FIRE DETECTION AND ALARM SYSTEM SECTION A. Refer to Section 16010, Electrical General Requirements.
|
|
- Darrell Nelson
- 7 years ago
- Views:
Transcription
1 FIRE DETECTION AND ALARM SYSTEM SECTION PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. Refer to Section 16010, Electrical General Requirements. 1.2 WORK INCLUDED A. Fire Detection and Alarm System including test and operational check of the system. 1.3 RELATED WORK A. Section 16050: Basic Construction Materials and Methods. 1.4 SUBMITTALS A. Manufacturer's literature describing product. B. Shop drawings of Control Panel showing all modules and/or components exactly as located within the Control Panel. C. Point to point wiring diagrams showing all devices and each conductor identified in accordance with identification details shown on drawings. D. Internal connection of components and of the Control Panel. E. Operation and Maintenance manuals. F. Floor plans, drawn to scale, showing device layouts, conduit routing and number of cables or conductors. G. Battery sizing calculations. H. Voltage drop calculations for alarm notification circuits. 1.5 CODES AND STANDARDS A. The System and all the devices shall be U.L. and Factory Mutual approved.
2 B. The installation shall comply with the latest edition of the following National Fire Protection Association Standards except where more stringent requirements are specified: 1. NFPA 70: National Electric Code, Article NFPA 72: National Fire Alarm Code. 3. NFPA 90A: Installation of Air Conditioning and Ventilation Systems. C. Uniform Building Code (UBC). D. Uniform Fire Code (UFC). E. The installation shall comply with the Americans with Disabilities Act of 1990 (ADA). 1.6 GOVERNMENT AGENCY APPROVAL A. The installation, including plans and material list shall require the review and approval by: 1. Local Fire Department. 2. State Fire Marshall's office. B. A walk-through of the building with the City Fire Inspector will be conducted by the Fire Alarm Contractor and attended by Owner just prior to the interior walls being finished and after rough-in conduit work is complete. The purpose of the walkthrough is to pick up any changes or additions desired by the Fire Inspector. 1.7 OPERATIONAL TEST & START UP See Part 3, Article 3.5 PART 2 PRODUCTS 2.1 GENERAL SYSTEM REQUIREMENTS
3 A. This specification outlines the requirements for a microprocessor based, electrically supervised, single stage, addressable fire detection and alarm system. The Contractor shall provide a complete, functional, tested fire detection and alarm system including all materials not specifically mentioned in the Specification but necessary for proper performance and operations. B. Major components of the system include but are not limited to the following: 1. Central Control Panel including power supply, standby battery, battery charger and all required control devices. 2. Alarm initiating devices include smoke, heat, and waterflow detection devices and manual activation (pull down) stations. 3. Alarm notification devices include horns, strobes and combination horn/strobes. 4. Hard-wired outputs for control of other related equipment or systems. 5. Supervisory functions for fire sprinkler system valve switches, system wiring (open/grounded) and detection device degradation. 6. Remote annunciation. C. The System shall provide the following features: 1. The system shall have a maximum capacity of 250 monitoring points and shall be expandable to the maximum capacity without additional cabinets. 2. The system shall be programmable using a standard on-site laptop computer or a panel mounted keypad with password security, user defined. Programmed information shall be stored in non-volatile memory. 3. The system shall automatically indicate the total quantity of alarms and of troubles which have occurred prior to reset at the control unit. 4. It shall not be possible to reset the system until all alarm and trouble signals have been acknowledged. 5. The system shall be capable of: a. Counting the number of addressable detectors within a "zone" which are in alarm. b. Counting "zones" which are in alarm. c. Counting the total number of addressable detectors which are in alarm.
4 d. Differentiating among types of addressable detectors such as smoke detectors, manual stations, water-flow switches and thermal detectors. e. Cross-zoning. D. System Function: 1. Activation of any manual station shall: a. Sound evacuation horns continuously and flash visual devices (strobes) with no time-out. Annunciator display shall remain active until the activated device is restored to normal and the system is reset. b. Flash system alarm lamp at the control panel. Acknowledgement of the alarm by operation of the silence switch shall silence the audible alarm and cause the alarm lamp to light steadily. Receipt of subsequent alarms shall cause the audible devices to sound and the alarm lamp to flash. c. Display individual detector and/or zone number on alpha-numeric display with user defined message. d. Close fire doors and unlock security doors as shown. e. Automatically notify the off-site 24 hour Central Station. f. Automatically notify the on-site Central Station. 2. Activation of any automatic fire sprinkler water flow switch shall cause functions specified for manual stations and sound sprinkler riser bell. 3. Activation of any duct mounted smoke detector shall cause functions specified for manual stations and shut down fans and operate dampers as shown. 4. Activation of any ceiling mounted smoke detector shall cause functions specified for manual stations and perform related functions as shown on drawings. In addition, smoke detectors in elevator lobbies shall also signal the elevator recall system. 5. Activation of any thermal detector shall cause functions specified for smoke detectors. 6. Activation of any supervisory switch for automatic fire sprinkler valves shall: a. Sound audible alert at the control panel. b. Indicate individual valve at the alphanumeric display with user defined message. c. Indicate valve operations as a distinct function. Circuit trouble shall not be used for valve supervision. d. Automatically notify the off-site 24 hour Central Station.
