2B.1 Chilled-Water Return (and Supply) Temperature B.3 Cooling-Water Supply Temperature / Flow

Size: px
Start display at page:

Download "2B.1 Chilled-Water Return (and Supply) Temperature...119. 2B.3 Cooling-Water Supply Temperature / Flow... 124"

Transcription

1 Appendix 2B: Chiller Test Results B.1 Chilled-Water Return (and Supply) Temperature B.2 Chilled-Water Flow B.3 Cooling-Water Supply Temperature / Flow B.4 Pressure/Temperature Figure 2B - 1: COP variation with change of chilled-water temperature Figure 2B - 2: Cooling load variation with change of chilled-water temperature Figure 2B - 3: COP variation with change of chilled-water Figure 2B - 4: Cooling load variation with change of chilled-water Figure 2B - 5: COP variation with change of cooling-water temperature Figure 2B - 6: Cooling load variation with change of cooling-water temperature Figure 2B - 7: COP variation with change of cooling-water Figure 2B - 8: Cooling load variation with change of cooling-water Figure 2B - 9: COP variation with change of steam pressure Figure 2B - 10: Cooling load variation with change of steam pressure Table 2B - 1: Primary inputs of the test program Table 2B - 2: Primary inputs and outputs of tests varying chilled-water temperature Table 2B - 3: Primary inputs and outputs of the tests by varying chilled-water Table 2B - 4: Primary inputs and outputs of the tests by varying cooling-water temperature Table 2B - 5: Primary inputs and outputs of the tests by varying cooling-water Table 2B - 6: Primary inputs and outputs of the tests by varying steam pressure

2 Appendix 2B: Chiller Test Results The effects of cooling load variations on the chiller performance (chilled-water temperature) have been summarized in sunsections and In the testing program, the effects of the following five operating conditions on chiller performance were tested using the same test approach: chilled-water (and ) temperature chilled-water cooling-water temperature / steam pressure Each of the five operating conditions identified above was varied one at a time over a range of their design values, as indicated in Table 2B-1. Table 2B-1 listed the variable adjusting ranges for each of the five operating parameters. Within its range each operating condition was tested at six to twelve values, and each test obtained 30 to 300 data sets at 2-minute intervals during steady-state operation of the chiller. A total of 51 tests were conducted over an estimated 220 hours of chiller operation. Table 2B - 1: Primary inputs of the test program Chilled-water Chilled - water m 3 /h Primary operation parameters Cooling-water Cooling-water pressure kg/s kpa Chilled water Design Design Design Design Chilled water Design Design Design Design Cooling water T Design Design Design Design Cooling water Design Design Design Design pressure Design Design Design Design Number of tests The results of these tests in terms of the chiller load and the coefficient of performance are reported and discussed in subsection 2B.1 to 2B.4. 2B.1 Chilled-Water Return (and Supply) Temperature There were a total of 11 individual tests of different chilled-water temperatures. The primary inputs and outputs of the chiller are listed in Table 2B-2. In these tests, the chilled-water temperature was set at 7, but when the chilled-water temperature was varied from 10.9 to 22, the chilled- 119

3 water temperature increased from 5.1 to The chiller coefficient of performance and the cooling load are plotted in Figure 2B-1 and 2B-2, respectively. In Figure 2B-1, as the chilled-water temperature increases gradually from 5.14 to 13.53, the COP increases from 1.0 to In Figure 2B-2, the solid curve represents the measured cooling load, and the dashed curve represents the cooling load provided by the manufacturer for a natural-gas-driven chiller with the same cooling capacity and similar structure. The two curves check closely. The primary reason for the cooling load and the COP increase with the increase of chilled-water and temperature is that the heat transfer in the evaporator is facilitated by increasing the chilledwater and temperature. The heat transfer capacity is a function of chilled-water and temperature, and rate. The component and comprehensive computational models will be used in chapter 3 to analyze the quantity effects of the chilled-water and temperature. In the operation of this absorption chiller, increasing the chilled-water and temperatures is one of the effective strategies to save thermal energy consumption. Both the COP and the cooling load are increased by increasing the chilled-water and temperatures. Table 2B - 2: Primary inputs and outputs of tests varying chilled-water temperature Measurement values for chiller inputs Coolingwater Chilled Cooling- water water Measurement values for chiller outputs Condensate Cooling load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s kg/h kw 120

