FILE NO. SVM SERVICE MANUAL AIR-CONDITIONER UNDER CEILING / CONSOLE TYPE RAV-SM562XT-E / RAV-SM562AT-E RAV-SM802XT-E / RAV-SM802AT-E R410A
|
|
|
- Maximilian Simmons
- 9 years ago
- Views:
Transcription
1 SERVICE MANUAL AIR-CONDITIONER UNDER CEILING / CONSOLE TYPE RAV-SM562XT-E / RAV-SM562AT-E RAV-SM802XT-E / RAV-SM802AT-E R410A April, 2006
2 CONTENTS 1. SPECIFICATIONS CONSTRUCTION VIEWS SYSTEMATIC REFRIGERATING CYCLE DIAGRAM WIRING DIAGRAM SPECIFICATION OF ELECTRICAL PARTS REFRIGERANT R410A CONTROL BLOCK DIAGRAM OPERATION DESCRIPTION TROUBLESHOOTING CHART DETACHMENTS EXPLODED VIEWS AND PARTS LIST Note : This Service Manual describes explanation for the Under Ceiling 1 console type indoor unit. For the combined outdoor unit, refer to the following Service Manual. Outdoor unit Model name SVM to be referred RAV-SMXX0AT-E A RAV-SPXXXAT-E A RAV-SMXX1AT-E A RAV-SMXX2AT-E A05-018
3 1. SPECIFICATIONS 1-1. Indoor Unit (Flexi Type) Model Indoor unit RAV-SM562XT-E RAV-SM802XT-E Outdoor unit RAV-SM562AT-E RAV-SM802AT-E Cooling capacity (kw) Heating capacity Power supply Electrical characteristics (kw) Cooling Running current (A) Power consumption (kw) Power factor (%) phase 230V ( V) 50Hz EER (W/W) Energy efficiency class * D E Energy rating * Heating Running current (A) Power consumption (kw) Power factor (%) COP (W/W) Energy efficiency class * C D Appearance Energy rating * Main unit Ceiling panel (Sold separately) Pure white Model - Panel color - Outer Main unit Height (mm) dimension Width (mm) Depth (mm) Ceiling panel (Sold separately) Height Width (mm) (mm) Depth (mm) - - Total weight Main unit (kg) Ceiling panel (kg) - - Heat exchanger Finned tube Fan Centrifugal Centrifugal Fan unit Standard air flow H/M/L (m 3 /h) 14.0 / 12.0 / / 13.5 / 10.7 Motor (W) Air filter Controller Dimensions pipe Attached main unit Attached main unit (WH-H2UE) Gas side (mm) Liquid side (mm) Drain port (mm) VP16 Sound level H/M/L (db A) 43 / 39 / / 42 / 37 Sound power level H/M/L (db A) 58 / 54 / / 57 / 52 * IEC standard ** AS standard 1
4 characteristic curve <Cooling> <Heating> RAV-SM802XT-E 14 RAV-SM802XT-E Current (A) RAV-SM562XT-E Conditions Indoor : DB27 C/WB19 C 2 Outdoor : DB35 C Air flow : High Pipe length : 7.5m 230V Compressor speed (rps) Current (A) RAV-SM562XT-E 4 Conditions Indoor : DB20 C 2 Outdoor : DB7 C/WB6 C Air flow : High Pipe length : 7.5m 230V Compressor speed (rps) Capacity variation ratio according to temperature <Cooling> <Heating> Capacity ratio (%) Capacity ratio (%) Conditions 55 Indoor : DB27 C/WB19 C Indoor air flow : High Pipe length : 7.5m Outsoor temp. ( C) Conditions Indoor : DB20 C Indoor air flow : High Pipe length : 7.5m Outsoor temp. ( C) 2
5 2. CONSTRUCTION VIEWS 2-1. Indoor Unit Front panel Knock out system Grille air inlet Back body For stud bolt (Ø8 Ø10) For stud bolt (Ø6) 200 Min Installation plate Mount plate M10 Suspention bolt Ø UNDER CEILING & CONSOLE INSTALLATION 70 Min Knock out system Wireless remote control 3
6 3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM 3-1. RAV-SM562XT-E / RAV-SM802XT-E Indoor unit TCJ sensor TC sensor Air heat exchanger Model RAV-SM Outer diameter of refrigerant pipe Gas side A Liquid side B Refrigerant pipe at liquid side Outer dia. B Refrigerant pipe at gas side Outer dia. A 562XT-E 12.7 mm 6.4 mm 802XT-E 15.9 mm 9.5 mm Packed valve Outer dia. B Outdoor unit Packed valve Outer dia. A Max 30m Note : This Service Mamual describes explanation for the Under Ceiling 1 console type indoor unit. For the combined outdoor unit, refer to the following Service Manual. Outdoor unit Model name SVM to be referred RAV-SMXX0AT-E A RAV-SPXXXAT-E A RAV-SMXX1AT-E A RAV-SMXX2AT-E A Cooling Heating 4
7 4. WIRING DIAGRAM Indoor Unit 1 INFRARED RAYS RECEIVE AND INDICATION PARTS LOUVER MOTOR CN25 WHI BLU BLU BLU BLU BLU BLU BLU BLU BLU CN13 BRW 1 1 RED 2 2 ORN 3 3 YEL 4 4 PNK 5 5 BLU 6 6 CN07 SWITCH PCB MCC-1428B CN CN R507 R09 R22 SG WHI GRY GRY IC04 DB01 R01 FUSE 250VAC F01 T6.3A C02 FOR FLOAT SWITCH (OPTION) When you use float switch you should cut J401 C01 R21 3 CN402 POWER SUPPLY CIRCUIT C J401 DC12V DC5V CR502 RY501 MCC-1428A RY401 HEAT EXCHANGER SENSOR (TCJ) R405 CN05 IC03 CR C501 CR401 2 CN03 BLK 2 2 BLK 1 1 BLK 2 2 BLK 1 1 CN01 R CN10 WHI RED BLK 3 3 BRW 2 2 GRY 1 1 YEL CN11 WHI RED BLK THERMO SENSOR (TA) 3 FOR DRAIN PUMP 2 (OPTION) 1 CN401 HEAT EXCHANGER SENSOR (TC) BLU PUR GRY 100 C FAN-MOTOR P04 BLK CN30 CN31 CN23 2 BLK WHI RED INDOOR TERMINAL BLOCK GRN&YEL INDOOR UNIT Check items OPERATION indicator Terminal block Fuse 6.3A DC 5V DC 12V SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS Diagnosis result Check to see if OPERATION indicator goes on and off when the main switch or breaker is turned on. Check the power supply voltage between 1-2 (Refer to the name plate.) Chack the fluctuate voltage between 2-3 (DC15 to 60V) Check to see if the fuse blows out. (Check the varistor. : R22, R21) Check the voltage at the No.8 pin on CN13 connector of the infrared receiver. (Check the transformer and the power supply circuit of the rated voltage.) Check the voltage at the brown lead of the louver motor. (Check the transformer and the power supply circuit of the rated voltage.) 5 OUTDOOR UNIT Color Identification BRW : BROWN RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE GRN&YEL : GREEN& YELLOW GRN : GREEN PUR : PURPLE
8 5. SPECIFICATION OF ELECTRICAL PARTS Indoor Unit No. Parts name Type Specifications 1 Fan motor (for indoor) AFP A Output (Rated) 50 W, V 2 Grille motor MP35EA DC 12 V 3 Thermo. sensor (TA-sensor) 550 mm 10 kω at 25 C 4 Heat exchanger sensor (TC-sensor) 6 mm, 500 mm 10 kω at 25 C 5 Heat exchanger sensor (TCJ-sensor) 6 mm, 500 mm 10 kω at 25 C 6
9 6. REFRIGERANT R410A This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer. The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time. The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work Safety During Installation/Servicing As R410A s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out installation/ servicing safely while taking the following precautions into consideration. (1) Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A. If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture. (2) Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A. The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22 (3) If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a poisonous gas may occur. (4) When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture of personal injury may be caused. (5) After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur. (6) When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level. If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result. (7) Be sure to carry out installation or removal according to the installation manual. Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc. (8) Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repair s may result in water leakage, electric shock and fire, etc Refrigerant Piping Installation Piping materials and joints used For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants. (1) Copper pipes It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table Never use copper pipes thinner than 0.8 mm even when it is available on the market. 7
10 Table Thicknesses of annealed copper pipes Thickness (mm) Nominal diameter Outer diameter (mm) R410A R22 1/ / / / (2) Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare joints Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used. Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables to below. b) Socket joints Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table Table Minimum thicknesses of socket joints Nominal diameter Reference outer diameter of copper pipe jointed (mm) Minimum joint thickness (mm) 1/ / / / Processing of piping materials When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover. (1) Flare Processing procedures and precautions a) Cutting the pipe By means of a pipe cutter, slowly cut the pipe so that it is not deformed. b) Removing burrs and chips If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation. c) Insertion of flare nut d) Flare processing Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure dimension A by using a gauge for size adjustment. D Fig Flare processing dimensions A 8
11 Table Dimensions related to flare processing for R410A Nominal diameter Outer diameter (mm) Thickness (mm) Flare tool for R410A clutch type A (mm) Conventional flare tool Clutch type Wing nut type 1/ to to to 2.0 3/ to to to 2.0 1/ to to to 2.5 5/ to to to 2.5 Table Dimensions related to flare processing for R22 Nominal diameter Outer diameter (mm) Thickness (mm) Flare tool for R22 clutch type A (mm) Conventional flare tool Clutch type Wing nut type 1/ to to to 1.5 3/ to to to 1.5 1/ to to to 2.0 5/ to to to 2.0 Nominal diameter Outer diameter (mm) Table Flare and flare nut dimensions for R410A Thickness (mm) Dimension (mm) A B C D Flare nut width (mm) 1/ / / / Nominal diameter Outer diameter (mm) Table Flare and flare nut dimensions for R22 Thickness (mm) Dimension (mm) A B C D Flare nut width (mm) 1/ / / / /
