CANTON FIRE DEPARTMENT
|
|
|
- Lambert Gray
- 9 years ago
- Views:
Transcription
1 CANTON FIRE DEPARTMENT Dean Floyd Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES FIRE PREVENTION CHECKLIST- To review prior to your inspection. 1. Is the address of your property clearly visible and marked in large numbers that can be easily seen from the street? Is the business name posted front and rear? Ensuring that the building or suite is visibly lettered and numbered ensures that responders in an emergency situation can readily find the location in a timely manner. Address numbers shall contrast with their background. Numerals shall be not less than four inches in height for residential and at least six inches in height for all other buildings, structures, or portions thereof. No script numerals shall be used. For buildings not visible from the street a post or sign on the roadway shall indicate the property number. Multi occupancy commercial buildings must be labeled front, rear and on all doors with the name of the occupancy in six inches high contrasting letters. 2. Is there at least one fire extinguisher within 75 feet travel distance from anywhere in the business? Ensuring that you or your employees have to travel no more than 75 feet to get to a location of a fire extinguisher ensures that the extinguisher can be quickly accessed. 3. Is the fire extinguisher mounted in a visible and accessible location? Ensuring that the fire extinguisher(s) is mounted visibly saves confusion in an emergency. Also, the fire extinguisher should be mounted near an exit so if you decide not to attempt to extinguish the fire, you can quickly exit the building. Extinguishers having a gross weight not exceeding 40 lb. shall be installed so that the top of the fire extinguisher is not more than 4 ft. above the floor. Extinguishers having a gross weight greater than 40 lb. shall be so installed that the top of the fire extinguisher is not more than 3 1/2 ft. above the floor. In no case shall the clearance between the bottom of the extinguisher and the floor be less than 4 in. 4. Is the fire extinguisher classification 2A 10BC or greater? (Size can be found on the extinguisher's label.) The fire extinguisher must be a minimum size rating of 2A-10BC dry chemical-type fire extinguisher to ensure that it is the proper size to put out a fire, should you have one. Does the commercial kitchen have a K Type extinguisher? Do your employees know the difference between an ABC and a K type extinguisher?
2 5. Have the fire extinguisher(s) been serviced within the last year? Checked monthly? Fire extinguisher(s) in a commercial structure must be inspected by a fire extinguisher company annually to ensure that they are in working order. Keeping a monthly checklist (on the rear of all inspection tags) for extinguishers serves two purposes; it helps employees learn the location and type of extinguishers and it notifies managers when it is time for an annual test. 6. Is there only one thumb turn or key lock on each exit door? (No slide bolts are allowed to be on exit doors.) Only one locking device is allowed on exit doors, and it must require only one action to open. This assures that in an emergency, the exit doors work and allow the people in the structure to exit without delay. 7. If the exit door has a key lock, do the required exit door(s) have a sign that reads, "This door to remain unlocked when building is occupied"? The signage needs to be affixed on all keyed exit doors to ensure that they remain unlocked at all times when the building is occupied. 8. Are exits identified with a lighted EXIT sign? Exit signs direct occupants to the required exits and, when required, should be illuminated at all times and have a battery backup to provide operation during a power outage. All bulbs in the light shall be working. Replace any burnt out bulbs or defective batteries. 9. Is the exit(s) clear of obstructions so during an emergency, people can exit quickly and safely? A path, equal to the width of the exit door, must remain clear and unobstructed at all times to allow persons in the building unrestricted exit. Are the exits easy to open and properly lit? 10. Do electrical panels have a 36-inch clear area in front for easy access? A 36-inch clear area needs to be maintained around electrical panels at all times so maintenance can be safely performed. The doors to the electrical panels should remain closed to minimize the chance of sparks being thrown in the event of an electrical failure or arc flash. Storage should be kept to a minimum in electrical panel rooms. 11. Are the electrical panels properly labled? Can you find the circuit breakers that provide power to emergency lights, exit signs and the Fire Alarm Control Panel (FACP)? All circuit breakers must be labled to properly isolate power where needed in an emergency. Properly marked breakers will allow you to test your emergency lights and exit signs periodically to ensure they will function correctly in case of an emergency. The FACP must have a dedicated circuit that is labled in the electrical panel and the circuit breaker must be locked in the on position to protect against tampering. 12. Are all stored materials stacked so they are at least two feet below the ceiling? Storage should be kept in an orderly manner and with at least two feet of clearance to the ceiling for buildings that are not equipped with an automatic sprinkler system. Eighteen inches of clearance is required in buildings that have an automatic sprinkler system. These clearances serve two important purposes: 1) They allow an area for smoke to collect in the event of a fire, giving persons in the building adequate time to exit, and 2) They provide a clear area so the spray pattern of a sprinkler head is not obstructed allowing the sprinkler system to function properly.