4 Figure 2B - 1: COP variation with change of chilled-water temperature 1.4 Coefficient of Performance (COP) Thermal COP Overall COP Chilled Water Supply Thermal COP Overall COP Temperature, T32 ( ) Figure 2B - 2: Cooling load variation with change of chilled-water temperature 24 Actual cooling load (kw) Measured data Manufacturer's rated performance data Cooling load Rated performance data Chilled water temperature ( ) 121

5 2B.2 Chilled-Water Flow To investigate how the chilled-water affects the chiller performance and other internal properties of the chiller, the chilled-water was varied from 1.2 m 3 /h to 3.6 m 3 /h in a series of 10 tests. The chilledwater temperature is maintained at 7 by decreasing and varying the chilled water temperature from 17 to The cooling-water temperature is set at 30, but the chiller actually maintains the cooling-water around 31 for all tests. The steam pressure is fixed at 620 kpa, the steam changed on the basis of the cooling loads. The test conditions and primary results are summarized in Table 2B-3. The bold line in the table refers to the design condition. Figure 2B-1 shows that the thermal COP increased from 0.96 to 1.06 as the chilled-water was increased from 1.2 m 3 /h to 3.6 m 3 /h. Figure 2B-2 shows the cooling load changes with the variations of chilled-water for the ten tests. The test results indicate that the chiller can be operated within a broad range of chilled-water from 2 m 3 /h to 3.3 m 3 /h without degrading chiller performance. The cooling load is affected slightly by the chilled-water because of its effect on the heat transfer in the evaporator, but the does not affect the COP and cooling load as much as the chilled-water and temperature. The quantitative analysis of chilled-water on the chiller performance will be discussed on the basis of chiller model in chapter 3. These data show that the best operational, most efficient strategy for chiller operation is to satisfy the cooling load to the extent possible with high chilled-water s and with high (and ) temperature. Table 2B - 3: Primary inputs and outputs of the tests by varying chilled-water Measurement values for chiller inputs Coolingwatewater Chilled- Cooling- water Measurement values for chiller outputs Condensate Cooling load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s kg/h kw 122

6 Figure 2B - 3: COP variation with change of chilled-water 1.30 Coefficient of Performance (COP) Overall COP Thermal COP Thermal COP Overall COP Chilled Water Supply Flow Rate (kg/s) Figure 2B - 4: Cooling load variation with change of chilled-water 20 Measured cooling load (kw) Cooling load Chilled Water Supply Cooling load Flow Rate (kg/s) 123

7 2B.3 Cooling-Water Supply Temperature / Flow Cooling-water removes heat from the absorber and the condenser. The heat transfer in these two components is a function of cooling-water and temperature. These conditions directly affect both the sorbent and the refrigerant temperature. Lower cooling-water temperature and higher rate effectively remove the heat generated in the absorber and the condenser, so the COP and cooling capacity are high, but if the cooling-water temperature is too low, the chiller is in danger of freezing the evaporator tubes and crystallizing the sorbent in the LTHX. Both situations are harmful to the chiller. The purpose of these tests is to investigate the effects of the cooling water temperature and rate on the chiller performance and other internal properties of the chiller. In these tests, the cooling-water temperature is decreased from to in a total of 12 steady state tests. The test results are plotted in Table 2B-4, Figures 2B-5, and 2B-6. Table 2B - 4: Primary inputs and outputs of the tests by varying cooling-water temperature Measurement values for chiller inputs Cooling- Chilled- Coolingwater water water Measurement values for chiller outputs Condensate Chilled- Cooling water load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s The cooling-water rate was decreased from 1.55 kg/s to 0.78 kg/s in a total of six steady-state tests. The cooling load for this experiment is lower than the design capacity because the cooling-water temperature is set at 32 instead of 30. The test results are summarized in Table 2B-5, Figures 2B-7 and 2B-8. In the experiments, the chilled-water temperature was set at 14 ; the chilled-water temperature set point was 7, and the steam pressure was fixed at 640 kpa. kg/h kw 124

