1 Unitary Products Group Voyager Commercial Packaged Rooftop Applications SUBJECT: Micro Controls with Voyager Ton Packaged Units The purpose of this bulletin is to answer common questions regarding the current Voyager Commercial Micro controls for stand-alone applications. In addition, the information provided will help in better understanding the value that Voyager commercial adds to the Voyager product line. The most frequently asked questions are presented in a question and answer format. Wiring ladder diagrams are included which depict the necessary wiring logic. Reference the most recent wiring diagrams prior to beginning any field modifications and consult local electrical codes for compliance. The Voyager Commercial micro controls has furthered the value of Voyager Light Commercial controls by providing many competitive and innovative product enhancements which are unique to the HVAC industry. It is a second generation of microprocessors which includes VAV capability and expanded constant volume features. Major control features that have been added to Voyager Commercial include, in part, the following: VAV Capability (Inlet Guide Vanes and VFD s) VariTrac Compatibility with TCI (constant volume only, not VAV) Ventilation Override (exhaust and pressurization mode) External auto stop User defined exhaust fan setpoint (0 to 100%) Compressor Lead/Lag Added Fan Failure Switch to UCP Remote Panel provides morning warm up on constant volume and VAV units Remote Panel provides supply air tempering on constant volume units Evaporator defrost controls which respond to coil temperature Two speed exhaust fans and added exhaust capacity Enhanced low ambient head pressure control as standard (cycle condenser fans) Thermal Expansion Valves External High head pressure switches for each compressor Adjustable position on the return air economizer damper In addition Voyager Commercial includes the proven performance and simplicity of the Voyager Light Commercial drum and tube heat exchanger with negative pressure gas valve. American Standard Inc Since The Trane Company has policy of continuous product improvement, it reserves the right to change specifications and design without notice.

2 TABLE OF CONTENTS Page Time Clocks & Start Up VAV Startup Time Clocks with VAV VAV Setpoint Control VAV Changeover Smoke Detection & Ventilation Override Smoke Detector Location Ventilation Override Ventilation Override (Purge) Economizer Control Strategies Energy Management Control Temperature Controls (General) Stand-alone VAV VAV Setpoint Range VAV Conversion Discharge Air Control Varitrac Compatibility VAV & Bypass Outside Air Compensation Compressor Lead/Lag When not to use CTI s Duct Heaters/Perimeter Heat Field Supplied Duct Heater Perimeter Heat Compressor Control Compressor Operation Coil Frost Protection Clogged Filter Switch Two speed Motors Low Ambient Control Cooling to zero Exhaust Fans Independent Exhaust Fans Smoke Purge Building Pressurization Control

3 Time Clocks & Start Up Question - How can the Voyager VAV start without a zone sensor? This is a temporary situation. Answer - LTB1-2 and LTB1-4 must be jumpered to enable the rooftop. It will become disabled when the jumper is removed. The rooftop is equipped with a factory installed supply air sensor and will control to the supply air setpoint. Question - What time clock features are available for Voyager VAV? Answer - A time clock contact can be installed between LTB1-11 and LTB1-12 (similar to light commercial Voyager). When contacts close, the unit operates as described below : Mechanical cooling is disabled, outside air damper will close and the fan goes into automatic mode. Inlet guide vanes (IGV) and boxes are forced opened during transition from occupied to unoccupied occurs. If a sensor is installed in the critical space (i.e. BAYSENS021A or BAYSENS013A (non - programmable)), heating can be enabled. If the zone temperature drops 10 degrees below the morning warm-up setpoint (MWUS) during unoccupied, heating will be enabled (down to a low limit of 50 degrees). If the factory installed MWUS is disabled, the heating default is 60 degrees. A sensor must be provided to enable heating functions. Question - How does the Voyager Commercial VAV control operate in conjunction with Tracer or a remote night set back panel during unoccupied mode? Answer - The inlet guide vanes will close when a transition from occupied to unoccupied cooling occurs. If the zone temperature rises above zone setpoint, cooling will be enabled and operates in constant volume mode (i.e. boxes open & IGV open). If the zone temperature drops below zone setpoint, heating is enabled and operates in constant volume mode. Unoccupied VAV heating and cooling setpoints are only available on Tracer or the remote setback panel. Question - Where does Voyager VAV connect electrically for heating change over, day time warm up or morning warm up? Answer - The boxes need to be wired into the VAV heating relay (VHR) contacts. These are shown on the wiring diagram as an inset. The terminals are LTB3-3,4 &5. Which terminal to use will depend on box type (i.e. normally open or normally closed). 3