3 13. If you have emergency lighting, does it work? Emergency lighting provides occupants the light needed to see the exits in an emergency. The lighting should be checked monthly to ensure that it is working properly. Emergency lighting should be tested monthly and a log be maintained. Curtains, draperies or signs that may obscure an exit or emergency lights are not permitted. 14. Are the areas outside and around the building free of weeds, debris and trash? Keeping the area around the building clear of high grass, weeds, and trash or debris reduces the fire risk around the outside of your building and also provides easy visibility for police officers patrolling the area. 15. Are extension cords used only for temporary use? Extension cords used for temporary use should be of good quality and listed for the application for which they are being used. This minimizes the risk of the extension cord overheating and potentially causing a fire. Extension cords cannot be used in lieu of permanent wiring. 16. Do the electrical receptacles have no more than two items plugged into them? Electrical outlets should have no more than one item per outlet plugged into them, which may include one listed outlet strip for each outlet without exceeding the ampacity. Following this practice minimizes the chance of circuit overload. 17. Are the electrical appliance cords in good repair? You can minimize the risk of electrical shock and fire by simply inspecting all appliance cords periodically for signs of fraying or damage, and replacing a cord if needed. 18. Are all electrical recepticle and switch boxes equipped with covers to protect the user from shock? All electrical junction boxes must be equipped with a cover plate which protects the employees and customers in your building from the dangers of electrical shock and prevents sparks from exiting the outlet junction box in the event of an electrical failure. 19. Are all garbage containers at least 5 feet away from combustible walls, combustible roofs, windows or door openings? Your trash cans and dumpsters should be kept a minimum of 5 feet away from exterior walls and roof overhangs. They should not be stored in the path of the exits. This minimizes the risk of your building catching on fire in the event of a fire in the dumpster. 20. Are there quantities of flammable or combustible liquids being stored on site? Small quantities of flammable or combustible liquids must be stored in approved and rated safety containers that are designed for the type of liquid being stored. Safety containers provide protection from damage and leakage of the material as well as leakage of vapors. The inspector will review storage limits with the property owner.