8 The test results indicate that decreasing the cooling-water temperature is one of the most effective ways for improving the total performance of the absorption chiller. The increase of cooling-water rate can improve the COP and the cooling load of the chiller; but the improvement is less effective than the decrease of cooling-water temperature. Figure 2B - 5: COP variation with change of cooling-water temperature 1.3 Coefficient of Performance (COP) Overall COP Thermal COP (model) Thermal COP Thermal COP Overall COP Cooling Water Supply Temperature ( ) Figure 2B - 6: Cooling load variation with change of cooling-water temperature Measured cooling load (kw) Cooling load Cooling Water Supply Cooling load Temperature ( ) 125

9 Table 2B - 5: Primary inputs and outputs of the tests by varying cooling-water Measurement values for chiller inputs Coolingwater Coolingwater Measurement values for chiller outputs Chilled- Condensate water Cooling load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s kg/h kw Figure 2B - 7: COP variation with change of cooling-water 1.2 Coefficient of Performance (COP) Thermal COP Overall COP Thermal COP Overall COP Cooling Water Flow (kg/s) 126

10 Figure 2B - 8: Cooling load variation with change of cooling-water 18 Measured cooling load (kw) Cooling load Cooling load Cooling Water Flow (kg/s) 2B.4 Pressure/Temperature The chiller requires steam input to the HTRG to heat the sorbent solution and produce the refrigerant at a pressure/temperature that allows for additional heat transfer to the sorbent and refrigerant production in the LTRG. The pressure of the steam should be appropriate to optimize the chiller performance in terms of the COP and cooling load. If the steam pressure/temperature to the HTRG is too low, it cannot transfer sufficient heat to the sorbent solution, and produce sufficient refrigerant; therefore, both the cooling load and COP are decreased. If the steam pressure is too high, too much refrigerant is generated, consequently the evaporation pressure/temperature may be too low and ice may formed in the evaporator. Excess refrigerant may spill from the refrigerant tray into the sorbent pool in the absorber, loosing its evaporation cooling capacity. If the steam pressure and the solution temperature are too high, corrosion will occur more rapidly in the HTRG and the noncondensable gases will degrade chiller performance. In practice, the sorbent solution temperature should not exceed 160. The chiller control system automatically adjusts the steam valve to avoid excess steam pressure/temperature. Figure 2B-9 shows that a COP increase from 0.61 to 0.99 results from increasing steam temperature from 176 kpa to 644 kpa. It is notable that a steam higher than 300 kpa or 145, changes the COP very little. Figure 2B-10 shows that the cooling loads increase almost linearly with the improvement of steam pressure. The effect of steam pressure/ temperature on chiller 127

11 performance will be further investigated on the basis of a computational performance model developed in chapter 3. Table 2B - 6: Primary inputs and outputs of the tests by varying steam pressure Measurement values for chiller inputs Coolingwater Coolingwater Measurement values for chiller outputs Chilled- Condensate water Cooling load Test F1 F6 T20 T32 T22 T23 F2 T21 Q cooling COP No. m 3 /h kg/s kg/h kw Figure 2B - 9: COP variation with change of steam pressure 1.2 Coefficient of Performance (COP) Thermal COP Overall COP Supply Thermal COP Overall COP Temperature ( ) 128

12 Figure 2B - 10: Cooling load variation with change of steam pressure 20 Measured cooling load (kw) Cooling load Supply Cooling load Temperature ( ) 129

2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control...

2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control... Appendix 2A: Chiller Control Principles... 104 2A.1 Features of Chiller Control Components... 104 2A.2 Start-up and Shutdown... 105 2A.2.1 Start-up...105 2A.2.2 Shutdown...106 2A.3 Chilled-Water Supply

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July 2008. Prepared by

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July 2008. Prepared by Regency TAFE, SA An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump July 2008 Prepared by Andrew Pang Andrew Pang & Associates Pty Ltd Phone: 0438 188 180 Facsimile: 9331 0898

More information

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS 9.1 Introduction Air conditioning and refrigeration consume significant amount of energy in buildings and in process industries. The energy consumed in

More information

New absorption chillers for high efficient solar cooling systems

New absorption chillers for high efficient solar cooling systems New absorption chillers for high efficient solar cooling systems Dipl.-Ing. Stefan Petersen & Dipl.-Ing. Jan Albers Foto: TU Berlin Foto: TU Berlin 1. General Technology Overview 2. Operating data 3. Solar