5 e. Automatically notify the on-site Central Station. 7. Failure of any circuit supervised by the Fire Alarm system shall: a. Indicate the nature of the trouble at the alphanumeric display. b. Automatically notify the Central Station of trouble condition. c. Automatically notify the on-site Central Station. 8. Audible and visual trouble indications at the control panel shall be caused by: a. Removal of a detection device from a detector circuit. b. An open circuit or ground fault in a detector circuit. c. An open circuit, short circuit, or ground fault in an audible/visual signal circuit. d. Internal faults and failures within the system. 9. Failure of AC power shall: 2.2 ACCEPTABLE PRODUCTS a. Cause a trouble indication at the Control Panel. b. Cause automatic transfer to the standby battery and maintain system operation for 60 hours 48. c. Notify the on-site Central Station. A. Products by Cerberus Pyrotronics, Edwards or Simplex, conforming to these specifications are acceptable. Other products must be pre-qualified by Owner for consideration. 2.3 CONTROL PANEL A. The Control Panel shall be composed of plug-in modules factory interconnected to meet the specific installation requirements. All electrical connections shall be front access through the hinged door and removable dead front panel. All indicating lamps shall be light emitting diodes (LED). B. The control panel shall be of modular construction for ease of expansion and servicing. Each individual function shall be on a replaceable plug-in panel or module to accommodate functional changes when required. All plug-in modules and panel connectors shall be supervised so as to give a trouble signal if removed or disconnected.
6 C. The Control Panel shall operate from a two-wire 120 VAC supply, and internal 24V back-up battery. See 2.4. D. The Control Panel shall contain equipment and modules for specified functions including but not limited to the following: 1. Alarm initiating cards, appropriate for type of devices connected, shall provide separate, electrically supervised alarm initiating zones as shown on the plans. The wiring for the alarm initiating devices up to and including the alarm relay coil shall be supervised against an open circuit fault condition. Operation of an initiating device shall cause an individual red zone LED to lock on and shall provide an alarm output to other sections of the control unit. Circuitry shall be provided to connect remote annunciators. 2. Each alarm initiating circuit shall be provided with an individual amber trouble lamp to indicate the location of any faults in the wiring to initiating devices. Fault conditions shall light the common trouble LED and sound the trouble buzzer. 3. The control panel shall be equipped with a march time coding module to provide a common, continuously pulsed output of approximately 84 pulses per minute to all audible alarm circuits. 4. Each alarm notification shall be provided with an individual zoned amber trouble LED circuit to indicate the location of any faults in the wiring to the audible/visual signals or signal circuit fuse. 5. LED test: The control unit alarm and trouble lamps may be tested to locate a failure by depressing the lamp test pushbutton. 6. When the alarm initiating devices have been restored the system control shall be reset by depressing a single reset pushbutton. 7. A green "power on" indication on the panel for each separate source of 120V AC input power. 8. Trouble indication: An amber trouble lamp and distinctive audible signal which shall operate when any of the specified supervised trouble conditions exist. The audible portion of the trouble signal shall be silenced with a "trouble silence" pushbutton. The trouble signal and indication shall automatically reset to normal when a trouble condition is corrected. 9. Ground Detection: A ground fault shall sound a trouble signal and illuminate an amber "ground fault" indication on the panel.
