Preprufe 160 Sheet Tanking and Waterproofing Membrane
|
|
|
- Ashley Powers
- 9 years ago
- Views:
Transcription
1 TECHNICAL Technical data may be updated at any time. It is the users responsibility to check data validity by reference to the website or Nuplex Construction Products MANUAL SECTION ISSUE DATE AUTHORISED REPLACES PAGE Waterproofing March 2008 PM Feb 2006 Page1 Preprufe 160 Sheet Tanking and Waterproofing Membrane Description Bituthene Preprufe 160 is is a DPM (damp proof membrane) consisting of a modified heavy duty sheet comprising of modified adhesive on a heavy polyethylene face which is a continuous reinforcement. It is pre-applied to the site and concrete is poured against Preprufe within formwork. The concrete fully bonds to the adhesive resulting in a fully adhered membrane to the floors and walls of a sub-ground structure. Application areas: DPM or below grade tanking (walls buried below ground). Preprufe 160 prevents water from entering the wall or building structure from the ground. Used behind walls or under floor slabs. Under floor slabs Behind poured in-situ concrete Features Compliant product with E2/AS1 July 2005; section 12.0, b Used in New Zealand for over 5 years Compliant with BRANZ bulletin #397, Waterproofing basements; section B2 50 Year durability compliant; Life of the building (refer BBA approval). cont.. No warranty either expressed or implied or statutory is made by NUPLEX in this document except as expressly stated in any sale and purchase agreement entered into between NUPLEX and the buyer. CERTIFIED ISO 9001 REG. NO. 158 This document is a technical data information sheet The description of the product or products and the properties of the product or products contained in this document is for the sole purpose of identifying the product or products and describing their property or properties and does not constitute a warranty that the product or its properties shall conform to that description; nor is the description of the product and/or its properties a warranty by NUPLEX that the goods are suitable for a particular purpose. H A M I L T O N Telephone: Fax: NUPLEX CONSTRUCTION PRODUCTS PO Box , Penrose, Auckland Telephone: , Fax: , [email protected] PALMERSTON NORTH W E L L I N G T O N Telephone: Telephone : Fax: Fax: C H R I S T C H U R C H Telephone: Fax;
2 BBA approval (British Board of Agreement). Grades 2,3 &4. BS8102:1990 All joints sealed by permanent self adhesive. Elongation: 300% min, ASTM D412 Moisture Vapour Transmission: Zero, 0 gram/day. BS3177:1995 Permeability: K=<1.4x10 ¹¹ cm.s ¹. ASTM D Fully bonds to concrete: will not fall away if ground collapses, settles or dries out. Forms an integral seal with the concrete. Not reliant on confinement. Materials Preprufe 160 roll 1.2 x 35m, 0.8mm thick (incls 0.4mm HDPE) Preprufe Tape roll 15 x 0.1m Bituthene liquid membrane (part polyurethane for sealing around penetrations.) Producer Statement Preprufe 160 complies with the requirements of the NZ building code and any relating acts. Preprufe 160 complies with E2/AS and durability under B2. The conditions under B2 (50years durability for elements that are inaccessible) are accepted and complied with providing all preparation and installation is carried out by Nuplex licenced contractors and all product installation details are followed. PREPRUFE 160 PRE-APPLIED SHEET BELOW GRADE TANKING Substrates - All surfaces are to be sound and solid to eliminate movement during concrete placement. Substrate must be regular and smooth with no gaps or voids greater than 12mm. Grout around all penetrations such as utility conduits for stability. Floor slabs Monolithic (site) concrete blinding, sand or mud slab is preferred. The blinding must be free of loose aggregate and sharp protrusions. An angular profiled blinding is recommended rather than a sloping or rounded substrate. Surfaces do not need to be dry but standing water must be removed to prevent overlaps being contaminated and waterproofing properties compromised. Walls Use concrete, plywood insulation, Hydroduct drainage system or other approved facing to sheet piling or other retaining structure to provide support for the membrane. Board systems such as timber lagging must be close butted to provide support and not more than 12mm out of alignment. The Preprufe is loose laid against the wall. The sides are self adhesive. The top edge can be nailed, power fastened, metal strip etc. Take care to protect this edge as it will need flashing and/or connection to other waterproofing Installation - Install Bituthene Preprufe membrane to all areas required to achieve a waterproof finish in accordance with the Grace technical data "Preprufe Foundation Protection". Temperatures must be greater than -4 C or above during installation: - Ensure HDPE film facing the prepared substrate and the treated white coating surface facing the new concrete. - End laps are to be staggered to avoid build up of layers. - Accurately position sheets to overlap the previous sheet a minimum of 75mm (side and end laps) along the selvedge. Underside of sheet must be clean, dry and free from contamination before attempting to overlap. Peel back the plastic release liner from between the overlaps as the two layers are bonded together. Ensure a continuous bond is achieved without creases and roll firmly with a heavy roller. - Secure the top of the membrane in vertical applications using a batten such as a termination bar or fixing 50mm below the top edge. - For vertical lengths greater than 2.4 metres mechanically fasten vertical laps at 0.6m intervals using flat head nails or fixings suitable for the substrate. Fixings are to be placed through the selvedge so that the
