER SECONDARY FAULT CURRENTS TABLES
|
|
- Horatio Butler
- 7 years ago
- Views:
Transcription
1 TRANSFORMER SECONDARY FAULT CURRENTS TABLES The information contained herein is made available to engineers, consultants and contractors solely for the purpose of providing help to Alabama Power Company customers in their selection of customer-owned service equipment. This data should be used for no other purpose. Assuming incorrect transformer or service sizes, when choosing values from the tables, can lead to errors in equipment selection and result in catastrophic failure of equipment. Alabama Power Company does not warrant this information and reserves the right to change the data in these tables without notice. The user of the information contained herein is fully responsible for correct use of this data; by making this data available, Alabama Power does not assume any responsibility relating to the use of the data or the customer-owned equipment. The information is not to be used for determining personal protective equipment requirements for arc flash hazards. Use of this data for such purposes may lead to incorrect selection of personal protective equipment and could result in injuries. SEE NEXT PAGE FOR TABLE OF CONTENTS
2 Effective October 24, 2013 Page 2 of 27 TABLE OF CONTENTS Pad Mounted Transformers KVA Overhead Transformer (#1/0 Aluminum Multiplex) KVA Overhead Transformer (#1/0 Aluminum Multiplex) KVA Overhead Transformer (#1/0 Aluminum Multiplex) KVA Overhead Transformer (#1/0 Aluminum Multiplex) KVA Overhead Transformer (#4/0 Aluminum Multiplex) KVA Overhead Transformer (#1/0 Aluminum Multiplex) KVA Overhead Transformer (#4/0 Aluminum Multiplex) KVA Overhead Transformer (4 # 500 KCM Aluminum) KVA Overhead Transformer (#1/0 Aluminum Multiplex) KVA Overhead Transformer (#4/0 Aluminum Multiplex) KVA Overhead Transformer (4 # 500 KCM Aluminum) KVA Overhead Transformer (4 # 1000 KCM Aluminum) KVA Overhead Transformer (#1/0 Aluminum Multiplex) KVA Overhead Transformer (#4/0 Aluminum Multiplex) KVA Overhead Transformer (4 # 500 KCM Aluminum) KVA Overhead Transformer (4 # 1000 KCM Aluminum) KVA Overhead Transformer (#4/0 Aluminum Multiplex) KVA Overhead Transformer (4 # 500 KCM Aluminum) KVA Overhead Transformer (4 # 1000 KCM Aluminum) KVA Overhead Transformer (4 X 2 # 1000 KCM Aluminum) KVA Overhead Transformer (4 X 3 # 1000 KCM Aluminum) KVA Overhead Transformer (4 # 1000 KCM Aluminum) KVA Overhead Transformer (4 X 3 # 1000 KCM Aluminum) KVA Overhead Transformer (4 X 3 # 1000 KCM Aluminum)... 27
3 Effective October 24, 2013 Page 3 of 27 Pad Mounted Transformers Three Phase Padmounts Size (KVA) Impedance (%) (Ph-Ph) Sym Fault Current (Amps) , , , , , , , , , , , , , , ,523 Single Phase Padmounts Size (KVA) Impedance (%) Sym Fault Current (Amps) , , , , , , , , , , , ,792
4 Effective October 24, 2013 Page 4 of KVA Overhead Transformer (#1/0 Aluminum Multiplex) %Z: 1.4 Three Phase Bank (3-10 KVA) Service Length (Ft.) ,949 5, ,425 4, ,985 4, ,610 4, ,287 3, ,006 3, ,759 3, ,540 3, ,346 3, ,171 3, ,014 2, ,871 2, ,742 2,746 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,953 2, ,987 2, ,288 2, ,759 2, ,346 2, ,014 2, ,742 2, ,514 2, ,322 2, ,156 2, ,013 2, ,887 2, ,777 1,940
5 Effective October 24, 2013 Page 5 of KVA Overhead Transformer (#1/0 Aluminum Multiplex) %Z: 1.4 Three Phase Bank (3-15 KVA) Service Length (Ft.) ,922 7, ,986 7, ,190 6, ,516 6, ,943 5, ,454 5, ,033 4, ,669 4, ,351 4, ,072 4, ,825 3, ,605 3, ,408 3,526 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,928 4, ,193 4, ,944 3, ,034 3, ,351 3, ,824 3, ,407 3, ,070 3, ,793 3, ,560 2, ,363 2, ,194 2, ,047 2,618
6 Effective October 24, 2013 Page 6 of KVA Overhead Transformer (#1/0 Aluminum Multiplex) %Z: 1.4 Three Phase Bank (3-25 KVA) 0 14,865 12,883 6, ,472 11,279 6, ,612 9,947 6, ,175 8,851 5, ,052 7,947 5, ,158 7,196 5, ,434 6,565 5, ,837 6,029 5, ,339 5,571 4, ,917 5,174 4, ,555 4,829 4, ,242 4,525 4, ,968 4,257 4,426 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,876 7, ,615 6, ,052 6, ,433 5, ,337 5, ,553 4, ,967 4, ,512 4, ,150 4, ,855 3, ,610 3, ,404 3, ,227 3,216