More information

How To Clean Water From An Ammonia Refrigeration System

How To Clean Water From An Ammonia Refrigeration System Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can

More information

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling HOT & COLD Basic Thermodynamics and Large Building Heating and Cooling What is Thermodynamics? It s the study of energy conversion using heat and other forms of energy based on temperature, volume, and

More information

Absorption. LG HVAC Solution. www.lgeaircon.com

Absorption. LG HVAC Solution. www.lgeaircon.com Ver. 1.0 LG HVAC Solution Absorption chiller www.lgeaircon.com LG Electronics, Air Conditioning & Energy Solution Company 20 Yoido-dong, Youngdungpo-gu, Yoido P.O.Box 355 Seoul 150-721, Korea For continual

More information

The final numerical answer given is correct but the math shown does not give that answer.

The final numerical answer given is correct but the math shown does not give that answer. Note added to Homework set 7: The solution to Problem 16 has an error in it. The specific heat of water is listed as c 1 J/g K but should be c 4.186 J/g K The final numerical answer given is correct but

More information

ADVANCED EXCEL FOR ENERGY EFFICIENCY PROFESSIONALS

ADVANCED EXCEL FOR ENERGY EFFICIENCY PROFESSIONALS ADVANCED EXCEL FOR ENERGY EFFICIENCY PROFESSIONALS TIPS TRICKS & TECHNIQUES A comprehensive web based course on Microsoft Excel specifically tailored for Energy Engineers, Energy Managers, Energy Analysts,

More information

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.

More information

Energy Matters Heat. Changes of State

Energy Matters Heat. Changes of State Energy Matters Heat Changes of State Fusion If we supply heat to a lid, such as a piece of copper, the energy supplied is given to the molecules. These start to vibrate more rapidly and with larger vibrations

More information

ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device

ALONE. small scale solar cooling device Project No TREN FP7EN 218952. Project No TREN/FP7EN/218952 ALONE. small scale solar cooling device Project No TREN/FP7EN/218952 ALONE small scale solar cooling device Collaborative Project Small or Medium-scale Focused Research Project DELIVERABLE D5.2 Start date of the project: October 2008, Duration:

More information

Maintenance for Energy Efficiency

Maintenance for Energy Efficiency Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark

More information

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A Int. J. Mech. Eng. & Rob. Res. 213 Jyoti Soni and R C Gupta, 213 Research Paper ISSN 2278 149 www.ijmerr.com Vol. 2, No. 1, January 213 213 IJMERR. All Rights Reserved PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION

More information

3/29/2012 INTRODUCTION HVAC BASICS

3/29/2012 INTRODUCTION HVAC BASICS INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

GLOBACON 05 HVAC Systems for Cogen

GLOBACON 05 HVAC Systems for Cogen GLOBACON 05 HVAC Systems for Cogen Track 2, Session 2B Advanced HVAC and Building Systems Date: March 24th, 2005 Gearoid Foley President Integrated CHP Systems Corp. Integrated CHP Systems Corp. Electricity

More information

UNIT 2 REFRIGERATION CYCLE

UNIT 2 REFRIGERATION CYCLE UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression

More information

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a

More information

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.

A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem

More information

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling for Simultaneous Heating and Cooling F. Sustainable Energy Centre, University of South Australia Mawson Lakes Boulevard, Mawson Lakes 5095 AUSTRALIA E-mail: Frank.@UniSA.edu.au Abstract The high efficiency

More information

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank

CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS. Blank CHAPTER 7 THE SECOND LAW OF THERMODYNAMICS Blank SONNTAG/BORGNAKKE STUDY PROBLEM 7-1 7.1 A car engine and its fuel consumption A car engine produces 136 hp on the output shaft with a thermal efficiency

More information

Appendix C. Minimum Equipment Efficiency Standards

Appendix C. Minimum Equipment Efficiency Standards Appendix C Minimum Equipment Efficiency Standards Appendix C: Minimum Equipment Efficiency Standards This Appendix is an overview of building and equipment standards in the State of California that have

More information

How To Save Energy With High Pressure Control

How To Save Energy With High Pressure Control Energy savings in commercial refrigeration equipment : High Pressure Control July 2011/White paper by Christophe Borlein AFF and IIF-IIR member Make the most of your energy Summary Executive summary I

More information

AdSORPTION CHILLER NAK

AdSORPTION CHILLER NAK AdSORPTION CHILLER NAK Chilling Capacity from 50 to 430 kw Usage of Surplus Heat from 50 C Ã*%8ÃPE+Ã TECHNICAL DESCRIPTION ADSORPTION CHILLER NAK 1 INTRODUCTION... 2 2 THE PRINCIPLE OF ADSORPTION... 2

More information

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes.