3 membrane lays flat to enable heavy rolling. Fixings within the sheet must be covered with a patch of Preprufe Tape. - Complete all cut ends or laps using Preprufe Tape. Preprufe Tape must be centered on laps. - Completely remove the plastic release liner to expose the protective coating before placing the concrete. Any initial tack will disappear. - Complete and seal all penetrations using Preprufe membrane and Preprufe tape. Mix and apply Bituthene LM3000 liquid membrane around all penetrations and detailed areas using a fillet to provide a watertight seal. - Inspect the Preprufe membrane prior to placement of the concrete and carry out repairs as necessary using Preprufe Tape and Preprufe membrane. Ensure repair extends 150mm beyond damaged areas. - Dirty areas can be cleaned by wiping with a damp cloth or low pressure water jet if required. - Concrete must be placed within 40 days of removing the protective release liner. - Install steel reinforcing as required. - Concrete must be placed and compacted carefully to avoid damaging the Bituthene Preprufe membrane. Formwork is to remain in position until the concrete has gained sufficient strength to develop the bond with the Preprufe membrane. - Seal top edge, penetrations, and detail work using Bituthene LM 3000 liquid membrane. Note the following: Must be installed by Licensed Nuplex Contractors who are members of The Nuplex Contractors Federation Inc. Top of the Bituthene Preprufe is to extend a minimum 150mm above ground level. Check Bituthene Preprufe Membrane for faults or damage prior to placement of the concrete Ensure finished ground surface falls away from the membrane a minimum 1:30 to divert ground water. Drainage Where required Bituthene Preprufe can be applied over a drainage medium such a Bituthene Hydroduct. Install minimum 100 mm dia drain with openings to collect water at the base of the wall. Drain is to be placed 200mm below the interior basement floor level. Drain must have minimum 1:200 fall to the outlet. General Bituthene Preprufe can be used in conjunction with other Bituthene waterproofing/ tanking materials. Bituthene Preprufe when used in conjunction with other Bituthene Products must positively seal with floor DPM and have adequate drainage installed. Preprufe laid out prior to reinforcing and concrete pour.
4 Grace Building Envelope Systems Preprufe 300R & 160R Pre-applied Waterproofing Membranes That Bond Integrally To Poured Concrete For Use Below Slabs Or Behind Basement Walls On Confined Sites Advantages Forms a unique integral seal to concrete poured against it. This prevents water migration and makes it unaffected by ground settlement beneath slabs. Fully-adhered watertight laps and detailing Provides a barrier to water, moisture and gas physically isolates the structure from the surrounding ground. BBA Certified for basement Grades 2, 3, & 4 to BS 8102:1990 Zero permeance to moisture Solar reflective - reduced temperature gain Simple and quick to install, requiring no priming or fillets. Can be applied to permanent formwork - allows maximum use of confined sites. Self protecting - can be trafficked immediately after application and ready for immediate placing of reinforcement. Unaffected by wet conditions - cannot activate prematurely. Inherently waterproof, non-reactive system: - not reliant on confining pressures or hydration - unaffected by freeze/thaw, wet/dry cycling Chemically resistant, effective in all types of soils and waters - protects structure from salt or sulphate attack. Description Preprufe 300R & 160R membranes are unique composite sheets comprising a thick HDPE film, an aggressive pressure sensitive adhesive and a weather resistant protective coating. Unlike conventional non-adhering membranes, which are vulnerable to water ingress tracking between the unbonded membrane and structure, the unique Preprufe seal to concrete prevents any ingress or migration of water around the structure. The Preprufe R System includes: Preprufe 300R - heavy-duty grade for use below slabs and on rafts (i.e. mud slabs). Designed to accept the placing of heavy reinforcement using conventional concrete spacers. Preprufe 160R - thinner grade for lighter applications and reverse tanking (i.e. blindside zero property line) applications against permanent formwork such as soil retention systems. Preprufe Tape LT - for covering cut edges, roll ends, penetrations and detailing (temperatures between -4 C and +30 C). Preprufe Tape HC - as above for use in Hot Climates (minimum10 C). Liquid Membrane - for sealing around penetrations, etc. Liquid Membrane Watertight and grout tight sealed laps Adhesive surface of Preprufe 300R & 160R membrane Slab formwork Selvedge Preprufe 300R & 160R membranes are applied either horizontally to smooth prepared concrete or well rolled and compacted sand or crushed stone blinding; or vertically to permanent formwork or adjoining structures. Concrete is then cast directly against the adhesive side of the membranes. The specially developed Preprufe adhesive layers work together to form a continuous and integral seal to the structure. Preprufe can be returned up the inside face of slab formwork but is not recommended for conventional twin-sided formwork on walls, etc. Use Bituthene self-adhesive membrane or Procor fluid applied membrane to walls after removal of formwork for a fully bonded system to all structural surfaces.
