PART C SECTION 5 SUBSECTION 5B
|
|
|
- Lionel Goodwin
- 10 years ago
- Views:
Transcription
1 Australian Transport Council National Standard for Commercial Vessels PART C DESIGN AND CONSTRUCTION SECTION 5 ENGINEERING SUBSECTION 5B ELECTRICAL Edition 2
2 Part C Section 5 Subsection 5B Edition 1 Draft for public comment issued 22 December 2000 Endorsed by the Australian Transport Council July 2002 First Published August 2002 (on CD) Second Publication April 2005 (on CD) Edition 2 Draft for public comment issued 10 December 2004 Endorsed by the Australian Transport Council 18 December 2005 First published 1 December 2005 (PDF version on web) Amendment 1: April 2011 Edition 2.1, incorporating Amendment 1, First published: April 2011 Commonwealth of Australia This work is copyright. Apart from any use as permitted under the Copyright Act 1968, no part may be reproduced by any process without written permission of the Chief Executive Officer, NMSC Inc. Published by The National Marine Safety Committee Inc, Level 5, 9-15 Young Street, Sydney NSW All inquiries to be addressed to the Chief Executive Officer, NMSC Inc. ISBN: Edition 2.1 Page 2 April 2011
3 Part C Section 5 Subsection 5B FOREWORD Edition 1 of this subsection of the was developed following a review of the Uniform Shipping Laws Code (USL) Code Section 9: Engineering, and replaced part 4: Electrical of that Section. The following documents were consulted during the development of this subsection of the NSCV: IEC Electrical installations in ships ISO Small craft Electrical systems Extra-low-voltage d.c. installations ISO Small craft - Electrical systems - Alternating current installations AS 1852 International electrotechnical vocabulary These documents may provide assistance to users of this Subsection. Public consultation was carried out in 2000 and 2001 with Edition 1 of this subsection being endorsed by the Australian Transport Council (ATC) in July 2002, and published on CD in August Edition 1 of this subsection had not been adopted through legislation. Following publication of Edition 1 of this subsection, a number of concerns were raised regarding the fact that the standard followed class society rules, rather than Australian standards. In 2003 NMSC commenced a revision of this subsection. The revised version was reviewed by a reference group comprising government and industry prior to release for public comment in December Public comment was reviewed by a reference group comprising industry and government in April 2005, with the recommendations of the group being accepted by NMSC in July The final draft of this subsection was approved by NMSC in August 2005, and endorsed by ATC on 18 November The Regulatory Impact Statement was prepared in accordance with COAG guidelines, and the final draft of the RIS was accepted by the Office of Regulatory Review (ORR). The major change between Edition 1 and 2 of this subsection is a requirement for vessels to comply with AS/NZS 3000: Electrical installations (known as the Australian/New Zealand Wiring Rules). Compliance with AS/NZS 3000 has meant a large number of prescriptive requirements have been deleted. Those remaining are specific requirements needed to meet the special conditions found on vessels and in the marine environment. Edition 2 was later subject to a correction amendment. Amendment 1 to Clauses (a) and (b) was endorsed by NMSC on 22 March 2011 and published in April This Subsection of the is intended to be read in conjunction with Part A Safety Obligations, and Part B General Requirements. April 2011 Page 3 Edition 2.1
4 Part C Section 5 Subsection 5B CONTENTS CHAPTER 1 PRELIMINARY Scope Application Objective Required outcomes Referenced documents Definitions Abbreviations CHAPTER 2 COMMON REQUIREMENTS FOR ALL ELECTRICAL SYSTEMS Scope Required outcomes Safety protection Functionality and reliability Protection against overcurrent Watertight and fire integrity Isolation Emergency supply Operation and maintenance Batteries Deemed-to-satisfy solutions Compliance Isolation Radios Earthing and bonding Navigation lights and navigation equipment Cables and wiring systems Lightning protection Unacceptable components materials and methods Engine room and cargo space ventilation Equipment and accessories in exposed locations Over current protection of essential services Edition 2.1 Page 4 April 2011
5 Part C Section 5 Subsection 5B 2.21 Commissioning inspection and testing Design Parameters CHAPTER 3 EXTRA-LOW VOLTAGE SYSTEMS AND BATTERIES Scope Application Required Outcomes Required outcomes Deemed-to-satisfy solutions Compliance Provisions of AS/NZS 3000 not to apply Engine starting cables Switches and circuit protection Batteries and battery installations Ventilation of batteries and battery compartments CHAPTER 4 LOW VOLTAGE SYSTEMS Scope Application Required outcomes Required outcomes Deemed-to-satisfy solutions Compliance Multiple earthed neutral (MEN) system Residual current devices Shore supply Generators control and instrumentation Inverters CHAPTER 5 EMERGENCY ELECTRICAL INSTALLATIONS Scope Objective Application Required outcomes General Function of essential services to be maintained April 2011 Page 5 Edition 2.1
6 Part C Section 5 Subsection 5B 5.6 Period of operation Emergency lighting Deemed-to-satisfy solutions Compliance General Power source Emergency switchboard Equipment required to be supplied with emergency power Capacity of emergency power supply Emergency lighting THIS PAGE LEFT BLANK Edition 2.1 Page 6 April 2011
7 Part C Section 5 Subsection 5B CHAPTER 1 PRELIMINARY 1.1 SCOPE This Subsection of the NSCV specifies the following: a) Common requirements for all electrical systems (Chapter 2). b) Specific requirements for extra-low voltage systems (Chapter 3). c) Specific requirements for low voltage systems (Chapter 4). d) Emergency electrical installations (Chapter 5). This Subsection of the NSCV shall be read in conjunction with Part B General Requirements of the NSCV. 1.2 APPLICATION Vessels of measured length 35 metres or more The electrical installations on vessels of measured length 35 m or more shall a) meet the requirements of, and be assessed under, the rules of a Classification Society; and b) comply with the requirements of Clauses 2.2 to 2.9 of this Subsection. NOTE: Classification Society is defined in NSCV Part B. In addition, electrical installations on the following vessels of measured length 35 m or more shall also comply with the following: i) Class 1A vessels shall comply with the requirements specified in Marine Orders Part 12 for SOLAS passenger vessels. ii) Class 2A and 3A vessels of 500 GT and over shall comply with the requirements specified in Marine Orders Part 12 for SOLAS cargo vessels Vessels of measured length less than 35 metres The electrical installations on vessels of measured length less than 35 m shall comply with this Subsection of the NSCV. Class 1A vessels of measured length less than 35 m shall also comply with the requirements for electrical installations specified in Marine Orders Part 12 for SOLAS passenger vessels Exceptions This subsection does not apply to Special Vessels provided for in Part F of this standard, unless Part F specifies otherwise. 1.3 OBJECTIVE NOTE: Such vessels include fast craft, hire and drive vessels and novel vessels. The objective of this Subsection is to provide vessel designers and builders with specifications on how to design, install and repair the electrical system April 2011 Page 7 Edition 2.1
8 Part C Section 5 Subsection 5B so that, when used with reasonable care and under normal conditions, the system will a) perform reliably; and b) minimise the risk of hazards such as fire and personal injury. 1.4 REQUIRED OUTCOMES In this Subsection of the NSCV, Chapter 2 specifies the required outcomes for the electrical system and installation as a whole. Where necessary, subsequent Chapters specify additional required outcomes for the part of the electrical system dealt with in that Chapter. The required outcomes are mandatory to the extent that they are applicable to a particular vessel. The required outcomes within each Chapter are followed by solutions that are "deemed-to-satisfy" these required outcomes. Compliance with required outcomes may also be achieved through the application of the equivalent solutions that comply with the principles set out in Part B of this National Standard. When developing an equivalent solution, it is a requirement of this National Standard that the overall system safety is maintained. NOTE: A proposed solution that satisfies one or more required outcomes in isolation but has negative effects on compliance with other required outcomes would not be considered an equivalent solution under Part B of this National Standard. 1.5 REFERENCED DOCUMENTS The following documents are referenced in this Subsection of the NSCV. Any referenced document shall be considered to be the latest revision of the document, including amendments and supplements. NATIONAL MARINE SAFETY COMMITTEE Part B General Requirements Part C Design and Construction Section 4: Fire Safety Section 5: Engineering Subsection 5A-Machinery Section 7: Equipment Subsection 7A Safety Equipment Subsection 7B Communication Equipment STANDARDS AUSTRALIA/STANDARDS NEW ZEALAND AS/NZS 1125 Conductors in insulated electric cables and flexible cords AS/NZS 1768 Lightning protection AS Guide to the installation, maintenance, testing and replacement of secondary batteries in buildings - Vented cells Edition 2.1 Page 8 April 2011
9 Part C Section 5 Subsection 5B AS Guide to the installation, maintenance, testing and replacement of secondary batteries in buildings - Sealed cells AS/NZS 3000 Electrical installations (known as the Australian/New Zealand Wiring Rules) AS/NZS 3004 Electrical installations Marinas and pleasure craft at low voltage AS/NZS Electrical installations Selection of cables cables for alternating voltages up to and including 0.6/1 KV Typical Australian installation conditions AS Electrical installations - Secondary batteries installed in buildings - Vented cells AS Electrical installations - Secondary batteries installed in buildings - Sealed cells AS/NZS 3017 Electrical installations - Testing and inspection guidelines AS/NZS 3112 Approval and test specification Plugs and socket-outlets AS/NZS 3123 Approval and test specification - Plugs, socket-outlets and couplers for general industrial application AS/NZS 3187 Approval and test specification - Mineral-insulated metalsheathed cables AS/NZS 3191 Electric flexible cords AS/NZS Electric cables - Polymeric insulated for working voltages up to and including 0.6/1 kv AS Degrees of protection provided by enclosures (IP Code) AS/NZS Safety of power transformers, power supply units and similar Part : Particular requirements for portable inverters AUSTRALIAN MARITIME SAFETY AUTHORITY Marine Orders Part 12 Construction Subdivision & Stability, Machinery and Electrical Installations 1.6 DEFINITIONS For the purposes of this Subsection of the NSCV a) the definitions provided in Part B of the NSCV, in addition to those in this Clause, shall apply; and b) the definitions in AS/NZS 3000 shall apply. Where there is any duplication in the terms defined in this subsection and the definitions in AS/NZS 3000 or the definitions in Part B of the NSCV, the definitions in this Clause shall apply. battery compartment a room, locker or space used solely for the storage of batteries. April 2011 Page 9 Edition 2.1