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes. providing insights for today s hvac system designer Engineers Newsletter volume 43 2 Chilled-Water Systems Design Issues Learning from past mistakes As with anything in life, you can learn HVAC design

More information

Research on the Air Conditioning Water Heater System

Research on the Air Conditioning Water Heater System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric

More information

The Second Law of Thermodynamics

The Second Law of Thermodynamics Objectives MAE 320 - Chapter 6 The Second Law of Thermodynamics The content and the pictures are from the text book: Çengel, Y. A. and Boles, M. A., Thermodynamics: An Engineering Approach, McGraw-Hill,

More information

SOLAR-POWERED COOLING, DEHUMIDIFICATION AND AIR CONDITIONING

SOLAR-POWERED COOLING, DEHUMIDIFICATION AND AIR CONDITIONING SOLAR-POWERED COOLING, DEHUMIDIFICATION AND AIR CONDITIONING Prof. Gershon Grossman Faculty of Mechanical Engineering Technion, Israel Institute of Technology Haifa 32000, ISRAEL November 2010 Solar Cooling,

More information

An Overview of Solar Assisted Air-Conditioning System Application in Small Office Buildings in Malaysia

An Overview of Solar Assisted Air-Conditioning System Application in Small Office Buildings in Malaysia An Overview of Solar Assisted Air-Conditioning System Application in Small Office Buildings in Malaysia LIM CHIN HAW 1 *, KAMARUZZAMAN SOPIAN 2, YUSOF SULAIMAN 3 Solar Energy Research Institute, University

More information

Modelling and Simulation of the Freezing Systems and Heat Pumps Using Unisim Design

Modelling and Simulation of the Freezing Systems and Heat Pumps Using Unisim Design Modelling and Simulation of the Freezing Systems and Heat Pumps Using Unisim Design C. Patrascioiu Abstract The paper describes the modeling and simulation of the heat pumps domain processes. The main

More information

COST AND PERFORMANCE ANALYSIS OF A SOLAR THERMAL COOLING PROJECT

COST AND PERFORMANCE ANALYSIS OF A SOLAR THERMAL COOLING PROJECT Proceedings of the ASME 21 4 th International Conference on Energy Sustainability ES21 May 17-22, 21 Phoenix, Arizona, USA 1 ES21-9248 COST AND PERFORMANCE ANALYSIS OF A SOLAR THERMAL COOLING PROJECT Joel

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

HVAC Efficiency Definitions

HVAC Efficiency Definitions HVAC Efficiency Definitions Term page EER - 2 SEER - 3 COP - 4 HSPF - 5 IPLV - 6 John Mix May 2006 Carrier Corporation 1 Energy Efficiency Ratio (EER) The energy efficiency ratio is used to evaluate the

More information

Boilers and cogeneration/trigeneration. Abhi Sawant Business Development Manager Simons Green Energy

Boilers and cogeneration/trigeneration. Abhi Sawant Business Development Manager Simons Green Energy Boilers and cogeneration/trigeneration Abhi Sawant Business Development Manager Simons Green Energy HEATING - COOLING - SUSTAINABLE ENERGY ENERGY EFFICIENCY IN BOILERS, COGENERATION & TRIGENERATION Presented

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Rusty Walker, Corporate Trainer Hill PHOENIX

Rusty Walker, Corporate Trainer Hill PHOENIX Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat

More information

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT ON Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT in the framework of the implementation of

More information

Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling

Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling Yefu Wang1, Xiaorui Wang1,2, and Yanwei Zhang1 ABSTRACT The Ohio State University 14 1 1 8 6 4 9 8 Time (1 minuts) 7 6 4 3

More information

CRAC Precision climate control units for data centres

CRAC Precision climate control units for data centres CRAC Precision climate control units for data centres 2 Rittal Computer Room Air Conditioner The whole is more than the sum of its parts The same is true of Rittal The System. With this in mind, we have

