EasiCool EZRE. Operation and Maintenance Manual
|
|
|
- Marybeth Sharon Barker
- 9 years ago
- Views:
Transcription
1 EasiCool EZRE Operation and Maintenance Manual
2 EasiCool EZRE Precision Air Conditioning Introduction Warranty, Commissioning & Maintenance As standard, Airedale guarantees all non-consumable parts only for a period of 12 months, variations tailored to suit product and application are also available; please contact Airedale for full terms and details. To further protect your investment in Airedale products, Airedale can provide full commissioning services, comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland). For a free quotation contact Airedale or your local Sales Engineer. All Airedale products are designed in accordance with EU Directives regarding prevention of build up of water, associated with the risk of contaminants such as Legionella. For effective prevention of such risk it is necessary that the equipment is maintained in accordance with Airedale recommendations. SafeCool In addition to commissioning, a 24 hour, 7 days a week on-call service is available throughout the year to UK mainland sites. This service will enable customers to contact a duty engineer outside normal working hours and receive assistance over the telephone. The duty engineer can, if necessary, attend site, usually within 24 hours or less. Full details will be forwarded on acceptance of the maintenance agreement. CAUTION Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance being carried out in accordance with the recommendations provided during the warranty period. Failure to have the maintenance procedures carried out will invalidate the warranty and any liabilities by Airedale International Air Conditioning Ltd. Spares A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on request. Training As well as our comprehensive range of products, Airedale offers a modular range of Refrigeration and Air Conditioning Training courses, for further information please contact Airedale. Customer Services For further assistance, please [email protected] or telephone: UK Sales Enquiries + 44 (0) [email protected] International Enquiries + 44 (0) [email protected] Spares Hot Line + 44 (0) [email protected] Airedale Service + 44 (0) [email protected] Technical Support + 44 (0) [email protected] Training Enquiries + 44 (0) [email protected] For information, visit us at our Web Site: Airedale Ltd endeavours to ensure that the information in this document is correct and fairly stated, but none of the statements are to be relied upon as a statement or representation of fact. Airedale Ltd does not accept liability for any error or omission, or for any reliance placed on the information contained in this document. The development of Airedale products and services is continuous and the information in this document may not be up to date. It is important to check the current position with Airedale Ltd at the address stated. This document is not part of a contract or licence unless expressly agreed. No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, including photocopying, recording, or information storage and retrieval systems, for any purpose other than the purchaser s personal use, without the express written permission of Airedale Ltd Airedale International Air Conditioning Limited. All rights reserved. Printed in the UK. 2
3 Precision Air Conditioning EasiCool EZRE Warranty All Airedale products or parts (non consumable) supplied for installation within the UK mainland and commissioned by an Airedale engineer, carry a full Parts & Labour warranty for a period of 12 months from the date of commissioning or 18 months from the date of despatch, whichever is the sooner. Parts or Equipment supplied by Airedale for installation within the UK or for Export that are properly commissioned in accordance with Airedale standards and specification, not commissioned by an Airedale engineer; carry a 12 month warranty on non consumable Parts only from the date of commissioning or 18 months from the date of despatch, whichever is the sooner. Parts or equipment installed or commissioned not to acceptable Airedale standards or specification invalidate all warranty. Introduction Warranty is only valid in the event that In the period between delivery and commissioning the equipment: is properly protected & serviced as per the Airedale installation & maintenance manual provided where applicable the glycol content is maintained to the correct level. In the event of a problem being reported and once warranty is confirmed as valid under the given installation and operating conditions, the Company will provide the appropriate warranty coverage (as detailed above) attributable to the rectification of any affected Airedale equipment supplied (excluding costs for any specialist access or lifting equipment that must be ordered by the customer). Any spare part supplied by Airedale under warranty shall be warranted for the unexpired period of the warranty or 3 months from delivery, whichever period is the longer. To be read in conjunction with the Airedale Conditions of Sale - Warranty and Warranty Procedure, available upon request. Procedure When a component part fails, a replacement part should be obtained through our Spares department. If the part is considered to be under warranty, the following details are required to process this requirement. Full description of part required, including Airedale s part number, if know. The original equipment serial number. An appropriate purchase order number A spares order will be raised under our warranty system and the replacement part will be despatched, usually within 24 hours should they be in stock. When replaced, the faulty part must be returned to Airedale with a suitably completed and securely attached Faulty Component Return (FCR) tag. FCR tags are available from Airedale and supplied with each Warranty order. On receipt of the faulty part, suitably tagged, Airedale will pass to its Warranty department, where it will be fully inspected and tested in order to identify the reason for failure, identifying at the same time whether warranty is justified or not. On completion of the investigation of the returned part, a full Report on Goods Returned will be issued. On occasion the release of this complete report may be delayed as component manufacturers become involved in the investigation. When warranty is allowed, a credit against the Warranty invoice will be raised. Should warranty be refused the Warranty invoice becomes payable on normal terms. Exclusions Warranty may be refused for the following reasons: Misapplication of product or component Incorrect site installation Incomplete commissioning documentation Inadequate site installation Inadequate site maintenance Damage caused by mishandling Replaced part being returned damaged without explanation Unnecessary delays incurred in return of defective component Returns analysis All faulty components returned under warranty are analysed on a monthly basis as a means of verifying component and product reliability as well as supplier performance. It is important that all component failures are reported correctly. 3
4 EasiCool EZRE Precision Air Conditioning Introduction Health and Safety IMPORTANT The information contained in this manual is critical to the correct operation and maintenance of the unit and should be read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit. Safety The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/ electrical equipment, care must be taken if you are to obtain the best results. CAUTION When working with any air conditioning units ensure that the electrical isolator is switched off prior to servicing or repair work and that there is no power to any part of the equipment. Also ensure that there are no other power feeds to the unit such as fire alarm circuits, BMS circuits, crank case heater permanent supplies etc. Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent and trained personnel in accordance with local relevant standards and codes of practice. The refrigerant used in this range of products is classified under the COSHH regulations as an irritant, with set Workplace Exposure Levels (WEL) for consideration if this plant is installed in confined or poorly ventilated areas. A full hazard data sheet in accordance with COSHH regulations is available should this be required. Protective Personal Equipment Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning equipment. Refrigerant Warning The Airedale EasiCool EZRE Precision Air Conditioning units use R410A refrigerant which requires careful attention to proper storage and handling procedures. Use only manifold gauge sets designed for use with refrigerants. Use only refrigerant recovery units and cylinders designed for the pressure category of the refrigerants. Refrigerants must only be charged in the liquid state to ensure correct blend makeup. The refrigerant must be stored in a clean, dry area away from sunlight. The refrigerant must never be stored above 50 C. Global Warming Potential R410A = 1900 EN378-1 :2008 (100 year life) Manual Handling Some operations when servicing or maintaining the unit may require additional assistance with regard to manual handling. This requirement is down to the discretion of the engineer. Remember do not perform a lift that exceeds your ability. 4
