I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

Size: px
Start display at page:

Download "I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed."

Transcription

1 FANs 268.1, Installation Bulletin M100Q Issue Date 1099 M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications I nstallation Parts Included M110QGA-1 and M130QGA-1: M100 Series spring return actuator five 1/4 in. female quick connect terminals LVR27A-602 crank arm M120QGA-1 and M150QGA-1: M100 Series non-spring return actuator five 1/4 in. female quick connect terminals M150QGB-1: M100 Series non-spring return actuator five 1/4 in. female quick connect terminals one 1/4 in. male/female quick connect terminals S91DJ-1 Auxiliary Switch Kit R81QAA-x: vertical board terminal board insulating barrier two No x 5/16 in. Phillips recess screws Note: An R81QAA-x can be used with an M100X actuator. (See Ordering Information section, Table 1 in the M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications Product Bulletin (LIT ). Tools Needed No. 2 Phillips screwdriver 1/8 in. (3 mm) flat-blade screwdriver hammer Precautions IMPORTANT: All M100Q Series actuators are designed for use only in conjunction with operating controls. Where an operating control failure would result in personal injury and/or loss of property, it is the responsibility of the user to add devices (safety, limit controls) or systems (alarm, supervisory) that protect against, and/or warn of control failure. Do not install the actuator in atmospheres where explosive vapors or gases could be present, or environments where substances corrosive to the device s internal components could be present. Seal wiring into return air systems to prevent aspiration of corrosive air into the actuator Johnson Controls, Inc. 1 Part No , Rev. A Code No. LIT

2 Control Input M100Q Series actuators receive their input commands from a remote A91/T91 temperature sensor. (Figures 1 and 2 illustrate sensor resistance characteristics.) The A91/T91 is connected to Terminals S1 and S2, for accurate positioning of the output shaft. Note: Use 40 to 90 F (4 to 32 C) A91 sensors for the 15 to 50 F (-9 to 10 C) R81QAA-2 Electronics Board. Sensor Resistance (ohms) F C Temperature Figure 1: Thermistor Sensor Characteristics for Ranges 15 to 50 and 40 to 90 F (-9 to 10 and 4 to 32 C) Sensor Resistance 1400 (ohms) F C Temperature Refer to the M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications Application Note (LIT ) for minimum position input and remote setpoint potentiometer applications. The voltage between Terminals T1 and X, jumpered from the Direct Acting (DA) Terminal XD or the Reverse Acting (RA) Terminal XR, is approximately 6 VDC at zero rotation of the output shaft. Full rotation of the output shaft occurs when the voltage between T1 and X is approximately 10 VDC. Direction of Rotation The actuators are factory set at the zero position and for 90 Clockwise (CW) travel. The zero position is 10 CW from vertical. (See Figure 3.) Spring return models always return CCW to the zero position when power is removed. Note: Direction of rotation is CW with temperature increase. Keyway Direction of Drive Rotation Terminals 8 and T1 Shorted LOAD END 10 Zero Position Direction of Drive Rotation Terminals 8 and 10 Shorted Drive Shaft Figure 3: Direction of Rotation All reference to the direction of rotation is when viewing the load end stamped on the actuator housing as shown in Figure 3. From this view, the Counterclockwise (CCW) limit is the zero position. Figure 2: Thermistor Sensor Characteristics for a 60 to 120 F (16 to 49 C) Range 2 M100Q Series Proportional Actuator with R81Q Controller Board Installation Bulletin

3 M ounting Actuator Follow installation steps for the linkage kit used to couple the actuator and the controlled device. When not utilizing a damper or valve linkage kit, use four 1/4 x 1 in. bolts to mount the actuator (not included). Upright mounting of the actuator is preferred with the output shaft parallel to the floor. Locate the actuator where the shaft and wiring terminals are accessible. Terminal Board Screws (2) Terminal Board Receptacles Insulating Barrier Pin Terminals IMPORTANT: For installations using the CVR83A-600R Weather Cover Kit, mount the actuator in an upright position to prevent water from entering the enclosure and damaging the actuator. All linkage connections should be made to the drive shaft on the load end of the actuator, rated for up to 200 lb dead weight. Limit the load on the auxiliary end to 10 lb dead weight. When mounting on a valve, mount the actuator above the horizontal plane of the valve piping to avoid damage to the actuator if the valve leaks or develops condensation. Note: Valve medium temperatures above 250 F (121 C) are acceptable only if the actuator s maximum ambient temperature is below 105 F (41 C). Figure 4: Installing the Insulating Barrier and the Terminal Board 2. Install the terminal board by carefully placing the terminal receptacles onto the pin terminals. 3. Fasten the board with the No x Phillips screws supplied. 4. Install the vertical board, carefully placing the terminal receptacles onto the two sets of pin terminals so all pins are aligned. (See Figure 5.) Vertical Board Pin Terminals Terminal Receptacles Receptacles Pin Terminals R81Q Installation! CAUTION: Equipment Damage Hazard. Disconnect all power supplies before removing the wiring connections and boards to avoid possible damage to the equipment. Figure 5: Installing the Vertical Board 5. Place the bracket, supplied with the actuator, over the vertical board and fasten it with the captive screw. (See Figure 6.) Installing Boards M100X base actuators are not provided with circuit boards. To install one, loosen the actuator s cover screws, remove the cover, and proceed as follows: 1. Install the insulating barrier into the wiring compartment. Make sure all the metal surfaces are covered. (See Figure 4.) Captive Screw Bracket Figure 6: Installing the Bracket M100Q Series Proportional Actuator with R81Q Controller Board Installation Bulletin 3