4 Smoke Detection and Ventilation Override Question - Where can I install a smoke detector? Answer - One can install fire stats or smoke detectors on stand alone units at the external auto stop. When immediate shutdown is required, use the external auto stop feature including those systems under Tracer control. Auto shutdown will cause heat and cool Led's to blink. Unit will be reset if contacts close for 5 seconds. There are other locations (i.e. line voltage of transformer), however specifying and locating life safety controls is the design engineer s responsibility. See Figure 1: Figure 1 Question - How does the Voyager Commercial Ventilation override operate? Answer - In order to initiate ventilation override the field supplied "A" contacts must close. After initiation, the ventilation mode is determined by field supplied contact "B". An open circuit between LTB4-3 and LTB4-4 (i.e. B contact open) is exhaust ventilation. A closed circuit (i.e. B contact closed) is pressurization mode. Exhaust Pressurization Heat/Cool OFF OFF Inlet Guide Vanes Closed Open Supply Fan Off On Exhaust Fan On Off Outside Air Damper Closed Open Return Air Damper Open Closed VAV Boxes N/A Open 4

5 Question - My Engineer requires a ventilation over ride sequence similar to the IntelliPak purge. This is the same as the Voyager III pressurization control, however the exhaust fan is allowed to run. What is the best way to modify the unit for Purge operation? Answer - Field install a two pole single throw relay in parallel with the Ventilation Override relay (24 VAC). The relay contacts are wired in parallel with the line voltage XFR exhaust fan contacts. Economizer Control Strategies Question - I have an energy management system. How do I take control over economizer operation? Can this be accomplished by a 24 volt signal to the actuator? Answer - No. This is not recommended for VAV applications. Also it is not possible on constant volume (except with Tracer). A 24 volt signal will not modulate or control the actuator. However, it may be possible to remove the existing micro actuator and economizer controls and add a field supplied actuator for constant volume systems. This actuator (Belimo) has been installed successfully on Voyager Light Commercial units. Temperature Controls (General) Question - I have a stand alone cooling only VAV unit with economizer and power exhaust. What controller should I order? Answer - Standard factory controls (i.e. supply air sensor, discharge air set point, static pressure setpoint, reset setpoint, exhaust fan setpoint, morning warm-up setpont, reset amount, etc) are unit mounted. No other controls are required. At start up a short must be provided between LTB1-2 and LTB1-4. This will enable unit operation. Question - What are the adjustment ranges for Voyager Commercial VAV utilizing the potentiometer inputs? Answer - All potentiometers are rated at 0 to 1000 ohms and 1/4 watt. Values for various features are listed below: Morning warm-up set point - 50 to 90 degrees F Supply air Reset Amount - 0 to 20 degrees F Supply Static pressure set point -.3 to 2.5 inch w.c. Static pressure deadband -.2 to 1 inch w.c. The corresponding resistance vs. temperature or static pressure is listed on the next page. Note: Morning Warmup Set point is identical to Cooling Supply Setpoint. 5

6 Supply Air Cooling Setpoint Setpoint Nominal (Deg F) Resistance (Ohms) Nominal Resistance (Ohms) Setpoint (Deg F) Static Pressure Setpoint Static Pressure Nominal Setpoint(in. w.c.) Resistance (Ohms) Static Pressure Setpoint(in. w.c.) Nominal Resistance (Ohms) Question - Can a constant volume Voyager III be field converted to a VAV unit? Answer - No. Question - Engineer has specified a discharge air controller for Voyager Commercial VAV. Is this possible? Answer - Yes. The standard unit is equipped with discharge air control. However it is not possible to control Voyager VAV with a generic discharge air controller. The VAV unit is not compatible with C.T.I. s similar to constant volume units. Question - Is Voyager Commercial compatible with Varitrac? Answer - Yes. A constant volume unit should be ordered with a TCI interface. VAV units are not software compatible with Varitrac. 6

