SE-701 MANUAL GROUND-FAULT MONITOR
|
|
|
- Harvey Howard
- 10 years ago
- Views:
Transcription
1 3714 Kinnear Place Saskatoon, SK Canada S7P 0A6 Ph: (306) Fx: (306) SE-701 MANUAL GROUND-FAULT MONITOR Revision 10-C Copyright 2014 by Littelfuse Startco All rights reserved. Document Number: PM-1040-EN Printed in Canada.
2 Page i This page intentionally left blank.
3 Page ii SECTION TABLE OF CONTENTS PAGE FIGURE LIST OF FIGURES PAGE 1 Introduction General Current-Sensor Selection Operation Configuration-Switch Settings Relay Operating Mode Trip Inhibit CT Verification Filter Selection Reset Mode Front-Panel Controls Ground-Fault Trip Level Ground-Fault Trip Time Reset Test Front-Panel Indication Power Trip Trip Inhibit Analog Output Self Diagnostics Installation SE-701 Compatibility Technical Specifications Ordering Information Warranty Ground-Fault Performance Test Appendix A SE-701 Revision History SE-701 Outline and Mounting Details Typical Connection Diagrams Typical Three-Phase-Starter Connection EFCT-1 Outline and Mounting Details EFCT-2 Outline and Mounting Details EFCT-26 and SE-CS30-26 Outline and Mounting Details SE-CS30-70 Current Sensor SE-CS30-4, -5, and -8 Current Sensors PMA-55 Panel-Mount Adapter PMA-60 Panel-Mount Adapter PGA-0500 Analog Percent Current Meter Ground-Fault-Test Circuits...18 TABLE LIST OF TABLES PAGE 1 Trip-Features Comparison Ground-Fault-Test Record...19 DISCLAIMER Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.
4 Page iii This page intentionally left blank.
5 Page 1 1. INTRODUCTION 1.1 GENERAL The SE-701 is a microprocessor-based ground-fault monitor for resistance-grounded and solidly grounded systems. It is uniquely suited for use on systems with significant harmonic content. Its output relay can operate in the fail-safe or non-fail-safe mode for undervoltage or shunt-trip applications. The SE-701 has one output relay with isolated normally open and normally closed contacts for use in independent control circuits. Additional features include LED trip, power, and inhibit indication, autoreset or latching trips with front-panel and remote reset, trip memory, test button, self diagnostics, 0- to 5-V analog output, inputs for ground-fault current sensors, CT verification for EFCT-series current sensors, digital selector switches, switch-selectable algorithms for fixedfrequency or variable-frequency applications, and an inhibit that can be enabled to prevent the output relay from operating during a high-current ground fault. Ground-fault current is sensed by a current transformer. Core-balance zero sequence current sensors (CT's) are most commonly used. Bus bar or toroid style CT's can also be used on the neutral to ground connection. See Fig. 2 in Technical Note CT-08 available at The trip level of the ground-fault circuit is switch selectable in 1% increments from 1 to 99% of the CT rating. 1.2 CURRENT-SENSOR SELECTION An SE-701 has inputs for 1-, 5-A, and 50-mA-secondary CT s. Choose a CT that provides the required ground-faulttrip range. For ground-fault detection, the ground-fault trip level must be substantially below the prospective ground-fault current. In a solidly grounded system, prospective groundfault current is similar to phase-fault current. In a resistancegrounded system, prospective ground-fault current is defined by the neutral-grounding-resistor let-through-current rating. In a solidly grounded system, protection against arcing ground faults requires a ground-fault CT that will detect low-level fault current but not saturate up to the operating value of the system overcurrent protection. In general, immunity to saturation is proportional to CT mass. To eliminate nuisance tripping, surge current must not saturate the CT. For low-level ground-fault protection use an EFCT-1, EFCT-2, or EFCT-26 earth-fault CT with a 5-A-primary rating. However, protection at this level might not be possible because of high surge current or prospective ground-fault current. For CT-selection assistance, see Technical Note CT-01 available at 2. OPERATION 2.1 CONFIGURATION-SWITCH SETTINGS See Fig RELAY OPERATING MODE Switch 1 is used to set the operating mode of the output relay. In the fail-safe mode, the output relay energizes when the ground-fault circuit is not tripped. In the failsafe mode, non-volatile memory retains the trip status of the SE-701. If tripped, and the supply voltage is cycled, the SE-701 will remain tripped, with the trip relay de-energized and the TRIP LED on, until reset. In the non-fail-safe mode, the output relay energizes when a ground-fault trip occurs. In the non-fail-safe mode, trip status is not retained in non-volatile memory TRIP INHIBIT Switch 2 is used to select Class I or Class II operation. In the OFF position, high-current trip inhibit is off for Class I operation. In the ON position, high-current trip inhibit is on for Class II operation. If high-current trip inhibit is on and ground-fault current escalates above eleven times the CT-primary rating before the groundfault circuit trips, the output relay will not operate until ground-fault current falls below eight times the CTprimary rating. This feature allows overcurrent protection to operate in applications where the ground-fault current can be larger than the interrupting capacity of the device tripped by the SE CT VERIFICATION Switch 3 is used to enable CT verification with an EFCT-series CT. In the ON position, a trip will occur if the CT is disconnected. Switch 3 must be in the OFF position when an EFCT-series CT is not used and must be in the ON position when an EFCT is used FILTER SELECTION Switch 4 is used to select the filtering algorithm for a fixed-frequency (50/60 Hz) or variable-frequency application. The FIXED FREQUENCY setting uses a DFT filter that allows lower trip levels to be used by rejecting harmonics that can cause nuisance tripping. The VARIABLE FREQUENCY setting uses a peakdetection algorithm with a wider bandwidth for fault detection in variable-frequency drive applications RESET MODE Switch 5 is used to select autoreset or latching trips. See Section