4 6. Apply the adhesive-backed identification label provided to the actuator bracket. (See Figure 7.) Bracket M150 X GA-1 Make all wiring connections using only copper conductors and in accordance with the National Electrical Code and local regulations. Use separate transformers on each M100 actuator to avoid potential miswiring or control signal problems. Locate all splicing and excess wiring outside the actuator wiring compartment. If desired, add a standard electrical box to the actuator s wiring compartment. (See Figure 8.) Q Identification Label Figure 7: Identification Label Wiring Compartment Removing Boards To remove a circuit board, loosen the cover screws and remove the actuator cover. (See Figure 3.) 1. Disconnect all wiring to the terminal board. 2. Loosen the captive screw, and remove the bracket. 3. Pull the vertical board straight upward, being careful not to bend or damage the pin terminals. 4. Remove the two screws from the terminal board. 5. Grasp the receptacles and remove the terminal board by lifting upward, being careful not to bend or damage the pin terminals. W iring! CAUTION: Equipment Damage Hazard. Disconnect all power supplies before wiring connections are made. Check all wiring connections before applying power to the system. Short-circuited or improperly connected wires will result in permanent damage to the equipment. Figure 8: Wiring the Junction Box The M100Q does not require shielded cable on runs less than 50 ft (15 m). Avoid running low voltage sensor wiring in the same conduit as line voltage wiring, 24 VAC wiring, or other conductors that supply highly inductive loads (contactors, coils, generators, etc.) Use shielded cable if the control wiring is longer than 50 ft (15 m), located in a common conduit, or near inductive loads. Use 22 AWG, Beldfoil 8761 or an equivalent for runs up to 250 ft (76 m). For runs of 250 to 500 ft (76 to 152 m), use 18 AWG, Beldfoil 8760 or an equivalent. Connect the shield to Terminal T1 (Common) only. To connect the wiring: 1. Use a hammer and punch to push the plug out of one of the access holes. 2. Install the conduit connector (not provided) to the actuator, and secure it using the conduit nut provided with the connector. 3. Connect the sensor to Terminals S1 and S2 located in the wiring compartment. (See Figure 9.) 4 M100Q Series Proportional Actuator with R81Q Controller Board Installation Bulletin

5 A91, T91 Thermistor Sensor Power Supply 24 VAC Potentiometer is factory set, do not adjust. S2 S1 T2 Setpoint Travel Potentiometer Proportional Band Inc. PB Factory Jumper T1 XD (DA) XR (RA) X 10 Figure 9: Typical Wiring Diagram 4. Connect 24 VAC to Terminals T1 and T2. Figure 6 shows a wiring configuration, and Table 1 shows the location of the wiring terminals. Refer to the M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications Application Note (LIT ) for more specific wiring information. Table 1: Wiring Terminals Terminal T1 T2 S1 S2 X XD XR Description Power Common 24 VAC Power Thermistor Sensor (Common) Thermistor Sensor Direct Acting (DA) or Reverse Acting (RA) Input DA Output RA Output 8 Slave Actuator 10 Slave Actuator A djustments Travel Travel is field adjustable from 65 to 270 with the travel potentiometer located on the R81Q terminal board. (See Figure 9.) Adjusting the potentiometer affects the CW limit of the actuator s rotation. (The CCW limit is not adjustable.) Refer to the appropriate valve or damper linkage literature for more information on travel adjustment. 1. Apply 24 VAC to Terminal T1 (Common) and Terminal T2. 2. Run the actuator to its CW limit by jumpering Terminals 8 and T1. 3. Turn the travel potentiometer CW to increase travel and CCW to decrease travel. Action DA Output A jumper is factory installed between Terminals X and XD for DA output. (See Figure 9.) An increase in temperature at the sensor causes an increase in the output signal, resulting in CW rotation of the actuator output shaft. Turn the setpoint knob to a setting below the sensed temperature to simulate an increase in temperature. The actuator s load end output shaft will rotate CW. Turn the setpoint knob to a setting above the sensed temperature, and it will rotate CCW. RA Output Remove the jumper from Terminal XD, and connect it to Terminal XR for RA output. A decrease in temperature at the sensor will increase the output signal. Turn the setpoint knob to a setting above the sensed temperature to simulate a decrease in temperature, and the actuator s output shaft will rotate CW. Turn the setpoint knob to a setting below the sensed temperature, and it will rotate CCW. Setpoint An internal setpoint adjustment for the remote sensor is located on the R81Q terminal board. (See Figure 6). Proportional Band IMPORTANT: If the actuator cannot maintain a stable position, increase the proportional band. Do not allow the actuator to oscillate, which could shorten the actuator s life. The proportional band adjustment (shown in Figure 9) controls the amount of change in the sensor temperature required to drive the actuator between the zero position and full stroke. (See Figure 10.) It is adjustable between 2 and 30 F (1 and 17 C). Make field adjustments with the system in operation. M100Q Series Proportional Actuator with R81Q Controller Board Installation Bulletin 5