12 43 to 45 FILE NO. SVM to 46 Fig Relations between flare nut and flare seal surface (2) Flare connecting procedures and precautions a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur. When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table shows reference values. Note: When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out. Table Tightening torque of flare for R410A [Reference values] Nominal Outer diameter Tightening torque diameter (mm) N m (kgf cm) Tightening torque of torque wrenches available on the market N m (kgf m) 1/ to 18 (140 to 180) 16 (160), 18 (180) 3/ to 42 (330 to 420) 42 (420) 1/ to 62 (500 to 620) 55 (550) 5/ to 77 (630 to 770) 65 (650) 10
13 6-3. Tools Required tools The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For copper pipe) of the refrigerant piping are lengthened. The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. (1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability. Tools exclusive for R410A (The following tools for R410A are required.) Tools whose specifications are changed for R410A and their interchangeability R410A air conditioner installation Conventional air conditioner installation No. Used tool Usage Existence of Whether Whether new equipment new equipment conventional can be used with for R410A equipment can conventional refrigerant be used 1 Flare tool Pipe flaring Yes *(Note 1) 2 Copper pipe gauge Flaring by for adjusting projection conventional flare Yes *(Note 1) *(Note 1) margin tool 3 Torque wrench 4 Gauge manifold 5 Charge hose Connection of flare nut Evacuating, refrigerant charge, run check, etc. Yes Yes 6 Vacuum pump adapter Vacuum evacuating Yes 7 Electronic balance for Refrigerant charge Yes refrigerant charging 8 Refrigerant cylinder Refrigerant charge Yes 9 Leakage detector Gas leakage check Yes! Charging cylinder Refrigerant charge (Note 2) (Note 1) (Note 2) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary. Charging cylinder for R410A is being currently developed. General tools (Conventional tools can be used.) In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools. (1) Vacuum pump (4) Reamer (9) Hole core drill ( 65) Use vacuum pump by (5) Pipe bender (10) Hexagon wrench attaching vacuum pump adapter. (6) Level vial (Opposite side 4 mm) (2) Torque wrench (7) Screwdriver (+, ) (11) Tape measure (3) Pipe cutter (8) Spanner of Monkey wrench (12) Metal saw Also prepare the following equipments for other installation method and run check. (1) Clamp meter (3) Insulation resistance tester (2) Thermometer (4) Electroscope 11
14 6-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. Connect the charge hose to packed valve service port at the outdoor unit s gas side. When the compound gauge s pointer has indicated -0.1 Mpa (-76 cmhg), place the handle Low in the fully closed position, and turn off the vacuum pump s power switch. Connect the charge hose of the vacuum pump adapter. Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge s pointer does not return. Open fully both packed valves at liquid and gas sides. Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump s power switch. Then, evacuating the refrigerant in the cycle. Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant. (For refrigerant charging, see the figure below.) 1 Never charge refrigerant exceeding the specified amount. 2 If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode. 3 Do not carry out additional charging. When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury. (INDOOR unit) (Liquid side) (OUTDOOR unit) Opened Refrigerant cylinder (With siphon pipe) (Gas side) Check valve Closed Open/Close valve for charging Service port Electronic balance for refrigerant charging Fig Configuration of refrigerant charging 12
15 1 Be sure to make setting so that liquid can be charged. 2 When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon. [Cylinder with siphon] Gauge manifold OUTDOOR unit [Cylinder without siphon] Gauge manifold OUTDOOR unit Refrigerant cylinder Refrigerant cylinder Electronic balance Electronic balance Siphon R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment varies. Fig Brazing of Pipes Materials for brazing (1) Silver brazing filler Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability. (2) Phosphor bronze brazing filler Phosphor bronze brazing filler is generally used to join copper or copper alloy. (3) Low temperature brazing filler Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes. 1 Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint. 2 When performing brazing again at time of servicing, use the same type of brazing filler Flux (1) Reason why flux is necessary By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler. In the brazing process, it prevents the metal surface from being oxidized. By reducing the brazing filler s surface tension, the brazing filler adheres better to the treated metal. 13
16 (2) Characteristics required for flux Activated temperature of flux coincides with the brazing temperature. Due to a wide effective temperature range, flux is hard to carbonize. It is easy to remove slag after brazing. The corrosive action to the treated metal and brazing filler is minimum. It excels in coating performance and is harmless to the human body. As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc. (3) Types of flux Noncorrosive flux Generally, it is a compound of borax and boric acid. It is effective in case where the brazing temperature is higher than 800 C. Activated flux Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound. (4) Piping materials for brazing and used brazing filler/flux Brazing As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N 2 ) flow. Never use gas other than Nitrogen gas. (1) Brazing method to prevent oxidation 1 Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder. 2 Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder. 3 Apply a seal into the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas. 4 When the Nitrogen gas is flowing, be sure to keep the piping end open. 5 Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m 3 /Hr or 0.02 Mpa (0.2 kgf/ cm 2 ) by means of the reducing valve. 6 After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands). 7 Remove the flux completely after brazing. M Flow meter Piping Used brazing Used material filler flux Copper - Copper Phosphor copper Do not use Copper - Iron Silver Paste flux Iron - Iron Silver Vapor flux Nitrogen gas cylinder Stop valve From Nitrogen cylinder 1 Do not enter flux into the refrigeration cycle. 2 When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chloring. 3 When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water). 4 Remove the flux after brazing. Pipe Rubber plug Nitrogen gas Fig Prevention of oxidation during brazing 14
17 7. CONTROL BLOCK DIAGRAM Heat Exchanger Sensor (TCJ) Heat Exchanger Sensor (TC) Temperature Sensor Infrared Rays Signal Receiver Infrared Rays 36.7 khz Initiallizing Circuit Clock Frequence Oscillator Circuit Indoor Unit Control Panel Functions Louver Control 3-minute Delay at Restart for Compressor Motor Revolution Control Processing (Temperature Processing) Timer Drain Pump ON/OFF M.C.U. Serial Signal Communication 8 MHz Hi POWER Display FILTER Sign Display PRE DEF. Sign Display TIMER Display OPERATION Display Indoor Fan Motor Remote Control Power Supply Circuit Noise Filter Serial Signal Transmitter/ Receiver Relay RY401 Louver ON/OFF Signal Louver Driver Louver Motor Float Switch Drain Pump From Outdoor Unit Serial Signal Communication REMOTE CONTROL Remote Control Infrared Rays (START/STOP) Mode Selection AUTO, COOL, DRY, HEAT, FAN ONLY Temperature Setting Fan Speed Selection ON TIMER Setting OFF TIMER Setting Louver Auto Swing Louver Direction Setting ECO Hi power Filter Reset 15
18 8. OPERATION DESCRIPTION 8-1. When power supply is reset (1) Distinction of outdoor units When the power supply is reset, the outdoors are distinguished, and control is exchanged according to the distinguished result. (2) Setting of the indoor fan speed Based on EEPROM data, rspeed of the indoor fan is selected. Remarks: Air speed 8-2. mode selection (1) Based on the operation mode selecting command from the remote control, the operation mode is selected. Remote control command STOP FAN COOL DRY HEAT AUTO Table Outline of control Air conditioner stops. Fan operation Cooling operation Dry operation Heating operation Automatic operation (2) Automatic The air conditioner selects and operates in one of the operating modes of cooling, heating or fan only, depending on the room temperature. If the AUTO mode is uncomfortable, you can select the desired conditions manually Air volume control (1) with [HIGH (H)], [MED (M)], [LOW (L)], or [AUTO] mode is performed by the command from the remote control. (2) When [FAN] button is set to AUTO, the indoor fan motor operates as shown in Fig , Fig and Table <COOL> (Room temp.) (Preset temp.) Preset temp. C NOTE : *1: The values marked with *1 are calculated and controlled by the difference in motor speed between M+ and L. Fig M+ *1 *1 *1 Room temperature in operation The set temperature +1 C or higher (in case that the room is hot) The set temperature 1 C to +1 C The set temperature 1 C or lower (in case that the room is cold) Cooling operation Fan only operation Heating operation Table Operating condition Performs the cooling operation at a temperature 1 C higher than the setting. Performs the fan only operation (low speed) while monitoring the room temperature. When the room temperature changes, the air conditioner will select the cooling or heating mode. Performs the heating operation at a temperature 1 C lower than the setting. 16
