ReadySET Aspirating Smoke Detection System Installers Handbook
|
|
|
- Poppy Wilcox
- 10 years ago
- Views:
Transcription
1 ReadySET Aspirating Smoke Detection System Installers Handbook P/N REV 03 ISS 19JUN12
2 Copyright Manufacturer Contact information 2012 UTC Fire & Security. All rights reserved. Kidde Products Limited Unit 2 Blair Way Dawdon City: Seaham, County Durham SR7 7PP United Kingdom Telephone: +44 (0) Fax: +44 (0) For contact information, see
3 Content Important information ii Chapter 1 Introduction 1 About this manual 2 Intended audience 2 Aspirating smoke detection system limitations 3 Chapter 2 Product description 5 Introduction 6 Features 6 Specifications 7 Indicators 8 Inside the detector 9 Chapter 3 Installation and configuration 11 Introduction 12 Antistatic precautions 12 System design 13 Installation 19 Chapter 4 Commissioning 29 Introduction 30 Precommissioning preparation 30 Commissioning checklist 30 Chapter 5 Troubleshooting 33 Troubleshooting 34 Chapter 6 Maintenance 37 Introduction 38 Scheduled maintenance 38 Maintenance procedures 38 Appendix A Communications card 43 Optional communications card 44 Glossary 47 Index 49 ReadySET Aspirating Smoke Detection System Installers Handbook i
4 Important information Regulatory information This product has been designed to meet the requirements of NFPA 72 National Fire Alarm Code, UL 864 Standard for Control Units for Fire Protective Signaling Systems, UL 268 Smoke Detectors for Fire Alarm Signaling Systems, UL 268A Smoke Detectors for Duct Application, and ULC S527 Standard for Control Units for Fire Alarm Systems. Limitation of liability To the maximum extent permitted by applicable law, in no event will UTCFS be liable for any lost profits or business opportunities, loss of use, business interruption, loss of data, or any other indirect, special, incidental, or consequential damages under any theory of liability, whether based in contract, tort, negligence, product liability, or otherwise. Because some jurisdictions do not allow the exclusion or limitation of liability for consequential or incidental damages the preceding limitation may not apply to you. In any event the total liability of UTCFS shall not exceed the purchase price of the product. The foregoing limitation will apply to the maximum extent permitted by applicable law, regardless of whether UTCFS has been advised of the possibility of such damages and regardless of whether any remedy fails of its essential purpose. Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory. While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, UTCFS assumes no responsibility for errors or omissions. Only qualified persons experienced, trained and certified in the installation of this equipment should design, service, maintain, test, install, and configure the ReadySET. They must be familiar and experienced with the wiring diagrams and components, electrical installation, and familiar not only with NEC, relevant NFPA and local codes but also trained and qualified by the manufacturer and/or its associated operating companies. The manufacturer of the components that make up the ReadySET detector is not responsible for its configuration or installation of the product. It is the responsibility of the professional installer (described above) to properly install, configure and test the systems. Under no circumstances will the manufacturer be liable for improper installation, maintenance, servicing, testing or configuration of the systems. ii ReadySET Aspirating Smoke Detection System Installers Handbook
5 The technical data contained herein is provided for informational purposes only and should not be used as a substitute for professional judgment and training. Although the manufacturer believes this information to be true and correct, it is published and presented without any guarantee or warranty whatsoever. The manufacturer disclaims any liability for any use of the data other than as set out in this manual. Advisory messages Advisory messages alert you to conditions or practices that can cause unwanted results. The advisory messages used in this document are shown and described below. WARNING: Warning messages advise you of hazards that could result in injury or loss of life. They tell you which actions to take or to avoid in order to prevent the injury or loss of life. Caution: Caution messages advise you of possible equipment damage. They tell you which actions to take or to avoid in order to prevent the damage. Note: Note messages advise you of the possible loss of time or effort. They describe how to avoid the loss. Notes are also used to point out important information that you should read. Product Symbols This symbol appears on the main board of the unit and indicates that the board contains static sensitive components. This label is located on the laser chamber at the bottom right of the open detector and signifies that the unit is a Class 1 Laser product as specified in IEC The unit incorporates a Class 3B embedded laser which must not be removed from the detector, as retinal damage may result if the laser beam enters the eye. This symbol indicates the safety ground studs. These are for grounding cable screens, etc., and should not be connected to 0V or signal earth. ReadySET Aspirating Smoke Detection System Installers Handbook iii
6 Safety summary This entire manual must be read and understood before installation. Installation precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING: Several different sources of power can be connected to this detector. Disconnect all sources of power before servicing. The control unit and associated equipment may be damaged by servicing while the unit is energized. Do not attempt to install, service, or operate this control unit until this manual is read and understood. Cautions System Reacceptance Test after Reprogramming: To ensure proper system operation, this system must be retested in accordance with NFPA 72 Chapter 10 after any programming change. Reacceptance testing is also required after any addition or deletion of system components, and after any modification, repair, or adjustment to system hardware or wiring. All components, circuits, and system operations known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices in a single installation that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified, in accordance with NFPA. This system meets FM and UL 268 requirements for operation at 32 to 100 F (0 to 38 C) and at a relative humidity of 90% (noncondensing) at 90 F (32.2 C). However, the useful life of the system s standby batteries and the electronic components may be adversely affected by continuous operation at these environmental limits. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 60 to 80 F (15 to 27 C). Like all solid-state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. This manual gives information likely to be needed for most installations, but for more detailed information on pipe networks, please refer to the PipeCAD System Design and Installation User Manual. WARNING: The use of overhead or outside aerial wiring is not recommended due to the increased susceptibility to nearby lightning strikes. Consult with the Technical Support department if any problems are anticipated or encountered. iv ReadySET Aspirating Smoke Detection System Installers Handbook
7 Do not install electronic assemblies prior to mounting and attaching conduit for field wiring to the enclosure. Before making modifications, verify that they will not interfere with battery and printed circuit board locations. Do not overtighten screw terminals. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the control unit. Follow the instructions in this manual. These instructions must be followed to avoid damage to the control unit and associated equipment. System operation and reliability depend upon proper installation. Caution: While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for insurance. An automatic fire alarm system or components of a system smoke detectors, heat detectors, manual pull stations, notification appliances, and a fire alarm control unit with remote-notification capability can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. General precautions The following general safety precautions are to be observed at all times. All electrical components associated with equipment should be installed and grounded in accordance with NEC and local regulatory requirements. Special precautionary measures are essential to prevent applying power to equipment at any time maintenance work is in progress. Before working on electrical equipment, use a voltmeter to ensure that the system is not energized. When working near electricity, do not use metal rulers, flashlights, metallic pencils, or any other objects having exposed conductive material. When connecting a meter to terminals for measurement, use a voltage range higher than expected voltage to be measured. ReadySET Aspirating Smoke Detection System Installers Handbook v
8 vi ReadySET Aspirating Smoke Detection System Installers Handbook
9 Chapter 1 Introduction Summary This chapter provides information about this manual. Content About this manual 2 Intended audience 2 Aspirating smoke detection system limitations 3 ReadySET Aspirating Smoke Detection System Installers Handbook 1