6 Page FRONT-PANEL CONTROLS GROUND-FAULT TRIP LEVEL The % CT PRIMARY selector switches are used to set the ground-fault trip level as a percentage of the CT-primary rating. In tripping systems, a ground-fault trip level of 10 to 20% of the prospective ground-fault current is often used. In alarm-only systems, a value of 50% of the prospective ground-fault current is often used. To avoid sympathetic tripping, the trip level must be above the charging current of the protected feeder. A 0% selection provides protection at 1% GROUND-FAULT TRIP TIME The SE-701 has a definite-time trip characteristic. The TIME (s) selector switch is used to set the ground-fault trip delay time for coordination with upstream and downstream ground-fault devices. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault RESET If the Reset Mode switch is in the LATCHING position, a trip remains latched until the RESET button is pressed or the remote-reset terminals are momentarily connected. In the non-fail-safe mode, cycling the supply voltage will also reset the SE-701. If the Reset Mode switch is in the AUTORESET position, a trip will reset when the fault is removed. The reset circuit responds only to a momentary closure so that a jammed or shorted button will not prevent a trip. The front-panel RESET button is inoperative when the remote-reset terminals (6 and 7) are connected. indicates a trip initiated by a CT fault. Two fast flashes indicate a diagnostic trip. See Section TRIP INHIBIT The yellow LED labelled INHB indicates that outputrelay operation was inhibited during a high-current ground fault. See Section When a ground-fault trip occurs during a high-current ground fault, both the TRIP and INHB LED s will be ON. Inhibit indication is reset when the ground-fault trip is reset. Inhibit operation and indication will not respond if the trip-inhibit switch is in the OFF position. 2.4 ANALOG OUTPUT The non-isolated, 0- to 5-V analog output indicates ground-fault current sensed by the ground-fault CT. The output is 5 V when ground-fault current is 100% of the CT-primary rating. Use a PGA-0500 Analog Percent Current Meter with the PGA-05CV Voltage Converter to indicate ground-fault current. See Figs. 2, 3, and SELF DIAGNOSTICS A diagnostic trip is indicated by two fast flashes of the TRIP LED. It can be caused by a diagnostic problem detected by the watchdog timer or from an incorrect reading from non-volatile memory. Press RESET or cycle supply voltage. If the problem persists, contact Littelfuse Startco TEST The TEST button is used to test the ground-fault circuit, the indication, and the output relay. When the TEST button is pressed for one second, a test signal is applied to the ground-fault-detection circuit, the circuit will trip, the TRIP LED will light, and the output relay will operate. If high-current inhibit has been selected, the INHB LED will light. 2.3 FRONT-PANEL INDICATION POWER The green LED labelled PWR indicates the presence of supply voltage TRIP The red LED labelled TRIP indicates a trip. A solid red LED indicates a ground-fault trip. A flashing LED
7 Page 3 3. INSTALLATION NOTE: Mounting, terminal-block connections, and wiring must conform to applicable local electrical codes. Check all applicable codes prior to installation. An SE-701 can be surface or DIN-rail-mounted. See Fig. 1. Panel mounting requires a PMA-55 or PMA-60 Panel-Mount Adapter. See Figs. 9 and 10. Use terminal 11 (L1) as the line terminal on ac supply systems or the positive terminal on dc supply systems. Use Terminal 10 (L2/N) as the neutral terminal on ac systems or the negative terminal on dc systems. Connect terminal 9 ( ) to ground. Pass the phase conductors through the CT window for 4-wire and single-phase systems also pass the neutral conductor through the CT window, as shown in Figs. 2 and 3. Do not pass ground conductors through the CT window. In applications that require shields or drain wires to pass through the CT window, return them through the CT window before connecting them to ground. If a ground-fault CT with a 5-A secondary is used, connect it to terminals 2 and 3 (terminals 1 and 3 with a 1-A secondary) and ground terminal 3. If an EFCT-x is used, connect it to terminals 4 and 5, connect the shield to terminal 5, and ground terminal 5. Set configuration switch 3 to ON. Remove the connection to terminal 9 for dielectric-strength testing all inputs and outputs have ANSI/IEEE C37.90 surge-protection circuits that conduct above 300 Vac. See Figs. 4, 5, and 6 for EFCT-series dimensional drawings and Figs. 6, 7, and 8 for the SE-CS30-series current sensors.
8 Page (0.34) 55.0 (2.17) 37.5 (1.48) CONFIGURATION SWITCHES CONFIGURATION SWITCHES RESET MODE 5 LATCHING AUTORESET FILTER SELECTION 4 FIXED VARIABLE FREQUENCY FREQUENCY CT VERIFICATION 3 OFF ON TRIP INHIBIT 2 OFF ON RESET MODE FILTER SELECTION CT VERIFICATION TRIP INHIBIT RELAY OPERATING MODE LATCHING FIXED FREQUENCY OFF OFF FAIL-SAFE AUTORESET VARIABLE FREQUENCY ON ON NON-FAIL-SAFE NOTE (2.41) 75.0 (2.95) RELAY OPERATING MODE FAIL-SAFE 1 NON-FAIL-SAFE NOTE 5 1A 5A C S1 S2 RS 1A/5A CT EFCT RESET ANALOG OUTPUT MOUNTING DETAIL 6.9 (0.27) TOP 55.0 (2.17) (NOTE 3) (4.65) (4.33) 6.3 (0.25) LITTELFUSE STARTCO GROUND-FAULT MONITOR SE-701 PWR INHB TRIP % CT PRIMARY TIME (s) (2.95) TEST RESET FRONT NOTES: SIDE L2 N L1 BOTTOM DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 OR OVERALL DIMENSION WHEN MOUNTED ON DINEN mm x 7.5 mm TOP-HAT RAIL. 4. ADJUSTMENT KNOBS ARE REMOVABLE. 5. CONFIGURATION SWITCHES SHOWN IN DEFAULT POSITION. FIGURE 1. SE-701 Outline and Mounting Details.
