1 CC8111 Series Electronic Controller Proportional and Single Stage Relay General Instructions DEVICE INFORMATION The CC8111 Controller is a proportional controller which directly accepts either a 1000 ohm sensor input(s), a 1 to 15 Vdc control signal, or a 135 ohm slidewire input and produces a proportional voltage output signal which operates a relay giving two position output control. This device consists of two temperature bridges, a solid state control amplifier, a comparator amplifier, and a relay output stage. The CP8111 is used in systems where solid state temperature sensing is desired to control electrically actuated devices SPECIFICATIONS 1. Controlling inputs Designated as input A and input B. a. Temperature One or two 1000 Ohm resistance type temperature sensors (TS8000 Series). b. Slidewire transducer 135 Ohms. Requires two resistors and connects to input A only. See input wiring diagrams No. 5 for further details. c. Voltage signal 1 to 15 Vdc. Requires removal of jumper between OP1 and IV1 terminals. Signal connected between IV1 (+) and COM () terminals. 2. Outputs a. Relay SPDT with adjustable dropout and selectable differential of 0.5, 1, 2 and 4 volts. Table1 Contact Rating 24 Vac 120 Vac 240 Vac Amps (continuous) Amps (inrush) Pilot duty sealed (VA) Pilot duty inrush (VA) b. Voltage signal 2 to 15V with a 10 ma. capacity. Output terminals OP1 (+) to COM (). c Vdc with 35 ma. capacity. Supply can be used for powering other TAC System 8000 controllers or adaptors. d ±.5 Vdc with 4 ma. capacity. Supply can be used for powering TAC System 8000 remote setpoint adjustors (AT8100 Series) and auxiliary bridges (CN8101, TS8601). 3. Supply inputs. Requires 24, 120 or 240 Vac 50/60 Hertz depending on models selected, 4 V.A. 4. External Screw Terminal Nomenclature Figure1 L1, L2 Supply voltage 50/60 Hz. GND Chassis ground NC1 Normally closed relay contact C1 Relay common NO1 Normally open relay contact Vdc power supply IV1 1 to 15 Vdc input (+) OP1 2 to 15 Vdc output (+) Vdc power supply ISA Input A AB1 Input, auxiliary bridges or setpoints ISB Input B COM System common () Printed in U.S.A. 9/08 Copyright 2008 TAC All Rights Reserved. F171925

2 Table2 Part Number Selection and Function Chart. Adjustable Functions Pin Selectable Functions Part Number Power Req. (50/60 Hz) Setpoint A Setpoint B Diff. Range Relay Dropout Throttling Range Authority Ratio Relay Diff. CC CC CC to 95 F 5 to 35 C 41 to 95 F 5 to 35 C 1 to 54 F Std. By Added Res F 2 to 12 Vdc (IV1 to Com) 3, 6 or 9 F 1.6, 3.4 or 5 C Aux Vdc (IV1 to Com) Units dual marked in C and F 5. Dimensions a. Direct reset: A temperature decrease on input B resets input A setpoint downward. b. reset: A temperature decrease on input B resets input A setpoint upward. ADJUSTMENTS & JUMPERS See Figures 5 and 6. INSTALLATION DEFINITIONS Figure2 1. Mode of operation Either direct acting or reverse acting. a. Direct acting (D.A.) means that an increase in temperature at the sensor(s) cause the CC8111 voltage output (OP1) to increase. b. acting (R.A.) means that an increase in temperature at the sensor(s) causes the CC8111 voltage output (OP1) to decrease. 2. Reset control action The direction of reset determines whether input A setpoint is reset upward or downward on a temperature decrease at input B. 1. Mounting The CC8111 can be mounted in any position on any surface free from severe vibration or shock. Avoid locations where excessive moisture or corrosive fumes are present. The unit is provided with a 71/2 inch piece of 37/8 inch wide mounting track. Mounting hardware required (not provided) is two #8 screws. Ambient Limits: 40 to 140 F (4 to 60 C). 2. Wiring Procedure a. Codes: Make all electrical connections in accordance with job wiring diagrams and in compliance with national and local electrical codes. b. Sensors: For sensor wiring, use No. 18 gauge twisted pair cable (6 turns per foot or equivalent) up to 200 feet. On runs over 200 feet, recalibrate the system or use larger diameter wire. Caution: Shielded cable (Belden No or equivalent) must be used when it is necessary to install the sensor leads in the same conduit with power wiring, or when it is known that high RFI/EMI generating devices are near. Ground the shield at the controller only on the COM () terminal. Figure3 Location Chart. 2 Copyright 2008 TAC All Rights Reserved F171925

