Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E.

Save this PDF as:
 WORD  PNG  TXT  JPG

Size: px
Start display at page:

Download "Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E."

Transcription

1 Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E. Basic Thermostat Types Many technicians have great difficulty understanding how to properly wire a thermostat or how to replace a thermostat with a different thermostat. In fact, the wiring of a thermostat is quite simple circuitry, the confusion arises principally because of the various different ways different equipment manufactures handle the heating mode of the systems and the different ways a cooling system can be interfaced with the assorted types of heating systems, ranging from furnaces, heat pumps, and electric heat or combinations of many of these heating systems operating in sequence. As a start, I think the first step is to understand the basic wiring for a simple cooling circuit of an air conditioner. Then we can add in the various methods of activating the different heating systems. First, the technician must understand, that just like a light switch circuit, to activate a relay, power is supplied from a power source to a load. In the case of HVAC/R systems, the power source is a low-voltage transformer (usually a 24 VAC transformer) and the two wires supplying the power are labeled C (common) and R. The common or C wire need not be run out to the thermostat, however if the thermostat requires power, the C wire should be routed to the thermostat. Even if the current thermostat being used does not require external power it is an excellent idea to bring the C wire out to the thermostat in anticipation of a future installation of a thermostat that requires power. For systems that do not have access to the C wire, a battery in the thermostat compartment must be used. This is a poor substitute for a line source of power, since the thermostat will cease to function when the battery dies.

2 Now for the HVAC/R labeling conventions of other thermostat wires: The G wire completes the circuit from the R-leg of the power supply, back to the blower contactor coil. The coil then gets the 24 VAC from the common and G wires. Individual circuit for blower relay coil Auto 2

3 The Y wire completes the circuit from the R-leg of the power supply back to the Compressor/Condenser fan contactor coil. Individual circuit for compressor relay coil 3

4 The W wire, if used, completes the circuit from the R-leg of the power supply back to the heater contactor coil. Sometimes there is a W1, W2, etcetera, for several stages of heating. Individual circuit for heat relay coil 4

5 The O terminal, if used, and when the heat pump thermostat mode selector switch is set to cool, completes the circuit from the R-leg of the power supply back to the O wire. It is typically used to bring power to the reversing valve and is used for a heat pump with a reversing valve where the normal (unpowered) position is for heating. If you re using the O terminal you will NOT use the B terminal. Type H reversing valve (notice O is a circuit while B is not wired) 5

6 The B wire, if used, is closed when the heat pump thermostat mode selector switch is set to heat. It is typically used to bring power back to the reversing valve and is used for a heat pump with a reversing valve where the normal (unpowered) position is for cooling. If you re using the B terminal you will NOT use the O terminal. Type C reversing valve (notice B is a circuit while O is not wired) 6

7 The low-voltage 24 VAC transformer is typically located on the air condition system air handler. This transformer might also be located in the condensing unit, or anywhere else for that matter. Locating that transformer and identifying the C (common) and R wires is likely the first thing you need to do before you begin wiring your thermostat. Sometimes there are two low voltage transformers, one for the heating system and one for the cooling systems and the outputs of each transformer should not be connected. Having two transformers is very common if the heating system is a furnace while the cooling system is an A/C. When there is a transformer in the cooling system and a second transformer on the heating system then the R wires from each transformer must be kept separated and so they are labeled as Rc (for the R wire from cooling transformer) and Rh (for the R wire from heating transformer). As we mentioned above, whenever there is an R wire there will be a C wire. So if you have two R wires you will also have two C wires. Once again, even if the thermostat you re working with runs on a battery, it s still wise to have the C wire run out to the thermostat in case the equipment owner changes the thermostat out, however only a single common or C wire needs to be run to the thermostat, and it is usually the Cc wire, that is the common wire from the cooling transformer. The Rh and Ch should only be used to power relays or other components of the heating system, and the thermostat will typically only connect Rh to W (when the thermostat is calling for heating). Likewise, Rc is connected to G, Y, O, B when appropriate. This next part may be confusing at first but is If there is only one transformer, then wires labeled Rh and Rc are the same and are typically connected or jumpered together in the thermostat. Other times there is another transformer at a heating source so Rh and Rc will be different. One should be connected to the heating unit s transformer (Rh) and the other should be connected to the cooling unit s transformer (Rc). A visual representation of a two transformer circuit is located on the next page. 7