7 10. Program Control: If needed, a diode matrix shall be provided to program audible signal circuits and auxiliary relays to alarm receiving circuits individually or in groups in accordance with the system function schedule on drawings. The program control shall be reprogrammable to allow any signal circuit or auxiliary relay to be reprogrammed to any alarm initiating circuit to accommodate any changes in the zoning schedule without removing the panel from the premises. 11. Remote Annunciation: a. Each zone module as well as common system trouble shall be remotely annunciated at the Building Fire Alarm Annunciator as specified hereafter. b. In addition, each zone module or auxiliary relay integral with fire alarm panel, shall provide contacts for use by the site and/or any other remote fire alarm annunciator panel(s) including off-site Central Station(s). 2.4 BATTERY, BATTERY CHARGER AND BATTERY CABINET A. The back-up battery shall have capacity for at least 60 hours of operation. Provide battery calculations for standby and alarm conditions to comply with duration requirements of local Fire Marshal. B. Unless indicated otherwise on drawings, the battery charger shall be integral with the power supply module located within the fire alarm panel. The power supply module shall include trouble indicators as follows: - External Power Monitor - Charger (Supervision of Charger Voltage to the Battery) - Battery Low/Card Out - Ground Fault - AC Pilot Battery cabinet shall have the following features: - Built-in battery tester with load for dynamic type testing of batteries - Charge Current Meter - Battery Terminal Voltage Meter - Pre-drilled Holes for Wall Mounting - Piano Hinged Door - Accessible Battery Connectors 2.5 ALARM INITIATING DEVICES
8 A. Manual Station: Non-code, individually addressable, single-action non-breakglass type equipped with key operated test-re-set lock and terminal strip. The stations shall be so designated that after actual emergency operations they cannot be restored to normal except by authorized personnel. Stations shall be red-faced, flush mounted with operating instructions on the cover. B. Smoke Detectors: Unless indicated otherwise on the plans, space smoke detectors shall be dual chamber ionization type. The combination detector head and twist-lock base shall be U.L. listed. The base shall, when required, include auxiliary SPDT relay contacts. The base shall be appropriate for either the ionization or Photoelectirc detector. The detector shall have a flashing status indicating LED for visual supervision of normal conditions and latch on steady with full brilliance when activated. Field adjustments of the sensitivity shall be possible. The addressable interface base shall be part of the assembly. C. Duct Smoke-Detectors: Similar to smoke detectors but with duct mounted housing and sampling tubes. Provide auxiliary relays to control HVAC system. 120 Volt input unless noted otherwise. Provide weatherproof enclosure in wet locations. Provide remote reset on wall as shown. D. Automatic Sprinkler Flow Switches and Valve Switches: Switches shall be furnished and mechanically installed under another section of these Specifications. All material and labor required to connect the switches to the fire alarm system as indicated on the plans shall be provided under this Section of the Specifications. Provide interface device to make each switch an individually addressable device. 2.6 ALARM NOTIFICATION DEVICES A. Alarm Horn: 24 VDC, flush or surface mounted as indicated on drawings, with sound output of 92 dba at 10 feet. B. Visual Alarm: 24 VDC Xenon strobe white lens with "FIRE" lettering. Strobe shall have 8000 peak candlepower and a minimum of 1 flash per second but not exceeding 3 flashes per second. Provide sync module. C. Combination Horn and Strobe: Where indicated on drawings combination horn and strobe shall be installed. Provide sync module. D. Sprinkler Flow Alarm Bell: 10" diameter, 24V DC weatherproof, vibrating type. Pyrotronics MBDC-10 Series or equal with matching backbox. 2.7 FIRE ALARM TERMINAL CABINET (FATC)
9 A. Provide FATC's where indicated on drawings. Wiring to fire alarm system devices associated with that area shall be terminated in the FATC before extending to the Control Panel. B. The FATC shall be provided with double row terminal blocks suitable for terminating wires #22 to #12 AWG, complete with terminal marking cover strips. Where adjacent terminal blocks are jumpered together standard plug-in jumpers shall be used. 2.8 BUILDING FIRE ALARM ANNUNCIATOR A. Pyrotronics RA Series or equal. The annunciator shall have a window for each initiating zone module in the Control Panel, common trouble window, sonalert buzzer, sonalert silencing switch and lamp test switch. Sonalert shall sound whenever any window is lit. The silencing switch when operated shall silence the sonalert but not reset the alarm. Reset shall be possible at the fire alarm panel only. PART 3 EXECUTION 3.1 GENERAL A. Install and connect equipment in accordance with manufacturer's recommendations unless where more stringent requirement is specified. B. All equipment that must be serviced, operated or maintained shall be located in fully accessible locations. C. Equipment, device and raceway locations shown on the drawings are diagrammatic. Coordinate actual location with the Architectural elevations and other trades. D. Final connections shall be done under supervision of equipment manufacturer's field representative. 3.2 INSTALLATION OF DEVICES A. All devices shall be provided with back boxes, flush, surface, cast or weather proof, appropriate for the location: B. Boxes for devices flush mounted in steel wall shall be 4" x 4" square with a sheet rock ring that meets the device requirements, 1 or 2 gang. All device boxes shall be secured to the metal studs using a side bracket.