3 Table3 Controller Setup and Definition Chart. Control/Sensor Sensor A or Sensor B Bridge A Bridge B Setpoint A/B (SPA) (SPB) Ratio Authority (ISB only) Throttling Range (T.R.) Relay Differential Jumper J1 J2 J3 J4 J5 Range/Output Function Jumper or Terminal Connection ISA, ISB to 6.2 ISA, ISB to COM COM 6.2 COM C 4195 F.5 to to to to 1 15 Table 6 Aux. 3 F (1.6 C) A 6 F (3.4 C) B 9 F (5 C) A with AB shorted.5 Volt.5 1 Volt 1 2 Volts 2 4 Volts 4 Factory Set COM F CAL Relay Dropout 2 to 12 Vdc 6V 1:1 A 1 Changes Res. when temp. changes Resistance voltage divider Input A/B temperature adjustment Amount of temp. change of the B bridge required to reset the A bridge 1 F. Sets amplifier volts per deg. change at ISA input Volts change between pullin and dropout Voltage where the relay drops out Definition/Function Balco Res. Pos. Temp. Coeff. Provides a voltage output relationship to sensor resistance Sensor A/B temp. at which OP1 to COM is 7.5 ±.5 Vdc Degrees temp. change at ISAinput to produce a 3 Vdc change OP1 to COM C1 makes to NC1 OPERATION Refer to Figure 4). The CC8111 Controller consists of two temperature sensing bridges with setpoint, one proportional voltage control amplifier, one voltage comparator amplifier with relay output and two power supplies. Input A and B sensors Each requires a 1000 Ohm, at 21 C (70 F), resistance type (Balco wire) temperature sensor. The sensor increases in resistance with an increase in temperature (3.96 Ohms/ C or 2.2 Ohm/ F). These changes are detected by input A and input B bridges. Input A and B bridges Each bridge input accepts the sensor resistance signal. The bridge converts the resistance signal change into a dc millivolt signal change. The output from input A bridge is fed to the proportional control voltage amplifier. The output from input B bridge is fed to the ratio selection network. Each bridge can be connected for either direct or reverse acting bridge output. This is accomplished on input A bridge by connecting J1 jumper (red/blue) to the pin marked COM for direct acting or to the pin marked +6.2 for reverse acting. Input B bridge jumper J2 (white/blue) is connected to the pin marked COM for direct acting or the pin marked +6.2 for reverse acting. Input A and B bridges each have temperature setpoint adjustments. Ratio selection network Ratio selection networks allow selection of the desired input B bridge gain in order to accomplish resetting type control systems. The output of the ratio selection networks is fed to the proportional voltage control amplifier. Proportional voltage control amplifier The control amplifier sums and amplifies the millivolts output signals from input A and B bridges. The control amplifier output is a proportional 2 to 15 Vdc signal which is fed to the voltage comparator amplifier. The amplifier uses overall negative feedback as a means of gain adjustment. The gain adjustment becomes the throttling range adjustment of the CC8111. Comparator amplifier This comparator receives the variable voltage from the control amplifier and compares it to the relay drop out and differential voltage settings. As these points are exceeded, the comparator changes state to operate the relay for two position output control action. CALIBRATION The CC8111 Controller normally requires no field calibration. The unit is factory calibrated for 7.5 ±.5 Vdc output between OP1 and COM, when input A and B sensors are at 21 C (70 F) temperature (1000 Ohms resistance) and their respective setpoints set for 21 C (70 F). The relay dropout voltage is factory set for 6.0 Vdc with a 1 volt differential selected. A throttling range of 3 F and a ratio of 1:1 have been selected. The input bridges are connected for (A) direct and F Copyright 2008 TAC All Rights Reserved 3

4 (B) reverse acting outputs. If field calibration becomes necessary or a calibration check is desired, proceed as follows: Caution: Line voltage is present on terminals L 1 and L 2. Figure4 Controller and System Block Diagram. 1. Disconnect sensor to input A terminals. Replace input A sensor with a 1000 Ohm ±.1% resistor (SYZE12987 test kit). Input A sensor will be connected to the CC8111 as follows: a. Between ISA and +6.2 terminals for direct acting controller output. b. Between ISA and COM terminals for reverse acting controller output. 2. Disconnect sensor to input B terminals. Replace input B sensor with a 1000 Ohm ±.1% resistor (SYZE12987 test kit). Input B sensor will be connected to the CC8111 as follows: a. Between ISB and +6.2 terminals for direct acting controller output. b. Between ISB and COM terminals for reverse acting controller output. 3. Remove cover from CC8111. Disconnect and tape the J3 jumper (Blue) on the CC Disconnect all input leads for the AB1 terminal on CC Connect a 20,000 Ohm per volt VOM between OP1 (+) and COM () terminals. Use a 15 to 20 Vdc scale range. 6. Rotate setpoint A (SPA) to the black dot by 68 F. The VOM should read 7.5 ±.5 Vdc. If not, rotate the SPA shaft until 7.5 ±.5 Vdc reading is obtained. Hold the shaft of the SPA firmly and then rotate the pointer in a CCW direction until the pointer is on the black dot by 68 F on the dial scale. 7. Connect the J3 jumper (blue) to the 1:1 ratio pin. 8. Repeat Step 6 above but now use setpoint B (SPB) adjustment. 9. Change SPA until VOM reads 6.0 ±.3 Vdc. The relay should have dropped out. If not, rotate stage 1 pot until relay dropout occurs. 10. The CC8111 is now calibrated. 11. Replace all sensors and the cover to the CC8111 and remove the meter. CHECKOUT 1. Check nameplate for correct supply voltage and measure with a VOM between L 1 and L 2 terminals on the controller. If the supply voltage is not present, check the power source for problems. 2. Check the 20 (1.5, +1) Vdc supply by measuring with a VOM between the +20 (+) and COM () terminals. If the 20 Vdc is not present or is out of tolerance, then: a. Check to see if the 20 Vdc supply is overloaded (35 ma. or greater). b. External device shorting the 20 Vdc supply. c. If neither A nor B above, consider the controller as defective and replace. 3. Check the +6.2 ±.5 Vdc supply by measuring with a VOM between the +6.2 (+) and COM () terminals. If the +6.2 Vdc is not present or is out of tolerance then: a. Check to see if the 6.2 Vdc supply is overloaded (7 ma. or greater). b. External devices shorting the 6.2 Vdc supply. 4 Copyright 2008 TAC All Rights Reserved F171925