7 Effective October 24, 2013 Page 7 of KVA Overhead Transformer (#1/0 Aluminum Multiplex) %Z: 1.4 Three Phase Bank ( KVA) 0 22,306 19,332 9, ,751 16,284 9, ,308 13,764 8, ,831 11,788 8, ,025 10,246 8, ,670 9,029 7, ,624 8,053 7, ,795 7,258 7, ,125 6,600 6, ,573 6,047 6, ,110 5,578 6, ,718 5,174 6, ,380 4,824 5,894 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,323 11, ,310 9, ,023 8, ,621 7, ,123 7, ,108 6, ,378 5, ,829 5, ,401 5, ,059 4, ,779 4, ,546 4, ,349 3,810
8 Effective October 24, 2013 Page 8 of KVA Overhead Transformer (#4/0 Aluminum Multiplex) %Z: 1.4 Three Phase Bank ( KVA) 0 22,306 19,332 9, ,477 17,452 9, ,113 15,802 9, ,170 14,372 8, ,573 13,140 8, ,250 12,077 8, ,145 11,156 8, ,211 10,354 8, ,415 9,651 7, ,728 9,032 7, ,132 8,484 7, ,609 7,995 7, ,148 7,557 7,186 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,323 11, ,119 10, ,574 9, ,144 9, ,413 8, ,130 8, ,146 7, ,370 7, ,743 6, ,227 6, ,795 6, ,428 5, ,113 5,572
9 Effective October 24, 2013 Page 9 of KVA Overhead Transformer (#1/0 Aluminum Multiplex) %Z: 2.0 Three Phase Bank (3-50 KVA) 0 20,813 18,038 9, ,716 15,293 8, ,613 13,031 8, ,350 11,241 7, ,679 9,830 7, ,411 8,705 7, ,424 7,795 7, ,637 7,049 6, ,997 6,427 6, ,467 5,903 6, ,022 5,455 6, ,642 5,069 5, ,316 4,733 5,621 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,828 10, ,615 9, ,677 8, ,422 7, ,995 6, ,020 6, ,313 5, ,780 5, ,363 4, ,028 4, ,753 4, ,524 3, ,330 3,711
10 Effective October 24, 2013 Page 10 of KVA Overhead Transformer (#4/0 Aluminum Multiplex) %Z: 2.0 Three Phase Bank (3-50 KVA) 0 20,813 18,038 9, ,275 16,351 8, ,154 14,872 8, ,400 13,587 8, ,948 12,474 8, ,737 11,508 7, ,718 10,667 7, ,851 9,930 7, ,108 9,281 7, ,464 8,707 7, ,902 8,196 7, ,408 7,739 6, ,970 7,329 6,794 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,828 10, ,160 9, ,950 9, ,717 8, ,106 8, ,900 7, ,968 7, ,229 6, ,628 6, ,132 6, ,715 5, ,360 5, ,055 5,359
11 Effective October 24, 2013 Page 11 of KVA Overhead Transformer (4 # 500 KCM Aluminum) %Z: 2.0 Three Phase Bank (3-50 KVA) 0 20,813 18,038 9, ,936 16,099 8, ,757 14,535 8, ,049 13,248 8, ,675 12,170 8, ,545 11,254 7, ,600 10,466 7, ,798 9,781 7, ,109 9,180 7, ,510 8,649 7, ,985 8,176 6, ,522 7,752 6, ,109 7,369 6,624
12 Effective October 24, 2013 Page 12 of KVA Overhead Transformer (#1/0 Aluminum Multiplex) %Z: 2.0 Three Phase Bank (3-75 KVA) 0 31,219 27,057 13, ,852 21,384 12, ,273 17,102 12, ,690 14,055 11, ,274 11,854 10, ,558 10,215 10, ,284 8,958 9, ,303 7,968 9, ,527 7,171 8, ,899 6,515 8, ,379 5,967 7, ,943 5,503 7, ,572 5,106 7,027 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,242 15, ,273 13, ,271 11, ,280 9, ,524 8, ,376 7, ,570 6, ,972 6, ,512 5, ,148 5, ,851 4, ,606 4, ,399 4,140
13 Effective October 24, 2013 Page 13 of KVA Overhead Transformer (#4/0 Aluminum Multiplex) %Z: 2.0 Three Phase Bank (3-75 KVA) 0 31,219 27,057 13, ,945 23,527 13, ,836 20,578 12, ,695 18,165 12, ,271 16,192 11, ,366 14,568 11, ,839 13,217 10, ,594 12,082 10, ,562 11,117 10, ,694 10,289 9, ,955 9,571 9, ,319 8,944 9, ,765 8,393 9,082 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,242 15, ,841 14, ,270 12, ,837 11, ,559 10, ,952 10, ,762 9, ,847 8, ,124 8, ,537 7, ,052 7, ,645 6, ,298 6,418
14 Effective October 24, 2013 Page 14 of KVA Overhead Transformer (4 # 500 KCM Aluminum) %Z: 2.0 Three Phase Bank (3-75 KVA) 0 31,219 27,057 13, ,153 22,907 12, ,060 19,861 12, ,113 17,529 11, ,889 15,688 11, ,152 14,197 11, ,757 12,964 10, ,612 11,929 10, ,656 11,046 9, ,845 10,285 9, ,149 9,623 9, ,545 9,040 9, ,016 8,524 8,765
15 Effective October 24, 2013 Page 15 of KVA Overhead Transformer (4 # 1000 KCM Aluminum) %Z: 2.0 Three Phase Bank (3-75 KVA) 0 31,219 27,057 13, ,250 22,980 12, ,176 19,957 12, ,225 17,630 11, ,992 15,785 11, ,244 14,288 11, ,839 13,048 10, ,685 12,006 10, ,722 11,117 9, ,904 10,351 9, ,203 9,683 9, ,594 9,095 9, ,060 8,575 8,815