10 Chapter 1: Introduction About this manual This manual provides information on how to install, configure, maintain, and operate the ReadySET Aspirating Smoke Detector. It is organized as follows. Chapter 1, Introduction: Provides information about this manual. Chapter 2, Product description: Provides technical descriptions of the detector and its operation. It also provides descriptions of the indicators. Chapter 3, Installation and configuration: Provides instructions for design and installation of the ReadySET Aspirating Smoke Detection System. Chapter 4, Commissioning: Provides procedures for commissioning the ReadySET detector. Chapter 5, Troubleshooting: Provides troubleshooting steps. Chapter 6, Maintenance: Provides scheduled and unscheduled maintenance procedures. Appendix A, Communications card: Provides installation information for the optional communications card. Intended audience This manual is to be used by qualified and factory-trained personnel, knowledgeable of NFPA standards and any other applicable standards in effect, and is intended to provide guidance to qualified technical professionals for the installation, operation, testing, and maintenance of the ReadySET Air Sampling Detector, referred to in this manual as the ReadySET or the detector. 2 ReadySET Aspirating Smoke Detection System Installers Handbook
11 Chapter 1: Introduction Aspirating smoke detection system limitations An Aspirating smoke detection system which can be made up of smoke detectors, heat detectors, manual pull stations, notification appliances, and a fire alarm control unit with remote-notification capability can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Any fire alarm system may fail for a variety of reasons. The following are only examples: Smoke detectors may not sense fire where smoke cannot reach the detectors, such as in chimneys, in walls, on roofs, or on the other side of closed doors. Smoke detectors on one level also may not sense a fire on another level or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire. All types of smoke detectors ionization, photoelectric and air aspirating have sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards such as smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Notification appliances, such as bells, may not alert people if these appliances are located on the other side of closed or partly open doors, or are located on another floor of a building. A fire alarm system will not operate without electrical power. If AC power fails, the system will operate from standby batteries only for a limited time. Auxiliary Equipment used in the system may not be technically compatible with the control unit. It is essential to use only equipment listed for service with your control unit. Telephone lines needed to transmit alarm signals from the protected site to a central monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions is inadequate maintenance. All devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection and testing should be scheduled monthly or as required by national and/or local fire codes and standards. Adequate written records of all inspections should be kept. ReadySET Aspirating Smoke Detection System Installers Handbook 3
12 Chapter 1: Introduction 4 ReadySET Aspirating Smoke Detection System Installers Handbook
13 Chapter 2 Product description Summary This chapter provides descriptions of the detector features, specifications, and controls and indicators. Content Introduction 6 Features 6 Specifications 7 Indicators 8 Inside the detector 9 ReadySET Aspirating Smoke Detection System Installers Handbook 5
14 Chapter 2: Product description Introduction The ReadySET detector is a highly sophisticated next generation aspirating smoke detection product that provides early detection and warning of smoke. Designed for easy installation and commissioning, the ReadySET incorporates a patented artificial intelligence known as ClassiFire, which allows the detector to configure itself to optimum sensitivity, alarm thresholds, and minimum nuisance alarms for various environments. The ReadySET detector can monitor an area of up to 2,500 sq. ft. (232 sq. m). The ReadySET detector is a smoke detector intended to provide localized fire detection. It is suitable for use in a wide range of applications, such as small noncompartmentalized rooms, warehouse racking, or pieces of electronic or electromechanical equipment where it is desirable to achieve individual fire reporting. In compartmentalized rooms, each compartment would normally use individual detectors. The ReadySET detector operates by drawing air from a protected space via a supervised piping network in relatively small areas. The sampled air is passed through a "dust separator" to remove dust and dirt before entering the laser detection chamber. Sophisticated, state-of-the-art electronics are used to analyze the sampled air and generate a signal representing the level of smoke present. ClassiFire intelligence also monitors the detector chamber and dust separator (filter) for contamination, continually adjusting the appropriate operating parameters to counteract the negative effects of any contamination. The ReadySET detector is unique in being able to provide a consistent level of protection in a very wide range of environments by continuously making minor adjustments to sensitivity. The ReadySET can easily be installed without any specialized tools or software. An optional communications card can be fitted inside the ReadySET detector to provide an RS-232 serial port and RS-485 network communication. There is also a ReadySET model that is shipped with the communications card factory installed. Refer to Appendix A Communications card on page 43. Features The following is a list of major features of the ReadySET detector: Patented artificial intelligence known as ClassiFire (automatically learns environment) Laser dust discrimination (LDD) Quick and easy installation Self-adjusting between the range of 0.4% and 2.0% obscuration Pre-engineered sampling pipe network designs Up to 2,500 sq. ft. (232 sq. m) area coverage 6 ReadySET Aspirating Smoke Detection System Installers Handbook
15 Chapter 2: Product description Specifications Caution: This equipment is only to be used in accordance with this specification. Failure to operate the equipment as specified may cause damage to the unit, injury, or property damage. Specification Supply voltage Current consumption Dimensions Weight Operating temperature range Operating humidity range Value VDC 350 ma 7.5 W x 9.0 H 4.3 D (in.) 190 W 230 H 110 D (mm) 2.65 lbs. (1.2 kg) 32 to 100 F (0 to 38 C) (UL 268 compliance) 0 to 90% noncondensing Coverage area 2,500 sq. ft. (232 sq. m) Sensitivity range (%obs/ft.) (%obs/m) Maximum sensitivity resolution Preengineered piping sample hole Detection principle Particle sensitivity range Relay contact rating Sampling pipe inlets 1 Sampling pipe internal diameter Relay outputs Chamber service intervals Dust separator (filter) replacement intervals Laser lifetime (MTTF) Programming APIC compatible Enclosure Min. = 7.62%, Max. = 0.122% FSD Min. = 25%, Max. = 0.4% FSD 0.12% obs/ft. (0.4% obs/m) 0.5% to 1.5% obs/ft. (1.64% to 4.92% obs/m) Laser light scattering mass detection tm to 10tm 1 A at 24 VDC resistive load 3/4-inch (20 mm) Alarm, Pre-Alarm, and Fault Greater than 8 years (depending on environment) Greater than 5 years (depending on environment) Greater than 1,000 years Internal DIP switches Yes NEMA-1 ReadySET Aspirating Smoke Detection System Installers Handbook 7
16 Chapter 2: Product description Indicators Figure 1 below shows the seven indicators on a ReadySET detector. Figure 1: ReadySET detector indicators (1) ALARM: Illuminates to indicate that the smoke level has passed the detector s Fire 1 threshold, and the normally open ALARM relay contacts have closed. (2) PRE-ALARM: Illuminates to indicate that the smoke level has passed the detector s Pre-Alarm threshold, and the normally open PRE-ALARM relay contacts have closed. (3) FAULT: Illuminates to indicate a fault condition and that the normally closed FAULT relay contacts have opened. Three additional LEDs indicate the type of fault. (4) OK: Illuminates to show normal operation when there are no faults. The OK lamp will flash during the 15-minute FastLearn period when the detector is first learning about its environment. Note: During initial setup, the OK LED will flash for 15 minutes while the detector learns its operating environment. This does not indicate a problem with the detector. 8 ReadySET Aspirating Smoke Detection System Installers Handbook
17 Chapter 2: Product description (5) FLOW: Illuminates to indicate an airflow fault. This may be due to blocked or broken pipes, although it can also occur if, for example, factory warehouse doors are opened on a windy day, a large pressure change occurs, or if industrial air conditioning turns on. Another possible cause is that the aspiration fan connection cable is damaged or disconnected. (6) FILTER: Illuminates to indicate that the detector s filter needs to be changed. (7) HEAD: Illuminates to indicate a problem with the detector laser chamber, as might be caused by the laser head connecting cable being damaged or disconnected. It can also be caused by certain kinds of internal system faults, which appear in the detector s event log as process errors. Note: If the FAULT LED is illuminated but none of the additional LEDs are lit, it indicates a problem with the power supply if its fault output is connected to the detector s INPUT terminals. Inside the detector Figure 2 below shows the main interior parts of a detector with the cover off. Figure 2: ReadySET internal components (1) Two holes for conduit connection. There are two 3/4 in. drilling guides provided on the top of the detector and one on the bottom providing holes for conduit. (2) Pipe entries provide a connection for 3/4-inch pipe. A 3/4 in. male to 25 mm female adapter is required when using larger than 1 inch (27 mm) O.D. pipe. Note: Do not glue pipes into the detector to allow for future removal. (3) Aspirating fan connector lead: If this lead is broken or not connected, the fan will not turn and the detector will indicate a FLOW fault. (4) Main PCB: No user-serviceable parts. ReadySET Aspirating Smoke Detection System Installers Handbook 9