9 Page 5 Ø A XXX:5 Ø A XXX:5 L XXX:5 Ø B Ø B N Ø C Ø C N N N L N A 5 A C S1 S2 11 L2 10 L1 N ISOLATED CONTACTS SE PHASE, 4-WIRE CONNECTION SE PHASE CONNECTION XXX:1 OR EFCT-X OR CS30-X REMOTE RESET 6 7 LEAKAGE 8 I PGA-05CV PGA-0500 RS G Y R SE-701 RESET ANALOG OUTPUT INDICATION PWR INHB TRIP 9 NOTE: 1. RELAY CONTACTS SHOWN WITH SE-701 DE-ENERGIZED A 5 A C S1 S2 SE-701 Technical Note CT-01 provides additional information on CT selection. ALTERNATE CT CONNECTIONS 3-PHASE, 3-WIRE CONNECTION FIGURE 2. Typical Connection Diagrams. Ø A XXX:5 Ø B Ø C L N A 5 A C S1 S ISOLATED CONTACTS STOP START 1M 1M O/L 11 L1 L2 10 N REMOTE RESET SE RS RESET 7 LEAKAGE ANALOG I 8 OUTPUT 9 PGA-05CV PGA-0500 INDICATION NOTES: 1. RELAY CONTACTS SHOWN WITH SE-701 DE-ENERGIZED. G Y R PWR INHB TRIP FIGURE 3. Typical Three-Phase-Starter Connection.
10 Page 6 4. SE-701 COMPATIBILITY The current SE-701 has been enhanced with the addition of non-volatile trip memory for the fail-safe relay operating mode. Prior to hardware revision 07, a mechanical flag was used instead of non-volatile trip memory. The current revision of the SE-701 can directly replace previous revision 00 to 06 units. Beginning with hardware revision 09, CT verification must be enabled when used with an EFCT-series earth-fault CT. Previous-revision SE-701 units used with EFCT-series CT s can operate with CT verification enabled or disabled. See Section The hardware-revision number is listed on the SE-701 model/serial-number label affixed to the SE-701 enclosure. The SE-701 generations are compared in Table 1. The SE-701 was previously available with SE Vac and SE Vac supply-voltage options. These have been discontinued. An SE-701-0U 120/240 Vac/Vdc unit can directly replace an SE or SE TABLE 1. TRIP-FEATURES COMPARISON HARDWARE REVISION 00 to LED trip indication Yes Yes Mechanical flag trip indication Yes No Non-volatile trip memory No Yes Device state after supply voltage cycled when tripped (ground-fault removed) Fail-safe Non-fail-safe Trip LED: Off Trip relay: Energized Trip flag: Red Trip LED: Off Trip relay: De-energized Trip flag: Red Trip LED: On Trip relay: De-energized Trip LED: Off Trip relay: De-energized CT Detection must be ON for EFCT No No Yes
11 R SE-701 Ground-Fault Monitor Page 7 NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M4 OR PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED. 4. RoHS COMPLIANT. 5. EN COMPLIANT (0.81) (4.76) (4.76) 80.0 (3.15) 30.0 (1.18) 56.0 (2.21) 46.0 (1.81) NOTE 2 M5 SCREWS TOP 25.0 (0.98) MOUNTING DETAIL 30.0 (1.18) EFCT-1 EARTH FAULT CT 600 V CLASS, INSULATION CLASS A R LR C US MAX (5.43) EFCT - 1FC FLUX CONDITIONER (OPTIONAL) 82.0 (3.23) 69.8 (2.75) 5.0 (0.20) Ø RECESSED FOR 8-mm HEX NUT 1.0 (0.04) DEEP 22.0 (0.87) (4.96) 5.5 (0.22) (4.33) 5.5 (0.22) 56.0 (2.21) FRONT SIDE FIGURE 4. EFCT-1 Outline and Mounting Details.
12 R R SE-701 Ground-Fault Monitor Page 8 NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MOUNTING SCREWS: M5 OR RoHS COMPLIANT. 4. EN COMPLIANT (8.46) 26.5 (1.04) (8.46) (6.38) 64.0 (2.52) 31.0 (1.22) P2 S1 S P (2.06) M5 OR TAP M5 SCREWS TOP 25.0 (0.98) MOUNTING DETAIL 31.0 (1.22) EFCT-2 EARTH FAULT CT 600 V CLASS, INSULATION CLASS A LR C US 236 MAX (9.29) (5.50) FLUX CONDITIONER (INCLUDED) BONDING SCREW 5.0 (0.20) DIA (8.46) 60.0 (2.36) 8.5 (0.33) (7.80) 8.5 (0.33) FRONT SIDE FIGURE 5. EFCT-2 Outline and Mounting Details.