16 Effective October 24, 2013 Page 16 of KVA Overhead Transformer (#1/0 Aluminum Multiplex) %Z: 2.5 Three Phase Bank (3-100 KVA) 0 33,299 28,859 14, ,667 23,099 13, ,466 18,384 12, ,480 14,982 12, ,823 12,537 11, ,957 10,733 10, ,586 9,361 10, ,539 8,290 9, ,716 7,432 9, ,053 6,731 8, ,508 6,149 8, ,052 5,659 7, ,665 5,239 7,491 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,323 16, ,465 14, ,819 12, ,582 10, ,713 9, ,505 8, ,663 7, ,042 6, ,567 5, ,192 5, ,887 4, ,636 4, ,425 4,291
17 Effective October 24, 2013 Page 17 of KVA Overhead Transformer (#4/0 Aluminum Multiplex) %Z: 2.5 Three Phase Bank (3-100 KVA) 0 33,299 28,859 14, ,892 25,275 13, ,433 22,117 13, ,963 19,471 13, ,279 17,290 12, ,177 15,491 12, ,501 13,998 11, ,142 12,748 11, ,022 11,689 11, ,085 10,785 10, ,290 10,005 10, ,609 9,326 10, ,020 8,730 9,736 Single Phase 1 Ph Sym Fault Current (Amps) Single Phase Service Length (Ft.) ,323 16, ,438 15, ,278 13, ,498 12, ,018 11, ,286 10, ,016 9, ,046 9, ,283 8, ,668 8, ,162 7, ,738 7, ,378 6,749
18 Effective October 24, 2013 Page 18 of KVA Overhead Transformer (4 # 500 KCM Aluminum) %Z: 2.5 Three Phase Bank (3-100 KVA) 0 33,299 28,859 14, ,510 24,204 13, ,014 20,839 13, ,820 18,293 12, ,434 16,300 12, ,584 14,698 11, ,109 13,383 11, ,904 12,283 10, ,902 11,351 10, ,055 10,549 10, ,331 9,854 9, ,703 9,244 9, ,155 8,706 9,146 Single Phase 1 Ph Sym Fault Current (Amps) Service Length (Ft.) ,323 16, ,020 14, ,434 13, ,107 12, ,899 11, ,328 10, ,152 9, ,240 8, ,511 8, ,915 7, ,420 7, ,001 6, ,642 6,553
19 Effective October 24, 2013 Page 19 of KVA Overhead Transformer (4 # 1000 KCM Aluminum) %Z: 2.5 Three Phase Bank (3-100 KVA) 0 33,299 28,859 14, ,508 24,203 13, ,015 20,838 13, ,822 18,293 12, ,437 16,302 12, ,589 14,701 11, ,114 13,386 11, ,909 12,287 10, ,908 11,355 10, ,061 10,554 10, ,337 9,859 9, ,710 9,249 9, ,161 8,711 9,147
20 Effective October 24, 2013 Page 20 of KVA Overhead Transformer (#4/0 Aluminum Multiplex) %Z: 2.5 Three Phase Bank (3-167 KVA) 0 55,623 48,206 24, ,878 38,973 22, ,118 31,611 21, ,643 26,195 20, ,203 22,204 19, ,019 19,197 18, ,640 16,871 17, ,804 15,029 16, ,346 13,539 15, ,163 12,311 15, ,184 11,283 14, ,362 10,411 13, ,661 9,662 13,097
21 Effective October 24, 2013 Page 21 of KVA Overhead Transformer (4 # 500 KCM Aluminum) %Z: 2.5 Three Phase Bank (3-167 KVA) 0 55,623 48,206 24, ,007 36,528 22, ,006 29,383 20, ,372 24,568 19, ,517 21,105 18, ,713 18,496 17, ,582 16,461 16, ,909 14,828 15, ,560 13,490 14, ,450 12,373 14, ,519 11,427 13, ,729 10,615 12, ,049 9,911 12,284
22 Effective October 24, 2013 Page 22 of KVA Overhead Transformer (4 # 1000 KCM Aluminum) %Z: 2.5 Three Phase Bank (3-167 KVA) 0 55,623 48,206 24, ,925 36,460 22, ,937 29,315 20, ,320 24,511 19, ,478 21,060 18, ,684 18,461 17, ,561 16,433 16, ,893 14,806 15, ,548 13,472 14, ,441 12,359 13, ,513 11,416 13, ,724 10,606 12, ,046 9,904 12,256
23 Effective October 24, 2013 Page 23 of KVA Overhead Transformer (4 x 2 # 1000 KCM Aluminum) %Z: 2.5 Three Phase Bank (3-167 KVA) Service Length (Ft.) ,623 48, ,800 41, ,925 36, ,845 32, ,937 29, ,838 26, ,320 24, ,235 22, ,478 21, ,979 19, ,684 18, ,555 17, ,561 16,433
24 Effective October 24, 2013 Page 24 of KVA Overhead Transformer (4 x 3 # 1000 KCM Aluminum) %Z: 2.5 Three Phase Bank (3-250 KVA) Service Length (Ft.) , , , , , , , , , , , , ,635
25 Effective October 24, 2013 Page 25 of KVA Overhead Transformer (4 # 1000 KCM Aluminum) %Z: 2.5 Three Phase Bank (3-250 KVA) Service Length (Ft.) , , , , , , , , , , , , ,746
26 Effective October 24, 2013 Page 26 of KVA Overhead Transformer (4 x 3 # 1000 KCM Aluminum) %Z: 3.0 Three Phase Bank (3-333 KVA) Service Length (Ft.) , , , , , , , , , , , , ,088
27 Effective October 24, 2013 Page 27 of KVA Overhead Transformer (4 x 3 # 1000 KCM Aluminum) %Z: 3.0 Three Phase Bank (1500 KVA) Service Length (Ft.) , , , , , , , , , , , , ,333
