1 Slavic Village Building Condition Review Slavic Village Development May 8, 2015

2 Page 1 EXECUTIVE SUMMARY City Architecture was commissioned by Slavic Village Development to review five existing facilities at the intersection of East 55 th Street and Broadway in Cleveland, Ohio to prepare a list of repairs, modifications and provide a proposed development options for the buildings. The buildings consist of the following: 1. Badgley Nichols Building 2. Carnegie Buildings 3. Marshall Building 4. Columbia Building 5. Viola Building For ease of reading this report we have assumed a Report North position. See the Key Plan above. We have listed the comments with the associated photos below the comments. The Viola Building, even though it is one building, was separated into the northern portion and the southern portion and they are very different conditions.

3 Page 2 The Carnegie Buildings are two small one story buildings that are side by side and not currently owned by Slavic Village at this time therefore only a cursory exterior review was performed. The vacant property immediately to the east of the Badgley Nichols Building is currently owned by the City of Cleveland Land Reutilization Program. This property was assumed to be consolidated in the future as part of the potential development property and is utilized as part of the development plans included in the Appendix. The focus of this study is to provide the general condition of the buildings to be reused for new development and to determine what it will take for the shell to be weather tight and safe. The largest issues found are related to water infiltration. There are numerous portions of the roofs that have been leaking for a long period of time causing multiple structural issues within the building. There are many masonry issues with the building but most are due to missing windows, leaking roof and lintels rusting. This water infiltration trapped the moisture inside the wall has rusted the lintels and the freeze thaw issues have pushed the brick out in on the Viola Building. The north façade of the Viola Building will require immediate attention to tie the brick back before it moves further out or completely delaminates from the building. There are no salvageable HVAC units or ductwork for any of the buildings. All of the existing systems that still exist will require replacement for any new construction. All of the buildings have natural gas lines to them but it is recommended to replace all of the lines due to not being used for an extended period of them except for the Columbia Building. There are no sprinkler systems in any of the buildings and no main fire water lines coming into the buildings at this time. The electrical system in the buildings are nonexistent or in poor condition and cannot be reused. Recommendations The East 55 th and Broadway Avenue intersection is one of two intersections in Cleveland where the existing buildings predate World War One. As such, we would strongly recommend the facades and main circulation routes be saved and renovated for the major architecturally significant buildings to maintain the character of the intersection. Badgley Nichols Building It is our opinion this building has architectural significance and should be saved and renovated. The floor plate is large enough to allow flexibility and a creative retrofit. There are structural issues with the building but they are not excessive. Carnegie Buildings These buildings are not currently owned by Slavic Village but there is a potential for ownership in the near future. These two building do not have any architectural significance and they are too small to obtain any true value for a renovation. A new building could be built on this site connecting the adjacent buildings and feeding new infrastructure to them.

4 Page 3 Marshall Building This building does not have significant architectural features on the exterior but it does contribute to the character of the overall East 55 th and Broadway intersection. The concrete structural system is in need of multiple repairs. The first floor has unique decorative plaster above the existing lay-in ceiling that could be salvaged. Columbia Building This building has extensive architectural significance and contributes greatly to the East 55 th and Broadway intersection. There are some structural problems that could be repaired. We propose to renovate the existing elevator and use this entrance to feed a potential new development to the north. This would allow the elevator costs to be captured in historic tax credits if desired. Viola Building The Viola building was split into two buildings for this report as there are two distinctly different structures. The northern portion of the building is two stories and contributes to the East 55 th and Broadway intersection. This building requires many repairs but is desirable to hold the character of the intersection. The masonry on the north façade must be pinned to the backup system to keep from delaminating and falling off. A new roof or major roof repairs is also needed to limit future water and structural damage. The southern portion does add to the character of the intersection but is only one story and has extensive structural and water damage. The receiving dock area has already partially collapsed. We recommend demolishing this building and constructing a new two story building in its place. We also recommend keeping the building locked and not allowing access until it could be demolished.

5 Page 4 OVERVIEW Badgley Nichols Building The building is predominately two stories with a basement. There is a small third floor. The structure consists of an exterior bearing masonry wall and interior wood and steel framing. Square Footage Basement 4,200 sf First Floor (if it existed) 4,150 sf Second Floor 3,100 sf Third Floor 350 sf Total 11,800 Roof 1. The building received a new low slope built up roof system, gutters and downspouts within the last two years that appears to be functioning properly. However there are multiple wall, door and window water infiltration issues so it is difficult to verify its effectiveness. Exterior Masonry Walls 2. The exterior masonry walls appear to be in sound condition. There are many areas that will require rebuilding of masonry around the windows and openings and there are many areas that require tuck pointing. There is a slight bowing of the wall in the basement. See the following note for further information on this condition.

6 Page 5 Framing/Walls 3. The first floor joists were removed (missing) and building to the east was razed with its basement backfilled to grade close to the original first floor elevation. Therefore, what visually appeared to be a 5 wythe brick basement wall now becomes laterally unsupported at its first floor elevation. We have performed a general calculation to determine if the wall provides enough of its own dead load to resist lateral earth pressures acting on it in a temporary state. We feel this wall must be braced temporarily to prevent potential lateral movement from the earth s surcharge pressure, until permanent floor joist replacement can occur. East Wall Bowing 4. There is currently no access without a ladder from the basement to the second floor. Access to the basement is via a construction stair inside the door to the north of the building on the west side. 2 nd Floor Stair Access 5. There exists a metal deck and steel beam in the basement vault that has deteriorated under the sidewalk. The beam appears to be rusted through and should be replaced or shored temporarily until future repairs occur. The slab/deck areas show signs of rust distress and should be temporarily shored until future replacement.