5 c. If neither A nor B above, consider the controller as defective and replace. 4. To check output operation, proceed as follows: For input A: Pull jumper J3 and tape. a. If the CC8111 has been connected for direct acting output operation, short the +6.2 and ISA terminals together. The voltage as measured with a VOM between OP1 (+) and COM () terminals should be 2.5 Vdc or less. b. If the CC8111 has been connected for reverse acting output operation, short the ISA and COM terminals together. The voltage as measured with a VOM between OP1 (+) and COM () terminals should be 15 Vdc or greater. c. Disconnect short across ISA and +6.2 or COM. For input B: Pull jumper J1 and tape. Remove sensor A. a. Repeat A, B and C above, except substitute ISB in the place of ISA. 5. Reconnect jumpers and sensors and the system is ready for operation. APPLICATIONS The units are shipped with input (A) direct and (B) reverse acting connections, throttling range (TR) at 3 F, ratio 1:1 and relay differential set to 1 volt. Other bridge connections will require recalibration. Single Input The controller may be used for a single input on either input A or B. The bridge action, sensor connections and internal connections are shown below. Table4 Input A B Dual Input Dual Input. Bridge and Input Action Internal Connections J1 to COM, J2 disconnect and tape J1 to +6.2, J2 disconnect and tape J1 disconnect and tape, J2 to COM, J3 on 1:1 ratio pin J1 disconnect and tape, J2 to +6.2, J3 on 1:1 ratio pin Sensor Connection ISA and +6.2 ISA and COM ISB and +6.2 ISB and COM The controller can be used as a control with reset action by using both A and B inputs. Determine the mode of operation of input A control, select the ratio or authority of input B and determine the reset control action. Set up the controller per Table 5. Table5 Input A Action Direct Sensor A Between +6.2 and ISA On dual input applications, J3 is connected to desired ratio pin. For additional ratios, connect jumper J3 to AUX pin and add additional resistors as shown below (See Figure 3 for location of pins and jumpers): Table6 Differential Inputs J1 to Pin COM ISA and COM +6.2 Reset Action of Input B J2 to Pin Sensor B Between Direct Reset +6.2 ISBCOM Reset COM ISB+6.2 Direct Reset COM ISB+6.2 Reset +6.2 ISBCOM Ratio Aux. Resistor Value (Connect between Aux. Pins) 2.5:1 29.4K, ±1%, metal film 5:1 57.6K, ±1%, metal film 10:1 115K, ±1%, metal film 20:1 221K, ±1%, metal film The controller can be used to respond to the difference between inputs A and B. Use sensor on ISA in the higher temperature media. Set differential to be maintained on SPA and SPB using SPA minus SPB as the selected differential number. Set ratio to 1:1. Table7 Input Sensor Connects Jumper Connection Relay Energizes A ISA6.2 J1 to COM Inc. Temp. A B ISBCOM J2 to 6.2 Dec. Temp. B The CC8111 differential range can be extended by setting SPA to the black dot by 68 F and placing the resistor selected from the table below between 6.2 and AB1 terminals. This will fix SPA to the indicated degrees in the table. The differential will be this fixed value minus the setting of SPB. Table8 Tank Differential Temperature Control. Setpoint A Degrees F Resistor ± 5% 1/4 Watt K K K K K K K F Copyright 2008 TAC All Rights Reserved 5

6 Figure5 Discharge Temperature Control with Outdoor Air Reset. Note: Connect J2 jumper to COM and refer to Dual Input Setup procedure. Figure6 Tank Differential Temperature Control. INPUT WIRING DIAGRAMS 1. Temperature Sensor(s) Input (Standard). Direct acting = DA, = RA. Room Sensor With Setpoint. Input A (J1) Input B (J2) Terminal DA RA DA RA COM 6.2 COM 8 ISA ISA ISB ISB Setpoint A adjusted for 21 C or 70 F Setpoint B adjusted for 21 C or 70 F Sensors Without Setpoint. Input A (J1) Input B (J2) Terminal DA RA DA RA COM 6.2 COM Blk 8 ISA ISA ISB ISB Blk 2. Remote Setpoints. Used with direct acting or reverse acting sensor inputs. Input A Input B Wire DA RA DA RA Red 6.2 COM 6.2 COM Yel AB1 AB1 AB1 AB1 Blue COM 6.2 COM Copyright 2008 TAC All Rights Reserved F171925