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION
INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION February 2013 NOTE: If conflict exists between St. Thomas Energy s Conditions of Service and this document, the Conditions
More informationHow To Get A Power Line Extension
GUIDELINES FOR COMMERCIAL ELECTRIC SERVICE HOOKUP 1 Steps to Commercial Service Pay the Design Deposit Commercial Buildings: Up to 1, sq ft = $1,. 1, 5, sq ft = $2,. Over 5, sq ft = $3,. Commercial jobs
More informationUnderground Commercial Electric Service
Underground Commercial Electric Service SCANA Corporation 2013 Revised: June 2013 Table of Contents SECTION PAGE I. Specification and Requirements 2 A. General B. Definition of Terms C. Company and Developer
More informationApproved Meter Sockets and Cabinets
Single Unit Residential Guide 1 PHASE, 120/240 VOLT S METERING (Metering sockets and cabinets are supplied by Customer). Outdoor meter mounting height is 1730 mm ( 5 8 ) to center of meter ± 100 mm ( 4
More information4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS
4160: THE GREEN 480 MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED MEDIUM VOLTAGE
More informationRISK MITIGATION for ELECTRICAL WORK. Feb 2013 San Diego CA
RISK MITIGATION for ELECTRICAL WORK Feb 2013 San Diego CA Agenda I. RISK Define the Risks Arc Flash Review II. MITIGATION 3 Easy Steps New Designs Vs. Existing Systems III. DUKE UNIVERSITY EXAMPLE I. Risk
More informationmisconceptions about arc-flash hazard assessments
misconceptions about arc-flash hazard assessments There are some common misconceptions about Arc-Flash Hazard Assessments which reduce the effectiveness of the Assessments and can increase electrical hazards.
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationMEDIUM VOLTAGE. Michael Mosman, PE. CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED
MEDIUM VOLTAGE ELECTRICAL SYSTEMS for DATA CENTERS Michael Mosman, PE Chief Technical Officer CCG Facilities Integration Incorporated FACILITIES INTEGRATION INCORPORATED CCG Facilities Integration Incorporated
More informationManagement Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question
More informationBGE Service Application Guidelines Commercial & Industrial Projects
BGE Service Application Guidelines Commercial & Industrial Projects To the Customer Following is important information to assist you in applying for BGE gas and/or electric service and in completing the
More informationCIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS
CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS David D. Roybal, P.E. Senior Member, IEEE Eaton Electrical 3697 Mount Diablo Boulevard Lafayette, CA 94549 Abstract Low-voltage circuit
More informationElectric Service Rules
2016 Electric Service Rules GENERAL INFORMATION TEMPORARY SERVICES OVERHEAD SERVICES UNDERGROUND SERVICES DISTRIBUTED GENERATION METERING HUD MANUFACTURED HOMES FARM SERVICES UTILITY/CATV SERVICES PRIMARY
More informationArc Flash Avoidance and its Application to Overhead Traveling Cranes
Arc Flash Avoidance and its Application to Overhead Traveling Cranes Whitepaper August 2012 Jason Wellnitz, Controls Product Manager Material Handling Numerous technical papers, bulletins, magazine articles
More informationLandscaping around electrical equipment
Landscaping around electrical equipment Electrical equipment and natural gas lines are a part of every home s landscaping. Whether these are visible, such as an overhead powerline or a padmount transformer,
More informationSECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER SIZING GUIDELINES
Issued 06-01-07 DESIGN Section DVD00 INFORMATION SECTION Page 1 of 1 INDEX SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER INTRODUCTION... Page 2 LOAD ESTIMATING AND TRANSFORMER SIZING GUIDELINES...Page
More informationWhat Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin?