10 C. All strobes and horn/strobes shall be mounted at 6'8" A.F.F. or 6" below the ceiling, whichever is lower. Before installing devices, confirm that the view of the strobes will not be obstructed by equipment, structure, etc. Contact the Architect for an alternate mounting location if obstructions are found. 3.3 WIRING A. All wiring shall be installed in conduit. The system shall be free from grounds, open and short circuits. Splices shall be allowed only in junction boxes, utilizing crimp type wire connectors and shields made continuous at the splice. B. All wires shall be identified at each terminal, splice and/or in each outlet. Use Brady Datab or similar devices. C. Wires shall be solid copper and listed (U.L. 2464) for use as fire alarm cable. Unless otherwise indicated on drawings minimum size shall be as follows: 1. Alarm initiating circuits: #16 AWG. 2. Alarm notification circuits: #14 AWG. 3. Annunciator wires: #16 AWG. 4. When installed in underground conduits: All circuits shall be #12 AWG minimum. 5. Wiring for smoke detectors shall be shielded type if required by equipment furnished volt DC power supply circuit: #12 AWG. D. Wires within the Control Panel and relay panels shall be run in slotted plastic wire duct. T&B nylon ty-wraps and anchor blocks are acceptable where space is limited. 3.4 PROGRAMMING A. The Contractor shall be responsible for programming and configuring the fire alarm system to meet the operational requirements as specified above. B. The Owner will review and approve the program before it is installed. 3.5 OPERATIONAL TEST AND START-UP
11 A. Each device shall be tested per the manufacturer's recommendations. When a device passes the prescribed test the Contractor shall initial that device on the device database. When the database is completely initialed a copy shall be given to the City Fire Inspector and the Owner. B. Each test shall provide an alarm giving device identification information to the Control Panel. Submit a copy to the Owner. C. Check initiating circuits to sprinkler flow and tamper switches. Check initiating circuits to pre-action system alarm pressure and low air switches. D. Check output circuits to pre-action release solenoids and smoke damper release modules. E. Check smoke detector initiating circuits associated with magnetic door holders. Check door release circuits. Confirm that doors close and latch when released. F. Perform a test of each area of the building, the result of which shall be zero trouble and zero alarms. This test shall be complete one week prior to occupancy. If any trouble or alarms occur, the problems shall be corrected an the test repeated until it passes. 3.6 TRAINING A. Allow four (4) hours of factory service engineer's time for training Owner's personnel in use, service and maintenance of the fire alarm system. B. Schedule the training session three (3) weeks in advance with the Owner. END OF SECTION
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
More informationFIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
More informationSECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
More informationDTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
More informationFLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
More informationFIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
More informationFire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEM
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
More informationDesign and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS
More informationFIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus
More informationPLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
More informationCITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
More informationNC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
More informationSECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION
SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled
More informationC. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
More informationSECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
More informationFire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
More informationSPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
More informationDORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationHERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
More information1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
More informationFA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February 2013. FA-300 SERIES Fire Alarm Control Panel
ABC DEF GHI JKL MNO PQR STU YZ WXY FA-300 Series LCD Fire Alarm Control Panel Advanced Life Safety Solutions System Normal 10:36AM WED 2003-10-01 SYSTEM RESET A.C. ON ALARM SUPV TRBL CPU FAIL SIGNAL SILENCE
More informationSECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM
KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as
More informationFIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
More informationFIRE DETECTION AND ALARM
FIRE DETECTION AND ALARM GENERAL INFORMATION 1.1 In general, follow the guidelines below when designing and specifying addressable fire alarm systems. Unless specifically indicated otherwise, these guidelines
More informationSECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM
SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS
More informationA. This Standard outlines the requirements for an addressable fire detection and alarm system.
1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and
More informationSECTION 16700 FIRE ALARM SYSTEM
SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the
More informationSFC-200 SERIES LCD FIRE ALARM PANEL
SFC-200 SERIES LCD FIRE ALARM PANEL User Guide LT-954SUM SFC-200 Series LCD Version User Guide Contents Introduction... 1 About this Manual... 1 Technical Support... 1 Main Display... 1 The Buzzer and
More informationSECTION 16620 FIRE ALARM SYSTEM
SECTION 16620 PART 1 GENERAL FIRE ALARM SYSTEM 1.01 SUMMARY A. Work included: Labor, materials and equipment necessary to complete the installation required for the item specified under this Division,
More informationDELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
More informationHONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)
HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT
More informationFire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
More informationSFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description
SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped
More informationMODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE
DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000
More informationFIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
More informationENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
More informationCity of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
More informationBELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
More informationFIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
More informationSection 13850 Fire Detection and Alarm Page 1 of 13
SECTION 13850 - FIRE DETECTION AND ALARM 1.1 APPLICABLE STANDARDS A. Fire detection and alarm systems shall be designed and installed in accordance with the following standards, including appendices (current
More informationHM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
More informationJULY 2013 UCB STANDARDS 16720-1
SECTION 16720 FIRE ALARM AND DETECTION SYSTEMS PART 1 GENERAL 1.01 Reference A. Related Sections 1. Section 15300 Fire Protection 2. Section 15950 Controls 3. Division 16 Electrical 4. Division 14 - Conveying
More informationFire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?