8 Two transformer basic thermostat circuit Some thermostats come pre-wired with Rh and Rc jumpered together and this jumper must be cut to create a individual Rh and Rc circuits for a two transformer thermostat circuit. Basic Wiring In the most basic form of control, the C or common terminal of the low voltage transformer is connected in parallel to all of the control relays.. The R terminal of the low-voltage transformer is connected through the thermostat to each control relay. The thermostat controls the operation of the heater, compressor and blower as shown in Figure 1. Figure 1 is a circuit diagram showing the simplest possible known thermostat control system for heating and cooling operation of an A/C and Furnace or A/C and electric heat system.. For this system, you will notice that G (air handler blower) and Y (compressor/condenser fan) are connected. Therefore, the compressor/condenser fan and the air handler blower should always turn on at the 8

9 same time. The W (heat) wire is on its own, so the air handler blower will NOT turn on when the heat is activated. In this case, a heater relay or some other control, such as a plenum temperature sensor, must activate the blower in heating mode. This separate control is not a part of the thermostat. The W heat wire control could also activate electric baseboard heat, where the blower is, of course, not operated. Figure 1. Basic Thermostat Circuit The following is an explanation of how Figure 1 s thermostat actually works. You don t need to know the following to make the thermostat work but if you learn the theory behind why the thermostat above is able to function then it will help you when you come across other more complicated thermostats. If you are new to thermostats or wiring diagrams you may need to read the following section carefully several times. Refer back to the diagram often and don t get ahead of yourself. If possible, share the section below with someone more experienced that can help explain how the thermostat above is capable of working. 9

10 Referring to Figure 1, the wire designated R continues the circuit from the transformer to the thermostat. The wire designated G, when connected to R by the thermostat (look in the area where it says cool, heat, and off ), continues the circuit from the R terminal of the transformer to the blower relay, completing the circuit and activating the blower relay and thereby operating the blower. That is when the thermostat connects R-G then the 24 volts from the transformer flows to the contactor coil via the 24 volts AC supplied to C and G. Likewise, the wire designated Y, when connected to R by the thermostat (see right next to where is says close on rise, the Y wire is connected to the G wire), continues the circuit from the R terminal of the transformer to the compressor relay, completing the circuit and activating the compressor relay and usually also the condenser (outdoor) fan. This is because the outdoor fan will always operate when the compressor is operating, therefore only a single contact is necessary. Refer to Figure 1, whenever the thermostat is set to cool the G and Y wires are both simultaneously connected to the R wire which completes all of their circuits. So when the system is set to cool the compressor/condenser fan (Y) and air handler blower (G) are both activated. The wire designated Wx, (where x can be 1 or 2, it would be 1 in the above figure) when connected to R by the thermostat, continues the circuit from the R terminal of the transformer to the electric heat heater relay, completing the circuit and activating the heater. In the case of heating, there can be several heating control circuits, sometimes designated W1, W2, etc., where the thermostat may activate one or more heaters depending on the difference between the desired temperature and the actual temperature (when in the heating mode). There are many known variations of the heating configuration where one heating circuit may activate a heat pump, a second may activate a furnace and a third activates an electric heating circuit. Note that in the simple thermostat of Figure 1, when the thermostat (set to the heating position) calls for heat, the W1 circuit is activated, but the blower is not activated because the G wire is not attached to the W wire like it is to the Y wire. In "Heating" mode, when a furnace is used for heating, the blower is not typically activated by the thermostat, but rather may be controlled by a plenum temperature sensor in the vicinity of the heat source. If electric baseboard heating is used, the blower need not be activated. Many newer replacement thermostats, allow a configuration set up where, if necessary, the G (blower) circuit can be activated when the system is calling for heat. This type of thermostat is commonly used for A/C systems with duct-mounted electric heat and the thermostat, typically has a jumper or software setting that will allow making of both the R-W circuit to activate the heat strip and the R-G circuit to activate the blower during heating operations. 10

11 For most heat pump and A/C systems with electric heat, typically only one transformer is used. However, as stated earlier, many furnace heating systems have a separate transformer to power the furnace heating circuit, so that a separate R circuit exists for the R to W switch, (where the Rc refers to the contact that closes Rc to G and Rc to Y during cooling, while the Rh to W1 contact is closed during heating). Once again, to provide the greatest flexibility, most thermostats have a separate circuit for Rc to G and Y and Rh to W, with a provision to jumper Rc and Rh together, to form the thermostat setup of Figure 1, namely a single R that can be connected to G, Y and W. If you have one transformer Rc and Rh will be jumped together, if the cooling and heat each have separate transformers Rc and Rh need to be separate circuits. Figure 2 and 3 display a thermostat that is similar in operation to the thermostat of Figure 1, but also has a provision (R to B or R to O, only one is typically used), to activate a reversing valve, for example, in the case of a heat pump. In Figure 2, power to O when cooling is selected is used to activate the reversing valve (use when normal unpowered state of the heat pump is heating) whereas in Figure 3 power to B when heating is selected is used to activate the reversing valve (use when normal unpowered state of the heat pump is cooling). 11