7 Question - I have a VAV system with constant volume bypass, similar to Varitrac. What control option is recommended? Answer - Order the Voyager III VAV unit without inlet guide vanes. Gas or electric heat units are not recommended for these applications. If the customer prefers their own controls, order a constant volume unit and install a CTI. For cooling only with two stages of control the Honeywell T7075B has been used successfully (Figure 2). Figure 2 Question - Does Voyager Commercial VAV include outside air compensation similar to IntelliPak? Answer - No. Question - Engineer has requested fully alternating lead/lag. Can I do this with the Voyager Commercial Micro? Answer - Yes, fully alternating compressor control is an option. Removing or cutting the wire at J1-7 on the UCP will enable lead/lag. It is advised to consider 1st and 2nd stage capacity control when using this option. As compressors lead/lag, the largest compressor can become 1st stage cooling. 40 & 50 ton systems (units with three compressors) alternate with 3 stages of cooling when the smallest compressor is lead. However when the lead compressor's are the largest, there will only be two stages of cooling. Units equipped with CTI's are limited to two stages of cooling. FIGURE 3 7

8 Question - When should I not use a C.T.I.? Answer - Voyager Commercial VAV will not work with a C.T.I.. Also vendor thermostats which use Triac outputs have created some problems. A C.T.I. will limit Voyager to two stages of cooling. Duct Heaters/Perimeter heat Question - How can I connect a field supplied duct heater to a cooling only Voyager Commercial unit? Answer - There is an isolated heat circuit on electric/cooling units, similar to Voyager Light Commercial, where a 75 volt/amp transformer can be added to accommodate additional power requirements and duct heat (figure 19). Field wiring and connectors must be provided as shown below. (See Figure 4) Figure 49 Question - I have a cooling only unit with perimeter heat in the zone. How can I enable fan operation when heating is required? Answer - Cut the wire going to J1-20 (See figure 4) on constant volume systems. If the unit is VAV, a zone sensor must be added. Compressor Control Question - How does the Voyager Commercial 40 and 50 ton units accomplish 3 stages of cooling? Answer - 1st stage is the smallest compressor (about one third of total capacity). 2nd stage de energizes 1st stage and enables the two manifolded compressors (about two thirds of total capacity). 3rd stage enables the smallest compressor. Question - What is the major difference between Voyager Light Commercial and Voyager Commercial compressor control? Answer - Voyager Commercial is equipped with direct sensing Froststats on each compressor circuit. 8

9 Fan Control Question - I have a customer who is currently using the clogged filter circuit on the Voyager Commercial micro. While he is satisfied that the micro will indicate a service problem, he is concerned that a broken belt or any fan failure may lead to compressor failure. Is there a way to lock out the unit in the event of a fan failure? Answer - Yes. This is a standard feature on Voyager Commercial. If the supply fan is enabled and the fan failure switch opens for more than 5 seconds then the supply fan is disabled and locked out, requiring a manual reset. The appropriate diagnostic will be communicated to Tracer and the Service LED will blink. Question - Is it possible to control a two speed motor with Voyager Commercial controls? Answer - No. The two speed option was removed with compressor lead/lag. However it may be possible to use inlet guide vanes (i.e. two position) in a constant volume application. Low Ambient Control Question - I have a computer room application which will require 100% of rated capacity at 0 F. Can this be accomplished with the Voyager Commercial micro? Answer - Depending on unit size, nominal capacity is 80 to 95% at zero degrees ambient. Since Voyager Commercial is equipped with either three or four condenser fans, additional head pressure control is not typically required. Head pressure control is accomplished by cycling two condenser fans based on outdoor temperature. This control will typically provide a minimum 198 psi head pressure which equals the control provided by add-on head pressure controls. The typical cycling sequence includes disabling compressors for 3 to 7 seconds in order to prevent condenser fan windmilling. Below is a typical condenser cycling schedule: 27.5 ton to 30 ton: 1st stage cooling - 3rd condenser fan is off when outdoor ambient is less than 90 F 2nd condenser fan is off when outdoor ambient is less than 70 F 2n stage cooling - 3rd condenser fan is off when outdoor ambient is less than 60 F 2nd condenser fan is off when outdoor ambient is less than -10 F 9