19 <HEAT> Preset temp. (Room temp.) (Preset temp.) MODEL C [FAN AUTO] NOTE : *1, *2 : The values marked with *1 and *2 are calculated and controlled by the difference in motor speed between M+ and L. Fig Table RAV-SM562XT-E *1 *2 M + RAV-SM802XT-E Motor speed Air flow level Motor speed Air flow level (rpm) (m 3 /h) (rpm) (m 3 /h) Cooling HIGH and MED Fan only LOW HIGH Heating MED LOW L H 8-4. Cool air discharge preventive control In heating operation, the indoor heat exchanger restricts revolving speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig and Table * A+4 A+4 A 8 A 8 *6 *5 AUTO NOTES : *1: The fan stops for 2 minutes after thermostat-off. *2: A is 24 C when the preset temperature is 24 C or more and A is the preset temperature when it is under 24 C. *3: SUL means Super Ultra Low. *4: Calculated from difference in motor speed between SUL and HIGH. Fig Cold draft preventing control *4 SUL* 3 SUL*1 Stop Manual (One of 5 steps) L H (Up to setting speed) LOW + = MED + = LOW+MED 2 MED+HIGH 2 *5 and *6: Table Fan *5 *6 speed Starting period Stabilized period AUTO Up until 12 minutes passed after starting the unit From 12 to 25 minutes passed after starting the unit and room temperature is 3 C lower than preset temperature Manual Room temperature (L H) < Preset temperature 4 C From 12 to 25 minutes passed after starting the unit and room temperature is between preset temperature and 3 C lower than preset temperature 25 minutes or more passed after starting the unit Room temperature Preset temperature 3.5 C 17
20 8-5. Freeze preventive control (Low temperature release) The cooling operation (including Dry operation) is performed as follows based on the detected temperature of Tc sensor or Tcj sensor. When [J] zone is detected for T1 minutes (Following figure), the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 2 minutes while operation is performed in [J] zone. In [K] zone, time counting is interrupted and the operation is held. When [I] zone is detected, the timer is cleared and the operation returns to the normal operation. ( C) Normal Fig In heating operation, the freeze-preventive control works if 4-way valve is not exchanged and the condition is satisfied. Remarks: Tcj : Indoor heat exchanger sensor temperature 8-6. High-temp release control I The heating operation is performed as follows based on the detected temperature of Tc sensor. When [M] zone is detected, the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [M] zone. In [N] zone, the commanded frequency is held. When [L] zone is detected, the commanded frequency is returned to the original value by approx. 6Hz every 60 seconds. T1 1 minute J K A 8-7. Louver control (1) Vertical air flow louver Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation. (2) Swing If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [SWING] button is pressed, it stops swinging Filter sign display (1) The operation time of the indoor fan is calculated, the filter lamp (Orange) on the display part of the main unit goes on when the specified time (240H) has passed. When a wired remote controller is connected, the filter reset signal is sent to the remote controller, and also it is displayed on LCD of the wired remote control. (2) When the filter reset signal has been received from the wired remote control after [FILTER] lamp has gone on or when the filter check button (Temporary button) is pushed, time of the calculation timer is cleared. In this case, the measurement time is reset if the specified time has passed, and display on LCD and the display on the main unit disappear. Remarks: [FILTER] goes on Tc ( C) 55 A B L M N Fig
21 FILE NO. SVM Auto Restart Function The indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored. This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work How to set auto restart function To set the auto restart function, proceed as follows: The power supply to the unit must be on; the function will not set if the power is off. Push the [TEMPORARY] button located in the center of the front panel continuously for three seconds. The unit receives the signal and beeps three times. The unit then restarts operating automatically in the event of power supply being accidentally shut down. When the unit is on standby (Not operating) Push [TEMPORARY] button for more The unit is on standby. than three seconds. Motions The unit starts to operate. The green lamp is on. After approx. three seconds, Hi POWER FILTER PRE.D 0 3S The unit beeps three times and continues to operate. The lamp changes from green to orange. TEMPORARY button If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off. When the unit is in operation Motions Push [TEMPORARY] button for more The unit is in operation. The green lamp is on. than three seconds. The unit stops operating. The green lamp is turned off. After approx. three seconds, Hi POWER FILTER PRE.D 0 3S The unit beeps three times. TEMPORARY button If the unit is required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it on. While this function is being set, if the unit is in operation, the orange lamp is on. This function can not be set if the timer operation has been selected. When the unit is turned on by this function, the louver will not swing even though it was swinging automatically before shutting down. While the filter check lamp is on, the TEMPORARY button has the function of filter reset button. 19
22 FILE NO. SVM How to cancel auto restart function To cancel auto restart function, proceed as follows: Repeat the setting prodedure: the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote control after the main power supply is turned off. When the unit is on standby (Not operating) Push [TEMPORARY] button for more The unit is on standby. than three seconds. Motions The unit starts to operate. The orange lamp is on. After approx. three seconds, Hi POWER FILTER PRE.D 0 3S The unit beeps three times and continues to operate. The lamp changes from orange to green. TEMPORARY button If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off. When the unit is in operation Motions Push [TEMPORARY] button for more The unit is in operation. The orange lamp is on. than three seconds. The unit stops operating. The orange lamp is turned off. After approx. three seconds, Hi POWER FILTER PRE.D 0 3S The unit beeps three times. TEMPORARY button If the unit is required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it on. While this function is being set, if the unit is in operation, the orange lamp is on Power failure during timer operation When the unit is in Timer operation, if it is turned off because of power failure, the timer operation is cancelled. Therefore, set the timer operation again Filter Check Lamp When the elapsed time reaches 1000 hours, the filter check lamp indicates. After cleaning the filters, turn off the filter check lamp How to turn off filter check lamp (1) Press [FILTER] button on the remote control. (2) Push [TEMPORARY] button on the indoor unit. Note: If [TEMPORARY] button is pushed while the filter check lamp is not indicating, the indoor unit will start the Automatic. 20
23 9. TROUBLESHOOTING 9-1. Summary of Troubleshooting Before troubleshooting (1) Required tools/instruments e and d screwdrivers, spanners, radio cutting pliers, nippers, etc. Tester, thermometer, pressure gauge, etc. (2) Confirmation points before check 1 The following operations are normal. a) Compressor does not operate. Is not 3-minutes delay (3 minutes after compressor OFF)? Does not thermostat turn off? Does not timer operate during fan operation? Is not outside high-temperature operation controlled in heating operation? b) Indoor fan does not rotate. Does not cool air discharge preventive control work in heating operation? c) Outdoor fan does not rotate or air volume changes. Does not high-temperature release operation control work in heating operation? Does not outside low-temperature operation control work in cooling operation? Is not defrost operation performed? d) ON/OFF operation cannot be performed from remote control. Is not forced operation performed? Is not the control operation performed from outside/remote side? 2 Did you return the cabling to the initial positions? 3 Are connecting cables between indoor unit and receiving unit correct? Troubleshooting procedure When a trouble occurred, check the parts along with the following procedure. Trouble Confirmation of check code by service mode Check defective position and parts. NOTE : For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cables of the signal line to shield cables Outline of Judgment A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure. <Judgment by flashing display on the indoor unit display part> The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the self-diagnosis are displayed with a block restricted to the following cases on the indoor unit display part (Sensor). Table Remote control code Block display Contents of self-diagnosis Check code lamp display flashes. (1Hz) Power failure (In power ON) 00 lamp display flashes. (5Hz) Indoor P.C. board 0b to 0F, 11, 12, b5, b6 01 /timer lamp displays flash. (5Hz) Inter-unit cables/transmission system /defrost lamp displays flash. (5Hz) Outdoor P.C. board 14 to 19, 1A, 1C 03 /timer/defrost lamp displays flash. (5Hz) Cycle system, etc. 1d, 1E, 1F, 21 1b, 8b 21