5 Precision Air Conditioning EasiCool EZRE Environmental Considerations Freeze Protection Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes the units subject to low ambient temperatures. Units with supply water temperatures below +5 C Glycol is recommended when a supply water temperature of +5 C or below is required or when static water can be exposed to freezing temperatures. Introduction Units subject to ambient temperatures lower than 0 C Glycol of an appropriate concentration (1) is used within the system to ensure adequate protection. Please ensure that the concentration is capable of protection at least 3 C lower than ambient. Water / glycol solution is constantly circulated through all waterside pipework and coils to avoid static water from freezing. Ensure that pumps are started and running even during shut down periods, when the ambient is within 3 C of the solution freeze point (1) (i.e. if the solution freezes at 0 C, the pump must be operating at 3 C ambient). Additional trace heating is provided for interconnecting pipework. (1) Refer to your glycol supplier for details. Environmental Policy It is our policy to: Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements Train personnel in sound environmental practices Pursue opportunities to conserve resources, prevent pollution and eliminate waste Manufacture products in a responsible manner with minimum impact on the environment Reduce our use of chemicals and minimise their release to the environment Measure, control and verify environmental performance through internal and external audits Continually improve our environmental performance CE Directive Airedale certify that the equipment detailed in this manual conforms with the following EC Directives: Electromagnetic Compatibility Directive (EMC) Low Voltage Directive (LVD) Machinery Directive (MD) Pressure Equipment Directive (PED) 2004/108/EC 2006/95/EC 89/392/EEC version 2006/42/EC 97/23/EC To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the Declaration of Conformity, supplied with each product. 5
6 EasiCool EZRE Precision Air Conditioning Introduction Contents Warranty, Commissioning & Maintenance 2 SafeCool 2 Customer Services 2 Warranty 3 Health and Safety 4 Safety 4 Protective Personal Equipment 4 Refrigerant Warning 4 Manual Handling 4 Environmental Considerations 5 Environmental Policy 5 Introduction 7 Pre Start Checks 8 Unit Operation 9 Controls 9 Display / Keypad 10 Standard Icons 10 Navigation 11 Navigation Sub Menus 11 Enabling the Unit 12 Changing the Setpoint 13 Unit Operating Parameters 14 Maintenance 16 General Inspections 16 Electrical Inspection 17 Refrigeration 18 Waterside 19 Controls 20 System 21 Troubleshooting 22 General Faults 22 Suction Throttle Valve (STV) (Optional Extra) 24 Humidifier (Optional Extra) 24 Alarms 25 Alarm Menu Display 25 Alarm Codes 26 CPY Board Alarms 31 6
7 Precision Air Conditioning EasiCool EZRE Introduction The EasiCool EZRE range of direct expansion and chilled water precision air conditioning units have been specifically designed for today s modern working environment. The present day demands for efficient operation of computer rooms, telecommunication centres, operating theatres, laboratories and clean rooms, which utilise stand-alone or multiple in room air handling units, require a high degree of control flexibility. Introduction The Airedale design philosophy has taken this fully into account offering an adaptable control system, utilising an microprocessor controller taking full advantage of the latest state of the art technology. The control system comprises 2 main parts, the controller and the display keypad. The controller offers powerful analogue and digital control to meet a wide range of monitoring and control features. The display keypad is used for viewing the unit operating status and making adjustments to control parameters by allowing the operator access to a series of display pages. Visual alarm acknowledgement and the facility to adjust and display control settings are available at the display keypad for local operator information and control. The microprocessor controller is supplied pre-programmed whilst allowing the control parameters to be individually set to suit the customer s requirements. 7
8 EasiCool EZRE Precision Air Conditioning Pre Start Checks CAUTION ALL work MUST be carried out by technically trained competent personnel. The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work. Crankcase Heater The compressor crankcase heaters must be energised for a period of 8 hours before the unit can be started. This is to ensures that liquid refrigerant has not condensed in the compressor during its off period. Compressors cannot pump liquid and damage will occur if it does. Check that the crankcase heater is operating correctly. Shut Off Valves All shut off valves must be opened prior to starting unit. Operation Electrical Power Supply The power supply to the unit must be correct to design. The three phase power must be of correct phase orientation. IMPORTANT Check phase rotation of electrical supply prior to running the compressor as the compressor is direction sensitive. Visual Inspection Check that the unit is of satisfactory condition and that it s not damaged. CAUTION A damaged component could indicate a reason why the unit is not operating. Refrigerant leaks etc. Electrical Overloads Check that circuit breakers are all turned on. If not investigate why they have tripped. This could be the reason why the unit is turned off. 8
9 Precision Air Conditioning EasiCool EZRE Unit Operation The unit must not be started unless the pre start checks have been carried out. As standard the units are supplied with a microprocessor controller connected to a back-lit LCD keypad display. The microprocessor controller can be linked together locally to provide run/standby operation. Windows based supervisor software is also available for local or remote networking. This modular approach provides great flexibility while at the same time reducing installation and maintenance costs Operation When more than one alarm is active the ALARM button will illuminate red. 1. ALARM Pressing the ALARM button once will indicate information regarding any active alarms. Pressing the ALARM button twice will reset any active alarms. Prg 2. PRG Pressing the PRG button will select the main navigation menu. Esc 3. ESC Pressing the ESC button will return the user to the main display screen showing unit status. Pressing the UP button can either: 4. UP 1.Scroll through the various display screens, providing the cursor is in the top left position. 2.Increase the value of a set point adjustment 5. ENTER Pressing the ENTER button will confirm any set point adjustments and move the cursor to the next available set point. Pressing the DOWN button can either: 6. DOWN 1.Scroll through the various display screens, providing the cursor is in the top left position. 2.Decrease the value of a set point adjustment. 9
10 Precision Air Conditioning EasiCool EZRE Display / Keypad The display keypad features a simple array of keys to navigate through the in built menus. With an 8 x 22 character (132 x 64 pixel) screen size, back lit in white for improved contrast, the larger screen provides for user friendly viewing and easy status recognition by displaying a combination of text and icons. Operation The default screen shows the unit status and room condition ( C/RH %) without the need for interrogation and an easy to navigate menu structure for further interrogation and adjustment. Standard Icons Fan operating Cooling - up to 2 stages Heating - up to 3 stages De-Humidification Humidification - Variable 10
11 Precision Air Conditioning EasiCool EZRE Navigation Prg Initially, use the button to access the main navigation menu, the cursor will appear in the top right hand corner with the first menu UNIT ON/OFF selected. Use the and buttons to move to the desired menu. The selected menu will be shown in BLOCK CAPITALS. Press to enter the selected menu. Navigation Sub Menus There are eight sub menu s available from the main navigation menu, these are listed below: 1 Unit On/Off Allows the user to switch on or switch off the unit. 2 Maintenance Allows the user to view maintenance related parameters, such as hours run, sensor calibration and manual overrides. 3 Alarm Log Allows the user to view the alarm log. 4 Input/ Output Allows the user to view the status of the controller inputs and outputs. 5 Clock Allows the user to view the current time, date and day of the week. On/Off and temperature time zones can also be set. 6 Set point Allows the user to adjust the return air temperature set point. Operation 7 User Allows the user to adjust user related parameters, such as high and low alarm limits and temperature bands. 8 Manufacturer Allows the user to enter the manufacturer menu and adjust various manufacturer related parameters, such as unit configuration and timing settings. 11