6 100% Actuator Travel 0% Reverse Acting Proportional Band Setpoint Sensor Temperature Proportional Band Figure 10: Proportional Band Completing Installation Direct Acting Perform at least three complete operating cycles of the system to complete actuator installation. T T roubleshooting Apply 24 VAC to Terminals T1 and T2, and proceed as follows: 1. Simulate a high temperature by shorting Terminals S1 and S2 together. (The actuator will drive to the CW travel limit if set for DA, and CCW to the zero position if set for RA.) 2. Simulate a low temperature condition by removing one of the wires connecting the sensor to Terminals S1 and S2. (The actuator will drive CCW to the zero position if set for DA, and to the CW travel limit if set for RA control.) 3. Verify that the voltage at Terminal 10, with reference to Terminal T1, is approximately +12VDC. 4. Connect the sensor to Terminals S1 and S2. 5. Verify that the voltage at Terminal 8 (+), with reference to Terminal 10 (-), varies proportionally between 0 and approximately 2 VDC as the setpoint is adjusted across the proportional band. 6. Perform at least three complete operating cycles. 6 M100Q Series Proportional Actuator with R81Q Controller Board Installation Bulletin

7 S pecifications Table 2: Specifications Product Power Requirements Input Signal Input Signal Adjustments M100Q Series Proportional Actuator 24 VAC, Class 2, (20 to 30 VAC) at 50/60 Hz, 25 VA spring return, 20 VA non-spring return Proportional control, thermistor sensor input using A91 or T91 sensors Mixed Air Setpoint: R81QAA-1 40 to 90 F (5 to 32 C) R81QAA-2 15 to 50 F (-9 to 10 C) R81QAA-3 60 to 120 F (16 to 49 C) Adjustable proportional band 2 to 30 F (1 to 17 C) Jumper selectable: Direct Acting (DA) or Reverse Acting (RA); factory set for DA Mechanical Connection 3/8 in. (9.5 mm) square shaft, both ends Maximum Dead Weight on Output Shaft: Load end, 200 lb (91 kg) Auxiliary end, 10 lb (4.5 kg) Mechanical Output Running Torque: Breakaway and Stall (minimum): M lb in (2.8 N m) spring return 100 lb in (11 N m) M lb in (4 N m) 70 lb in (8 N m) M lb in (5.6 N m) spring return 200 lb in (23 N m) M lb in (8.5 N m) 150 lb in (17 N m) M lb in (17 N m) 300 lb in (34 N m) Rotation Range Fixed zero, adjustable full travel 65 to 270, factory set at 90 Rotation Timing (at Rated Load) Cycle Life Electrical Connection Action Ambient Operating Conditions Ambient Storage Conditions Enclosure 60 seconds for 160 travel nominal, 60 Hz 38 seconds for 90 travel nominal, 60 Hz 75 seconds for 90 spring return M110 and M130 Spring Return Models: 150,000 cycles at rated load M120, M140 and M150 Non-spring Return Models: 200,000 cycles at rated load 1/4 inch quick-connect spade terminals CW rotation in DA mode and CCW rotation in RA mode with temperature increase Non-spring Return: -40 to 125 F (-40 to 52 C), 90% RH, 25% duty cycle Spring Return: -35 to 125 F (-37 to 52 C), 90% RH, 25% duty cycle -40 to 140 F (-40 to 60 C), 90% RH NEMA 2, IP32 Dimensions (H x W x D) Spring Return: 5.81 x 5.64 x 7.68 in. (148 x 143 x 195 mm) Non-spring Return: 5.81 x 5.64 x 4.94 in. (148 x 143 x 125 mm) Shipping Weight Spring Return: 9 lb (4.1 kg) Non-spring Return: 6.5 lb (2.9 kg) Agency Compliance UL: M100Q: UL 916 Listed, File E107041, CCN PAZX (M100QGA only) UL 873 Recognized, File E27734, CCN XAPX2 M100X and R81: No UL Listing CSA: M100Q: C22.2 No. 24 Certified, File LR948, Class M100X and R81: No CSA Certification EU Directive Compliance 89/336/EEC The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. M100Q Series Proportional Actuator with R81Q Controller Board Installation Bulletin 7