10 Exhaust Fans Question - A customer has independent exhaust fans. Can he utilize any of the micro features to control a separate power exhaust? Answer - Yes. The unitary economizer module (U.E.M) has a 24 Volt DC output which is utilized with the standard power exhaust (do not exceed 75 milli-amps). The same connection points may be utilized. The exhaust fan output will energize based on exhaust fan setpoint (i.e. 0 to 100%). The exhaust set point (i.e. on/off control) is adjusted by a 0 to 1000 Ohm potentiometer. The wiring interface will require ordering two BAYSENS016A thermistors. While the thermistor is not utilized the accompanying wiring harness and plug is. See the below wiring diagram. Question - I have a smoke purge sequence which will require the exhaust fans to go from low speed (factory setting is low speed) to high speed. How can I accomplish this with ventilation override? What is the exhaust fan capability in this mode? Answer - Add a field installed 24 VAC relay with contacts rated for line voltage ("R" 4PDT) in parallel with the ventilation override relay and wire as shown below. Exhaust fans will exhaust approximately 12,000 CFM on high speed and 10,000 CFM on low speed at zero return static pressure. 10

11 Question - Is Statitrac building pressure control available for Voyager Commercial? Answer - No. However some offices have used variations of the control shown on figure 5. Figure 5 11

Variable Air Volume - VAV

Variable Air Volume - VAV Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

Workshop 7 PC Software - Tracker

Workshop 7 PC Software - Tracker Workshop 7 PC Software - Tracker Goal: You will startup and perform advanced setup functions using Tracker PC software. You will also setup equations to control MP503 binary outputs. The Binary Output

More information

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps Operation and Maintenance Manual Model: 71028004 Applies to: Single Circuit Water-to-Water Twin Circuit Units Without DDC Controls MAMM WHSP

More information

Controller Operator Guide. VariTrac TM Central Control Panel VAV-SVU01A-EN

Controller Operator Guide. VariTrac TM Central Control Panel VAV-SVU01A-EN Controller Operator Guide VariTrac TM Central Control Panel VariTrac Central Control Panel Operation Guide This guide and the information in it are the property of American Standard Inc. and shall not

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong

More information

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU Automatic Temperature Control Diagnosis and Repair Diagnosis of Automatic A/C Systems The most common automatic A/C system malfunctions tend to be the result of basic air conditioning problems. These problems

More information

01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09

01-3 0000-00 6810-20 AIR CONDITIONING SYSTEM 1. FFH SPECIFICATION AIR CONDITIONING SYSTEM RODIUS 2004.09 0000-00 01-3 6810-20 1. FFH SPECIFICATION 01-4 0000-00 2. SYSTEM LAYOUT AND COMPONENTS 0000-00 01-5 01-6 0000-00 3. FFH GENERAL INFORMATION The system is to increase the coolant temperature quickly by

More information

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment

5.6 Technical Specification: Premium Efficiency Electric Air Conditioning Equipment 5.6 Technical Specification: Premium Efficiency Electric Conditioning Equipment Small Premium Project Type: For Premium Conditioning Retrofit Projects: Projects that voluntarily replace existing unitary

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

CONTROL STRATEGIES FOR HVAC SYSTEMS

CONTROL STRATEGIES FOR HVAC SYSTEMS CONROL SRAEGIES FOR HVAC SYSEMS ZBIGNIEW POPIOLEK Department of Heating, Ventilation and Dust Removal echnology Silesian University of echnology, Poland 1 Definition of control: to apply a regulating influence

More information

Tracker. Tracker Version 12 Building Automation System BAS-PRC010-EN. March 2008

Tracker. Tracker Version 12 Building Automation System BAS-PRC010-EN. March 2008 Tracker Tracker Version 12 Building Automation System March 28 BAS-PRC1-EN Introduction The Tracker Version 12 building automation system (BAS) is a heating, ventilating, and air conditioning (HVAC) energy

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

PNEUMATIC CONTROLS Selection and Description

PNEUMATIC CONTROLS Selection and Description PNEUMATIC CONTROLS Selection and Description Carnes pneumatic controlled throttling units are suitable for a standard 20 psi control system and may be supplied with pressure dependent or pressure independent

More information

HEAT HEAT COOL HEAT PUMP COOL

HEAT HEAT COOL HEAT PUMP COOL OWNER S MANUAL RESIDENTIAL THERMOSTAT P/N P374-1800 HEAT COOL HEAT PUMP Su AUTO 0I20: Pm 74 COOL HEAT 27 7-DAY MABLE DIGITAL THERMOSTAT 3 Configurable Outputs Accepts Optional Humidity Module: Control