13 R SE-701 Ground-Fault Monitor Page (0.67) 68.0 (2.68) 68.0 (2.68) 34.0 (1.34) 26.5 (1.04) 52.5 (2.07) 42.6 (1.68) M4 OR 8-32 TAP MAX (0.43) M5 SCREWS TOP 25.0 (0.98) MOUNTING DETAIL 26.5 (1.04) SE-CS30-26 CURRENT SENSOR C R US LR (2.83) 26.0 (1.02) 4.0 (0.16) Ø RECESSED FOR 7-mm HEX NUT 3.0 (0.12) DEEP 34.0 (1.34) 58.0 (2.28) 7.0 (0.87) 5.0 (0.20) FRONT 5.0 (0.20) 52.5 (2.07) SIDE NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL A ). DETAIL A MOUNTING FOOT INSTALLA TION TOOL 3. MOUNTING SCREWS: M4 OR RoHS COMPLIANT. 5. EN COMPLIANT. 6. SE-CS30-26 SHOWN. FIGURE 6. EFCT-26 and SE-CS30-26 Outline and Mounting Details.
14 R R SE-701 Ground-Fault Monitor Page (0.81) (4.76) (4.76) 80.0 (3.15) 30.0 (1.18) 56.0 (2.21) 46.0 (1.81) NOTE 3 M5 SCREWS TOP 25.0 (0.98) MOUNTING DETAIL 30.0 (1.18) SE-CS30-70 CURRENT SENSOR C US LR MAX (5.43) 69.8 (2.75) Ø 5.0 (0.20) RECESSED FOR 8-mm HEX NUT 1.0 (0.04) DEEP (4.96) 22.0 (0.87) 5.5 (0.22) (4.33) FRONT 5.5 (0.22) 56.0 (2.21) SIDE MOUNTING FOOT INSTALLATION TOOL NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. PRESS MOUNTING FEET IN PLACE USING INSTALLATION TOOL PROVIDED (DETAIL A ). 3. MOUNTING SCREWS: M4 OR DETAIL A 4. RoHS COMPLIANT. 5. EN COMPLIANT. FIGURE 7. SE-CS30-70 Current Sensor.
15 Page 11 C J D H G TOP (COVER REMOVED) F 72.0 (2.83) 14.0 (0.55) MOUNTING DETAIL SE-CS30-8 OUTLINE NOTES: 1. DIMENSIONS IN MILLIMETRES (INCHES). A B 2. MOUNTING SCREWS: M5 OR RoHS COMPLIANT. 4. CE COMPLIANT. E FLUX CONDITIONER DIMENSIONS SE-CS30-4 SE-CS30-5 SE-CS30-8 A 95.0 (3.74) (5.12) (7.87) B (6.89) (8.78) (12.17) FRONT 1.7 (0.07) C D (6.22) (5.55) (7.99) (7.01) (11.44) (10.50) E 82.0 (3.22) (4.07) (5.90) G F 32.0 (1.26) 32.0 (1.26) 34.0 (1.34) I K G 17.5 (0.69) 11.0 (0.43) 11.0 (0.43) L D C BOTTOM J H I J 15.0 (0.59) 33.0 (1.30) 9.0 (0.35) 13.3 (0.52) 34.0 (1.34) 11.0 (0.43) 13.3 (0.52) 43.0 (1.69) 11.5 (0.45) K 40.0 (1.57) 40.0 (1.57) 50.0 (1.97) L 5.3 (0.21) 7.0 (0.28) 7.0 (0.28) FIGURE 8. SE-CS30-4, -5, and -8 Current Sensors.
16 Page (3.35) (4.33) PANEL THICKNESS 1.6 (0.06) TO 4.8 (0.19) (1.67) LITTELFUSE STARTCO GROUND-FAULT MONITOR PWR INHB TRIP SE % CT PRIMARY TIME (s) 85.0 (3.35) (2.95) TEST RESET FRONT VIEW BEZEL BRACKET SIDE VIEW 55.0 (2.20) WIDE MONITOR 42.5 (1.67) 30.0 (1.18) 6.0 (0.24) 85.0 (3.35) 72.0 (2.83) 60.0 (2.36) 2.0 (0.08) RAD MAXIMUM 4.0 (0.16) DIA 8.7 (0.34) DIA 4.3 (0.17) RAD ALTERNATE CONFIGURATIONS 6.0 (0.24) 9.5 (0.37) 60.0 (2.36) 79.0 (3.11) INSTALLATION INSTRUCTIONS: 1. REMOVE BEZEL AND LATCH MONITOR ON BRACKET. 2. INSERT BRACKET THROUGH FRONT OF PANEL CUTOUT AND SECURE WITH FLAT WASHERS AND LOCKNUTS PROVIDED. 3. CONNECT WIRING TO TERMINALS. 4. INSTALL BEZEL USING 6-32 x 0.31 SCREWS PROVIDED. NOTE: 1. DIMENSIONS IN MILLIMETRES (INCHES). 9.5 (0.37) PANEL CUTOUT DETAIL FIGURE 9. PMA-55 Panel-Mount Adapter.