12 Figure 2. Thermostat wired to activate a reversing valve to activate cooling mode 12

13 Figure 3. Thermostat wired to activate reversing valve to activate heating mode Figure 2 and 3 display circuit diagrams of a common modern heat pump thermostat which do not use the W circuit to apply normal heat, instead both Y and G circuits are energized when either cooling or heating is needed, In Figure 2, the R-O circuit is used to energize the reversing valve when set to "COOL. In Figure 3 the same thermostat uses the R-B circuit to energize the reversing valve when set to "HEAT." While heat pumps use a reverse cycle to produce heating, they are almost always equipped with electric heat as a back-up emergency heat source. The R-W2 circuit in this thermostat is used to activate this emergency heating. Finally, on most thermostats, when the fan switch is placed in the ON position it will complete the R-G circuit without regard to the position of the System Selector Switch, which can be set to "COOL," "OFF," or "HEAT. 13

14 Wiring Routing The normal wiring of an air conditioning and heating thermostat uses a multiconductor thermostat wire. As a minimum R, G, Y and W are needed, since Connecting R to G activates the blower, R to Y activates the Compressor, and R to W activates the heat as we have seen, there are lots of variation on how the heat is activated. In addition, if a common C is supplied then 24 VAC is available at the thermostat (across R and C) to power the thermostat. If the thermostat requires power and a C wire is not available, then a battery in the thermostat must be provided to provide the power. Since batteries die at the worst times, and typically the thermostat open-circuits, which turns the system off, when the battery dies, this is a bad procedure. If the home is unoccupied for long periods, such as summer or winter homes, mold or freezing problems can develop, all caused by a dead battery in the thermostat. As a minimum, it is recommended to run at least 6 conductors (C, R, G, Y, W, and B or O) even in an AC installation, since a retrofit to a future heat pump system is still possible. Additional wires prove to be extremely useful when an installed wire fails and it is nearly impossible to run a new set of wires. Summary A typically thermostat will have a C terminal which along with the R wire provides 24 VAC to the thermostat for clock and other setback purposes. The G terminal is connected to the blower contactor coil, the Y to the compressor contactor coil, and the W terminal is used for heater activation. When W is used for emergency back up heat, it is typically labeled W2. Either the B terminal or O terminals are used for the heat pump reversing valve, while they can be used for any heating or cooling specific function.. A thermostat will make a R-B connection when it the System Selector is set to "HEAT" (as shown in Figure 3) and it will make the R-O terminal when the system is set to "COOL" as shown in Figure 2). Which circuit to use, namely the R-B or R-O depends on the heat pump reversing valve. If the reversing valve is normally closed in the cooling position, then it has to be powered to switch to heating mode, so the R-B circuit is used and the reversing solenoid is connected to C and B so that when the thermostat is calling for heat and completes the R-B circuit, then 24 VAC is supplied across C-B and the reversing valve is activated into heating mode. Likewise, if the reversing valve is normally closed in the heating position, then it has to be powered to switch to cooling mode, so the R-O circuit is used and the reversing solenoid is connected to C and O so that when the thermostat is calling for cooling and completes the R-O circuit, then 24 VAC is supplied across C-O and the reversing valve is activated into cooling mode. The B and O terminals can also be used to energize dampers in heating or cooling modes or control any other device that is heating or cooling mode specific, however in 14