7 Note: Adjust SPA and SPB adjustments in CC8111 for 21 C or 70 F. Ratio select set for 1:1. 3. Night depression and/or morning warmup. Wire Direct Red 6.2 COM Yel AB1 AB1 Note: Adjust SPA in CC8111 for 21 C (70 ). Disconnect J3 jumper and tape end. Do not use TR greater than 3 F on CC Solar compensation using TS8531 sensor and CN8101 auxiliary bridge. Blue COM Temperature indication and control. TS8531 Sensor Leads Orange ISA ISE Orange ISB ISF Black ISE ISA Black ISF ISB Input A Input B Wire DA RA DA RA X 6.2 ISA 6.2 ISB Y ISA COM ISB COM J1 to COM J1 to 6.2 J2 to COM J2 to 6.2 Note: For temperature indication and control on input B, OP1 of the TSP is connected by a resistor, selected from the table below, to AB1 of the CC8111. Connect CC8111 jumper J3 as shown in the table for the ratio selected. Note: No calibration of CN8101 required. CN8101 Ratio Setting Degrees Reset (No Sun to Full Sun).5:1 70 F 1:1 35 5:1 7 10: : Ratio R Value Jumper J3 Connects To 1:1 None 1:1 ratio pin 5:1 45.3K, ± 1%, M/F Aux. ratio pin. 57.6K, ± 1% between aux. pins. 10:1 102K, ±1%, M/F Aux. ratio pin. 115K, ±1% between aux. pins. 15:1 158K, ±1%, M/F 15:1 ratio pin. 20:1 215K, ±1%, M/F Aux. ratio pin. 221K, ±1% between aux. pins. CC8111 Input A Action Solar Compensation Connected for: 7. AD8501 Automatic Reset Adaptor. Reset Action Increased Sun Load Resets Setpoint A: Down Up Up Down Ohm slidewire Input A only. F Copyright 2008 TAC All Rights Reserved 7

8 Note: 1. Remove jumper between OP1 and IV1 on CC Can be used with either D.A. or R.A. 9. Humidity indication and control reverse acting CC8111 output only. 8. Humidity control only reverse acting CC8111 output only. Note: 1. SPA adjustment becomes system calibration adjustment only. 2. Disconnect J2 jumper (wht/blu) and tape end. Note: 1. J1 jumper (red/blu) must be connected to pin marked Disconnect J2 jumper (wht/blu) and tape end. 3. SPA adjustment can be used for setting humidity control point. 10. Power Monitor Control Override. Note: Remove jumper between OP1 and IV1 terminals of CC8111. Power an isolation relay through the power monitor output contacts and wire the isolated contacts as shown below. Copyright 2008, TAC All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. F TAC 1354 Clifford Avenue P.O. Box 2940 Loves Park, IL

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE

Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE Service Information Calibration & Adjustments CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS Part Number DYN1-10752-000-0-12/24 DYN1-10752-001-0-12/24* DYN1-10753-000-0-12/24

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed. FANs 268.1, 1628.3 Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and

More information

POWERS CONTROL RC 195 Single Input Receiver-Controller

POWERS CONTROL RC 195 Single Input Receiver-Controller Document No. 155-119P25 RC 195-4 POWERS CONTROL RC 195 Single Input Receiver-Controller Description The RC 195 Single lnput Receiver-Controller is a pneumatic instrument which receives one pneumatic input,

More information

T7079A,B Solid State Remote Temperature Controllers

T7079A,B Solid State Remote Temperature Controllers T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature

More information

Part I - Installation

Part I - Installation 400 Series Pressure and Differential Pressure Switches Types: H400, H402, H403, H400K, H402K, J400, J402, J403, J400K, J402K UNITED ELECTRIC CONTROLS Installation and Maintenance Instructions Please read

More information

Model 201 Wiegand Touchpad Reader Installation Guide

Model 201 Wiegand Touchpad Reader Installation Guide Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without

More information

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB6444-02 TABLE OF CONTENTS DESCRIPTION 2 MOUNTING INSTRUCTIONS 2 HOW TO CABLE THE IPX 2/3 POWER SUPPLY INSTALLATION 3 OPERATION 3 CARE

More information

System 350 A350E Electronic Cooling Control

System 350 A350E Electronic Cooling Control FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0899 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw

More information

PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller

PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller BLZPTS-1 NOVEMBER 19, 2013 TS350 TS752 BLPS PRESSURE AND TEMPERATURE SENSORS for use with the BURNERLOGIX Burner Management System and PPC4000 Series Fuel/Air Ratio Controller DESCRIPTION The BLPS, TS350

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

Solid State Timers Type F

Solid State Timers Type F Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application

More information

Digital Pressure Measuring Instrument MDR480

Digital Pressure Measuring Instrument MDR480 Description The digital panel instrument MDR480 is designed to measure, display, and monitor pressures in industrial applications. The instrument is panel mounted with a front frame dimension of 96 mm

More information

Operating Instructions

Operating Instructions VMD202 Vehicle Motion Detector Operating Instructions CAUTIONS AND WARNINGS Never use the VMD202 as a safety reversing or presence detection system. The VMD202 requires that a vehicle be moving for detection.