7 Page 6 6. The second floor has soft spots and structural damage to the floor joist and decking with the worst damage to the floor along the mid-point of the space along the east wall. Care should be taken when walking on the second floor. These areas require barriers surrounding them to prevent foot-traffic access via a 2x4 stud OSHA approved guard rail, used for floor openings during construction. The location of the barrier will require a group effort including Slavic Village, City Architecture, CSCPE and the Contractor to assist in defining the distressed boundaries for rail placement. Damaged Flooring Underside of 2 nd Floor 7. The exterior wall in the same location as this damaged flooring on the second floor as is noted above has extensive damage and will require to be rebuilt due to damaged wood and mold. 8. The interior walls have too much damage to remain. Some of the wood studs are still functional but due to the mold on them it is recommended to be removed in their entirety.

8 Page 7 9. Most of the plaster for the ceiling of the second floor is missing due to water damage before the roof was replaced. 10. There is a small third floor of the building that only has one stairway for egress. The three walls of this space are masonry but the south wall consists of wood framing. A second means of egress is required if this space is to be occupied. Windows 11. Most of the windows throughout the building are either missing or in very poor condition. The building currently has all the window openings covered with plywood. They are not sealed tight and are still allowing water infiltration to occur. This is causing further damage to the masonry and the framing. Mechanical 12. Currently there are no mechanical systems serving the building.

9 Page 8 Plumbing and Fire Protection 13. No domestic water service could be located serving the building. The building does have a utility vault under the sidewalk on the south side that could be used for tapping to the water line for service after the vault is cleaned out and re-supported. 14. There is no sprinkler system in the building nor is there a fire water line serving the building. Electrical 15. There is no electrical service in the building. It is assumed the electrical service was fed to the building from the northern exterior wall.

10 Page 9 Carnegie Buildings The Carnegie Buildings consist of two small single story buildings. It is assumed they have basements as the adjacent buildings all have basements. The structure appears to consist of an exterior bearing masonry and interior wood framing. There is no architectural significance to these buildings. Square Footage Basement 3,000 sf First Floor 3,000 sf Total 6,000 sf Note: These buildings are not currently owned by Slavic Village Development and therefore they were not included in the reviews of the buildings. Roof 1. The low slope built up roof of the building appears to be in poor condition from aerial photographs. Based on the condition of the roof the building is expected to have water damage and mold on the interior of the building. Exterior Masonry Walls 2. The exterior masonry walls appear to be in sound condition. There are many areas that will require tuck pointing. The exterior masonry walls do not have any architectural significance. The north exterior elevation of the building is covered with vines. The vines have worked their way into the mortar joints and causing the accelerated deterioration to the masonry.

11 Page 10 Framing/Walls 3. The interior was not reviewed. Windows 4. There are only a couple of windows on the building entrance on the south elevation. They are in poor condition. The windows on the north elevation have been filled in. Mechanical 5. The mechanical systems were not reviewed. Plumbing and Fire Protection 6. The plumbing and fire protection systems were not reviewed. Electrical 1. Each building has an electrical feed that appears to be in good condition. Newer Electrical Service Newer Electrical Service

12 Page 11 Marshall Building The building is three stories with a basement. The structure consists of exterior stone/masonry and concrete framing. Square Footage Basement 1,430 sf First Floor 1,480 sf Second Floor 1,570 sf Third Floor 1,570 sf Total 6,050 Roof 1. The building has a built up low slope roof system with gutters and downspouts. There are a few areas where the roof is leaking and is causing water damage on the interior. Exterior Masonry Walls 2. The exterior masonry walls appear to be in fair condition. The north wall and upper portion of the east wall are in need of repairs. There are some areas where light if visible through the exterior building wall.

13 Page 12 Framing/Walls 3. The interior framing is a concrete structural system. There are many areas where failures have occurred. Temporary columns and beams are used for support on the second and third floors of the building. There is also an opening punched through a bearing concrete wall with no support. This wall requires temporary support. 4. The first floor concrete framing is generally in good condition. There is a portion of the ceiling along the east wall that has a jack column temporarily supporting the second floor. It is assumed this carries the temporary supports above. Jack Column Support

14 Page The basement has multiple new columns added. Some are temporary and some are permanent concrete or steel columns. They are due to reframing and infill of the first floor. 6. Soft areas of the first floor are currently protected with temporary shoring, however, the wall will need re-waterproofing and parging/patching repairs. 7. Miscellaneous areas in the basement have wood shoring posts deteriorated at their bases. These posts require replacement or repairs to be effective.

15 Page 14 Windows 8. Most of the windows throughout the building are either missing or in poor condition. The windows on the south façade are still in place. The windows on the north façade have all been filled in with plywood. All windows need to be replaced. Mechanical 9. Currently there are no mechanical systems serving the second and third levels of the building. The first floor retail space is served by a split system mechanical unit with the condenser located on the roof and the air handler in the basement on the east wall and the first floor in a closet on the north end of the space. Plumbing and Fire Protection 10. There is domestic water service to the building in the basement on the south side. It appears to be in fair condition but it is recommended to be replaced.

16 Page There is no sprinkler system in the building nor is there a fire water line serving the building. Electrical 12. The existing electric system is in fair condition. The second and third floors do not have any salvageable electrical components. It is recommended to be replaced for the entire building. The incoming electrical is feed from the north elevation.

17 Page 16 Columbia Building The building is three stories with a basement. The structure consists of an exterior bearing masonry wall and wood framing. At one point there was a cupola removed above the south side of the building above the third floor. Square Footage Basement 1,630 sf First Floor 1,430 sf Second Floor 1,550 sf Third Floor 1,550 sf Total 6,160 Roof 1. The building has a built up low slope roof system with gutters and downspouts. There are a few areas where the roof is leaking and is causing water damage on the interior. It is recommended to replace the roof and provide parapet flashing and seal the stone coping. Exterior Masonry Walls 2. The exterior masonry walls appear to be in fair to good condition. There are portions of the masonry that will require repairs. It is recommended to repair and tuck point the masonry to preserve the façade.

18 Page 17 Framing/Walls 3. The interior framing is a wood structural system. There are multiple problems with the framing. It appears that most have already received temporary repairs in the basement. Temporary columns and beams are used throughout the basement for support of the first floor. 4. The existing steel column bases in the basement are rusting out. No additional temporary action is required at this time due to the redundancy of supports in this area and the non-use of occupants above. The columns will require replacement at a future date and can act as temporary shoring at this time.

19 Page Existing metal deck and concrete sidewalk distressed on rusted deck and beams. This space is currently temporarily shored accordingly. No additional temporary action is required at this time. 6. There are multiple soft spots in the floor on the first, second and third floors. The finished flooring is damaged and requires replacement. Various joists require repairs or replacement. Windows 7. Most of the windows throughout the building are in place and in poor to fair condition. These will need to be replaced with thermopane windows that match the character and style of the existing windows for the building to be eligible for historic tax credits.

20 Page 19 Stair 8. There is only one stair for the building on the north end of the building. There was an exterior egress stair but it is rusted, deteriorated and non-functional. A second means of egress will be required to occupy the second and third floors of the building. Elevator 9. The elevator is currently stationed at the second to third floor and is not functioning. This will need to be safely lowered to the basement so it does not free-fall from rusted or corroded parts. It is recommended to retrofit this elevator in the historic building to service any new building to the north to allow the costs to be included with any future potential historic tax credits. Mechanical 10. Currently there are no mechanical systems serving the second and third levels of the building. The first floor retail space is served by a split system mechanical unit with the condenser located on the roof and the air handler in a closet on the west elevation. There is an old boiler in the basement that will require removal. The incoming natural gas service on the west wall in the basement appears to be in good working condition.

21 Page 20 Plumbing and Fire Protection 11. There is domestic water service to the building in the basement on the west side. It appears to be in fair condition. 12. There is no sprinkler system in the building nor is there a fire water line serving the building. Electrical 13. The existing electric system is in fair condition. The second and third floors do not have any salvageable electrical components. It is recommended to be replaced for the entire building. The incoming electrical is feed from the north elevation.

22 Page 21 Viola Building North The building is two stories with a basement. The structure consists of an exterior bearing masonry wall and interior wood and steel framing. Square Footage Basement 2,150 sf First Floor 2,350 sf Second Floor 2,350 sf Total 6,850 Roof 1. The building has a built up low slope roof system with gutters and downspouts. There are a many areas where the roof is leaking and is causing water damage on the interior. It is recommended to replace the roof and provide parapet flashing and seal the stone coping as soon as possible to prevent further damage. Exterior Masonry Walls 2. The exterior masonry walls appear to be in fair condition. There are portions of the masonry that will require repairs. It is recommended to repair and tuck point the masonry to preserve the façade. The brick on the façade of the building facing Broadway Avenue has begun to pull away from the structure and requires some pinning or removal at this time. We recommend pinning the stone and brick to the substrate backup, and/or remove loose portions and protect against the weathering elements. The stone above the windows was already removed to prevent falling. Delaminating brick Stone that was removed

23 Page 22 Framing/Walls 3. There are multiple distressed and broken floor joists and fire damage on the northern end of the building. It appears to be secure from its own weight, but the area should remain vacant due to multiple failures that can occur under foot-traffic loading conditions. The doors to the space should remain locked and only authorized personnel understanding and equipped for the potential safety risks shall be allowed to enter. It is recommended to remove all of the interior walls and gypsum board with any renovation. 4. There are multiple soft spots and holes in the second floor. The finished floor is damaged and requires replacement. Various joists require repairs or replacement. Conditions are changing daily due to the consistent water infiltration. 5. There are multiple leaks in the roof that are causing moisture and structural damage to the roof joists, ceiling and throughout the building.

24 Page 23 Windows 6. Most of the windows throughout the building are in place and in fair condition. These will need to be replaced with thermopane windows that match the character and style of the existing windows for the building to be eligible for historic tax credits. 7. The storefront windows are in fair condition. It is recommended to replace these as they are not energy efficient and have multiple thermal breaks. Stair 8. There is only one stair for the building on the north end of the building. There was an exterior egress stair but it rusted, deteriorated and we could not confirm the exit of the discharge. A second means of egress will be required to occupy the second floor of the building. Portion of egress stair Mechanical 9. Currently there are no mechanical systems serving the building. The incoming natural gas service on the north wall in the basement. Plumbing and Fire Protection 10. There is domestic water service to the building in the basement on the north side. It appears to be in poor condition.

25 Page There is no sprinkler system in the building nor is there a fire water line serving the building. Electrical 12. The existing incoming electric system is in poor condition. The second floor does not have any salvageable electrical components. It is recommended to be replaced for the entire building. The incoming electrical is feed from the south elevation. Incoming electrical service

26 Page 25 Viola Building South The building is one story building with a basement. The structure consists of an exterior bearing masonry wall and interior wood and steel framing. Square Footage Basement 4,330 sf First Floor 4,330 sf Total 6,850 Roof 1. The building has a built up low slope roof system with gutters and downspouts to the west. There are a many areas where the roof is leaking and is causing water damage on the interior. It is recommended to replace the roof, portions of the roof framing and provide parapet flashing and seal the stone coping. Exterior Masonry Walls 2. The exterior masonry walls appear to be in fair condition. There are a few locations where the masonry will require repairs. If the building is to remain, it is recommended to repair and tuck point the masonry to preserve the façade.

27 Page 26 Framing/Walls 3. There are multiple distressed and broken floor joists throughout building. The flooring in the receiving area has partially collapsed. It appears to be secure from its own weight, but the building should remain vacant due to multiple failures that can occur under foot-traffic loading conditions. The doors to the space should remain locked and only authorized personnel understanding and equipped for the potential safety risks shall be allowed to enter. It is recommended to remove all of the interior walls and gypsum board with any renovation. Collapsed joists 4. There are multiple soft spots and holes in the second floor. The floor has extensive damage and needs to be repaired. Many of the floor joist and most of the flooring will require replacement.

28 Page There are multiple leaks in the roof that are causing moisture and structural damage to the roof joists, ceiling and throughout the building. Windows 6. Most of the windows throughout the building are in place and in fair condition. These will need to be replaced with thermopane windows that match the character and style of the existing windows for the building to be eligible for historic tax credits. Stair 7. There are two stairs to the basement. Both of which are in poor condition and will require replacement. Basement 8. The concrete floor slab in the basement is heaving in multiple areas and will require being removed in its entirety and replaced.

29 Page 28 Mechanical 9. Currently there are no mechanical systems serving the building. Plumbing and Fire Protection 10. There is domestic water service to the building in the basement on the north side. It appears to be in fair condition. 11. There is no sprinkler system in the building nor is there a fire water line serving the building. Electrical 12. The existing incoming electric system is in poor condition. The second and third floors do not have any salvageable electrical components. It is recommended to be replaced for the entire building. The incoming electrical is feed from the west elevation. The electrical meters have all been removed. Multiple incoming electrical services

30 Page 29 APPENDIX Graphic Information System Site Plan with Property Lines North Broadway Proposed Building Layouts South Broadway Proposed Building Layouts Existing Building Plans

31

32

33

34

35

36

37 EXISTING BUILDING PLANS 1. Badgley Nichols Building 2. Marshall Building 3. Columbia Building 4. Viola Building

38 50'-2" 91'-2" NORTH BADGELY NICHOLS BASEMENT PLAN SCALE: 3/32" = 1'-0"

39 50'-2" 91'-2" NORTH FIRST FLOOR PLAN SCALE: 3/32" = 1'-0"

40 50'-2" 74'-6" NORTH SECOND FLOOR PLAN SCALE: 3/32" = 1'-0"

41 26'-5" UP 70'-6" NORTH MARSHALL BUILDING BASEMENT PLAN SCALE: 3/32" = 1'-0"

42 26'-5" HVAC UP 70'-6" DN NORTH FIRST FLOOR PLAN SCALE: 3/32" = 1'-0"

43 26'-5" UP 70'-6" DN NORTH SECOND FLOOR PLAN SCALE: 3/32" = 1'-0"

44 26'-5" 70'-6" DN NORTH THIRD FLOOR PLAN SCALE: 3/32" = 1'-0"

45 25'-1" UP 70'-6" NORTH COLUMBIA BUILDING BASEMENT PLAN SCALE: 3/32" = 1'-0"

46 25'-1" UP DN 70'-6" NORTH FIRST FLOOR PLAN SCALE: 3/32" = 1'-0"

47 25'-1" UP DN 70'-6" NORTH SECOND FLOOR PLAN SCALE: 3/32" = 1'-0"

48 25'-1" DN 70'-6" NORTH THIRD FLOOR PLAN SCALE: 3/32" = 1'-0"

49 22'-9" 68'-0" UP NORTH VIOLA BUILDING NORTH BASEMENT PLAN SCALE: 3/32" = 1'-0"

50 22'-9" 67'-3" DN UP DN NORTH FIRST FLOOR PLAN SCALE: 3/32" = 1'-0"

51 22'-9" 67'-3" DN NORTH SECOND FLOOR PLAN SCALE: 3/32" = 1'-0"

52 49'-11" 80'-9" NORTH VIOLA BUILDING SOUTH FIRST FLOOR PLAN SCALE: 3/32" = 1'-0"

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland

Building Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland

Building Condition Assessment: 109-111 North Howard Street Baltimore, Maryland KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,

More information

Facility Assessment for. 11801 East Main Street, Huntley, IL

Facility Assessment for. 11801 East Main Street, Huntley, IL Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested

More information

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA

STRUCTURAL ASSESSMENT. Full Metal Jacket Building 0 Prince Street, Alexandria, VA STRUCTURAL ASSESSMENT FOR Full Metal Jacket Building 0 Prince Street, Prepared by: ALPHA CORPORATION (Alpha) 1850 S. Loudoun Street, Suite 200 Winchester, VA 22601 540-723-0704 September 22, 2010 J. Michael

More information

March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202

March 19, 2014. Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Ms. Jean McDonald CAP Management 910 16th Street, Suite 1010 Denver, Colorado 80202 Re: Prospector s Point Walkway/Façade Repairs Martin/Martin, Inc Project No.: 13.0358.S.02 Ms. McDonald: Per your request

More information

Engineers, Civil Structural Survey

Engineers, Civil Structural Survey Engineers, Civil Structural Survey 317 STREET 0 6 3 6 0 886-1966 886-9165 FAX. September 1 1 Mr. Alan Bergren City Manager City of Norwich Broadway, Floor Norwich, 06360 Re: Limited Structural Condition

More information

Building Foundation and Structure

Building Foundation and Structure Building Foundation and Structure Overview The construction of the Hall of Waters building began in 1936, and was constructed over the original site of the Siloam and Sulpho-Saline Springs. The original

More information

BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208

BROWNSVILLE STRUCTURES STUDY. July 2012. Prepared by. LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 BROWNSVILLE STRUCTURES STUDY July 2012 Prepared by LDA ARCHITECTS 33 Terminal Way, Suite 317 Pittsburgh, Pennsylvania 15219 1208 TABLE OF CONTENTS I. SUMMARY OF BUILDING ANALYSIS.. 1 II. INDIVIDUAL BUILDING

More information

17,280 square feet Overview:

17,280 square feet Overview: CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The

More information

EAST LYME HIGH SCHOOL

EAST LYME HIGH SCHOOL Overview: 1971 N 1966 GYM 1966 CLASSROOM WING 1966 AUD. 1971 GYM 1998 1998 POOL EAST LYME HIGH SCHOOL Original 1966 Building: The original East Lyme High School was constructed in 1966 and was composed

More information

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE

201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE STRUCTURAL INSPECTION REPORT DRAFT 201 WATER STREET FORWARDERS MUSEUM AND VISITORS INFORMATION CENTRE TOWN OF PRESCOTT Date: November 2013 GENIVAR No.: 131-20617-00 2611 Queensview Drive, Suite 300, Ottawa,

More information

Saint Cloud Business Center

Saint Cloud Business Center Saint Cloud Business Center 14 7th Avenue North Saint Cloud, MN 56303 For Sale Located on 7th Avenue in the heart of downtown across from the Court House Square. A large professional reception area with

More information

Structural Assessment Report

Structural Assessment Report Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive

More information

423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT

423 NORTH HOWARD ST. VISUAL STRUCTURAL ASSESSMENT Urgent Needs II City of Baltimore No. 1099 423 NORTH HOWARD ST. 423 North Howard Street (circa 1880) is a multi-story building constructed second in row south of Franklin Street and between the vacant

More information

REQUEST FOR PROPOSALS FOR: THE PURCHASE AND RENOVATION OF ADJOINING PROPERTIES AT 200/240 SOUTH 16 TH STREET ORD, NEBRASKA BY:

REQUEST FOR PROPOSALS FOR: THE PURCHASE AND RENOVATION OF ADJOINING PROPERTIES AT 200/240 SOUTH 16 TH STREET ORD, NEBRASKA BY: REQUEST FOR PROPOSALS FOR: THE PURCHASE AND RENOVATION OF ADJOINING PROPERTIES AT 200/240 SOUTH 16 TH STREET ORD, NEBRASKA BY: THE COMMUNITY DEVELOPMENT AGENCY OF THE CITY OF ORD JULY 2014 A. STATEMENT

More information

Seattle Public Schools Building Excellence IV Projects Under Construction

Seattle Public Schools Building Excellence IV Projects Under Construction Seattle Public Schools Building Excellence IV Projects Under Construction Project Slide Number Arbor Heights Elementary School 2 Cascadia Elementary School & Robert Eagle Staff Middle School 13 Genesee

More information

May 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,

May 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client, PROPERTY INSPECTION PROFESSIONALS May 5, 2010 Client Client Address Re: Inspection Address, Chicago, Illinois Dear Mr. Client, On May 4, 2010, Tomacor completed a property inspection of the above referenced

More information

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES

BUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE

More information

Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components

Facility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development

More information

Page & Turnbull imagining change in historic environments through design, research, and technology

Page & Turnbull imagining change in historic environments through design, research, and technology DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED

More information

October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.

October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr. 117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This

More information

EXISTING MASONRY WALL TO REMAIN (TYP.). EXISTING PARTITION TO REMAIN PROVIDE 3'-3" W. X 8'-0"H. NEW PELLA WINDOWS AS INDICATED ON PLANS. (TYP.

EXISTING MASONRY WALL TO REMAIN (TYP.). EXISTING PARTITION TO REMAIN PROVIDE 3'-3 W. X 8'-0H. NEW PELLA WINDOWS AS INDICATED ON PLANS. (TYP. EXISTING MASONRY WALL TO REMAIN N EXISTING MASONRY WALL TO REMAIN (TYP.). PROVIDE COPPER THROUGH-WALL FLASHING DN EXISTING MASONRY PARTY CHIMNEY AND WALL TO REMAIN (TYP.). EXISTING MASONRY PARTY WALL TO

More information

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102

14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We

More information

Chapter 5. In-depth Building Analyses and Recommendations. Planning Study for Downtown Revitalization City of Martinsville

Chapter 5. In-depth Building Analyses and Recommendations. Planning Study for Downtown Revitalization City of Martinsville 75-77 East Washington Street In-depth Building Analyses and Recommendations Chapter 5 In-depth Building Analysis Overview Four of the nineteen downtown buildings selected for façade assessments and recommendations

More information

SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST

SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS HIGH SCHOOL REPAIRS AND UPGRADES SITE Construction Estimate = $100,000

More information

Chapter 11: Demolition

Chapter 11: Demolition City of Independence Chapter 11: Demolition In this chapter you will find: Demolition Mothballing Treatment Types of Demolition By Neglect and Recommended Corrective Measures DEMOLITION Photograph on cover

More information

STRUCTURAL ASSESSMENT

STRUCTURAL ASSESSMENT STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha

More information

STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA

STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA College of Marin c/o Swinerton Management & Consulting P.O. Box 144003 835 College Avenue, Building MS-3 Kentfield, California

More information

Odd Fellows Hall. 63-65 Warren Avenue, East Providence, RI Historic Structure Assessment. June 2014

Odd Fellows Hall. 63-65 Warren Avenue, East Providence, RI Historic Structure Assessment. June 2014 Odd Fellows Hall 63-65 Warren Avenue, East Providence, RI Historic Structure Assessment June 2014 Ms. Jeanne M. Boyle, Executive Director East Providence Waterfront Commission East Providence City Hall

More information

REQUEST FOR BOARD ACTION HENDERSON COUNTY BOARD OF COMMISSIONERS. ATTACHMENTS: 1. Construction Management Update

REQUEST FOR BOARD ACTION HENDERSON COUNTY BOARD OF COMMISSIONERS. ATTACHMENTS: 1. Construction Management Update REQUEST FOR BOARD ACTION HENDERSON COUNTY BOARD OF COMMISSIONERS MEETING DATE: March 16, 2011 SUBJECT: PRESENTER: ATTACHMENTS: Construction Management Update David Berry Yes 1. Construction Management

More information

PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007

PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007 PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT November 2007 PURPOSE OF INVESTIGATION Determine possible locations of moisture intrusion into and through facade. Determine cause of horizontal and vertical

More information

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona Project Report Structural Investigations Yuma, Arizona Prepared by: 2619 Spruce Street Boulder, CO 80302 303-444-3620 Prepared for: Principle Engineering Group, Inc. 833 East Plaza Circle, Suite 100 Yuma,

More information

Reference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls

Reference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto

More information

Building Condition Assessment Report

Building Condition Assessment Report Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.

More information

www.citiesinspection.com October 5, 2015 Dear Client,

www.citiesinspection.com October 5, 2015 Dear Client, www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.

More information

BUNKER HILL ELEMENTARY SCHOOL

BUNKER HILL ELEMENTARY SCHOOL INITIAL YEAR BUILT 1970 BUILDING AREA 98,200 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 387 WARD 5 PROPOSED PROGRAM CAPACITY 750 Site Plan BUNKER HILL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

Estimated Cost of Repair

Estimated Cost of Repair 1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:

More information

Photos showing the change in condition from 2006 to 2012 are located in Appendix A.

Photos showing the change in condition from 2006 to 2012 are located in Appendix A. January 27, 2012 Ms. Theresa Gallavan Economic Development Director City of Lompoc 100 Civic Center Plaza Lompoc, California 93436 RE: Lompoc Theater Limited Visual Condition Assessment Dear Theresa: Representatives

More information

Basement & Foundation Damage

Basement & Foundation Damage Basement & Foundation Damage Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

Property Condition Assessment

Property Condition Assessment Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar

More information

Rehab Inspection Report Page 1

Rehab Inspection Report Page 1 Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation

More information

Memorandum. July 16, 2008. To: Plan Commission City of Madison

Memorandum. July 16, 2008. To: Plan Commission City of Madison Memorandum July 16, 2008 To: Plan Commission City of Madison From: Marc Schellpfeffer Engberg Anderson Re: Structural/Architectural Assessment of Homes for Proposed Demolition Findorff Yards Office Lofts

More information

48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.

48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No. Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two

More information

School Construction Authority Architecture & Engineering

School Construction Authority Architecture & Engineering SCOPING GUIDELINES 1.0 GENERAL GUIDELINES 2.0 BUILDING ENVELOPE SCOPING GUIDELINES 3.0 CATEGORIES AND COMPONENTS: The Flood Elimination/Below Grade Capital Category may include some or all of the following

More information

MEMORANDUM. General: Foundation:

MEMORANDUM. General: Foundation: MEMORANDUM State of Alaska Department of Transportation and Public Facilities Central Region - Division of Construction and Operations Public Facilities Branch TO: Jennifer Murrel DATE: August 19, 2010

More information

SAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT

SAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT SAMPLE SCHEDULE OF S 1.00 General Conditions 1.01 Project Management 1.02 General Superintendent 1.03 Superintendents 1.04 Safety Engineer 1.05 Scheduling 1.06 Field Engineering 1.07 Bonds 1.08 Trailer

More information

Brookview Community Center Building Assessment July 1, 2014

Brookview Community Center Building Assessment July 1, 2014 Brookview Community Center Building Assessment July 1, 2014 HGA COMMISSION NUMBER2065-004-00 EXECUTIVE SUMMARY Golden Valley hired HGA to study three sites for a potential Community Center. One of the

More information

Historic Preservation Certification Application Part 2 343-345 Main Street West South Haven, Vermont NPS Project No. 12345

Historic Preservation Certification Application Part 2 343-345 Main Street West South Haven, Vermont NPS Project No. 12345 Exterior Features 1 site and drainage 2 foundation 3 wood siding and trim 4 exterior doors 5 windows / storm windows 6 porches front and rear 7 chimneys 8 roofing Interior Features 9 frame 10 basement

More information

Re: Damages to Alaska Building from Legislative Information Office Construction

Re: Damages to Alaska Building from Legislative Information Office Construction 510 L Street Suite 200 Anchorage, AK 99501-1949 (907) 274-22362236 Phone (907) 274-25202520 Fax www.bbfm.com July 22, 2015 Jim Gottstein Alaska Building 406 G Street, Suite 206 Anchorage, AK 99501 Re:

More information

Certification: Building Plans Examiner. Exam ID: B3

Certification: Building Plans Examiner. Exam ID: B3 Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building

More information

RRIO Checklist. Use of checklist: Definitions: Limitations

RRIO Checklist. Use of checklist: Definitions: Limitations CITY OF SEATTLE RENTAL REGISTRATION AND INSPECTION ORDINANCE (RRIO) RRIO Checklist Use of checklist: Property owners will use the RRIO Checklist to confirm that their rental housing properties and units

More information

Doughty Environmental Hygiene Associates

Doughty Environmental Hygiene Associates Top: Photo #1: View of the top of the elevator shaft from the roof. The open ventilation causes condensation to form inside on the sheetrock. It also allows for the access for insects. Note the discoloration

More information

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011

GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com

More information

Vision Home Inspection

Vision Home Inspection Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the

More information

Date: March 7, 2006 Report for [removed]

Date: March 7, 2006 Report for [removed] Date: March 7, 2006 Report for [removed] The Preservation Resource Center Of New Orleans, in conjunction the National Trust for Historic Preservation, has conducted a condition survey of your property.

More information

Structure Survey Findings:

Structure Survey Findings: Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,

More information

Self-Home Inspection Checklist

Self-Home Inspection Checklist To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional

More information

Prestige Home Inspection LLC

Prestige Home Inspection LLC Cover Page Prestige Home Inspection LLC IAC2/ESA - Mold Assessment and Water Damage Report 555 W. Brook ave., Client's town MI, 48059 Inspection prepared for: Client's name Inspection Date: 10/15/2012

More information

Building Condition Assessment Report

Building Condition Assessment Report C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses

More information

Evanston Main Street Station TOD Plan and Study. Appendix A.1: Station Area Existing Conditions

Evanston Main Street Station TOD Plan and Study. Appendix A.1: Station Area Existing Conditions Evanston Main Street Station TOD Plan and Study Appendix A.1: Station Area Existing Conditions EvanstonMainStreetStation TODPlanandStudy A 1 AppendixA.1: ExistingConditions Table of Contents Station Locations

More information

City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage

City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage Property Address: Company Name: Contractor Name: Contractor Address: City: State: Zip: License Number: Phone Number

More information

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training Foundations 65 5 FOUNDATIONS by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. 66 Foundations Foundations 67 FOUNDATIONS Let's assume that the retrofit has been done correctly from the roofline

More information

REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N

REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N

More information

SECTION XI OPINION OF PROBABLE COST

SECTION XI OPINION OF PROBABLE COST SECTION XI OPINION OF PROBABLE COST OPINION OF PROPABLE COSTS HARBOR ISLAND THE PAVILION 1) Provide a sprinkler system for the entire building. 8000 SF X $15/SF $120,000 2) Remove and replace existing

More information

SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM

SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM Shepherd University Board of Governors June 9, 2005 Agenda Item No. 9 SCHEMATIC AND PROJECT BUDGET APPROVAL EAST CAMPUS NURSING EDUCATION AND CLASSROOM In 1994 construction began on the Byrd Science and

More information

How To Repair A House

How To Repair A House Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

GUIDELINES FOR REHABILITATION OF TRADITIONAL COMMERCIAL BUILDINGS DESIGN GUIDELINES

GUIDELINES FOR REHABILITATION OF TRADITIONAL COMMERCIAL BUILDINGS DESIGN GUIDELINES GUIDELINES FOR REHABILITATION OF TRADITIONAL COMMERCIAL BUILDINGS DESIGN GUIDELINES PAGE 13 DESIGN GUIDELINES The following design guidelines have been developed to guide appropriate design in the Downtown

More information

PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com

PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com June 17, 2015 Ms. Kimberley Heaton McCarthy Supervising Planner Building and Safety

More information

Building Control Guidance Note

Building Control Guidance Note Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you

More information

SECTION 3 ONM & J STRUCTURAL ANALYSIS

SECTION 3 ONM & J STRUCTURAL ANALYSIS Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION

More information

OTTAWA CIVIC CENTRE & NORTH SIDE STANDS LANSDOWNE PARK FRANK CLAIR STADIUM STRUCTURAL ADEQUACY REPORT 2007

OTTAWA CIVIC CENTRE & NORTH SIDE STANDS LANSDOWNE PARK FRANK CLAIR STADIUM STRUCTURAL ADEQUACY REPORT 2007 OTTAWA CIVIC CENTRE & NORTH SIDE STANDS at LANSDOWNE PARK FRANK CLAIR STADIUM STRUCTURAL ADEQUACY REPORT 2007 for CITY OF OTTAWA REAL PROPERTY ASSET MANAGEMENT prepared by ADJELEIAN ALLEN RUBELI LIMITED

More information

A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET

A0 SHEET 1 OF 5 400 LOCUST STREET FRANKFORT, KANSAS 66427 FRANKFORT, KANSAS 66427 ROOF REPAIR OF THE 400 LOCUST STREET POYNTZ AVENUE, STE 9 MANHATTAN, KS 0..0..9 FAX WEST th STREET JUNCTION CITY, KS.... FAX 0, Bruce McMillan AIA, Architects, P.A. HERITAGE TRUST FUND GRANT PROJECT NO. 0-0 ROOF REPAIR OF THE 00 LOCUST STREET

More information

Water Damage & Repair

Water Damage & Repair Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below

More information

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing

Foundation Experts, LLC Specializes in Foundation Repair and Waterproofing 1 Most basements show some signs of leaking and cracking. Through the years, problems with water, poor soils, grading, drainage and possible settling affect the integrity of a basement. Being able to recognize

More information

WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204

WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 WEBSTER ELEMENTARY SCHOOL New Rochelle, New York Evaluation of Collapsed Ceiling Room 204 Structural Inspection Report Client: CSArch Architecture Engineering Construction Management 19 Front Street, Newburgh,

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

Excerpts from the Canadian National Building Code (NBC)

Excerpts from the Canadian National Building Code (NBC) Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more

More information

Braselton Bros. Store Redevelopment 5134 HWY 53 BRASELTON, GA 30548 LEVEL 0 - DEMO & NEW PLAN. Room. Room. Room. Room. Room. Room. Room. Room.

Braselton Bros. Store Redevelopment 5134 HWY 53 BRASELTON, GA 30548 LEVEL 0 - DEMO & NEW PLAN. Room. Room. Room. Room. Room. Room. Room. Room. 1.d 2.d 3.d 4.d 1.d 2.d 3.d 4.d REMOVE, REPAIR, & REPLACE EXISTING STOREFRONT SYSTEMS D.1 D.2 REMOVE, REPAIR, & REPLACE EXISTING STOREFRONT SYSTEMS D.1 D.2 REMOVE STAIR & INFILL WALL C.1 REMOVE DOOR &

More information

Basement Moisture Problems

Basement Moisture Problems Foundations Foundation Purpose The purpose of a foundation is to distribute the weight of a structure securely into the ground. Engineering data regarding soil, rock and water conditions are used to design

More information

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.

All substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal. 2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other

More information

Solving Persistent Moisture Problems and Moisture Damage

Solving Persistent Moisture Problems and Moisture Damage B etter buildings Solving Persistent Moisture Problems and Moisture Damage Summary This three-storey, 15-unit, 1,300 square metre (13,993 sq. ft) walk-up was built in 1958. In the 1980s, the building started

More information

BUILDING SAFETY UNIT

BUILDING SAFETY UNIT POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential

More information

The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE

The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE The Lambton County Homeowner's BUILDING PERMIT INFORMATION GUIDE BUILDING SERVICES DEPARTMENT 789 Broadway Street, Box 3000 Wyoming, ON N0N 1T0 Telephone: 519 845-0801 Toll-free: 1-866-324-6912 Fax: 519

More information

Exterior Repair Project. By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek. Building Technology Consultants, PC BTC

Exterior Repair Project. By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek. Building Technology Consultants, PC BTC Exterior Repair Project Glen Ellyn Public Library By: Kami Farahmandpour, PE, RRC, RWC, CCS, CCCA Alex Szatanek Outline 2010 and 2011 Roof Replacement and Facade Repair Project Review Primary Reasons for

More information

MURCH ELEMENTARY SCHOOL

MURCH ELEMENTARY SCHOOL INITIAL YEAR BUILT 1929 BUILDING AREA 47,700 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 491 WARD 3 PROPOSED PROGRAM CAPACITY 500 Site Plan MURCH - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

Bernie Nimer, Dave Seton Mayfair Hotel Development Corporation

Bernie Nimer, Dave Seton Mayfair Hotel Development Corporation SITE INVESTIGATION REPORT NO. S1r1 PROJECT: The Mayfair Hotel PROJECT NO: 140565 ATTN: Bernie Nimer, Dave Seton Mayfair Hotel Development Corporation PREPARED BY: Cory Zurell, PhD, P.Eng. DATE: 13 April

More information

Guernsey s Structural Engineering Experience

Guernsey s Structural Engineering Experience Guernsey s Structural Engineering Experience Foundation Settlement Issues: Trinity Valley Electric Cooperative, Kaufman, TX: Analyzed their headquarters facility for issues with soil movement that was

More information

Roof Inspection. Summary Report

Roof Inspection. Summary Report Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:

More information

Common Problems with Walls

Common Problems with Walls Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly

More information

Disaster Prevention and Protection Checklist

Disaster Prevention and Protection Checklist Preservation Services Leaflet 1438 West Peachtree Street, Suite 200/Atlanta, GA 30309 Phone: 404-892-0943/Fax: 404-892-7879 Website: Disaster Prevention and Protection Checklist The inspection

More information

D Sample Notices to Property Owners, Sample Affidavits, and Other Material

D Sample Notices to Property Owners, Sample Affidavits, and Other Material D Sample Notices to Property Owners, Sample Affidavits, and Other Material These samples are offered to illustrate specific points in the Desk Reference. States and communities should examine them carefully

More information

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas

INSPECTION PROPERTY ADDRESS: Fort Bend County, Texas 5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction

More information

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

PUBLIC MINUTES PROPERTY MAINTENANCE APPEALS BOARD. Wednesday, November 25, 2015, 3:46 p.m. Committee Room B, City Hall

PUBLIC MINUTES PROPERTY MAINTENANCE APPEALS BOARD. Wednesday, November 25, 2015, 3:46 p.m. Committee Room B, City Hall PUBLIC MINUTES PROPERTY MAINTENANCE APPEALS BOARD Wednesday,, 3:46 p.m. Committee Room B, City Hall PRESENT: Mr. Ian Oliver, Chair Mr. Michael Brockbank, Vice-Chair Mr. Roy Fleming, Member Mr. Donald Stiller,

More information

PROFESSIONAL ENGINEERING INSPECTIONS, INC.

PROFESSIONAL ENGINEERING INSPECTIONS, INC. PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest

More information

Estimating Database Checklist

Estimating Database Checklist Estimating Database Checklist If you are creating a new estimating database for projects, the following list offers a thorough listing of Main and Sub Categories. You can also use it as a checklist to

More information

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09

TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It

More information

Pre-Drywall Inspection Report

Pre-Drywall Inspection Report SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion

More information