House Wiring and EMFs
|
|
|
- Sydney Fowler
- 10 years ago
- Views:
Transcription
1 House Wiring and EMFs Introduction (please also read the legal and safety Notes on page 12) Electric and magnetic fields (EMFs) are produced as a result of the flow of electric current. The wiring in our houses, the electric appliances and lights we use, all produce EMFs. EMFs can be measured using an appropriate meter (for details see end of this article add comment). At mains-frequency, the magnetic fields and the electric fields need to be considered separately, and there are different safety guidelines for each. At high frequencies, such as those used for telecommunications, magnetic and electric fields are so linked they are usually considered together as electromagnetic radiation. Frequency means the number of vibrations per second, so high frequency means more vibrations per second. In our homes we are surrounded by EMFs, both from the house wiring and from the appliances which use the electricity supply. This article is about fields from the house wiring. The three illustrations below show examples of EMFs in the home from a lamp and a transformer. The electric and magnetic fields are similar to those produced by house wiring. Switched off This picture shows electric fields from sockets and from the wire to the lamp, even though the light is not switched on. These electric fields are present all the time electricity is present in the wires, even if it is not actually being used. Switched on This picture shows the electric and magnetic fields from the lamp when it is switched on. The electric fields now extend to the lamp. Magnetic fields are also being produced by the current flowing along the wire and light bulb although these usually reduce quickly as you get further away. At the socket This illustration shows a common type of mains-adapter transformer that converts the 230 volt mains electricity to a lower voltage needed for many, usually portable, electronic devices. Once again, both electric and magnetic fields are emitted. The magnetic fields are considerable and can still be high up to half a metre away from the transformer. Page 1 of 18
2 Sometimes transformers are built into radios and music players and are actively emitting magnetic fields all the time the player is plugged into the mains, even when it is not actually in use. A magnetic field is produced whenever an electrical current flows. The larger the current, the higher the magnetic field produced. A mains electricity electrical circuit effectively starts and ends at the local electricity substation transformer. The supply from the substation feeds the building s electricity meter, main switch, consumer unit ( fuse box ) and final circuits. If the outward and return currents are be equal and flow in the same cable (wire bundle), as they should be, then the magnetic fields produced in the house rooms should be negligible. What are normal EMFs? The magnetic fields in the house, with the electricity switched off, should be as low as possible and are usually less than the UK average of 0.04 microtelsa (μt). For detached houses set back from the road, the average fields from outside sources is about 0.02 μt. For flats and for terraced houses right up to the pavement have higher fields, however if they are about about 0.1 μt then an external electrical supply fault should be suspected. External faults are caused by many things, but the commonest are Neutral and Earth currents flowing in the wrong conductors and in metal water and gas pipes. When all go and return currents travel together in the same cable, or bundle of cables, then magnetic fields fall off very rapidly as you move away from the cables. If they don t run together then much higher than usual magnetic fields can extend over wide areas. There is little that you can do to reduce such fields other than pester you local electricity distributor to investigate them and, hopefully, correct Page 2 of 18
3 the worst faults. See External Net Currents later in this document for more technical information about this. In most cases, a cable supplying 230 volts single-phase power will have three conductors; phase and neutral conductors providing the outward and return paths for the current and a safety (protective) earth conductor. The protective conductor usually carries virtually no current except under fault conditions, although some small currents are to be expected from capacitive circuit devices. The protective earth conductor is there to provide an alternative path back to the source for the electricity if a fault to earth occurs. This conductor is usually an uninsulated wire in normal circuit cables but is fitted with green and yellow (or just green on older cables) plastic sleeving at its ends. The Neutral conductor is connected to earth at the local electricity substation (and sometimes elsewhere, too, under protective multiple earthing [PME] schemes) and is used to carry the returning current. This wire is now coloured blue in the UK (compulsory by April 2006 for new installations). It used to be black, which is the colour that will be still be found in most building wiring (installed in 2005 and earlier). The third wire is the Live, Line or Phase conductor and this has the electric pressure (i.e. the voltage) on it and it is the source of the current used to power electrical equipment. This wire now has brown insulation in the UK (compulsory since April 2006 for new installations). It used to be red, which is the colour that will be still be found in most building wiring (installed in 2005 and earlier). The easiest way for an electrician to check the circuits for current flows is by using a clamp-ammeter around the cable. Although this is best done around the Phase/Line and Neutral conductors only, this is not always easy to do. However, in practice, a very good indication is usually obtained by using the clamp-meter around the whole (twin & earth) cable. This is because discontinuities in Line or Neutral will still show up and also any leakage to earth rarely stays in that specific earth conductor. The clamp-meter reading should rarely show more than 0.01 A (10 ma), even when the circuit is loaded using a high load such as an electric kettle or a 3 kw fan heater. If it does, then there is a wiring fault which will be causing elevated magnetic fields. Final ring circuits usually feed the socket-outlets in UK homes. These rings of cable always give rise to higher magnetic fields than simple radial or tree and branch wiring. A tree or radial circuit forces the return current to travel back down the same piece of cable. A ring final circuit is not required, but is recognised, in BS7671 (IEE/IET Wiring Regulations) and is what most electricians traditionally install. They were originally introduced after the second World War in order to minimise the use of copper wire while at the same time allowing for a number of electrical heaters, etc, to be used at the same time. In a ring final circuit, the wires are laid out in a circle (more or less), starting and finishing at the consumer unit (fuse box). This means that current used from a socket-outlet has two possible ways to flow to and from the consumer unit. Currents may not flow equally both ways around the ring, so the magnetic fields produced may not cancel, and the cables then radiate these higher magnetic fields into the room and the adjacent rooms. At every socket-outlet two cables are joined. A small difference in the impedance back each way to the consumer unit around the loop will cause a problem almost as bad as a poor connection. Page 3 of 18