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual

Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual Uni-Valve A /S VENTILER & INSTRUMENTER Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com UNI-EL Electric actuator Installation and operating manual Remote position

More information

Model EC5111 Speed Controller Isochronous / Droop

Model EC5111 Speed Controller Isochronous / Droop R Conforms to EC Directive on Electromagnetic Compatibility ADVANT ANTAGE SERIES Quality System Certification Model EC5111 Speed Controller Isochronous / Droop Features Isochronous or Droop governing Rugged,

More information

LOXONE 12 Channel Amplifier

LOXONE 12 Channel Amplifier LOXONE 12 Channel Amplifier Item no.: 200110 Thank you for purchasing the Loxone Twelve Channel Amplifier. The versatility of the Amplifier makes it the perfect choice for almost every type of custom multi-room

More information

T775U Series 2000 Electronic Stand-Alone Controller

T775U Series 2000 Electronic Stand-Alone Controller T775U Series 2000 Electronic Stand-Alone Controller INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of universal controls capable of remote

More information

Operating Instructions

Operating Instructions CS101 CarSense Vehicle Motion Detector Operating Instructions CAUTIONS AND WARNINGS Never use the CS101 as a safety reversing or presence detection system. The CS101 requires that a vehicle be moving for

More information

SX460. Generator Automatic Voltage Regulator Operation Manual

SX460. Generator Automatic Voltage Regulator Operation Manual SX460 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage SX460* * Use for reference purpose only and not a genuine Newage product. 1.

More information

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese.

Technote. Frese OPTIMA Compact actuators DN10-DN32. Application. Features thermic actuators. Features motoric actuators. Approval. www.frese. Page 1 of 6 Application Proportional 0-10V or 3-position modulating or On/ Off control of Frese OPTIMA Compact valves in heating, ventilating and air conditioning systems. The actuator can be mounted on

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS PIPELINE INSPECTION COMPANY LTD. OPERATING INSTRUCTIONS Wet Sponge Holiday Detectors 670,673, and MSRB Wet Sponge Holiday Detectors Portable and In-Plant Detectors Table of Contents General Information.......................3

More information

System 350 A350R Electronic Temperature Reset Control (with Relay)

System 350 A350R Electronic Temperature Reset Control (with Relay) FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350R Issue Date 0899 System 350 A350R Electronic Temperature Reset Control (with Relay) The A350R Electronic Temperature Reset Control is designed

More information

KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual

KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual KBIC Solid State SCR DC Motor Speed Controls See table 2 page 4 for KBIC models covered by this manual Patented Ultra Fast CL Circuit Prevents Demagnetization in PM Motors Installation and Operating Instructions

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &

More information

Model SRMD Setra Remote Monitoring Display

Model SRMD Setra Remote Monitoring Display Model SRMD Setra Remote Monitoring Display 1.0 GENERAL INFORMATION Thank you for purchasing the Setra Remote Monitoring Display (SRMD). The SRMD is a digital panel meter with a bright 1 LED display for

More information

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The

More information

T-100-R Installation Guide

T-100-R Installation Guide T-100-R Installation Guide Table of Contents Page 2 Overview T-100-R Z-Wave Thermostat 3-4 Installation HVAC System Setup 6 Installer Settings Menu Items 7-9 Installer Settings Summary 10-11 Wiring Standard

More information

MODEL 2202IQ (1991-MSRP $549.00)

MODEL 2202IQ (1991-MSRP $549.00) F O R T H E L O V E O F M U S I C F O R T H E L O V E O F M U S I C MODEL 2202IQ (1991-MSRP $549.00) OWNER'S MANUAL AND INSTALLATION GUIDE INTRODUCTION Congratulations on your decision to purchase a LINEAR

More information

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate

More information

Sanitary Type Electronic Flow Switches

Sanitary Type Electronic Flow Switches Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts

More information

DLP-PU/E Instruction Manual

DLP-PU/E Instruction Manual Instruction Manual BEFORE USING THE POWER SUPPLY UNIT Pay attention to all warnings and cautions before using the unit. Incorrect usage could lead to an electrical shock, damage to the unit or a fire hazard.

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

RC 195 Multiple Input Receiver-Controller

RC 195 Multiple Input Receiver-Controller Document No. 129-230 RC 195 Multiple Input Receiver-Controller Product Description The RC 195 Multiple Input Receiver-Controller is a pneumatic instrument that can be used as a one input (DA or RA), two

More information

Powers Controls TH 192 S Single Temperature Room Thermostat

Powers Controls TH 192 S Single Temperature Room Thermostat Technical Instructions Document No. 155-065P25 TH 192-1 Powers Controls TH 192 S Single Temperature Room Thermostat 50 60 70 80 TH0355R1 70 80 POWERS Description The TH 192 S thermostats are proportional

More information

Pow-R-Con Multi Function Control

Pow-R-Con Multi Function Control 37264 Pow-R-Con Multi Function Control Product Specification Product Specification 37264 Product Information DYNA Power Controls Pow-R-Con TM GENERAL The Barber-Colman Pow-R-Con TM represents an integrated