More information

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping

CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes

More information

VACUUM REFRIGERATION SYSTEMS

VACUUM REFRIGERATION SYSTEMS VACUUM REFRIGERATION SYSTEMS CHILL VACTOR The Croll-Reynolds CHILL-VACTOR is a chiller that uses a vapor flashing process. Water has a pressure-temperature relationship which is its boiling point. If its

More information

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential

A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of Low Global Warming Potential International Journal of Scientific and Research Publications, Volume 2, Issue 9, September 2012 1 A Performance Comparison of Vapour Compression Refrigeration System Using Eco Friendly Refrigerants of

More information

Model-Based Performance Monitoring: Review of Diagnostic Methods and Chiller Case Study

Model-Based Performance Monitoring: Review of Diagnostic Methods and Chiller Case Study LBNL-45949 CD-425 ACEEE 2000 Summer Study on Energy Efficiency in Buildings, Efficiency and Sustainability, August 20-25, 2000, Asilomar Conference Center, Pacific Grove, CA, and published in the Proceedings.

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

Secondary Loop Chilled Water In Super High-Rise

Secondary Loop Chilled Water In Super High-Rise The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

AIR CONDITIONING TECHNOLOGY

AIR CONDITIONING TECHNOLOGY AIR CONDITIONING TECHNOLOGY PART 9 Water Cooled Condensers & Cooling Towers IN LAST month s article we looked at how Air Cooled Condensers are used to transfer the total heat of rejection from the air

More information

Model-Based Approach for Optimizing a Data Center Centralized Cooling System

Model-Based Approach for Optimizing a Data Center Centralized Cooling System Model-Based Approach for Optimizing a Data Center Centralized Cooling System Monem H. Beitelmal, Chandrakant D. Patel Enterprise Software and Systems Laboratory HP Laboratories Palo Alto HPL-6-67 April

More information

Commercial Hot Water. Make a difference...

Commercial Hot Water. Make a difference... Commercial Hot Water Make a difference... heat S O L A R pumps The Company Quantum Energy Technologies The Quantum story is based on innovation and the quest to harness renewable energy to produce sustainable

More information

SOLAR COOLING WITH ICE STORAGE

SOLAR COOLING WITH ICE STORAGE SOLAR COOLING WITH ICE STORAGE Beth Magerman Patrick Phelan Arizona State University 95 N. College Ave Tempe, Arizona, 8581 bmagerma@asu.edu phelan@asu.edu ABSTRACT An investigation is undertaken of a

More information

Testing methods applicable to refrigeration components and systems

Testing methods applicable to refrigeration components and systems Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University

More information

Small Business Services. Custom Measure Impact Evaluation

Small Business Services. Custom Measure Impact Evaluation National Grid USA Small Business Services Custom Measure Impact Evaluation March 23, 2007 Prepared for: National Grid USA Service Company, Inc. 55 Bearfoot Road Northborough, MA 01532 Prepared by: RLW

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

More information

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.

Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process. Thermo 1 (MEP 261) Thermodynamics An Engineering Approach Yunus A. Cengel & Michael A. Boles 7 th Edition, McGraw-Hill Companies, ISBN-978-0-07-352932-5, 2008 Sheet 5:Chapter 5 5 1C Name four physical

More information

Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014

Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014 Dharam V. Punwani President, Avalon Consulting, Inc. Presented at Turbine Inlet Cooling Association Webinar April 9, 2014 Background: What is the problem that needs a solution? What is Turbine Inlet Cooling

More information

Type: Single Date: Homework: READ 12.8, Do CONCEPT Q. # (14) Do PROBLEMS (40, 52, 81) Ch. 12

Type: Single Date: Homework: READ 12.8, Do CONCEPT Q. # (14) Do PROBLEMS (40, 52, 81) Ch. 12 Type: Single Date: Objective: Latent Heat Homework: READ 12.8, Do CONCEPT Q. # (14) Do PROBLEMS (40, 52, 81) Ch. 12 AP Physics B Date: Mr. Mirro Heat and Phase Change When bodies are heated or cooled their

More information

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

Impact of Control System Technologies on Industrial Energy Savings

Impact of Control System Technologies on Industrial Energy Savings Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110