More information

for Plans Examiners and Building Inspectors

for Plans Examiners and Building Inspectors Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared

More information

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function

HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function Specifications Supply Voltage 240VAC @ 0.07Amps or 24VAC @ 0.380Amps Relays 240V @ 12A max (resistive) / Comp1,2,3, Aux Ht, Rv O/B) Fuses (Equipment) 15 Amps Maximum 3AG Control Range Minus 10 to 50C Control

More information

TECHNICAL APPLICATION AND PROGRAMMING GUIDE

TECHNICAL APPLICATION AND PROGRAMMING GUIDE TECHNICAL APPLICATION AND PROGRAMMING GUIDE MILLENNIUM SINGLE PACKAGE ROOFTOP UNITS 25, 30 & 40 TON EQUIPPED WITH SIMPLICITY ELITE CONTROLS MILLENNIUM 25-40 TON SINGLE PACKAGE COMMERCIAL ROOFTOP UNIT EQUIPPED

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount

More information

Contents Contents Introduction... 1.1 Equipment... 2.1 Zone-All Control Systems Inc 10/2010

Contents Contents Introduction... 1.1 Equipment... 2.1 Zone-All Control Systems Inc 10/2010 Contents Contents Introduction... 1.1 The Starzone 4000 System... 1.2 SZM-4000 Master Controller... 1.3 SZT-4000 Thermostat... 1.3 Zone Dampers... 1.4 Bypass Damper... 1.4 Starcom Hub and Building Software...

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Air conditioning, electrical testing

Air conditioning, electrical testing just a test. Air conditioning, electrical testing 01-253 Wire and component test using VAG1598 A test box Special tools and equipment VAG 1598 A test box and VAG 1598/11 adapter cable and VAG 1598/12 VAG1526

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html

http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html http://waterheatertimer.org/how-to-troubleshoot-gas-water-heater.html APPLY POWER TO APPLIANCE FIELD WIRING CORRECT? DPLAY ERROR CODE 1 OR 2 Intelli-Vent TM Sequence of Operation REQUEST FOR HEAT PRESENT?

More information

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM

TAC I/NETTM MR-VAV-AX. Application Specific MicroRegulator TM TAC I/NETTM TM TAC s TM has an extensive range ofpre-engineered VAV control sequences, which combined with a fully integrated actuator and airflow transducer, makes it a low Total Installed Cost solution

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

CONTROLS KITS AND ACCESSORIES. 507240-01 12/2014 Supersedes10/2014

CONTROLS KITS AND ACCESSORIES. 507240-01 12/2014 Supersedes10/2014 2014 Lennox Industries Inc. Dallas, Texas, USA CONTROLS KITS AND ACCESSORIES 507240-01 12/2014 Supersedes10/2014 Litho U.S.A. Equipment Interface Module Installation Instructions for the Equipment Interface

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

Product Catalog BAS-PRC010-E4. Tracker Version 12 Building Automation System. August 2010

Product Catalog BAS-PRC010-E4. Tracker Version 12 Building Automation System. August 2010 Product Catalog Tracker Tracker Version 12 Building Automation System August 2010 BAS-PRC010-E4 Introduction The Tracker Version 12 building automation system (BAS) is a heating, ventilating, and air conditioning

More information

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008 Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE Table of Contents PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE # Electric Room Comfort Controller NEW! RDY2000 Room Comfort Controller RDY 129-905 D-3 Electric for Specialized Applications Surface

More information

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06 A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner

More information

Water-Source Heat Pump

Water-Source Heat Pump Application Jauary 1999 Water-Source Heat Pump Application Economizer (Optional) BO-6,7 Discharge Air Temperature (Optional) Heating/Cooling Coil AI-6 Outdoor Air Temperature (Optional) Aux Input AI-5

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

Installation Owner Diagnostics

Installation Owner Diagnostics Installation Owner Diagnostics Tracer ZN524 for water-source heat pumps Order No: CNT-SVX11A-EN Date: August 2003 CNT-SVX11A-EN Notice Notice Warnings and Cautions appear at appropriate sections throughout

More information

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C Installation TURN OFF POWER TO THE SYSTEM AT THE MAIN POWER PANEL TO AVOID ELECTRICAL SHOCK. Installation should be carried out by an electrician or a qualified technician. 1.1 Find a Location for the