More information

GLOLAB Two Wire Stepper Motor Positioner

GLOLAB Two Wire Stepper Motor Positioner Introduction A simple and inexpensive way to remotely rotate a display or object is with a positioner that uses a stepper motor to rotate it. The motor is driven by a circuit mounted near the motor and

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

The Do s and Don ts of Pressure Transducers

The Do s and Don ts of Pressure Transducers The Do s and Don ts of Pressure Transducers ABSTRACT When specifying a pressure transducer for a process measurement, a number of items have to be considered. Some of the more important ones are discussed

More information

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations 12S, 14S, 15S Series Time Delay Relays and Sequencers Time Delay Relays and Sequencers The Therm-O-Disc type 12S, 14S and 15S series time delay relays and sequencers are field-proven devices for controlling

More information

Y7230A CO 2 Alarm System

Y7230A CO 2 Alarm System Y7230A CO 2 Alarm System FOR CO 2 GAS DETECTION PRODUCT DATA FEATURES APPLICATION Y7230A CO 2 alarm system is used to detect gas leaking from CO 2 beverage dispensing systems and posts an alarm to occupants

More information

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05

RI-215A Operator s Manual. Part Number: 71-0045RK Revision 0 Released: 10/3/05 RI-215A Operator s Manual Part Number: 71-0045RK Revision 0 Released: 10/3/05 Warranty RKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materials and workmanship,

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

T775A/B/M Series 2000 Electronic Stand-Alone Controllers

T775A/B/M Series 2000 Electronic Stand-Alone Controllers T775A//M Series 2000 Electronic Stand-Alone Controllers INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The T775 electronic stand-alone controllers are the next generation of commercial and agricultural

More information

Series 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

Series 427. 1/16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS Series 427 1/16 DIN Multi-Mode Bar Graph Display Timer PRODUCT HIGHLIGHTS Digital Setting with 0.1% Accuracy Unique LED Bargraph Indicates Time Cycle in 20% Increments 8 Field Selectable Modes of Operation

More information

3-Wire Wallbox Adapter For Seeburg SMC jukeboxes with the GEN2 MCU

3-Wire Wallbox Adapter For Seeburg SMC jukeboxes with the GEN2 MCU 3-Wire Wallbox Adapter For Seeburg SMC jukeboxes with the GEN2 MCU Connect any 3-wire wallbox selector to your Seeburg SMC jukebox Requires the 'GEN2' Microcomputer Control Unit AMI W-40 AMI W-80 AMI W-120

More information

SLIM LINE FUME HOOD MONITOR

SLIM LINE FUME HOOD MONITOR SLIM LINE FUME HOOD MONITOR Phoenix Controls FHM420 Fume Hood Monitor is sized to fit any fume hood and includes icons for simple and universal operation. The FHM420 slim line monitor works in conjunction

More information

1993 ACCESSORIES & EQUIPMENT Volkswagen Instrument Panels. Volkswagen; EuroVan, Passat

1993 ACCESSORIES & EQUIPMENT Volkswagen Instrument Panels. Volkswagen; EuroVan, Passat Article Text Saturday, March 18, 2000 10:33PM ARTICLE BEGINNING 1993 ACCESSORIES & EQUIPMENT Volkswagen Instrument Panels Volkswagen; EuroVan, Passat DESCRIPTION & OPERATION Instrument cluster for most

More information

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital

More information

Kit 106. 50 Watt Audio Amplifier

Kit 106. 50 Watt Audio Amplifier Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications

More information

POWER SUPPLY MODEL XP-15. Instruction Manual ELENCO

POWER SUPPLY MODEL XP-15. Instruction Manual ELENCO POWER SUPPLY MODEL XP-15 Instruction Manual ELENCO Copyright 2013 by Elenco Electronics, Inc. REV-A 753020 All rights reserved. No part of this book shall be reproduced by any means; electronic, photocopying,

More information

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES

THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES TSI and TSI logo are registered trademarks of TSI Incorporated. SmartTune is a trademark of TSI Incorporated. THERMAL ANEMOMETRY ELECTRONICS, SOFTWARE AND ACCESSORIES IFA 300 Constant Temperature Anemometry

More information

This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets.

This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets. 1/99 Modutrol Motors Selection Guide This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets. 2-POSITION SPRING

More information

bba - Balboa Bluetooth Audio (AMP) Installation & User Guide

bba - Balboa Bluetooth Audio (AMP) Installation & User Guide bba - Balboa Bluetooth Audio (AMP) Installation & User Guide Bluetooth Integration CONNECT YOUR SMART DEVICE TO YOUR HOT TUB With Bluetooth connection you can now play all your favorite songs directly

More information

Combustible Gas Transmitter 65-2400RK-05

Combustible Gas Transmitter 65-2400RK-05 Combustible Gas Transmitter 65-2400RK-05 Overview This detection insert describes the combustible gas transmitter. This insert also describes how to install, start up, maintain, and calibrate the transmitter.