5 Installation Preprufe 300R & 160R membranes are supplied in rolls 1.2m wide, with a selvedge on one side to provide selfadhered laps for continuity between rolls. The rolls of Preprufe membrane and Preprufe Tape are interwound with a disposable plastic release liner which must be removed before placing reinforcement and concrete. Substrate Preparation All Surfaces - It is essential to create a sound and solid substrate to eliminate movement during the concrete pour. Substrates must be regular and smooth with no gaps or voids greater than 12 mm. Grout around all penetrations such as utility conduits, etc. for stability. Horizontal Blinding - Monolithic concrete blinding or mud slab is preferred. The blinding must be free of loose aggregate and sharp protrusions. An angular profiled blinding is recommended rather than a sloping or rounded substrate. The surface does not need to be dry, but standing water must be removed. Vertical Sheet Piling - Use concrete, plywood, insulation or other approved facing to sheet piling to provide support to the membrane. Board systems such as timber lagging must be close butted to provide support and not more than 12 mm out of alignment. fixings must be covered with a patch of Preprufe Tape. Ensure the underside of the succeeding sheet is clean, dry and free from contamination before attempting to overlap. Roll firmly to ensure a watertight seal. Roll Ends and Cut Edges - Overlap all roll ends and cut edges by a minimum 75 mm and ensure the area is clean and free from contamination, wiping with a damp cloth if necessary. Allow to dry and apply Preprufe Tape LT (or HC in hot climates) centered over the lap and roll firmly. Immediately remove printed plastic release liner from the tape. Penetrations Use the following steps to seal around penetrations such as service pipes, piles, lightning conductors, etc. Grout around the penetration if the penetration is not stable. Scribe membrane tight to the penetration. If the membrane is not within 12mm of the penetration, apply Preprufe Tape to Corners Internal and external corners should be formed as shown in the diagrams returning the membrane a minimum of 100mm and sealing with Preprufe Tape. Ensure that the apex of the corner is covered and sealed with tape and roll firmly. Crease and fold the membrane to ensure a close fit to the substrate profile and avoid hollows. fold Membrane Installation Preprufe can be applied at temperatures of -4ºC or above. During cold or damp conditions, the selvedge and tape adhesive can be gently warmed using a hot air gun or similar to remove moisture or condensation and improve initial adhesion. Horizontal Substrates - Place the membrane HDPE film side to the substrate with printed coated side up facing towards the concrete pour. End laps should be staggered to avoid a build up of layers. Leave plastic release liner in position until overlap procedure is completed. Accurately position succeeding sheets to overlap the previous sheet 75 mm along the marked selvedge. Ensure the underside of the succeeding sheet is clean, dry and free from contamination before attempting to overlap. Peel back the plastic release liner from between the overlaps as the two layers are bonded together. Ensure a continuous bond is achieved without creases and roll firmly with a heavy roller. Completely remove the plastic liner to expose the protective coating. Any initial tack will quickly disappear. Internal fold Preprufe Tape 100 min External min Preprufe Tape Vertical Substrates - Mechanically fasten the membrane vertically using fixings (i.e. fasteners) appropriate to the substrate with the printed coated side facing towards the concrete pour. The membrane may be installed in any convenient length. Secure the top of the membrane using a batten such as a termination bar or fixing 50 mm below the top edge. Fixings can be made through the selvedge so that the membrane lays flat and allows firmly rolled overlaps. Immediately remove the plastic release liner. Any additional 4
6 cover the gap. Wrap the penetration with Preprufe Tape by positioning the tape 12 mm above the membrane. Mix and apply Bituthene Liquid Membrane around the penetrations using a fillet to provide a watertight seal between the Preprufe membrane and Preprufe Tape. Membrane Repair Inspect the membrane before installation of reinforcement steel, formwork and final placement of concrete. The membrane can be easily cleaned by jet washing if required. Repair damage by wiping the area with a damp cloth to ensure the area is clean and free from dust, and allow to dry. Apply Preprufe Tape centered over the damaged area and roll firmly. Any areas of damaged adhesive should be covered with Preprufe Tape. Remove printed plastic release liner from tape. Where exposed selvedge has lost adhesion or laps have not been sealed, ensure the area is clean and dry and cover with fresh Preprufe Tape, rolling firmly. Alternatively, use a hot air gun or similar to activate adhesive and firmly roll lap to achieve continuity. Pouring of Concrete Ensure the plastic release liner is removed from all areas of Preprufe R membrane and Tape. It is recommended that concrete be poured within 56 days (42 days in hot climates) of application of the membrane. Concrete must be placed and compacted carefully to avoid damage to the membrane. Never use a sharp object to consolidate the concrete. Wall base detail 5 3 Alternative wall base detail for early shutter removal mm lap mm lap 300 mm Wall base with toe detail showing drainage option Wall base detail against permanent shutter mm lap mm lap line of permanent formwork mm lap 100 mm lap Pipe penetration 2 Pile detail 4 1 reinforcement Preprufe 3 Bituthene or Procor 5 Protection 2 Preprufe Tape 4 Liquid Membrane 6 Hydroduct Details shown are typical illustrations and not working details. For assistance with detailing and problem solving please contact Grace Technical Department.