What Are the Qualifications to Conduct Arc Flash Studies? Where Do You Begin? Comparing apples-to-apples bids Plant Services Special Report A shock hazard analysis should be included as part of an arc
More informationWellesley Municipal Light Plant. Standard Requirements for Electric Service
Wellesley Municipal Light Plant Standard Requirements for Electric Service Index Section 1... General Information Section 2..General Requirements for Service Section 3. Types of Available Service Section
More informationBypass transfer switch mechanisms
Power topic #6013 Technical information from Cummins Power Generation transfer switch mechanisms > White paper By Gary Olson, Director, Power Systems Development This paper describes the configuration
More information11 Guardrail. W-Beam Guardrail Pre-Installation Inspection During Installation Basis for Use. Modified Guardrail. End Treatments and Transitions
11 Guardrail W-Beam Guardrail Pre-Installation Inspection During Installation Basis for Use Modified Guardrail End Treatments and Transitions Footings and Anchors Impact Attenuators Measurement and Payment
More informationIssued 06-01-07 E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1
Issued 06-01-07 E.C.S. Section WTR00 INFORMATION SECTION Page 1 of 1 INDEX SECTION WTR01: ELECTRICAL CONNECTIONS PRIMARY.. Page 1 SERVICE DROPS FROM THREE-PHASE TRANSFORMER BANKS.. Page 9 SECTION WTR02:
More informationNEGLIGENCE BY DOCTORS AND OTHER HEALTH PROFESSIONALS A GUIDE TO YOUR ENTITLEMENTS
NEGLIGENCE BY DOCTORS AND OTHER HEALTH PROFESSIONALS A GUIDE TO YOUR ENTITLEMENTS This guide includes the following: Adverse outcomes contrasted with negligent outcomes. What is negligence? If my treatment
More informationArc Flash Mitigation. Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear.
Arc Flash Mitigation Remote Racking and Switching for Arc Flash danger mitigation in distribution class switchgear. Distance is Safety We will discuss through examples of actual occurrences and possible
More informationTown of Maiden. Request for Proposals For Sign Replacement Project
Town of Maiden 19 N. Main Avenue Maiden, NC 28650 (828) 428-5000 Request for Proposals For Sign Replacement Project Section I Introduction and Intent of RFP: Pursuant to the General Statutes of North Carolina
More informationIO-DIM6 6-Channel, Digital to Analogue Converters
Page 1 of 6 IO-DIM6 6-Channel, Digital to Analogue Converters Features: Benefits: Input status indication Calibrated output DIN Rail mounting Expands controller input capacity Fault finding LED indication
More informationTransformer-coupled passive transmit path with a fixed insertion loss of approximately 1.0dB.
Charles Industries, Ltd. Section 319 29P 201 Equipment Issue 1 Second Printing, August 1999 STS 3192 9P Short Loop Office Repeater CONTENTS Complies with UL Standard 1459 Second Edition. PAGE Part 1. GENERAL.............................................................................
More informationThis section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
More informationELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS
Prepared by: ABB1 ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS 052521 Asset Type: Electric Metering Function: Construction Issued by: Quoc Hoang (QxH1) Date: 07-01-16 Rev. #06: This document
More informationBRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E
BRANDON AND CLARK INC. // SCOTT W. CLARK, P.E. ELECTRICAL CONTINUING EDUCATION ARC FLASH - NFPA 70E Training is not a substitute for following corporate safety guidelines. Always refer to the latest safety
More informationCall the Experts at REA Energy Services for all of Your Electrical and HVAC Needs.
Call the Experts at REA Energy Services for all of Your Electrical and HVAC Needs. REA Energy Services Sells and Installs: Heating and Air Conditioning Electrical Contracting Geothermal Heat Pumps Back-Up
More information4/1/2016 Revision of the CNP Service Standards Book (Effective Date 5-1-2016)
0 4/1/2016 Revision of the CNP Service Standards Book (Effective Date 5-1-2016) 1. Article 422.1 Meter Pole Installations - Requirements (Page 59). Revised paragraph - Steel poles shall be truck accessible.
More informationChanges in the 10/2/2013 Revision of the CNP Service Standards Book
0 Changes in the 10/2/2013 Revision of the CNP Service Standards Book 1. Article 303 - Three Phase (Page 19). Revised 240/120V Delta, Added Max Load to Overhead and Underground 2. Article 408 - Service
More informationLow Voltage Transformer Through-Fault Protection: A System Approach
Data Bulletin 7400DB1001 Nashville, TN USA Low Voltage Transformer Through-Fault Protection: A System Approach Introduction Low Voltage Transformer Protection Criteria NEC Article 450 Transformers and
More informationFIT TIER 2 Application
FIT TIER 2 Application Application Information The below information Auto-Fills from your registration information: Building Permit Application Date: Project Completion Date: Name: Address: City: State:
More informationSimple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
More informationNovember 2014. Stray Voltage Test Procedure for Electrical Contractors
Stray Voltage Test Procedure for Electrical Contractors 1 LIMITATION OF LIABILITY AND DISCLAIMER Any person who uses, relies on, or otherwise deals with this document and the information herein, does so
More informationPolicy and Guidelines for Electric Service
Policy and Guidelines for Electric Service FRANKLIN MUNICIPAL POWER & LIGHT 1050 Pretlow Street Franklin, VA 23851 757-562-8568 757-562-7883 Fax January 2008 Franklin Power & Light HELPFUL TELEPHONE NUMBERS
More information3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
More informationTechnical Guide. SKM Arc Flash Line Side vs. Load Side
SKM Arc Flash Line vs. Load The option of choosing the line-side or the load-side arc flash incident energy for arc flash labels is an important decision when performing an arc flash hazard analysis. When
More informationLitigation Services & Information
Litigation Services & Information Laurence "Lo" Lehman, P.E. Lehman Engineering Company Lehman Engineering has been providing engineering, design, and consulting services for electrical power systems to
More information4. REQUEST FOR ELECTRIC SERVICE. 4.1 General Service Information
4. REQUEST FOR ELECTRIC SERVICE To establish an electric service, temporary or permanent, contact UI s Customer Care Center by calling: 1-800-722-5584 (7:00 a.m. 7:00 p.m., Monday Friday and 7:00 AM to
More informationWelcome to Home Wiring Repair Essential. No-cost, no hassle home wiring repairs.