8 Notes Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI Printed in U.S.A. 8 M100Q Series Proportional Actuator with R81Q Controller Board Installation Bulletin

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators Product Bulletin Code No. LIT-1201742 Issued February 12, 2015 The M9102 and M9104 Series Actuators are directmount,

More information

DPT-2015 Differential Pressure Transmitter for VAV Box Applications

DPT-2015 Differential Pressure Transmitter for VAV Box Applications FANs 216, 1628.3 Product/Technical Bulletin DPT-2015 Issue Date 1298 DPT-2015 Differential Pressure Transmitter for VAV Box Applications The DPT-2015 Differential Pressure Transmitter senses differential

More information

A99B Series Temperature Sensors

A99B Series Temperature Sensors FANs 125, 121, 930, 930.5 Product/Technical Bulletin A99 Issue Date 0615 A99B Series Temperature s The A99B Series Temperature s are passive PTC (Positive Temperature Coefficient) sensors. The A99B sensors

More information

WE-350 Series ¼ Turn Electric Actuator

WE-350 Series ¼ Turn Electric Actuator WE-350 Series ¼ Turn Electric Actuator Operation and Installation Manual Pg 1 (Rev. 020113) Table of Contents 1.0 General 1.1 Pre-Installation Inspection 1.2 Storage 1.3 Features & General Information

More information

System 350 A350E Electronic Cooling Control

System 350 A350E Electronic Cooling Control FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350E Issue Date 0899 System 350 A350E Electronic Cooling Control The A350E is an on/off, electronic, cooling-only control with Single-Pole, Double-Throw

More information

Series 71, 72, and 76 Modutrol IV Motors

Series 71, 72, and 76 Modutrol IV Motors Series 7, 7, and 76 Modutrol IV Motors PRODUCT DATA FEATURES APPLICATION The Series 7, 7 and 76 Modutrol IV Motors are spring return and nonspring return motors used to control dampers and valves. The

More information

System 350 A350R Electronic Temperature Reset Control (with Relay)

System 350 A350R Electronic Temperature Reset Control (with Relay) FANs 930, 930.5, 125, 121 Product/Technical Bulletin A350R Issue Date 0899 System 350 A350R Electronic Temperature Reset Control (with Relay) The A350R Electronic Temperature Reset Control is designed

More information

G670 Intermittent Pilot Ignition Controls

G670 Intermittent Pilot Ignition Controls Installation Sheets Manual 121 Gas Combustion Combination Controls and Systems Section G Technical Bulletin Issue Date 0300 Intermittent Pilot Ignition Controls Figure 1: Intermittent Pilot Ignition Control

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

Series 90 Modutrol IV Motors

Series 90 Modutrol IV Motors Series 90 Modutrol IV Motors PRODUCT DATA FEATURES APPLICATION The Series 90 Modutrol IV Motors are spring return and non-spring return modulating proportional control motors. Use these motors with controllers

More information

Installation Instructions

Installation Instructions 0.1.2....6.7..9 1 0.1.2....6.7..9 1 Installation Instructions Quick-Mount Visual Instructions for Mechanical Installation Quick-Mount Visual Instructions 1. Rotate the damper to its fail-safe position.

More information

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) TECHNICAL DATASHEET #TD1102AX CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version) Part Number: Connector Amplifier CAPV-H-4-20MA-x complete with cable CAPV-4C-yM Where: x = current output

More information

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors

Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for Single-Phase Motors European Refrigeration Controls Catalogue Catalogue Section 4 Product Bulletin P215PR/RM Issue 01/03/2013 Series P215PR/RM Direct- and Remote-Mount Pressure-Actuated Condenser Fan Speed Controllers for

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. McDonnell & Miller Installation & Maintenance Instructions MM-600G) Series FS8-W General Purpose Liquid Flow Switch OPERATION This control is an independently mounted water flow sensing device that makes

More information

This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets.