7 Physical Properties Property Typical Value Test Method 300R 160R Colour White Thickness* 1.2 mm 0.8 mm ASTM D3767 Peel Adhesion to Concrete 880 N/m ASTM D903 modified Shear Strength of Joints 440 N/m ASTM D1876 modified Methane permeability 9.1 mls/m 2 /day NA University of London, QMW College3 Resistance to Hydrostatic Head >70 m ASTM D5385 modified Low Temperature Flexibility <-20 C ASTM D1970 Puncture Resistance 990 N 445 N ASTM E 154 Elongation 300% minimum ASTM D412 modified Tensile Strength, Film 27.6 Mpa ASTM D412 Crack -23 C Pass ASTM C 836 Permeability K=<1.4 x cm.s -1 ASTM D Typical test values represent average values from samples tested. Test methods noted may be modified. * Nominal thickness refers to the thickness of the membrane without release liner. Supply Preprufe 300R 160R Tape LT or HC* Thickness (nominal) Roll size Roll area Roll weight Min. edge/end laps 1.2 mm 1.2x30.0 m 36.0 m 2 50 kg 75 mm 0.8 mm 1.2x35.0 m 42 m 2 42 kg 75 mm * LT denotes Low Temperature (between -4 C and +30 C) HC denotes Hot Climates (>+10 C) Ancillary Products Liquid Membrane, 5.7 litre mmx15.0 m - 2 kg 75 mm Removal of Formwork Preprufe membranes can be applied to removable formwork, such as slab perimeters, elevator and lift pits, etc. Once the concrete is poured the formwork must remain in place until the concrete has gained sufficient compressive strength to develop the surface bond. Preprufe membranes are not recommended for conventional twin-sided wall forming systems. A minimum concrete compressive strength of 10 N/mm 2 (1500 psi) is recommended prior to stripping formwork supporting Preprufe membranes. Premature stripping may result in displacement of the membrane and/or spalling of the concrete. As a guide, to reach the minimum compressive strength stated above, a structural concrete mix with an ultimate strength of 40 N/mm 2 (6000 psi) will typically require a cure time of approximately 6 days at an average ambient temperature of 4ºC, or 2 days at 21ºC. Specification Clauses Preprufe 300R or 160R shall be applied with its adhesive face presented to receive fresh concrete to which it will integrally bond. Only Grace Construction Products approved membranes shall be bonded to Preprufe 300R &160R. All Preprufe 300R &160R system materials shall be supplied by Grace Construction Products, and applied strictly in accordance with their instructions. Specimen performance and formatted clauses are also available. Health and Safety Refer to relevant Material Safety data sheet. Complete rolls should be handled by a minimum of two persons. Grace Technical Services For assistance with working drawings for projects and additional technical advice, please contact Grace Technical Services. Australia: Brisbane (61-7) Hong Kong (852) Japan (81-3) Korea (82-32) Mainland China: Beijing (86-10) , Guangzhou (86-20) , Shanghai (86-21) Singapore (65) Taiwan (886-3) Thailand (66-2) Vietnam: Ho Chi Minh City (84-8) Bituthene, Hydroduct, Preprufe and Procor are registered trademarks of W. R. Grace & Co.-Conn. The information given is based on data and knowledge considered to be true and accurate and is offered for the user s consideration, investigation and verification. Since the conditions of use are beyond our control we do not warrant the results to be obtained. Please read all statements, recommendations or suggestions in conjunction with our conditions of sale including those limiting warranties and remedies which apply to all goods supplied by us. No statement, recommendation or suggestion is intended for any use which would violate or infringe statutory obligations or any rights belonging to a third party. These products may be covered by patents or patents pending. Copyright W. R. Grace (S) Pte Ltd 110-BIT-5 Printed in Singapore 09/07
8 Preprufe Waterproofing Details
9
10 These diagrammatic aid in site detail recognition. See the Preprufe full details for installation.
11 Installation Sequence
12 Heavy Duty Water-proofing Featuring: Preprufe 160 & Preprufe Systems Features Benefits Fully Bonded to Concrete Tough Becomes integral with concrete floor slab or wall. Does not delaminate if fill subsides as Bentonites will do. Preprufe seals to the structure, not the substrate (compared with Bentonite) Difficult to puncture in the hard extremes of slab siteworks. Puncture resistance 445N Easy to program Easy to install Fits with the building programme. Can be left exposed for 42 days. With Bentonites, the programme must fit that product due to its sensitivity to rain water. Convenient roll form: 35m x 1.2m x 0.8mm Fully adhered watertight laps Tough Bond Will not allow water migration between sheet and concrete interface. Cuts do occur in real sites. Preprufe 160 controls that water. Bentonites do not. Compatible Easy to join with / to other water proofing systems eg Bituthene 3000, LM3000 liquid membrane. Detailed Easy and quick to detail on site around columns, pile caps, penetrations etc Resistant Zero moisture vapour transmission. Gas impermeable isolates the structure from the ground. Cost Efficient Can build to the boundary. Preprufe is a pre-applied waterproofing applied to the cut face. (or under Slab) Flexible Elongation 300% min Multipurpose Used in commercial or residential applications. Although recommended under the slab, it can tie to polythene.(see detail over) Warranty Extensive warranty from two large multinational companies: Nuplex Industries and Grace Construction products. Compliant with E2/AS1 50 year durability requirements.
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description
Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing
Fosroc Proofex Engage
Technical Data Sheet Pre-applied waterproofing membrane conforming to the requirements of BS EN 13967:2004 and BS 8102:2009. Proofex Engage mechanically bonds to poured concrete, remaining in place if
Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.
CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,
SikaProof A Technology
SikaProof A Technology The fully bonded waterproofing system Keep your basements durably and securely watertight What is SikaProof A? How does it work? Where can it be used? What are the advantages of
BBA BRITISH. tanking. Application. Storage & Handling
58 Visqueen Self Adhesive Damp Proof Membrane 60 Visqueen Gas Resistant Self Adhesive Damp Proof Membrane 62 Visqueen Torchon Tanking Membrane 64 Visqueen GX Pre Applied Membrane 66 Visqueen Protect&Drain
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
Waterproofing below-ground with Proofex Engage
Waterproofing below-ground with Proofex Engage Pre-applied waterproofing membrane conforming to the requirements of BS EN 13967:2004 and BS 8102:2009. Proofex Engage mechanically bonds to poured concrete,
Concrete Waterproofing Systems. Integral Protection. www.tritonsystems.co.uk
Concrete Waterproofing Systems Integral Protection n Type B Integral Protection in accordance with BS 8102 (2009) n Unique chemical admix for waterproofing and protection of concrete n A complete and permanent
DENSO WATERPROOFING SYSTEMS
DENSO WATERPROOFING SYSTEMS Approved Quality Management System AS/NZS ISO 9001:2008 Lloyds Register Certificate N o Mel 0927759 Denso (Australia) Pty Ltd A MEMBER OF WINN & COALES INTERNATIONAL 411 413
RIW SHEETSEAL 226 BENEFITS APPLICATIONS APPLIED TO. CI/SfB TN6 L6813. November 2013. l Water and water vapour barrier. l Factory controlled thickness
CI/SfB TN6 L6813 November 2013 RIW SHEETSEAL 226 is a cold applied, high density polyethylene film, coated with a bitumen/rubber self adhesive layer with a removable reinforced silicone paper. Primer is
INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS. Multi-Layer Technology provides increased strength.
INTERIOR WALLS AND BASEMENTS CHOOSING THE RIGHT MEMBRANE FOR INTERIOR WALLS Multi-Layer Technology provides increased strength. Specifically designed for interior applications. Compatible with most internal
WATERPROOFING SikaProof -A TECHNOLOGY
SikaProof -A TECHNOLOGY content What is SikaProof -A? 6 How does it work? 8 Where can it be used? 0 What are the advantages of SikaProof -A? 2 How should it be installed? SikaProof -A system components
Waterproofing below-ground with Proofex Engage. constructive solutions
Waterproofing below-ground with Proofex Engage constructive solutions Our profile Since the company s beginnings over 50 years ago, Fosroc has developed into an International leader in delivering Constructive
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
constructive solutions Fosroc total waterproofing protection of below-ground structures
constructive solutions Fosroc total waterproofing protection of below-ground structures Our profile Since the company s beginnings over 50 years ago, Fosroc has developed into an International leader in
Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades
Construction Sika For Sealing and Waterproofing Construction Gaps in Building Façades Waterproof and Airtight Flexible Seal Controlled Vapour Diffusion Bonds to any Building Substrate Prevents Interstitial
High Performance PSA in Sheet Membrane in Water Protection
High Performance PSA in Sheet Membrane in Water Protection Xia Cao, Senior R&D Chemist, W. R. Grace, Cambridge MA 02140 Jyoti Seth, Strategic Program Leader, W. R. Grace, Cambridge MA 02140 Concrete is
A Guide to Structural Waterproofing
A Guide to Structural Waterproofing Part One Waterproofing Protection For Below Ground Structures 1 2012 W. R. Grace & Co Benjamin J. Brooks Table of Contents Grace Around The World Reference Material
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
DELTA Premium Moisture Management Systems for Foundations.
DELTA protects property. Saves energy. Creates comfort. DELTA Premium Moisture Management Systems for Foundations. DELTA Premium Moisture Management Systems provide the best protection for foundations.
Essential Performance Attributes of Preapplied waterproofing
Essential Performance Attributes of Preapplied waterproofing Craig Boucher, LEED AP Grace Construction Products 62 Whittemore Ave., Cambridge, MA 02140 Phone: 617-498-4429 Fax: 617-498-4419 E-mail: [email protected]
Chapter 2 Basis of design and materials
Chapter 2 Basis of design and materials 2.1 Structural action It is necessary to start a design by deciding on the type and layout of structure to be used. Tentative sizes must be allocated to each structural
Section 5.0. Basements. Wall insulated externally. Wall insulated internally. Ba02. Product: Polyfoam ECO Floorboard Ba01.
Section 5.0 Basements Wall insulated externally Product: Polyfoam ECO Ba01 Wall insulated internally Product: Polyfoam ECO Ba02 Basements Basements Basement design Waterproofing BS 8102: 2009 Code of practice
Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM
P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 2 below and above ground V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V The flexible, fast and cost-effective answer
Please read the entire document before purchasing and installing any of these products
Please read the entire document before purchasing and installing any of these products USA SBS UNDERLAYMENT ROOFING UNDERLAYMENT SBS Mineral Surfaced MINERAL SURFACE CAP SHEET Ice and Water Protection
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)
NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology CONCRETE MASONRY FOUNDATION WALL DETAILS TEK 5-3A Details (2003) Keywords:
RIW STRUCTURESEAL. Structureseal is a highly effective waterproofing composite, of high strength green coloured geotextile, and sodium bentonite.