Welcome to Home Wiring Repair Essential. No-cost, no hassle home wiring repairs. Important program terms and conditions are inside. Please file for future reference. 2015 Duke Energy Corporation 151299-hw
More information2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes
2012 Canadian Electrical Code, Part I (CEC) Top Fifteen changes 1) Tamper resistant receptacles. 2009 CEC Required in dwelling units 2012 CEC Expanded to child care facilities First introduced in the 2009
More informationCeiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
More informationElectrical. This section applies to the design and installation of building power distribution systems.
Basis of Design This section applies to the design and installation of building power distribution systems. Design Criteria This section contains the architectural, structural and mechanical provisions
More informationOracle Health Sciences Network Patient Recruiter Cloud Service - Overview
Oracle Health Sciences Network Patient Recruiter Cloud Service Services Description Version: 2.0 Effective Date: 01-April-2013 Oracle Health Sciences Network Patient Recruiter Cloud Service - Services
More informationConsidering UNDERGROUND. tampaelectric.com
Considering UNDERGROUND Electric Service? tampaelectric.com INTRODUCTION The majority of Tampa Electric s customers receive their electric service through overhead construction, which is the standard type
More informationHelp protect your home, possessions and family.
Help protect your home, possessions and family. A guide to your Square D electrical distribution system SM Make the most of your energy Understanding your home s electrical distribution system As one of
More informationPrimary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
More information2.4 kv to 34.5 kv SP-1099
Specifications for Customer Electric Service 2.4 kv to 34.5 kv SP-1099 FORWARD...1 CHAPTER 1 - PRIMARY METERED SERVICE...4 General Service Information...4 CA-206...6 CA-208A...7 Section 1...8 Existing
More informationMOBILE HOME SERVICE REQUIREMENTS GAS
ELECTRIC AND GAS 1.0 INDEX 1.0 INDEX 2.0 PURPOSE 3.0 GENERAL 4.0 REFERENCE MATERIAL 5.0 TYPICAL UNDERGROUND UTILITY LAYOUT 6.0 METER PAD DETAILS 7.0 GENERAL INSTALLATION PROCEDURES 8.0 PEDESTAL SPECIFICATIONS
More informationBroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
More informationSchool District Design and Project Management For Rochester, NY
The following is a list of projects completed by Engineered Solutions or its President Eric Sheffer, P.E.: Medium Voltage Design and project management for replacement of 1500KVA double ended substation
More informationMODEL VG08008 CONTENT PACKING LIST / TOOLS NEEDED PANEL DIMENSIONS FITTINGS / TECHNICAL DATA WALL/CORNER INSTALLATION CARE AND TROUBLE SHOOTING
CONTENT PACKING LIST / TOOLS NEEDED PANEL DIMENSIONS FITTINGS / TECHNICAL DATA WALL/CORNER INSTALLATION CARE AND TROUBLE SHOOTING WARRANTY 1 PACKING LIST DESCRIPTION MODEL NUMBER - PANEL HOUSING 88062
More informationTABLE OF CONTENTS 1.0 INTRODUCTION... 2 1.1 PURPOSE... 2 1.2 DEVIATION... 2 4.0 INTERTIE PROTECTION REQUIREMENTS... 4
Page: 1 of 14 KEY BULLETIN POINTS: THIS GUIDE OUTLINES MINIMUM REQUIREMENTS FOR CONNECTION OF CUSTOMER-OWNED EMERGENCY AND STANDBY (ESG) TO THE GEORGIA POWER COMPANY (GPC) DISTRIBUTION SYSTEM. THESE ARE
More informationElement D Services Electrical
Service and PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as
More informationApplying For New or Revised Electric Service
Applying For New or Revised Electric Service Dear Customer: ComEd is happy to assist you in initiating new or revised electric service to your location. Please complete, sign and return the attached service
More informationATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
More informationELECTRIC SERVICE GUIDELINES (For Indiana)
ELECTRIC SERVICE GUIDELINES (For Indiana) FOR COMMERCIAL / INDUSTRIAL DEVELOPMENTS ELECTRIC SERVICE GUIDELINES FOR COMMERCIAL/INDUSTRIAL DEVELOPMENTS INTRODUCTION... 2 WHAT YOU NEED TO OBTAIN ELECTRIC
More informationSnow/Ice Melt Heating Cable System Gutters & Roof Drains Installation Manual Nexans TXLP/1 Series Resistance Cables
1. GENERAL INFORMATION Description Snow or ice dams that have built up on a roof can cause water damage to the interior of homes as well as damage to gutters and downspouts. This custom TXLP/1 single conductor
More informationNFPA 70E Updates Affect Your Most Valuable Assets
NFPA 70E Updates Affect Your Most Valuable Assets EXECUTIVE SUMMARY Electrocution is a well-known hazard associated with direct contact with electrical energy. According to the U.S. Department of Labor,
More informationAN96-07. Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x
TRANSIENT IMMUNITY STANDARDS: IEC 61000-4-x On January 1, 1996, exports into Europe began facing some tough transient immunity standards. The International Electrotechnical Commission (IEC), a worldwide
More informationWritten Program ELECTRICAL SAFETY. Based on OSHA Subpart S and NFPA 70E Standards