15 actual practice these circuits are rarely used on thermostats that are not controlling a heat pump. With the rising popularity of heat pumps, as well as multiple heating sources, thermostats have been designed with greater flexibility when controlling the assorted heating methods. These newer thermostats are different from standard heatingcooling thermostats in that on heating the thermostat can be configured to make R-W and R-G, compared to a standard thermostat that makes only R-W when heating is being called. On most thermostats, there is also typically a jumper, or shut that can be cut, when the Rh-W circuit is powered by a heating transformer and the Rc-G is powered from a different transformer. With Rc coming from the cooling system transformer and Rh coming from the heating system transformer. Of course heat pumps only have one transformer. If these heat pump thermostats have a R-W circuit, it is typically labeled R-W2 (since the first stage of heat is obtained by the reversing valve position and operating the compressor(r-y) and blower (R-G) and the back-up heat is obtained by activating R- W2. Typically, there is no W1 terminal on this type of heat pump thermostat. Typically a thermostat for an AC system with electric heat coils in the air handler is configured to make both the R-G circuit at the same time it makes the R-W circuit, instead of relying on an extra set of contacts on the heating relay to activate the blower. As shown in Figure 1, for a standard heating-cooling thermostat there is no power to the Y circuit when the thermostat is set to either "OFF" or "HEAT." Similarly, if the fan switch is set to "AUTO" there is also no power to the G circuit when the thermostat is set to either "OFF" or "HEAT." There is, however, power to the G circuit if the fan switch is set to "ON," regardless of whether the thermostat is set to "COOL", "OFF" or "ON." See the images below for a visual representation of the various completed G circuits in a basic thermostat. 15

16 Individual circuit for blower relay coil Auto 16

17 Individual circuit for blower relay coil On For a typical thermostat, as shown in Figure 1, when the thermostat is set to "COOL" and the fan set to "AUTO" both the blower (G) circuit and the compressor (Y) circuit are activated simultaneously when the thermostat calls for cooling. When the thermostat is set for "HEAT" (and the fan set to "AUTO"), neither the blower (G) circuit nor the compressor (Y) circuit are activated, regardless of the thermostat setting. Alternatively for a heat pump thermostat, both the R-Y circuit and the R-G circuit are activated on a call for either cooling or heating as shown in Figures 2 or 3. This guide is by no means completely exhaustive of all thermostat configurations available to control an HVAC/R system. However, I hope that it serves as an in depth introduction to thermostat wiring and principles that a beginner can grow upon. 17

Installation Questions

Installation Questions Installation Questions How do I determine what type of heat I have? There may be several ways to determine what type of heat you have. First, if you can access the unit that is responsible for creating

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

ELECTRIC POSITION for electric heat, then confirm with Fan Test below. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The

More information

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead just as planned. Manual : 2100-360B Supersedes: 2100-360A File: Volume

More information

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace) UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system

More information

INSTALLATION AND OPERATION MANUAL

INSTALLATION AND OPERATION MANUAL RCS MODEL ZC4 4 ZONE HVAC INSTALLATION AND OPERATION MANUAL DCN: 141-0020-02 /0/03 INTRODUCTION The 4 Zone HVAC Controller series allows up to 4 standard electronic thermostats to independently control

More information

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps Operation and Maintenance Manual Model: 71028004 Applies to: Single Circuit Water-to-Water Twin Circuit Units Without DDC Controls MAMM WHSP

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

Heating and Cooling Basics Thermostat Control

Heating and Cooling Basics Thermostat Control Heating and Cooling Basics Thermostat Control UNI-LINE PRODUCT KNOWLEDGE 2012 Invensys. All Rights Reserved. The names, logos, and taglines identifying the products and services of Invensys are proprietary

More information

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work. Install Guide CT100 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the

More information

T-100-R Installation Guide

T-100-R Installation Guide T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

Variable Air Volume - VAV

Variable Air Volume - VAV Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:

More information

Install Guide CT101. Caution. Caution

Install Guide CT101. Caution. Caution Install Guide CT101 PG 1 Caution top cover Your thermostat is a precise instrument, handle it with care. Turn off electricity to the system before installing or servicing thermostat or any part of the

More information

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat Builder MODEL 1010 Series Non-Programmable Single Stage Heat/Cool Thermostat USER MANUAL Compatible with low voltage single stage gas, oil or electric heating or cooling systems, including single stage

More information

37-7498. Professional Contractor INSTALLATION GUIDE

37-7498. Professional Contractor INSTALLATION GUIDE 37-7498 Professional Contractor INSTALLATION GUIDE Wireless Setup Connect Exit Next Exit 3 EASY STEPS Installing Sensi thermostat isn t that different than installing a non Wi-Fi thermostat. 1. Install

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

HEAT HEAT COOL HEAT PUMP COOL

HEAT HEAT COOL HEAT PUMP COOL OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control