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

Packaged Cooling with Electric Heat Rooftop Units

Packaged Cooling with Electric Heat Rooftop Units Packaged Cooling with Electric Heat Rooftop Units Voyager 12½ - 25 Tons - 60 Hz December 2003 RT-PRC002-EN Introduction Voyager TM... a proven performer built to provide ultimate indoor comfort. Voyager

More information

Bring the fresh in. Dedicated Outside Air Systems

Bring the fresh in. Dedicated Outside Air Systems Bring the fresh in. Dedicated Outside Air Systems The inside story on outside air. On average, we breathe in 3,400 gallons of air each day. Ambient indoor air pollution is a major problem, affecting health

More information

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT

48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT 48/50E-4SB 48/50EJ,EK,EW,EY038, 044, 048 SINGLE-PACKAGE COOLING UNITS VARIABLE VOLUME CONSTANT VOLUME FACTORY-INSTALLED OPTIONAL HEAT GAS HEAT ELECTRIC HEAT PERFORMANCE DATA CERTIFIED DIMENSION PRINT CERTIFIED

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

February 1, 2006. Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure

February 1, 2006. Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure February 1, 2006 Performance Tested Comfort Systems Air Source Heating Pump Installation Commissioning Procedure Overview - Several measurements of air source heat pump system performance are required

More information

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7

Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7 THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3

More information

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify

Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2

More information

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596

Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital

More information

MP-4000 Alarm List (Software version 2.4.3 or later)

MP-4000 Alarm List (Software version 2.4.3 or later) Service Bulletin SUBJECT: MP4000 Alarm s BULLETIN: C 100 DATE: June 19, 2013 ALARM LIST Where it is possible the alarm number is kept the same as for MP-3000. MP-3000 holds alarm number from 0 to 127.

More information

Digi-Motor Installation Guide

Digi-Motor Installation Guide Digi-Motor Installation Guide Installation Video...located at marsdelivers.com Digi-Motor Installation Guide Digi-Motor For technical assistance with your Azure Digi-Motor, call the MARS technical support

More information

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

HVAC and Lighting Control Products for Open Building Automation Systems

HVAC and Lighting Control Products for Open Building Automation Systems HVAC and Lighting Control Products for Open Building Automation Systems Distech Controls offers an extensive line of feature-rich and cost effective controllers for building automation, covering HVAC

More information

DATA AIRE, Inc. MINI DATA ALARM PROCESSOR II

DATA AIRE, Inc. MINI DATA ALARM PROCESSOR II DATA AIRE, Inc. MINI DATA ALARM PROCESSOR II Operation and Maintenance Manual Precise Temperature and Humidity Control Air and Water/Glycol Cooled and Chilled Water TABLE OF CONTENTS INTRODUCTION... 1-5

More information

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60

ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 ModPac II 1 to 5-Ton Vertical Wall Mount Air Conditioners Models AVPA12-20-24-30-36-42-48-60 General Description The Marvair ModPac II air conditioner is a vertical, wall mounted, cost effective air conditioner

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Impact of Control System Technologies on Industrial Energy Savings

Impact of Control System Technologies on Industrial Energy Savings Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110

More information

Air Conditioning System

Air Conditioning System Air Conditioning System 1 Chonan Technical Service Training Center Chonan Technical Service Training Center 2 Objectives To understand the components of air conditioning system. To understand the control

More information

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM

AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM SECTION 7D AUTOMATIC CONTROL HEATING, VENTILATION AND AIR CONDITIONING SYSTEM TABLE OF CONTENTS Description and Operation... 7D- General... 7D- FATC Control... 7D- FATC Input/Output Routing Diagram...

More information

MicroTech III Unit Controller for Water Source Heat Pump Units

MicroTech III Unit Controller for Water Source Heat Pump Units Operation & Maintenance Data OM 931-1 Group: WSHP Part Number: 910100893 Date: April 2009 MicroTech III Unit Controller for Water Source Heat Pump Units 2009 McQuay International Table of Contents Introduction...