4 A final ring circuit is usually protected against overload current above 30/32 amps, while the cable is nominally rated at only 20 amps. Multiple plug-in electric heaters are other plug-in high amperage loads are now rarely used and it is now most unlikely for the total load on a ring circuit in a house to exceed 20 amps, meaning that a radial circuit with a 20 amp circuit-breaker can be used instead in most areas, except in a kitchen where higher loads are more often used. A circuit can pass the required BS7671 tests but can still have a poor ratio of resistance between different sections of the circuit, leading to unnecessarily high magnetic fields. BS7671 requires ring circuits to be tested by cross connecting line and neutral to form a figure of 8 loop and then resistance readings taken between phase and neutral at each socket, which should be substantially the same. This may detect the asymmetry in resistance that is the problem here, but a ratio of 0.1 to 0.01 ohms will cause a 10:1 split in current flow, hence elevated magnetic fields, as surely as a ratio of 1 to 0.1 ohms. Page 4 of 18
5 In the worst case, which is surprisingly common, a Line or Neutral actually gets disconnected (often as a result of incompetent DIY) and this effectively results in a single-turn transformer loop. When a significant load is applied, the magnetic field in rooms throughout the inside of the ring can rise to many microtesla. Comment: For situation B ~ this is with phase and neutral broken towards opposite ends of the ring. For only one broken ring conductor, the EMF levels will somewhere between the levels shown as A (perfect condition) and B. Page 5 of 18
6 Choosing a consumer unit The consumer unit is the "fuse box" which goes between the electricity meter and all the electrical circuits in the house. Modern units do not contain fuses, but miniature mechanical circuit breakers (MCBs) which have replaced them. They often also contain an extra protective device called a residual current device RCD, which replaces the isolator switch. Modern consumer units can also contain other devices such as time switches and door-bell transformers. In order to keep the electric fields in the house low, we recommend a metal consumer unit (the cheaper ones, often used, are plastic and provide no electric field shielding). We also recommend the use of screened wire for the same reason - see the section on Minimising Electric Fields. The purpose of the MCB is to protect the wiring of its circuit from excessive current due to an overload or short-circuit - in a similar but more controlled way than a wire fuse did. If the rated current is exceeded, the MCB will trip, and merely needs to be switched back on again to re-connect. It is more convenient than a fuse, and it is more obvious to see which one has tripped after a fault occurs. Common values are 6A or 10A for lighting circuits, 16A or 20A for radial power socket circuits and immersion heaters, 32A for ring mains, 7kW electric showers and electric cookers, and 40A or 50A for 8kW and larger ones. RCDs (sometimes wrongly called Earth Leakage Circuit Breakers - see below) are primarily designed to protect against electrocution (death from electric shock) by detecting unbalanced current flows. The RCD monitors the balance of the Neutral and Phase currents and disconnects the circuit if any out-ofbalance current reaches a pre-set limit. Because under normal circumstances there should be very little earth current, they can be made very sensitive: 30 milliamps (0.03 A) is common, with 100 ma (0.1 A) for circuits with motors and higher current switched loads. In some cases, the RCD does not protect all the circuits, in which case there is also an overall isolator switch to disconnect everything. This type of arrangement is called a "split load" consumer unit. Under the latest (2008) 17 th Edition UK Wiring Regulations (BS 7671) many more circuits are required to be protected by a 30 ma RCD and some consumer boxes now have two split multi-mcb circuit groups each of which is protected by an RCD. It is normal to feed a freezer from an unprotected circuit so that in the event of a trip while the house is unoccupied, it will continue to function. Garages and outhouses are also often fed in this way if they have their own RCD, so that the main house RCD will not trip in the event of a fault. RCDs do not protect against overloads so must always be used in conjunction with MCBs. An RCD usually protects several circuits, any one developing a fault will result in them all being disconnected. It can be better to use an RCBO (a combined MCB and RCB) for each circuit, though these are significantly more expensive and physically larger at the present time. Some advanced RCDs/RCBOs have extra features, such as detection of live/neutral reversal or earth disconnection (for which they need an earth sense wire). Page 6 of 18
7 RCDs are current operated, but there is also an older voltage operated Earth Leakage Circuit Breaker (ELCB). There is some confusion over these names. They sense the voltage between the earth of the protected area (e.g. all the sockets and pipes in the house) and "true" earth (the sheath of the incoming supply cable or an earth rod). When there is sufficient leakage current the ELCB will trip, disconnecting the circuits protected by it. It then has to be reset manually. Voltage operated devices have the disadvantage that they can only detect leakage to the earth circuit that passes through them. Thus, they will not detect current passing through the body to the ground when using equipment outdoors, or to current passing through the body to plumbing if it is connected to the ground and therefore cannot be included in the protection circuit. They are now only used when the house is supplied by what is known as a TT system where a Protective Earth Conductor is not supplied by the electricity supply company and the house relies on a local Earth Electrode buried in the ground. Even where TT systems are used, an RCD is generally now preferred to an ELCB. Here is a more detailed diagram of a traditional UK final ring circuit: An alternative for electrical designers and electricians who insist on traditional ring final circuits is the folded ring. Two cables are taken together around the rooms, one connecting to the socket outlets and the other connecting to the final socket outlet to complete the loop. This ensures that magnetic fields are minimised. Radial circuits have low emissions of magnetic fields. It is often possible to convert an existing ring final circuit into one long radial circuit without major rewiring by removing one end connection and lowering the value of the protective device to 20 amps. In other cases it is possible to break the ring near its middle and, likewise, protect the two new circuits with either one or two 20 amp circuit-breakers depending on the expected electrical loading. 2 x 20A radial circuits provides for more load than the original ring final circuit. Page 7 of 18
8 If a Residual Current protective Device (RCD) is used, any significant imbalance in Line & Neutral currents (i.e. any Net currents, which will almost always raise magnetic field levels) will cause the circuit to trip out and indicate a fault. RCDs are usually double-pole devices that switch both the line and neutral conductors. They can cause unnecessary circuit trips when some high loads are suddenly applied to the circuit, especially if these are highly inductive or capacitive loads. An RCD can be combined with an over-current protective device (MCB) in one unit and it is then known as an RCBO. It is now a legal requirement that any (newly wired) sockets that might be connected to an extension cable to be used outside (i.e. if they are close to a garden window) must be protected by and RCD or RCBO. An earthed metal conduit system (with cables or insulated wires in metal pipes), with radial final circuits will always produce the lowest electric and magnetic fields. The earthed metal pipes completely screen the electric field but, generally, have little effect on the magnetic field. Another common cause of high magnetic fields comes from poorly laid-out lighting wiring. When possible, Phase (Live) and Neutral conductors should always be run together, keeping the go and return currents together in the same cables. To minimise magnetic fields, both Live and Neutral should be taken to each luminaire (light) and then the Live take to-and-from each switch as a twin and earth cable. The Live and Neutral conductors should always be connected to the same circuit from the consumer box and should never be connected between different circuits. It is not uncommon to find two-way switched lighting circuits that, incorrectly, interconnect different circuits. This is against the requirements of BS7671. It is important that such circuits are fed from only one Live and are kept with their own Neutral; special 3 core + earth cable (easily available) is required to do this satisfactorily. Electric Fields Page 8 of 18