CI/SfB Tr9 L1415 November 2013 RIW STRUCTURESEAL is a highly effective waterproofing composite, of high strength green coloured geotextile, and sodium bentonite. BENEFITS l Pre-applied tanking systems
SIKA TANKING MEMBRANES SIKAPROOF A MEMBRANES
Sika Limited Watchmead Welwyn Garden City Hertfordshire AL7 1BQ Tel: 01707 394 444 Fax: 01707 329 129 e-mail: [email protected] website: www.sika.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL
SIKABIT W-15 WET-BONDED WATERPROOFING MEMBRANE
SIKABIT W-15 WET-BONDED WATERPROOFING MEMBRANE BASEMENT WATERPROOFING INTRODUCTION Many different products are available for basement waterproofing. Considering ideal jobsite conditions (perfect substrate
WATERPROOFING BASEMENTS
WATERPROOFING BASEMENTS CONSTRUCTION CHEMICALS DIVISION Pidilite manufactures and markets a wide range of construction chemical products under two brands Dr. Fixit & Roff covering different aspects of
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
Improving the flood resistance of your home. Advice sheet 6: Flood-resilient floors
Improving the flood resistance of your home Advice sheet 6: Flood-resilient This sheet provides guidance on identifying different types of floor, assessing the routes floodwater may enter, and describes
CHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
Monarflex Tanking & DPM Systems. Cold and Hot. Applied. Structural. Waterproofing. Membranes YEAR. Geomembr nes WORLD LEADER IN WATERPROOFING
Monarflex Tanking & DPM Systems CI/SfB 27.2 May 2005 N6 Cold and Hot Applied Structural Waterproofing Membranes 20 YEAR STRUCTUAL WATERPROOFING GUARANTEE Exclusively Supplied and Installed by WORLD LEADER
A. This Section includes rubberized asphalt sheet membrane waterproofing systems.
SECTION 07110 SHEET MEMBRANE WATERPROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
Tunnels & Arches OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM
P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 5 Tunnels & Arches V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V Create dry usable space with the original X pattern
Soils, Foundations & Moisture Control
Soils, Foundations & Moisture Control Soil The top loose layer mineral and/or organic material on the surface of the Earth that serves as a natural medium for the growth of plants and support for the foundations
ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057. Lecturer: Jim Cahill
ARCHITECTURAL TECHNOLGY 4 ADVANCED CONSTRUCTION TECHNOLOGY BASEMENT CONSTRUCTION YEAR 3 SEMESTER 1 AIDAN WALSH R00060057 Lecturer: Jim Cahill 29 th November 2011 TABLE OF CONTENTS SUMMARY 1 MAIN BODY SECTION
METHOD STATEMENT 006 TORCH APPLIED MEMBRANE TO BASEMENT WALLS
This Document is designed to cover best practice installation procedures for a one layer torch applied sheet membrane system to basement walls. PRELIMINARY WORK Ensure that all surface preparation work,
Ground Gas Barriers. www.tritonsystems.co.uk
Minimum 2 Coats Triton TTVM 0.5l/m² 1st Coat 0.7l/m² 2nd Coat 3 Coats Triton TTVM Incorporating GRM MSSM to Joints Triton Fillet Seal 25mm x 25mm Minimum Construction Joint Ground Gas Barriers n HDPE/PP
EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES
Building and Construction Industry A joint industry initiative produced by BSA Supershow logo.indd 1 30/01/2008 9:43:29 AM EXTERNAL WATERPROOFING MEMBRANES BEST PRACTICE GUIDELINES FAILING WATERPROOFING
INTERIM ADVICE NOTE 96 /07 Revision 1 GUIDANCE ON IMPLEMENTING RESULTS OF RESEARCH ON BRIDGE DECK WATERPROOFING
Interim Advice Note 96/07 INTERIM ADVICE NOTE 96 /07 Revision 1 GUIDANCE ON IMPLEMENTING RESULTS OF RESEARCH ON BRIDGE DECK WATERPROOFING Summary This interim advice note provides guidance on improving
Issue of the Guidelines on Prevention of Water Seepage in New Buildings
graphic: Buildings Department Your REF 來 函 檔 號 :. OUR REF 本 處 檔 號 :.BD GR/1-55/173 FAX 圖 文 傳 真 :..28400451 TEL 電 話 :..2626 1717 www.info.gov.hk/bd To : All Authorized Persons 7 March 2005 Registered Structural
Construction. Pre-Bagged Structural Waterproofing System. Product Description. Product Data. Tests. Form
Construction Product Data Sheet Edition 15/07/2013 Identification no: 01 07 05 04 001 0 000001 Sika 1 Pre-Bagged Structural Waterproofing System Product Description Pre-Bagged Structural Waterproofing
INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles
INSTALLATION RECOMMENDATIONS Outdoor Rubber Tiles Prior to Installation: The Outdoor Rubber Tiles and accessory transition pieces intended for this installation have been shipped to you via a freight carrier
Wastewater Capital Projects Management Standard Construction Specification
CITY AND COUNTY OF DENVER ENGINEERING DIVISION Wastewater Capital Projects Management Standard Construction Specification 10.1 Precast Concrete Pipe 10.1.1 General This section covers material requirements,
The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs
The better way to build TM Installation Manual FOUNDATION SIPs & FROST WALLS SIPs February 2016 PWF FOUNDATION & FROST WALL SIPs Installation Manual Table of Contents Topics General Requirements...................................