17 Page (3.90) (4.57) PANEL THICKNESS 1.6 (0.06) TO 4.8 (0.19) M (1.73) LITTELFUSE STARTCO GROUND-FAULT MONITOR SE-701 PWR INHB TRIP % CT PRIMARY TIME (s) 88.0 (3.46) M (2.95) TEST RESET FRONT VIEW TRANSPARENT COVER (NOTE 2) BRACKET SIDE VIEW 55.0 (2.20) WIDE MONITOR 44.0 (1.73) 30.0 (1.18) 6.0 (0.24) 99.0 (3.90) 72.0 (2.83) 60.0 (2.36) 2.0 (0.08) RAD MAXIMUM 4.5 (0.18) DIA 8.7 (0.34) DIA 4.3 (0.17) RAD 6.0 (0.24) 9.5 (0.37) 60.0 (2.36) 79.0 (3.11) INSTALLATION INSTRUCTIONS: 1. WITH COVER REMOVED LATCH MONITOR TO BRACKET. 2. INSERT BRACKET THROUGH FRONT OF PANEL CUTOUT AND SECURE WITH FLAT WASHERS AND LOCKNUTS PROVIDED. 3. CONNECT WIRING TO TERMINALS. 4. ATTACH COVER USING SECURITY SCREWS OR THUMB SCREWS PROVIDED. NOTES: ALTERNATE CONFIGURATIONS 1. DIMENSIONS IN MILLIMETRES (INCHES). 2. MEETS NEMA3, IP53. PANEL CUTOUT DETAIL 9.5 (0.37) 3. INCLUDES TWO TR20 TAMPER-RESISTANT TORX SCREWS (M4-0.7x16 mm, INSTALLED) AND TWO THUMB SCREWS. FIGURE 10. PMA-60 Panel-Mount Adapter.
18 Page (2.657) R1.25(0.049) MAXIMUM 48.0 (1.890) 66.0 (2.598) 67.5 (2.657) NOTES: 1. CONVERSION KIT FOR 0-5 V ANALOG OUTPUT. SEE PGA-0500 DOCUMENTATION. 2. DIMENSIONS IN MILLIMETRES (INCHES). TOP MOUNTING CUTOUT % NOTE (2.795) 65.0 (2.559) 0 PGA-0500 ANALOG % CURRENT METER FRONT FIGURE 11. PGA-0500 Analog Percent Current Meter. SIDE REAR 5. TECHNICAL SPECIFICATIONS Supply: 0U Option... 5 VA, 120 to 240 Vac, (+20, -55%) 50/60 Hz; 2 W, 100 to 240 Vdc, (+20, -25%) 0D Option... 2 W, 12 to 30 Vdc, (+20, -25%) 0T Option... 2 W, 40 to 55 Vdc, (+20, -25%) 03 Option VA, 24 Vac, (+15, -40%), 50/60 Hz Trip-Level Range... 1 to 99% CT-Primary Rating in 1% increments (50 ma to 4.95 A with EFCT-x) Trip-Time Settings , 0.10, 0.20, 0.30, 0.40, 0.50, 1.0, 1.5, 2.0, and 2.5 s Accuracies (1) : Trip Level (2)... Largest of 5% of setting or: 1-A input: 1% setting , +15 ma 2-99% setting ma 5-A and EFCT (4) inputs: 1% setting , +60 ma 2-99% setting ma Trip Time (3)... 5% of setting (-25, +20 ms minimum) Trip Inhibit: Off... Class I On... Class II Level x CT-Primary Rating Input: Algorithms... DFT or Peak DFT 3 db Frequency Resp to 86 Hz Peak 3 db Frequency Resp to 420 Hz CT or 5-A Secondary Rating, or EFCT-x CT Detection... Open-Circuit Detection with EFCT-x
19 Page 15 Thermal Withstand: Continuous... 5 x CT-Secondary Rating 1-Second x CT-Secondary Rating Burden: 5-A input... < A input... < 0.05 EFCT input... 2 Analog Output: Range... 0 to 5 Vdc, 5 V = 100% CT Rating Output Impedance Reset... Front-Panel Button and Remote N.O. Momentary Contact Functional Test... Front-Panel Button Output Relay: Contact Configuration... Isolated N.O. and N.C. Operating Mode... Fail-Safe or Non-Fail-Safe CSA/UL Contact Rating... 8 A General Use, 250 Vac, 8 A Resistive, 30 Vdc 0.25 HP, 120/240 Vac Supplemental Contact Ratings: Carry Current... 8 A, maximum Break: 30 Vdc W Resistive, 170 W Inductive (L/R = 7 ms) 120 Vdc W Resistive, 17 W Inductive (L/R = 7 ms) ac... 2,000 VA Resistive, 875 VA Inductive (PF = 0.4) (Subject to maximums of 8 A and 250 Vac/ 30 Vdc or 200 ma at 120 Vdc) Trip Mode... Latching or Autoreset Terminals... Wire-clamping, 24 to 12 AWG (0.2 to 2.5 mm 2 ) conductors Dimensions: Height mm (3.0 ) Width mm (2.2 ) Depth mm (4.5 ) Environment: Operating Temperature: Altitude: 1,000 m (3,281 ) to 60 C (-40 to 140 F) 3,000 m (9,843 ) to 55 C (-40 to 131 F) 5,000 m (16,404 ) to 50 C (-40 to 122 F) Storage Temperature to 80 C (-67 to 160 F) Humidity... 85% Non-Condensing Altitude... 5,000 m (16,404 ) maximum PWB Conformal Coating... MIL qualified UL QMJU2 recognized Surge Withstand... ANSI/IEEE (Oscillatory and Fast Transient) Vibration... EN (Vibration, Shock, and Seismic) EN (Shock and Bump) EMC Tests: Verification tested in accordance with EN 50263:2000 Radiated and Conducted Emissions... CISPR 11:2009, CISPR 22:2008, EN55022:2010 Class A Current Harmonics and Voltage Fluctuation... IEC and IEC Class A Electrostatic Discharge... IEC ± 6 kv contact discharge (direct and indirect) ± 8 kv air discharge Radiated RF Immunity... IEC V/m, MHz, 80% AM (1 khz) 10 V/m, 900 MHz, 200 Hz pulse modulated Shipping Weight kg (1 lb)
20 Page 16 Fast Transient... IEC kv on AC mains and I/O lines Surge Immunity... IEC Zone B ± 1 kv differential mode ± 2 kv common mode Conducted RF Immunity... IEC V, MHz, 80% AM (1 khz) Magnetic Field Immunity... IEC Hz and 60 Hz, 30 A/m and 300 A/m Voltage Interruption... IEC , IEC , 0% for 5, 10, 20, 50, 100 & 200 ms 3x each Power Frequency... IEC Zone A: differential mode 150 Vrms Zone A: common mode 300 Vrms 1 MHz Burst... IEC ± 1 kv differential mode (line-to-line) ± 2.5 kv common mode RFI Compliance... FCC Part 15, Subpart B, Class A Unintentional Radiators Certification... CSA, Canada and USA R LR C US UL Listed Australia N11659 FCC CE, European Union Complies to IEC :2001 (2 nd Edition); EN :2001 (2 nd Edition) Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use Part 1. NOTES: (1) Over operating temperature range of -40 to 60 C (-40 to 140 F). (2) CT accuracy not included. (3) Trip time at 3 x trip-level setting from the first peak. (4) For maximum lead resistance of ORDERING INFORMATION SE Conformal Coating: Blank Partial Conformal Coating CC Full Conformal Coating Supply: 3 24-Vac Supply U Universal 120/240-Vac/Vdc Supply D 12/24-Vdc Supply T 48-Vdc Supply EFCT-1... Earth-Fault CT, 5-A-primary rating, 82 mm (3.2 ) window EFCT-1FC... Flux Conditioner for EFCT-1, 70 mm (2.7 ) window EFCT-2... Earth-Fault CT, with Flux Conditioner, 5-A-primary rating, 139 mm (5.5 ) window EFCT Earth-Fault CT, 5-A-primary rating, 26 mm (1 ) window (All EFCT s include 6 m (19.2 ) 22 AWG (0.3 mm 2 ) shielded cable.)