24 9-2. Self-Diagnosis by Remote Control (Check Code) (1) If the lamps are indicated as shown 00 to 03 in Table 9-1-1, exchanger the self-diagnosis by the remote control. (2) When the remote control is set to the service mode, the indoor controller diagnoses the operation condition and indicate the information of the self-diagnosis on the display of the remote control with the check codes. If a fault is detected, all lamps on the indoor unit will blink at 5 Hz and it will beep for 10 seconds (Pi, Pi, Pi...). The timer lamp usually blinks (5 Hz) during the self-diagnosis How to use remote control in service mode SET CLR RESET CLOCK CHECK (1) Press [CHECK] button with a tip of pencil to set the remote control to the service mode. 00 is indicated on the display of the remote control. The timer lamp on the indoor unit blinks continuously. (5 times per 1 sec.) FAN SWING FIX AUTOA MODE ECO TIMER PRESET AUTO Hi-POWER ON OFF SET CLR FILTER A B START/STOP MEMO RESET CLOCK CHECK (2) Press [TIMER 8] button. If there is no fault with a code, the indoor unit will beep once (Pi) and the display of the remote control will change as follows: d 1E 22 Check the unit with all 35 check codes (00 to 22). as shown in Table Press [TIMER 9] button to change the check code backwards. If there is a fault, the indoor unit will beep for 10 seconds (Pi, Pi, Pi...). Note the check code on the display of the remote control. 2-digits alphanumeric will be indicated on the display. All lamps on the indoor unit will blink. (5 times per 1 sec.) (3) Press [CLR] button. After service finish for clear service code in memory. 7F is indicated on the display of the remote control. Alphanumeric characters are used for the check code. is 5. is 6. is A. is B. is C. is D. (4) Press [START/STOP] button to release the service mode. The display of the remote control returns to as it was before service mode was engaged. 22
25 The indoor thermo sensor (TA) is defective. Disconnection or short-circuit The indoor heat exchanger sensor (TC) is defective. Disconnection or short-circuit The indoor fan motor or its circuit is defective. The part other than the above parts on the indoor P.C. board is defective. EEPROM access error IOL operation The variation of TC, 5 minutes after starting the compressor, is 2K or less. The serial signals can not be transmitted and received between indoor and outdoor units. The crossover wire is connected wrongly. The serial signal transmitting circuit on the outdoor P.C. board is defective. The serial signal receiving circuit on the indoor P.C. board is defective. The operation command signals are not transmitted from the indoor unit to the outdoor unit. The outdoor thermo sensor (TE) is defective. Disconnection or short-circuit The outdoor heat exchanger (TD) sensor is defective. Disconnection or short-circuit The reply serial signal has been transmitted when starting the unit, but stops being transmitted shortly after. 1. Compressor thermo operation Gas shortage Gas leak 2. Instantaneous power failure The discharge temperature is over 120 C. The IOL operation is defective. Table of diagnostic function Check Check Unit Block Symptom code code status Indoor P.C. board The block is unidentifiable Cable connection Outdoor P.C. board Other parts (including compressor) continues. continues. All off continues. All off continues. continues. continues. All off All off continues. All off All off 23 Condition The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. And it returns to the normal condition when recovering from errors. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is defected. And it returns to the normal condition when recovering from errors. The lamp on the indoor unit blinks when error is defected. The lamp on the indoor unit blinks when error is detected. Judgement and action 1. Check the indoor thermo sensor (TA). 2. Check the indoor P.C. board. 1. Check the indoor heat exchanger sensor (TC). 2. Check the indoor P.C. board. 1. Check the connector circuit of the indoor fan motor (CN10). 2. Check the indoor fan motor. 3. Check the indoor P.C. board. 1. Check the indoor P.C. board. (EEPROM and peripheral circuits) Overload operation of refrigerating cycle 1. Check whether or not the TC sensor comes off. 2. Check whether or not it is possible to operate the compressor and the outdoor fan motor. 3. Check gas leak. 1. In the case of the outdoor unit not operating at all; Check the crossover cable and connect it properly. Check the outdoor P.C. board. 2. In the case of the outdoor unit operating normally; Check whether or not both of serial LED (Green) and serial LED (Orange) is blinking. If the serial LED (Green) is not blinking, check the outdoor P.C. board. If the serial LED (Orange) is not blinking, check the indoor P.C. board. If the operation command signals continue to be transmitted between 2 and 3 of the indoor terminal block, replace the outdoor P.C. board. 1. Check the outdoor thermo sensor (TE). 2. Check the outdoor P.C. board. 1. Check the outdoor heat exchanger sensor (TD). 2. Check the outdoor P.C. board. 1. Repeatedly turn the indoor unit on and off with the interval of approx. 10 to 40 minutes. (The check code is not indicated during operation.) And supply gas. (Check gas leak.) 2. The indoor unit operates normally during the check. If the reply serial signal continues to be transmitted between 2 and 3 of the indoor terminal block, replace the outdoor P.C. board. If the signal stops between them, replace the indoor P.C. board. 1. Check the heat exchanger sensor (TD). 2. Gas purging When turning on the unit, the normal phase (RST) is detected but T-R waveform has not been detected for 120 seconds or more.
26 Table Block Check code of diagnostic function Symptom Unit status Condition Judgement and action [MODE] [TIMER] lamp 5Hz flash The serial signal is not output from outdoor unit to indoor unit. Miscabling of inter-unit cables Defective serial sending circuit on outdoor P.C. board Defective serial receiving circuit on outdoor P.C. board Compressor case thermo operation continues. 1. Outdoor unit does not completely operate. Inter-unit cable check, correction of miscabling Outdoor P.C. board check, P.C. board cables check Compressor case thermo check 2. In normal operation When outdoor sending serial LED (Green) flashes, the receiving serial LED (Orange) also flashes. : Indoor P.C. board (Main P.C. board) check When the receiving serial LED (Orange) does not flash: Outdoor P.C. board check BUS communication circuit error * BUS communication was interrupted over the specified time. continues (According to remote control of indoor unit) 1. Communication line check, miscabling check Power supply check for central control (Central control remote control, etc.) and indoor unit 2. Communication check (XY terminal) 3. Indoor P.C. board check 4. Central control check (Communication P.C. board) Error in 4-way valve system Indoor heat exchanger temperature rise after start of cooling operation. Indoor heat exchanger temperature fall after start of heating operation. continues. 1. Check 4-way valve. 2. Check 2-way valve and non-return valve. 3. Check indoor heat exchanger sensor (TC). 4. Check indoor P.C. board (Main P.C. board). * Error in other cycles Indoor heat exchanger temp (TC) does not vary after start of cooling/ heating operation. continues. 1. Compressor case thermo operation. 2. Coming-off of detection part of indoor heat exchanger sensor. 3. Check indoor heat exchanger sensor (TC). 4. Check indoor P.C. board (Main P.C. board). [MODE] lamp 5Hz flash Coming-off, disconnection or short of indoor temp sensor (TA) continues. 1. Check indoor temp sensor (TA). 2. Check indoor P.C. board (Main P.C. board). Coming-off, disconnection or short of indoor temp sensor (TC) continues. 1. Check indoor temp sensor (TC). 2. Check indoor P.C. board (Main P.C. board). Coming-off, disconnection or short of indoor temp sensor (TCJ) continues. 1. Check indoor temp sensor (TCJ). 2. Check indoor P.C. board (Main P.C. board). [MODE] lamp 5Hz flash Error in indoor fan system Revolutions frequency error of fan All stop 1. Check indoor fan motor connector circuit (CN210). 2. Check indoor fan. 3. Check indoor P.C. board (Main P.C. board). Error in indoor unit or other positions 1. EEPROM access error continues. 1. Check indoor P.C. board (EEPROM and peripheral circuits) (Main P.C. board). Outside error input Detected by input voltage level from outside devices continues. 1. Check outside devices. 2. Check indoor P.C. board (Main P.C. board). Outside interlock input Detected by input voltage level from outside devices All stop *: No display in the setting at shipment 24