12 EasiCool EZRE Precision Air Conditioning Enabling the Unit To turn the unit on press the Prg key to enter the program menu. Using the and keys select the Unit On/Off option and press : Operation When is pressed the above screen will be shown. To turn the unit on simply press the key again and the screen will change: CAUTION The unit will be going through its start-up sequence. Pressing will turn the unit off. Once the screen has changed to the above press the Esc key which will return back to the main screen. 12
13 Precision Air Conditioning EasiCool EZRE Changing the Setpoint To change the setpoint of the unit from the main screen press the Prg button. Use the and to scroll to the setpoint option as shown below and press : The following screen will be shown: Operation Using the or button, scroll to the password screen. Enter the password 4648 using the and keys and press after each number is entered. (The numbers start at So down one to 4, up one to 6 etc). When the final number is entered the screen will jump to the set point adjustment screen: To adjust the setpoint press the key to highlight the set point, using the and keys enter the required setpoint and press the until the cursor returns to the top of the screen. 13
14 EasiCool EZRE Precision Air Conditioning Unit Operating Parameters Inputs and outputs can be located by the labels to the microprocessor controller. Operation Analogue Inputs Digital Inputs Analogue Outputs Digital Outputs X/WX Unit CW Unit B1 Return air humidity B1 Return air humidity B2 Condensing Pressure B2 Supply Air Temperature B3 Coil Temperature B3 Coil Temperature B4 Not Used B4 Not used B5 Return Air Temperature B5 Return air temperature B6 Not Used B6 Not used ID1 Remote on/off ID1 Remote on/off ID2 Airflow differential pressure switch ID2 Airflow differential pressure switch ID3 Critical Alarm ID3 Critical Alarm ID4 Overheat cut-out ID4 Overheat cut-out ID5 Not Used ID5 Not used ID6 Low pressure safety switch ID6 Not used ID7 Compressor 1 status alarm ID7 Not used ID8 Compressor 2 status alarm ID8 Not used Y1 Main Fan Speed Controller Option 2 / EC Fans Y1 Main Fan Speed Controller Option 2 / EC Fans Y2 Thyristor Heating Y2 Thyristor Heating Y3 Main Fan Speed Controller Option 1 Y3 Main Fan Speed Controller Option 1 Y4 Condenser Fan Speed Controller Y4 Chilled Water Valve NO1 Compressor 1 NO1 Open CW Valve NO2 Compressor 2 NO2 Close CW Valve NO3 Not Used NO3 Not Used NO4 HGRH / Heat Stage 1 / LPHW Valve Open NO4 Heat Stage 1 / Open LPHW Valve NO5 Heat Stage 2 / LPHW Valve Close NO5 Heat Stage 2 / Close LPHW Valve NO6 Heat Stage 3 NO6 Heat Stage 3 NO7 Not Used NO7 Not Used NO8 Common Alarm NO8 Common Alarm CAUTION Inputs or outputs not required will not be connected nor will they appear on the display keypad. SERVICE INDICATOR The maintenance of key components such as compressors, fans and air filters can be monitored via a service indicator which visually demonstrates the status relative to the component service intervals. Inputs and outputs can be located by the labels to the microprocessor controller. 14
15 Precision Air Conditioning EasiCool EZRE Operational Maintenance checks Owners Responsibility To ensure that the unit can be maintained correctly ensure the following requirements are met. Maintain a safe working environment around the unit, free from obstructions and debris. The unit shall follow the following maintenance regime as a minimum. CAUTION The equipment contains live electrical and moving parts, ISOLATE prior to maintenance or repair work. Ensure Lock off procedures are carried out accordingly. Maintenance 15
16 EasiCool EZRE Precision Air Conditioning Maintenance General Inspections General Inspections Task Check for visible mechanical damage to unit. Visually inspect the unit for general wear and tear, treat metalwork. Rust should be inhibited, primed and touched up with matching paint. Check for excess vibration from other rotating equipment. Frequency 3 Mths 12 Mths 60 Mths Service Tools / Test Equipment Safety Equipment Touch up paint Stiff Brush Safety Glasses / Goggles Gloves Procedures General Wear Visually inspect the equipment checking for signs of mechanical damage such as scratches etc. Treat with touch up paint avaliable from Airedale. Ensure adequate ventilation is avaliable when using solvents and paint. Maintenance Excess Vibration Check fans and rotating equipment for excess vibration. Be careful near rotating equipment. 16
17 Precision Air Conditioning EasiCool EZRE Maintenance Electrical Inspection Electrical Inspection Task Check main power supply voltages Check electrical terminals are tight. Check for signs of hot spots / discolouration on power cables. Check amperages are as per design. Frequency 3 Mths 12 Mths 60 Mths Service Tools / Test Equipment Voltmeter Screwdrivers / Allen Keys Ammeter Safety Equipment Safety Glasses / Goggles Procedures Electrical Connections Ensure all electrical connections are tight and correctly terminated. Electrical Earthing Check that the unit is correctly earthed. Voltage Measure the voltage at the following points and record on the maintenance sheet: Voltage at busbar Dedicated power supply Voltage at permanent supply Control voltage at transformer (min 22.5V, max 25V) The voltage measurements should be carried out with the unit MCB s turned off. EC Fan Interrogation The EC fans can be interrogated by connecting a hardware interface kit to the fan and PC. The kit comprises of a USB to RS232 9-pin D-type adapter. This should be installed on the PC with the software supplied with the kit. The COM port of the USB to RS232 adapter should be assigned to a free COM port between COM 1 and COM 4 via the system device manager. Maintenance Connect the RS232 to RS485 interface converter to the USB port of your PC via the USB to RS232 serial interface lead and connect the RS485 output to the fan. Tx += RS A Tx - = RS B 17
18 EasiCool EZRE Precision Air Conditioning Maintenance Refrigeration Refrigeration Task Compare the following and compare results with commissioning records. Suction, Liquid and Discharge pressures. Refrigeration system temperatures, Suction, Liquid and Discharge. Record superheat and sub cooling readings. Check each circuit sight glass for dryness and bubbles for indication of leaks. Head pressure control is maintained. Record details on F-Gas record. Check compressor oil level. Frequency 3 Mths 12 Mths 60 Mths Service Tools / Test Equipment Refrigerant Manifold gauges Spanners Voltmeter Safety Equipment Safety Glasses / Goggles Gloves Overalls Procedures HP / LP Safety Pressure Switch Settings Check operating of HP / LP cut-out, Settings Maintenance LP cut-out (Manual reset) Has a 2 minute delay on start-up (similar to a Low ambient kit) plus 60 second run delay. Low pressure cut-out 1.5 +/- 0.2 Barg HP switch (manual reset): High pressure switch bar +/- 1 Barg Compressor Oil Level (Full load) Check the compressor oil level at full load. (record oil level) 18
19 Precision Air Conditioning EasiCool EZRE Maintenance Waterside Waterside Task Check pressure drop of water strainer. If excessive clean the strainer. Visually inspect pipe and pipework insulation. Pipework clamps are secure. Inspect for water leakage. Check condition of Water / Glycol solution to ensure that the system is protected against corrosion, scale and microbiological fouling, ensuring maximum heat transfer efficiency. Frequency 3 Mths 12 Mths 60 Mths Service Tools / Test Equipment Spanners Manometer Thermometer Refractometer Safety Equipment Safety Glasses / Goggles Gloves Overalls Procedures Binder Points Binder points should be fitted to both the flow and return pipe work adjacent to the cooling coil. Water Strainer A water strainer must be fitted to the inlet side of the evaporator. Failure to do so may result in severe damage and will void the AIREDALE warranty. Water Flow Rate Check that the design water flow rate is available to the unit. If not available do not turn unit on. Waterside Pressure Drop Measure the waterside pressure drop of the unit ensuring control valves are operating satisfactory. Maintenance Glycol Strength Check and record the glycol type and strength. Low levels of glycol can cause freeze up problems when operating at low temperatures or during the unit off state during cold ambient conditions. Glycol concentration is measured by use of a Refractometer. 19
20 EasiCool EZRE Precision Air Conditioning Maintenance Controls Controls Task Change controller battery. The controller will keep the strategy for a short period of time with no battery. Frequency 3 Mths 12 Mths 60 Mths Service Tools / Test Equipment Small Terminal Screwdriver Safety equipment Electrostatic Wristband Procedures The following controller settings are to be recorded on the maintenance sheet: Return air setpoint ( C) Return air humidity setpoint (%RH) Superheat setpoints ( C) Head pressure setpoint (Bar) Compressor hours run Unit hours run Maintenance 20