More information

Using Time-of-Day Scheduling To Save Energy

Using Time-of-Day Scheduling To Save Energy The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved

sip Sanyo Modbus Guide Technical Specification Pinouts, Cable Connections & Wiring Issue 2: February 2009 Synapsys Solutions Ltd, all rights reserved Sanyo Section : Section : Section : Section : Section : sip Modbus Guide Configuration Modbus Table Technical Specification Pinouts, Cable Connections & Wiring Alarm Fault Codes Issue : February 009 Section

More information

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system

Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system AURETU004 Application Competency Field Unit Sector Elements Elements describe the essential outcomes. 1. Prepare to diagnose and repair air conditioning and HVAC system 2. Diagnose air conditioning and

More information

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E.

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E. Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E. Basic Thermostat Types Many technicians have great difficulty understanding how to properly wire a thermostat or how to replace a thermostat with

More information

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ TSQ--0 7-7-07 T Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T SQ Model Configuration T SQ- Heating / Cooling Border Type (Lay-In) Full Face Nominal Round Duct Size

More information

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW

CCH/CCW, VFC/VFW, MHC/MHW, LVC/LVW Operation & Maintenance Manual OM 931-6 Group: WSHP Part Number: 910157590 Date: September 2014 MicroTech III Unit Controller for Water Source Heat Pump Units Used with Enfinity Models CCH/CCW, VFC/VFW,

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

Section 6. Introduction to Automatic A/C. Automatic Temperature Control

Section 6. Introduction to Automatic A/C. Automatic Temperature Control Automatic Control Introduction to Automatic A/C The heating, ventilation and air conditioning (HVAC) system in a house contains a wall-mounted thermostat to control outlet temperatures, distribution and

More information

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Chapter 5 Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams Objectives Upon completion of this course, you will be able to: Explain what electrical loads are and their general purpose

More information

Installation & Operation Manual for Energenics Air-Flow Optimizer

Installation & Operation Manual for Energenics Air-Flow Optimizer 1470 Don Street Naples, Florida 34104 Telephone: (239) 643-1711 Fax: (239) 643-6081 Customer Service: (800) 944-1711 Installation & Operation Manual for Energenics Air-Flow Optimizer Table of Contents

More information

Smart Thermostat page 1

Smart Thermostat page 1 Smart Thermostat page 1 3. APPROACH In today s home appliances market, automation is becoming the norm and Smart Thermostat is a typical automation appliance able to be applied easily at home. With Smart

More information

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY

SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY RV Products Division SERVICE MANUAL FOR 12 VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOF TOP UNITS ONLY Airxcel, Inc. RV Products Division P.O. Box 4020 Wichita, KS 67204 1976A376 (1-11) TABLE OF CONTENTS

More information

STANDARD COMMISSIONING PROCEDURE FOR PACKAGED HEAT PUMP (AIR-TO-AIR) & AIR CONDITIONING UNITS

STANDARD COMMISSIONING PROCEDURE FOR PACKAGED HEAT PUMP (AIR-TO-AIR) & AIR CONDITIONING UNITS STANDARD COMMISSIONING PROCEDURE FOR PACKAGED HEAT PUMP (AIR-TO-AIR) & AIR CONDITIONING UNITS BUILDING NAME: APPLICATION #: BUILDING ADDRESS: NAME & FIRM OF PERSON(S) DOING TEST: DATE(S) OF TEST: General

More information

Electronically Controlled Clutchless or Variable Drive Compressors

Electronically Controlled Clutchless or Variable Drive Compressors Electronically Controlled Clutchless or Variable Drive Compressors On many new air conditioning systems, such as Lexus, Cadillac, Chrysler, and others, a new type of compressor has been fitted. There are

More information

Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History

Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems. History Proper Applications & Sequences for Constant Volume Pressure Dependent Zoning Systems Ryan R. Hoger, LEED AP 708.670.6383 ryan.hoger@tecmungo.com History VAV systems came into favor for mid and large size

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

Technical Information

Technical Information Date of last update: Oct-11 Ref: D7.8.4/1011/E Application Engineering Europe CORESENSE DIAGNOSTICS FOR STREAM REFRIGERATION COMPRESSORS CoreSense Diagnostics for Stream Refrigeration Compressors... 1

More information

TSB #: 74 Date: 9/7/2013 HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS

TSB #: 74 Date: 9/7/2013 HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS HOLDEN VE/WM HVAC & A/C DIAGNOSTIC HINTS TSB #: 74 Date: 9/7/2013 Initial Once Read: In this technical bulletin we have listed diagnostic advice relating to the Holden VE/WM HVAC & A/C system. This information