9 Electric fields are present all the time the home circuits are connected to the mains and not just when current flows. A common cause of elevated electric fields is from the wiring of lighting circuits. It is not always obvious that these are the source, and care needs to be taken interpreting electric field readings taken with hand-held meters. To track down the source it is worth referencing the meter to a known good electrical earth - it can then be used to pinpoint the live sources. Otherwise it is easy to become confused as electric fields can travel through conducting bodies (including people) and then return to a nearby earth - such as a radiator. It is not uncommon to obtain apparently high electric field readings from a radiator, when the source of the field is actually below the floor and the radiator is acting as the return Earth, with the circuit connection being supplied by the person holding the meter. Electric fields are produced by a conductor having a potential (voltage) on it with respect to earth, and an earthed metal conduit or screened cable system effectively provides an electrical screen around all such conductors. The metal mountings for halogen lights should be earthed - this will significantly reduce the electric fields. Ideally, one side of the secondary of the low-voltage transformer should also be earthed, but this is not always possible with electronic low-voltage adapters that are often supplied nowadays. Metal radiators are normally earthed through the legally required earth bonding to the metal water pipes. If plastic pipes are used, it is still recommended that most metal radiators are earthed. This will require an earthing lead to the nearest mains electricity safety earth. Mineral insulated cables (e.g. Pyrotenax) are screened by their metal outer covering, but are expensive to install. Armoured (steel wire screened) cables also emit very little in the way of electric or magnetic fields but are not suitable for general wiring. NOTE: There is a specific British Standard screened cable intended for fixed wiring installations. The standard is BS 8436:2004, Electric cables. 300/500 V screened electric cables having low emission of smoke and corrosive gases when affected by fire. Screened cable to BS 8436:2004 is fully approved for domestic building installations. The soft skin fire cables described below are not intended for this application, although they are satisfactory and may legally be used to reduce electric fields. The other cables, described below, are approved (to BS ) for installations in the UK, but not specifically for residential installations. They are quite adequate (and maybe better for screening) but a Part-P electrical inspector may query their use. BASEC state that they are legal and suitable! Most "FP200" type cables use a solid aluminium or copper screening sheath, however some fireproof cables use a (permitted) polyester screening/fire-protection tape that is not very electrically conductive and will not provide good electric field screening. The wires in the cores are identical for BS and BS The BS 8436 cable has the wires loose inside a strong circular aluminium circular screen which then has a PVC sheath bonded on to it. The cable has the screening foil tightly wound around the inner wires and then the outer sheath is extruded over the top leaving virtually no internal air spaces at all. Page 9 of 18
10 We recommend Prysmian FP200 Gold and also Noburn Platinum fire resistant cable as both have proper metal aluminium earthing shields inside the cable around the wires. Both are very easy to work with (easier than standard twin and earth unscreened cable). No special glands are needed and the outer is very easy to cut round and strip off the inner wires. Please note that FP200 Gold is a Prysmian registered trade mark product, which complies with BS7629. It should not be used as a generic term for other manufacturer's products, especially as thicknesses and materials are frequently different and may have different characteristics. The above two cable types are fully compliant with BS and are BASEC and LPCB approved. In addition to approvals to BS and BS6387 Category CWZ these cables have received BASEC and LPCB approval to BS5839-1:2002 for 'standard' applications. If you require a cable to purely reduce the electric field, and this cable is installed such that it is not required to meet clause , then these cables can be used. "By choice" you should use white (or black) sheathed cable to distinguish it from red alarm cables, but if you use the red cables for general purposes that should be clearly stated next to every consumer/distribution box/panel. Although the screened cables are considerably dearer, the actual cost of the cable is only a relatively small part of the re-wire costs. Labour is usually by far the largest element. You should be able to get the cables locally, but if not these supply them. TLC will supply shorter cut lengths. FP200: Noburn cables: PYROTENAX Multi-Plus fire resistant cable This is another, dearer and stronger cablemulti-plus is a multi-purpose screened and fire-proof wiring cable system from Tyco. MultiPlus is a new generation of high performance cables which has been specifically developed to meet the ever changing needs of the modern building services installation. MultiPlus is a multi-purpose, simple to install, one step cable system. This is available at higher ratings (up to 6mm 2 ) There is also suitable, reasonably priced, screened flexible cable now available (types CY and SY), intended for eliminating electrical interference in industrial and commercial use. The braided screen is electrically separate from the insulated green/yellow earth conductor and they need to be connected at every junction point. Page 10 of 18
11 This can be used for flexible cords but should not really be used for rewiring a house. Page 11 of 18
12 Demand Switches Demand switches can be used to minimise electric fields from circuits which are not actually supplying power. A Demand Switch is an electronically controlled mechanical circuit breaker (MCB) that replaces the 230 volts AC with a low or a DC voltage that is then used to sense when a switch is closed, when the 230 volts AC is automatically re-connected to the circuit. These can be fitted in consumer units and wired in series with the circuit-breaker or fuse. They are not needed if metal conduit or screened cables are used in the installation, but can otherwise be useful for remedial electric field reduction. EMFields stock the most commonly used and generally useful one from Gigahertz Solutions range. It can switch 16 amps and be used for lights (one or two circuits protected at 6A, or one at 10A and one at 6A) or radial power circuits (with a 16A MCB in series, one Demand Switch for each circuit). We do not know of a 30A one suitable for UK ring final circuits, but we would anyway always recommend splitting every ring final circuit into two radial circuits. They will each also need to be protected against overload using 16A MCBs. To reduce electric fields in the home, it really is a much better long-term solution to rewire using screened cable. However, there are times where this is just too much work and expense and fitting a few demand switches is an easier and cost-effective solution. It is usually necessary to install another consumer unit next to the existing one to take the demand switches. It is often easiest to have all the Demand Switches in the new consumer unit and keep the MCBs and RCDs in the existing one. The demand switches are fitted after the MCBs before the cables go off to the lights or to the power sockets. Demand switches do not offer overload protection. External faults in the supply that can cause high magnetic fields The Neutral conductor is connected to Earth at the local electricity substations and, with Protective Multiple Earthing (PME), at regular intervals along the low-voltage electricity distribution system in the locality. This can give rise elevated magnetic field levels, but it is difficult to get the electricity company to do anything about it as the levels are below the ICNIRP guidance of 100 μt and the electricity supply still seems to work correctly for users. Generally, if an Earth facility is provided by the local electricity distribution network operator (DNO), the consumer s Earthing conductor is either connected to the neutral or the cable sheath/armour. Neutral and Earth must not be connected together anywhere else in the building. An undetected Neutral to Earth short circuit can cause a high magnetic field within a building. Insulation tests on the Live and Neutral conductors of each circuit will detect such a fault. Insulation tests must officially be performed when any wiring changes are made (though they often aren t as it is extra hassle for the electrician) and, ideally, at suitable periodic intervals when the building wiring is checked. A Neutral to Earth short-circuit contravenes the requirements of the IEE Wiring Regulations. One problem that causes high magnetic fields due to external distribution problems, but one that can be dealt with by the building owner, are stray net currents flowing on incoming metal gas and water pipes. These stray currents enter, or leave, the building and then transfer via the required electrical safety bonding to the electrical safety earth. The currents are easily detected by either holding a magnetic field meter next to the pipes where they enter the building (the fields Page 12 of 18
13 will rise as you get closer to the pipe) or by using a clamp-ammeter around the pipe. Zero current should be flowing in the pipe. If there is more than about 10 or 20 ma (and it can be as high as several amps), then a short section of suitable plastic pipe should be inserted into the metal pipe. This will break the circuit and stop the current flowing. NOTE! : Internal metal pipework must still be correctly Earth-bonded as per BS7671. Also, the incoming pipe should be isolated as near the ground as possible and any exposed pipe covered with insulating tape or sleeving as, under fault conditions, it would be possible for a significant voltage to exist between the house Electrical Safety Earth and the incoming pipe tail that could give rise to a voltage shock hazard. IMPORTANT NOTES: Remember that electricity can be lethal, and all wiring installations should be checked by a competent person with suitable test equipment to ensure that they are safe and that they fully comply with the UK BS7671 Requirements for Electrical Installations. The Building Regulations (Part P) set out the latest applicable requirements. It is not worth taking any risks with electrical safety in the course of trying to reduce EMFs in the UK, about 20 people are killed by accidental electrocution each year. We are aware that many trades people are set in their normal ways of doing things. Some of the techniques described in this article will be different from what they are used to doing. We believe that the techniques and materials described in this leaflet will provide installations that comply with the latest thinking and requirements of BS7671. If any electrician or electrical contractor disputes this then we would like to hear from them. Please details to [email protected] or [email protected]. It is now illegal for unqualified people to undertake major electrical work without formal independent third-party inspection and test. Meters that measure both electric and magnetic fields can be hired or bought from EMFields This leaflet was mostly written in 2007 and revised in 2009 and in September 2012 by Alasdair Philips, BSc(Eng), DAgE, MIAgE, MInstPhys, for Powerwatch and EMFIELDS. Page 13 of 18
14 Wiring in homes - extract from SAGE Report This is extracted from the First Report (July 2007) of the UK Department of Health s SAGE working group on ELF EMFs. 3.1 Introduction In all homes, the internal wiring makes some contribution to the electric and magnetic fields inside the home. For magnetic fields, however, normal, correctly installed home wiring is rarely a significant source of fields, because go and return currents are usually balanced and close together, resulting in a large degree of cancellation. Home wiring becomes a significant source of magnetic fields only if one of a number of specific features is present (described in more detail in Supporting Paper S9): A ring-main power circuit where, because of an interrupted conductor or a high-impedance joint, the phase and neutral currents split in different proportions round the two arms of the ring, resulting in unbalanced currents. A circuit, usually a two-way switched lighting circuit, where the phase and neutral currents flow different ways round a loop An accidental connection between neutral and earth within the wiring which allows some of the neutral current to return via earth and creates an unbalanced current Loops of current in the vicinity of the electricity meter and the consumer unit The electricity meter itself; traditional rotating disc meters produce relatively high magnetic fields, which fall off over a metre or so but which can be a significant source of exposure eg if a child sleeps with their head close to the meter, including on the other side of a wall. The best data available in the UK 1 suggest that, of the 0.4% of homes (80,000 homes) where fields are greater than 0.4 µt, perhaps a quarter or 0.1% (20,000 homes) are due to house wiring. For electric fields, external sources of field are less significant inside the home because they are screened by the building structure. Wiring in the home is therefore a more significant source of field than for magnetic fields. In addition, the cancellation between phase and neutral is not as effective. Electric fields are produced by all wiring containing a live conductor, unless the wiring is contained in a metal conduit or has a screen in the sheath, and are present all the time. For blocks of flats and apartments, we believe our analysis and conclusions about internal wiring still apply. In addition, however, fields can arise from the way electricity is distributed to the flats within a building. These issues will be considered by the next SAGE Working Group, on Distribution, discussed in Section Options for reducing fields from wiring in the home We looked at a long list of possible options for reducing exposures, so as to be sure of covering everything relevant, including: Primarily to reduce magnetic fields Changing ring power circuits to radial circuits Inserting plastic sections in metal services such as gas and water pipes Keep go and return currents together at all times Protect whole installation with a residual current device (RCD, see Supporting Paper S9) 1 Page 14 of 18
15 Primarily to reduce electric fields Placing all wiring in metal conduits Use all-metal accessories and mounting boxes Use cables with a screen String-pull or remote control light switches Locate sockets away from the bed Apply earthed metal screening tape over cables in walls and ceilings Use demand switches to disconnect voltage when circuit not in use For both electric and magnetic fields Site the meter and consumer unit appropriately Use extra-low-voltage circuits in homes Use DC circuits in homes To allow people to know about and reduce their exposures by their own actions Labelling of meter and installed equipment Requiring a document in each home recording the fields We assessed these options against the following criteria: Safety Effectiveness at reducing fields Level of technical difficulty Complexity to introduce Cost 3.3 Best available options For wiring in homes, there is no single best option, and instead we have identified the following as best available package of options: To reduce magnetic fields: Wire power circuits as radial circuits instead of ring circuits Ensure that go and return currents are kept physically close together at all time, particularly in relation to two-way switching of lights and to the layout of underfloor heating cables Protect the whole electrical installation with a residual current device (RCD) Use electronic electricity meters rather than rotating-disc meters Keep meter tails physically close together Position consumer units (and rotating-disc meters) away from high-occupancy areas To reduce electric fields: Wire homes using cable which has a screen within the overall sheath We have examined these options for their consequences, including safety. None have any serious problems, and specifically, we do not believe that any are less safe than at present, and some bring safety advantages. These options could be applied to varying degrees, which we summarise in Table 3.1. Page 15 of 18
16 Precautionary Action Implementation Characteristics Do nothing; no change to existing situation No legislation, regulation or voluntary codes needed No cost Likely continuing dispute Potential political fallout and continuing criticism No reduction in exposure levels Provide information No legislation or regulation needed Demonstrates acceptance of desirability of reducing exposures Empowers people to make a choice Could either allay or aggravate public concern Low cost Does nothing directly to reduce exposures Voluntary testing of homes for high fields. Remedial action paid for by householder. No legislation or regulation needed. Agreed procedures and training for tests. Empowers people to make a choice Take up may be low (based on radon experience) New wiring practices for all new homes IET guidance to electricians Changes to Wiring Regulations or Building Regulations Reduces exposures in new homes and when homes rewired Additional cost Mandatory testing of existing homes and remediation Building Regulations or other regulation or secondary legislation More effective at reducing high fields now Considerable extra cost Training for electricians (shaded areas show SAGE s preferred options) 3.4 Conclusions As discussed in Section 2.1, our primary focus is to reduce magnetic fields, because it is these which are most strongly associated with childhood leukaemia. For electric fields, we consider more research would be desirable. To apply our package of options to reduce magnetic fields to a new home or when completely rewiring an existing home would, we estimate, cost an additional 20. The benefit in terms of reduced cases of childhood leukaemia ( WHO/HPA ), even assuming that magnetic fields are causal, we estimate as 1 per new home (the details of how we derived these figures are in Supporting Paper S10). Considering other adverse health effects as well as childhood leukaemia ( California, as discussed in Section 1.1) would strengthen the case for these options, but amongst the stakeholders within SAGE we do not have agreement on whether this is appropriate. Therefore, we do not have a clear justification for this package of options in health cost-benefit terms. However, in view of the small absolute cost per home, particularly when seen in the context of the total cost of building a new home, and the fact that there is a trend for some of these options to happen anyway for other reasons, we nonetheless recommend that this package of options should be implemented. Page 16 of 18
17 Therefore we recommend that: The IET should issue guidance to electricians (contained either in the On Site Guide or as a separate Guidance Note) recommending the change to radial power circuits, keeping go and return currents together, and keeping meter tails together. The IET Wiring Regulations Policy Committee should consider this, and the Government representatives on this committee should take responsibility for monitoring acceptance and implementation of this recommendation. We considered the alternative of recommending a change to BS7671 (the wiring regulations ), but felt that guidance to electricians would be just as effective and easier to achieve. BS7671 should be changed to require RCDs for the whole installation. We understand this is likely to happen with the next revision in January 2008 anyway, but if it does not, then the IET should implement it as guidance for electricians as for the previous options. Use of rotating-disc electricity meters should be phased out. There is already a strong trend to this and 95% of meters currently being installed in new properties, and to meet recertification requirement, are electronic. However, it is not clear how this can be made mandatory. Alternatively, depending on how effectively a move to electronic meters can occur, CLG (formerly ODPM) should modify the Building Regulations to specify that electricity meters and consumer units for new homes should not be located close to high-occupancy areas. HPA should produce information for householders on sources of field and steps that can be taken to reduce them. These measures would result in the package of options being applied to new homes and when rewiring is taking place anyway. We do not believe it is justifiable to require these options to be applied retrospectively in all homes. However, if a test shows that high-magnetic fields are present in a home due to some feature of the wiring, we believe it is sensible to take actions to reduce the field, using whichever of these options is appropriate to the source of field that has been identified. Taking such action would also be justified in cost-benefit terms as shown in Supporting Paper S10. We therefore recommend: That where high magnetic fields as a result of house wiring are identified in an existing home, the source of those fields should be removed or remediated. To identify high fields in existing homes, it should be an option that a simple measurement of magnetic fields be performed when either a Periodic Inspection of the house wiring or a Building Survey in connection with the sale of the home is being performed. This would require at least some electricians and surveyors to be suitably trained and equipped. If this test identified high fields, identification of the source might require a separate visit by a more highly trained person. We describe the tests we envisage in Supporting Paper S11. In due course, in the light of experience, a separate decision could be made as to whether to make this test mandatory, perhaps as part of the home buyer s report. Page 17 of 18
18 Occasionally, high fields in one home arise from a source in the neighbouring home. We recognise that the options available to the person affected may be limited in this situation. In line with Supporting Paper S3, we consider that the measures we propose for homes should also be applied to schools, similarly applying to new wiring and available as an option for existing wiring, though we recognise this places an extra burden on school budgets. For electric fields, there is a less strong case for reduction, and we do not recommend that our option should be implemented routinely. Rather, it should be available to those householders or developers who wish to use it. Our option for reducing electric fields requires a type of cable (conventional twin-and-earth but with a screen inside the sheath) that is available at present only at a considerably higher price than normal cable; we recommend that a cheaper version should be developed. In the interim, we give other methods of reducing electric fields which householders or developers can use if they wish, in Supporting Paper S12. The above section (3) is extracted from the First Report (July 2007) of the UK Department of Health s SAGE working group on ELF EMFs. The Stakeholder Advisory Group on ELF EMFs (SAGE) was set up by the Department of Health to explore the implications and to make practical recommendations for a precautionary approach to power frequency electric and magnetic fields. It has now produced its first report, and more information is available from the Department of Health website. The main first report and the supporting papers are worth downloading and reading. Some specifically relate to house wiring. his was followed by a "Cross-Party Inquiry into Childhood Leukaemia and Extremely Low Frequency Electric and Magnetic Fields (ELF EMF)", which was set up to allow the five Members to consider in detail the evidence for an association between Electric and Magnetic Fields (EMF) from High Voltage Overhead Transmission Lines (HVOTL) and an increased risk of childhood leukaemia and determine what should be done. Their findings and recommendations can be found on the epolitix.com website. Page 18 of 18
SELECTION OF FINAL CIRCUIT PROTECTION
SELECTION OF FINAL CIRCUIT PROTECTION By Phil Williams, Product Marketing Manager, Power Distribution Components, Eaton Executive summary The selection of devices for final circuit protection in electrical
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL. Utility Systems Electrical. Main Panel
CHAPTER 4 UTILITY SYSTEMS ELECTRICAL Utility Systems Electrical The electrical supply to your home begins outside, where you will see either an overhead feed and piping down the side of your home or (if
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
GUIDE TO THE AM2 EXAM
AM2 GUIDE TO THE AM2 EXAM What is AM2? AM2 or the Achievement Measurement 2 is a practical performance skill test administered by the National Electrotechnical Training (NET). You must take the AM2 test
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
Safety & Environmental Protection Services Guidance Note
Safety & Environmental Protection Services Guidance Note A STEP-BY-STEP GUIDE TO VISUAL INSPECTION OF ELECTRICAL EQUIPMENT Why Inspect? The Health and Safety at Work etc Act 1974 and the Electricity at
Electrical Resistance Resistance (R)
Electrical Resistance Resistance (R) Any device in a circuit which converts electrical energy into some other form impedes the current. The device which converts electrical energy to heat energy is termed
DIOCESE OF LINCOLN GUIDELINES
DIOCESE OF LINCOLN GUIDELINES FOR ELECTRICAL INSTALLATIONS INSIDE CHURCHES Diocesan Advisory Committee for the Care of Churches Revised March 2006 Electrical Installations inside Churches As with all
Building Regulations P.4. Socket Outlets P.6. Other Considerations P.10. Training Seminars P.24
1 Introduction For well over one hundred years the Wiring Regulations have provided the rules which must be followed to make sure that electrical installations are safe. The introduction of the 17 th Edition
Fire Protection Notice No. 9 ELECTRICAL SAFETY
Fire Protection Notice No. 9 ELECTRICAL SAFETY Because electricity is one of the most controllable forms of energy it can also be one of the safest. But, as industry and commerce draw ever more heavily
INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES
1 By kind permission of MK INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS RESIDUAL CURRENT DEVICES By Mark Coles The IEE receives many enquiries relating to the inspection and testing of electrical
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
DOMESTIC ELECTRICAL INSTALLATION CERTIFICATE (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) DETAILS OF THE CLEINT Client and address ADDRESS OF THE INSTALLATION Installation
PROTECTION AGAINST ELECTRIC SHOCK by John Ware
16 become live under fault conditions. The potential of the metal enclosure is higher than that of the main earthing terminal of the installation (and that of Earth) because of a potential difference created
Inspection and testing of portable electrical equipment
February 2008 Inspection and testing of portable electrical equipment This is a guidance document for Schools and Support Services. Units should use the guidance to help them develop their own local health
Electrical safety and you
Electrical safety and you A brief guide Introduction Electricity can kill or severely injure people and cause damage to property. Every year many accidents at work involving electric shock or burns are
AJ s Technical Tips: Designing a Small Solar PV System Part IV; Selecting Wires for the System
AJ s Technical Tips: Designing a Small Solar PV System Part IV; Selecting Wires for the System A little while back Simon Nyukuri of Kitale wrote to ask me about sizing wires and cables for solar PV systems.
Electrical Practices for Construction Work
1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in
Electrical safety for entertainers
Electrical safety for entertainers Electrical safety for entertainers If you are an entertainer who uses electrical equipment for sound, lighting or other effects, this leaflet is for you. It sets out
Electrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations)
Original Certificate DETAILS OF THE CLIENT Certificate reference: ELECTRICAL INSTALLATION CONDITION REPORT (Requirements for Electrical Installations BS 7671 IEE Wiring Regulations) Name: Address: PURPOSE
Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au
ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks
6.0 Electrical Installations
6.0 An electrical installation is a combination of electrical equipment installed to fulfill a specific purpose and having coordinated characteristics. In dealing with the electrical installation, it is
Screened cable and data cable segregation
December 2007 Screened cable and data cable segregation Can an armoured power cable be considered a screened cable and how does this relate to power and data cable segregation? The short answer is yes;
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
Section B: Electricity
Section B: Electricity We use mains electricity, supplied by power stations, for all kinds of appliances in our homes, so it is very important to know how to use it safely. In this chapter you will learn
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
Indoor Environment Electromagnetic Radiation
Indoor Environment Electromagnetic Radiation Purpose: To increase the students awareness of the sources of electric and magnetic fields and the potential for adverse health effects from prolonged exposure
NEW ZEALAND ELECTRICAL CODE OF PRACTICE REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE
NZECP 50:2004 ISSN 0114-0663 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR REPAIR AND MAINTENANCE OF DOMESTIC ELECTRICAL APPLIANCES BY THE OWNER OF THE APPLIANCE Issued by: Deputy Secretary Energy Safety
Homeowner Information Guide Electrical Safety. British Columbia Safety Authority
Homeowner Information Guide Electrical Safety British Columbia Safety Authority The following information should be carefully reviewed before performing any electrical work. The information contained in
The electrical energy produced at the gen
300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5
Residual Current Devices. Switching on to Safety
Residual Current Devices Switching on to Safety Contents What is a Residual Current Device? 2 Types of RCDs 3 Switchboard RCDs 3 1 Residual Current Devices Socket outlet RCDs 4 Portable RCDs 4 Changes
St Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
St Peter s College ELECTRICAL SAFETY References: A. Peninsula Business Services Guidance Note 4-1, Electrical Safety. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016. Underground branch circuit feeding a detached garage:
Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, 2016 * Garage construction requires permits (electrical, building) * Permits must be applied for at the time. * Dial
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 BASEC APPROVED PRODUCT DATASHEET & APPLICATIONS GUIDE KEY BENEFITS:
PRODUCT DATASHEET & APPLICATIONS GUIDE BASEC APPROVED AFUMEX LSX LOW SMOKE ZERO HALOGEN SCREENED WIRING CABLES BS8436 KEY BENEFITS: BASEC approved for the full size range of BS8436 (1.0mm 2 to 2.5mm 2
chapter8 Testing and commissioning Unit 2 outcome 2
Testing and commissioning chapter8 Unit 2 outcome 2 It is important that electricians are not just able to construct; they should also be able to recognise faults and take action to help prevent them.
HOUSING QUALITY STANDARDS (HQS)
HOUSING QUALITY STANDARDS (HQS) Series 5 Electrical Safety And INSPECTIONS 5.01 ELS Revised 8-17-06 Electricity is Dangerous All electrical repairs should be made by licensed professionals. Touching any
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS
MISCELLANEOUS ELECTRICAL JOBS REQUIRING PERMITS 01. SAFETY INSPECTION of service equipment at FPL Power Source 02. Construction GFI power outlets (Temp Pole for Construction) 03. 90 day temporary power
A B Brown. This sheet forms part of *Inspection Report Number/*Certificate Number NA/ * EC/ * PIR *Delete as applicable DB1 60898
NAPIT Electrical Test Continuation Sheet Requirements for Electrical Installations BS 767 [IEE Wiring Regulations] and for Please complete all the unshaded areas. This sheet forms part of *Inspection Report
Electrical Safety Plugs What are the different types of plugs? Extension Cords What are some potential hazards involving extension cords?
Electrical Safety Electricity can be a friend, but it can also hurt if you do not treat it with respect. Everyday someone loses his or her home or business due to an electrical fire. These tragedies are
Unit 4: Electricity (Part 2)
Unit 4: Electricity (Part 2) Learning Outcomes Students should be able to: 1. Explain what is meant by power and state its units 2. Discuss the importance of reducing electrical energy wastage 3. State
Complete Solar Photovoltaics Steven Magee. Health and Safety
Health and Safety Health and safety around solar photovoltaic systems is very important. In the DC circuit you will find up to 600 volts in residential and commercial systems. In utility systems you may
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
ScottishPower Distribution Cables & Equipment. Metal Theft
ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated
A guide to our training courses and premises. 01444 872 145 www.electriciancourses4u.co.uk
A guide to our training courses and premises Contents 3. About Us 4. Why Us? 5. Our Premises 6-16. Training Courses 6. Domestic Electrician Course 7. Domestic Electrician Package 8. 17th Edition Course
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Maintaining portable electric equipment in low-risk environments
Maintaining portable electric equipment in low-risk environments Introduction This leaflet explains the simple and sensible precautions that need to be taken to prevent danger from portable or movable
ONLINE VERSION ONLINE VERSION ONLINE VERSION. 2006 edition. Electrical safety dwellings APPROVED DOCUMENT. The Building Regulations 2000
The Building Regulations 2000 P1 P Design and installation of electrical installations APPROVED DOCUMENT Coming into effect 6 April 2006 2006 edition Amendments to Approved Documents and Compliance Guides
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS
GUIDELINES FOR ELECTRICAL WIRING IN RESIDENTIAL BUILDINGS 2008 EDITION www.st.gov.my CONTENTS Chapter Title Page 1. 1.1 1.2 1.3 Introduction Purpose References 4 4 5 2. Supply System 6 2.1 Electricity
Building Services Engineering Technician
Building Services Engineering Technician A competent Building Services Engineering Technician is expected to be able to demonstrate the following skills and competences: Systems design in the building
ions T ondi Terms & C
Terms & Conditions CONTENTS: 1.0 What s Covered 1.1 MyCare 1.2 MyCare Plus 2.0 Qualifications 2.1 General 2.2 Gas Packages 2.3 My Care Plus 3.0 Exclusions 3.1 General 3.2 MyCare Plus Exclusions 4.0 General
ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1
ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1 Design and Planning Specification for New Low Voltage Installations for Housing Developments 1. SCOPE This appendix to ENA
2 electrical. electrical. 2010 PulteGroup, Inc. All Rights Reserved.
2 12 2010 PulteGroup, Inc. All Rights Reserved. circuit breakers Circuit breakers protect your home s system from power failure. The wiring in your home is protected by circuit breakers. Circuit breakers,
Residual Current Circuit Breaker
Introduction Residual Current Circuit Breaker / ELCB The Fault current overloads and short circuits can be detected by circuit breakers like MCB s MCCB s & HRC Fuses etc. But, Circuit breakers don t detect
WATER LEAKS AND DAMAGE
WATER LEAKS AND DAMAGE OUTLINE A quarter of all insurance claims made on flats are for damage caused by water leaks. The damage caused costs millions of pounds, heartache to those involved and disputes
Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13
Interfacing electrification and system reliability Roger White Professional Head of Electrification and Plant Rail Abstract Integration is the term given to ensuring that the different elements of an electrified
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and
PART P: DOMESTIC ELECTRICAL SAFETY April 2006 Revisions (modified April 2007)
THE BUILDING REGULATIONS Guide for Householders, Designers and Builders PART P: DOMESTIC ELECTRICAL SAFETY April 2006 Revisions (modified April 2007) THE BUILDING REGULATIONS PART P : Domestic Electrical
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT
**ATTENTION** WE DO NOT PROMOTE OR ENCOURAGE YOU TO DO YOUR OWN ELECTRICAL WIRING!!! IT IS BY FAR THE MOST DANGEROUS THING YOU CAN ATTEMPT. YOU COULD PUT YOUR FAMILY AND WORLDLY POSSESSIONS IN DANGER!!!
Earthing Guidance Notes
Central Networks Earthing Manual Section E2 Earthing Guidance Notes Version: 2 Date of Issue: September 2007 Author: Nigel Johnson Job Title: Earthing Specialist Approver: John Simpson Job Title: Head
Electrical Hazards. Power Tools. Extension Cords
Electrical Hazards Electrical hazards can be found in nearly every roofing work site. Whether the hazard is posed by worn or damaged power tools or cords, improperly grounded tools or equipment, or the
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov PHOTOVOLTAIC PERMITTING GUIDELINES The information provided in this document is general and is intended only as a
Odyssey of the Mind Technology Fair. Simple Electronics
Simple Electronics 1. Terms volts, amps, ohms, watts, positive, negative, AC, DC 2. Matching voltages a. Series vs. parallel 3. Battery capacity 4. Simple electronic circuit light bulb 5. Chose the right
For Models #6-5001, #6-7501, #10-7501 & #10-12K1
EmerGen Switch Manual Transfer Switch Manufactured by CONNECTICUT ELECTRIC SWITCH MFG. CO. 1-800-730-2557 OWNER S MANUAL & INSTALLATION INSTRUCTIONS For Models #6-5001, #6-7501, #10-7501 & #10-12K1 PLEASE
A guide to understanding and maintaining your home s electrical system. A publication presented by the Electrical Safety Foundation International
A guide to understanding and maintaining your home s electrical system A publication presented by the Electrical Safety Foundation International What s Inside? Everything you need to know Should You Do-It-Yourself?
Electrical test equipment for use on low voltage electrical systems
Electrical test equipment for use on low voltage electrical systems Guidance Note GS38 (Fourth edition) This general series guidance note is aimed at people (including electricians, electrical contractors,
Guidance notes for the installation of electrical supply in mobile trailers for breast screening
NHS Breast Cancer Screening Programme Cancer Screening Programmes Guidance notes for the installation of electrical supply in mobile trailers for breast screening B Mansfield, CP Lawinski NHSBSP PUBLICATION
RCD Inspection Log Book
RCD Inspection Log Book This book is the property of: Commenced: / /. Completed: / /. 2 Clipsal Australia Pty Ltd Clipsal Australia Pty Ltd 3 4 Clipsal Australia Pty Ltd Clipsal Australia Pty Ltd 5 6 Clipsal
THERMONET UNDERFLOOR HEATING STANDARD THERMOSTAT KIT STOCK CODE 5260
THERMONET UNDERFLOOR HEATING STANDARD THERMOSTAT KIT STOCK CODE 5260 STANDARD THERMOSTAT KIT 1.0 KIT CONTENTS Parts included: 1 x Thermostat 1 x Wall plate 2 x Mounting box screws 1 x Floor temperature
The Different Types of AC Power Connectors in North America
The Different Types of AC Power Connectors in North America White Paper #20 Executive Summary A confusing array of AC power plugs and receptacles exist to deliver power to various electronic loads. This
chapter6 Basic electrical circuitry and applications Unit 2 Outcome 3
Basic electrical circuitry and applications chapter6 Unit 2 Outcome 3 The primary role of an electrician is the installation of electrical circuits and applications. In order to install any type of application,
Construction Electrical Terminology. Electricians
Construction Electrical Terminology Electricians Acknowledgments Winnipeg Technical College and the Department of Labour and Immigration of Manitoba wish to express sincere appreciation to all contributors.
1. The diagram below represents magnetic lines of force within a region of space.
1. The diagram below represents magnetic lines of force within a region of space. 4. In which diagram below is the magnetic flux density at point P greatest? (1) (3) (2) (4) The magnetic field is strongest
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
Regulation IO-6.0: Electrical Safety Regulations
Regulation IO-6.0: Electrical Safety Regulations 6.1 Workmanship & Material 6.2 Electrical Conductors 6.3 Overcurrent Protective Devices 6.4 Precautions against Earth Leakage and Earthfault Currents 6.5
Neutral Wire Facts and Mythology. White Paper #21
Neutral Wire Facts and Mythology White Paper #21 Executive Summary This Technical Note discusses many common misunderstandings about the function of the neutral wire and its relation to power problems.
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
Electrical installation condition reporting:
Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations FUSED 4 Issue 3 This is one of a series of Best Practice Guides produced by the Electrical
Balanced vs. Unbalanced Audio Interconnections
Revised 7/2/08 Balanced vs. Unbalanced Audio Interconnections In discussing the characteristics and performance of various interconnect systems; two points should be kept in mind. Balance is defined in
October Safety Subject
October Safety Subject Electrical Hazards All electrical equipment should be kept in good repair. Replace defective equipment or have it repaired by a qualified person. Watch for wiring on appliances that
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
Ontario Electrical Safety Code 25 th Edition/ 2012
Ontario Electrical Safety Code 25 th Edition/ 2012 Ted Olechna Director, Codes and Standard Chief Engineer 1 What I Will Cover ESA s role is as the regulator Highlight of 2012 Code changes The Code and
INFRARED QUARTZ WALL HEATER
INFRARED QUARTZ WALL HEATER MODEL NO: IQ2000 PART NO: 6939004 MOUNTING & OPERATION INSTRUCTIONS GC0715 INTRODUCTION Thank you for purchasing this CLARKE Infrared Wall Heater. Before attempting to use this
FIRE RESISTANT CABLES FP200 GOLD
FIRE RESISTANT CABLES FP200 GOLD FIRE RESISTANT CABLES FP200 GOLD BS7629-1:2008 Certificate No 077f Certificate No 077k FP200 GOLD The original highly durable and dressable, easy to terminate and install
County of Riverside Building and Safety Department
County of Riverside Building and Safety Department Mike Lara Director Photovoltaic Permitting Guidelines The information provided in this document is general and is intended only as a guide. Each project
LOXONE 12 Channel Amplifier
LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL 34471 (352) 629-8421; FAX: (352) 629-8264
BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
ELECTRICAL PRACTICES FOR CONSTRUCTION WORK
CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational
USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES
USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES 204.CAxxx 204.CBxxx 204.UBxxx 204.WBxxx MP36289 1 ZP90856-GB-6 INDICE 1 SYSTEM DESCRIPTION... 4 1.1 MODES OF OPERATION... 4 2 USER INTERFACE... 6 2.1
employed to ensure the continuing reliability of critical systems.
4 Regulations 1989, Regulation 4, places a duty on employers to provide safe systems for their workers: Regulation 4 of the Electricity at Work Regulations 1989 Systems, work activities and protective
Questions and Answers for Heating and A/C Contractors
1. How do we accomplish grounding of furnaces and / or water heaters on two wire circuits? 250.134 Equipment Fastened in Place or Connected by Permanent Wiring Methods (Fixed) Grounding. Unless grounded