21 Precision Air Conditioning EasiCool EZRE Maintenance System System Task Check the following against the commissioning records. Record operating conditions. Water on / off temperatures. Water pressure drop. Frequency 3 Mths 12 Mths 60 Mths Unit Operation Checks Record the following operating conditions of the unit at stable conditions: Suction pressure (Bar) Superheat ( C) Liquid pressure (Bar) Sub cooling ( C) Discharge pressure (Bar) Water return temperature ( C) (CW Units) Suction temperature ( C) Water supply temperature ( C) (CW units) Liquid temperature ( C) Return air temperature ( C) Discharge temperature ( C) Return air humidity (%RH) Liquid line sight glass Record the status of the liquid line sight glass Clear / Flashing Wet / Dry The sight glass is used to indicate: The condition of the refrigerant in the system Lack of refrigerant Moisture content of the refrigerant The colour of the sight glass depends on the moisture content of the refrigerant. The recommended moisture levels of a system should be below 75ppm. An indication of green / dry are to be considered as perfect conditions meaning full protection by the filter drier against effects from moisture. If the green colour starts to fade, the colour change from green to yellow has begun and the indicator should therefore be watched carefully. If the colour changes to yellow it is a clear signal that the capacity of the filter drier is exceeded and should be replaced as soon as possible. F-Gas Leak Detection Checks Perform an F-Gas refrigerant leak detection on the unit and ensure no refrigerant leaks are visible. Maintenance 21
22 EasiCool EZRE Precision Air Conditioning Troubleshooting General Faults POSSIBLE CAUSE REMEDY / ACTION No power to compressor. Check isolator, fuses, MCBs, contactor and control circuit wiring. Seized compressor, possibly due to lack of oil, broken valve. Replace compressor - investigate oil trapping and general installation. Compressor not operating. Defective compressor motor. Compressor phase loss. Check winding resistances - replace compressor. If burnt out follow burn out procedure using suction line burn-out drier. Check 3 phase supply to compressor. Klixon out and does not reset. Sometimes it takes up to 4 hours to reset. Replace compressor if necessary. Low pressure switch operated (large or complete loss of refrigerant charge). Repair leak and recharge system - if completely out evacuate before charging. Condenser fan motor thermal trip open circuit. Investigate and correct. Noisy compressor. Lack of oil. Repair leaks if any, add oil if required but not too much - remember too much is as bad as too little. Investigate pipe system and trapping. Best method to pump down to see if oil can be encouraged back. If no oil still, drain compressor and measure in correct quantity. Expansion valve stuck in open position (abnormally cold suction Iine). Ensure bulb is tight on suction and superheat is correct (normally 5 to 6 C). Replace power assembly or valve as necessary. Damaged or worn compressor bearing (excessive knocking). Replace compressor. Condenser coil clogged or dirty. Clean condenser coil. Air or other non-condensable gas in system. Evacuate system and re-charge with new refrigerant. Head pressure too high. Overcharge of refrigerant. Always install new drier before evacuating. Reclaim excess refrigerant from system (liquid only). Head pressure controller faulty. Check fan speed controller - if faulty - replace. Fan not operating or operating inefficiently. Check motor - if faulty - replace. Head pressure too low. Fan operating too fast in low ambient conditions. Check fan speed controller adjustment - if faulty - replace. Dirty filters. Replace. Dirty or icing evaporator (reduced airflow). Defrost and/or clean. Check gas charge and expansion valve. Lack of refrigerant (bubbles in sight glass only as indication). Check for leaks - repair and recharge system. Troubleshooting Compressor short cycles or LP cut-out operated. Clogged filter drier (pressure / temperature drop across it). Condenser fan running at full speed in winter (full airflow). Start up problems in very low ambients. Replace. Check fan speed controller setting - if faulty - replace. Check for low suction pressures on start-up and fit a low ambient start kit if required, or check operation of system if already fitted. 22
23 Precision Air Conditioning EasiCool EZRE Troubleshooting FAULT POSSIBLE CAUSE REMEDY / ACTION Depending on model: Low evaporator airflow. Check fan motor speed set point or Check fan motors, belts and drives Suction pressure too low. Condenser fan not operating - power on. Condenser fan runs too fast. Condenser fans runs only slowly. Flash gas (bubbles in sight glass) at expansion valve. Clogged filter drier (pressure / temperature drop across it). Obstruction in expansion valve. Motor / fan assembly jammed. Fault at motor terminal box supply terminals. Motor internal overheat protector tripped. Power supply failure. Wiring to motor. Faulty motor windings / capacitor. Minimum speed set too low. Faulty pressure sensor. Faulty Controller. High ambient condition or excessive recirculation of air around condenser coil. Minimum set speed setting incorrect. Incorrect pressure setting. Faulty Fan Speed Controller. Faulty pressure sensor. Motor wired incorrectly. Motor / capacitor faulty. Investigate for refrigerant leaks, repair and re-charge system. Replace. Inspect, clean or replace. Isolate unit and check free rotation of motor / fan assembly. If faulty - replace. Isolate and check electrical connections are secure. Carry out continuity check at terminals TK in motor terminal box. If tripped and motor hot - check bearings. If tripped and motor cold - replace motor. Check power supply at circuit breaker. Check voltage at motor terminals. Motor humming would indicate fault in motor or capacitor. Adjust head pressure controller to suit. Check electrical connections are secure at controller and pressure sensor. Replace controller and sensor (as they are matched sets). Link wires line and load to bypass controller. If motor runs full speed - replace unit. Check installation against design. Adjust as necessary. Adjust sensor screw as necessary. Replace controller and sensor (as they are matched sets). Replace controller and sensor (as they are matched sets). Check against wiring diagram - correct as required. Replace. Troubleshooting 23
24 EasiCool EZRE Precision Air Conditioning Troubleshooting Suction Throttle Valve (STV) (Optional Extra) FAULT POSSIBLE CAUSE REMEDY / ACTION Suction pressure too low. Suction throttle valve fully shut. Check valve opens fully at 100% cooling demand. Inspect, clean or replace. Check suction throttle valve operation. Inspect, clean or replace. Suction throttle valve in operation. Open suction throttle valve to High discharge temperature. reduce discharge temperature. High compressor superheat. Cooling output insufficient. Large or complete loss of refrigerant charge. Suction throttle valve shut. Large or complete loss of refrigerant charge. Suction throttle valve in operation. Investigate for refrigerant leaks, repair and re-charge system. Check suction throttle valve operation. Inspect, clean or replace. Investigate for refrigerant leaks, repair and re-charge system. Check supply air setpoint and unit cooling demand. Hot Gas Re-Heat (HGRH) (Optional Extra) FAULT POSSIBLE CAUSE REMEDY / ACTION Cooling output insufficient. Hot gas re-heat coil in operation. Check cooling demand and ensure hot gas re-heat valve is closed. Check hot gas re-heat valve operation. Inspect, clean or replace. Re-heat output insufficient. Faulty hot gas re-heat valve. Check hot has re-heat valve operation. Inspect, clean or replace. Humidifier (Optional Extra) Troubleshooting FAULT POSSIBLE CAUSE REMEDY / ACTION Main fuses / MCB trips when initially switched on. Cylinder damage (shorted electrode(s). Test with Megger - Replace cylinder. Humidifier called for but not filling. Water not available at cylinder. Check all mains cold water valves. Check any strainers fitted. Check inlet solenoid valve (yellow) strainer - clean as necessary. Inlet water solenoid not operating - check for feed. Replace solenoid / control board as necessary. Mains water pressure over 8 Bar - fit pressure reducing device. Too high steam delivery back pressures. Check steam delivery pipe is not blocked with debris. Cylinder inlet filter clogged. Clean the filter. The humidifier loads with water but does not produce steam. Limescale inside the supply tank. Clean the supply tank. Check 24 Vac anomalous presence Drain solenoid valve faulty. on the drain solenoid valve and/or replacement of drain solenoid valve. Supply or overflow hydraulic circuit leaking. Check the entire hydraulic circuit. The humidifier wets the underlying floor. Steam delivery pipe not properly fastened to the cylinder. Check fastening of the clamp on the steam delivery pipe. Cylinder operating - Low Current / Low output. Humidifier in start-up phase. Cylinder nearing end of useful life. Wait for impurity concentration to build up through natural drain cycle. This will allow an increase in passed current. Strip and clean or replace. 24