21 Page 17 SE-CS Current Sensor, 26.0 mm (1.02 ) window SE-CS Current Sensor c/w Flux Conditioner, 69.8 mm (2.75 ) window SE-CS Current Sensor c/w Flux Conditioner, 95.0 mm (3.74 ) window SE-CS Current Sensor c/w Flux Conditioner, mm (5.12 ) window SE-CS Current Sensor c/w Flux Conditioner, mm (7.87 ) window 5SHT-101-E (1)... Current Sensor, 100-A-primary rating, 40 mm (1.6 ) window 5SHT-151-E (1)... Current Sensor, 150-A-primary rating, 40 mm (1.6 ) window 5SHT-500-E (1)... Current Sensor, 50-A-primary rating, 40 mm (1.6 ) window 7SHT-301-E (1)... Current Sensor, 300-A-primary rating, 64 mm (2.5 ) window 7SHT-401-E (1)... Current Sensor, 400-A-primary rating, 64 mm (2.5 ) window 7. WARRANTY The SE-701 Ground-Fault Monitor is warranted to be free from defects in material and workmanship for a period of five years from the date of purchase. Littelfuse Startco will (at Littelfuse Startco s option) repair, replace, or refund the original purchase price of an SE-701 that is determined by Littelfuse Startco to be defective if it is returned to the factory, freight prepaid, within the warranty period. This warranty does not apply to repairs required as a result of misuse, negligence, an accident, improper installation, tampering, or insufficient care. Littelfuse Startco does not warrant products repaired or modified by non- Littelfuse Startco personnel. PGA Analog Percent Current Meter (PGA-05CV included) PMA Panel-Mount Adapter, NEMA 1 PMA Panel-Mount Adapter, NEMA 3, IP53. Includes two TR20 tamper-resistant Torx screws and two thumb screws. PMA-3... Adapter Plate, GES/MCGG PMA-6... Adapter Plate, FPL-GFRM PMA Adapter Plate, MGFR SE-EFVC... Voltage Clamp Consult factory for custom mounting adapters. NOTES: (1) Includes mounting brackets.
22 Page GROUND-FAULT PERFORMANCE TEST To meet the requirements of the National Electrical Code (NEC), as applicable, the overall ground-fault protection system requires a performance test when first installed. A written record of the performance test is to be retained by those in charge of the electrical installation in order to make it available to the authority having jurisdiction. A test-record form is provided for recording the date and the final results of the performance tests. The following ground-fault system tests are to be conducted by qualified personnel: a) Evaluate the interconnected system in accordance with the overall equipment manufacturer s detailed instructions. b) Verify proper location of the ground-fault current sensor. Ensure the cables pass through the groundfault-current-sensor window. This check can be done visually with knowledge of the circuit. The connection of the current-sensor secondary to the SE- 701 is not polarity sensitive. c) Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current sensor. High-voltage testers and resistance bridges can be used to determine the existence of alternate ground paths. d) Verify proper reaction of the circuit-interrupting device in response to a simulated or controlled ground-fault current. To simulate ground-fault current, use CT-primary current injection. Fig. 12 (a) shows a test circuit using an SE-400 Ground-Fault- Relay Test Unit. The SE-400 has a programmable output of 0.5 to 9.9 A for a duration of 0.1 to 9.9 seconds. Set the test current to 120% of the SE-701 setting. Fig. 12 (b) shows a test circuit using an SE-100T Ground-Fault-Relay Tester. The SE-100T provides a test current of 0.65 or 2.75 A for testing 0.5- and 2.0-A trip levels. Inject the test current through the current-sensor window for at least 2.5 seconds. Verify that the circuit under test has reacted properly. Correct any problems and re-test until the proper reaction is verified. e) Record the date and the results of the test on the attached test-record form. a) USING SE-400 FROM POWER SOURCE REMOTE TEST b) USING SE-100T FROM POWER SOURCE REMOTE TEST 11 L 10 N 11 3 L N L 10 N XXX: A 5 A C S1 S2 L1 SE-701 L2/N OP1 L1 L2 RMT1 RMT2 SE-400 XXX:5 OP A 5 A C S1 S2 L1 SE-701 L2/N C LO L L1 HI N L2 RMT SE-100T FIGURE 12. Ground-Fault-Test Circuits. 12 LOAD LOAD 0.65 A 2.75 A NOTE: Do not inject test current directly into CT-input terminals 1, 2, 3, 4, and 5.