Written Program ELECTRICAL SAFETY Based on OSHA Subpart S and NFPA 70E Standards Revised November 2012 Disclaimer The presentations and program provided by Workplace Safety Solutions, Inc. are based on
More informationCritical SQL Server Databases:
Webinar Critical SQL Server Databases: Provide HA with SQL Server Failover Clustering and Cluster Shared Volumes Edwin Sarmiento Microsoft MVP/Microsoft Certified Master: http://www.edwinmsarmiento.com
More informationL5354 ControlNet Communications Interface
L5354 ControlNet Communications Interface Technical Manual HA470733 Issue 2 Copyright SSD Drives Inc 2005 All rights strictly reserved. No part of this document may be stored in a retrieval system, or
More informationTransmission Business Electrical Incident & Safety Performance Reporting Guide
Transmission Business Electrical Incident & Safety Performance Reporting Guide December 2011 Version 1.0 Energy Safe Victoria PO Box 262 Collins Street West MELBOURNE VIC 8007 AUSTRALIA Telephone (03)
More informationBS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
More informationPIPELINE AND UTILLITY PERMIT APPLICATION PACKET
Orange County Drainage District 8081 Old Hwy 90 Orange, Texas 77630 Main Office (409) 745-3225 Fax (409) 745-3004 PIPELINE AND UTILLITY PERMIT APPLICATION PACKET Contact the Orange County Drainage District
More informationHeat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation.
Heat Tracing is the use of an externally applied heat source to a pipeline to compensate for heat losses through the thermal insulation. Heat tracing evolved from the need to maintain the flow of low,
More informationApplication for. Commercial New Service
Application for Commercial New Service Welcome to Lake Country Power! In order to make your new service installation easy, we provide individualized help to process and install a new service. In order
More informationBC Hydro. Electric Distribution System Cost of Service Study
BC Hydro Electric Distribution System Reimer Consulting Group Inc. Arnie Reimer May 7, 2010 Table of Contents 1. Executive Summary... 3 2. BC Hydro Electric Distribution System... 4 2.1. General Description...
More informationUL 508A Industrial Control Panels Power Distribution and Control. Lunch & Learn Training. 2002 Eaton Corporation. All rights reserved.
UL 508A Industrial Control Panels Power Distribution and Control Lunch & Learn Training 2002 Eaton Corporation. All rights reserved. Agenda Who is UL and what role do they play? What is the UL 508A Standard?
More informationHyperlinks are Inactive
Prepared by: NIB/EOB PLANNING GUIDE FOR SINGLE CUSTOMER SUBSTATIONS SERVED FROM TRANSMISSION LINES 05503 Department: Electric T&D Section: T&D Engineering and Technical Support Approved by: G.O. Duru (GOD)
More informationHow Much Voltage Drop Is Acceptable?
How Much Voltage Drop Is Acceptable? Article supplied by Ideal The National Electrical Code (NEC) recommends that the combined voltage drop of the electrical system (branch circuit and feeders) not exceed
More informationWelcome to Home Wiring Repair Premium. No-cost, no hassle home wiring repairs.
For more information about all the powerful ways Duke Energy can help you, please visit duke-energy.com/homeprotection or call 888.999.8856. Welcome to Home Wiring Repair Premium. No-cost, no hassle home
More informationSPECIFICATIONS FOR ELECTRIC SERVICE GARLAND POWER & LIGHT
FOREWORD This booklet is issued by the Electric Department of the City of Garland, herein after referred to Garland Power & Light or GP & L, to acquaint electric customers of Garland Power & Light, or
More informationData Center Server Cart User Guide
Data Center Server Cart User Guide Contents General Safety Information 1 Correct Use 1 Improper Use 1 Personnel Qualifications 2 Product Description 2 Operating Data 2 Setting Up the Data Center Server
More informationMAJOR EQUIPMENT PURCHASE CONTRACT
MAJOR EQUIPMENT PURCHASE CONTRACT CONSUMERS ENERGY COMPANY ONE ENERGY PLAZA JACKSON, MI 49201 ( Buyer ) ( Seller ) Date:, 20 Subject to the provisions of this Major Equipment Purchase Contract ( Contract
More informationDistribution Substation Manual (DSM) Section 3 Substation Arrangements
(DSM) Section 3 Substation Arrangements July 2015 Document release information Client Project name Western Power Distribution Substation Manual Document number 5 Document title Revision status Substation
More informationOVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B
OVR-3SP Recloser with PCD Control Style Guide 1VAL263901-SG March 30, 2009 Revision B The OVR-3SP three-phase recloser style guide aids in the proper selection of your OVR-3SP style number. The OVR-3SP
More informationInformation and Requirements for Electric Service. Chapters 1, 2, 4, 6 and Appendix
Organization: Manual: Section: Electric Distribution Information and Requirements for Electric Service Chapters 1, 2, 4, 6 and Appendix Tracking Number: 05-077 Date: January 6, 2006 SME: Jim Calore Contact
More information3.) Remove Page Nos. 15, 16, 17, 18, 19, 20, 21, 22 of 30 and replace with Page Nos. 15, 16, 17, 18, 19 & 20 of 28 marked, REVISED 10/18/2013.