25 Precision Air Conditioning EasiCool EZRE Alarms Alarm Menu Display Alarm Number Alarm Name Alarm Status Time Date Alarm Log The alarm page offers a log of the last 100 alarm messages in a scrolling log, pressing the alarm button will enter the alarm page. Consequently the most recent alarm has the lowest log number (001) and will be displayed upon entering the alarm page. As another alarm occurs, the alarm number increases until 100 alarms have occurred. From this point on, alarm 001 moves to 002 and any new alarm will reside in position 001. As new alarms are generated and cleared, the highest number logs (100) in the scroll will be lost. Viewing the Alarm Log By using the arrow keys, the last 100 alarms generated can be reviewed in chronological order. The display provides the alarm type information and the time and date of each alarm occurrence. Alarm Detection When the controller detects an alarm an output is generated to the relevant alarm relay which in turn illuminates the button. To see which alarm has accrued press the button and the most recent alarm will be displayed. If the alarm light is on, the alarm page can be interrogated to identify which alarm is active. Resetting the Alarm The auto reset alarms will automatically reset once the conditions are within the set parameters. To clear a manual alarm press the button twice and the red LED will disappear. Troubleshooting 25
26 EasiCool EZRE Precision Air Conditioning Alarm Codes Alarm 1: Airflow Failure This alarm indicates that the airflow switch has not detected any airflow for 60 seconds when the main fan has been switched on. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 2: Critical Alarm This alarm indicates that a critical alarm has occurred and the unit has shutdown. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 3: Overheat Cut-out This alarm indicates that the auto overheat cut-out(s) has tripped and has switched off all stages of electric heating. This alarm is auto reset within the controller. Alarm 4: Low Pressure This alarm indicates that the low pressure safety switch has tripped and the controller has switched off DX cooling. This alarm is manual reset and can be cleared by referring to resetting the Alarm.. Alarm 5: Condensing Unit Trip This alarm indicates that the condensing unit has tripped. During this alarm the controller will switch off DX cooling. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 6: Compressor 1 Trip This alarm indicates that compressor 1 contactor did not close within 5 seconds of the compressor 1 output switching on. This alarm can be triggered by either one or more of the following conditions; high pressure safety switch, discharge gas thermostat or thermal cut-out protection. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 7: Compressor 2 Trip This alarm indicates that compressor 1 contactor did not close within 5 seconds of the compressor 1 output switching on. This alarm can be triggered by either one or more of the following conditions; high pressure safety switch, discharge gas thermostat or thermal cut-out protection. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 8: Filter Change This alarm is generated after the main fan has operated for 1500 hours and indicates the air filters should be cleaned or replaced. This alarm is manual reset and be cleared after filter maintenance by referring to resetting the Alarm. Alarm 9: Return Humidity Fault This alarm indicates that the return air humidity sensor is not operating correctly. During this alarm the controller disables all humidification and dehumidification outputs. When the sensor is operating normally the alarm will auto reset and the controller will enable humidification and dehumidification. Alarm 10: Condensing Pressure Fault This alarm indicates that condensing pressure sensor is not operating correctly. During this alarm the controller will operate the condenser fan at full speed. When the sensor is operating normally the alarm will auto reset and the controller will resume normal head pressure control. Troubleshooting Alarm 11: Return Temperature Fault This alarm indicates that the return air temperature sensor is not operating correctly. During this alarm the controller disables all heating and cooling outputs. When the sensor is operating normally the alarm will auto reset and the controller will enable heating and cooling. Alarm 12: Coil Temperature Fault This alarm indicates that the coil temperature sensor is not operating correctly. When the sensor is operating normally the alarm will auto reset. Alarm 13: High Return Temperature This alarm indicates that the return air temperature has exceeded the return air temperature high limit. To prevent nuisance alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the return air temperature is below the high limit the alarm is auto reset within the controller. 26
27 Precision Air Conditioning EasiCool EZRE Alarm 14: Low Return Temperature This alarm indicates that the return air temperature has exceeded the return air temperature low limit. To prevent nuisance alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the return air temperature is above the low limit the alarm is auto reset within the controller. Alarm 15: High Return Humidity This alarm indicates that the return air humidity has exceeded the return air humidity high limit. To prevent nuisance alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the return air humidity is below the high limit the alarm is auto reset within the controller. Alarm 16: Low Return Humidity This alarm indicates that the return air humidity has exceeded the return air humidity low limit. To prevent nuisance alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the return air humidity is above the low limit the alarm is auto reset within the controller. Alarm 17: Hours Limit Compressor 1 This alarm indicates that the running hours of compressor 1 have exceeded the hours run threshold. This alarm is for maintenance use only and the compressor will continue to operate. Before attempting to reset this alarm, the running hours of compressor need to adjusted below the hours run threshold. Then this manual reset alarm can be cleared by referring to resetting the Alarm. Alarm 18 Hours Limit Compressor 2 This alarm indicates that the running hours of compressor 2 have exceeded the hours run threshold. This alarm is for maintenance use only and the compressor will continue to operate. Before attempting to reset this alarm, the running hours of compressor need to adjusted below the hours run threshold. Then this manual reset alarm can be cleared by referring to resetting the Alarm. Alarm 19: Hours Limit Main Fan This alarm indicates that the running hours of the main fan have exceeded the hours run threshold. This alarm is for maintenance use only and the main fan will continue to operate. Before attempting to reset this alarm, the running hours of main fan need to adjusted below the hours run threshold. Then this manual reset alarm can be cleared by referring to resetting the Alarm. Alarm 20: Hours Limit Humidifier This alarm indicates that the running hours of the humidifier have exceeded the hours run threshold. This alarm is for maintenance use only and the humidifier will continue to operate. Before attempting to reset this alarm, the running hours of humidifier need to reset. Then this manual reset alarm can be cleared by referring to resetting the Alarm. Alarm 21: Clock Faulty This alarm indicates that the controller s real time clock is not operating correctly. During this alarm any time zones setup would be ignored. When the clock is operating normally the alarm will auto reset and the controller will resume any time zones previously set-up. Alarm 22: LAN Disconnected This alarm indicates that there is a network communications fault between one or more units. If the unit is configured as standby, the unit will automatically start-up and continue to operate until the network communications fault has been rectified. This alarm is auto reset. Alarm 23: High Pressure This alarm indicates that the condenser pressure has exceeded the condenser high limit and DX cooling has switched off. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 24: Frost Protection This alarm indicates that the controller has disabled DX cooling to prevent frost damaging the heating coil. This alarm is auto reset. Alarm 25: High Conductivity Alarm This alarm indicates that the mains water supply conductivity has exceeded the high conductivity limit and the humidifier has been disabled. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Troubleshooting 27