23 Page 19 DATE TABLE 2. GROUND-FAULT-TEST RECORD TEST RESULTS Retain this record for the authority having jurisdiction.
24 Page 20 MANUAL RELEASE DATE July 24, 2014 October 21, 2013 April 12, 2013 MANUAL REVISION 10-C B A APPENDIX A SE-701 REVISION HISTORY PRODUCT REVISION (REVISION NUMBER ON PRODUCT LABEL) 09 MANUAL REVISION HISTORY REVISION 10-C SECTION 4 Fig. 8 updated. SECTION 5 Update to include altitude and vibration specifications. APPENDIX A Revision history updated. REVISION 10-B SECTION 4 Fig. 6 updated to include EFCT-26 and SE-CS SECTION 5 Conformal coating specifications added. FCC certification mark added. SECTION 6 Updated ordering information with full conformal coating (CC) option. APPENDIX A Revision history updated. REVISION 10-A SECTION 3 Figs. 2 and 3 updated to include PGA-05CV. SECTION 4 Figs. 7, 8, and 9 added. SECTION 5 Environment section updated to include Fahrenheit temperature range. SECTION 6 Additional current sensors added to ordering information. APPENDIX A Revision history added. PRODUCT REVISION HISTORY REVISION 09 Firmware: Improved operation of front-panel test button.
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac & 230Vac NEC Class 2 / Limited
TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector
Product datasheet Characteristics TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC - 0.5 A - M8 connector Main Range of product Product or component type Range compatibility Enclosure material Bus
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
Waveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
ATC-300 Automatic Transfer Switch Controller
ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage without power de-rating Efficiency > 87.0% @ 115Vac, > 89.0% @ 230Vac NEC Class
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG
Highlights & Features Protection Class II, Double Isolation (No Earth connection is required) Universal AC input voltage and full power up to 55 C Power will not de-rate for the entire input voltage range
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
CompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
Energy Management Energy Meter Type EM23 DIN
Energy Management Energy Meter Type EM23 DIN Class 1 (kwh) according to EN62053-21 Class B (kwh) according to EN50470-3 Class 2 (kvarh) according to EN62053-23 Accuracy ±0.5 RDG (current/voltage) Energy
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
White Paper Mervin Savostianik P. Eng. Littelfuse, Inc.
Ground-Fault Protection with VFDs How to use a Sensitive Relay to Find Hard-to-Spot Ground Faults in VFDs on Resistance-Grounded Systems White Paper Mervin Savostianik P. Eng. Littelfuse, Inc. How to Use
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
Thermistor motor protection relays CM-MSS.22 and CM-MSS.23
Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
RoHS APPROVAL SHEET. ituner 12V/6.6A SERIES NO. (E17) EA10953A. ( ) Edac Power Electronics (Suzhou) Co., Ltd. 59 No.59, Chang Sheng Road, Sheng Pu,
APPROVAL SHEET CUSTOMER ituner CUSTOMER P/N DESCRIPTION EDAC MODEL 12V/6.6A SERIES NO. (E17) EA10953A DATE 2010-06-22 REVISION 0 APPROVED DESIGN PREPARE RoHS CONCLUSION APPROVED CONDITON CUSTOMER S APP
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL
ALARM ANNUNCIATOR ME - 3010 INSTRUCTION MANUAL INTRODUCTION... 2.. TECHNICAL DATA... 3 ACCESSORIES... 5. INSTALLATION... 7 OPERATION... 12. TECHNICAL INFORMATION... 13 MAINTENANCE... 14. CONFIGURATIONS...