27 Table of diagnostic function Check code Symptom Unit status Condition Inverter over-current protective circuit operates. (For a short time) All stop Judgement and action 1. Inverter immediately stops even if restarted. Compressor rare short 2. Check IPDU. Cabling error Error on current detection circuit Current value is high at AC side even while compressor stops. Phase of power supply is missed. All stop 1. Compressor immediately stops even if restarted. : Check IPDU. 2. Phase-missing operation of power supply Check power voltage of R, S, T. Coming-off, disconnection or short of outdoor temp sensor All stop 1. Check outdoor temp sensor (TE, TS). 2. Check CDB. Coming-off, disconnection or short of outdoor temp sensor All stop 1. Check outdoor temp sensor (TD). 2. Check CDB. Compressor drive output error Tin thermistor temp, Tin error (IPDU heat sink temp. is high.) Communication error between IPDU Connector coming-off between CDB and IPDU All stop 1. Abnormal overload operation of refrigerating cycle 2. Loosening of screws and contact error of IPDU and heat sink 3. Cooling error of heat sink 4. Check cabling of CDB and IPDU. Compressor does not rotate. (Over-current protective circuit works when constant time passed after activation of compressor.) All stop 1. Compressor error (Compressor lock, etc.) : Replace compressor. 2. Cabling trouble of compressor (Phase missing) Discharge temp error Discharge temp over specified value was detected. All stop 1. Check refrigerating cycle. (Gas leak) 2. Error of electron control valve 3. Check pipe sensor (TD). Compressor breakdown frequency lowered and stops though operation had started. All stop 1. Check power voltage. (AC200V±20V) 2. Overload operation of refrigerating cycle 3. Check current detection circuit at AC side. High-voltage protection error by TE sensor TE temp over specified value was detected. All stop 1. Overload operation of refrigerating cycle 2. Check outdoor temp sensor (TE). DC outdoor fan motor error IDC operation or lock was detected by DC outdoor fan driving. All stop 1. Position detection error 2. Over-current protection circuit operation of outdoor fan drive unit Check CDB. Refer to Judgment of outdoor fan. Error on IPDU position detection circuit All stop 1. Position detection circuit operates even if driving by removing 3P connector of compressor. Replace IPDU. Coming-off, disconnection or short of outdoor temp sensor continues. 1. Check outdoor temp sensor (TO). 2. Check P.C. board. 25
28 Relational graph of temperature sensor resistance value and temperature TA sensor TC, TCJ sensor Resistance (kω) Caracteristics-1 Resistance (kω) 30 Caracteristics Temperature [ C] Temperature [ C] 200 Caracteristics-3 20 TE, TO, TS sensor Resistance (kω) (10 C or lower) 100 Resistance (kω) (10 C or higher) Temperature [ C] Caracteristics-4 TD sensor 20 Resistance (kω) (50 C or lower) 100 Resistance (kω) (50 C or higher) Temperature [ C] 0 26
29 10. DETACHMENTS Indoor Unit No. Part name Procedures Remarks 1 Air Inlet grille <How to remove the Air inlet grille> 1) Stop the operation of the Air conditioner and turn off its main power supply. 2) Open the Air inlet grille with both hands. Air inlet grille 3) Unfasten 3 screws (about two to three rounds) for fixing the Panel arms. 4) Move the Air inlet grille toward. 5) Remove the Grille stopper from the axis of the Front panel. After that, remove the Air inlet grille. Panel arm Grille stopper 6) Remove the Panel arms from the Front panel. <How to install the Air inlet grille> 1) Insert three Panel arms on the Air inlet grille and fix each securely by screws. 2) Set the Air inlet grille arm to the axis of the Front panel. 3) Insert the Grille stopper to the correct position and fix it securely with screws. 4) Push the Air inlet grille to the correct position. 27 Air inlet grille Panel arm
30 No. Part name Procedures Remarks 2 Front panel <How to remove the Front panel> 1) Remove the Air inlet grille. (1) 2) In case of the Drain hose is installed through the Front panel. : Remove the Drain band from the Front panel. : Cut away the Opening base for piping from Front panel and keep parts. Drain band Drain panel 3) Open 3 Cap screws and remove the screws. Cap screws 4) Remove 5 screws fixing the Front panel. Front Panel Screws 5) Remove the hooks of the Panel LED nearly side from the Drain pan. 28 (Continue)
31 No. Part name Procedures Remarks 2 Front panel 6) Remove both side hooks and remove the Front panel by turn to air inlet part direction. <How to install the Front panel> 1) In case of the Drain hose installation through the Front panel, install the opening base for piping in the Back body by a screw (M4 x 12). Prepare it by yourself. 2) Fit the Front panel in the Drain pan. Then fix it in the Drain pan with 2 hooks in the center of the air outlet. 3) Fix 5 hooks around the Front panel with conformation the Guide-rib is inserting into the Back body. 4) Fix 8 screws and close 3 Cap screws. 5) Install the Drain band into the Front panel. 6) Check the gap between the Front panel and the Back body. Hook Guide-rib 3 Drain pan assembly <How to remove the Drain pan> 1) Remove the Air inlet grille and the Front panel. (1, 2) 2) Remove the Louver motor from the Drain pan. 3) Remove the shaft of Horizontal louver. 4) Remove the LED base and Electrical wire. Louver motor Electrical wire LED base Shaft of Horizontal lover 5) Remove the TA sensor wire. 6) Remove the Drain hose. Drain hose TA sensor (Continue) 29
32 No. Part name Procedures Remarks 3 Drain pan 7) Remove 7 screws and remove the Drain Screw assembly pan assembly. Drain Pan Screw 4 Electrical parts assembly <How to remove the Electrical parts assembly> 1) Remove the Air inlet grille, the Front panel and the Drain pan assembly. (1, 2, 3) 2) Remove the Terminal cover. 3) Unfasten the screw of Cord clamp and disconnect the connecting cable. 4) Remove the Connector cover and disconnect the Fan motor cords. 5) Remove the TC sensor, TCJ sensor and earth wire from Refrigeration assembly. 6) Remove the Electrical parts assembly. NOTE : When install the electrical parts assembly, fix the screw after the Back body is fixed. Connecting TC sensor Refrigeration assembly cable Cord clamp Earth wire Electrical parts assembly TCJ sensor Fan motor cords 5 Refrigeration assembly <How to remove the Refrigeration assembly> 1) Remove the Air inlet grille, the Front panel and the Drain pan assembly. (1, 2, 3) 2) Stop the gas at the Outdoor unit. 3) Remove 2 pipes from the Refrigeration assembly. 4) Remove the TC sensor and TCJ sensor from holder. 5) Remove the pipe holder. 6) Remove the earth wire. TCJ sensor Earth wire TC sensor Pipe holder (Continue) 30
33 No. Part name Procedures Remarks 5 Refrigeration assembly 7) Remove 2 screws and remove the refrigeration assembly with pushing it to right hand. 2 Screws 6 Multiblade fan and Fan motor <How to remove the Multiblade fan and Fan motor> 1) Remove the Air inlet grille and the Front panel. (1, 2) 2) Disconnect 2 connectors. 3) Remove the Fan covers. 4) Remove the Motor band with holding the Fan motor and then remove the Fan motor with the Multi-blade fans. Fan cover Motor band Motor 2 Connectors 5) Unfasten the Set-screw and remove the Multi-blade fans. Multi-blade fan 31
34 11-1. Indoor Unit (E-Parts Assy) 11. EXPLODED VIEWS AND PARTS LIST Location No. Part No. Description Location No. Part No. Description T69564 PC BOARD (RAV-SM802XT-E) T69565 PC BOARD (RAV-SM562XT-E) T50004 SENSOR; HEAT EXCHANGER T60002 TERMINAL BLOCK; 3P T62003 CORD CLAMP T69315 DISPLAY UNIT T50302 TEMPERATURE SENSOR T69564 PC BOARD (RAV-SM562XT-E) T69565 PC BOARD (RAV-SM802XT-E) T08349 SWITCH COVER 32
35 11-2. Indoor Unit Location No. Part No. Description Location No. Part No. Description T09379 AIR-GRILLE T00445 PANEL ARM ASSY T00446 FRONT PANEL ASSY T01306 MARK T79312 DRAIN BAND T80302 AIR FILTER T00433 CAP SCREW C T00434 CAP SCREW LR T20303 FAN COVER T20318 MOTOR BAND ASSY T20317 FAN ASSY (MULTIBLADE FAN) T19309 SCREW SET (D-T) T21369 FAN MOTOR T72309 DRAIN PAN ASSY T79311 GUIDE DRAIN T21376 MOTOR; STEPPING T09378 HORIZONTAL LOUVER FLOCK T44377 REFRIGERATION ASSY (SM562XT-E) T44378 REFRIGERATION ASSY (SM802XT-E) T03339 BACK BODY ASSY T09314 VERTICAL LOUVER T49303 PIPE HOLDER T19324 COVER BODY L T19325 COVER BODY R T19328 COVER BODY LD T19326 BUSH BODY R T19327 BUSH BODY D T82308 PLATE; INSTALLATION T60314 TERMINAL COVER T62303 CONNECTOR COVER T83003 HOLDER; REMOTE CONTROLLER T69309 WRIRELESS REMOCON T49326 FLEXIBLE PIPE ASSY (SM562XT-E) T49328 FLEXIBLE PIPE ASSY (SM802XT-E) T80003 FILTER; FRAME T00447 ASM-GRILLE-STOPPER 33
36 TOSHIBA CARRIER (THAILAND) CO., LTD. 144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI, AMPHUR MUANG, PATHUMTHANI 12000, THAILAND. 86
Outdoor Unit RAS-07PAVP-E RAS-10PAVP-E RAS-13PAVP-E RAS-16PAVP-E RAS-18PAVP-E. (North Europe Type)
FILE. A08-010 AIR-CONDITIONER (SPLIT TYPE) SERVICE MANUAL Model name: Indoor Unit (Standard Type) RAS-07PKVP-E RAS-10PKVP-E RAS-13PKVP-E RAS-16PKVP-E RAS-18PKVP-E (North Europe
AIR-CONDITIONER SPLIT TYPE
FILE NO. SVM-10070-1 SERVICE MANUAL Indoor Unit AIR-CONDITIONER SPLIT TYPE RAS-M22SKV-E RAS-M24SKV-E R410A PRINTED IN JAPAN (Revised, May 2011) CONTENTS 1. SAFETY PRECAUTIONS...