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single
Simplifying design and construction. Alan Tovey, Director The Basement Information Centre
Simplifying design and construction Alan Tovey, Director The Basement Information Centre Simplifying design and construction Grades of construction Construction options Design and waterproofing issues
BELOW GROUND TANKING
BELOW GROUND TANKING Basement & Foundation Waterproofing Systems - What, Why & How By Paul Evans MBAV Specialist Contractor, Registered Building Practitioner Vice President Australian Institute of Waterproofing
Secondary Containment Comparison ATI Ultra COAT vs HDPE
When choosing a secondary containment system it must be chosen based on its ability to withstand long term contact with the natural elements (weather), whatever the tanks hold (unrefined oil, fuels, acids,
Grace Waterproofing Systems
Product data updates tech letters details contact Grace Construction Products Grace Waterproofing Systems Contractor s Handbook July 2013 www.graceconstruction.com P P A ROJECT POINTERS...4 RODUCT LISTING...8
Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing
1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries
Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries Introduction Wastewater of petrochemical industries and refineries contains high amounts of emulsified aliphatic or
LAYING BLOCK AND BRICK
LAYING BLOCK AND BRICK Products highlighted in this section: SAKRETE Type N Mortar Mix SAKRETE Type S Mortar Mix Brick And Block Laying Basics The first step in building a brick or block wall is to construct
DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H
DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H Soil Drainage Mat with Built-In Protection Layer POLYGUARD DRAINAGE MATS are three-part prefabricated geocomposite drain consisting of a
Chapter 5.4. Waterproofing of basements and other below ground structures
Chapter Waterproofing of basements and other below ground structures Waterproofing of basements and other below ground structures CONTENTS SCOPE DESIGN Clause Page D1 Design standards D1 2 D2 Statutory
Knauf Aquapanel Interior. Tile Backing. Cement board for wet areas. Will not deteriorate in water. Easy to score and snap
Tile Backing Will not deteriorate in water Easy to score and snap Resistant to mould and mildew Knauf Aquapanel Interior Cement board for wet areas Knauf Aquapanel Interior Cement Board Drywall for Wet
Gas Membrane and Waterproof Tanking Systems
Gas Membrane and Waterproof Tanking Systems Improving Choice, Quality & Service Why Choose Miers? About Miers Miers Construction Products is an independent supplier of construction products delivering
Including. Rubershield-Pro. Breather Membrane
Including RubershieldPro Breather Membrane 2 Ruberoid produces a wide range of underslating membranes, primarily to be installed below tiles, slates or metal roofing providing a secondary barrier against
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
System 5000 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY
CI/SfB Oct 12 (47) Ln Uniclass L524 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY Bailey Flame-free felt roofing Bailey
State of Connecticut Department of Public Health RADON PROGRAM
State of Connecticut Department of Public Health RADON PROGRAM Scope The Connecticut Department of Public Health (DPH) Radon Program is providing this information for contractors who decide to build radon
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 16 BRIDGE DECK WATERPROOFING. 16.1 General...16-1. 16.2 Materials...16-1. 16.3 Equipment...
SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 16 BRIDGE DECK WATERPROOFING TABLE OF CONTENTS 16.1 General...16-1 16.2 Materials...16-1 16.3 Equipment...16-1 16.4 Installation...16-2 16.4.1 Traffic Restrictions...16-2
The assessment is described in the following pages which form integral parts of this certificate, which should be read in its entirety.
Cl/SfB (13.1) Ly (L2) BRE CERTIFICATION LTD CERTIFICATE OF ASSESSMENT PRODUCT Powerbase RB 340 and RB 370 Radon Resistant Membranes CERTICATE NO. 100/03 ISSUED: MARCH 03 REISSUED: NOVEMBER 07 SUPPLIED
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS
AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings
HYLINER AKS HDPE LINING
HYLINER AKS HDPE LINING FOR CONCRETE PIPE Manufactured from HDPE Available in white and black Sheets up to 3 m width D1.12 HyLiner AKS HDPE Lining for Concrete Pipe October 2013 0800 WE PIPE (93 7473)
ELASTOCEM. Technical features. Applications. Two-component flexible, waterproofing and protective cementitious grout.
Two-component flexible, waterproofing and protective cementitious grout. 1504-2 PI-MC-IR Technical features Two-component grout, based on cements, selected aggregates, special additives and synthetic polymers
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
Permeable Pavement Construction Guide
Permeable Pavement Construction Guide Permeable pavement at Olympic Park, Waitakere Final Construction result What are permeable pavements? Permeable pavements are hard surface paving systems that reduce
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
SPECIAL COMPOUND FOR RHEOPLASTIC AND ANTI-CORROSION SUPERCONCRETE WITH VERY HIGH DURABILITY
BS 40 M6 MuCis mono SPECIAL COMPOUND FOR RHEOPLASTIC AND ANTI-CORROSION SUPERCONCRETE WITH VERY HIGH DURABILITY LE CE LE type: "expansive binder which allows the production of extremely fluid concrete
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
Design and Construction of Cantilevered Reinforced Concrete Structures
Buildings Department Practice Note for Authorized Persons, Registered Structural Engineers and Registered Geotechnical Engineers APP-68 Design and Construction of Cantilevered Reinforced Concrete Structures
CertainTeed. Self-Adhering Roof Systems for Low Slope Residential Roofs
CertainTeed Self-Adhering Roof Systems for Low Slope Residential Roofs Goes down fast. Stays on strong. Flintlastic SA performs in all the right ways. What s more important to you? Speed of installation,
WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.