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

FTQ. Daikin Inverter Ducted Heat Pump

FTQ. Daikin Inverter Ducted Heat Pump FTQ Daikin Inverter Ducted Heat Pump A TRADITIONAL CENTRAL AIR SYSTEM MADE BETTER WITH DAIKIN CONSTANT COMFORT INVERTER TECHNOLOGY. The Daikin Inverter Ducted Heat Pump line is a cost effective alternative

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype SPLIT TYPE ROOM AIR CONDITIONER INVERTER. Models Indoor unit Outdoor unit AOU 9RLFW AOU12RLFW AOU15RLS SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASU 9RLF ASURLF ASU5RLS AOU 9RLFW AOURLFW AOU5RLS R40A CONTENTS. DESCRIPTION OF EACH CONTROL

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Programming Logic controllers

Programming Logic controllers Programming Logic controllers Programmable Logic Controller (PLC) is a microprocessor based system that uses programmable memory to store instructions and implement functions such as logic, sequencing,

More information

Controls for fan coil units and cassettes

Controls for fan coil units and cassettes Controls for fan coil units and cassettes Selection of controls for use with fan coil & cassette units. Stand alone, selection guide Control unit Motor Standard QZAZ-04-10 QZAZ-04-20 QZAZ-04-75 QZAZ-05-11

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

Infinity/ Evolution Troubleshooting Guide User Interface Software Ver. -03, -05, -06, -08, -10 and -12. Table of Contents

Infinity/ Evolution Troubleshooting Guide User Interface Software Ver. -03, -05, -06, -08, -10 and -12. Table of Contents Software Revs 3,5,6,8, 10, 12 Infinity /Evolution Troubleshooting (Rev. 2) 10/12/2006 Infinity/ Evolution Troubleshooting Guide User Interface Software Ver. -03, -05, -06, -08, -10 and -12 Table of Contents

More information

MicroTech III Unit Controller for Water Source Heat Pump Units

MicroTech III Unit Controller for Water Source Heat Pump Units Operation & Maintenance Data OM 931-3 Group: WSHP Part Number: 669479403 Date: May 2012 MicroTech III Unit Controller for Water Source Heat Pump Units 2012 McQuay International 800.432.1342 www.daikinmcquay.com

More information

SERVICE MANUAL REFRIGERATION

SERVICE MANUAL REFRIGERATION SERVICE MANUAL REFRIGERATION ELECTROLUX HOME PRODUCTS S.p.A. Publication no. Spares Operations Italy 599 36 16-90 Corso Lino Zanussi, 30 031117 I - 33080 PORCIA / PN (ITALY) ITZ/SERVICE/AA Fax +39 0434

More information

INSIDE WDDCMON. User s Guide for the ENVIRO-TEC DDC Control System Windows Based Software

INSIDE WDDCMON. User s Guide for the ENVIRO-TEC DDC Control System Windows Based Software INSIDE WDDCMON User s Guide for the ENVIRO-TEC DDC Control System Windows Based Software Stock ID: WDDCMON August, 1997 1997 Environmental Technologies, Inc. Largo, FL Contents Getting Started 1 Minimum

More information

UA-NJ Air Conditioning & Refrigeration Division Training Curriculum

UA-NJ Air Conditioning & Refrigeration Division Training Curriculum UA-NJ Air Conditioning & Refrigeration Division Training Curriculum 1st Year Basic Mathematics for HVAC Using formulas as an expression of logical sequence in solving problems. Measuring using a ruler

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

NSN 4120-01-21 4-3692

NSN 4120-01-21 4-3692 *TM 9-4120-388-14 TECHNICAL MANUAL Operator s, Unit, Direct Support, And General Support Maintenance Manual AIR CONDITIONER, VERTICAL, COMPACT, 18,000 BTU/HR 208 VOLT, 3 PHASE, 50/60 HERTZ NSN 4120-01-21

More information

ELECTRIC POSITION for electric heat, then confirm with Fan Test below.

ELECTRIC POSITION for electric heat, then confirm with Fan Test below. Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please

More information

Basic Technology Series

Basic Technology Series Basic Technology Series Fundamentals of Car Air Conditioning 2007 Air Conditioning #003 The Rear Cooler Construction Fan Fan Filter Figure A : Trunk Figure B : Overhead Dual Air-Conditioner In This Issue

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information