CITY OF HOUSTON Annise D. Parker Mayor P.O. Box 1562 Houston, Texas 77251-1562 Telephone Dial 311 www.houstontx.gov http://purchasing.houstontx.gov October 22, 2013 Subject: To: Letter of Clarification
More informationPower plant safety: a wise business move
Power plant safety: a wise business move Power plant safety: a wise business move Going to work in a controlled and safe environment is not an unreasonable expectation for any worker. In many occupations,
More information2013WWOA Conference Technical Conference Program
2013WWOA Conference Technical Conference Program Understanding Arc-Flash Hazards, Its Implications on Operations and Solutions that Mitigate Such Exposure Presented by Jerry Baskin Senior Product Manager
More informationELECTRIC RATE SCHEDULES
LITTLETON WATER & LIGHT DEPARTMENT 65 LAFAYETTE AVENUE LITTLETON, NH 03561 ELECTRIC RATE SCHEDULES 1. Table of Contents 2. Residential Service Rate 3. Special Service Rate a. Churches b. Municipal Public
More information16300 MEDIUM VOLTAGE DISTRIBUTION
16300 MEDIUM VOLTAGE PART 1: GENERAL 1.01 SYSTEM DESCRIPTION A. Most new loads will be served from the underground electric distribution system. This system is a primary open loop configuration served
More informationJob Site Electrical Safety A Matter of Life and Death
Job Site Electrical Safety A Matter of Life and Death Scott Forsyth, PE Senior Engineer Johnson Controls Performing the Job Right and on Time is Top Priority!!!! Right? Wrong!!!! Performing the Job Safely
More information-1- HARDWICK ELECTRIC DEPARTMENT STREET LIGHTING RATE 06
-1- AVAILABILITY: To be available for street lighting purposes and billed to the appropriate municipality, village, town, governmental unit and unincorporated community within the Hardwick Electric Department
More informationQUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room
QUESTIONS and ANSWERS RFB 745-15-9894, Metal Clad Switchgear and Power Control Room 1) When you click on the UTHSCSA Drawing the site takes you to the E-1 drawing no other. Will there be other drawings
More informationInternet Application for New Multi-Family Electric Service Builders/Developers Fax to: (800) 351-3853 or call (800) 454-3853 Date Faxed: 1
Internet Application for New Multi-Family Electric Service Builders/Developers Fax to: (800) 351-3853 or call (800) 454-3853 Date Faxed: 1 2 Service address City 3 (Inside city: Yes No) State 4 Complex
More informationBest Practices to Minimize Action Over Claims
Best Practices to Minimize Action Over Claims David Matthiessen Vice President, Claims Everest National Insurance Company The information presented in this material has been developed from sources believed
More informationRadial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
More informationIn the year Two Thousand Eleven.. Resolved by the City Council of the City of Burlington, as follows:
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 APPROVAL OF AMENDMENTS TO BURLINGTON ELECTRIC DEPARTMENT S OPERATING GUIDELINES In the year Two Thousand Eleven.. Resolved
More information10 ma LED driver in SOT457
SOT457 in SOT457 Rev. 1 20 February 2014 Product data sheet 1. Product profile 1.1 General description LED driver consisting of resistor-equipped PNP transistor with two diodes on one chip in an SOT457
More informationHIGH-RELIABILITY DESIGNS FOR ECONOMICAL DATA CENTERS
HIH-RLIABILITY DSINS FOR CONOMICAL DATA CNTRS Design Features that Add Reliability to Data Centers while Reducing Costs per kw Michael Mosman, P Vice President, Chief Technology Officer Baltimore, MD Discussion
More informationWhat s up with Arc Flash?
What s up with Arc Flash? Presented by Mark Haskins, CSP Practical Safety Solutions, LLC CONN OSHA Breakfast Roundtable February 18, 2014 2014 Practical Safety Solutions, LLC What is Arc Flash? Definition
More informationChoosing the Best Solution for Reducing Arc Energy
CONVENTION SESSION HANDOUT Choosing the Best Solution for Reducing Arc Energy Terry L. Schiazza, Business Development Manager Square D / Schneider Electric SESSION #11 Independent Electrical Contractors
More informationPreliminary Feasibility Assessment For. The Rio Tinto Alcan to BCH Transfer Limit of 460 MW. With 50% Series Compensation on Both KMO KIT lines
Preliminary Feasibility Assessment For The Rio Tinto Alcan to BCH Transfer Limit of 460 MW With 50% Series Compensation on Both KMO KIT lines Report : ASP2010-T001 July 2010 Asset Strategy & Planning,
More informationSUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS
SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS PRIMARY METER POLE ELECTRIC SYSTEM BULLETIN No. 753 JUNE 1993, 2 ND PRINTING APRIL 2002 (Supersedes issue dated March 1983 and incorporates Nov.
More informationABB ! CAUTION. Type COQ Negative Sequence Generator Relay. (50/60 Hertz) 41-161J. Instruction Leaflet
ABB Instruction Leaflet 41-161J Effective: May 1997 Supersedes I.L. 41-161H Dated July 1984 ( ) Denotes Change Since Previous Issue Type COQ Negative Sequence Generator Relay (50/60 Hertz)! CAUTION Before
More information