WET/DAMP BASEMENTS PROBLEM. IS THIS BASEMENT LEAKING OR COULD WE HAVE ANOTHER PROBLEM? Water line arching up on wall in corners of basement. Water collecting on concrete floor starting in corners. ANSWER:
HIGHWAYS DEPARTMENT GUIDANCE NOTES ON THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE DECKS
HIGHWAYS DEPARTMENT GUIDANCE NOTES ON THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE DECKS Research & Development Division RD/GN/033 June 2008 THE USE OF WATERPROOFING MEMBRANES ON CONCRETE BRIDGE
The Optimum Basement Wall
The Optimum Basement Wall Solutions to the Wet Blanket Basement Problem February 27 th, 2014 1 Adapting to Change! We ve made significant advances in water management. Customers no longer accept that musty
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150
THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150 SECTION ONE A. Objective The objective of this guide is to provide Owners and General Contractors/Construction
Installation PowerPoint for Grasscrete Formers
Installation PowerPoint for Grasscrete Formers 1 This document describes the two single-use tools utilized to create the Grasscrete product. The original Former is a vacuum formed light gauge plastic mold
Division 9. SignaFlor Pad and Pour Flooring System
Division 9 SignaFlor Pad and Pour Flooring System SPECIFICATIONS Page 1. General... 2 1.1 Description 2 1.2 Quality Assurance 2 1.3 Submittals 2 1.4 Delivery and Storage 3 1.5 Warranty 3 1.6 Working Conditions
Uniclass L31:N14:P7111 C1/SfB (16.9) Rn7 (J4) February 2008. Foundation Heave Protection
Uniclass L31:N14:P7111 C1/SfB (16.9) Rn7 (J4) February 2008 Foundation Heave Protection The safe, sure way to provide foundation protection Clayshield is the proven solution to protecting foundations against
MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS
MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS May 29, 2013 Revision B Structural Guideline for Design and Installation Holes in Composite Floor Slab Terminal 3, Departure Level
How To Test A Wrap N Drain X Dampproofing System
National Research Council Canada Institute for Research in Construction Conseil national de recherches Canada Institut de recherche en construction CCMC 13094-R &&0& EVALUATION DIVISION 07111 REPORT Issued
Chapter. Restoration of Damaged Structures
5 Chapter Restoration of Damaged Structures Bringing back a damaged structure to its pre-earthquake state and original strength is called restoration. This is the first step of building rehabilitation.
DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP
DIY GUIDE 10 EASY STEPS FOR TREATMENT OF RISING DAMP CONTENTS WHAT IS RISING DAMP STEP 1 SURVEY STEP 2 METER READINGS STEP 3 CONCLUSION STEP 4 PREPARATION FOR TREATMENT STEP 5 TYPE OF TREATMENT STEP 6
Although we do a fair amount of residential roofing, my family s breadand-butter. Installing a. Sealants aren t universal
Installing a Low-Slope Exposed EPDM for roof transition Exposed EPDM for resistance to ice damming Sidewall flashing Done with care, a flat roof can provide 0 years or more of leak-free service Gravel
The AQUAFIN Approach to Concrete Repair
Concrete Repair Building Product Systems Waterproofing & Concrete Restoration Decorative Coatings Moisture Vapor Remediation & Flooring Injection Grouting The AQUAFIN Approach to Concrete Repair www.aquafin.net
Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5. 1. Purpose
Document type: Practice Note Title: External and internal membranes Document number: AC2234 Version: 5 1. Purpose The purpose of this practice note is to address the incidence of deck and roof membrane
SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION
SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION 1. SCOPE Pipe subsoil drains shall be constructed in accordance with this specification and in conformity with the lines, grades and cross-sections shown
Ubiflex. Non-lead flashing system
Ubiflex Non-lead flashing system Ubiflex non-lead flashing Ubiflex is a non-lead waterproof flashing material which can be used in most applications where lead is traditionally used to provide a weatherproof
Guidelines for Durable Driveways, Carports Patios, Walks, Garage Floors
Guidelines for Durable Driveways, Carports Patios, Walks, Garage Floors The Right Concrete Mix Placing and Finishing Joints Correctly Spaced Curing for Durability "Concrete durability is the ability to
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the
BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS.
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET USE OF BREATHABLE ROOFING FELTS. Last updated 16/11/2010 Page 1 of 6 PURPOSE: This Guidance
WATERPROOFING OF WET ROOMS
WATERPROOFING OF WET ROOMS Waterproofing under tiles For longterm enjoyment of a wetroom area a complete and resistant waterproofing system is an important precondition. Most tiles are by themselves waterproof