This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets. 1/99 Modutrol Motors Selection Guide This chart is intended for selection purposes only. For complete product application information, refer to individual product specification sheets. 2-POSITION SPRING

More information

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application 33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection

More information

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection

More information

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function Document No. 155-751 SKP15U.. Description Only when assembled to Series VGU Gas valves SKP15 electro-hydraulic actuators combine with

More information

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital

More information

S03, S05 Series Low-Torque Spring- Return Direct-Coupled Actuators

S03, S05 Series Low-Torque Spring- Return Direct-Coupled Actuators S, S Series Low-Torque Spring- Return Direct-Coupled Actuators S, S, S, S, S, S INSTALLATION AND OPERATING INSTRUCTIONS S, S Series Low-Torque Spring-Return Direct-Coupled Actuators (DCA) are used for

More information

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER (PWM Input, 1.2A or 2A Output, Metal Box or PCB) PCB Board - P/N: PWMC-PCB-2A, PWMC-PCB-1.2A Packaged Driver (metal box with 1.5 m (5 ft.) cable)

More information

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Introduction. Refrigerant Leak Detecting System. Feature and Benefits PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for

More information

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE Scaletron Industries, Ltd. Bedminster Industrial Park 53 Apple Tree Lane P.O. Box 365 Plumsteadville, PA 18949 USA Toll Free: 1-800-257-5911 (USA &

More information

HMI display Installation Guide

HMI display Installation Guide HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC

More information

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C DESCRIPTION FEATURES PRODUCT DATA Very low operating trip points LED status indication Integral DIN rail mounting

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks Securitron Magnalock Corp. www.securitron.com ASSA ABLOY, the global leader Tel 800.624.5625 techsupport@securitron.com in door opening solutions INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate

More information

CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter

CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter CD-Pxx-00-1 Series Duct Mount CO 2 Transmitter Product Bulletin CD-Pxx-00-1 Code No. LIT-216525 Issued December 6, 2010 Supersedes September 12, 2008 Johnson Controls offers a complete line of Carbon Dioxide

More information

NEXUS FX04 and FX04-1 Servo Motor Installation. Fireye DESCRIPTION SAFETY INFORMATION. FX04-1 Shown

NEXUS FX04 and FX04-1 Servo Motor Installation. Fireye DESCRIPTION SAFETY INFORMATION. FX04-1 Shown NEX-3004 AUGUST 4, 2015 Fireye NEXUS FX04 and FX04-1 Servo Motor Installation FX04-1 Shown DESCRIPTION This bulletin describes the installation and operating instructions for the FX04 and FX04-1, 3 lb.-ft./

More information

P66 Series Electronic Fan Speed Controls

P66 Series Electronic Fan Speed Controls P66 Series Electronic Fan Speed Controls Product Bulletin Code No. LIT-125465 Issued September 30, 2009 Supersedes March 23, 2006 The P66 Series Electronic Fan Speed Controls are refrigerant pressure actuated,

More information

RC 195 Multiple Input Receiver-Controller

RC 195 Multiple Input Receiver-Controller Document No. 129-230 RC 195 Multiple Input Receiver-Controller Product Description The RC 195 Multiple Input Receiver-Controller is a pneumatic instrument that can be used as a one input (DA or RA), two

More information

Advantium 2 Plus Alarm

Advantium 2 Plus Alarm ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia

More information

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions. B Installation & Maintenance Instructions MM-414 Series 150E and 157E Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications A Typical Applications: Primary or secondary

More information

Radiant Temperature Sensor TY7321

Radiant Temperature Sensor TY7321 AB-5361-U Specifications/Instructions Radiant Temperature TY7321 General TY7321 Radiant Temperature s are designed to measure infrared radiation from perimeter windows and walls and provide a proportional

More information

5800 Temperature Sensor Cable Assembly

5800 Temperature Sensor Cable Assembly 5800 Temperature Sensor Cable Assembly Removal and Replacement Instruction Sheet #60-4702-070 Revision D, January 14, 2013 Overview The 5800 has two refrigeration temperature sensors, one attached to the

More information

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS PLEASE READ COMPLETE INSTRUCTIONS BEFORE YOU BEGIN LEAVE INSTALLATION INSTRUCTIONS AND USER'S GUIDE WITH OWNER ALL ELECTRIC WIRING AND PLUMBING MUST BE DONE

More information

Electronic Control Devices The European Product Catalogue 2007

Electronic Control Devices The European Product Catalogue 2007 FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,

More information

MP8000 Series Pneumatic Valve Actuators

MP8000 Series Pneumatic Valve Actuators 14-1161- 9, Rev. A Technical Bulletin MP8000 Issue Date March 2016 MP8000 Series Pneumatic Valve Actuators Pre-Assembly Details Page 3 MP8000 Actuator Components 3 Tools Required to Assemble an MP8000

More information

POWERS CONTROL RC 195 Single Input Receiver-Controller

POWERS CONTROL RC 195 Single Input Receiver-Controller Document No. 155-119P25 RC 195-4 POWERS CONTROL RC 195 Single Input Receiver-Controller Description The RC 195 Single lnput Receiver-Controller is a pneumatic instrument which receives one pneumatic input,