More information

Small-Scale Solar Heating and Cooling Systems

Small-Scale Solar Heating and Cooling Systems Contact Austria: AEE INTEC (www.aee-intec.at) France: Tecsol (www.tecsol.fr) Germany: Fraunhofer ISE (www.ise.fraunhofer.de) Greece: CRES (www.cres.gr) Italy: EURAC (www.eurac.edu) University of Bergamo

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

Silicagel-water adsorption cooling prototype system for mobile air conditioning

Silicagel-water adsorption cooling prototype system for mobile air conditioning Silicagel-water adsorption cooling prototype system for mobile air conditioning R. de Boer S.F. Smeding S. Mola Paper to be presented at the Heat Powered Cycles Conference 09 Berlin, 7 to 9 September 2009

More information

Refrigeration and Air Conditioning with Psychrometry

Refrigeration and Air Conditioning with Psychrometry Refrigeration and Air Conditioning with Psychrometry Refrigeration is a process of maintaining low temperature in comparison to surrounding temperature. Refrigeration is the process of removing heat from

More information

Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger

Performance Improvement of an Air Conditioning System Using Matrix Heat Exchanger International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 2, Issue 11 (August 2012), PP. 66-70 Performance Improvement of an Air Conditioning

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

Solar Cooling. Methods and Applications. Sargon Ishaya, PE, LEED AP

Solar Cooling. Methods and Applications. Sargon Ishaya, PE, LEED AP Solar Cooling Methods and Applications Sargon Ishaya, PE, LEED AP Objectives Describe two practical methods for solar cooling Give air conditioning engineers the confidence to offer customers a mechanical

More information

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM J.S. Hu, Philip C.W. Kwong, and Christopher Y.H. Chao Department of Mechanical Engineering, The Hong Kong University of Science and Technology Clear Water Bay,

More information

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine G Vicatos J Gryzagoridis S Wang Department of Mechanical Engineering,

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

Mohan Chandrasekharan #1

Mohan Chandrasekharan #1 International Journal of Students Research in Technology & Management Exergy Analysis of Vapor Compression Refrigeration System Using R12 and R134a as Refrigerants Mohan Chandrasekharan #1 # Department

More information

Modeling Guide for Daikin VRV in EnergyPro 6

Modeling Guide for Daikin VRV in EnergyPro 6 Modeling Guide for Daikin VRV in EnergyPro 6 Table of Contents Introduction... 1 Program Installation... 2 Importing Designated VRV Product File... 3 System Modeling... 6 Modeling air-cooled outdoor units...

More information

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment

More information

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems Fundamental Principles of Environmentally Responsible, Energy Efficient Buildings 1. Energy efficiency is

More information

News in Data Center Cooling

News in Data Center Cooling News in Data Center Cooling Wednesday, 8th May 2013, 16:00h Benjamin Petschke, Director Export - Products Stulz GmbH News in Data Center Cooling Almost any News in Data Center Cooling is about increase

More information

What are the Carrier ChillerVu Energy Dashboards?

What are the Carrier ChillerVu Energy Dashboards? Energy Dashboard CARRIER CORPORATION 2015 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-564-01 12/9/2015 Verify that you have the most current version of this

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

1 Overview of applications and system configurations

1 Overview of applications and system configurations Content 1 Overview of applications and system configurations... 1 1.1 Solar thermal technology... 1 1.2 General Heating (GH)... 2 1.2.1 Heating of large buildings... 3 1.2.2 District heating and Local

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

Simulation of a small size solar assisted adsorption air conditioning system for residential applications

Simulation of a small size solar assisted adsorption air conditioning system for residential applications Heat Powered Cycles Conference 2009 2009 Simulation of a small size solar assisted adsorption air conditioning system for residential applications Salvatore Vasta, Andrea Frazzica, Gaetano Maggio, Alessio

More information

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant

More information

How To Know If A Refrigeration System Is Efficient

How To Know If A Refrigeration System Is Efficient Universitatea de Ştiinţe Agricole şi Medicină Veterinară Iaşi ASSESSMENT OF E SUBCOOLING CAPABILITIES OF A ERMOELECTRIC DEVICE IN A VAPOR COMPRESSION REFRIGERATION SYSTEM R. ROŞCA 1, I. ŢENU 1, P. CÂRLESCU