AIR-CONDITIONER SPLIT TYPE
FILE NO. A06-05 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE INDOOR UNIT Heat Pump Model RAS-M0SMUV-E RAS-M3SMUV-E RAS-M6SMUV-E Cooling Only Model RAS-M0SMUCV-E RAS-M3SMUCV-E RAS-M6SMUCV-E R40A PRINTED IN
FILE NO. SVM-03016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10UKCV-E, RAS-M13UKCV-E, RAS-M16UKCV-E / RAS-3M23YACV-E
FILE NO. SVM-03016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10UKCV-E, RAS-M13UKCV-E, RAS-M16UKCV-E / RAS-3M23YACV-E R410A June, 2003 CONTENTS 1. SPECIFICATIONS... 3 2. REFRIGERANT R410A... 7 3. CONSTRUCTION
AIR-CONDITIONER SPLIT TYPE
FILE. A04-015 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-B10EKVP-E, RAS-B13EKVP-E /RAS-M14EAV-E RAS-M10EKCVP-E, RAS-M13EKCVP-E /RAS-M14EACV-E RAS-B10EKVP-E, RAS-B13EKVP-E, RAS-B16EKVP-E/RAS-M18EAV-E
Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español
Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
FILE NO. SVM-07013 11. HOW TO DIAGNOSE THE TROUBLE
FILE. SVM-070. HOW TO DIAGSE THE TROUBLE The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below.
SERVICE MANUAL SPLIT TYPE 42NQV025H 38NYV025H 42NQV035H 38NYV035H 42NQV035M 38NYV035M 42NQV045H 38NYV045H 42NQV045M 38NYV045M R410A
FILE NO. SVM-07013-1 SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit 42NQV025H 38NYV025H 42NQV035H 38NYV035H 42NQV035M 38NYV035M 42NQV045H 38NYV045H 42NQV045M
AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE R410A RAV-SM566KRT-E, RAV-SM806KRT-E RAV-SM566KRT-TR, RAV-SM806KRT-TR INDOOR UNIT.
FILE. SVM-2004 SERVICE MANUAL AIR-CONDITIONER INDOOR UNIT SPLIT TYPE High Wall Type RAV-SM566KRT-E, RAV-SM806KRT-E RAV-SM566KRT-TR, RAV-SM806KRT-TR R40A FILE. SVM-2004 Adoption of New Refrigerant This
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
AIR-CONDITIONER SPLIT TYPE
ONE-TOUCH COMFORT SLEEP SWING FAN FIX QUIET POWER-SEL Hi POWER FILE. SVM-056 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE Indoor Unit RAS-8N3KV-E RAS-BN3KV-E Outdoor Unit
AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE
SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-10GKV-E2 / RAS-10GAV-E2 RAS-13GKV-E2 / RAS-13GAV-E2 RAS-16GKV-E2 / RAS-16GAV-E2 RAS-10NKV-A2 / RAS-10NAV-A2 RAS-13NKV-A2 / RAS-13NAV-A2 RAS-16NKV-A2 /
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
FILE NO. A010-024 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE. <Heat Pump Type> RAS-M10PKVP-E RAS-M13PKVP-E RAS-M16PKVP-E RAS-M18UAV-E
FILE. A010-024 SERVICE MANUAL Indoor Unit RAS-M10PKVP-E RAS-M13PKVP-E RAS-M16PKVP-E Outdoor Unit AIR-CONDITIONER RAS-M18UAV-E SPLIT TYPE R410A PRINTED IN JAPAN, Mar., 2011 CONTENTS 1.
FILE NO. SVM-10029 SERVICE MANUAL SPLIT TYPE RAS-10SKVR-E2 / RAS-10SAVR-E2 R410A
FILE. SVM-10029 SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit RAS-10SKVR-E2 / RAS-10SAVR-E2 R410A March, 2010 CONTENTS FILE. SVM-10029 1. SAFETY PRECAUTIONS...
FILE NO. SVM-14016 SERVICE MANUAL SPLIT TYPE RAS-35G2KVP-ND / RAS-35G2AVP-ND R410A
FILE. SVM-14016 SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit RAS-25G2KVP-ND / RAS-25G2AVP-ND RAS-35G2KVP-ND / RAS-35G2AVP-ND R410A May, 2014 CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER SHARP CORPORATION SHARP CORPORATION CONTENTS
SERVICE MANUAL SPLIT SYSTEM ROOM AIR CONDITIONER INDOOR UNIT AH-129 AH-MP14 OUTDOOR UNIT AU-129 AU-MP14 CONTENTS SPECIFICATIONS...2 EXTERNAL DIMENSIONS...4 WIRING DIAGRAMS...5 ELECTRICAL PARTS...6 MICROCOMPUTER
AIR-CONDITIONER SPLIT TYPE
FILE NO. A08-016 SERVICE MANUAL AIR-CONDITIONER SPLIT TYPE RAS-M10PKVP-E, RAS-M13PKVP-E, RAS-M16PKVP-E, RAS-M18PKVP-E / RAS-M10PKVP-ND, RAS-M13PKVP-ND, RAS-M16PKVP-ND, RAS-M18PKVP-ND / RAS-3M26GAV-E1,
SERVICE INSTRUCTION R410A. SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER Universal Floor / Ceiling Duct / Cassette Wall Mounted / Floor type INVERTER MULTI R410A Models Indoor unit Outdoor unit AB*14LBAJ AB*18LBAJ AB*F14LAT
TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05
TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
SERVICE MANUAL. Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/
SERVICE MANUAL Room Air Conditioner Multi Split type Outdoor unit /R410A DC Inverter/ FS2MI-147HFD FS2MI-187HFD FS3MI-217HFD FS3MI-277HFD FS4MI-277HFD FS4MI-367HFD FS5MI-367HFD NOTE: Before servicing the
OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)
OPERATION MANUAL (Ceiling mounted duct type) VAM50FB VAM500FB VAM650FB VAM800FB VAM000FB VAM500FB VAM000FB 8 7 6 9 5 7 5 0 6 8 6 9 0 5 5 7 7 6 7 A A B B 5 6 5 6 7 VAM50F VAM800F VAM500F VAM500F VAM000F
SERVICE MANUAL OUTDOOR UNIT. No. OBH590 REVISED EDITION-B. Models HFC
SPLIT-TYPE AIR CONDITIONERS Revision B: MUZ-EF25/35/42/50VE - E2 and MUZ-EF25/35VEH - E2 have been added. Please void OBH590 REVISED EDITION-A. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH590 REVISED
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
AIR CONDITIONER SERVICE MANUAL SPLIT WALL TYPE
FILE. SVM-09036 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-18SKHP-ES / RAS-18S2AH-ES RAS-24SKHP-ES / RAS-24S2AH-ES RAS-18SKP-ES / RAS-18SA-ES RAS-24SKP-ES / RAS-24SA-ES February, 2009 CONTENTS
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
Floor Type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA. English
Floor Type Air-Conditioner MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA INSTALLATION MANUAL This manual only describes the installation of indoor unit. When installing the outdoor unit, refer to the installation manual
CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE
Order No. PHAAM1003090C3 Outdoor Unit CU-2E15LBE CU-2E18LBE CU-3E18LBE CU-4E23LBE Air Conditioner Please file and use this manual together with the service manual for Model No. CS-E7LKEW CU-E7LKE CS-E7LKEW
SERVICE MANUAL. Heat Recovery Type R410A
FILE. A05-004- Revised: Jan./006 SERVICE MANUAL R40A System air conditioner The indoor units in the Super Heat Recovery Multi System are common to those used in the Super Modular Multi System air conditioner.
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL SCHEMATIC DIAGRAM 13 5. EXPLOSION VIEW 16 6
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE080528 Models KFTHP-12 KFTHP-18 KFTHP-24 CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. ELECTRICAL
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
SERVICE MANUAL MUZ-GE25VA - E1 MUZ-GE25VAH - E1 MUZ-GE35VA - E1 MUZ-GE35VAH - E1 MUZ-GE42VA - E1 MUZ-GE42VAH - E1 MUZ-GE50VA - E1 MUZ-GE50VAH - E1
SPLIT-TYPE AIR CONDITIONERS Revision A: MUZ-GE42/50VA(H) - E1 has been added. Please void OBH516. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OBH516 REVISED EDITION-A Models MUZ-GE25VA - E1 MUZ-GE25VAH
ROOM AIR CONDITIONER INSTALLATION MANUAL
ROOM AIR CONDITIONER INSTALLATION MANUAL ( Split Type) Please read this installation manual completely before installing the product When the power cord is damaged, replacement work shall be performed
CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM 11 5. EXPLOSION VIEW 12 6.
TCL WALL MOUNTED SPLIT-TYPE AIR CONDITIONERS SERVICE MANUAL No.TE051220 Models TAC-09CHSA/GI TAC-12CHSA/GI CONTENTS 1. IMPORTANT NOTICE 2 2. TECHNICAL SPECIFICATION 3 3. OPERATION DETAILS 4 4. WIRING DIAGRAM
INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.
EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium
CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE
Order No. MAC0512111C8 Air Conditioner CS-XE9EKE CU-XE9EKE CS-XE12EKE CU-XE12EKE TABLE OF CONTENTS PAGE 1 Safety Precautions----------------------------------------------- 3 2 Specifications -----------------------------------------------------
CS-CE9NKE CS-CE12NKE CU-CE9NKE CU-CE12NKE TABLE OF CONTENTS WARNING
Order No: PAPAMY1207094CE Indoor Unit CS-CE9NKE CS-CE12NKE Outdoor Unit CU-CE9NKE CU-CE12NKE WARNING This service information is designed for experienced repair technicians only and is not designed for
DC INVERTER MULTI-SYSTEM AIR CONDITIONER
AIR CONDITIONER AIR CONDITIONER TECHNICAL & SERVICE MANUAL INDOOR UNIT : CS-MKE7NKU CS-MKE9NKU CS-MKE12NKU CS-MKE18NKU CS-MKE24NKU DC INVERTER MULTI-SYSTEM AIR CONDITIONER Capacity 7,500BTU / h 9,000BTU
FILE NO. SVM-10017 SERVICE MANUAL SPLIT TYPE RAS-107SKV-E3 RAS-107SAV-E3 R410A
SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit RAS-107SKV-E3 RAS-107SAV-E3 R410A Feburary, 2010 CONTENTS FILE NO. SVM-10017 1. SAFETY PRECAUTIONS... 2 2.
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL CSKS12NB41 & CZ18BT1U + CUKS12NK1A CSKS18NB4UW & CZ18BT1U + CUKS18NKU CSKS18NB4UW & CZ18BT1U + CUKS18NKUA DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel)
13. Troubleshooting. Indoor unit s LED indication of Corona DC inverter unit. Indoor unit s LED indication of Alfa DC inverter unit
Troubleshooting 13. Troubleshooting Indoor unit s LED indication of Corona DC inverter unit MCAC-HTSM-2007-11 E0 E1 E2 E3 E5 E6 P0 P1 P2 P3 P5 EEPROM error outdoor communication error Zero-crossing examination
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
TECHNICAL & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER + SAP C181MA + SAP C181GA + SAP C181BA + SAP C241MA + SAP C241BA FILE NO.
TECHNICAL & SERVICE MANUAL SAP K161GJA SAP K181GJA SAP K181MBA SAP K241GJA SAP K241MBA + SAP C161GA + SAP C161JA + SAP C181GA + SAP C181JA + SAP C181MA + SAP C181BA + SAP C241GA + SAP C241JA + SAP C241MA
SERVICE MANUAL INDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision E: MSZ-GE22VAD- A1 has been added. Please void OBH531 REVISED EDITION-D. INDOOR UNIT SERVICE MANUAL. OBH531 REVISED EDITION-E Models MSZ-GE22VA - A1 MSZ-GE50VA - A1
AIR-CONDITIONER SERVICE MANUAL SPLIT TYPE RAV-SP804ATZG-E RAV-SM454SDT-E RAV-SP564ATZG-E R410A INDOOR UNIT OUTDOOR UNIT FILE NO.
FILE. A08-007 SERVICE MANUAL AIR-CONDITIONER INDOOR UNIT RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E OUTDOOR UNIT RAV-SP404AT-E RAV-SP404ATZ-E RAV-SP404ATZG-E
FILE NO. SVM-10044 SERVICE MANUAL SPLIT TYPE RAS-18SAV2-E R410A
FILE NO. SVM-0044 SERVICE MANUAL SPLIT TYPE Indoor Unit Outdoor Unit RAS-B0UFV-E RAS-B3UFV-E RAS-B8UFV-E RAS-0SAV-E RAS-3SAV-E RAS-8SAV-E RAS-8SAV-E R40A April,
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS
NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE
AIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
OWNER'S MANUAL R-410A Duct Free Split System Air Conditioner and Heat Pump
R-410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H)-System, DFC4(A/H)3-Outdoor, DFF4(A/H)H-Indoor Please read the operating instructions and safety precautions carefully
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY
RV Products Division SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY Airxcel, Inc. RV Products Division P.O. Box 4020 Wichita, KS 67204 1976A376 (1-11) TABLE OF CONTENTS
NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS
INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the
FILE NO. SVM-09030 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-13SKHP-ES / RAS-13S2AH-ES
FILE. SVM-09030 SERVICE MANUAL AIR CONDITIONER SPLIT WALL TYPE RAS-13SKHP-ES / RAS-13S2AH-ES January, 2009 CONTENTS 1. SPECIFICATIONS 2. CONSTRUCTION VIEWS 2-1 Indoor Unit 2-2 Outdoor Unit 3. WIRING DIAGRAM
CS-HE9NKE CS-HE12NKE CS-AE9NKE CU-HE9NKE CU-HE12NKE CU-AE9NKE TABLE OF CONTENTS WARNING
Order No: PAPAMY1207093CE Indoor Unit CS-HE9NKE CS-HE12NKE CS-AE9NKE Outdoor Unit CU-HE9NKE CU-HE12NKE CU-AE9NKE WARNING This service information is designed for experienced repair technicians only and
REMOTE CONTROL MANUAL
REMOTE CONTROL MANUAL ENGLISH CONTENT PRECAUTIONS...1-2 USING THE REMOTE CONTROL UNIT...3 OPERATION...4-9 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read
9ASNA-A1-1202 SERVICE MANUAL SENVILLE AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE
9ASNA-A1-1202 SERVICE MANUAL SENVILLE AIRCONDITIONER DC INVERTER SPLIT WALL-MOUNTED TYPE CONTENTS 1. Precaution... 1 1.1 Safety Precaution... 1 1.2 Warning... 1 2. Function... 6 3. Dimension... 9 3.1 Indoor
york air-conditioning products Residential & VRF News 2015
york air-conditioning products Residential & VRF News 2015 york air-conditioning products Catalogue Content Split Systems Pag. High wall High Efficiency Inverter YWHJZH 09 to 24 K 6 High wall Inverter
AIR CONDITIONER OUTDOOR UNIT
AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL For authorized personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. English Français MANUAL DE INSTALACIÓN Solo para personal autorizado.
AIR CONDITIONING & HEAT PUMP SYSTEMS
AIR CDITIING & HEAT PUMP SYSTEMS SERVICE GUIDE Including outdoor unit (FDC 6 Series and 8 Series) FDT 4-Way Cassette FDEN Ceiling Suspended FDKN Wall Mounted FDR Ducted Cassette FDU Ducted - gh Static
TECHNICAL & SERVICE MANUAL WINDOW TYPE AIR CONDITIONER SA 79G SA 99G FILE NO. SA 79G SA 99G REFERENCE NO. SM700402
TECHNICAL & SERVICE MANUAL SA 79G SA 99G FILE NO. WINDOW TYPE AIR CONDITIONER Model No. Product Code No. Destination SA-79G-A 1 851 005 18 General (50Hz) & Europe SA-99G-A 1 851 005 19 SA 79G SA 99G REFERENCE
SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET
SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION INSTRUCTION SHEET (PART NO. 97474700) For authorized service personnel only. This installation instruction sheet describes how to install the outdoor unit only.
AIR-CONDITIONER MULTI TYPE
Leading Innovation FILE NO. SVM-02 SERVICE MANUAL AIR-CONDITIONER MULTI TYPE < Console Type> MML-AP0074NH-E, -TR MML-AP0094NH-E, -TR MML-AP024NH-E, -TR MML-AP054NH-E, -TR MML-AP084NH-E, -TR This Service
Model: AC-S13CG x 2. Model No: AC-S13CGx2.doc Version 1.0
Air Conditioner Service Manual 2 3 Model: AC-S13CG x 2 3 Content Technical specification.. 4 Performance curve.5 Outline & dimension of indoor unit..10 Outline & dimension of outdoor unit 11 Exploded view
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
CU-S9KKQ CU-S12KKQ CU-S18KKQ CU-S24KKQ CS-S9KKQ CS-S12KKQ CS-S18KKQ CS-S24KKQ WARNING
Order No: PHAAM1001037C3 Indoor Unit CS-S9KKQ CS-S12KKQ CS-S18KKQ CS-S24KKQ Outdoor Unit CU-S9KKQ CU-S12KKQ CU-S18KKQ CU-S24KKQ WARNING This service information is designed for experienced repair technicians
SERVICE MANUAL INDOOR UNIT
SPLIT-TYPE AIR CONDITIONERS Revision B: "How to check miswiring and serial signal error" for MUZ type has been added. The description about "Low standby power control" has been added to "TECHNICAL CHANGES".
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board.
EVANS ELECTRONIC TEMPERATURE CONTROL TROUBLESHOOTING GUIDE for systems equipped with electric coolant valve and external PC board. This Troubleshooting Guide covers the electric coolant valve and control
technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air
technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t
AIR CONDITIONER (SPLIT TYPE) Installation manual. Outdoor Unit. English. Model name:
AIR CONDITIONER (SPLIT TYPE) Installation manual Outdoor Unit Model name: RAV-SM2244AT7 RAV-SM2244AT7Z RAV-SM2244AT7ZG RAV-SM2244AT8-E RAV-SM2244AT8Z-E RAV-SM2244AT8ZG-E RAV-SM2804AT7 RAV-SM2804AT7Z RAV-SM2804AT7ZG
INDOOR UNIT <DIGITAL INVERTER>
FILE. A-08 SERVICE MANUAL SPLIT TYPE INDOOR UNIT Concealed Duct Type RAV-SM406BT-E RAV-SM456BT-E RAV-SM566BT-E RAV-SM806BT-E RAV-SM06BT-E RAV-SM406BT-E RAV-SM606BT-E RAV-SM406BT-TR RAV-SM456BT-TR
Multi System. 16 SEER, Inverter System. 9,000 to 18,000 BTU/Hr. Single Split
Multi System 16 SEER, Inverter System 9,000 to 18,000 BTU/Hr Single Split 4MXW8-A 4TXM6-A March2013 42 Warnings and Cautions Warnings and Cautions. Notice that warnings and cautions appear at appropriate
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
Technical service manual 2009
MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS Technical service manual 2009 KSIM MULTI ZONE SERIES R410A DC Inverter multi Series Models KSIM20912-H216 KSIM30912-H216 KSIM40912-H216 CONTENT 1. Product features
AIR-CONDITIONER SERVICE MANUAL (MULTI TYPE) R410A
FILE NO. A-0 SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) Medium Static Ducted Type MMD- AP0074BH2UL MMD- AP0094BH2UL MMD- AP024BH2UL MMD- AP054BH2UL MMD- AP084BH2UL MMD- AP024BH2UL MMD- AP0244BH2UL MMD-
ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS
ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Céliera Corporation. All rights reserved. Unauthorized duplication, reproduction prohibited. CONTENTS SAFETY PRECAUTIONS...
DC INVERTER SPLIT SYSTEM AIR CONDITIONER
TECHNICAL & SERVICE MANUAL CSKE1NB41 & CZ18BT1U + CUKE1NK1 CSKE18NB4UW & CZ18BT1U + CUKE18NKU DC INVERTER SPLIT SYSTEM AIR CONDITIONER Indoor Model No. Body (Panel) CSKE1NB41 (CZ18BT1U) CSKE18NB4UW (CZ18BT1U)
Installation manual MMU-AP0071MH2UL MMU-AP0091MH2UL MMU-AP0121MH2UL MMU-AP0151MH2UL MMU-AP0181MH2UL AIR CONDITIONER (MULTI TYPE) Indoor Unit
AIR CONDITIONER (MULTI TYPE) Installation manual Indoor Unit Model name: Compact 4-way Cassette type MMU-AP0071MH2UL MMU-AP0091MH2UL MMU-AP0121MH2UL MMU-AP0151MH2UL MMU-AP0181MH2UL Installation manual
TIG INVERTER INSTRUCTION MANUAL
TIG INVERTER INSTRUCTION MANUAL Contents Warning General Description Block Diagram Main Parameters Circuit Diagram Installation and Operation Caution Maintenance Spare Parts List Troubleshooting 3 4 4
RAV-SM560AT-E/RAV-SM800AT-E RAV-SM560UT-E/RAV-SM800UT-E RAV-SM560BT-E/RAV-SM800BT-E RAV-SM560KRT-E/RAV-SM800KRT-E RAV-SM560XT-E/RAV-SM800XT-E
FILE. A0-04 Revised Nov. 00 SERVICE MANUAL SPLIT TYPE RAV-SM560AT-E/RAV-SM800AT-E RAV-SM560UT-E/RAV-SM800UT-E RAV-SM560BT-E/RAV-SM800BT-E RAV-SM560KRT-E/RAV-SM800KRT-E RAV-SM560XT-E/RAV-SM800XT-E File
LG Floor Standing Type Air Conditioner INSTALLATION MANUAL
website http://www.lgservice.com e-mail http://www.lgeservice.com/techsup.html LG Floor Standing Type Air Conditioner INSTALLATION MANUAL LG IMPORTANT Please read this installation manual completely before
TMS TANK MANAGEMENT SYSTEM
TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS
RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1604UT-E
AIR CONDITIONER (SPLIT TYPE) Owner s Manual Indoor Unit Model name: For commercial use 4-way Cassette Type RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM1604UT-E Owner s Manual English
Wall Mounted Mini Split Heat Pump Air Conditioner
Wall Mounted Mini Split Heat Pump Air Conditioner OPERATING AND INSTALLATION MANUAL Model: KFIHP-09-ID / KFHIP-09-OD KFHHP-12-ID / KFHHP-12-OD Indoor Unit. Outdoor Unit. Thank you for selecting Soleus
SERVICE MANUAL OUTDOOR UNIT MUZ-A09NA,- 1,- U1,- U2 MUZ-A12NA,- U1 MUZ-A15NA,- U1 MUZ-A17NA,- U1 MUY-A15NA MUY-A17NA MUY-A24NA,- 1,- U1,- U2
SPLIT-TYPE AIR CONDITIONERS Revision E: MUZ-GA24NA and MUY-GA24NA have been added. Please void OB451 REVISED EDITION-D. OUTDOOR UNIT SERVICE MANUAL HFC utilized R410A. OB451 REVISED EDITION-E Models MUZ-A09NA,-
AIR CONDITIONER OUTDOOR UNIT
AIR CONDITIONER OUTDOOR UNIT INSTALLATION MANUAL For authorized personnel only. MANUEL D'INSTALLATION Pour le personnel agréé uniquement. English Français MANUAL DE INSTALACIÓN Solo para personal autorizado.
User Manual. Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com
Air-conditioner Controller SB-DN-HVAC (MAC01.331) www.hdlautomation.com Document updates: Version Data Description V1.0 2015.05.25 Finish new document HVAC Controller User Manual INDEX 1. Overview...1
SWIMMING POOL HEAT PUMP Owners Manual
SWIMMING POOL HEAT PUMP Owners Manual This manual refers to the 17.0kw and 21.0kw models only. The heat pump unit is sold with a 1 year warranty. In addition there is a 2 year parts warranty on the compressor
New Deluxe Wall Mounted Heat Pump Series EXTERIOS
New Deluxe Wall Mounted Heat Pump Series EXTERIOS May 2013 New Deluxe Wall Mounted Heat Pump Series Panasonic Adding New Air Conditioner Lineup Setting Another Mile Stone in the US Ductless Split History