More information

T7079A,B Solid State Remote Temperature Controllers

T7079A,B Solid State Remote Temperature Controllers T7079A,B Solid State Remote Temperature Controllers FEATURES PRODUCT DATA Switch selection of heat or cool mode. Temperature sensing up to 400 feet. Does not require field calibration. 0K NTC temperature

More information

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V

Installation. Smart-UPS VT MGE Galaxy 3500. Maintenance Bypass Panel. 10-40 kva 400 V Installation Smart-UPS VT MGE Galaxy 3500 Maintenance Bypass Panel 10-40 kva 400 V Contents Safety.................................................. 1 Save these instructions...................................

More information

Contactless Encoder RI360P0-QR24M0-INCRX2-H1181

Contactless Encoder RI360P0-QR24M0-INCRX2-H1181 Compact, rugged housing Many mounting possibilities Status displayed via LED Immune to electromagnetic interference 1024 pulses per revolution (default) 360, 512, 1000, 1024, 2048, 2500, 3600, 4096, parametr.

More information

LUCCI AIRFUSION QUEST II CEILING FAN

LUCCI AIRFUSION QUEST II CEILING FAN LUCCI AIRFUSION QUEST II CEILING FAN WITH IR REMOTE INSTALLATION OPERATION MAINTENANCE WARRANTY INFORMATION CAUTION READ INSTRUCTIONS CAREFULLY FOR SAFE INSTALLATION AND FAN OPERATION. V1.0 QUEST II IR

More information

Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual

Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com. Installation and operating manual Uni-Valve A /S VENTILER & INSTRUMENTER Telefon (+45) 43 43 82 00 Telefax (+45) 43 43 74 75 mail@uni-valve.com www.uni-valve.com UNI-EL Electric actuator Installation and operating manual Remote position

More information

Single Phase Soft Starter

Single Phase Soft Starter Single Phase Soft Starter Installation & Operating Manual 6/02 Table of Contents Section 1 General Information................................................... 1 1 General Description................................................

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator

JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator JANUS INTERNATIONAL CORPORATION INSTALLATION INSTRUCTIONS Pantheon Mini Operator The Janus Pantheon mini operator does not typically require the provision of any additional site requirements other than

More information

DUCT SMOKE DETECTOR D4120

DUCT SMOKE DETECTOR D4120 Purpose/Application National and local safety standards and codes recognize the ability of air duct systems to transfer smoke, toxic gases, and flame from area to area. Sometimes smoke can be of such quantity

More information

OPL BASIC. Dosing System for Professional Laundry machines. Contents

OPL BASIC. Dosing System for Professional Laundry machines. Contents OPL BASIC Dosing System for Professional Laundry machines Contents 1 Getting Started. Page 2 2 Installation. Page 4 3 Set Up & Operation. Page 8 4 Maintenance & Accessories. Page 10 5 Troubleshooting Page

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS

BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS BURSTCHECK LINE OF RUPTURE DISC BURST INDICATORS INTRODUCTION Rupture discs are often used as primary pressure relief devices and to isolate pressure relief valves. When used as a primary pressure relief

More information

Model 2300DR Installation Guide

Model 2300DR Installation Guide Model 2300DR Installation Guide POWER ACCESS CORPORATION P.O. BOX 1050 170 MAIN STREET NEW HARTFORD, CT 06057 800-344-0088 WEBSITE: www.power-access.com EMAIL: salesinfo@power-access.com 1 STANDARD PARTS

More information

Solid State Timers Type F

Solid State Timers Type F Solid State Timers Type F Class 9050 CATALOG CONTENTS Description.....................................................Page Product Descriptions............................................. 3 Application

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

HP UPS R1500 Generation 3

HP UPS R1500 Generation 3 HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications

More information

FX07 Field Controller

FX07 Field Controller Product Bulletin FX07 Field Controller Issue Date March 25, 2008 FX07 Field Controller The FX07 is a high performance field controller designed specifically for commercial Heating, Ventilating, Air Conditioning,

More information

T25 Two-Stage Room Thermostat

T25 Two-Stage Room Thermostat Installation Instructions T25 Issue Date 05/27/14 T25 Two- Room Thermostat Application Requirements T25 thermostats are for line- or low-voltage service requiring accurate control of two operating functions.