More information

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore

Variable Capacity Compressors, a new dimension for refrigeration engineers to explore Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents

More information

Creating Efficient HVAC Systems

Creating Efficient HVAC Systems Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical

More information

THE POWER OF COLD Antistaseos 2A Tel: 22575231 Kyriacos@ret.com.cy 2034, Strovolos Mob: 99622425 www.sunchill.net Heat activated absorption refrigeration cycles can be used for heat pumping Free Air Conditioning

More information

SustainE(Sustainable Energy)

SustainE(Sustainable Energy) SustainE(Sustainable Energy) Air Source Heat Pump Water to water Heat Pump Total Energy Heat Pump/Chiller Integrated Heat Pump AHU Swimming Pool Heat Pump Remote Condenser / Radiator H e n n e x S u s

More information

6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through

6 18 A steam power plant receives heat from a furnace at a rate of 280 GJ/h. Heat losses to the surrounding air from the steam as it passes through Thermo 1 (MEP 261) Thermodynamics An Engineering Approach Yunus A. Cengel & Michael A. Boles 7 th Edition, McGraw-Hill Companies, ISBN-978-0-07-352932-5, 2008 Sheet 6:Chapter 6 6 17 A 600-MW steam power

More information

ME 201 Thermodynamics

ME 201 Thermodynamics ME 0 Thermodynamics Second Law Practice Problems. Ideally, which fluid can do more work: air at 600 psia and 600 F or steam at 600 psia and 600 F The maximum work a substance can do is given by its availablity.

More information

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances. C4. Heat Pump I. OBJECTIVE OF THE EXPERIMENT We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances. II. INTRODUCTION II.1. Thermodynamic

More information

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment

Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment Green Building Handbook for South Africa Chapter: Heating, Ventilation and Cooling Luke Osburn CSIR Built Environment The heating, ventilation and cooling loads of typical commercial office space can range

More information

SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS

SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALTERNATIVE REFRIGERANTS INTERNATIONAL JOURNAL OF MECHANICAL ENGINEERING AND TECHNOLOGY (IJMET) International Journal of Mechanical Engineering and Technology (IJMET), ISSN 0976 6340(Print), ISSN 0976 6340 (Print) ISSN 0976 6359

More information

Energy consumption and heat recovery of refrigeration system in modern Arena

Energy consumption and heat recovery of refrigeration system in modern Arena Energy consumption and heat recovery of refrigeration system in modern Arena By Alexander Cohr Pachai Johnson Controls Building Efficiency Christian X s Vej 201 8270 Hoejbjerg Denmark alexander.c.pachai@jci.com

More information

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C

R407C GUIDELINES FOR UTILIZATION OF. DATE: August 2009 REFERENCE DOCUMENT NO. RD-0005-E GUIDELINES FOR UTILIZATION OF R407C GUIDELINES FOR UTILIZATION OF R407C 2009 Tecumseh Products Company. All rights reserved. Page 1 of 6 After many years of testing and investigation, R407C is recognized as a suitable alternative refrigerant

More information

Hines Property Management, NYC

Hines Property Management, NYC Energy Science Division Hines Property Management, NYC Energy Performance Report Summary Results PermaFrost NMR Performance Report Hines - Data Center Chiller January, 2012 This Hines Property Management

More information

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT

More information

8. Heat pumps, heat pipes, cold thermal energy storage

8. Heat pumps, heat pipes, cold thermal energy storage Kylteknik ( KYL ) Refrigeration course # 424503.0 v. 2014 8. Heat pumps, heat pipes, cold thermal energy storage Ron Zevenhoven Åbo Akademi University Thermal and Flow Engineering Laboratory / Värme- och

More information

Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2

Dew Point Tester. Instruction Manual. CVS Regular Chiller Model A-2. CVS Regular Chiller Model A-2 Instruction Manual Dew Point Tester The CVS Dew Point Tester is a chilled mirror apparatus, which operates by attaining the conditions necessary by the definition of dew point. When a gas is cooled out

More information

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL

DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil

More information

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415. Table of Contents Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, 5415 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 HELPER AND INTERMEDIATE JOBS...

More information

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It. I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is

More information

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX Cooling Systems Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX Cooling Water Systems Water is used for cooling because of its capacity to remove and store heat and availability. Cooling water is used in

More information