4 21. If quantities of more than 5 gallons of flammable or combustible liquids are being stored, are they in noncombustible cabinets? It is advised that you not store any flammable or combustible materials in your building but if you choose to do so, smaller quantities must be stored in listed and rated flammable storage cabinets. If you store larger quantities, fire-rated construction requirements for your building are required. 22. If you have a sprinkler system in your building, has it been tested and serviced within the past twelve months? Your sprinkler system must be checked annually by a fire sprinkler company that is licensed and certified in the state of Georgia. A compliant sprinkler system has a green tag hanging on the main riser in the sprinkler riser room. The owner or designated representative must immediately contact the fire department if the sprinkler system is tagged yellow or red. The sprinkler room must be labeled RISER ROOM on the door to the area. The Fire Department Connection must be labeled with a red sign with white letters FDC *** The last 3 years of reports are to be supplied at time of inspection*** 23. If your building has a fire alarm system, has the system been tested and serviced within the past twelve months? Your fire alarm must be checked annually by a fire alarm company that is licensed and NICET certified in the state of Georgia. During your inspection we may have you test the alarm to insure the monitoring company is properly receiving the signal. Batteries in the Fire Alarm Control Panel must be labled with the date of manufacture. A floor plan of all the zones in the fire alarm system must be mounted next to the fire alarm panel in a way to prevent tampering. A list of building contacts, managers shall also be posted. *** The last 3 years of reports are to be supplied at time of inspection*** 24. Is the area around the furnace, water heater or any other heat producing appliance clear of combustible materials? Keeping a minimum 36-inch clear area around any heat-producing appliance minimizes the chance of it igniting combustible materials due to the radiant heat the appliance produces. 25. If your building has a cooking equipment exhaust hood, has the hood been cleaned within the past 4, 6 or 12 months as required? Proper cleaning of the vent hood at least twice a year minimizes the chance of fire that could result from excessive grease build up. A properly trainined, qualified and certified company must clean the hood on a regular basis. The Fire Inspector can mandate more frequent cleanings if needed. *** The last 3 years of reports are to be supplied at time of inspection*** 26. If your cooking equipment exhaust hood has a fire suppression system, has it been serviced in the last six months? Proper maintenance of the hood suppression system must be performed every six months by a company licensed to service the system. ***The last 3 years of reports are to be supplied at time of inspection*** 27. Are exhaust fans clean and free of dust, grease and/or fat build up? There are a number of instances where ceiling exhaust fans, clothes dryers and bathroom heater/light/fan combinations have failed and in some instances caught fire. The buildup of dust, grease and fat can lead to restricted air. This can then result in increased operating temperatures and eventually a fire could be the result.
5 28. Are there any missing or damaged ceiling tiles in the building? Missing, damaged and/or dislodged ceiling tiles negatively affect the integrity of the fire sprinkler system in the building. Replace any damaged or missing tiles and fix any dislodged tiles. Sheetrock is also part of the fire protection system in a building and prevents the spread of fire. All holes in sheetrock shall be repaired. 29. Does the Fire Department have an up to date copy of all emergency contacts? If the Fire Department does not have valid contact information, please inform the fire department or provide it to the Fire Inspector at time of inspection. 30. Are Fire Lanes marked and maintained and proper signage posted? Fire lanes are designated by the Fire Department to allow access to the buildings and sprinkler system connections. They must remain open and accessible for fire trucks and ambulances. Signage and or curb marking are required. Fire lanes must be a minimum of 18 feet wide and 14 feet high. 31. Is there a lock box on the building? All commecial properties are required by city ordinance to have a Fire Department Lock Box. The Fire Department specifically uses the "Knox Box" system. This allows non- damaging access to the building by the fire department during off business hours to check for alarm conditions or sprinkler problems. Knox boxes can be ordered at, Are chemicals stored properly? Are any chemicals on site stored as to not create a hazard? Is pool chemical storage rooms labeled? 33. No Smoking! Smoking is prohibited where conditions are such as to make smoking a hazard and in places where flammable or combustable materials are stored or handled. 34. Barbeque Grills and propane tanks Charcoal Grills or open flame devices should be used ten feet from combustible structures and not used on combustible surfaces such as wood decks or balconies. Propane cannot be stored or used above the level of the first floor on decks or balconies. Propane should never be stored inside a building or near an exit. 35. Are window treatments or decorations fire resistant and approved for use in a public building? Window treatments, decorations, upholstered furniture in most public buildings are subject to NFPA 701 flammability standard. A certification tag must be affixed to the items that meet the standard. 36. Is the Occupancy load of a room clearly posted? Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design, with a minimum 3 inch high numbers in contrasting colors, and shall be maintained by the owner or authorized agent.