28 EasiCool EZRE Precision Air Conditioning Alarm 26: High Conductivity Warning This alarm indicates that the mains water supply conductivity has exceeded the warning conductivity limit, the humidifier is still allowed to operate. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 27: High Current Humidifier This alarm indicates that the humidifier has a high operating current. During this alarm the humidifier will be switched off. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 28: Low Current Humidifier This alarm indicates that the humidifier has a low operating current, suggestion the cylinder needs replacing or cleaning. During this alarm the humidifier will be switched off. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 29: Lack Water Humidifier This alarm indicates that the humidifier has not measured any current during the fill cycle and hence determined that no water has entered the humidifier. During this alarm the humidifier will be switched off. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 30: Low Production Humidifier This alarm indicates that the humidifier has not reached its required steam production. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 31: Drain Alarm Humidifier This alarm indicates that the humidifier cannot drain the water from the cylinder. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 32: Humidifier Full This alarm indicates that the water level within the cylinder has reached the high level electrodes. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 33: Pre-exhaustion Humidifier This alarm indicates that the cylinder needs to be replaced. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 34: Foam In The Humidifier This alarm indicates that foam or bubbles have been detected within the cylinder. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 35: Exhaustion Humidifier This alarm indicates that the cylinder has ceased working and needs to be replaced. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 36: Probes Error Driver This alarm can be triggered by either a suction pressure transducer fault or a suction line temperature sensor fault. During the alarm the electronic expansion valve is closed and compressor 1 is switched off. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Troubleshooting Alarm 37: EEPROM Error Driver This alarm indicates that there has been an error between the data stored in the EEPROM memory and the data stored in the controller. During the alarm the electronic expansion valve is closed and compressor 1 is switched off. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 38: Stepper Motor Error Driver This alarm indicates that there has been an electrical fault with the electronic expansion valves stepper motor. During the alarm compressor 1 is switched off. This alarm is manual reset and can be cleared by referring to resetting the Alarm. 28
29 Precision Air Conditioning EasiCool EZRE Alarm 39: Battery Error Driver This alarm indicates that the battery is not recharging correctly or storing electrical charge. This alarm is manual reset and can be cleared by referring to resetting the Alarm.. Alarm 40: MOP Alarm Driver This alarm indicates that the evaporating temperature has exceeded the MOP limit. During the alarm the electronic expansion valve driver modulates the valve closed to reduce the operating pressure, still maintaining the super heat. This alarm is auto reset. Alarm 41: LOP Alarm Driver This alarm indicates that the evaporating temperature has exceed the LOP limit. During the alarm the electronic expansion valve driver modulates the valve open to increase the operating pressure, still maintaining the super heat. This alarm is auto reset. Alarm 42: Low Super Heat Alarm Driver This alarm indicates that the super heat has exceeded the low super heat limit. During the alarm compressor 1 is switched off. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 43: High Suction Temperature Alarm Driver This alarm indicates that the suction temperature sensor has exceeded the high suction temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm. Alarm 44: Valve Not Closed Driver This alarm indicates that the electronic expansion valve was not closed when the power was restored. During this alarm compressor 1 is switched until the alarm is reset. This alarm is manual reset and can be cleared by referring to Resetting the Alarm. Alarm 45: Supply Air Temperature Sensor Fault This alarm indicates that the supply air temperature sensor is not operating correctly. During this alarm the controller will disable supply air limiting, if enabled. When the sensor is operating normally the alarm will auto will resume reset and the controller supply air limiting, if enabled. Alarm 45: High Supply Air Temperature Alarm This alarm indicates that the supply air temperature has exceeded the supply air temperature high limit. To prevent nuisance alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the supply air temperature is below the high limit the alarm is auto reset within the controller. Alarm 46: Low Supply Air Temperature Alarm This alarm indicates that the supply air temperature has exceeded the supply air temperature low limit. To prevent nuisance alarms on initial fan start-up, the alarm is delayed for 2 minutes. When the supply air temperature is above the low limit the alarm is auto reset within the controller. Alarm 48: Discharge Temperature 1 Sensor Fault This alarm indicates that the Discharge temperature sensor is not operating correctly. During this alarm the controller will disable compressors, if enabled. When the sensor is operating normally the alarm will auto resume reset. Alarm 49: Discharge Temperature 2 Sensor Fault This alarm indicates that the Discharge temperature sensor is not operating correctly. During this alarm the controller will disable compressors, if enabled. When the sensor is operating normally the alarm will auto resume reset. Alarm 50: Fire / Smoke Alarm This alarm indicates that a Fire/Smoke alarm has occurred and the unit has shutdown. This alarm is manual reset. Troubleshooting Alarm 51: Water Flood Alarm This alarm indicates that the water has been detected by the unit and the unit has shutdown. This alarm is manual reset. 29
30 EasiCool EZRE Precision Air Conditioning Alarm 52: Phase Failure When the phase failure is detected, the unit will shut down and the alarm will be indicated on the display and circuit 1 and 2 alarm relays. The alarm will auto reset when alarm condition is cleared. The unit will restart after the delay on period has elapsed Alarm 53: Warning Cylinder 1 Maintenance This alarm indicates that the cylinder operating hours have exceeded. The warning can be reset by the operation hour s counter. Alarm 54: Alarm Cylinder 1 Maintenance This alarm indicates that the cylinder maximum operating life has been exceeded and the bottle needs replacing. Alarm 55: Warning Compressor 1 High Discharge Temperature This alarm is a warning that indicates the discharge temperature sensor is close to the high discharge temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 56: Compressor 1 High Discharge Temperature This alarm indicates that the discharge temperature sensor has exceeded the high discharge temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 57: Warning Compressor 1 Low Discharge Temperature This alarm is a warning that indicates the discharge temperature sensor is close to the low discharge temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 58: Compressor 1 Low Discharge Temperature This alarm indicates that the discharge temperature sensor has exceeded the low discharge temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 59: Warning Compressor 2 High Discharge Temperature This alarm is a warning that indicates the discharge temperature sensor is close to the high discharge temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 60 Compressor 2 High Discharge Temperature This alarm indicates that the discharge temperature sensor has exceeded the high discharge temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 61: Warning Compressor 2 Low Discharge Temperature This alarm is a warning that indicates the discharge temperature sensor is close to the low discharge temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 62: Compressor 2 Low Discharge Temperature This alarm indicates that the discharge temperature sensor has exceeded the low discharge temperature limit. This alarm is manual reset and can be cleared by referring to resetting the Alarm Alarm 63: Driver 1 LAN Disconnected This alarm indicates that the system cannot detect a connection to EEV driver 1. Troubleshooting Alarm 64: Bottle Change Alarm This alarm indicates that the cylinder needs to be changed when a vapac humidifier is selected. Alarm 65: Unit Switched Off By Display This alarm indicates that the unit is turned off by the display, the unit can be turned on in the programming section of the controller. Alarm 66: Maintenance Required (Mn) The Mn alarm occurs when the life timer within the CPY board is greater than 1.5 times the user s maintenance life time. 30