More information

Nest Learning Thermostat Pro installation & configuration guide

Nest Learning Thermostat Pro installation & configuration guide Nest Learning Thermostat Pro installation & configuration guide Need help? Help online: http://support.nest.com/certified Nest Certified Professional support: 1-855-VIP-NEST (1-855-847-6378) Hours: 5am-9pm

More information

C-Bus Application Messages & Behaviour Chapter 25 Air Conditioning

C-Bus Application Messages & Behaviour Chapter 25 Air Conditioning C-Bus Application Messages & Behaviour Chapter 25 Air Conditioning Document Number: CBUS-APP/25 Comments on this document should be addressed to: Engineering Manager Clipsal Integrated Systems PO Box 103

More information

REMOTE CONTROL MANUAL

REMOTE CONTROL MANUAL REMOTE CONTROL MANUAL ENGLISH CONTENT PRECAUTIONS...1-2 USING THE REMOTE CONTROL UNIT...3 OPERATION...4-9 Thank you for purchasing our Room Air Conditioner. Before using your air-conditioner, please read

More information

PSPA711a. LUXPRO PSPA711a INSTALLATION AND OPERATING INSTRUCTIONS. Mt. Laurel, New Jersey 08054, USA www.luxproproducts.com

PSPA711a. LUXPRO PSPA711a INSTALLATION AND OPERATING INSTRUCTIONS. Mt. Laurel, New Jersey 08054, USA www.luxproproducts.com PSPA711a LUXPRO PSPA711a INSTALLATION AND OPERATING INSTRUCTIONS 52070 1 COMPATIBILITY...................................... 2 2 FEATURES............................................ 2 3 ELECTRICAL RATINGS................................

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

1F72 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning

1F72 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning CONTENTS Installation Instructions for Heating & Air Conditioning 1F72 5/2 Day Programmable Heat Pump Thermostat Preparations... 1 Thermostat Details... 1 Removing Old Thermostat... 1-2 Mounting and Wiring...

More information

February 1, 2006. Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure

February 1, 2006. Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure February 1, 2006 Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure Overview - Several measurements of air source heat pump system performance are required

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

Zoning Reference Guide

Zoning Reference Guide Zoning Reference Guide Part No. RG-0508-001 Table of Contents Introduction 1 Braeburn Zone Systems: Comfort on Demand 1 What is a Zoning System? 2 The Braeburn Advantage 4 The Best Value in Zoning Today

More information

Install Guide 3M-50. Caution. Caution

Install Guide 3M-50. Caution. Caution PG 1 Install Guide 3M-50 aution Your thermostat is a precise instrument, handle it with care. Turn off electricity to the HVA system before installing or servicing thermostat or any part of the system.

More information

Lesson 36 Selection Of Air Conditioning Systems

Lesson 36 Selection Of Air Conditioning Systems Lesson 36 Selection Of Air Conditioning Systems Version 1 ME, IIT Kharagpur 1 The specific objectives of this chapter are to: 1. Introduction to thermal distribution systems and their functions (Section

More information

Electronically Controlled Clutchless or Variable Drive Compressors

Electronically Controlled Clutchless or Variable Drive Compressors Electronically Controlled Clutchless or Variable Drive Compressors On many new air conditioning systems, such as Lexus, Cadillac, Chrysler, and others, a new type of compressor has been fitted. There are

More information

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment 5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

Single Zone LCD Thermostat Operating Instructions

Single Zone LCD Thermostat Operating Instructions Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip

More information

FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE

FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE Form 2B, Page 1 FLORIDA STATE COLLEGE AT JACKSONVILLE NON-COLLEGE CREDIT COURSE OUTLINE COURSE NUMBER: ACR 0100 COURSE TITLE: PREREQUISITE(S): COREQUISITE(S): Basic Electricity and Schematics None None

More information

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee 37091 Phone (931) 359-6211 1-800-251-8990 www.doleref.com

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee 37091 Phone (931) 359-6211 1-800-251-8990 www.doleref.com DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee 37091 Phone (931) 359-6211 1-800-251-8990 www.doleref.com SEQUENTIAL DEFROST SERVICE MANUAL June 2002 1 SEQUENTIAL DEFROST Table of Contents

More information

1F82-0261 5/1/1 Day Programmable. 1F82-0261 Thermostat Thermostat Configuration Options Heat Pump. Maximum Stages Heat/Cool 2/1

1F82-0261 5/1/1 Day Programmable. 1F82-0261 Thermostat Thermostat Configuration Options Heat Pump. Maximum Stages Heat/Cool 2/1 Blue 2 Heat Pump Thermostat Heat Pump Installation and Operating Instructions Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING

More information

DIABLO VALLEY COLLEGE CATALOG 2015-2016

DIABLO VALLEY COLLEGE CATALOG 2015-2016 HEATING, VENTILATION, AIR CONDITIONING, REFRIGERATION - HVACR Tish Young, Dean Physical Sciences and Engineering Division Physical Sciences Building, Room 263 Possible career opportunities Upon successful

More information

MicroTech III Unit Controller for Water Source Heat Pump Units

MicroTech III Unit Controller for Water Source Heat Pump Units Operation & Maintenance Data OM 931-1 Group: WSHP Part Number: 910100893 Date: April 2009 MicroTech III Unit Controller for Water Source Heat Pump Units 2009 McQuay International Table of Contents Introduction...

More information

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

Air Conditioner Stalling Unit Level Solutions Test Report

Air Conditioner Stalling Unit Level Solutions Test Report By: TDBU Engineering Advancement Power Systems Technologies Richard Bravo Robert Yinger Loic Gaillac The preparation of this white paper was conducted with support from the California Energy Commission

More information

CT3200 Programmable Thermostat

CT3200 Programmable Thermostat CT3200 Programmable Thermostat Welcome to the world of comfort and energy savings with your new Honeywell Programmable Thermostat. Your new thermostat will automatically control the temperature in your

More information

RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump

RESEARCH HIGHLIGHT. Performance Assessment of a Cold-Climate Air Source Heat Pump RESEARCH HIGHLIGHT December 2014 Technical Series 14-102 Performance Assessment of a Cold-Climate Air Source Heat Pump INTRODUCTION Most Canadians are familiar with air source heat pump technology in the

More information

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW Operation & Maintenance Manual OM 931-6 Group: WSHP Part Number: 910157590 Date: September 2014 MicroTech III Unit Controller for Water Source Heat Pump Units Used with Enfinity Models CCH/CCW, VFC/VFW,

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount

More information

INSTALLER'S GUIDE. Supplementary Electric Heaters 18-GJ08D1-1. Table of Contents

INSTALLER'S GUIDE. Supplementary Electric Heaters 18-GJ08D1-1. Table of Contents INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: BAYEAAC051A BAYEAAC05LG1A BAYEAAC081A BAYEAAC08LG1A BAYEAAC101A BAYEAAC10LG1A BAYEABC151A BAYEABC201A

More information

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

MicroTech III Unit Controller for Water Source Heat Pump Units

MicroTech III Unit Controller for Water Source Heat Pump Units Operation & Maintenance Data OM 931-3 Group: WSHP Part Number: 669479403 Date: May 2012 MicroTech III Unit Controller for Water Source Heat Pump Units 2012 McQuay International 800.432.1342 www.daikinmcquay.com

More information

Basic Technology Series

Basic Technology Series Basic Technology Series Fundamentals of Car Air Conditioning 2007 Air Conditioning #003 The Rear Cooler Construction Fan Fan Filter Figure A : Trunk Figure B : Overhead Dual Air-Conditioner In This Issue

More information

1F82-261 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

1F82-261 Programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION ELECTRICAL DATA Electrical Rating: 20 to

More information

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,

More information

T5000 T000 LCD Digital Fan Coil Thermostat

T5000 T000 LCD Digital Fan Coil Thermostat T5000 T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostat T000 LCD Digital Fan Coil Thermostats are designed to control heating, cooling, or year round air conditioning unit in Commercial,

More information

6. Diagnostics for A/C System Malfunction

6. Diagnostics for A/C System Malfunction 6. A: A/C OR SELF-DIAGNOSIS SYSTEMS DO NOT OPERATE TROUBLE SYMPTOM: Set temperature is not indicated on the display, switch LEDs are faulty or switches do not operate. Self-diagnosis system does not operate.

More information

INSTALLER S & OWNER S MANUAL

INSTALLER S & OWNER S MANUAL INSTALLER S & OWNER S MANUAL HVAC INSTALLER: PLEASE LEAVE MANUAL FOR HOMEOWNER DEH 3000 DEH 3000 Part No. 4028539 Dehumidifier & Ventilation System Controller P.O. Box 8680 Madison, WI 53708 TOLL-FREE

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

www.inspection-for-industry.com

www.inspection-for-industry.com Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.