6 . Do you have an Emergency / Preparedness Plan? The development of emergency plans, training and conducting of fire exit drills shall comply with the applicable requirements of the Fire Code. Places of Assembly; (a)general. The employees or attendants of places of public assembly shall be trained and drilled in the duties they are to perform in case of fire, panic or other emergency. (b) Egress plan. A plan showing the occupant load, seating diagram and location of exits and of aisles leading thereto shall be submitted to the fire department and an approved copy shall be conspicuously posted in the premises.
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
Town of Bellingham Fire Department
Town of Bellingham Fire Department OFFICE OF THE Fire Prevention Division Captain Robidoux- [email protected] Lieutenant Bangma- [email protected] Fire Safety Inspection Guidelines for
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
Fire and Life Safety Requirements for Special Events and Temporary Use of the Facilities at the Kitsap County Fairgrounds.
Fire and Life Safety Requirements for Special Events and Temporary Use of the Facilities at the Kitsap County Fairgrounds. PURPOSE This document is developed to assist event planners and responsible parties
Minnesota State Department of Public Safety
Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
HAZARDS AND THREATS WILDFIRES HOMEOWNERS CHECKLIST INSIDE THE HOME
HAZARDS AND THREATS WILDFIRES HOMEOWNERS CHECKLIST INSIDE THE HOME KITCHEN Keep a working extinguisher in the kitchen. Maintain electric and gas stoves in good operating condition. Keep baking soda on
MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services
MITT ROMNEY GOVERNOR KERRY HEALEY LT. GOVERNOR EDWARD A. FLYNN SECRETARY The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services P.O. Box 1025 State Road Stow, Massachusetts
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
Errata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
Commercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.
1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310
MONARCH FIRE PROTECTION DISTRICT
MONARCH FIRE PROTECTION DISTRICT 13725 OLIVE BLVD., CHESTERFIELD, MO 63017 314-514-0900, EXT. 309 [email protected] www.monarchfpd.org TENT / BOOTH REQUIREMENTS To help insure the safety, health
TOWN OF DAVIE BUSINESS TAX RECEIPT 6591 ORANGE DRIVE DAVIE, FLORIDA 33314-3399 PHONE: 954.797.1212 FAX: 954.797.1086 WWW.DAVIE-FL.
BUSINESS TAX RECEIPT BUSINESS TAX RECEIPT CHECKLIST FOR SUBMITTALS COMMERCIAL/INDUSTRIAL The following information is required in order for your application to be submitted for review. Items A-E are required
Code Compliance Guideline: Swimming Pool Chemicals
A publication of Fairfax County, Virginia CODE COMPLIANCE GUIDELINE SWIMMING POOL CHEMICALS AND FIRE SAFETY REQUIREMENTS RELATED TO POOL OPERATIONS This publication outlines the Fire Prevention Code requirements
CHILD CARE CENTER INFORMATION SHEET
CHILD CARE CENTER INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2007 Minnesota State Fire Code (MSFC) and the 2007 Minnesota State Building Code (MSBC). It
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST
SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST School Name: School Address: Town: Phone: Inspected By (Please Print): Inspection Organization Name: Inspector Phone: Date of Inspection: Building Name:
Monthly Inspection Checklists
Monthly Inspection Checklists These safety checklists are part of a monthly inspection of church property. The items listed are not meant to imply that other concerns could not be present. The items listed
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
Special events and tents Fire and life safety requirements
Special events and tents Fire and life safety requirements Section A - Temporary Use Occupancies or Operations Fire and Life Safety Requirements In order to provide a standard method of inspection of temporary
Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
Medicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012
Medicine Hat Fire Department Special Event Requirements August 202 medicinehat.ca/fire The following is a standard guide for event organizers to ensure occupant safety and compliance with the Alberta Fire
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1
Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection OSHA Office of Training and Education 1 Introduction Fires and explosions kill more than 200 and injure more than 5,000 workers
FIRE AND LIFE SAFETY TRAINING
FIRE AND LIFE SAFETY TRAINING 1 Objectives General Information Emergency Evacuation Plans / Regulatory Requirements Notification Systems Emergency Exits and Fire Doors Electrical Safety Fire Prevention
ESTABLISHMENT OF A NEW BUSINESS
ESTABLISHMENT OF A NEW BUSINESS ATTENTION BUSINESS OWNERS Certificate of Occupancy Permit Requirements & Application Prior to any materials associated with your business being moved into the property that
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
LOS ANGELES CITY FIRE DEPARTMENT
LOS ANGELES CITY FIRE DEPARTMENT Division 5 Permit LOCATION INFORMATION FD USE ONLY Date of Use: Date Granted PERMIT # Date Expires Name Phone#: City: Los Angeles State: California Zip: 90089 CONTRACTOR
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
Home Electrical Safety Challenge
Home Electrical Safety Challenge Home Electrical Safety Challenge Why is there a different kind of outlet in my bathroom? What does that TEST button do? Why does the circuit breaker trip every time my
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
How To Check If A Building Is Safe For A Disabled Person
GENERAL SAFETY-FIRE-SECURITY SURVEY CHECKLIST CAMPUS INSPECTION DATE BUILDING NAME INSPECTOR: ASSISTED BY: OUTSIDE/INSIDE BUILDING 1. ADA (Americans with Disabilities Act) Entry/Exit (If area is designed
FIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
St. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
INTERNATIONAL FIRE CODE SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES
INTERNATIONAL FIRE CODE SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES 3103.1 General. All temporary tents and membrane structures shall comply with this section. 3103.2 Approval required. Tents
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
Department: Manager: Safety Coordinator: Date:
SAFETY and staff, regardless of hiring status or job position 1 1. Can staff name their department safety coordinator? 2. Is the Department Safety Binder current? 3. Do slip/trip hazards exist? 4. How
Development Services City of Lawrence, KS
Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.
Texas Department of Insurance. Fire Safety. Provided by. Workers Health & Safety. Pub. No. HS01-028D (7-08)
Texas Department of Insurance Provided by Workers Health & Safety Pub. No. HS01-028D (7-08) A fire safety plan is an essential part of any workplace safety program. In fact, the Occupational Safety and
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
Fire Department Fire Prevention Inspection Services. ASSEMBLY OCCUPANCY Fire Inspection Program
ASSEMBLY OCCUPANCY Fire Inspection Program FIRE CHIEF Calvin E. Wells 2 Our Mission Deputy Fire Marshal Anthony J. Bagan 3 Fire Department Mission The mission of the Pasadena Fire Department is to provide
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
Orange County Fire Rescue Division Fire Loss Management Bureau 109 East Church Street Lower Level Orlando, Florida 32801-3319
Standard 6005 Orange County Fire Rescue Division Fire Loss Management Bureau 109 East Church Street Lower Level Orlando, Florida 32801-3319 Orange County Fire Loss Management Bureau Standard 6005 AUTHORITY
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES
CHAPTER 24 TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES > SECTION 2401 GENERAL 2401.1 Scope. Tents, canopies and membrane structures shall comply with this chapter. SECTION 2402 DEFINITIONS 2402.1 Definitions.
Restaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
Flammable and Combustible Liquids. Slide 1 (of 23)
Flammable and Combustible Liquids Slide 1 (of 23) Introduction The two primary hazards associated with flammable and combustible liquids are explosion and fire Safe handling and storage of flammable liquids
Safety Inspections and Sample Safety Inspection Checklists
Safety Inspections and Sample Safety Inspection Checklists Even if safety inspections were not strongly recommended, they are an excellent way for the department to reference the commitment to safe work
FIRE RISK ASSESSMENT
The Regulatory Reform (Fire Safety) Order 2005 FIRE RISK ASSESSMENT Employer or other responsible person Name of Premises Address Post Code Telephone N o Name of Assessor(s) Date of Assessment Date of
Fire Safety PROCEDURES January 2011
Fire Safety PROCEDURES January 2011 [email protected] Campus Phones EMERGENCY Dial 911 Fire Safety Service is the focal point for the coordinated administration of the University Fire Safety program and
exit routes and fire protection
exit routes and fire protection OSHA 11 Exit Routes and Fire Protection Osha 11 Exit Routes and Fire Protection Exit routes and fire protection Learning Objectives By the end of this lesson, students will
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
Property Maintenance Check List
Property Maintenance Check List Scope These minimum conditions and responsibilities of persons for maintenance of structures, equipment and exterior property shall govern. Responsibility. Owners shall
Requirements for Hydrogen Storage and Use
Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These
Fire Damage. To Help Prevent. a Guide
a Guide To Help Prevent Fire Damage Fire damage in your home can be costly and emotionally devastating. The damage caused by the flames and smoke can destroy a lifetime of memories in a matter of minutes.
LABORATORY SAFETY INSPECTION CHECKLIST
LABORATORY SAFETY INSPECTION CHECKLIST As part of EH&S's laboratory safety survey program, we have compiled a list of the most common safety problems. This is not a list of every possible hazard, but can
Safety Inspection Checklist
Inspector(s): Building: Room Number (s): Department/Unit: Date Inspected: Supervisor: To customize your local inspection checklist, delete or add as required. Inspection Headings: 1. Administrative 8.
ADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
Quartzone Infrared Quartz Tube & Metal Sheathed Electric Heaters
Quartzone Owner s Manual File E97759 COMFORT S for INDOOR* and OUTDOOR** USE *Excluding Residences ** With Quartz Elements and when mounted Underneath an Overhang by means of brackets out of the reach
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level
The Basics of Commercial Kitchen Exhaust Cleaning
The Basics of Commercial Kitchen Exhaust Cleaning ANSI/IKECA C 10 ANSI/IKECA C 10: Standard for Cleaning of Commercial Exhaust Systems IKECA Introduces the Kitchen Exhaust Cleaning Industry s First American
BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
GENERAL WIRING RULES FOR HOUSES
GENERAL WIRING RULES FOR HOUSES 1. Romex has to be installed in drilled holes in joists or studs even above suspended ceilings - No stapling to bottom edges of joists or studs. You may staple wire to flat
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
5-8.1.4* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.
NFPA 101 Life Safety Code Section 5-8 Illumination of Means of Egress 5-8.1 General. 5-8.1* Illumination of means of egress shall be provided in accordance with this section for every building and structure
Quality Assurance Calendar Maintenance Responsible Party Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Generator fire up Generator 1 hour load test Generator 4 hour load test Fire extinguisher integrity checks Fire extinguisher certification Fire drills Fire door integrity Fire signage lighting Fire alarm
FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH
FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH Safety signs are the primary way to communicate important warnings and messages to your employees, on-site contractors and other
NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
St. John s University Fire Safety Plan
St. John s University Fire Safety Plan Flynn Hall St. John s University Fire Safety Plan Part 1-Building Information Section Flynn Hall 300 Howard Ave. Staten Island, N.Y. 10301 Fire Safety Director: Address:
How To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
The Fire Safety Manager at 312 791 6079 (FAX 312 791 6013) can answer any questions or provide a set of fire code information.
FIRE SAFETY REGULATIONS Fire Prevention reserve the right to make any final decisions regarding the outlined requirements, according to Section 2 36 220 of the Municipal Code of Chicago on Fire Prevention.
Beth Israel Deaconess Medical Center Environment of Care Manual
Beth Israel Deaconess Medical Center Environment of Care Manual Title: Interim Life Safety Measures (ILSM) Plan Policy #: EC39 Purpose: ILSM are fully adhered to in areas where the hospital/site occupants