More information

TorqPlus TM Electric Valve Actuators and Controls

TorqPlus TM Electric Valve Actuators and Controls TorqPlus TM Electric Valve Actuators and Controls Torque 150 IN/LB 600 IN/LB The Engineered Solution Bettis TorqPlus quality line of electric actuators are designed for quarter turn applications ball,

More information

P70, P72, and P170 Series Controls for Dual Pressure Applications

P70, P72, and P170 Series Controls for Dual Pressure Applications P70, P72, and P170 Series Controls for Dual Pressure Applications Product Bulletin Code No. LIT-125455 Issued August 30, 2012 Supersedes September 1, 2000 The P70, P72, and P170 controls for dual pressure

More information

Powers Controls TH 192 S Single Temperature Room Thermostat

Powers Controls TH 192 S Single Temperature Room Thermostat Technical Instructions Document No. 155-065P25 TH 192-1 Powers Controls TH 192 S Single Temperature Room Thermostat 50 60 70 80 TH0355R1 70 80 POWERS Description The TH 192 S thermostats are proportional

More information

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL

N20xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL N2xxA, N34xxA NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR FLOATING AND 2-POSITION CONTROL SPECIFICATIONS Supply voltage N224A / N3424A N223A / N3423A PRODUCT DATA 24 Vac 15%, 5/6 Hz 23 Vac 15%,

More information

8146/5 Series Breaker Panelboards

8146/5 Series Breaker Panelboards 8146/5 Series Breaker Panelboards DISTRIBUTION BREAKER PANELBOARDS FOR HAZARDOUS & CORROSIVE ENVIRONMENTS Breaker Panels Features: Wide variety of Flameproof branch circuit breakers for Zone 1 & Division

More information

Product/Technical Bulletin

Product/Technical Bulletin EP-8000 eries Electro-Pneumatic Transducers convert a voltage or current signal from an electronic controller into a pneumatic output pressure signal. An increase or decrease in the input signal proportionally

More information

98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC.

98371000 REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN 46515 (574) 295-8330 FAX (574) 293-9914 2011 ELKHART BRASS MFG. CO., INC. 81471067 Electric Monitor Motor Control Panel For use with Model 8394059 SPIT-FIRE Monitor Installation, Operation, and Maintenance Instructions FOR ATEX APPLICATIONS 1302 WEST BEARDSLEY AVENUE P.O. BOX

More information

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description Samba OPLC SM35-J-R20 Installation Guide The Unitronics SM35-J-R20 offers the following onboard I/Os: 12 Digital Inputs, configurable via wiring to include: 1 HSC/Shaft-encoder Input, 2 Analog inputs (only

More information

LIEBERT VNSA Installation Sheet

LIEBERT VNSA Installation Sheet LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display

More information

Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE

Service Information CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS NOTE Service Information Calibration & Adjustments CALIBRATION PROCEDURE AND TROUBLESHOOTING FOR LINEAR GOVERNOR CONTROLLERS Part Number DYN1-10752-000-0-12/24 DYN1-10752-001-0-12/24* DYN1-10753-000-0-12/24

More information

Duct Humidity Transmitter

Duct Humidity Transmitter SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers

More information

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide

SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide SOLAR ELECTRIC MODULE ES-124 & ES-62T Owners Manual and Installation Guide circuit. Reverse connection will damage the module and may result in fire. CAUTIONS Solar electric modules produce DC electricity

More information

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY

PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY PS4-24 OWNERS MANUAL 24 VAC 90 WATT WALL MOUNTED CCTV POWER SUPPLY 7320 Ashcroft, Suite 104 Houston, Texas 77081 p: 713-772-1404 f: 713-772-7360 e: info@juicegoose.com www.juicegoose.com 06-06 CONGRATULATIONS

More information

Operator: Save these instructions for future use!

Operator: Save these instructions for future use! WHITE-RODGERS 36C01 Combination Gas Valves (24 Volt and 120 Volt Models) INSTALLATI INSTRUCTIS FAILURE TO READ AND FOLLOW ALL INSTRUCTIS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CTROL COULD CAUSE

More information

E-PDD Duct Smoke Detector Installation Sheet

E-PDD Duct Smoke Detector Installation Sheet E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating

More information

Table of Contents. www.hunterfan.com. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing.

Table of Contents. www.hunterfan.com. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing. www.hunterfan.com Table of Contents What to Expect with Your Installation 30 inches Hanging the Fan Wiring 8 Maintenance, Operation & Cleaning Light Kit 13??? 14 1 9 Troubleshooting 11 5 Blades Motor Housing

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

V46 Pressure-Actuated Water-Regulating Valve

V46 Pressure-Actuated Water-Regulating Valve V46 Pressure-Actuated Water-Regulating Valve Product Bulletin Code No. LIT-125687 Issued August 9, 2010 Supersedes October 1, 1995 The V46 pressure-actuated modulating valves come in two types of control

More information

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches DS 1.102 02/99 AIR ROOM TEMPERATURE SENSOR with fan speed control switches Specification No. 528-X-XXX* The Active Room Temperature sensor incorporating fan speed control switches is designed to give a

More information

V47 Series Temperature Actuated Modulating Water Valves

V47 Series Temperature Actuated Modulating Water Valves V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate

More information

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE 4 3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE A. Changing the Control Board B. Replacing a Heating Element C. Thermistor Replacement D. High Limit Switch Replacement E. Level Detector Replacement

More information

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit Installation Instructions This document provides instructions for the installation of a DC bus connector kit for PowerFlex 700S and 700H frame 12 drives

More information

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.