More information

User s Information/Installation Instructions

User s Information/Installation Instructions Outdoor Heat Pump User s Information/Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity and effi ciency in accordance with A.R.I.

More information

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function Specifications Supply Voltage 240VAC @ 0.07Amps or 24VAC @ 0.380Amps Relays 240V @ 12A max (resistive) / Comp1,2,3, Aux Ht, Rv O/B) Fuses (Equipment) 15 Amps Maximum 3AG Control Range Minus 10 to 50C Control

More information

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7 THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

HVAC Claims: Repair vs. Replacement

HVAC Claims: Repair vs. Replacement HVAC Claims: Repair vs. Replacement Curtis M. VanNess Field Operations Manager Outline Brief history of HVAC How do HVAC systems work? Types of systems and equipment Causes of failure Repair vs. Replace

More information

WHITE-RODGERS COMFORT-SET 90 SERIES

WHITE-RODGERS COMFORT-SET 90 SERIES INSTALLATI DESCRIPTI WHITE-RODGERS COMFORT-SET 90 SERIES MULTI-STAGE INSTALLATI/CFIGURATI This White-Rodgers Automatic Setback Digital Thermostat uses microcomputer technology to provide precise time and

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

Mt. Carmel Area School District Energy Conservation Policy Adopted 6/19/06

Mt. Carmel Area School District Energy Conservation Policy Adopted 6/19/06 Mt. Carmel Area School District Energy Conservation Policy Adopted 6/19/06 These guidelines supersede all previous instructions. It is crucial that these energy guidelines be observed in the operation

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

Ceiling Mount Air Handler Manual

Ceiling Mount Air Handler Manual www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

AIR CONDITIONER & HEAT PUMP SERVICE MANUAL

AIR CONDITIONER & HEAT PUMP SERVICE MANUAL AIR CONDITIONER & HEAT PUMP SERVICE MANUAL AL This Service Manual is the result of the dedication of The Dometic Corporation and its engineers to providing service people the necessary instructions for

More information

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual

ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual QUALITY STEAM SPECIALTIES SINCE ABC-1000 Automatic Boiler Level Controller Operation and Installation Manual Section: C500 Bulletin: C500.40 Date: 06-26-01 Supersedes: New PRODUCT DESCRIPTION: The Clark-Reliance

More information

Low Profile Unit Cooler

Low Profile Unit Cooler Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost

More information

Air Conditioning System

Air Conditioning System Air Conditioning System 1 Chonan Technical Service Training Center Chonan Technical Service Training Center 2 Objectives To understand the components of air conditioning system. To understand the control

More information

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions

RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create

More information

Homeowners Air Conditioning Troubleshoot Checklist

Homeowners Air Conditioning Troubleshoot Checklist Homeowners Air Conditioning Troubleshoot Checklist Before calling for repairs for your central air conditioner here are a few things you can check yourself (this check list could save the cost of an unnecessary

More information

ELECTRICAL WIRING (R.H. DRIVE VEHICLES)

ELECTRICAL WIRING (R.H. DRIVE VEHICLES) C-1 ELECTRICAL WIRING (R.H. DRIVE VEHICLES) CONTENTS GENERAL.......................... 3 WIRING HARNESS CONFIGURATION DIAGRAMS......................... 4 ENGINE COMPARTMENT................ 4 DASH PANEL...........................

More information

Impact of Control System Technologies on Industrial Energy Savings

Impact of Control System Technologies on Industrial Energy Savings Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110

More information

Technical Support Bulletin Nr. 20 Special AC Functions

Technical Support Bulletin Nr. 20 Special AC Functions Technical Support Bulletin Nr. 20 Special AC Functions Summary! Introduction! Hot Start Control! Adaptive Control! Defrost Start Temperature Compensation Control! Anti-Sticking Control! Water Free Cooling

More information

Heating and Hot Water Services Controls General Technical Specification

Heating and Hot Water Services Controls General Technical Specification Construction Services Heating and Hot Water Services Controls General Technical Specification Version 1.0 Environment Heating and Hot Water Services Controls General Technical Specification Contents 1.

More information

Electrical Systems - IQAN Digital Control System. IQAN Control System Components... 5.1.3

Electrical Systems - IQAN Digital Control System. IQAN Control System Components... 5.1.3 Section 5.1 Electrical Systems - IQAN Digital Control System IQAN Control System Components........................... 5.1.3 IQAN Operational Description: At Machine Startup.....................................