10 Part C Section 5 Subsection 5B earth the conductive mass of earth, whose electric potential at any point is conventionally taken as equal to zero. NOTE: A vessel's earth is established by a conducting connection (intentional or accidental) with the earth, including any conductive part of the wetted surface of a hull. earth electrode all earth connections, including a main earth connection, to the hull of a metal hulled vessel and the connection(s) to the earth plate of a vessel with a non conductive hull. Earth electrodes include hull or earth plate connections for protective earthing, equipotential bonding, lightning protection, and/or communication systems. emergency switch board (ESB) a switchboard supplied by the emergency source of power and from which the emergency electrical installation can be supplied. essential services those services essential for safety of persons and safe navigation. NOTE: This may include auxiliaries necessary for propulsion and power generation, steering gear, watertight doors, bilge and fire pumps, engine room ventilation, navigation lights, emergency lighting, communication equipment, navigation aids, and alarm systems. inverter a device that uses semi-conductor devices to transfer power between a d.c. source or load and an a.c. source or load. isolated earth system a system of distribution in which no point is normally connected to earth. licensed electrician a person licensed or authorised by a state or territory electrical licensing authority to carry out electrical work in that state or territory. main switch board (MSB) a switchboard directly supplied by the main source of electrical power and from which the whole electrical installation can be supplied. shore supply a supply of electrical energy located onshore or at any other source external to the vessel. voltage the difference in potential between conductors and between conductors and earth as follows: a) extra-low voltage (ELV) not exceeding 50 V a.c. or 120 V d.c. b) low voltage (LV) exceeding extra-low voltage but not exceeding 1000 V a.c. or 1500 V d.c. c) high voltage (HV) exceeding low voltage. NOTE: From AS/NZS Edition 2.1 Page 10 April 2011
11 Part C Section 5 Subsection 5B 1.7 ABBREVIATIONS ELV Extra-low voltage ESB emergency switchboard LV Low voltage HV High voltage MEN multiple earthed neutral MSB main switchboard RCD residual current device April 2011 Page 11 Edition 2.1
12 Part C Section 5 Subsection 5B CHAPTER 2 COMMON REQUIREMENTS FOR ALL ELECTRICAL SYSTEMS 2.1 SCOPE This Chapter sets out the requirements for electrical equipment and electrical installations that are common to all electrical systems used in vessels. REQUIRED OUTCOMES 2.2 SAFETY PROTECTION Protection must be provided to prevent inadvertent contact by personnel and passengers with parts of the electrical installation that are live in normal service and those that may become live during fault conditions. Electrical equipment and installations must minimise the risk of fire, damage and physical injury when a vessel's electrical equipment is used with reasonable care. Minimisation must include overcurrent protection, appropriate insulation, appropriate construction, fault indication, safety trips, and effective operational and maintenance procedures. 2.3 FUNCTIONALITY AND RELIABILITY A vessel's electrical installation must be designed, and electrical equipment selected and installed, so as to maintain the functionality and reliability of the installation under operating conditions expected in the marine environment. The functionality and reliability of systems and equipment necessary for the safe operation of the vessel must be maintained during normal and emergency operations (e.g. avoidance of electromagnetic interference with navigation equipment). The vessel's electrical installation must be of a quality and standard that will limit the degradation of the installation from the extreme conditions expected in the marine environment (e.g. electrochemical corrosion). 2.4 PROTECTION AGAINST OVERCURRENT Protection must be provided against damage due to excessive temperature rise or electromechanical stresses caused by over-currents that may arise in conductors. 2.5 WATERTIGHT AND FIRE INTEGRITY Where a wiring system passes through a deck or bulkhead that is required to be of watertight or fire-rated construction the integrity of the construction must be maintained. Where the routing of a wiring system requires the penetration of solid surfaces such as bulkheads or decks, the wiring system must be effectively protected from mechanical damage. 2.6 ISOLATION Electrical installations, and parts of installations, must be provided with isolation devices to prevent or remove hazards associated with abnormal Edition 2.1 Page 12 April 2011
13 Part C Section 5 Subsection 5B operation (e.g. faults such as short circuits) and to allow maintenance of electrical equipment. 2.7 EMERGENCY SUPPLY Electrical services essential for personal safety, the safety of the vessel and the safety of navigation must remain operational under emergency conditions. 2.8 OPERATION AND MAINTENANCE The electrical system of a vessel must be designed and installed to facilitate its identification, safe use, inspection and maintenance. 2.9 BATTERIES Battery installations must be designed and installed to eliminate or minimise risks associated with the emission of gases, corrosive fluids, electrochemical corrosion, movement, mechanical damage, and exposed terminals. DEEMED-TO-SATISFY SOLUTIONS 2.10 COMPLIANCE For the purpose of this National Standard, the common requirements for an electrical installation shall be deemed-to-satisfy the required outcomes in Clauses 2.2 to 2.9 if they comply with a) AS/NZS 3000 Electrical installations; and c) Clauses 2.11 to 2.22 of this Chapter. Where there is any conflict in the requirements in this Subsection and the requirements in AS/NZS 3000 Electrical installations the requirements in this Subsection shall apply ISOLATION 2.12 RADIOS Isolation devices must operate in all active conductors but must not interrupt a neutral conductor unless allowed for in AS/NZS 3000 or in this standard. Isolation devices must not interrupt an earthing conductor. The electrical power supply for radios shall comply with the relevant requirements of Part C Subsection 7B Communication Equipment of the NSCV. April 2011 Page 13 Edition 2.1
14 Part C Section 5 Subsection 5B 2.13 EARTHING AND BONDING Earthing General Earthing arrangements shall comply with AS/NZS 3000 and the provisions in Clauses to of this Chapter Earthing systems Method of earthing The method of earthing for a.c. systems at voltages greater than 50 V shall be a) a multiple earthed neutral (MEN) system; or b) an isolated earth system. The method of earthing for d.c. systems shall be i) a negative earth; or ii) an isolated earth. NOTES: 1. AS/NZS 3000 provides guidance for earthing of ELV systems. 2. An installation may include mixed methods of earthing. Earthing systems should be mixed only after consideration of the possible fault currents in each system Main earth connection In a vessel with a hull constructed wholly of metal, the main earth conductor shall be taken from the earth terminal, bar, or link at the main switchboard to an earth electrode solidly connected to the hull. In a vessel with a hull not constructed wholly of metal, the main earth conductor shall be taken from the earth terminal, bar, or link at the main switchboard to an earth electrode solidly connected to an earth plate The main earth conductor shall run in as direct a manner as practicable and shall not be connected to any other appliance MEN earth systems In an MEN earthing system the neutral to earth bond should be made at each generator. NOTE: This avoids tripping of shore based RCDs. The MEN bond is switched out of the system because the shore power/vessel supply changer over switch operates in all live conductors Isolated earthing systems An electrical system isolated from earth shall employ an earth fault monitor or insulation resistance monitor. Where earth lamps are used for this function, the lamps shall a) be of a filament type; b) not exceed 30 W; Edition 2.1 Page 14 April 2011
15 Part C Section 5 Subsection 5B c) be of the same colour; d) be placed not more than 125 mm apart; and e) have a lamp test capability. Each generator in an isolated earth system shall have an earth fault monitor or insulation resistance monitor Earthing and bonding electrodes All connections to the vessel's hull or earth plate shall a) be accessible for inspection; b) be secured by means of a screw or stud used for this purpose only with a diameter suited to the size of the earth conductor but not less than 6 mm; c) be protected against corrosion; and d) remain unpainted. NOTE: Care should be taken to ensure bright metallic surfaces at the contact areas immediately before the nut or screw is tightened. The use of washers of a type that bite into the metal is recommended. To protect against electrolytic corrosion, care must be taken in the choice of metals and methods used to make the connection. Where necessary the joint should be protected with anti-oxidation grease. Earth electrodes used for the connection of lightning protection to a vessel's hull or earth plate shall not be used for connection of protective earthing, equipotential bonding or communication equipment earthing Earth plates All electrical installations on vessels of non-metal hull construction shall incorporate an earth plate that complies with the following: a) The earth plate shall be i) manufactured from copper or other material of equivalent mechanical and electrical properties; and ii) securely attached with non-corrodible fastenings to the hull of the vessel. b) The earth plate shall be positioned so that it is immersed at all times during operation of the vessel. c) The earth plate shall have an area of at least 0.25 m2, and shall be at least 3.2 mm thick. d) Connections to the earth plate shall comply with Clause If more than one earth plate is used, all earth plates shall be equipotentially bonded (see Clause ). The same earth plate may be used for protective earthing, functional earthing of communications equipment, and lightning protection. Main earth (protective earth), functional earthing and lightning down conductors shall be run separately to the earth plate(s) and connected by separate electrodes to the earth plate(s). April 2011 Page 15 Edition 2.1
16 Part C Section 5 Subsection 5B Bonding Equipotential bonding shall a) have a resistance to earth of less than 0.5 ohm; and a) in non metallic vessels, be provided between all engine bedplates, generator frames, metallic elements of the fuel system, fixed metal objects with a surface area in excess of 0.4m 2, and the earth plate. To help dissipate possible static build up and to minimise the effects of electrolytic corrosion it is recommended that metallic fittings, particularly those in contact with the sea, are bonded to the main earth system. NOTE: For electrical bonding requirements relating to preventing static charges on fuel tanks and fuel systems see NSCV Part C Subsection 5A NAVIGATION LIGHTS AND NAVIGATION EQUIPMENT General The provision of navigation lights, navigation equipment and their sources of power shall comply with the provisions of NSCV Part C Section 7 and Clauses to of this Subsection Navigation lights Each light shall be wired by a separate circuit to a a) discrete section of a distribution board; or b) panel dedicated to navigation lights. The use of junction boxes in navigation light circuits shall be limited to those needed to connect the navigation lights to fixed wiring. Navigation light circuits shall not share wiring enclosures or junction boxes with other circuits. Each light shall be i) individually controlled; and ii) protected in each insulated pole by a fuse or a circuit breaker, mounted on the navigation light distribution board or panel Navigation light distribution board The navigation light distribution board or panel shall only be used for supplying power to the navigation lights. The board or panel shall be connected either directly, or through a transformer, to the main switchboard (MSB) and /or the emergency switchboard (ESB). If a separate emergency supply is used then there shall be two separate supplies to the navigation light distribution board or panel, one from the MSB and one from the ESB. Any alternate supply change over (i.e. from the main to the emergency supply), and any change over for alternate navigation lights, shall be operable from the wheel house or the helm position, and shall be easily accessible to the watchkeeper. Edition 2.1 Page 16 April 2011
17 Part C Section 5 Subsection 5B Indicators and alarms If the navigation lights are not visible from the vessel's deck then the lights shall be provided with an automatic indicator to give an audible or visual indication of lamp failure. The indicators shall be in the wheel house or at the helm position and placed to gain the attention of the watchkeeper. If a visual indicator is connected in series with the navigation lamp then a means shall be provided to prevent failure of the navigation lamp in the case of failure of the indicator. If an audible indicator is used, it shall be connected to a separate source of supply, and provision shall be made for testing this supply CABLES AND WIRING SYSTEMS A Wiring systems The following shall apply in addition to the wiring system requirements of AS/NZS a) In machinery spaces and on exposed decks cable fixing (i.e. saddles, clips, clamps, ties and straps) shall be of non corrosive metal. b) Wiring systems and equipment onboard a vessel shall be considered as 'likely to be disturbed'. NOTE: AS/NZS 3000 provides the requirements for wiring systems likely to be disturbed Stranded conductors All conductors in cables, with the exception of mineral-insulated metal sheathed (MIMS) cables, shall be of stranded, annealed copper, constructed in accordance with AS/NZS MIMS cables shall meet the requirements of AS/NZS Connections NOTE: MIMS has limited application in the marine environment due to the risk of vibration and movement. Care should be taken to ensure that MIMS is used appropriately. Cable connections and terminations shall be at fixed, enclosed terminals. All connections and terminations shall be accessible Penetration of bulkhead or deck Where the routing of a cable requires the penetration of solid surfaces such as bulkheads or decks, the cable shall be effectively protected from mechanical damage. Where the penetration is through a watertight or fire rated bulkhead or deck, the watertight and fire rated integrity of the bulkhead or deck shall be maintained. Penetrations of refrigeration bulkheads or decks, or other insulated bulkheads or decks, shall be as close as practicable to perpendicular to the plane of the bulkhead or deck. Cable shall not be laid under thermal or sound insulation. April 2011 Page 17 Edition 2.1
18 Part C Section 5 Subsection 5B Glands and bushes used in bulkhead or deck penetrations shall be corrosion-resistant Duplicate supply Where a duplicate or alternative supply is required (e.g. alternative supplies for the navigation light panel), the two cables shall be routed separately so as to avoid the risk of concurrent damage to both cables LIGHTNING PROTECTION Vessels with non metallic hulls and/or non metallic structures shall be provided with lightning protection. The minimum level of protection shall be to the requirements for the protection of boats in AS/NZS 1768 Lightning protection. NOTES: 1. Surge suppression devices should be used for the protection of individual circuits and equipment that may contain sensitive components. 2. Information concerning the safety of personnel in electrical storm conditions should be maintained in the vessel's documentation and also that information should be made available to personnel by way of safety signage. 3. Maintenance to the lightning protection system may be required, particularly after exposure to lightning UNACCEPTABLE COMPONENTS MATERIALS AND METHODS The following components, materials and methods are not suited to the marine environment and shall not be used: a) Re-wireable fuses. b) Hull return, except for cathodic protection systems. c) Aluminium conductors ENGINE ROOM AND CARGO SPACE VENTILATION Each engine room and cargo space fan shall be supplied from a separate final sub-circuit. All ventilation systems shall be capable of being stopped from a readily accessible position outside the ventilated space. NOTE: Refer to NSCV Part C Section 4 Fire Safety for requirements regarding remote stops for use in case of fire EQUIPMENT AND ACCESSORIES IN EXPOSED LOCATIONS Electrically operated equipment and accessories with an IP Rating (International Protection Rating: see AS/NZS 60529) suitable for the location shall be used in exposed locations. No accessories shall be installed less than 0.3 m above the deck unless specifically made for the application, for example a foot switch windlass control OVER CURRENT PROTECTION OF ESSENTIAL SERVICES Steering gear circuits shall have short circuit protection only and shall be equipped with overload and trip alarms at each helm position. Edition 2.1 Page 18 April 2011
19 Part C Section 5 Subsection 5B Other circuits deemed essential may have short circuit protection only, if equipped with an overload alarm COMMISSIONING INSPECTION AND TESTING Tests At the conclusion of construction, modification, or repairs the electrical system, equipment or part shall be inspected and tested in accordance with AS/NZS The functioning of each RCD shall be verified. NOTE: Further information on inspection and testing is also available in AS/NZS Commissioning tests shall include, as a minimum, the correct operation (i.e. in accordance with manufacturers specifications and the objectives and requirements of this Subsection) of the following equipment where fitted a) generator operation including: i) engine governors; ii) iii) parallel operation; load sharing; iv) voltage regulator operation by instantaneous loading and unloading of generator; and v) safety devices, such as overspeed trips, reverse power trips, over current trips, load shedding, together with the associated controls and alarms. b) load testing of motors; c) overload alarm circuits of essential service motors; d) main engine safety alarms and trips; e) machinery and equipment that incorporates remote controls, remote stops and limit switches; f) emergency stop circuits; g) vessel's alarm systems; and h) other systems and equipment installed in the vessel Test results All test results shall be recorded and the test results shall remain with the vessel's documentation. Test results should be dated, accurate, legible and retained for the life of the vessel DESIGN PARAMETERS Unless otherwise specified, electrical equipment shall be designed for an ambient temperature of at least 45ºC. April 2011 Page 19 Edition 2.1
20 Part C Section 5 Subsection 5B CHAPTER 3 EXTRA-LOW VOLTAGE SYSTEMS AND BATTERIES 3.1 SCOPE This Chapter sets out the requirements for electrical equipment and electrical installations for extra-low voltage systems. 3.2 APPLICATION NOTE: Extra-low voltage includes voltages up to 50 V a.c and 120 V d.c This Chapter applies to those parts of a vessel's electricity supply that do not exceed 50 V a.c and 120 V d.c. REQUIRED OUTCOMES NOTE: Requirements for the separation of ELV and LV electrical installations in vessels that have both are covered in AS/NZS REQUIRED OUTCOMES The required outcomes given in Clauses 2.2 to 2.9 of Chapter 2 shall apply to this Chapter. DEEMED-TO-SATISFY SOLUTIONS 3.4 COMPLIANCE For the purpose of this National Standard an extra-low voltage electrical installation shall be deemed to have satisfied the required outcomes in Clause 3.3 if it complies with Clauses 3.5 to 3.9 of this Chapter and the relevant Clauses of AS/NZS PROVISIONS OF AS/NZS 3000 NOT TO APPLY The following provisions of AS/NZS 3000 shall not apply: a) The provision that states 'Protection against direct contact is not necessary for voltages of 25 V a.c. or 60 V d.c., or below, in dry indoor conditions'. It is deemed that dry indoor conditions do not occur in the marine environment. NOTE: This provision is in the NOTE to Clause (ii) in the 2000 edition of AS/NZS b) The provision that refers to 'electrical equipment used in dry locations'. It is deemed that dry locations do not occur in the marine environment. NOTE: This provision is in Clause (b) in the 2000 edition of AS/NZS c) The provisions for ELV that allow switches to 'operate in one less conductor than the number of conductors in the circuit'. NOTES: Edition 2.1 Page 20 April 2011
21 Part C Section 5 Subsection 5B 1. These provisions are in Clauses (b) and (b) in the 2000 edition of AS/NZS As a result of Clause 3.5 c), in isolated systems switches and circuit protection are required to interrupt all active conductors (See Clause 3.7). 3.6 ENGINE STARTING CABLES Engine starting cables shall a) be protected from mechanical damage; b) have their terminals protected from mechanical damage and from contact with conductive materials; c) be as short in length as is compatible with the stowage arrangements of the starter motor batteries; d) either be routed to avoid the possibility of coming into contact with petroleum products or be enclosed or sheathed with a material resistant to the effects of petroleum products; e) be of adequate size for the expected cranking current and to minimise voltage drop; f) be connected directly to the starter via the starting relay contacts; and g) be suitably sealed at terminals in such a manner as to reduce corrosion. NOTE: Starter motor manufacturers specifications should be used for cable size. The starting motor relay shall be mounted either directly on the starter or adjacent to it. 3.7 SWITCHES AND CIRCUIT PROTECTION In isolated systems, switches and circuit protection shall interrupt all active conductors i.e. double pole switches are to be used. 3.8 BATTERIES AND BATTERY INSTALLATIONS General Batteries and their installations shall comply with this Subsection and the relevant requirements of Part C Subsection 5A, Part C Section 4, and Part C Subsection 7B of the NSCV. NOTES: 1. Part C Subsection 5A (Machinery) specifies requirements for the capacity of batteries used for starting main engines (number of starts) and for alternative starting arrangements. 2. Part C Section 4: Fire Safety specifies requirements for the capacity of batteries used in fire-detection and fire-suppression systems. 3. Part C Subsection 7B (Communication Equipment) specifies requirements for batteries used in radios. 4. In addition to the battery provisions of AS/NZS 3000, guidance on batteries can be found in AS 2676 and AS These standards cover batteries with voltages in excess of 24 V. However, the guidance offered is sound for battery installations under 24 V. April 2011 Page 21 Edition 2.1
22 Part C Section 5 Subsection 5B 5. Where specific parts of the NSCV are referenced but have not yet been published, refer to Part B Clause 1.5. Clause 3.8, shall not apply to batteries integral to particular equipment when those batteries do not feed into a vessel's distribution system. NOTE: These batteries may include those used in hand held and portable equipment, internal back up batteries for electronic navigation devices, fire detector back up batteries and batteries for stand alone emergency lighting units Isolation of batteries All batteries shall be controlled by an isolation switch operating in all active conductors. Isolation switches shall be located as close as practicable to the battery, and cables between the battery and isolating switch shall be double insulated or installed in a wiring enclosure throughout their entire length. Certain circuits may be required when the main distribution system is isolated (for example, automatic bilge pumps and solar battery charging circuits). These circuits shall be fitted with individual isolation switches and protection devices located as close as practical to the battery Change over and paralleling switch Systems involving multiple battery installations shall be provided with switching to allow the parallelling and/or change over of batteries used for engine starting. Where such arrangements are provided the isolation capability and overcurrent protection for each battery shall be maintained Location and mounting of batteries Location of starting batteries To limit voltage drop in cables, starting batteries should be located as close as practicable to the engines they serve while minimising the risk of hydrogen released by the battery being ignited by a spark from the starter motor Mechanical protection Batteries shall be located and mounted in a) a suitably sized and well secured battery box with fitted lid and adequate ventilation that complies with Clause ; or b) a dedicated battery compartment or room that complies with Clause Battery boxes NOTE: This is to ensure a high level of protection against mechanical damage, exposure to moisture, and the possibility of short circuit caused by accidental contact with loose metal tools and other conductive articles. Battery boxes shall be a) of a chemically resistant material, capable of containing the whole volume of electrolyte; and Edition 2.1 Page 22 April 2011
23 Part C Section 5 Subsection 5B b) mounted and arranged to prevent movement of the battery due to the motion of the vessel Battery compartments In dedicated battery compartments or rooms, batteries shall be mounted in drip trays or containers of a chemically resistant material that are capable of containing the total volume of electrolyte. Mounting arrangements for the containers and the batteries within the containers shall prevent movement of the batteries due to the motion of the vessel Housing of batteries Batteries, or sets of batteries, charged by chargers where the sum of all chargers is greater than 2 kw in total shall be housed in a compartment dedicated to batteries only. Battery compartments shall be well ventilated to the open deck (refer to Clause 3.9). Cable entries to battery compartments shall be gas tight. Lead acid batteries and alkaline batteries shall not be housed in the same compartment or container, or in close vicinity to each other. NOTE: Alkaline electrolytes and acids react violently and noxious fumes may be generated, even in sealed cells. Batteries shall not be housed in accommodation spaces unless they are in a container sealed from the accommodation space and vented to the open deck Switches in battery compartments Switches and other circuit interrupting devices shall not be housed in battery boxes, battery compartments or dedicated battery rooms. These devices shall be mounted as close as practicable, but external to, these housings Battery charging Charging capacity shall be such that fully discharged batteries can be charged to 80 per cent of full charge within 10 hours while maintaining essential services and without exceeding a safe charge rate. To avoid damage to batteries and their charging systems, battery chargers shall incorporate devices for a) regulation of charging current commensurate with the capacity of the battery and/or the manufacturers recommendations; b) protection against overcharge, over voltage and reversal of charging current; c) charge rate indication; and d) circuit isolation and protection. April 2011 Page 23 Edition 2.1
24 Part C Section 5 Subsection 5B Battery charging systems shall incorporate regulators designed to suit the particular power input or inputs used (e.g. LV, engine driven generator, wind generator, solar power) Battery protection Battery terminals shall be protected from mechanical damage and from contact with conductive materials. Batteries supplying essential services, excluding engine starting batteries, shall have short circuit protection as a minimum protection for overcurrent. Engine starting batteries shall have either: a) Short circuit protection; or b) Mechanical protection of the starting cables. For all other battery circuits, short circuit and overload protection shall be provided. Short circuit and overload protection shall comply with the manufacturers specifications. If manufacturer's information on prospective short circuit currents and fault current capacity is not available, for the purposes of providing protective devices the prospective fault current at the terminals shall be considered to be i) for vented cells 20 times the nominal battery capacity at the 3 hour rate; and ii) for sealed cells 35 times the nominal battery capacity at the 3 hour rate. 3.9 VENTILATION OF BATTERIES AND BATTERY COMPARTMENTS General To avoid the potential for an explosion or fire, battery compartments, rooms and boxes shall be well ventilated to free air so that hazardous gases cannot accumulate. NOTE: This clause is based on AS , AS , AS and AS While these standards are for batteries with voltages above 24 V and most marine battery installations are 12 V or 24 V, the general provisions in the standards are applicable Minimum exhaust rate The minimum exhaust ventilation rate required to maintain the concentration of hazardous gases below 2 per cent is calculated by the following formula: where q v n I q v = the minimum exhaust ventilation rate, in litres per second n I = the number of battery cells = the charging current, in amperes Edition 2.1 Page 24 April 2011
25 Part C Section 5 Subsection 5B Natural ventilation For natural ventilation the minimum size of inlet and outlet vents is given by: where A 100 q v A q v = the minimum area of vent, in square centimetres = the minimum exhaust ventilation rate, in litres per second With natural ventilation, an air velocity of at least 0.1 m/s is assumed. NOTE: Based on the provisions of AS 2676 and AS Mechanical ventilation Where mechanical ventilation is used to meet the minimum exhaust rate (q v ) the following shall apply a) exhaust air shall be discharged outside the ship's structure; b) fans shall not be located within a duct (i.e. best mounted at discharge end of duct); c) exhaust ducting shall have a positive gradient over the full length of the duct and shall not connect to other ductwork; d) non sparking material shall be used for fan blade and fan housing; e) controls for the fan shall be external to the compartment being ventilated; and f) air flow shall be monitored and an audio/visual flow alarm fitted. April 2011 Page 25 Edition 2.1
26 Part C Section 5 Subsection 5B CHAPTER 4 LOW VOLTAGE SYSTEMS 4.1 SCOPE This Chapter sets out the requirements for electrical equipment and electrical installations specific to low voltage electrical systems. 4.2 APPLICATION NOTE: Low voltage exceeds 50 V a.c. and 120 V d.c but is less than 1000 V a.c. and 1500 V d.c. This Chapter applies to vessels having an electricity supply that exceeds 50 V a.c. and 120 V d.c but is less than 1000 V a.c. and 1500 V d.c. NOTE: REQUIRED OUTCOMES 1. Vessels with an LV system may also have an ELV supply. 2. AS/NZS 3000 contains provisions regarding the segregation of circuits of different voltage. 4.3 REQUIRED OUTCOMES The required outcomes given in Clauses 2.2 to 2.9 of Chapter 2 apply to this Chapter. DEEMED-TO-SATISFY SOLUTIONS 4.4 COMPLIANCE For the purpose of this National Standard a low voltage electrical system shall be deemed-to-satisfy the required outcomes in Clause 4.3 if it complies with Clauses 4.5 to 4.9 of this Chapter and the relevant Clauses of AS/NZS 3000 relating to low voltage installations. 4.5 MULTIPLE EARTHED NEUTRAL (MEN) SYSTEM Where the vessel uses a MEN system the vessel's MEN link shall be made at each generator. NOTE: This avoids nuisance tripping of shore side RCDs. The vessel's MEN point is switched out of the circuit by the shore supply change over switch. 4.6 RESIDUAL CURRENT DEVICES State and Territory Workplace Health and Safety legislation may have specific requirements for RCDs beyond the requirements of AS/NZS Designers, builders and surveyors are advised to check with their local authorities. 4.7 SHORE SUPPLY General Where electricity is to be supplied to a vessel from a shore supply the shipboard shore power facility shall include: Edition 2.1 Page 26 April 2011
27 Part C Section 5 Subsection 5B a) A circuit breaker operating in all live conductors of the supply, including neutral, fitted adjacent to the shore supply inlet on the vessel. b) A test device, connected on the supply side of the vessel's shore supply circuit breaker to check, and visually indicate, the polarity of the shore supply in relation to the vessel's system c) An interlocking circuit to ensure the shore power can not be connected unless the polarity is correct or a polarity reversal arrangement incorporating interlocking circuitry is installed. d) In three phase supplies: i) a means of checking the phase sequence in relation to the vessel's system; and ii) appropriate switchgear to facilitate the reversal of phase sequence. The polarity of plugs, socket outlets and couplers used for a vessel's shore power supply equipment shall be in accordance with AS/NZS 3112 and AS/NZS 3123 Note Where necessary, repairs may be required to correct the polarity of the shore supply connection. State or Territory electrical safety regulations may require that low voltage work be carried out by licensed electricians. Fixed wiring shall be used between the shore connection circuit breaker and the change over switch. At the main switchboard or adjacent to the changeover switch, there shall be a means of indicating for each phase when the shore supply is energised Shore supply cable The vessel's shore supply connecting cable shall a) be a heavy duty flexible cord or flexible cable; b) have a minimum current capacity of 15 A; c) comply with AS/NZS 3191; AS/NZS and/or AS/NZS as applicable; d) be arranged to allow for the movement of the vessel at the berth without imposing tension on the cable or connections, or exposing the cable to mechanical stress or damage; and e) have a length that will ensure the voltage drop for the vessel's electrical installation is kept within the requirements of AS/NZS 3000 relating to voltage drop; i.e. the voltage drop at any point of the electrical installation shall not exceed 5 per cent of the nominal voltage Changeover switch The changeover switch or device for the vessel supply/shore supply shall operate simultaneously in all live conductors and neutral. Except where the change over switch is direct acting (i.e. a mechanical switch), the control April 2011 Page 27 Edition 2.1
28 Part C Section 5 Subsection 5B Earth Notices circuit of any change over arrangement shall include, in addition to any mechanical interlocks, electrical interlocks on contactors, circuit breakers or other switching devices. Earth continuity between the vessel's earth and the shore earth shall be maintained through the appropriate pin in a plug/socket shore power connection or by a dedicated earth terminal in a shore supply connection that uses terminals. A notice containing the following information shall be provided at the shore connection facility on the vessel: a) Supply voltage. b) Frequency of the vessel's a.c. system. c) The procedure for carrying out the connection Supply inlet plug A means to prevent stress on terminal connections or the accidental removal of the supply inlet plug shall be provided on the shore connection facility on the vessel. NOTE: Suitable arrangements include, but are not limited to, the screw cap of plug/socket units, or a lanyard between the cable and a stout attachment on the vessel to relieve stress on the 0.5 to 1.0 m of cable closest to the shore connection Arrangement of shore connection Guidance regarding possible configurations for the vessel's shore connection may be found in AS/NZS GENERATORS CONTROL AND INSTRUMENTATION Control Overcurrent Overload and short circuit protection for each generator shall be provided by a circuit breaker. The generator manufacturer's specifications should be adhered to for circuit breaker ratings and time delay settings. If the manufacturer's specifications are unavailable, for the purpose of providing overload and short circuit protection the following settings shall apply: a) 110 per cent of rated output current 15 min b) up to 150 per cent of rated output current 2 min c) 150 per cent or greater of rated output current instantaneous Consideration should be given to providing an alarm warning for overloads of less than 110 per cent of rated output current. Edition 2.1 Page 28 April 2011
29 Part C Section 5 Subsection 5B Load shedding Where essential and non essential services are separated, consideration should be given to the provision of load shedding of non-essential services when one or more generators become overloaded Instruments General Instruments shall be provided that indicate the operational conditions of voltage, frequency and load and any variation from the limits of safe operation of the vessel's electrical system Minimum requirements A1 Each generator shall have as a minimum a) a voltmeter; b) for systems using an isolated earth, a means of detecting earth leakage; c) either an ammeter in each phase, or an ammeter with a selection switch to enable the current in each phase to be measured; d) for a.c. generators, a frequency meter located on the supply side of the main switch or main circuit breaker; and e) for generators above 50 kw, a wattmeter Generators operated in parallel For generators operated in parallel, in addition to the instruments specified under Clause each generator shall have: a) A wattmeter. b) Reverse power protection, operating with time delay and in the range 2 per cent to 15 per cent of rated power. A 50 per cent fall of applied voltage shall not render the reverse power protection inoperative. To facilitate the parallelling operation, the following instrumentation shall be the minimum provided: i) Two voltmeters. ii) iii) Two frequency meters. A synchroscope, synchronising lamps, or an equivalent arrangement. One voltmeter and one frequency meter shall be connected to the busbars, the other voltmeter and frequency meter may be either those dedicated to each generator or shall be switched to enable the voltage and frequency of any generator to be measured. April 2011 Page 29 Edition 2.1
30 Part C Section 5 Subsection 5B Range of instruments Voltmeters Ammeters The upper limit of the range of a voltmeter shall be 120 ± 5 per cent of the nominal voltage of the circuit in which it is installed. The nominal voltage of the circuit shall be clearly indicated on the voltmeter. The upper limit of the range of an ammeter shall be 130 ± 5 per cent of the rated full load current of the circuit in which it is installed. Rated full load current shall be clearly indicated on the ammeter Wattmeters Wattmeters used on generators that may be operated in parallel shall be capable of indicating 15 per cent reverse power. 4.9 INVERTERS General Where applicable, inverters used on board vessels shall comply with AS/NZS Part Inverters with outputs isolated from other electrical systems Inverters supplying individual or multiple outlets isolated from other supply systems shall comply with the provisions of AS/NZS 3000 relating to protection by electrical separation, including the provisions applying to protective earthing. Circuit protection for inverter output shall be double pole. Switching at outlets shall be double pole Inverters used to supply the vessel s power system Inverters used to supply a vessel s LV system shall comply with the requirements for generators (Clause 4.8). Inverters shall have the capability to monitor, give alarm, and disconnect when out of specification values of voltage, frequency and current are detected. Disconnection shall occur in all live conductors, including the neutral. There shall be enough output capacity to operate the required systems. Supply to the vessel s distribution system shall be controlled by an appropriate interlocking changeover switch, or equivalent device, operating in all live conductors including neutral. NOTE: Inverters with variable output or unusual arrangements of metering and controls should meet safety and operational needs. Power and supply management systems are now in use and the technology in this field is advancing rapidly. Without restricting the progress of this technology, the basic tenets of electrical safety must be addressed before any other installation design elements are considered. Edition 2.1 Page 30 April 2011
31 Part C Section 5 Subsection 5B CHAPTER 5 EMERGENCY ELECTRICAL INSTALLATIONS 5.1 SCOPE This Chapter specifies the requirements for the equipment and installation of a vessel's emergency electrical system. 5.2 OBJECTIVE The objective of this Chapter is to provide vessel designers and builders with specifications for the design and installation of emergency electrical systems to ensure a source of power is available in the event of failure of the main electrical system. 5.3 APPLICATION This Chapter applies to all vessels subject to this subsection of the NSCV. REQUIRED OUTCOMES 5.4 GENERAL The required outcomes given in Clauses 2.2 to 2.9 of Chapter 2 apply to this Chapter. 5.5 FUNCTION OF ESSENTIAL SERVICES TO BE MAINTAINED The electrical system must be designed and installed so that, in the event of a failure in the main electrical system, power can be supplied and maintained to all services essential for safety. 5.6 PERIOD OF OPERATION Essential services must be maintained during emergency situations for a period sufficient for the emergency to be overcome or for evacuation of the vessel to be completed. 5.7 EMERGENCY LIGHTING In the event of a failure in the main electrical system, sufficient emergency lighting must be provided to facilitate the initiation, undertaking and completion of appropriate emergency responses. DEEMED-TO-SATISFY SOLUTIONS 5.8 COMPLIANCE For the purpose of this National Standard, an emergency electrical installation shall be deemed-to-satisfy the required outcomes in Clauses 5.4 to 5.7 if it complies with a) Clauses 5.9 to 5.14 of this Chapter; b) the requirements of Chapters 2, 3 and 4 of this Subsection; and c) the relevant clauses of AS/NZS April 2011 Page 31 Edition 2.1
32 Part C Section 5 Subsection 5B 5.9 GENERAL Design and location An emergency source of electrical power shall be self-contained. Unless otherwise provided for in Clause , the emergency source of electrical power, including any fuel required to supply that source, shall comply with the following: a) It shall not be located forward of the collision bulkhead. b) It shall be located above the weathertight deck, or where there is no weathertight deck then above the water line, and shall be accessible from the open deck. c) It shall be located so that a fire or other unplanned occurrence in the propulsion machinery space will not interfere with the supply or distribution of emergency power outside that space. d) The space in which it is located shall be i) protected from exposure to moisture; and ii) Operation provided with ventilation sufficient to enable the emergency power source to operate at full power. The emergency generator and its engine, and any emergency battery, shall be capable of operating at full power when the vessel is a) upright; b) rolling up to an angle of 22.5 either way and simultaneously pitching 10 by bow or stern; or c) in any combination of angles within those limits Duplication of main source of electrical power Where a vessel is designed with two, non-contiguous machinery spaces having separate electrical installations with separate distribution systems, each installation may be considered as the emergency source of electrical power for the other POWER SOURCE Type of power source Battery An emergency source of electrical power shall be: a) a battery complying with Clause ; or b) a generator driven by a diesel engine complying with Clause The emergency battery shall be capable of carrying the total emergency load in accordance with Table 1. Edition 2.1 Page 32 April 2011
33 Part C Section 5 Subsection 5B Where a vessel in Category 1 or 2 (Vessel use) has an emergency source of power from a battery only, the emergency lighting system shall automatically come into operation upon failure of the main electrical supply. The emergency source of electrical power for Category A and B (Operational area) vessels shall not be the normal starting batteries. Category C, D and E (Operational area) vessels may use the normal starting batteries provided those batteries are located in accordance with Clause NOTES: Diesel engines General Fuel 1. Part B, Table 2 and 3 describes vessel use and operational area categories. 2. Chapter 3 of this Subsection of the NSCV specifies requirements for the installation and ventilation of batteries and battery compartments. Where a generator driven by a diesel engine provides the emergency source of power, the engine shall be capable of being easily started in its cold condition at a temperature of 0 C. Fuel for an emergency generator engine shall have a flashpoint of not less than 60 C Starting arrangements Where an engine is not designed to be started manually, the following requirements apply: a) The starting equipment shall be capable of providing 3 consecutive starts. NOTE: Starting methods can be electrical from batteries, compressed air, hydraulic, or other forms of stored energy. b) A second source of energy capable of providing an additional 3 starts within a 30 minute period shall be provided. c) Where compressed air is used as the sole means of starting an engine, a manually started, mechanically driven air compressor shall be provided. d) Where an air receiver for an emergency generator is supplied from the main or auxiliary compressed air system, the air supply line shall be fitted with a non-return valve which shall be located in the emergency generator space. e) Where a hydraulic starter is used it should have both an engine driven and a manual pump for charging the accumulator Location of starting arrangements The starting arrangements specified in Clause shall not be situated in any of the following locations: April 2011 Page 33 Edition 2.1
34 Part C Section 5 Subsection 5B a) Below the bulkhead deck in the case of a Category 1 vessel or below the weathertight deck in the case of a Category 2 vessel. b) Forward of the collision bulkhead. c) In the space containing the main source of electrical power. d) In a space that would be rendered inaccessible or uninhabitable by a fire or other incident in the space containing the main source of electrical power Temporary source of emergency power Unless an emergency generator is designed to start and come on load automatically, all Class 1B vessels and all vessels of 25 m and over in measured length that carry berthed passengers shall be provided with a temporary source of emergency power. This temporary source of emergency power shall consist of a battery of sufficient capacity to a) supply emergency lighting continuously for 30 minutes; b) close electrically-operated watertight doors; and c) operate any electronic alarms and indicators associated with the watertight doors. NOTE: All electrically operated watertight doors need not be closed simultaneously EMERGENCY SWITCHBOARD General Location An emergency switchboard may be supplied from the main switchboard in normal operation, and shall be supplied from an emergency supply in situations where the main supply has failed. Unless otherwise provided for in Clauses and , an emergency switchboard forming part of the emergency electrical installation shall be installed adjacent to, or as near as possible to, the emergency source of electrical power Generators driven by diesel engines Batteries Where the emergency source of electrical power is a generator driven by a diesel engine, the emergency switchboard shall be located in the same space as the generator, except where the operation of the emergency switchboard would be impaired by such a location. Where the emergency source of electrical power is a battery, the emergency switchboard shall not be installed in the same space as the battery. Edition 2.1 Page 34 April 2011
35 Part C Section 5 Subsection 5B 5.12 EQUIPMENT REQUIRED TO BE SUPPLIED WITH EMERGENCY POWER The electrically operated equipment required to be supplied with emergency power shall be as follows: a) The following equipment as specified in Part C Section 4: Fire Safety of the NSCV: i) Fire alarms. ii) iii) Emergency fire pumps. Fixed fire-extinguishing systems. iv) Remote stops. v) Communications equipment other than radios (e.g. PA systems). b) Mustering alarm as specified in NSCV Part C Subsection 7A (Safety Equipment). c) Signalling lamp as specified in NSCV Part C Subsection 7B (Communication Equipment). d) Electronic navigational aids, navigation lights and sound signals as specified in NSCV Part C Subsection 7C (Navigation Equipment). e) Watertight doors and their associated indicators and alarms. f) Emergency lighting in accordance with Clause g) Any bilge pump relying on the emergency power source as its alternative power supply (see Part C Subsection 5A: Machinery) CAPACITY OF EMERGENCY POWER SUPPLY The emergency power supply for each Class of vessel shall be capable of operating continuously and simultaneously all equipment required to be supplied with emergency power for the periods specified in Table EMERGENCY LIGHTING For vessels specified in Table 1, emergency lighting shall be situated to illuminate the following: a) Service alleys, accommodation alleyways, stairways, exits and personnel lift cars. b) The machinery spaces and main generating stations, including their control positions. c) Control stations and all machinery control rooms. d) The stowage positions for fire-fighting equipment. e) The steering gear. f) Pumps for fixed fire extinguishing systems, emergency fire pumps and any bilge pump relying on the emergency power source as its alternative power supply. April 2011 Page 35 Edition 2.1
36 Part C Section 5 Subsection 5B g) The starting positions for the motors of the pumps specified in Clause 5.14 f). h) Public spaces, evacuation routes, exits and mustering areas. i) Lifeboat stations on deck. j) Stowage positions of life rafts for which launching devices are not provided. k) Life rafts and their launching devices during mustering and launching. l) The area of water into which life rafts are launched, for the period of time required for launching to be completed. Edition 2.1 Page 36 April 2011
37 Part C Section 5 Subsection 5B Table 1 Capacity of emergency power supply Class of vessel Minimum period for continuous and simultaneous operation of all equipment listed in Clause 5.12 Hours Requirement Class 1A As specified in Marine Orders Part 12 for SOLAS passenger vessels. Class 1B 12 hours As specified in Marine Orders Part 12 for SOLAS passenger vessels. Class 1C 3 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 25 m and over in measured length or 500 GT and over. Signalling lamps need only be supplied with emergency power where such lamps are normally operated from the main electrical power source. Class 1D 3 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 25 m and over in measured length. Class 1E 2 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 25 m and over in measured length. Class 2A Class 2B As specified in Marine Orders Part 12 for SOLAS cargo vessels. 6 hours for vessels that are either 125 m in measured length or 5000 GT. 3 hours for all other vessels. As specified in Marine Orders Part 12 for SOLAS cargo vessels. The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 50 m and over in measured length or 500 GT and over. Signalling lamps need only be supplied with emergency power where such lamps are normally operated from the main electrical power source. Class 2C 3 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 25 m and over in measured length or 500 GT and over. Signalling lamps need only be supplied with emergency power where such lamps are normally operated from the main electrical power source. Class 2D 3 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 25 m and over in measured length or 500 GT and over. Class 2E 2 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 2 5m and over in measured length or 500 GT and over. Continued April 2011 Page 37 Edition 2.1
38 Part C Section 5 Subsection 5B Table 1 cont. Class of vessel Minimum period for continuous and simultaneous operation of all equipment listed in Clause 5.12 Hours Requirement Class 3A As for Class 2A As for Class 2A Class 3B 6 hours for vessels that are either 125 m in measured length or 500 GT. 3 hours for all other vessels. The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 50 m and over in measured length or vessels 500 GT and over. Signalling lamps need only be supplied with emergency power where such lamps are normally operated from the main electrical power source. Class 3C 3 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 500 GT and over. Signalling lamps need only be supplied with emergency power where such lamps are normally operated from the main electrical power source. Class 3D 2 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 500 GT and over. Class 3E 2 hours The requirement for emergency lighting in accordance with Clause 5.14 applies only to vessels 500 GT and over. NOTE: Check with your workplace authority for any additional requirements they may have for emergency lighting. Edition 2.1 Page 38 April 2011
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
HIGH VOLTAGE SHORE CONNECTION
Guide for High Voltage Shore Connection GUIDE FOR HIGH VOLTAGE SHORE CONNECTION NOVEMBER 2011 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 1862 Copyright 2011
12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting
12 SOLAR PHOTOVOLTAIC POWER by John Ware IT IS PLANNED for BS 7671:2008 to include a new Section 712 providing additional requirements for safety applicable to solar photovoltaic (pv) power supply systems.
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE
NZECP 14: 1995 ISSN 0114-0663 COVER PAGE NZECP 14:1995 NEW ZEALAND ELECTRICAL CODE OF PRACTICE FOR CONTROL PROTECTION AND SWITCHBOARDS Issued by the Office of The Chief Electrical Engineer, Energy and
Electrical Practices for Construction Work
1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in
Electrical Shore Connections / Cold Ironing
STANDARD FOR CERTIFICATION No. 2.25 Electrical Shore Connections / Cold Ironing JULY 2014 The electronic pdf version of this document found through http://www.dnv.com is the officially binding version
CLASSIFICATION NOTES
CLASSIFICATION NOTES Type Approval, Installation and Testing of Water Level Detectors on Bulk Carriers and Single Hold Cargo Ships other than Bulk Carriers General Information This edition of the classification
Trade of Electrician. Three-phase Distribution Boards And Socket Circuits
Trade of Electrician Standards Based Apprenticeship Three-phase Distribution Boards And Socket Circuits Phase 2 Module No. 2.3 Unit No. 2.3.2 COURSE NOTES Created by Charlie Walsh - Athlone TC Revision
MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing
MEM10019 Select circuit protection devices by type and rating, fit to switchboards and install earthing Release: 1 MEM10019 Select circuit protection devices by type and rating, fit to switchboards and
Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.
SOLAR ALTERATIONS REQUIREMENTS August 2015 These requirements address typical alterations to solar installations; they cannot address every scenario. In Victoria, an alteration to a solar installation
RCD Inspection Log Book
RCD Inspection Log Book This book is the property of: Commenced: / /. Completed: / /. 2 Clipsal Australia Pty Ltd Clipsal Australia Pty Ltd 3 4 Clipsal Australia Pty Ltd Clipsal Australia Pty Ltd 5 6 Clipsal
INTERNATIONAL STANDARD
IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60
CHECKING AND TESTING ELECTRICAL INSTALLING WORK
CHECKING AND TESTING ELECTRICAL INSTALLING WORK Department of Consumer and Employment Protection Energy Safety Preface It is a requirement of the Electricity (Licensing) Regulations 1991 that all electrical
Australian Transport Council. National Standard for the Administration of Marine Safety SECTION 4 SURVEYS OF VESSELS
Australian Transport Council National Standard for the Administration of Marine Safety SECTION 4 SURVEYS OF VESSELS Edition 1 Draft for comment issued 20 December 2005 Endorsed by the Australian Transport
AS/NZS 3000:2007 Amendment 2
AS/NZS 3000:2007 Amendment 2 Published 14 December 2012 Under Victorian legislation the day a revised standard is published it becomes the requirement. The aim of this document is to highlight the important
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors
ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants Installation instructions Contents Key points of installation Before installation Installation Installation check
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING
HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC
Competency Framework for Marine Engineer Class 6. Competency Framework for Marine Engineer Class 6
Table of Contents (MEC 6)... 1 Function: Operate Vessel Machinery and Systems... 1 Diesel engines.... 1 Operational procedures.... 3 Operate and monitor a vessel s engines and auxiliary equipment.... 4
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
ELECTRICAL PRACTICES FOR CONSTRUCTION WORK
CONTRACTOR S CHECKLIST ELECTRICAL PRACTICES FOR CONSTRUCTION WORK 2007 WorkCover. Watching out for you. New South Wales Government Disclaimer This publication contains information regarding occupational
This Guideline does not address electrical equipment in the following categories:
Policy Hierarchy link Responsible Officer Contact Officer Superseded Documents HS418 Portable Electrical Equipment Inspection, Testing and Tagging Guideline Work Health and Safety Act 2011 Work Health
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE
GUIDE TO THE MAINTENANCE, INSPECTION AND TESTING OF PORTABLE EQUIPMENT (ELECTRICAL APPLIANCES AND TOOLS) IN THE WORKPLACE ET 215:2008 ELECTRO-TECHNICAL COUNCIL OF IRELAND 2008 Page 1 of 6 Published by
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Heading FACT SHEET. Overview. www.safeworkaustralia.gov.au
ELECTRICAL RISKS AT THE WORKPLACE Heading FACT SHEET Overview This fact sheet provides general guidance for persons conducting a business or undertaking (PCBUs) and workers on managing electrical risks
DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
MIOSHA-STD-1313 (10/15) 6 Pages For further information Ph: 517-284-7740 www.michigan.gov/mioshastandards DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE CONSTRUCTION SAFETY STANDARDS
32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw
,1'8675,$/#*(16(7 6HULHV#'9#448 32:(5#5$7,1* 4833#USP283#+] 4;33#USP293#+] 3ULPH 113 kva, 90 kw 124 kva, 99 kw 6WDQGE\ 114 kva, 91 kw 125 kva, 100 kw Generator set consisting of engine and alternator mounted
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.
POWER SUPPLY SYSTEMS AND ELECTRICAL EQUIPMENT FOR DESALINATION PLANTS Y.M. Hamud and A.H. Anwar Abu Dhabi Water and Electricity Authority, Abu Dhabi, UAE Keywords : Electrical System, Network for Desalination,
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST
Name of School: OPTIONAL INFORMATION Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ELECTRICAL - WIRING DESIGN AND PROTECTION SELF INSPECTION CHECKLIST Guidelines: This checklist
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
ST Series POWER SUPPLIES USER INSTRUCTIONS
Introduction These instructions detail the installation and operation requirements for the ST20 & ST35 power supplies. These have been designed for operation in RV s providing a DC power system, with optional
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Trial Exams C. Standards and Regulations. Examination No: GH-08-C- 1 hour and 5 minutes plus 10 minutes reading time
Trial Exams C Standards and Regulations Examination No: GH-08-C- This test is intended to gauge your knowledge of essential information contained within AS/CA S009:2013. To qualify for an allpication to
Manual for Fire Suppression & Methane Detection System
Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327
Australian Standard. Intruder alarm systems. Part 1: Systems installed in client s premises AS 2201.1 1998
AS 2201.1 1998 Australian Standard Intruder alarm systems Part 1: Systems installed in client s premises This Australian Standard was prepared by Committee EL/31, Intruder Alarm Equipment and Installations.
Evaluating Fire- and Heat-Damaged Electrical Equipment
Evaluating Fire- and Heat-Damaged Electrical Equipment www.nema.org 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to heat
What are the basic electrical safety issues and remedies in solar photovoltaic installations?
What are the basic electrical safety issues and remedies in solar photovoltaic installations? Presented by: Behzad Eghtesady City of Los Angeles Department of Building and Safety Topics Covered Photovoltaic
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
BATTERY CHARGER OWNER S MANUAL
SAVE THESE INSTRUCTIONS This manual contains important safety and operating instructions for the automatic battery charger. Do not expose charger to rain or snow. Do not use and an attachment not recommended
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
Top Commercial / Residential Electrical Requirements *
Department of Community Development Building Division 4800 West 92 nd Avenue Westminster, Colorado 80031 For Information call (303) 658-2075 Fax (303) 706-3922 www.westminsterpermits.com Top Commercial
Inverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
Rules for Classification and Construction Ship Technology
I Rules for Classification and Construction Ship Technology 1 Seagoing Ships 19 Guidelines for the Carriage of Refrigerated Containers on Board Ships Edition 2003 The following Guidelines come into force
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
Regulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment
Regulations for the Installation of Electrical Wiring, Electrical Equipment and Air Conditioning Equipment Qatar General Electricity & Water Corporation KAHRAMAA Customer Services Department State of Qatar
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical Equipment 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been exposed to water through flooding, fire
Low Voltage Switchboards The Best Technical Solution for Your Ship
The Best Technical Solution for Your Ship Wärtsilä SAM Electronics Optimal Power Distribution The uninterrupted supply of power to systems and consumers onboard modern ships is an extremly important matter.
Building Services Engineering Technician
Building Services Engineering Technician A competent Building Services Engineering Technician is expected to be able to demonstrate the following skills and competences: Systems design in the building
PART C SECTION 7 SUBSECTION 7B
National Standard for Commercial Vessels PART C DESIGN AND CONSTRUCTION SECTION 7 EQUIPMENT SUBSECTION 7B COMMUNICATIONS EQUIPMENT Part C Section 7 Subsection 7B Communications Equipment National Standard
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
INSTALLATION INSTRUCTIONS: Viewline 52 mm
-5 Safety information The product was developed, manufactured and inspected according to the basic safety requirements of EC Guidelines and state-of-the-art technology. The instrument is designed for use
1 Introduction. 2 Hazards From Electricity
Risk Assessment Application to Electrical Rigs A guide to assist the Competent Named person who will verify the safety of rigs consisting mainly of electrical equipment. 1 Introduction Every employer shall
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM
EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values a) For 33/11 KV Power Transformer 2500 V megger is to be need. b) Power Transformer neutral Earthing is
Regulations relating to maritime electrical installations
Regulations relating to maritime electrical installations Published by: Norwegian Directorate for Civil Protection (DSB) 2012 ISBN: 978-82-7768-306-5 Preface These regulations have been laid down pursuant
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
NATIONAL CERTIFICATE (VOCATIONAL)
NATIONAL CERTIFICATE (VOCATIONAL) SUBJECT GUIDELINES ELECTRICAL PRINCIPLES AND PRACTICE NQF Level 4 September 2007 ELECTRICAL PRINCIPLES AND PRACTICE LEVEL 4 CONTENTS INTRODUCTION 1 DURATION AND TUITION
Evaluating Water-Damaged Electrical Equipment
Evaluating Water-Damaged Electrical www.nema.org Evaluating Water-Damaged Electrical 1 USE OF THIS PUBLICATION This publication provides information on how to evaluate electrical equipment that has been
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
Electrical Grounding. Appendix C
Appendix C Electrical Grounding Low-Voltage Equipment Grounding The most frequently cited Office of Safety and Health Administration (OSHA) electrical violation is improper occupational grounding of equipment
Instructions for Safe Use
Instructions for Safe Use (Certification N:o VTT 08 ATEX 029) Thank you for choosing Slam Trans portable transformer for your job site. Purpose of this manual is to provide you all the necessary safety
Oil and Coolant Circulating Heating System. Model - OCSM
Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine
St Peter s College ELECTRICAL SAFETY. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
St Peter s College ELECTRICAL SAFETY References: A. Peninsula Business Services Guidance Note 4-1, Electrical Safety. B. University Safety Office Policy Statement S4/10, Working safely with Electricity.
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
Electrical Equipment in Hazardous Areas: Field Inspections
Electrical Equipment in Hazardous Areas: Field Inspections Bill Rankin Electrical Engineer / Senior Electrical Inspector Abstract Electrical equipment and installations that fall within explosive gas atmospheres
MANAGING ELECTRICAL RISKS IN THE WORKPLACE
MANAGING ELECTRICAL RISKS IN THE WORKPLACE Code of Practice MARCH 2015 Safe Work Australia is an Australian Government statutory agency established in 2009. Safe Work Australia consists of representatives
Guide to the Safety, Health and Welfare at Work (General Application) Regulations 2007. Part 3: Electricity
Guide to the Safety, Health and Welfare at Work (General Application) Regulations 2007 Part 3: Electricity 9 Guide to the Safety, Health and Welfare at Work (General Application) Regulations 2007 Part
Installation Instructions for Alarm Module Kit A043F059
Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line
Installation and safety instructions for AC/DC built-in devices
The device type and date of manufacture (week/year) can be found on the device rating plate. In the event of any queries about the device, please quote all the details given on the rating plate. For further
Part 0 - Classification and Surveys Classification and Surveys I-0 2016-01
Code Edition I - Ship Technology Part 0 - Classification and Surveys Classification and Surveys I-0 2016-01 Part 1 - Seagoing Ships Chapter 1 - Hull Structures I-1-1 2016-01 Chapter 1 - Hull Structures
Battery Power Inverters
Battery Power Inverters Renogy 500W 1000W 2000W Pure Sine Wave Inverter Manual 2775 E. Philadelphia St., Ontario, CA 91761 1-800-330-8678 1 Version 1.1 Important Safety Instructions Please save these instructions.
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems
Recommended Practice for Installation of Transit Vehicle Fire Protection Systems Approved October 25, 2007 APTA Fire Safety Working Group Approved May 3, 2008 APTA Bus Safety Committee Approved October
Electrical safety code of practice 2013. Managing electrical risks in the workplace
Electrical safety code of practice 2013 Managing electrical risks in the workplace This Queensland code of practice has been approved by the Attorney-General and Minister for Justice and commences on 1
USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920
USER MANUAL Stand Alone Power Supply PSQ 2909 / PSQ 3909 / PSQ 4909 PSQ 2920 / PSQ 3920 / PSQ 4920 [This page intentionally left blank] Warning for Your Protection 1. Read these instructions. 2. Keep these
USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018
USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and
Conventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:
ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS: Chapter 12 of the Burlington Code of ordinances allows owner occupants of single family homes to do their own wiring if they choose. If you choose to
Circuit Electrical Testing
Safe Isolation Procedure Circuit Electrical Testing Site Safety Management It is essential from the outset that effective management and control of the system, apparatus and equipment used on site is achieved
OVERSEAS MARINE CERTIFICATION SERVICES (OMCS)
SURVEYOR S MANUAL - STATUTORY TD-SP-DGC Page. 1 de 8 CARRIAGE OF DANGEROUS GOODS SECTION 1 General 1.1 Surveyors carrying out surveys for the carriage of dangerous goods should be familiar with the applicable
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
Portable Air Conditioner
Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE
Batteries and inverters
Batteries and other energy storage devices store energy so that it can be used when needed. In a stand-alone power system, the energy stored in batteries can be used when energy demand exceeds the output
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical
Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical Victor Lee Commercial Marketing Manager SEA Eaton Oil & Gas Solution Tech Day 2013 Eaton. All Rights Reserved. Eaton is a leading
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 June 2016
RMM 306 Lockout/Tagout (LOTO) Program for the Control of Hazardous Energy Page 2 3 Related Documents 3.1 Occupational Health and Safety Act, R.S.O. 1990 3.2 Regulations for Industrial Establishments, R.R.O.
LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells
Engineering Production Sales LEAD CRYSTAL Valve-regulated lead-crystal batteries Energy storage Cells User Manual www.axcom-battery-technology.de [email protected] Chapter 1: 1. Introduction
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings
*** Provide this document to the inspector along with ALL system installation instructions *** Project Address: Scope: Standard plan for the installation of grounded microinverter solar PV systems, not
PRECAUTIONS ON TANKER AND TERMINAL DURING CARGO HANDLING
Chapter 24 PRECAUTIONS ON TANKER AND TERMINAL DURING CARGO HANDLING This Chapter provides guidance on precautions to be observed by both tanker and shore when cargo handling, ballasting, bunkering, tank
Electrical Safety Tips. Help us keep you safe
Electrical Safety Tips Help us keep you safe To help you stay safe when using electricity, ActewAGL has compiled these electrical safety tips. For natural gas safety tips please see ActewAGL s natural