More information

Electri-SAFE DataFlo Digital Electronic Positioner Installation, Operation and Maintenance Instructions

Electri-SAFE DataFlo Digital Electronic Positioner Installation, Operation and Maintenance Instructions WCAIM2025 (Part 14944) Electri-SAFE DataFlo Digital Electronic Positioner Installation, Operation and Maintenance Instructions MODELS 15 DP 72 - DataFlo Positioner Mounted On 15-72 Electri-SAFE Actuator

More information

Fuel Injection Pump, Rotary (005-014)

Fuel Injection Pump, Rotary (005-014) Fuel Injection Pump, Rotary View Related Topic Page 1 of 30 Fuel Injection Pump, Rotary (005-014) Table of Contents Summary General Information Preparatory Steps Remove Front Gear Train Rear Gear Train

More information

HQ Series ¼ Turn Actuator

HQ Series ¼ Turn Actuator HQ Series ¼ Turn Actuator HQ-015 thru HQ-300 Installation & Maintenance Manual HQ Series I&M Manual HQ-400-1005 1 Table of Contents: General 1.0 Actuator Mounting 2.0 External Construction 3.0 Wiring Diagrams

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual

Introduction. Safety Guidelines. Part Numbers. Operation and Maintenance Manual. Operation and Maintenance Manual Operation and Maintenance Manual Introduction Read all instructions thoroughly. Installation of the OilTector must comply with all Federal, State and Local Codes, Regulations and Practices. The OilTector

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve

36G22, 36G23, 36G24 & 36G52 36J22, 36J23, 36J24 & 36J52 DSI and HSI Single Stage Combination Gas Valve Operator: Save these instructions for future use! FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE. DESCRIPTION

More information

T7560A,B,C Digital Wall Module

T7560A,B,C Digital Wall Module T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital

More information

INSTALLATION & SERVICE MANUAL. Display Panel

INSTALLATION & SERVICE MANUAL. Display Panel INSTALLATION & SERVICE MANUAL Display Panel The PowerLine EMS TM is a specialized power distribution and energy management system intended to be used in recreational vehicles. The Control Module is housed

More information

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual

PART 8: FIELD WIRING. n WARNING NOTICE. Boiler Manual PART 8: FIELD WIRING A. INSTALLATION MUST COMPLY WITH: 1. National Electrical Code and any other national, state, provincial or local codes or regulations. 2. In Canada, CSA C22.1 Canadian Electrical Code

More information

VG2000 Series Cast Iron Flanged Globe Valves

VG2000 Series Cast Iron Flanged Globe Valves VG2000 Series ast Iron Flanged Globe Valves Installation Instructions Part No. 14-1161-106, Rev. Issued November 15, 2013 Supersedes June 15, 2007 pplications VG2000 Series ast Iron Flanged Globe Valves

More information

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 Form No. 74-00-4001 S168-195-001 Revision E DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS 52 635.0 INTRODUCTION Allied Healthcare Products, Inc. s Digital Alarm

More information

ATS Overhead Table Shelf System INSTRUCTION MANUAL

ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship

More information

Contractors Guide Central Inverter System Installation

Contractors Guide Central Inverter System Installation Contractors Guide Central Inverter System Installation Step By Step Procedures 2,200 Watt/VA 6 Step Installation 1. Mount Bottom Cabinet 2. Mount Top Cabinet 3. Install Batteries 4. Install Conduit 5.

More information

TS93 EMR T/PT/TDE. Surface applied door closer

TS93 EMR T/PT/TDE. Surface applied door closer TS EMR T/PT/TDE Surface applied door closer Installation instructions: Pull side track mount door closer with smoke detector (EMR T) Push side track mount door closer with smoke detector (EMR PT) Double

More information

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE

SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE SECTION G2: CABLE PROCESSOR MODULE MAINTENANCE Cable Processor Module overview WARNING! When tipping the Cable Processor Module back, (after removing the toggle arm pin), use extreme caution not to drop

More information

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles Clear Glass Sensor Optimum Sensor for Detecting Transparent Glass and Plastic Bottles E3S-CR67/62 Retroreflective Sensor smoothly detects 5-mm gaps. Detects transparent bottles that have a lens effect.

More information