18 Chapter 2: Product description Note: The PCB is fixed in place with 5 M3 x 6 screws. The detector should not be operated with any of the screws missing, as this could cause air leaks and unreliable operation. (5) Power supply connection terminals (6) Volt-free relay contact terminals (7) Configuration DIP switch: Used to configure user-selectable detector functions. (8) Input switch terminals (9) Optional communication terminals: used when the optional communication card is fitted to connect the RS-485 network (10) Detector head ribbon connector: If this lead is broken or not connected, the detector will indicate a HEAD Fault. (11) Detector head assembly: No user-serviceable parts. Do not remove this from the detector, due to the risk of exposure to the laser. (12) Detector head cover plate: This protects the laser head. The plate should not be removed from the detector. (13) Replaceable dust separator: This simply slides in and out of its mounting. The separator and its replacement have IN written in red on one side, and OUT on the other to indicate correct orientation. (14) Three mounting holes to mount the detector. Use #10-24 pan-head screws for mounting. Note: Ensure that the detector is fixed to a flat surface so that the enclosure will not twist and become damaged. 10 ReadySET Aspirating Smoke Detection System Installers Handbook
19 Chapter 3 Installation and configuration Summary This chapter provides information necessary to install the ReadySET detector system. Content Introduction 12 Antistatic precautions 12 System design 13 Sample pipe networks 14 Air handling unit installation 15 Below/above the ceiling installation 15 Return air duct sampling method 17 Return air grill sampling method 18 Installation 19 Installation guidelines 19 Removing the front cover 20 Mechanical installation 21 Electrical installation 21 Configuration 25 Final installation 28 Removing the detector 28 ReadySET Aspirating Smoke Detection System Installers Handbook 11
20 Chapter 3: Installation and configuration Introduction This chapter provides information necessary to install the ReadySET detector system. Installation consists of the following steps: 1. Unpack the shipping carton. Ensure that the package contains product literature, one ferrite ring, and the detector. 2. Determine the optimum location for the detector. 3. Mount the detector at the selected location. 4. Connect the detector to the sampling pipe network. Installation should only be done by factory-trained technicians in accordance with applicable installation requirements. These include: NFPA 70, National Electrical Code NFPA 72, National Fire Alarm and Signaling Code Any other local, national, or installation requirements or standards. Note: Power should be turned off during installation. Antistatic precautions This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits. Caution: When handling any electric components or printed circuit boards, antistatic precautions must be followed. Failure to do so may result in component damage. Static discharge can be reduced by adhering to the following guidelines: Always use conductive or antistatic containers for transportation and storage, if returning any item. Wear a wrist strap while handling devices and ensure that a good ground is maintained throughout the installation process. Never subject a static sensitive device to sliding movement over an ungrounded surface and avoid any direct contact with the pins or connections. Avoid placing sensitive devices onto plastic or vinyl surfaces. Minimize the handling of sensitive devices and printed circuit boards (PCBs). 12 ReadySET Aspirating Smoke Detection System Installers Handbook
21 Chapter 3: Installation and configuration System design Pre-engineered piping designs simplify the installation of the detector pipe network. The following criteria ensure that the airflow and transport times are within the design of the detector. The design parameters listed below must be adhered to for all preengineered pipe designs. Pre-engineered piping networks should not exceed the transport time requirement of 120 seconds. During the system test, transport times are often less than 55 seconds. The maximum of three elbows and one pipe tee can be used in any pipe network design. When using a pipe tee, it must be located within 20 feet of pipe from the detector. All capillary tubes will have a maximum length of 3 feet and use a 9/64 inch sampling hole size. The first sampling hole must be 10 feet or more from the detector. The use of sampling capillary tubes and sampling holes can be mixed in any combination on the pipe network. On branch designs, the same number of sampling holes must be used on each branch. Table 1: Sample pipe network parameters Total pipe length Max amount elbows Max sampling points Sampling hole size Capillary tube sample hole size End cap hole 164 feet /8 inch 9/64 inch 5/32 inch Note: PipeCAD pipe modeling software is used to design pipe networks outside the above parameters. Refer to the PipeCAD System Design and Installation User Manual for complete instructions. The ReadySET detector employs a fan designed to detect smoke in relatively small areas. The ReadySET detector is not intended to protect large areas, or to sample from areas where there may be any difference in airflow rates or pressure differentials. If detection in environments conforming to these descriptions is required, other AIR- Intelligence products should be used. Always locate the sampling points in positions to which smoke may reasonably be expected to travel. It is usually better to locate the sampling pipe directly in the airflow (for example, across the return air register of an air conditioning unit). Note: There is no substitute for carrying out smoke tests prior to installation of pipework to indicate suitable sampling point location. ReadySET Aspirating Smoke Detection System Installers Handbook 13
22 Chapter 3: Installation and configuration Sample pipe networks Simple designs with short sampling pipes produce the best results. Maximum allowed sampling pipe length is 164 feet (50 meters) in still air. In areas or applications where the external airflow rate is greater than 3 feet per second (1 meter per second), the maximum sampling pipe length is reduced to 33 feet (10 meters). Figure 3: Sample pipe network 10 ft. or greater Single pipe sampling network ReadySET detector Two branched pipe sampling network 10 ft. or greater ReadySET detector 14 ReadySET Aspirating Smoke Detection System Installers Handbook
23 Chapter 3: Installation and configuration Air handling unit installation No more than one air handling unit may be protected with one ReadySET detector. In this application, ensure that the sampling pipe is raised clear of high velocity air in the immediate vicinity of the air intake grill on standoff posts as shown in Figure 4 below. Figure 4: Air handling unit in vicinity of the ReadySET detector (exhaust pipes not shown for clarity) Sampling pipe Incorrect Detector Standoff post Sampling pipe Direction of smoke AHU Detector Correct Equipment cabinet Below/above the ceiling installation The ReadySET detector is supplied with an exhaust port (see Figure 2 on page 9). This allows the ReadySET detector to sample from areas which may be at different air pressure than the detector location. Typical uses are for air-duct sampling and allowing the installation of the detector in under-floor or ceiling voids or when sampling from pieces of computer related equipment. See Figure 5 on page 16 and Figure 6 on page 16. ReadySET Aspirating Smoke Detection System Installers Handbook 15
24 Chapter 3: Installation and configuration Figure 5: Installation of pipework above ceiling with exposed detector (piped exhaust) Sampling pipe Exhaust pipe Sampling hole False ceiling Detector Figure 6: Installation with detector mounted in ceiling void (no exhaust piping) Sampling hole Sampling pipe False ceiling Detector 16 ReadySET Aspirating Smoke Detection System Installers Handbook
25 Chapter 3: Installation and configuration Return air duct sampling method Duct sampling generally is the most cost-effective method of air sampling because the pipe runs are minimal and a single detector may be used to cover a larger area. The speed of response of the detector to smoke is given by the exchange rate in the rooms ventilated by the duct ventilation system. This tends to be rapid, giving early warning of any smoke present. This type of sampling is particularly suited to aspirated smoke detection, since the smoke content in the air will tend to be diluted to a level below that of point type detectors. Also, the relatively high airflow in the duct reduces the effectiveness of point-detection devices. The duct sampling method does have one major disadvantage. If the ventilation becomes inoperative, the air-flow through the duct system ceases and the smokedetection system becomes ineffective. Figure 7: Return air duct sampling Figure 7 above shows a typical sampling pipe arrangement for an air duct. The right pipe is the sampling pipe and the holes on it are drilled 4 inches apart and face into the oncoming air stream. The left pipe exhausts air from the detector. The detector is UL 268A and ULC approved for duct applications with an operating air velocity range of 300 to 4,000 ft/min ( m/sec). The following guidelines apply. Only one duct can be monitored per detector. ReadySET Aspirating Smoke Detection System Installers Handbook 17
26 Chapter 3: Installation and configuration If the sampling pipe system and ReadySET detector is used as the primary smoke detection system, methods should be employed to notify stoppage of airflow in the duct(s). The exhaust air from the detector must be returned back to the duct using an exhaust-port adapter and associated piping. This requirement assures positive airflow through the detector. Locate sampling pipe in the main supply duct return side, downstream of the filters and a minimum of six duct widths from any source of turbulence (such as bends, inlets, or deflection plates) to reduce the effects of stratification. In installations where the filter is capable of removing smoke, install the sampling tube upstream of the filter. Note: Where it is physically impossible to locate the sampling pipe in accordance with this guideline, the sampling pipe may be positioned closer than six duct widths, but as far as possible from inlets, bends, or deflection plates. Locate the sampling pipe such that dampers do not restrict airflow at the sampling pipe. The sampling pipe should be located before air exhausts from the building or before diluting return air with outside air. For accurate identification of the source of an alarm, locate sampling pipe as close as possible to the protected area's air entry into the duct system. Locate sampling pipe on the downstream side of the filter to sense fire in the filters. Note: If filters are blocked, sufficient airflow may no longer be present for proper operation. Do not locate sampling pipe near outside air inlets except to monitor smoke entry to the handling system for adjacent areas. Whenever possible, locate sampling pipe upstream of air humidifiers and downstream of dehumidifiers. Return air grill sampling method Return air grill sampling systems are designed with sampling pipes centered in the front of the return air grill. Sampling holes should be spaced so that a minimum of three holes are used for each grill. Larger grills require more sampling holes. The sampling holes should be in the direction of the airflow with an end cap. When using the air grill sampling without another sampling method, the smokedetection system will be ineffective when the ventilation system is inoperative. If this method is being used as the primary smoke detection system, the grill should be monitored for stoppage of airflow. 18 ReadySET Aspirating Smoke Detection System Installers Handbook
27 Chapter 3: Installation and configuration Figure 8 below shows a typical mounting to stand sampling pipe away from high velocity low pressure air at the entrance to the return air grill. Figure 8: Return air grill sampling method Installation Installation guidelines The following is a brief set of guidelines on installing detectors: The detector should normally be mounted at a level where there is easy access. The exhaust air from the unit must not be impeded in any way. If the detector is mounted in a different air pressure than where the air is being sampled (for example an air duct), then a pipe must be routed from the exhaust port back to the same air pressure zone as the sampling holes. All wiring must comply with NEC, NFPA 70, and the requirements of the local AHJ. All signal cables must be suitable for the application. The detector must not be placed in areas where either the temperature or humidity is outside the specified operating range. The detector should not be placed in close proximity to any equipment expected to generate high radio frequency levels (such as radio alarms) or units generating high levels of electrical energy (such as large electric motors or generators). ReadySET Aspirating Smoke Detection System Installers Handbook 19
28 Chapter 3: Installation and configuration Table 2 below contains a list of procedural guidelines for installation of the ReadySET detector. Table 2: Procedural guidelines Do Ensure that the ClassiFire alarm factor is appropriately set. Ensure that the power and signal cables are correctly connected before powering up by use of cable identifiers or electrical continuity checks. Incorrect connection could damage the detector. Ensure that cable of an appropriate approved type is used for interconnection. Place sampling points so that the detector will be able to detect smoke at the earliest opportunity. Ensure that the detector exhaust is in an area with the same atmospheric pressure as the sample pipes, either by placing the detector physically in the protected area or by leading a pipe from the detector exhaust to the protected area. Ensure that the environment of the protected area is within the environmental operating parameters of the detector (32º to 100º F or 0º to 38º C, humidity 0-90%, noncondensing). Ensure the detector is properly grounded. Don t Remove or connect boards when the detector is powered up. Attempt to adjust or alter detector settings other than via the userprogrammable functions. Any attempts to adjust the laser potentiometer are detectable and will void the warranty on the product. Drop the detector or use excessive force when fitting sampling pipes as this may damage the detector. Connect internal 0 volt terminals to local earth. Use sampling pipe of less than 1 inch (27 mm) outside diameter without a suitable 1-inch (27- mm) pipe adapter. It is important that there are no leaks where the pipe connects to the detector. Place the detector so close to other equipment that there is insufficient room to access and change the dust separator (filter) or access the RS- 232 connector (if installed). Install the detector near high power RF sources or in damp or exposed areas. Attempt to re-use dust separator (filter) cartridges once removed. Removing the front cover To remove the front cover, unfasten the cover securing screw located on the bottom of the unit. The cover may then be removed. 20 ReadySET Aspirating Smoke Detection System Installers Handbook
29 Chapter 3: Installation and configuration Mechanical installation Refer to Inside the detector on page 9 for conduit, pipe interface information, and mounting hole locations. The detector is connected to the installed sampling pipework and fixed to the mounting surface using three screws of a type appropriate to the mounting surface. Ensure that the sampling and exhaust pipes are securely seated in the pipe ports before securing. If using a piped exhaust connection, be sure that the sampling and exhaust pipe are fitted into the relevant port as shown in Inside the detector on page 9. Electrical installation In keeping with good wiring practice, keep cables and individual stripped conductors as short as possible while allowing stress-relieving cable forming. Power cables should be current-rated at 1 A or greater. Signal cable should be 120 Ω or less twisted pair. Figure 9 on page 22 shows the terminal block connections that connect the ReadySET detector to other electronic components. It is recommended that all connection wires be marked with suitable identification labels or colored rings to aid in the connection process. ReadySET Aspirating Smoke Detection System Installers Handbook 21
30 Chapter 3: Installation and configuration Figure 9: Detector terminal block connections 22 ReadySET Aspirating Smoke Detection System Installers Handbook
31 Chapter 3: Installation and configuration WARNING: Electrocution hazard. All connections should be made with the power turned off. Power supply connections The grounded power supply cable should be routed through the metal cable gland provided, leaving about 1-1/4 inch (35 mm) of the cable extending from the bottom of the cable gland. Depending on the type of cable used, it may be necessary to increase the diameter of the cable with sleeving or insulating tape to ensure that the cable is firmly held when the cable gland is fully tightened. Note: If this equipment is part of a fire detection system, power should be supplied from a supervised UL Listed power supply, designed for fire system use. To connect the power supply: 1. Remove the ReadySET detector front cover, and then locate the power supply terminal block. Refer to Figure 2 on page 9 for an illustration of the ReadySET detector with the front cover removed. Refer to Figure 10 below for a detailed illustration of the power input terminals. 2. Connect 0 V and +24 VDC to the 0V (-24) and +24V screw terminals, respectively. 3. Connect the shielded (screened) wire to the EARTH screw terminal. Figure 10: Power supply terminals Relay connections The ReadySET detector includes an Alarm and a Pre-Alarm relay, which will transfer to the normally open (NO) position on alarm. It also includes a general Fault relay, which will transfer to the normally closed (NC) position during a fault condition or on power-down. ReadySET Aspirating Smoke Detection System Installers Handbook 23
32 Chapter 3: Installation and configuration The relays are of the volt-free type, with a maximum current capacity of 1 A at 24 VDC maximum. To comply with radiated immunity requirements, it is recommended that the relay connection wires be looped once around a suppression ferrite (provided). There should be about 1-1/4 inch (30 mm) of wire between the end of the ferrite and the terminal block to give adequate stress relief. To achieve this, it is necessary to strip back the cable shield approximately 5 inches (130 mm). The shield should be terminated under the cable gland cap. The ReadySET detector interfaces to fire alarm panels using the detector s ALARM, PRE-ALARM, and FAULT relay contacts. Make all connections shown in Figure 11 on page 25. Input connection The ReadySET detector is fitted with an INPUT connection. This provides an input which can be used to monitor the PSU or to desensitize the detector by using the day/night feature. DIP switch number 7 must be set as described in Figure 11 on page 25. The INPUT terminals on the detector circuit board are set by default to monitor the power supply. If power supply monitoring and ClassiFire override are not required, fit a wire link across the two terminals to prevent a fault condition on power-up. Make all connections shown in Figure 11 on page ReadySET Aspirating Smoke Detection System Installers Handbook
33 Chapter 3: Installation and configuration Figure 11: Wiring diagram Configuration The default settings of the detector meet most application needs. These settings can be customized to meet additional requirements. Customizing the ReadySET detector requires changing the settings of the eight segments of the configuration DIP switch (Figure 12) mounted on the main PCB. See Table 3 on page 26 and the paragraphs following the table to determine the proper switch setting for the application. ReadySET Aspirating Smoke Detection System Installers Handbook 25
34 Chapter 3: Installation and configuration Figure 12: DIP switch Table 3: DIP switch settings Setting Set detector sensitivity Switch 1 Switch 2 Alarm factor 6 OFF OFF Alarm factor 7 ON OFF Alarm factor 8 OFF ON Alarm factor 9 ON ON Classifire On Fixed alarms Flow limit offset Switch 3 OFF ON Switch 4 Switch 5 ±40 OFF OFF ±20 ON OFF ±5 OFF ON ±3 ON ON Flow delay Switch seconds OFF 30 seconds ON Input select Psu fault Classifire Override Auto calibration Enable Disable Note: The settings in bold text are the factory default settings. Switch 7 OFF ON Switch 8 OFF ON 26 ReadySET Aspirating Smoke Detection System Installers Handbook
35 Chapter 3: Installation and configuration Alarm factor The detector calculates sensitivity relative to the ambient pollution level. Higher Alarm Factors provide reduced sensitivity. Note: Changing the alarm factor starts a new FastLearn cycle. Alarm factor: The ClassiFire system statistically analyzes the background smoke level and sets detector sensitivity to a level giving a statistical probability of nuisance alarm. The software assesses the arithmetic mean and variance (standard deviation) of the normal ambient smoke level and places the alarm flags at a certain number of standard deviations from the mean of the distribution. The number of standard deviations at which the alarm flag is set away from the mean is directly proportional to the ClassiFire alarm factor chosen. The probability of nuisance alarm and the maximum detector sensitivity are higher when a low level of alarm factor is chosen and lower as the alarm factor is increased. A low alarm factor may be desirable in the case of a high-value computer center where the cost of down-time and call-out costs may be offset by the high value of the protected installation. On the other hand, this will not be desirable in a machine shop with very variable levels of background smoke. In this case, it may be more important to ensure that an elevated level of smoke really does indicate an incipient fire before alarms are raised. The probability of nuisance alarm for a given environment also depends on the stability of the background smoke level. For example, a clean, controlled environment will unlikely have a smoke level that will vary over time. Under these circumstances, a low alarm factor will not imply a radically increased probability of nuisance alarm. ClassiFire On Selecting ClassiFire On allows the artificial intelligence system to continuously adjust alarm thresholds in order to avoid unwanted alarms from environmental changes (recommended). Note: Disabling this feature means that nuisance alarms due to fluctuations in ambient pollution levels become more likely. Fixed alarms Switches the artificial intelligence system off, locking sensitivity to that set at initial setup. This deactivates the dust filter monitoring system (not recommended). Note: Enabling this feature means that nuisance alarms due to fluctuations in ambient pollution levels become more likely. ReadySET Aspirating Smoke Detection System Installers Handbook 27
36 Chapter 3: Installation and configuration Flow limit offset Flow limit offset sets the sensitivity of the airflow monitoring system. A small offset makes the system very sensitive to air flow changes. This detector must react to ±20% changes in airflow, which equates to a change in flow sensor reading of +5. Areas with fluctuating air pressures may require a less sensitive setting. Note: Changing the flow limit offset starts a new flow calibration set up. Flow delay Sets the time for which a flow fault must continue before a fault is signaled. Input select The detector input terminal may be used to either monitor an associated power supply for faults, or for ClassiFire override (reduces normal sensitivity by 50%). Note: In the factory default condition, the switch is set to OFF (power supply monitoring). This gives a fault condition if there is an open circuit on the INPUT terminals. Fit a wire link if you do not require power supply monitoring. If you fit a wire link across the INPUT terminals, you must set this switch OFF, or else the detector sensitivity is dramatically and permanently reduced by the ClassiFire override function. Auto calibration Auto calibration automatically starts a new FastLearn cycle when the detector is powered up. This may be disabled if the previous settings need to be retained. Final installation Once the power and signal connections are made, place the detector cover onto the unit and secure the cover to the unit using the cover mounting screw. Note: The detector is designed solely for operation with the front cover securely fitted using the cover mounting screw. Removing the detector Removing the detector is the reverse of the installation process, disconnecting the pipework and wiring connections installed in the unit. 28 ReadySET Aspirating Smoke Detection System Installers Handbook
37 Chapter 4 Commissioning Summary This chapter provides information to commission the ReadySET detection system. Content Introduction 30 Precommissioning preparation 30 Commissioning checklist 30 Acclimation period 31 Suction pressure verification 31 Transport time verification 31 Gross smoke test 32 ReadySET Aspirating Smoke Detection System Installers Handbook 29
38 Chapter 4: Commissioning Introduction This chapter covers the commissioning procedures for the ReadySET detector. Commissioning strategy initially depends upon the detector s environment. Commissioning should only be done by factory-trained technicians in accordance with the same applicable standards listed in Chapter 3 Installation and configuration on page 11. Precommissioning preparation Commissioning should be performed after all construction has been completed and cleaned of any lingering post-construction dirt. If ambient monitoring conditions are recorded before the installation is cleaned up, they may not accurately reflect normal operating conditions. Commissioning checklist The following brief checklist allows quick setup of the detector. This procedure will be adequate for most standard installations. Caution: Ensure all wiring connections are checked prior to powering up the detector. Incorrect wiring of the detector will cause permanent damage to the detector. 1. Before powering up the detector, visually check all cabling to ensure correct connection. If wire identification is not immediately clear (e.g., by use of different colored wires or wire identification sleeves), an electrical check should be made. 2. Disconnect the detector from the fire control unit, if applicable. 3. Power up the detector and wait for the 15 minute FastLearn cycle to finish. The OK LED will be steadily lit when complete. 4. The detector automatically performs a FastLearn cycle which takes approximately 15 minutes. The OK indicator on the front panel will begin to flash. When using day/night switching, check that day start and night start settings reflect site operations. 30 ReadySET Aspirating Smoke Detection System Installers Handbook
39 Chapter 4: Commissioning 5. The detector will generate no alarms during the 15 minute FastLearn period and, after this, the detector will operate at a reduced sensitivity for 24 hours while ClassiFire learns and acclimates to the protected environment and sets up appropriate day and night sensitivity settings. 6. Reconnect the detector to the fire control unit, if applicable Acclimation period The detector will operate at a reduced sensitivity for 24 hours. ClassiFire will set up the appropriate day and night sensitivity settings. All air handling units, thermostats, and other systems that can have an effect on the operating environment should be turned on to simulate normal operating conditions as closely as possible. Investigate and correct any condition that cannot be accounted for. Suction pressure verification Sample hole suction pressures can be measured and recorded on the checklist for future reference using the steps below. To perform a pressure test: 1. Attach a flexible hose onto the suction side of the magnehelic pressure gauge. 2. Place the hose against the sampling hole and hold it in place. 3. Hold the gauge in the plane in which it was calibrated and read the suction pressure from the gauge as shown in Figure 13 below. Figure 13: Magnehelic test setup ReadySET Aspirating Smoke Detection System Installers Handbook 31
40 Chapter 4: Commissioning Transport time verification A maximum transport time verification test measures the amount of time it takes for the detector to respond to smoke that enters the sampling point furthest from the detector. The results of this test and the calculated maximum transport time from PipeCAD must be recorded on the checklist if applicable. Measured transport time less than the calculated time is acceptable. To measure the maximum transport time of the system: 1. Determine the furthest sampling point from the detector. 2. Allow test smoke to enter pipe at the furthest sampling point. 3. Record the amount of time for the detector to respond. This is the actual maximum transport time. This time must not exceed 120 seconds. Gross smoke test The gross smoke test is a measurement of the amount of time elapsing from the activation of the smoke generating medium, until PRE-ALARM and ALARM states are reached. This test should be repeated at least three times with consistent results. The recommended smoke generating medium is canned smoke or a wire burner. Smoke from a punk or cotton wick is also acceptable. Caution: Oil-based canisters that are used to test point detectors are not suitable for testing aspirating systems, as the particulate is heavy and tends to drop out in the pipe, never actually reaching the detector. Also, the oily residue that is left behind may affect the functionality of the detector. When using canned smoke, introduce only enough smoke into the protected area to cause a FIRE condition. This may require a number of practice sprays. Follow the manufacturer s instructions.. 32 ReadySET Aspirating Smoke Detection System Installers Handbook
41 Chapter 5 Troubleshooting Summary This chapter provides information about troubleshooting the ReadySET detection system. Content Troubleshooting 34 Troubleshooting the ReadySET detector 34 Contacting technical support 35 ReadySET Aspirating Smoke Detection System Installers Handbook 33
42 Chapter 5: Troubleshooting Troubleshooting Troubleshooting the ReadySET detector This chapter provides some possible solutions if a problem should occur with your ReadySET detector. If the problem is not addressed in this chapter or, if after performing the suggested actions, the problem persists, contact Technical Support. Problem Nuisance alarms occur too often Elevated smoke levels do not generate alarms Low mean output Detector sensitivity varies over time Solution or corrective action This normally indicates that the detector is set at an alarm factor inappropriate to the installed environment. Increase the alarm factor to reduce sensitivity. Check that the ClassiFire alarm factor setting is appropriate for the normal working environment of the protected area. Check that the ClassiFire override switch is appropriately set to reflect active and inactive periods. The sensor chamber may be contaminated. If so, return the detector to the factory for cleaning and recalibration. Check that detector is not in FastLearn (if in FastLearn, the OK light will flash). Check if green OK LED is on and flashing. The detector FastLearn cycle may have been carried out during or immediately after a smoke test. Reinitialize FastLearn with the detector in a clean environment. Check that the detector sampling points are in the smoke stream. Check that sampling pipes are firmly and cleanly seated in their ports and undamaged. Check that the correct alarm factor setting has been set. if the alarm factor is too high, change the alarm factor to a lower, more sensitive setting. Check that the detector has had a 24-hour learning period. Check that the dust separator cartridge does not require changing (refer to Replacing the dust separator filter cartridge on page 40 for details) and that the air plenum chamber is clean. The chamber may become clogged when, for example, heavy building activity has occurred near the sampling pipes. If so, the chamber may require factory service. The detector is not designed to handle large quantities of coarse debris and dust. There are many reasons why particle densities may vary, and the ClassiFire system is designed to automatically compensate for this in order to reduce the likelihood of nuisance alarms due to normal variations in background smoke density. Within limits set by the ClassiFire alarm factor, this is a normal part of the detector s operation. 34 ReadySET Aspirating Smoke Detection System Installers Handbook
43 Chapter 5: Troubleshooting Problem Flow fault errors ( FLOW LED illuminated) Long transport times Detector laser chamber error ( HEAD LED illuminated) Solution or corrective action These occur when the airflow rate into the detector exceeds the programmed parameters. This usually occurs when there has been some change in conditions. It may indicate that a sampling pipe is damaged, or that the pipe has been blocked, e.g., by nearby building operations. Flow monitoring is too sensitive for the environment. Increase the flow limit offset. If the detector input is sampled from one area and the exhaust is in another area with different pressure (e.g., the detector is in a roof space and sampling from an enclosed room), this may lead to flow faults. In this case it, would be necessary to lead a pipe from the exhaust to the protected area to ensure nominal flow. The airflow may be subject to temporary changes (spikes). Increase the flow delay to 240 seconds. Check that installed pipework is fitted with end caps. When used, PipeCAD pipe modeling software prompts for the use of appropriate end caps. Open bore pipes are not recommended. Sampling pipe may be too long or have too many sampling holes/capillaries or incorrect hole sizes. Check the design with pipe modeling software. For pre-engineered piping, ensure that the piping is within the specified parameters. Sampling pipes, sampling holes and/or the exhaust pipe may be partially blocked by dust or debris. Clean pipe work with dry compressed air and/or clean the sampling holes. Fan may be defective. Send detector to manufacturer for repair. Electrical lead from fan may be disconnected. Reconnect lead. This occurs when a problem is present in the detector laser chamber. Inspect wires that are connected to the laser head for damage and loose connections. Contacting technical support Tel Fax [email protected] ReadySET Aspirating Smoke Detection System Installers Handbook 35
44 Chapter 5: Troubleshooting 36 ReadySET Aspirating Smoke Detection System Installers Handbook
45 Chapter 6 Maintenance Summary This chapter provides scheduled and unscheduled maintenance procedures. Content Introduction 38 Scheduled maintenance 38 Maintenance procedures 38 ReadySET Aspirating Smoke Detection System Installers Handbook 37
46 Chapter 6: Maintenance Introduction This chapter contains maintenance instructions for the ReadySET aspirating smoke detection system. These procedures should be performed on a scheduled basis. In the event that system problems are found during routine maintenance, refer to Troubleshooting on page 34. Failure to properly maintain the system may affect the functioning of the system. Scheduled maintenance The scheduled maintenance of the system should be performed at an established interval. At a minimum, the interval between performance of maintenance procedures should not exceed any applicable regulations. (See NFPA-72 or other local requirements.) This chapter contains minimum maintenance procedures, however, additional and/or more frequent procedures may be required by applicable codes and standards. Maintenance procedures The following paragraphs outline general scheduled maintenance procedures. Visual check The visual check must be performed at least every six months. This check is to ensure pipe network integrity. Ensure that the design is still valid. Building upgrades can require changes to the piping and detector requirements. To perform the visual check, observe the entire piping network and check for abnormalities in the pipes including any breaks, blockages, crimps, etc. Battery status check Caution: Any battery that has been in service for 36 months or more must be replaced. The battery backup used in the power supply to power the detector must be tested at least every six months. A battery status check is best accomplished by running the load with the batteries for about one hour. While the load is still on, measure the individual battery voltages. If any battery reads 1.5 V or more below its rated voltage, that battery should be replaced. 38 ReadySET Aspirating Smoke Detection System Installers Handbook
47 Chapter 6: Maintenance Generally, if one of a series set of batteries is low, the others will soon fail. Therefore, it is advisable to replace all the batteries of a series set when one requires replacement. Gross smoke test The gross smoke test is a go/no-go test which ensures that the detector responds to smoke. This test must be performed at system commissioning and at least every year thereafter. To perform this test, smoke must be introduced into the last sampling hole in each branch of the pipe network and the proper detector response must be verified. Smoke from a punk or cotton wick may be used. Canned smoke may also be used. Caution: Oil-based canisters that are used to test point detectors are not suitable for testing aspirating systems as the particulate is heavy and tends to drop out in the pipe, never actually reaching the detector. Also, the oily residue that is left behind may affect the functionality of the detector. Transport time verification test The maximum transport time of the pipe network must be measured and compared to the recorded transport time at commissioning. (Refer to Transport time verification on page 32 for test details.) The transport time verification test must be done at commissioning and at least every year thereafter. Detector sensitivity test The detector sensitivity test must be performed within one year of installation and at least every alternate year thereafter. Example: Year-one check Year-three check The detector employs a self-monitoring, automatically adjusting calibration for the system. The inspection only requires a periodic visual inspection for a detector fault indication and performing the detector sensitivity test function. If the self-monitoring feature of the system senses that the operation of the detector head is outside its normal range, a trouble condition will be generated. Cleaning the detector The exterior of the detector should be cleaned as necessary. Clean the detector with a damp (not wet) cloth. ReadySET Aspirating Smoke Detection System Installers Handbook 39
48 Chapter 6: Maintenance Caution: Do not use solvents to clean the detector. Use of solvents may cause damage to the detector. Replacing the dust separator filter cartridge The only part that may require field replacement during servicing is the dust separator filter cartridge. The FILTER LED will illuminate when the detector s air filter needs to be changed. WARNING: If, due to the environment of the area being protected, the dust in the dust separator filter will expose maintenance personnel to health hazards, it is recommended that suitable masks and protective clothing be worn when changing filters. Maintenance work should be performed in compliance with OSHA if applicable. Note: Used dust separator cartridges are not intended for reuse and should be discarded. To replace the filter: 1. Remove power to the detector. 2. Remove the front cover mounting screw securing the unit s front cover. 3. With the front cover removed, grasp the filter firmly and pull the filter out (directly towards you). 4. Properly dispose of the used cartridge. 5. Locate the orientation markings on the new filter cartridge. The word IN is marked on one side and the other is marked OUT. 6. Insert the replacement filter cartridge (part number ) so that the IN mark on the cartridge is on the left as viewed in Figure 14 on page Slide the cartridge all the way into place. 8. Replace the detector cover and secure it into place. Initiate a FastLearn routine by re-energizing the detector. 40 ReadySET Aspirating Smoke Detection System Installers Handbook
49 Chapter 6: Maintenance Figure 14: Location of dust separator (filter) cartridge ReadySET Aspirating Smoke Detection System Installers Handbook 41
50 Chapter 6: Maintenance 42 ReadySET Aspirating Smoke Detection System Installers Handbook
51 Appendix A Communications card Summary An optional communications card can be fitted inside the ReadySET detector. The ReadySET is also available in a model that is shipped with the communications card factory installed. ReadySET Aspirating Smoke Detection System Installers Handbook 43
52 Appendix A: Communications card Optional communications card An optional communications card can be fitted inside the ReadySET detector to provide an RS-232 serial port and RS-485 network communication. A ReadySET model is also available with the communications card factory installed. Figure 15: Optional communications card Direct connection of a PC to the communications card is done using a 9 pin RS-232 interface on the communications card, using a null modem cable configuration, as shown in the diagram below. 44 ReadySET Aspirating Smoke Detection System Installers Handbook
53 Appendix A: Communications card A connected PC can access the detector event memory to review previous or current events, such as detector alarms or faults. The detector internal chart recorder can also be accessed to allow analysis of detector behaviour (refer to the Remote Software Configuration User Manual for further information). The PC cannot be used to configure the detector except to enter time and date settings for the detector event log and chart recorder to be viewed in the remote configuration software. The detector does not incorporate a real-time clock, so the time and date need to be re-entered if the detector is powered down for any reason. Installation of the communications card also provides the detector with RS-485 network communication via the A, B, and SCREEN terminals on the detector main board (see Figure 9 on page 22). This can be used for simple remote display indication or integration into a larger site wide management and display system, separate from the local fire detection and alarm system. ReadySET Aspirating Smoke Detection System Installers Handbook 45
54 Appendix A: Communications card 46 ReadySET Aspirating Smoke Detection System Installers Handbook
55 Glossary C Degrees centigrade F Degrees Fahrenheit A Ampere AC Alternating current ADA Americans with Disabilities Act AH Ampere hour AHJ Authority having jurisdiction ARC Automatic release circuit AWG American wire gauge CSFM California State Fire Marshal DACT Digital alarm comm. transmitter DC Direct current DET Detector EOLD End of line device EOLR End of line resistor FM Factory Mutual ft. Feet HSSD High sensitivity smoke detector Hz Hertz (frequency) in. Inches LCD Liquid crystal display LED Light emitting diode MEA Materials and Equipment Acceptance Division of the City of New York NAC Notification appliance circuit N.C. Normally closed NEC National Electrical Code ReadySET Aspirating Smoke Detection System Installers Handbook 47
56 Glossary NFPA N.O. NYC PCB pf P/N PSU RAM SLC TB UL/ULI V VAC VDC VRMS National Fire Protection Association Normally open New York City Printed circuit board Picofarads Part number Power supply unit Random access memory Signaling line circuit Terminal block Underwriters Laboratories, Inc. Volts Volts AC Volts DC Volts root mean square 48 ReadySET Aspirating Smoke Detection System Installers Handbook
57 Index A Addressing DIP switch location, 7 Advisory messages, iii Alarm factor, 27 Antistatic precautions, 12 Aspirating smoke detection system limitations, 3 Auto calibration, 28 C ClassiFire, 6, 20, 24, 26, 27, 28, 31 Cleaning the detector, 39 Commissioning, 29 Acclimation period, 31 Commissioning checklist, 30 Precommissioning preparation, 30 Suction pressure verification, 31 Transport time verification, 32 Communications card, 44 Configuration, 25 D Detector internal components, 9, 21 DIP switch settings, 26 Dust separator filter cartridge, replacing, 40 F FastLearn, 8, 27, 28, 30, 34, 40 Fixed alarms, 27 Flow delay, 28 I Indicators, 8 ALARM, 8 FAULT, 8 FLOW, 9 HEAD, 9 OK, 8 PRE-ALARM, 8 Input connection, 24 Input select, 28 Installation, 19 Electrical installation, 21 Installation guidelines, 19 Mechanical installation, 21 M Maintenance, 37 Maintenance procedures, 38 Scheduled maintenance, 38 P Power supply connections, 23 R Relay connections, 23 Removing the detector, 28 S Safety summary, iv Specifications, 7 System design, 13 Air handling unit installation, 15 Below/above the ceiling installation, 15 Return air duct sampling method, 17 Return air grill sampling method, 18 Sample pipe networks, 14 T Technical support, contacting, 35 Testing Battery status check, 38 Detector sensitivity test, 39 Gross smoke test, 32, 39 Transport time verification test, 39
58 Index Visual check, 38 Troubleshooting, 33 W Wiring diagram, ReadySET Aspirating Smoke Detection System Installers Handbook
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
E-PDD Duct Smoke Detector Installation Sheet
E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating
StorTrends 3400 Hardware Guide for Onsite Support
StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200
SPECIAL APPLICATIONS
Page 1 SPECIAL APPLICATIONS The protection of microelectronics clean rooms using aspirating smoke detection systems requires special consideration. The physical configuration of the room(s) and the direction
TS93 EMR T/PT/TDE. Surface applied door closer
TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double
BroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors
D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH
FAAST. Fire Alarm Aspiration Sensing Technology
FAAST Fire Alarm Aspiration Sensing Technology The world s finest manufacturing facility System Sensor s European products are researched, designed and manufactured at our 10,000m2 state-ofthe-art facility
Automatic Phone-Out Home Monitoring Systems
Automatic Phone-Out Home Monitoring Systems Power Outage and Freeze Alarm Model Number: THP202 Power Outage, Freeze and Flood Alarm Product Description Model Number: THP201 These monitoring systems are
LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual
CMR Electrical Ltd Bolton House Five Chimneys Lane Hadlow Down East Sussex TN22 4DX Tel: 01825 733600 LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual Contents 1) Operation 2)
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE
Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported PCIe Cards 1.2 PACKAGE
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
How To Use A Ds340 (Dsp)
Ideal for monitoring dust levels in the exhaust gas of industrial combustion or air filtration processes. Innovative Dynamic Detection Principle (DDP) measurement technique Immune to gradual reductions
RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05
RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,
AT&T. PARTNER Plus Door Phone. Installation and Operation Manual
AT&T PARTNER Plus Door Phone Installation and Operation Manual Copyright 1990 AT&T All Rights Reserved Printed in U.S.A. CIC# 999-500-317 OII722050-051 Issue 1 October 1990 PARTNER Plus Door Phone is a
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
Power Max Level 2 Charging Station en Installation and Operating Instructions This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the
Fire Fighter Phone System Installation Instructions
Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).
Series 510 Submersible Level Transmitters
Series 510 Submersible Level Transmitters The Series 510 Submersible Level Transmitters are solid state instruments designed for direct submergence into many types of liquid for quick, accurate and reliable
WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:
Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
FIRERAY 2000 Installation Guide
FIRERAY 2000 Installation Guide Features Range 33ft to 330 ft. 24Vdc operation Selectable alarm thresholds Low current consumption Ground level electronics Manual or Automatic reset System Description
8251F FAAST Fire Alarm Aspiration Sensing Technology
INSTALLATION AND MAINTENANCE INSTRUCTIONS 8251F FAAST Fire Alarm Aspiration Sensing Technology 3825 Ohio Avenue, St. Charles, Illinois 60174 1.800.SENSOR2; Fax: 630.377.6495 www.systemsensor.com I56-3904-001
OASIS-PLUS 120V READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE
OASIS-PLUS 120V INFORMATION & OPERATING INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE OPERATING READ ALL INSTRUCTIONS BEFORE OPERATING OZONE IS A POWERFUL OXIDIZER AND MUST BE USED WITH CARE 56041852 WARNING:
INSTRUCTION MANUAL MODEL PCD-88
INSTRUCTION MANUAL MODEL PCD-88 CLOSED CAPTION DECODER LINK ELECTRONICS, INC. 2137 Rust Avenue Cape Girardeau, Missouri 63703 Phone: 573-334-4433 Fax: 573-334-9255 e-mail: sales @ linkelectronics.com website:
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
Fire detection equipment
PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,
FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON
FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON SERIAL NUMBER Flash Technology, 332 Nichol Mill Lane, Franklin, TN 37067 (615) 261-2000 Front Matter Abstract This
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE
MODEL HAA51 PASSIVE INFRARED INTRUSION DETECTOR PASSIVE INFRAROOD DETECTOR DETECTEUR D INTRUSION PASSIF INFRAROUGE OPERATING MANUAL HAA51 PASSIVE INFRARED INTRUDER DETECTOR INTRODUCTION HAA51 Passive Infrared
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
HART HSSD High Sensitivity Smoke Detection
HART HSSD High Sensitivity Smoke Detection The HART High Sensitivity Smoke Detection system (HSSD) is an Aspirating Smoke Detection system (ASD) designed to give very early indication of an incipient
SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE
SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS
Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and
INSTALLER S & OWNER S MANUAL
INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE
3M Wrist Strap and Footwear Tester 740. User s Guide
3M Wrist Strap and Footwear Tester 740 User s Guide Table of Contents Section Page Safety Information...3 1.0 General...4 2.0 Description...4 3.0 Operation...5 4.0 Wall Mounting...5 5.0 Wrist Strap Test...6
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010
CETA Application Guide for the Exhaust System Requirements of Class II, Type B Biosafety Cabinets CAG-007-2010 March 24, 2010 1. Background Class II Type B Biosafety Cabinets (BSCs) are unique laboratory
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
Express5800/120Ed. Rack Mount Kit Installation Procedures PN: 455-01607-001
Express5800/120Ed Rack Mount Kit Installation Procedures PN: 455-01607-001 Proprietary Notice and Liability Disclaimer The information disclosed in this document, including all designs and related materials,
IP DSLAM IDL-2402. Quick Installation Guide
IP DSLAM IDL-2402 Quick Installation Guide Table of Contents Package Contents... 3 Overview... 4 Setup the IDL series IP DSLAM... 5 Safety Instruction... 5 Hardware Installation... 6 WEB Configuration...
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
Ceiling Mount Air Handler Manual
www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty
About this Manual. Support for Your Product
About this Manual We ve added this manual to the Agilent website in an effort to help you support your product. This manual is the best copy we could find; it may be incomplete or contain dated information.
CalMod Design-Build Electrification Services
SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
Perle Protocol Transparent Media Converter Modules
Perle Protocol Transparent Media Converter Modules Installation Guide C-4GPT-DSFP CM-4GPT-DSFP Part# 5500335-10 Overview This document contains instructions necessary for the installation and operation
ENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS
Manual No. BLWR043 Rev. 4 September 2012 OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS CVF-8AC CVF-8AC50 CVF-6ACAN CVF-15ACAN CVF-25ACAN CVF-8A15KIT CVF-8A25KIT MODELS: CVF-8DC CVF-6DCAN CVF-15DCAN CVF-25DCAN
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
Perle 10/100 Ethernet Media Converters
Perle 10/100 Ethernet Media Converters Installation Guide S-110-XXXXXX S-110-XXXXXX-XT P/N 5500302-16 (Rev B) Overview This document contains instructions necessary for the installation and operation of
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services
Section 6 Fire Detection and Alarm Systems Russell Porteous Chief Executive Officer Firewize Services General Information Section 6 of AS1851-2012 covers: Fire Detection and Alarms Systems Electrical Detection
EVALUATION OF THE PERFORMANCE OF FIRE DETECTION SYSTEM IN AN INSTITUTIONAL BUILDING
, Volume 6, Number 4, p.333-343, 2004 EVALUATION OF THE PERFORMANCE OF FIRE DETECTION SYSTEM IN AN INSTITUTIONAL BUILDING C.M. Tse Department of Building Services Engineering, The Hong Kong Polytechnic
OPL BASIC. Dosing System for Professional Laundry machines. Contents
OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
aseries A13B Mini Bullet Camera User Manual
aseries A13B Mini Bullet Camera User Manual Thank you for purchasing our product. If there are any questions, or requests, please do not hesitate to contact the dealer. This manual applies to the MicroView
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U SURT192RMXLBP2 SURT192RMXLBP2J English 990-2485B 02/2009 Introduction About this UPS The American Power Conversion (APC ) SURT192RMXLBP2 external
Model 201 Wiegand Touchpad Reader Installation Guide
Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without
SDX Submersible Depth Transmitter User Manual
SDX Submersible Depth Transmitter User Manual January 2011 USER INFORMATION Stevens makes no warranty as to the information furnished in these instructions and the reader assumes all risk in the use thereof.
Triple Expansion Chassis
Triple Expansion Chassis AP9604 Installation Manual Contents Introduction............................. 1 Installation.............................. 2 Power Considerations...................... 5 Operations..............................
2-3 SAS/SATA II HDD Canister USER S MANUAL XC-23D1-SA10-0-R. Document number: MAN-00076-A
2-3 SAS/SATA II HDD Canister XC-23D1-SA10-0-R USER S MANUAL Document number: MAN-00076-A ii Preface Important Information Warranty Our product is warranted against defects in materials and workmanship
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
RAY-MAX Integrated Solar Power Strip
RAY-MAX Integrated Solar Power Strip 600008, 600009, 600010, 600208, 600209, 600210 Owner s Manual NEXTRONEX, INC. Revision Date: 10/27/14 Contents 1. Safety Instructions... 3 2. General Equipment Warnings...
Solar Home System. User Manual. AEH-SHS01-10W2L Solar Home System 2 Lamps
Solar Home System User Manual AEHSHS0110W2L Solar Home System 2 Lamps All rights reserved Specifications subject to change without prior notice 2 Dear Customer, Thank you for purchasing Schneider Electric
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 Getting Started Getting Started with the Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 You only need a few minutes to get started
USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
AC-115 Compact Networked Single Door Controller. Installation and User Manual
AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.
Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008
Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be
DUCT SMOKE DETECTOR D4120
Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity
G670 Intermittent Pilot Ignition Controls
Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control
Installation Guide Smart-UPS X External Battery Pack SMX120BP
Installation Guide Smart-UPS X External Battery Pack SMX120BP Inventory Inspect the contents upon receipt. Notify the carrier and dealer if there is damage. Two bezels Tie brackets used to secure multiple
Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868
Instruction Sheet 10-2004 Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868 PowerCommand is a registered trademark of Cummins Inc. InPower
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide
SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
MIC-BP4 Bi-Phase Converter Card For the MIC400 series camera
MIC-BP4 Bi-Phase Converter Card for the MIC400 PTZ Camera Series Bosch Security Systems EN Installation and Operation Manual BP4 Bi-phase card Installation and Operation Manual AAAEN 2 MIC-BP4 Bi-Phase
Owner s Manual & Safety Instructions
Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s
University of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
Vertical Display and Storage B1350-2. SKOPE Gen2: Three Door Chiller
Vertical Display and Storage User Manual MAN1227 Rev. 3.0 March 2008 edition CONTACT ADDRESSES Designed and Manufactured by New Zealand SKOPE INDUSTRIES LIMITED PO Box 1091, Christchurch New Zealand Freephone:
Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,