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

Position Transducers with Restoring Spring 10, 25, 50, 75, 100 mm TR, TRS Series

Position Transducers with Restoring Spring 10, 25, 50, 75, 100 mm TR, TRS Series Position Transducers with Restoring Spring 10, 25, 50, 75, 100 mm TR, TRS Series Special features long life 100 x 10 6 movements outstanding linearity up to ±0.075% choice of plug or cable connection DIN

More information

In-Line Electronic Flow Switches

In-Line Electronic Flow Switches In-Line Electronic Flow Switches Industries Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information

Introduction. Drenth Motorsport Gearboxes Fleuweweg 10 7468 AG Enter The Netherlands Phone: +31 (0)547 38 26 96 Fax: +31 (0)547 38 20 65

Introduction. Drenth Motorsport Gearboxes Fleuweweg 10 7468 AG Enter The Netherlands Phone: +31 (0)547 38 26 96 Fax: +31 (0)547 38 20 65 25.03.0023 Introduction The display comes with a software application. With the software application information shown on the display can be adjusted. There are different modes to adjust: the shape of

More information

Single Station Remote Alarm

Single Station Remote Alarm ADI 5106G Certified ISO 9001:2000 Single Station Remote Alarm 529 5106-01-120 529 5106-01-220 INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Controls Corporation

More information

ABB Power T&D Company Inc. Power Automation and Protection Division Coral Springs, FL 33065

ABB Power T&D Company Inc. Power Automation and Protection Division Coral Springs, FL 33065 ABB Power T&D Company Inc. Power Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-252A Effective: December 1996 Supersedes I.L. 41-252. Dated April 1987 ( ) Denotes Change

More information

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output Forced current sharing at parallel operation Power OK signal

More information

CONTENTS. PAGE Chapter 1 General Information 1. Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13

CONTENTS. PAGE Chapter 1 General Information 1. Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13 CONTENTS PAGE Chapter 1 General Information 1 Chapter 2 Setup 4 DP450-VDC 7 DP450-VAC 7 DP450-DCC 7 DP450-F 8 DP450-HACC 9 DP450-HDCC 11 DP450-E 13 Chapter 3 Alarm/Excitation Options 15 Wiring 17 Chapter

More information

Talon and Talon SR User Manual

Talon and Talon SR User Manual Talon and Talon SR User Manual Brushed DC motor controller Version 1.3 Cross the Road Electronics, LLC www.crosstheroadelectronics.com Cross The Road Electronics, LLC Page 1 4/2/2013 Device Overview Clear,

More information

Solid-State Timer H3G

Solid-State Timer H3G ASH & ALAIN INDIA PVT LTD S-100, F.I.E.E., Okhla Industrial Area, Phase-ii, New Delhi-11000(India) Tel : 011-43797575 Fax : 011-43797574 E-mail : sales@ashalain.com Solid-State Timer Low-Cost, Plug-In

More information

Electronic Flow Switches

Electronic Flow Switches Industries Electronic Flow Switches Petrochemical Refining Oil Production Water Treatment Pharmaceutical Food and Beverage Pulp and Paper Power Production Gas Processing Mining Biotechnology Semiconductor

More information

User's Manual. Research Isometric Transducer 0 to 5 grams and 0 to 50 grams

User's Manual. Research Isometric Transducer 0 to 5 grams and 0 to 50 grams Research Isometric Transducer 0 to 5 grams and 0 to 50 grams User's Manual Research Isometric Transducer 0 to 5 g and 0 to 50 g, 110 VAC/60 Hz MA1 72-4481 Research Isometric Transducer 0 to 5 g and 0 to

More information

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY 7320 Ashcroft, Suite 104 Houston, Texas 77081 p: 713-772-1404 f: 713-772-7360 e: info@juicegoose.com www.juicegoose.com 06-06 CONGRATULATIONS

More information

TC-9102 Series Surface Mount Temperature Controllers

TC-9102 Series Surface Mount Temperature Controllers TC-9102 Series Surface Mount Temperature Controllers General Description & Applications The TC-9102 Series Temperature Controller offers a versatile solution for a wide variety of applications that may

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

DPT-2015 Differential Pressure Transmitter for VAV Box Applications FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential

More information

Contents. Document information

Contents. Document information User Manual Contents Document information... 2 Introduction... 3 Warnings... 3 Manufacturer... 3 Description... Installation... Configuration... Troubleshooting...11 Technical data...12 Device Scope: PCB

More information

ATL Fuel Level Sender Probes

ATL Fuel Level Sender Probes T E C H N I C A L S P E C I F I C A T I O N The ATL EL-AD-151 (Resistance Output) and EL-AD-152 (Voltage Output) Fuel Level Senders are highly advanced sensors for continuously measuring the contents of

More information

i ChatterBox! Motorcycle Security

i ChatterBox! Motorcycle Security i Before you Start the Installation * Please read this manual to become familiar with the requirements necessary to complete the installation. * Use a high quality multi-meter to test all wires before