31 Precision Air Conditioning EasiCool EZRE This is defaulted to 4500 hours of operation. The cylinder may need cleaning or replacing at this stage. Alarm 67: High Supply Water Conductivity (EC) This alarm implies the water entering the humidifier cylinder has high conductivity. If the water continues to have high conductivity the humidifier will stop production. Alarm 68: Configuration Parameters Corrupt (E1) This alarm is associated with the parameters within the CPY when they become corrupted. This will stop the humidifier from working correctly. Alarm 69: Internal Error (E0) This alarm is similar to the alarm 68, it is associated with the internal memory within the device. This will cause humidification to stop. Alarm 70: High Current (EH) This alarm will be active when the CPY detects a high electrode current, a current higher than the maximum limits. The humidifier will cut power from the electrodes and drain the cylinder. Alarm 71: Low Steam Production (EP) The CPY estimates the steam production rate using the current drawn by its electrodes. If this steam production rate is lower than what it expects this alarm will be activated. Alarm 72: High Water Level with no Humidification Demand (EU) This alarm occurs when the humidifier is effectively switched off however there is a high water level within the cylinder. Usual the result of a faulty fill valve. Alarm 73: External Control Signal Fault (E3) This alarm is active when there is no external control signal connected to the CPY Board. This signal can be a 0-10V connection or a serial connection depending on the circuit setup. Alarm 74: Lack of Supply Water (EF) This alarm occurs when the CPY Board tries to add water but the level doesn t increase within the cylinder. This level is estimated by the TAM circuit as the current will increase as the water content increases. Alarm 75: Drain Fault (Ed) This signals there is a fault with the drain, either the pump has become blocked or is not working correctly. Alarm 76: Maintenance Time Expired (CY) This alarm signals that the maintenance time has expired and the cylinder may need cleaning or replacing. The maintenance period is defaulted to 3000 operating hours. Alarm 77: Foam in Humidifier Cylinder (EA) This alarm is active when the CPY Board constantly has its high water level sensor active. This means that there is foam in the cylinder which keeps triggering a high water level alarm. If the water added to the cylinder is too soft it can cause the cylinder to foam. Alarm 78: Humidifier Cylinder Requires Clean (CP) Lime scale can build up on the electrodes as water is boiled and minerals are left behind. This can limit the amount of steam being produced, this alarm will be active when the CPY realises this. Alarm 79: Replace Humidifier Cylinder (CL) This alarm is active 3 hours prior to the bottle being completely depleted. The Cylinder is full of flakes and cannot operate to the required standard anymore, it needs replacing. Alarm 80: CPY Device Offline When there is no active connection over the serial bus the CPY will pco will display this alarm. Troubleshooting Alarm 81: Serial Disconnected (Su) When there is no demand sent over the serial connection this alarm is displayed. 31
32 EasiCool EZRE Precision Air Conditioning Troubleshooting 32
33 Precision Air Conditioning EasiCool EZRE Troubleshooting 33
34 Head Office Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY Tel: +44 (0) Fax:+44 (0) Web OM_ _Easicool_EZRE_SCROLL_V1.0.0_02_2013
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
PANASONIC TROUBLE SHOOTING GUIDE
A General Guide To Room Style Products Pipework Pipe sizes and lengths should be as the relevant Technical Guide Both lines should be insulated No line accessories or oil traps should be fitted In cooling
Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty
Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents
Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook
National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.
THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you
Bradlee Boilers Ltd. Instruction Manual for starting up Bradlee Hire Boiler from Cold
Bradlee Boilers Ltd Instruction Manual for starting up Bradlee Hire Boiler from Cold To be read in conjunction with Bradlee Boiler guide to Commissioning Boilers Document Ref: HM001 1. Ensure that all
Heat Pump Water Heater IOM Manual
Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump
14. Troubleshooting Guide
14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include
R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Trouble Shooting. Pump
Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
10 tips for getting more reliability from your air-conditioning system [reliability]
10 tips for getting more reliability from your air-conditioning system [reliability] A guide for installers, specifiers, contractors and architects February 2010 10 tips for getting more reliability from
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
Refrigerant Charging Unit ICOGD. 020AH1000 Operating Manual. FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00
E Refrigerant Charging Unit ICOGD 020AH1000 Operating Manual FR.8.2.4-09 İ-COLD 12.03.2014 Rev. 00 Contents Technical Specifications... 20 Safety... 21 A/C System... 22 Components... 23 Control Panel...
LOBOY 16 AIR CONDITIONERS
INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps
A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
Technical Information
Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1
Liebert Deluxe System/3
Precision Cooling For Business-Critical Continuity Liebert Deluxe System/3 Operation and Maintenance Manual 50 and 60 Hz, 6-30 Ton DX Systems (DH/DE/VH/VE); 12-60 Ton CW Systems (FH/UH) TABLE OF CONTENTS
Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify
Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2
Air Conditioner Water Heater - A Product of HotSpot Energy LLC
Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR
USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting
MP-4000 Alarm List (Software version 2.4.3 or later)
Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
SMM. Installation Operation Maintenance
SMM Configuration SMM Module for Scroll Units, H Generation Installation Operation Maintenance 1 0 L80 IM 022 GB SMM Configuration SMM Module for Scroll Units, H generation Foreword These installation,
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Faults on refrigeration systems, general...3 Fault location without the use of instruments...3 Categorisation...3
Meaco 30L and Meaco 40L dehumidifier instruction manual
Meaco 30L and Meaco 40L dehumidifier instruction manual Please read this instruction manual before using the dehumidifier and keep safe for future reference SAFETY INSTRUCTIONS PLEASE READ ALL INSTRUCTIONS
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W
MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS
SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications
NetworkAIR FM Precision Air Conditioner. Operation and Maintenance
NetworkAIR FM Precision Air Conditioner Operation and Maintenance Contents Operation...1 Display Interface.................................... 1 Using the Display................................... 2
MAINTENANCE INSTRUCTIONS. Thermia Robust heat pump
MAINTENANCE INSTRUCTIONS Thermia Robust heat pump 9 6 8 0-5 4 7 4 5 0 0 1 R e v. 3 Table of contents 1 Important information.................. 2 1.1 Product description....................... 2 1.2 General................................
SmartCool Downflow Precision Air Conditioning R410A
SmartCool Downflow R410A Installation, Maintenance and Commissioning SmartCool TM - D About Airedale Products & Customer Services Warranty All AIAC products or parts (non consumable) supplied for installation
User Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
COMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system
AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and
CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)
CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive
COMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
Aerosphere Midibus. Air Conditioning System. Operation Manual. Aerosphere Midibus 05/2013 P.N. 10000038A
Air Conditioning System Operation Manual Aerosphere Midibus 05/2013 P.N. 10000038A To receive the best performance from the air conditioning system, we suggest carefully reading this manual before operating
with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.
B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat
Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage
SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit
SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS
ON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units.
R Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL for SPLIT SYSTEM Bus Air Conditioning Units T--326 Rev -- OPERATOR S MANUAL BUS AIR CONDITIONING UNITS GEN IV & GEN V CONTENTS
Water Priming Mode Purge air from plumbing system. How do I solve ER-3 WATER PRIME: TIPS ON FILLING SPA IMPORTANT NOTE WARNING
Water Priming Mode Purge air from plumbing system TIPS ON FILLING SPA Before filling remove spa skirt and be sure that all valves in the plumbing system are fully open to maximise the amount of air that
USER S MANUAL HSC-24A
AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL
Si10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06
A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner
ECOCIAT. Domestic hot water heat recovery unit
Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY
! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)
Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
4 Alarm and info. Alarm. Yes Warning. No Information No Reset alarms > No Current list > Alarm log list > Delete alarm log > No
6. 6.1 and info (Menu 4) NB are shown in the event of unit faults or irregular operation Check the Current list (Menu 4) for alarm messages and refer to the list of alarms given at the end of these instructions.
Operating instructions
6302 6959 02/2006 GB For the user Operating instructions Logano G215 WS Oil and gas-fired boilers Please read thoroughly before use. Overview Regulations and directives Installation: 90/396/EEC gas appliance
FOXAIR 60/50 ALL MODELS
FOXAIR 60/50 ALL MODELS OPERATION AND SERVICE MANUAL UNIT WEIGHT - ALL MODELS APPROX. 300 POUNDS FOXTRONICS, INC. 38 L x 28 W x 24 H Love Field-Dallas TX MADE IN THE USA 3448 West Mockingbird Lane Dallas,
COMPTROL 5000 INDEX 52. Issue 5.99 AIR CONDITIONING MICROPROCESSOR OPERATING INSTRUCTIONS. STULZ GmbH, Hamburg
COMPTROL 5000 INDEX 52 Issue 5.99 AIR CONDITIONING MICROPROCESSOR STULZ GmbH, Hamburg OPERATING INSTRUCTIONS Contents Page INTRODUCTION... 4 NOTES ON SAFETY... 4 PAGE CODE... 4 DESCRIPTION OF THE CONTROLLER...
Condensing unit type EPSILON-ECHOS LE Technical information manual
Condensing unit type EPSILON-ECHOS LE Technical information manual 2 > EPSILON ECHOS Water chiller > EPSILON ECHOS /HP Reversible heat pump > EPSILON ECHOS /ST Water chiller with storage tank and pumps
CC145. Air Conditioning System. Operation Manual. CC145 Compact Cooler 4/2013 P.N. 10000034A
Air Conditioning System Operation Manual CC145 Compact Cooler 4/2013 P.N. 10000034A To receive the best performance from the air conditioning system, we suggest carefully reading this manual before operating
Online UPS. PowerWalker VFI 1000R/1U
Online UPS PowerWalker VFI 1000R/1U Manual Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4.
User's Guide. CTS6000 WebControl
User's Guide CTS6000 WebControl Version 1.01, 29.06.2010 Contents Contents... 2 List of figures... 3 Introduction... 4 Introduction to CTS6000... 4 Reading instructions... 4 Quick startup... 5 Daily operation...
Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.
Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,
Vertical Display and Storage B1350-2. SKOPE Gen2: Three Door Chiller
Vertical Display and Storage User Manual MAN1227 Rev. 3.0 March 2008 edition CONTACT ADDRESSES Designed and Manufactured by New Zealand SKOPE INDUSTRIES LIMITED PO Box 1091, Christchurch New Zealand Freephone:
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW
Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer
ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user
For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
T-Series Air Conditioner T62 Model
INSTRUCTION MANUAL T-Series Air Conditioner T62 Model Protecting Electronics. Exceeding Expectations. McLean Cooling Technology 11611 Business Park Blvd N Champlin, MN 55316 USA Tel 763-323-8200 Fax 763-576-3200
Chilled Water Precision Air Conditioner For Critical Application
AIRSYS-P-SC-OPTIMA-HD-E1304V01.2 HD Chilled Water Precision Air Conditioner For Critical Application Cooling capacity: 42.1kW~161.5kW OPTIMA product family is designed for medium to large data center.
Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS
Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar
prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2008-36 TSG-PRESTIGE Date revised: 12/6/10
prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 12/6/10 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1-2 SERVICING TIPS AND INSTRUCTIONS Page 3-4
Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W
Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support
Single Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems
Universal Split Systems If there is a fault on any LG Universal unit, a two digit number will appear on the remote controllers led display. If the unit does not have a remote controller the fault will
How to read this guide
How to read this guide The following shows the symbols used in this Quick start guide with descriptions and examples. Symbol Description Example P oint Reference Caution [ ] This symbol explains information
PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167
PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION
SUGGESTED GUIDELINES FOR REFRIGERATION PLANT MAINTENANCE
SUGGESTED GUIDELINES FOR REFRIGERATION PLANT MAINTENANCE SEPTEMBER, 2003 ONTARIO RECREATION FACILITIES ASSOCIATION INC. 1185 EGLINTON AVENUE EAST, SUITE 402 NORTH YORK, ONTARIO CANADA M3C 3C6 T.416.426.7062
Help. Help Software Tutorial. Building a load sizing project with an ME Series Humidifier
Help Help Software Tutorial Building a load sizing project with an ME Series Humidifier 502-B 18 Aug 2015 Help Tutorials provide step-by-step examples of complete load sizing projects and browser projects
User manual. 086U6297 Rev. 9 EN
User manual Atria Atria Duo Atria Duo Optimum Atria Optimum Comfort Diplomat Diplomat Duo Diplomat Duo Optimum Diplomat Duo Optimum G2 Diplomat Optimum Diplomat Optimum G2 086U6297 Rev. 9 EN Thermia Värme
PBX Series Quick Fit Connector Bimetallic Steam Traps
6262100/6 IM-P626-01 ST Issue 6 PBX Series Quick Fit Connector Bimetallic Steam Traps Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning
sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved
Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section
To suit Daikin FDY "F" Series and FD "F" Series. (and other models incorporating BRC1B62/52 Remote Controller)
OPERATION MANUAL Split System Ducted Air Conditioner To suit Daikin FDY "F" Series and FD "F" Series AIR CONDITIONER A hr o C (and other models incorporating BRC1B62/52 Remote Controller) Dear Owner, Thank
Aerona Air Source Heat Pumps
ADDENDUM to INSTALLATION INSTRUCTIONS for Aerona Air Source Heat Pumps DOC.87-05/05 Rev.04 March 2013 ATTENTION INSTALLERS - UPDATED INFORMATION! Your Grant Aerona Air Source Heat Pump has a number of
MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS
MAKING MODERN LIVING POSSIBLE UniLynx Indoor User Manual ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS Contents Contents 1. Introduction 2 Introduction 2 2. Function Description 3 Definition
DEFROSTING. Service Engineers Section Technical Bulletin No 3
Service Engineers Section Technical Bulletin No 3 DEFROSTING 1. INTRODUCTION This bulletin is presented to cover the methods used and problems experienced with defrosting of coils for chill and frozen
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
Safety Requirements Specification Guideline
Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:[email protected] -1- Summary Safety Requirement
Domestic heat pumps. DHP-A Opti DHP-C Opti DHP-C Opti W/W DHP-H DHP-H Opti DHP-H Opti Pro/Opti Pro + DHP-L DHP-L Opti DHP-L Opti Pro/Opti Pro +
MAKING MODERN LIVING POSSIBLE User Guide DHP-A Opti DHP-C Opti DHP-C Opti W/W DHP-H DHP-H Opti DHP-H Opti Pro/Opti Pro + DHP-L DHP-L Opti DHP-L Opti Pro/Opti Pro + www.heating.danfoss.com The English language
HVAC Preventative Maintenance Basics. Presented by Mike Crawley
HVAC Preventative Maintenance Basics Presented by Mike Crawley Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE
ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and