Analog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
STRATO LED Drivers 70W, Single output
Features STRATO switch mode driver technology is designed to generate one constant current output from a wide range AC input. The size and performance of these products make them the ideal choice for LED
CPCI-3U-AC-300W-R. Rugged 300W AC Input 3U CompactPCI Power Supply. Electrical Specification for: Telkoor Part Number: 900-4602-0000
Electrical Specification for: CPCI-3U-AC-300W-R Rugged 300W AC Input 3U CompactPCI Power Supply Telkoor Part Number: 900-4602-0000 GENERAL SCALE RELEASE DATE 12/9/06 SHEET 1 OF 6 REVISION HISTORY Rev Level
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
Power Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5
Model Number Single head system Features Parameterization interface for the application-specific adjustment of the sensor setting via the service program ULTRA 000 programmable switch outputs Hysteresis
Quick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
CliQ DIN Rail Power Supply 24V 120W 1 Phase / DRP024V120W1AA
Highlights & Features Reliable design, with expected life of 10 years Compact, rugged design for ease of handling and installation Multiple connections to terminals allowed Designed for Class I Div. 2
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits
Features 71.11.8.230.0010 71.11.8.230.1010 1 - Phase 230 V Over & Under voltage monitoring relays 71.11.8.230.0010 - Fixed Over & Under voltage detection - Link selectable 5 or 10 minute lock-out delay
Series 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS
Series 427 1/16 DIN Multi-Mode Bar Graph Display Timer PRODUCT HIGHLIGHTS Digital Setting with 0.1% Accuracy Unique LED Bargraph Indicates Time Cycle in 20% Increments 8 Field Selectable Modes of Operation
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
SURGE PROTECTIVE DEVICES
SURGE PROTECTIVE DEVICES 1. INTRODUCTION In order to ensure safety of people, protection of equipment and, to a certain extent, continuity of supply, insulation co-ordination aims at reducing the likelihood
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic
Safety Manual BT50(T) Safety relay / Expansion relay
Safety Manual BT50(T) Safety relay / Expansion relay ABB Jokab Safety Varlabergsvägen 11, SE-434 39, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this document
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
Trip circuit supervision relay. Type RXTCS
Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h
0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
Panel Meters and Controllers Modular Panel Meter Type EDM 35
Panel Meters and Controllers Modular Panel Meter Type EDM 35 Modular digital panel meter, 3 1/2-digit Indicating or controlling current, voltage, resistance, temperature, tacho or frequency. Easy programming
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C
Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting
EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility
EVlink Electric Vehicle Charging Solutions Powering the Future of Sustainable Mobility Catalog 2800CT1001 2014 Class 2800 CONTENTS Description............................................ Page 2 Outdoor
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
RM35UA13MW. range 15..600 V. Main. Product or component type. Relay monitored parameters
Characteristics multifunction voltage control relay RM35-U - range 15..600 V Complementary Reset time Maximum switching voltage [Us] rated supply voltage Supply voltage limits Power consumption in W Main
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
Solid State Timers Type F
Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application
VLT Series 3500 Adjustable Frequency Drive Instruction Manual
Adjustable Frequency Drive Instruction Manual VLT Series 3500 Instruction Manual 175R5237 - Document Version 5.00 This manual applies to all VLT Series 3502-3800 Adjustable Frequency Drives with software
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
Operating Manual UWAPS-TINY Series
Operating Manual UWAPS-TINY Series Powecon Oy WWW.POWECON.FI 1/9 Table of content 1 Warranty...3 2 Safety information...3 3 Abbreviations and terminology...3 4 List of appendices...4 5 Introduction...4
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter
FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current
MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet 100260_en_01. 1 Description
Voltage Transducer for DC Voltages TERFACE Data Sheet 000_en_0 PHOENIX CONTACT - /00 Description The MCR voltage transducer measures DC voltages in several signal ranges from 0... ±0 V DC to 0... ±0 V
HMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE
Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008
CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER
TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description
Photoelectrics, Background Suppression reflective with IR light Main features Description The PD30ET... stainless steel sensors are built with high-quality materials and designed for harsh environments.
80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 6 A 80. Multi-function and mono-function timer range - Multi-function & multi-voltage 80. - ON delay, multi-voltage 7.5 mm wide Six time scales from 0.s to 24h 35 mm rail (EN
Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W
14713221 001 Seite 2 von 37 Page 2 of 37 Model List: No Model Rated Voltage(V) 1. EG-LED0827-01 Rated Power(W) 8W 2. EG-LED0840-01 8W 3. EG-LED1027-01 10W 4. EG-LED1040-01 AC 100-240V, 10W 5. EG-LED1027-02
Cross-beam scanning system to detect slim objects. 100 mm 3.937 in
891 Object Area Sensor General terms and conditions... F-17 Related Information Glossary of terms... P.1359~ Sensor selection guide...p.831~ General precautions... P.1405 PHOTO PHOTO Conforming to EMC
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE
SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.
NI 9423. NI C Series Overview DATASHEET. 8-Channel Sinking Digital Input Module
DATASHEET NI 9423 8-Channel Sinking Digital Input Module 8-channel, 100 µs digital input 24 V logic, sinking digital input Compatible with NI CompactDAQ counters 250 Vrms, CAT II isolation 10-position
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
A project to optimise quality and energy efficiency must include metering
EMDX 3 : Energy Metering A project to optimise quality and energy efficiency must include metering Metering upstream identifies the critical points and ensures optimum targeting of the actions to be taken,
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Capacitor Protection Relay SPAJ 160 C. Product Guide
Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase
EVlink Electric Car Charging Stations Powering the Future of Sustainable Mobility
EVlink Electric Car Charging Stations Powering the Future of Sustainable Mobility Catalog 2800CT1001 R09/15 2015 Class 2800 CONTENTS Description............................................ Page 2 Home
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY
TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY 2 TRACTION NETWORK MONITORING AND PROTECTION SYSTEM Traction network monitoring and protection system,
How To Test A Power Distribution Unit
PDUAC3U SERIES AC POWER DISTRIBUTIO UITS www.unipowerco.com Manual o. PDUAC3U-1 pduac3u-man-rev1-1015.indd 2015 UIPOWER LLC All Rights Reserved ORTH AMERICA 3900 Coral Ridge Drive, Coral Springs, Florida
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications