Property Condition Assessment
|
|
- Bathsheba Blankenship
- 8 years ago
- Views:
Transcription
1 Property Condition Assessment Inspection Address: 15 Beta St, Rome, GA Inspection Date: 12/19/2007 Prepared For: Mr. Bill Jones The ABC Group 51 Alpha St Report Number: 12373C Prepared By: Champia Corp 336 Lamplighter Lane Marietta, GA Fax Inspector: Christopher Howe / Dr. Tore Knos
2 Report Number: 12373C Page 2 of 34 Table of Contents 1.0 SUMMARY INTRODUCTION STRUCTURE ELECTRICAL HEATING AIR CONDITIONING VENTILATION PLUMBING ROOFING INTERIOR EXTERIOR INSULATION CLOSING COMMENTS 24 APPENDIX A: 25 PHOTOGRAPHS 25 APPENDIX B: 34 SUMMARY OF ROOFTOP EQUIPMENT 34
3 Report Number: 12373C Page 3 of Summary This is a reasonably well built building in which maintenance has been somewhat lacking. The priority items should be roof repairs or replacement. No major electrical deficiencies were noted. The heating and air-conditioning systems are good condition. Updating parts of these HVAC systems may be required within the next few years. The plumbing system was generally found to be fair condition. Updating older plumbing fixtures is required. The flat roofing system is poor condition with numerous areas of damage and active leaks. Reroofing will be required. The exterior walls were found to be good. The asphalt paving is fair. Updating sections of the asphalt paving may be required within the next few years. Cosmetic improvements represent an area where a significant amount of work could be performed. While some cosmetic items are addressed in this report, they are not the intended focus. The improvements suggested in this report are not unusual for a building of this age. No outstanding building code or fire code violations are on record with the local authorities. SUMMARY OF REPAIRS 1.1 SUMMARY OF NECESSARY REPAIRS The following table summarizes the recommendations made in this report that are of an immediate, necessary nature. Recommendations Report Reference Budget Cost (2010 Dollars) Service air conditioning equipment $ $4000 Electrical distribution equipment repairs Minor Repair batteries - Emergency lights Minor Repair loose plumbing fixtures at baths Minor Reroof the EPDM system Over $200,000 Service expired fire extinguishers Minor
4 Report Number: 12373C Page 4 of 34 Repair broken doors left side entry Minor 1.2 SUMMARY OF SHORT-TERM REPAIRS The following table summarizes the recommendations made in this report that should be addressed within the next 2 years. Recommendations Report Reference Budget Cost (2010 Dollars) Fix air leaks at ductwork Minor Replace water damaged drywall at left side entry $ $4000 Repair damaged EIFS at front, sides and parking area $ $ SUMMARY OF UNPREDICTABLE REPAIRS The following table summarizes the recommendations made in this report that are unpredictable by nature, but may require addressing within the next few years. Recommendations Report Reference Budget Cost (2010 Dollars) Replace water damaged ceiling tiles $4000 Repair miscellaneous interior items at office Minor Replace water heaters $ $4000 Improve drop ceiling insulation when renovating $ $4000 Vent bath fans to exterior Minor Recaulk windows Minor Replace windows with broken seals at right and left front $ $4000 Replace broken windows center front Minor Modify grade to stop ponding water at paver front entry $ $4000 Asphalt paving renewal Over $10000 * The timing for replacement of this component is unpredictable. Statistically, it has reached the end of its life expectancy at this time.
5 Report Number: 12373C Page 5 of Introduction As per the request and in the company of Mr. Bob Jones representing The ABC Group and in accordance with our proposal dated 12/21/2007, a visual inspection was performed of the property. Our inspection was limited to identify the existing conditions of the following readily visible building components: Structure Heating System Plumbing System Ventilation System Insulation Fire Protection Systems Electrical System Air-conditioning System Roofing System Exterior Components Interior Components This assessment meets or exceeds the ASTM standard for Property Condition Assessments. This report provides recommendations, preliminary cost estimates and priorities for: remedying major deficiencies, updating ageing major components, and undertaking further detailed investigations. The recommendations are for remedial actions that are considered to be beyond the normal maintenance of the building. Costs are provided for recommendations expected to exceed $3,000. The costs are only intended to provide an order of magnitude. Contractors should be contacted for exact quotations. This report is intended for the exclusive use of our client. Use of the information contained within the report by any other party is not intended and, therefore, we accept no responsibility for such use. Fire pump house
6 Report Number: 12373C Page 6 of DESCRIPTION 3.0 Structure The building is of slab-on-grade construction. The exterior walls are of CMU-concrete masonry units- at sides and rear. The concrete foundations support the exterior CMU walls. The metal roof deck is supported by OWS- open web steel joist. The roof joists are supported by steel frame construction. Steel I beams bear upon metal columns throughout the facility. 3.2 OBSERVATIONS AND DISCUSSION Minor cracks were noted in CMU at both sides of structure. Cracks occur at or near expansion joints designed to allow for movement within the wall. Cracks are less than 1/4inch wide and not deflecting. An older repair was made to cracks using sealant and paint- all appear stable now These cracks are not a major structural concern and no remedial action is considered necessary It is understood that plans are contemplated for the warehouse to add office / call center workspaces. No concerns are noted by the inspection team. 3.3 RECOMMENDATIONS, COSTS, AND PRIORITIES Recommendations Costs Time Frame 3.4 LIMITATIONS The examination of the structural components was visual only; a design review was not undertaken.
7 Report Number: 12373C Page 7 of DESCRIPTION 4.0 Electrical The electrical service feeding the property is overhead and transitions to underground before reaching the transformer at rear of building. The electrical service into the building is underground. The building is equipped with a 2000 amp, 480-volt, three-phase, four-wire electrical service. This capacity was determined by the rating of the main disconnect switch. The main service is divided into the following sub-services: Location Amperage Center rear electric room MDP 2000 amp 408Y/277 PPA 408Y/277 PPB 408Y/277 PPC 408Y/277 Center middle RPE 225 amps 208Y/120 Right side LDP 225amps 480Y/277 RPD 125amps 208Y/120 Right Middle PRL14 600amps 408Y/277 Right Front PRL14B 600amps 408Y/277 Right front Utility Closet RPB 100amps 208/120 PRL2 100amps 480/277 Office Phone Room RPA 100amps 208/120 LPA (lights) 100amps 480Y/277 Several transformers were noted in the building. These are as follows: Location Center rear Exterior Right side interior Right Middle interior Ceiling over office utility room Left side interior Transformer size (kva) 500 KVA 150 KVA 150 KVA Min access- appears to be 100 KVA 150KVA
8 Report Number: 12373C Page 8 of 34 There is a single meter for the building located at center rear exterior. A meter for the site lightning is at front exterior. The distribution panels employ circuit breakers. The wiring examined is a combination of copper and aluminum; however, the majority appears to be copper. Fluorescent lighting is used in the office area. This lighting is typical 480/277volt. Receptacles in office areas are typical 120volt with ground. Emergency exit indicator lighting is present at all exit doors. Egress flood lights are mounted on walls throughout the facility. The exterior fire pump has an electric motor and fire pump control installed at the right front of the property. The pump draws water from two detention ponds on the property. Site lighting is a combination of pole mounted lights and wall packs mounted to building. 4.2 OBSERVATIONS AND DISCUSSION While detailed load calculations were not performed, no problems are suspected with the service capacity The distribution equipment is well arranged Surface rust is present on the panel covers of Subpanels RPA & LPA located in the Utility Closet at the front of the warehouse. A utility sink and mops are contained in this room- mops likely stored against panel covers. No repairs are required Representative samples of accessible wiring were examined and electrical switches were spot tested in the areas inspected. All switches tested operated satisfactorily No major deficiencies were noted. Extension cords were noted in the right front office drop ceiling. These should be replaced with permanent wiring The electrical system and transformer appear to be properly grounded Emergency egress lighting wall packs did not operate when tested. Batteries and or fixtures need replacement The support legs of the fire pump controller are extremely decayed and need immediate repair. Water did not damage interior electrical components of controller. Other panels within the fire pump room have rust and corrosion and should be replaced. 4.3 RECOMMENDATIONS, COSTS, AND PRIORITIES
9 Report Number: 12373C Page 9 of 34 Recommendations Costs Time Frame Fire pump electrical distribution equipment repairs. $3000 Immediate Repair batteries - Emergency lights Minor Immediate 4.4 LIMITATIONS This was a visual review only. No load calculations or equipment testing was undertaken.
10 Report Number: 12373C Page 10 of DESCRIPTION 5.0 Heating The building is heated by 16 roof-mounted electric heat pump units. The heat pumps are equipped with supplemental electric heating elements. The center rear left/right warehouse section is heated by two electric, ceiling-mounted unit heaters. Thermostats are located thought out all sections of the facility. Appendix B gives details of the roof-mounted equipment. 5.2 OBSERVATIONS AND DISCUSSION While the exact heating capacity was not determined, no problems are suspected. Adequate heating capacity should be available under normal circumstances The heat distribution is considered to be fair and acceptable for present configuration No heat was noted in the metal building additions at rear While it is impossible to predict with certainty when a heat exchanger will fail, the average life for roof top heating systems of this type is 15 to 20 years units are approximately 3 years old Two original units are approximately 12 years old and located at center rear left & right Poor supply air duct connections were noted above the office area. A temperature difference of plus 15 degrees was noted above the drop ceiling compared to the heated office area. Exterior temp during inspection was 45 degrees. Air leaks at ductwork should be sealed above office ceiling Thermostats are protected and locked with a key. Owner should provide keys to buyer. 5.3 RECOMMENDATIONS, COSTS, AND PRIORITIES Recommendations Costs Time Frame Fix air leaks at ductwork Minor Immediate 5.4 LIMITATIONS This was a visual review only. No load calculations or equipment testing was undertaken.
11 Report Number: 12373C Page 11 of DESCRIPTION 6.0 Air Conditioning The building is air-conditioned by rooftop HVAC systems. The total available cooling capacity for the building is 85.5 tons. The air is distributed through the same air handling equipment previously mentioned in the Heating section. Details of the air-conditioning equipment are provided in Appendix B. The building is equipped with a heat pump to provide central air-conditioning and to supplement the heating system. As with all heat pumps in this climate, the system is not designed to handle the entire heating load under all circumstances. The air is distributed through the same air handling equipment previously mentioned in the Heating section. 6.2 OBSERVATIONS AND DISCUSSION While detailed heat gain calculations were not performed, no problems are suspected with cooling capacity The newer units are approximately 3 years old. These units need basic servicing including air filter changes and checking of belts serving blower motors. Observed were dirty filters and damaged belts at numerous units This older two units are approximately 12 years old. Blower motor has been replaced in the center left unit and the filters need replacement. 6.3 RECOMMENDATIONS, COSTS, AND PRIORITIES Recommendations Costs Time Frame Service air conditioning equipment. $ $4000 Immediate
12 Report Number: 12373C Page 12 of LIMITATIONS This was a visual review only. No load calculations or equipment testing was undertaken. Since the heating components were operating at the time of this inspection, the rooftop units were not observed in the cooling mode.
13 Report Number: 12373C Page 13 of DESCRIPTION 7.0 Ventilation The washrooms are ventilated by bath exhaust fans at the ceilings. The offices receive fresh air from the heating and cooling rooftop units. These units are equipped with economizer units, which allow fresh air from the exterior to enter into the return air plenum. This introduction of fresh air helps to improve indoor air quality as well as compensate for air that is expelled through exhaust fans. There are exhaust fans for each building addition at the rear. 7.2 OBSERVATIONS AND DISCUSSION No major deficiencies were noted The washroom exhaust fans operated properly at the time of the inspection. These fans are improperly vented to ACT- drop ceiling above the offices. These should be vented to the building exterior The building addition exhaust fans did not respond when tested. These appear to be electrically turned off. 7.3 RECOMMENDATIONS, COSTS, AND PRIORITIES Recommendations Costs Time Frame Vent bath fans to exterior Minor Discretionary 7.4 LIMITATIONS
14 Report Number: 12373C Page 14 of DESCRIPTION 8.0 Plumbing There are three 19-gallons, electric domestic water heater in the utility closet, office ceiling and center rear of warehouse. Men s and women s washrooms are located in the left and right office areas and at center of office areas. The building does have a wet fire sprinkler system with an electric pump and pond at left front. Fire Department Connections FDC- are located at left side of building and at the pump house. The building has a septic system. 8.2 OBSERVATIONS AND DISCUSSION Adequate water pressure appears to be available No active leaks were noted in the supply plumbing pipes The domestic water heaters are approximately 12 years old While it is impossible to predict with certainty when a domestic water heater will fail, these units typically last 15 years. Therefore, updating the water heater may be necessary within the next few years Most plumbing fixtures that were tested operated satisfactorily However, improvements are recommended to the following areas: The middle men s baths toilet should be better secured to the floor. The women s middle toilet leaked when tested and should be repaired The Fire Sprinkler stand pipe is located at the left inside of the warehouse. A service tag states it was serviced/ tested 16 AUG 2007 by GA Automatic Sprinkler Co- Valdosta GA. The fire pump controller is located in the exterior pump house (see Electrical Section) Building owner could not provide details on the servicing of the septic system. With an unknown history Champia recommends the system be pumped prior to occupation. No seepage or leaking was observed at the septic location during inspection.
15 8.3 RECOMMENDATIONS, COSTS, AND PRIORITIES Report Number: 12373C Page 15 of 34 Recommendations Costs Time Frame Replace water heaters $ $4000 Unpredictable Repair loose plumbing fixtures at bathrooms Minor Immediate 8.4 LIMITATIONS The internal evaluation of the septic system is beyond the scope of this assessment.
16 Report Number: 12373C Page 16 of DESCRIPTION 9.0 Roofing The building is covered by a single-ply EPDM rubber membrane on one level. The membrane is covered by large-stone ballast. Metal flashing is used to cap the parapet wall around the building perimeter. Skylights are installed throughout the warehouse. The center office area has a painted galvanized metal roof. The roof drainage is via an interior collection system. Water is directed to these drains via a designed slope. Water is collected and deposited to rear of building Metal building additions at rear have metal galvanized roof panels. 9.2 OBSERVATIONS AND DISCUSSION The EPDM rubber membrane appears to be in poor condition. This installation is estimated to be original 12 years old. This type of system has an average life expectancy of 15 to 20 years The majority of problems found with single-ply membranes to date relate to incorrect installations and subsequent seam failures. This appears to be a single-ply installation. Two-ply installations are more desirable, as they tend to have longer life expectancies. No improvements are considered practical. The membrane is not properly adhered to the metal drip edge at the parapet perimeters. This should be repaired. The skylight flashings appear to be in poor condition. It is not uncommon to encounter problems with leakage around skylight flashings. From inside the warehouse they are leaking at some locations Tears in EPDM roof is present at nearly all HVAC curbs and is allowing water to entry building.
17 Report Number: 12373C Page 17 of The EPDM roof is considered to be in poor condition and, ideally, should be replaced. Existing roofing materials should be removed before adding a new membrane Evidence of water penetration was found around the skylights Metal roof at front center office are in serviceable condition Metal roof panels at rear addition are in serviceable condition. 9.3 RECOMMENDATIONS, COSTS, AND PRIORITIES Recommendations Costs Time Frame Reroof the EPDM areas. Over $200,000 Immediate 9.4 LIMITATIONS
18 Report Number: 12373C Page 18 of DESCRIPTION 10.0 Interior The office ceiling finishes consist of suspended ACT- acoustical ceiling tiles. The office wall finishes consist of steel studs and drywall with paint or wall paper. The office floor coverings consist of carpet or VCT vinyl composite tile. Warehouse has open ceilings to framing and roof decking. Walls are structural concrete block at sides, nonload bearing steel stud and drywall at middle, nonload bearing CMU abutting office areas. Warehouse floor is raw or painted concrete OBSERVATIONS AND DISCUSSION Considering the age of the building, walls are relatively plumb, doorjambs are square and floors are reasonably level Drywall has water damaged and mold is present at left side office entry. Likely this is from damaged roofing at above location. Drywall should be removed and replaced. (Mold was not tested for toxicity) Water stains were noted at drop ceilings in the office areas. This occurs throughout and will likely require the replacement of most tiles Sink cabinet bottom is decayed at center front break room and needs replacement Toilet partition walls are loose throughout bathrooms and needs repair or replacement Fire extinguishers are observed throughout the facility. The inspection tags show FEB 2007 as expiration dates. Extinguishers need servicing On the whole, the interior finishes are fair RECOMMENDATIONS, COSTS, AND PRIORITIES Recommendations Costs Time Frame Replace water damaged ceiling tiles. $4000 Discretionary
19 Report Number: 12373C Page 19 of Replace water damaged drywall at left side entry Repair miscellaneous interior items at baths/ break rooms $ $4000 Immediate Minor Unpredictable Service expired fire extinguishers Minor Immediate 10.4 LIMITATIONS
20 Report Number: 12373C Page 20 of DESCRIPTION 11.0 Exterior The exterior walls are solid masonry at both sides and rear. The front exterior walls are clad with EIFS (Exterior Insulation and Finish System- aka Synthetic Stucco, Dryvit). The ceilings of the covered parking also have EIFS installed. The front entrance doors and windows are aluminum-framed, double-glazed units. All windows are fixed glazing. The exit doors at the warehouse areas are steel units. The overhead garage doors are metal sectional units. There are 2 loading docks in the left and right rear façade. The Left and Right rear additions have metal galvanized siding. There is a poured-concrete sidewalk around the perimeter of the building. Concrete pavers patio is located at center front entry. There is asphalt paving parking at right, left and rear of property. A total of 109 spaces were counted with 2 being marked as handicapped. An asphalt drive runs past the front entry. There are two fire pump ponds at the left front side of the building. The present owners sign is attached to the front façade. A flagpole is installed at center front of property.
21 11.2 OBSERVATIONS AND DISCUSSION Report Number: 12373C Page 21 of The exterior masonry is in good condition. Sealing of expansion joints is required when normal paint maintenance is performed The EIFS cladding requires attention to improve weather tightness. Cracks and damage are present throughout the facade, columns and parking ceilings. Sealant can be used at some locations but EIFS repairs will be required at most. This should be a high priority to keep water from damaging interior finishes The metal siding at the additions has minor damage and is loose /separating. The separation should be secured/ repaired The office entry doors are in fair condition condition. The left side entry door did not close and needs adjustment The overhead doors are in fair condition. The automatic overhead door openers operated properly at the time of the inspection. Weather strips are damaged on most and will need replacement The caulking around the windows and in the exterior wall expansion joints is deteriorated and should be renewed The right front windows have lost their seal and condensation has formed between the glazing. Windows at left front have loose gaskets and likely will become fogged as time progresses. These windows need only be replaced for cosmetic reasons Center right window has a hole through the glass and will need replacement The site grading is considered to be good. Ponding of water has occurred at paver patio at front entry The interlocking pavers patio at the front entry has settled at the in the center. This may pose a tripping hazard. Repairs are likely because this is the front entry to the building The asphalt paving is in poor condition. Alligator and spalling has occurred as would be typical for a parking area of this age. Sealing may extend the life of the parking areas Concrete curb and gutters are damaged at some locations. Minor repairs maybe required Flagpole hardware is damaged and needs servicing RECOMMENDATIONS, COSTS, AND PRIORITIES Recommendations Costs Time Frame Repair damaged EIFS at front, sides and parking ceiling $ $5000 One Year Repair broken doors- left side Minor Immediate Recaulk windows. Minor Unpredictable Replace windows with broken seals at right and left office. $ $4000 Discretionary Replace broken windows Minor Discretionary Modify grade to stop ponding water at $ $4000 Discretionary
22 Report Number: 12373C Page 22 of pavers- front entry Asphalt paving renewal Over $10000 Discretionary LIMITATIONS Trucks and equipment was being loaded through most of the overhead doors, limiting the inspection in this area.
23 Report Number: 12373C Page 23 of DESCRIPTION 12.0 Insulation The presence of insulation in the exterior walls could not be verified. It is quite possible that little or no insulation is present. The cavity in the exterior masonry walls is typically minimal. It is probably not economically viable to fill this cavity with insulation. The amount of insulation in the flat roof could not be ascertained. This is likely 2 or 3inch insulation board and part of the EPDM roofing system. NO insulation was noted in the drop ceiling at office OBSERVATIONS AND DISCUSSION The amount of insulation noted on the roof is considered typical for a building of this age The recommended amount of insulation in flat roofs is R-10 to R-20. This can be checked when reroofing and upgraded, if necessary The amount of insulation in the drop ceiling is below modern standards. The recommended amount of insulation in attic spaces is R RECOMMENDATIONS, COSTS, AND PRIORITIES Recommendations Costs Time Frame Improve drop ceiling insulation when renovating. $ $4000 Discretionary 12.4 LIMITATIONS
24 Report Number: 12373C Page 24 of Closing Comments This report provides you with an overview of the condition of the major components in the building. Should you have any questions, please do not hesitate to contact us. The Brooks County Building Inspection Department was contacted to inquire for outstanding permits for the facility. NO outstanding permits are open for the property. The Brooks County Fire Service was contacted to inquire if the building has fire /safety violations against it. No recorded violations are shown in the records. Ms. Cynthia Peelor was the contact at Fire Department Please find photographs documenting several conditions noted in Appendix A. Please find a summary of the rooftop heating and cooling equipment in Appendix B.
25 Report Number: 12373C Page 25 of 34 Appendix A: Photographs Photo 1 Front view Photo 2 Crack in CMU wall- typical 3.2.1
26 Report Number: 12373C Page 26 of 34 Photo 3 Meter at rear Photo 4 Surface rust utility closet Photo 5 Rust at fire pump 4.2.8
27 Report Number: 12373C Page 27 of 34 Photo 6 Rust on base of Fire Controller Photo 7 Damaged HVAC belt- typical Photo 8 Dirty HVAC filters typical 6.2.2
28 Report Number: 12373C Page 28 of 34 Photo 9 Rear addition vents Photo 10 FDC at pump building Photo 11 FDC at left side 8.2.7
29 Report Number: 12373C Page 29 of 34 Photo 12 Roof overview Photo 13 Metal roof at office and parapet separation Photo 14 Tears in roof membrane typical 9.2.4
30 Report Number: 12373C Page 30 of 34 Photo 15 Separation / delaminating of roof patching Photo 16 Damaged roof membrane Photo 17 Mold on walls of bath and entry
31 Report Number: 12373C Page 31 of 34 Photo 18 Water stains on ceiling- one of many! Photo 19 Rotted break room sink bottom Photo 20 Expired fire ext inspect
32 Report Number: 12373C Page 32 of 34 Photo 21 Damaged EIFS Photo 22 Damaged EIFS at parking ceiling Photo 23 Sealant / caulk at joints 11.2
33 Report Number: 12373C Page 33 of 34 Photo 24 Damaged curbs- typical Photo 25 Low water at fire pump / detention pond
34 Report Number: 12373C Page 34 of 34 Appendix B: Summary of Rooftop Equipment HVAC Unit # Year Built Cooling Capacity X 1000 BTUs Heating Capacity [output] Operating Mode Makeup Air Manufacturer Area Serviced Comments 4 10 Ton 10kw Auto Yes YORK Left Middle Dirty Filters 2 5 none Auto N/a YORK Left Front kw Auto Yes YORK Left Front Auto Y YORK Left Front Dirty Filters/ Loose control splice Auto Y YORK Left Middle Dirty Filters No label N/A Auto N/A Name worn off Warehouse training room RSM Auto Y YORK Right Middle Belt Damaged RSR Auto Y YORK Right Rear RMR Auto Y YORK Right Mid Rear W1 4 10kw Auto Y YORK Rear West West AC 1 E1 4 10KW Auto Y YORK Rear East East AC 1 85 tons total Small unit with blower unit insidesplit system, like residential
Property Condition Assessment
Property Condition Assessment Business, Wisconsin Inspection Date: 8/2009 Prepared For: Business Owner Report Number: TD999909 Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar
More informationInspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More informationCrawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
More informationCLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
More informationVision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
More informationPROPERTY INSPECTION REPORT
(850) 297-1998 1716 Monticello Dr Tallahassee, Florida 32303 PROPERTY INSPECTION REPORT THIS INSPECTION IS A DETAILED LISTING OF AREAS VISUALLY INSPECTED AT:, Tallahassee FL Client Tallahassee, FL 32304
More informationInspection Report Atlanta Strip Mall Commercial Building Property Address:
Page 1 of 25 Inspection Report Atlanta Strip Mall Property Address: Smyrna GA 30082 Page 2 of 25 South East Building Consultants Ray Thoroman Serving the entire State of Georgia 6 678-410-3005 Page 3 of
More informationMay 5, 2010. Client Client Address. Re: Inspection Address, Chicago, Illinois. Dear Mr. Client,
PROPERTY INSPECTION PROFESSIONALS May 5, 2010 Client Client Address Re: Inspection Address, Chicago, Illinois Dear Mr. Client, On May 4, 2010, Tomacor completed a property inspection of the above referenced
More informationTotal Home Inspection Checklist
Total Home Inspection Checklist Use a checklist like this to make sure that you are looking at all parts of the house. Check off those items that are in good condition and make notes about those that are
More informationInspection Item COMMENTS
APPENDIX 9 AFFORDABLE HOUSING PROGRAM INSPECTION CHECKLIST Participating Jurisdiction: Homeowner Name: Assisted Property Address: Date of Physical Inspection of Property: Total Square Footage of Property:
More informationBuilding Condition Assessment Report
Building Condition Assessment Report Asset C3c - Oak Terrace Cottage 121 Address Riverview Lands, 2601 Lougheed Highway, Coquitlam, BC. V5C 4J2 Construction Year Size (Gross Floor Area) 1920. 2,553 Sq.Ft.
More informationCOMPREHENSIVE PROPERTY INSPECTIONS
COMPREHENSIVE PROPERTY INSPECTIONS Thank you for selecting CPI for your Deficiency Observation. A full home inspection was not performed on this property at the buyers request. This inspection is a limited
More informationBuilding Condition Assessment Report
C2 - Nurses Resident (aka Administration) Building Condition Assessment Report Asset Address Address Construction Year Size (Gross Floor Area) Asset Type Floors Above Ground Inspection Date C2 - Nurses
More informationSelf-Home Inspection Checklist
To be used as a first home visit for note taking. Visit www.homeinspectiondirect.com for more tips and information about buying a home and hiring a home inspector. This form in no way replaces a professional
More informationINVOICE. DATE: May 11, 2005. DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl.
INVOICE DATE: May 11, 2005 CLIENT: The Buyer DESCRIPTION Inspection and report on a property located at OF SERVICES: Perfect Street, Sarasota, Fl. TOTAL FEE: $ See Schedule Tom Villani Hallmark Inspection
More informationPROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792
More informationReport for. Dick and Jane Homeowner. 1234 Lovers Lane, Houston, Texas 77000
Report for Dick and Jane Homeowner 1234 Lovers Lane, Houston, Texas 77000 March 17, 2004 I NI NP R Inspection Item I. STRUCTURAL SYSTEMS o o o A. Foundations (If all crawl space areas are not inspected,
More informationSODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST
SODA SPRINGS JOINT SCHOOL DISTRICT NO. 150 RECOMMENDED REPAIRS, REPLACEMENT, AND ADDITIONS OPINIONS OF PROBABLE COST SODA SPRINGS HIGH SCHOOL REPAIRS AND UPGRADES SITE Construction Estimate = $100,000
More informationBUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207
BUILDING DEPARTMENT 8748 W. 82 nd Place - Justice, IL 60458 Phone: (708) 458-2130 Fax: (708) 458-3207 SELF EVALUATION CHECKLIST FOR RESIDENTIAL AND MULTI-FAMILY DWELLING INSPECTIONS The attached checklist
More informationFacility Summary. Facility Condition Summary. Seattle School District David T. Denny International Infrastructure. Facility Components
Infrastructure Facility Condition Summary Weighted Avg Condition Score Facility Components Systems Surveyor/ Date Done Comments G Sitework.9 Site Improvements Parking Pedestrian Paving Site Development
More informationInspection Report. Jacksonville Krystals Inspection. Property Address: Downtown. Jacksonville FL 32204. South East Building Consultants
Page 1 of 53 Inspection Report Jacksonville Property Address: Jacksonville FL 32204 South East Building Consultants Ray Thoroman Inspecting Jacksonville FL and entire South East Page 2 of 53 Table of Contents
More informationBUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES
Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE
More informationCHRIS CURLES and ASSOCIATES INSPECTION SERVICES
CHRIS CURLES and ASSOCIATES INSPECTION SERVICES Inc. Chris Curles, President www.homeinspectionsatlanta.com chriscurl@comcast.net Office: 770-493-0227 Professional Member Of: GAHI # 93006 ASHI # 211725
More informationInspection Tech. (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg
Inspection Tech (330) 310-6559 http://www.inspectiontech.us a_westerburg@inspectiontech.us Inspected By: Aaron Westerburg Inspection Tech Home Inspection Report Prepared For: Mr. & Mrs. Homebuyer Property
More informationI NI NP R Inspected Items
6/ /07 The Inspection of the property listed above must be performed in compliance with the rules of TREC. The inspection is of conditions which are present and visible at the time of the inspection, and
More informationHome Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
More informationGeorgia Home Inspection Services
Cover Page Property Inspection Report My street, Anytown GA, 30000 Inspection prepared for: John Doe Inspection Date: 7/18/2011 Time: 5pm Age: 25+ Size: >1500 Weather: Clear This ranch style home is in
More informationHome Inspection Report
Report# 21009 Page 1 of 24 Home Inspection Report Property Address: 123 Maple Lane, St. Augustine, FL 32092 Prepared For: Mr. Smith Prepared By: EDGE Inspections www.edgeinspections.com PO Box 601055 Jacksonville,
More information17,280 square feet Overview:
CENTRAL OFFICE Located at 167 Boston Post Road, East Lyme, Connecticut, the Central Office was built in 1916 as the original Flanders Elementary School and remains connected to the current school. The
More informationPEPPER VINER HOMES WARRANTY GUIDELINES
PEPPER VINER HOMES WARRANTY GUIDELINES All non-emergency warranty and customer service requests MUST be made in writing. This provides you with documentation and allows Pepper Viner to operate efficiently.
More informationOrlando Home Inspection Services
PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com
More information159 Morningside Avenue, Toronto
159 Morningside Avenue, Toronto Inspection Report February 6, 2013 159 Morningside Avenue, Toronto Inspection Report Overall Condition: This 60±-year-old home was extensively renovated and extended in
More informationHomeSpec REPORT SUMMARY
HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above
More informationRoof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
More informationVari Inspection Services
Cover Page Vari Inspection Services Property Inspection Report Inspection prepared for: Sample Real Estate Agent: None - Date of Inspection: 5/13/2015 Inspector: Tony Vari License # HI8047 23110 STRD 54
More informationINSPECTION PROPERTY ADDRESS: Fort Bend County, Texas
5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction
More informationAccurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois
Accurate Home Inspection of Illinois 815-260-1727 1213 Norley st. Joliet, illinois 60435 aaccurate1@yahoo.com We Inspect to Protect!!! Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave.,
More informationA TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS
A TO Z HOME INSPECTIONS PROFESSIONAL HOME INSPECTION SERVICES FOR HOME BUYERS AND SELLERS Insurance Inspection Report 1234 Main Street Tallahassee, Florida Report Prepared For: Charles Smith Report Prepared
More informationInspecton Report. Property Address:
Inspecton Report Provided by: National Home Inspections Inspector: Bob Smith 456 S Main Denver, CO 46312 (645) 423-3242 bob@nationalhomeinspections.com www.nationalhomeservices.com Property Address: 873
More informationPROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: Somewhere, FL CLIENT: GAIA GC ID No: 2015000 DATE: 12/31/2015 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792 FLORIDA
More informationHOME INSPECTION CHECKLIST
CLOSING.COM LEARNING CENTER HOME INSPECTION CHECKLIST CONTENTS Attic 1 Balconies 1 Basement 1 Bathroom 2 Ceiling, Floors and Walls 2 Crawlspace 3 Decks and Porches 3 Doors and Windows 4 Drainage 4 Driveways
More informationA.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111
A.C.E. Home Inspection Service www.acehomeweb.com St. Peters, MO 63376 (636) 978-9111 Inspector Name: Tim Knight, ASHI Member 202490 Inspection No: 12121212 Inspection Date: 1/1/2012 Client: Address: John
More informationStructure Survey Findings:
Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,
More informationRoof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
More informationDoes Wall Township require an inspection by the building department on resale of a home?
Selling your home Does Wall Township require an inspection by the building department on resale of a home? No. We do not require a Certificate of Continued Occupancy on the resale of home. A Smoke Detector,
More informationBUNKER HILL ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1970 BUILDING AREA 98,200 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 387 WARD 5 PROPOSED PROGRAM CAPACITY 750 Site Plan BUNKER HILL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationFacility Assessment for. 11801 East Main Street, Huntley, IL
Facility Assessment for 11801 East Main Street, Huntley, IL July 12, 2012 Prepared by: Dewberry Architects Inc. 25 S. Grove Avenue, Suite 500 Elgin, IL 60120 (847) 695-5840 The Village of Huntley requested
More informationWater Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
More informationSTATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE:
STATE OF FLORIDA HOME INSPECTION STANDARDS OF PRACTICE: 61-30.801 Standards of Practice, General. (1) Home inspections performed to these Standards of Practice are intended to provide the client with information
More informationPropery Inspection Report
Propery Inspection Report Cover Page,, Ok Inspection prepared for: Date of Inspection: 9/28/2014 Time: 8:30 AM Age of Home: 2011 MOL Weather: Clear 62 degrees Inspector: License #130 5400 Hwy 177, Marland,
More informationCONSERVATION MAINTENANCE WORKSHEET Universal Checklist
3.1 SITE 1 Concrete curbs Check for cracks, spalling, growth from joints X 2 Stone curbs Check for cracks, spalling, growth from joints X 3 Concrete walkways Look for uneven surfaces, ponding, growth from
More informationHow To Check For A Deficiency
UPCS in Pictures The following pictures are not all inclusive nor does it cover every deficiency. The pictures, however are some of the most commonly cited deficiencies on REAC inspections. Erosion The
More informationNominal Life Expectancy for Building Components
Nominal Life Expectancy for Building Components Building System Page A. HVAC 2 B. Elevator/Escalator 6 C. Plumbing 7 D. Roofing 8 E. Electrical 10 F. Fire/Life/Safety/Security System 11 G. Interior Finishes
More informationSAMPLE SCHEDULE OF VALUES APPLICATION & CERTIFICATE FOR PAYMENT
SAMPLE SCHEDULE OF S 1.00 General Conditions 1.01 Project Management 1.02 General Superintendent 1.03 Superintendents 1.04 Safety Engineer 1.05 Scheduling 1.06 Field Engineering 1.07 Bonds 1.08 Trailer
More informationThe Uniform Building Inspection Report Condensed
The Uniform Building Inspection Report Condensed Single Family Residence:, Scottsdale, AZ Condensed Report Version Prepared for: John Doe Inspection Date: 9/19/2005, 1:00:00 AM Report Number: 091805s Inspection
More informationJagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922
Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922 November 09, 2002 Name deleted, Esq. address deleted Your client:
More informationPrinted Monday, August 27, 2007 Inspected By: Michelle Teague. Client Information: Inspection, Condo City Lane Chicago, IL. Inspected 8/22/07 8:00 AM
Pa g e 1 o f 1 5 All About Homes, LLC Michelle M. Teague Owner 312-371-7414 Phone 773-508-6209 Fax www.michelleinspects.com michelle@michelleinspects.com 1725 W. Granville Ave. Chicago, IL 60660 Printed
More informationPROPERTY INSPECTION REPORT Property Address:
Scott Certified Member P. O. Box 9007 Indianapolis, IN 690-007 (7)-750-60 Fax: 7-876-8 PROPERTY INSPECTION REPORT Property Address: Prepared for: Inspection Inspector: Lou Buehler Inspection #: BUYERS
More informationPre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
More informationCommon Problems with Walls
Common Problems with Walls Common Problems with Walls There are problems and concerns that are shared by all walls and siding installations. In this article, we will learn about the following commonly
More information#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check
#1) BEFORE Purchasing Land Here Is A Checklist Of Things You Should Check Zoning laws Deed restrictions on home size, foundation style, roof pitch, etc. Suitability (slope, wetland issues, etc.) Accessibility
More informationCONDITION OF QUALITY ITEMS
CONDITION OF QUALITY ITEMS FOUNDATION Always look for moisture problems and any bulges or irregularities in the walls. Lines on the walls or floors may indicate water problems. Have these been cured? If
More informationAttachment #23 Health Safety Table. Client Education Inform issue and document. How to clean & maintain gutters. How to adjust sprinklers
Exterior Visual Health & Safety Issue Allowable Action Site Drainage Exterior grade does not slope 2% within the first 10' Site drainage causing bulk moisture in crawl space or basement Repairs to existing
More informationSWF Home Inspections
Cover Page SWF Home Inspections Property Inspection Report Inspection prepared for: Mr & Mrs Home Buyer Real Estate Agent: My Favorite Agent - Date of Inspection: 7/4/2013 Age of Home: 2004 Size: 1568
More informationBOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE
More informationVilla Home Inspections
PROPERTY INSPECTION REPORT SITE INFORMATION Property Address: City, State, Zip: Date of Inspection: Time of Inspection: Parties Present during Inspection: Inspector: Address Omitted. Inglewood, CA 90305.
More informationPRE-OWNED MOBILE / MANUFACTURED HOME PRE-INSPECTION
PRE-OWNED MOBILE / MANUFACTURED HOME PRE-INSPECTION Receipt # Official Use Only Date: Owner name: Phone #: Check One The home is currently located in the following City or County,, and I have attached
More informationAll substantial design decisions and budget confirmation shall be resolved for the College to approve the Design Development Submittal.
2.02 DESIGN DEVELOPMENT PHASE GENERAL The Architect shall prepare the Design Development Documents from the approved Schematic Design. The Design Development Documents shall consist of drawings and other
More informationHOMEOWNER S PERMIT GUIDE
HOMEOWNER S PERMIT GUIDE WHEN IS A PERMIT REQUIRED? Department of Development and Permits 306 Cedar Road, City Hall 2 nd Floor P.O. Box 15225 Chesapeake, VA 23328 Phone: (757) 382-6018 Fax: (757) 382-8448
More informationMURCH ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1929 BUILDING AREA 47,700 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 491 WARD 3 PROPOSED PROGRAM CAPACITY 500 Site Plan MURCH - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationInspection Report. Todd Shafer 13190 Kaufman Ave. Hartville, Ohio CAPSTONE INSPECTIONS, LLC. Inspector: Tim Rollins. 3664 Camaro St.
Inspection Report Todd Shafer 13190 Kaufman Ave. Hartville, Ohio CAPSTONE INSPECTIONS, LLC Inspector: Tim Rollins 3664 Camaro St. NE Canton, Ohio 44721 Property Informaon Client: Todd Schafer Structure
More informationSlavic Village Building Condition Review
Slavic Village Building Condition Review Slavic Village Development May 8, 2015 Page 1 EXECUTIVE SUMMARY City Architecture was commissioned by Slavic Village Development to review five existing facilities
More informationInspection Report. Dream Home Inspections. www.timinspects.com. 415 Second Ave. Frisco CO 80443-1789 (970) 368-2668
Inspection Report Property Address: 123 Dream Home Way Frisco, CO 80443 Prepared for: Inspector: Tim Nixon Tim Nixon Inspection date: 3/28/2014 1 of 9 General Information Property Information Address:
More information2. What building projects are exempted? (permit not required)
BUILDING AND SAFETY DEPARTMENT 1. What building projects require a permit? Following is a list of projects that require building permits based on Appendix chapter 1 of the California Building Code and
More informationEstimating Database Checklist
Estimating Database Checklist If you are creating a new estimating database for projects, the following list offers a thorough listing of Main and Sub Categories. You can also use it as a checklist to
More informationHow To Plan A Building
State of Nevada Department of Administration Purchasing Division Las Vegas Purchasing Warehouse Facility Condition Analysis LAS VEGAS PURCHASING WAREHOUSE 1054 South Commerce Street Las Vegas, Nevada Site
More informationCITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
More informationINSPECTION REPORT. LOCATION OF PROPERTY 1234 Sample Street Tucson, AZ 85701. CLIENT Mr. & Mrs. John Q. Sample c/o Agent DATE OF INSPECTION 1/30/2008
INSPECTION REPORT LOCATION OF PROPERTY 1234 Sample Street CLIENT Mr. & Mrs. John Q. Sample c/o Agent DATE OF INSPECTION 1/30/2008 INSPECTOR Dave Woityra FILE CODE: 0100114.SAM AGENT Sample Q. Jones A.B.C.
More informationELIGIBLE REPAIR PROJECT PARAMETERS
THE DISTRICT MUNICIPALITY OF MUSKOKA ONTARIO RENOVATES PROGRAM FOR HOMEOWNERS ELIGIBLE REPAIR PROJECT PARAMETERS 1. To have your project considered and payment processed, all projects requiring a Building
More informationInspection Report of 1895 Jamesport Circle PSL, Fl 33953 Prepared for Yen Ho
Inspection Report of 1895 Jamesport Circle PSL, Fl 33953 Prepared for Yen Ho The State of Florida requires the builder to build in compliance with the Florida Building Code. Florida State Statutes 455
More informationA comfortable house is a great source of happiness. - Sydney Smith. Home Maintenance Guide
A comfortable house is a great source of happiness. - Sydney Smith Home Maintenance Guide HOME GUIDE By conducting regular maintenance checks, you can prevent small inexpensive repairs from becoming more
More information48. AQUARIUM. Aquarium. Classification: Cluster: Location: Close to junction of Inselrhue and Loiter Way, Belle Isle. Total Area: No.
Classification: Cluster: Location: Total Area: No. of Stories Aquarium Acreage Owned: Acquired: 1904 Most Recent Improvements: THE AQUARIUM Close to junction of Inselrhue and Loiter Way, Belle Isle Two
More informationCommercial Roof Inspection Form
Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building
More information29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York
Due Diligence Report New York, New York Prepared for Mr. On February 8, 2010 P a g e 1 Table of Contents PAGE 3.. GENERAL INFORMATION PAGE 4 FILINGS PERMITS AND ENCUMBRANCES PAGE 6. CORE AND SHELL PAGE
More informationProperty Inspection Report
Property Inspection Report Sample Commercial Inspection, Ca 95123 Inspection Date: Sample Sample Report Number: I1028548 Inspector: Martin Morgan 2005 All Bay Home Inspection Sample, San Jose Page 2 of
More informationHome Energy Evaluation Report for Fritz Kreiss and Catherine McQueen
Home Energy Evaluation Report for Fritz Kreiss and Catherine McQueen May 2008 Wisconsin Area PO BOX 115 Lake Geneva, WI 53147 CELL (414) 550-4765 Home Performance with ENERGY STAR Evaluation Report Customer
More informationReport Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10
Report Index PROPERTY DESCRIPTION 1 ELECTRICAL SYSTEM 2 COMMON INTERIOR AREAS 3 INTERIOR ROOMS 6 KITCHEN 8 BATHROOMS 10 PROPERTY DESCRIPTION PROPERTY INSPECTED: INSPECTION ADDRESS: 4722 Baltimore Avenue
More informationWhitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.
Building Type Building Code Whitley Classroom Buildings BOCA, UBC, SBCCI, NEC, ADA Structural Support Outrigger construction standard, Whitley model classrooms. Main support beams to be 12 11.8# per lineal
More informationBuilding Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
More informationThis report presents the findings and recommendations of the assessment of energy use and
This report presents the findings and recommendations of the assessment of energy use and environmental stewardship of Arlington Street Church, Boston, MA. As stewards of the earth it is important that
More informationProperty Inspection Report
Property Inspection Report 1234 Bear St., Denver, CO 80223 Prepared For: John Smith Inspection Date: 12/11/2015 Prepared By: Bill Heine, Certified Professional Inspector ResInspect, LLC 303-359-7573 Email:
More informationHome Inspection Report
Home Inspection Report Report Number: 144 For The Property Located On: 123 Any Street 27587 Prepared For Exclusive Use By: Mr. Sample N/A,,, Report Prepared By: Edward Carapezza; License No.: 3447 Inspector
More informationRehab Inspection Report Page 1
Rehab Inspection Report Page 1 Home Address: Construction Style: Number of bedrooms Square footage: Value of offer: Estimated rehab cost: Value of resale: Orientation of house: N S E W Note: orientation
More informationFacility Assessment Report, Montgomery Independent School District
THE LEARNING CENTER CAMPUS DATA THE LEARNING CENTER 700 Dr. Martin Luther King Jr. Drive, Montgomery TX 77356 Year Built 1958 Approx. Total Square Footage Grades Served Current Enrollment 22,050 n/a n/a
More informationThis handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
More informationStuccoSpec Moisture Testing Inspection
e-mail - stuccospec@juno.com StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012
More informationThermal Imaging for Home Inspectors
Thermal Imaging for Home Inspectors Structural member placement The gabled end of a cathedral ceiling. Note the studs and the ceiling joists with blocking. What is that glow in the upper right hand corner?
More informationbout your house before you start Renovating Your Bathroom
A bout your house CE 28e before you start Renovating Your Bathroom Inadequate lighting Water-wasting showerhead Renovating your bathroom is a great way to add value to your home both for your family s
More informationWOODLAND HOMES BUILDING PROCESS A STEP BY STEP CONSTRUCTION GUIDE TO YOUR NEW HOME
WOODLAND HOMES BUILDING PROCESS A STEP BY STEP CONSTRUCTION GUIDE TO YOUR NEW HOME 1 THE BUILDING PROCESS The focus of Woodland Homes building department is Quality, Service and Predictability. Through
More information