More information

PRODUCT PROFILE FEATURES

PRODUCT PROFILE FEATURES PRODUCT PROFILE Pressure Transmitters & Pneumatic Transducer Airflow Transmitter, Differential Air Pressure Transmitter and Differential & Gauge Liquid/Gas Pressure Transmitter FEATURES AIRFLOW TRANSMITTER

More information

Atkinson Dynamics Intercoms Models AD-26, AD-27, AD-56, and AD-57. Installation and Service Instructions

Atkinson Dynamics Intercoms Models AD-26, AD-27, AD-56, and AD-57. Installation and Service Instructions Atkinson Dynamics Intercoms Models AD-6, AD-7, AD-56, and AD-57 Installation and Service Instructions Address all communications and shipments to: 65 Federal Signal Drive University Park, IL 6066-95 (888)75-500

More information

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit) 000W Single Output Power Supply AK-000 series Features: Universal AC input / Full range Programmable output Voltage (0% ~ 05%) Programmable output Current (% ~ 05%) + / 0.5A auxiliary output U profile,

More information

Technical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.

Technical data. General specifications. Signal voltage 15... 30 V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output. Model Number Features Very small housing High climatic resistance 4 Bit multiturn Analog output Surge and reverse polarity protection Description This absolute rotary encoder with internal magnetic sampling

More information

VIBRATION SWITCHES SOLID STATE

VIBRATION SWITCHES SOLID STATE SOLID STATE VIBRATION SWITCHES The PMC/BETA electronic vibration switch makes available in a relatively low-cost device many of the benefits formerly found only in high-end protection systems. Model Adjustable

More information

PB-600 series. 600W Single Output Battery Charger SPECIFICATION MODEL PB-600-12 PB-600-24 PB-600-48 14.4V 28.8V 57.6V 13.8V

PB-600 series. 600W Single Output Battery Charger SPECIFICATION MODEL PB-600-12 PB-600-24 PB-600-48 14.4V 28.8V 57.6V 13.8V .. 600W Single Output Charger PB600 series SPECIFICATION MODEL OUTPUT INPUT PROTECTION FUNCTION ENVIRONMENT SAFETY & EMC (Note 2) OTHERS NOTE BOOST CHARGE VOLTAGE FLOAT CHARGE VOLTAGE RECOMMENDED BATTERY

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624 v.1.0 AC/AC power supply unit Edition: 1 from 24 th October 2008 Supercedes edition: ---------- 10062009 CONTENTS: 1. Technical description. 1.1. General description

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

R&D Electronics 8440 N. Waukegan Rd., Morton Grove, IL 60053 -- (847) 583-9080 -- Issue 12/08/06 om_207f.doc --

R&D Electronics 8440 N. Waukegan Rd., Morton Grove, IL 60053 -- (847) 583-9080 -- Issue 12/08/06 om_207f.doc -- R&D Electronics 8440 N. Waukegan Rd., Morton Grove, IL 60053 (847) 5839080 Issue 12/08/06 om_207f.doc MODEL AH 207 Heat Call MICRO PROCESSOR SYSTEM Temperature Averaging OWNERS MANUAL Model AH207, 207M

More information

TDAS G5-DB Hardware User s Manual

TDAS G5-DB Hardware User s Manual TDAS G5-DB Hardware User s Manual July 2003 Rev. 1A Table of Contents DTS Support... 3 Introducing the TDAS G5-DB... 4 Summary of TDAS G5-DB Features... 4 Basic Care and Handling... 4 Shock Rating...5

More information

Power Supplies 3. SDN-P DIN Rail Series

Power Supplies 3. SDN-P DIN Rail Series SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.

More information

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function Document No. 155-751 SKP15U.. Description Only when assembled to Series VGU Gas valves SKP15 electro-hydraulic actuators combine with

More information

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED

More information

MNL-10Rxx Series MNL-15Rxx Series MNL-20Rxx Series

MNL-10Rxx Series MNL-15Rxx Series MNL-20Rxx Series MNL-10Rxx Series MNL-15Rxx Series MNL-20Rxx Series TAC I/A Series MicroNet MN 100, MN 150, and MN 200 Controllers Installation Instructions Application The TAC I/A Series MicroNet MNL-10Rxx, MNL- 15Rxx,

More information

T-SERIES INDUSTRIAL INCLINOMETER ANALOG INTERFACE

T-SERIES INDUSTRIAL INCLINOMETER ANALOG INTERFACE T-SERIES INDUSTRIAL INCLINOMETER ANALOG INTERFACE T-Series industrial inclinometers are compact high performance sensors used to determine inclination in roll and pitch axes with excellent precision and

More information

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections

More information

PART 1 - INTRODUCTION...

PART 1 - INTRODUCTION... Table of Contents PART 1 - INTRODUCTION... 3 1.1 General... 3 1.2 Sensor Features... 3 1.3 Sensor Specifications (CDE-45P)... 4 Figure 1-1 CDE-45P Sensor Dimensions (standard, convertible style)... 4 PART

More information

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Applied Electronics. Commercial Dimming System UPDATE NOTICE REV. A Applied Electronics Commercial Dimming System UPDATE NOTICE This notice is to inform the end user of an additional feature added to this DP12/2400 dimming unit. This unit has been outfitted with

More information