More information

City School District of Albany. Energy Management Plan

City School District of Albany. Energy Management Plan City School District of Albany Energy Management Plan June 2013 District Energy Plan Objective The district shall use energy resources in a safe and efficient manner, with an ongoing focus on identifying

More information

Heating, cooling and irrigation system for a house. Control with two controllers TS-55T + 2 depending on the seasons. option 1 Functional scheme

Heating, cooling and irrigation system for a house. Control with two controllers TS-55T + 2 depending on the seasons. option 1 Functional scheme Heating, cooling and irrigation system for a house. Control with two controllers TS-T + depending on the seasons. option R, R, R, R4, R, R6, R7 - Heat pump. Sx - nsors. F - Thermal cutoff. B - Electric

More information

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner

More information

LOBOY 16 AIR CONDITIONERS

LOBOY 16 AIR CONDITIONERS INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com

More information

SECTION 412-00 Climate Control System General Information and Diagnostics

SECTION 412-00 Climate Control System General Information and Diagnostics 412-00-i Climate Control System General Information and Diagnostics 412-00-i SECTION 412-00 Climate Control System General Information and Diagnostics CONTENTS PAGE DIAGNOSIS AND TESTING Climate Control

More information

Installation Instructions

Installation Instructions Installation Instructions Model TSTATG2111 Use with most systems: 2-Heat, 1-ool 1- Day Prog ram m ab l e Digital Thermostat u p t o 2 - H e a t & 1 - o o l ontrol up to 2 Heat & 1 ool Stages Backlit Display

More information

Aerona Air Source Heat Pumps

Aerona Air Source Heat Pumps ADDENDUM to INSTALLATION INSTRUCTIONS for Aerona Air Source Heat Pumps DOC.87-05/05 Rev.04 March 2013 ATTENTION INSTALLERS - UPDATED INFORMATION! Your Grant Aerona Air Source Heat Pump has a number of

More information

Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units.

Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units. R Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL for SPLIT SYSTEM Bus Air Conditioning Units T--326 Rev -- OPERATOR S MANUAL BUS AIR CONDITIONING UNITS GEN IV & GEN V CONTENTS

More information

Emergency Heat slide switch on the panel or an external switch. Do not use the panel switch or the external switch if Dip switch #4 is set to HP.

Emergency Heat slide switch on the panel or an external switch. Do not use the panel switch or the external switch if Dip switch #4 is set to HP. Installation Instructions The ED4 is a 4-zone panel that can control gas/ electric, hydronic, electric and both conventional and dual fuel heat pumps with multi-stage heating and cooling. Low cost heat-cool

More information

Integrated Metering Systems, Inc.

Integrated Metering Systems, Inc. Integrated Metering Systems, Inc. EM Pro Energy Allocation System Product Guide Technical Specifications PN: 114-000X Revision 0.7 List of Figures... 2 List of Tables... 2 1. Product Description... 3 1.1

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility

More information

Infinity/ Evolution Troubleshooting Guide User Interface Software Ver. -03, -05, -06, -08, -10 and -12. Table of Contents

Infinity/ Evolution Troubleshooting Guide User Interface Software Ver. -03, -05, -06, -08, -10 and -12. Table of Contents Software Revs 3,5,6,8, 10, 12 Infinity /Evolution Troubleshooting (Rev. 2) 10/12/2006 Infinity/ Evolution Troubleshooting Guide User Interface Software Ver. -03, -05, -06, -08, -10 and -12 Table of Contents

More information

OPERATING INSTRUCTIONS (TRANSLATION OF THE ORIGINAL) SUPPLEMENTARY OPERATING INSTRUCTIONS FOR YOUR AIR CURTAIN SYSTEM. Serial number: Year: --- Page 1

OPERATING INSTRUCTIONS (TRANSLATION OF THE ORIGINAL) SUPPLEMENTARY OPERATING INSTRUCTIONS FOR YOUR AIR CURTAIN SYSTEM. Serial number: Year: --- Page 1 --- OPERATING INSTRUCTIONS (TRANSLATION OF THE ORIGINAL) SUPPLEMENTARY OPERATING INSTRUCTIONS FOR YOUR AIR CURTAIN SYSTEM Serial number: Year: Please quote this number when contacting customer service!

More information

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING

HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING HOW TO CORRECTLY CONNECT DEEP CYCLE BATTERIES AND CHOOSE THE RIGHT CABLE SIZING There are several ways to wire multiple batteries to achieve the correct battery voltage or capacity for a particular DC

More information