5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,
More informationFIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
More informationINTRUSION DETECTION SYSTEM Section 281600
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
More informationModule 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
More informationSECTION 28 31 00 FIRE DETECTION AND ALARM
SECTION 28 31 00 PART 1 - GENERAL 1.1 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the fire alarm equipment to form a complete coordinated
More informationFIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
More informationSECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification
More informationFIRE ALARM SYSTEM Section 16750 Page 1
FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract
More informationAll work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
More informationFIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
More information16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC
1. GENERAL 1. Fire alarm system shall be manufactured by Simplex, Autocall or Edwards. Simplex part numbers are provided in this spec for clarification only and do not exclude equivalent part numbers of
More informationSECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.
More informationFIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
More informationTelluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
More informationFIREDEX 2200. Conventional Fire Panels
68 Flexible, high specification system Choice of 1, 2, 4 or 8 zones Simple one-shot auto-reset user test facility Approved to EN54 Maintenance free poly switch circuit protection, with auto reset Class
More informationSARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
More informationFIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
More informationSECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationSecurity Systems Intrusion Alarm
Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted
More informationSECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
More informationCommercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14
City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire
More informationInvitation to Bid FIRE ALARM & DETECTION SYSTEM
Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066
More informationSECTION 16610 FIRE DETECTION AND ALARM SYSTEM
SECTION 16610 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply
More informationModule 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
More informationSECTION 16760 - PLANT INTERCOMMUNICATION SYSTEM. City of San Diego, CWP Guidelines
PART 1 - GENERAL SECTION 16760-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing plant intercommunication systems with power supplies, signal amplifiers,
More informationSMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
More informationFVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
More informationLife Alarm Fire Alarm Controls
FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six
More informationOFPC Standard Specification
OFPC Standard Specification DIVISION 28 FIRE ALARM AND SMOKE DETECTION SYSTEM This Standard Specification Section is controlled by the Office of Facilities Planning and Construction, UT System. It is to
More informationSmall Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work
GE Security Small Building Life Safety Solutions Affordable FireShield Conventional Fire Alarm Control Panels imagination at work cost Location: Environment: Solution: Flower shop Finely decorated, gentle
More informationPROJECT TITLE PROJECT NO: 0000000 CONTRACT TITLE GRANT NO: 0000000 UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA
Fire alarm--all types of occupancies. The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-28 31 75.00 10 (November 2008) ----------------------------------- Preparing Activity: USACE Superseding UFGS-28 31 75.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationUniversity Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationINTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.
INTRODUCTION The information provided herein covers the range of products known as the 'Sensor 901' series. The range of equipment is designed to meet the requirements of BS 5839 parts 1 & 4 1988. The
More informationSECTION 16721 MULTI-FIRE ALARM SYSTEM
PART 1. GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification Sections, apply to this Section.
More informationUsing your LED Plus keypad
Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced
More informationFireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual
FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance
More informationSECTION 28 31 11 FIRE ALARM AND SMOKE DETECTION SYSTEMS WITH VOICE EVACUATION NOTIFICATION
SECTION 28 31 11 FIRE ALARM AND SMOKE DETECTION SYSTEMS WITH VOICE EVACUATION NOTIFICATION PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire Alarm and Smoke Detection Systems with Voice Evacuation Notification.
More informationwww.sebury.com.cn Digital Keypad Use s Manual
K3 K4 www.sebury.com.cn Digital Keypad Use s Manual Contents Introduction Introduction Specifications Intramural Interface Circuit 3 Mounting 3 Wiring 5 Power UP 7 Engineer Programming Mode 7 The K3/K4
More informationConventional Fire Detection and Extinguishant Control System Specification
Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release
More information527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
More informationB. NICET: National Institute for Certification in Engineering Technologies.
PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
More informationOriginal Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
More informationA. 70 National Electrical Code (NEC). B. 72 National Fire Alarm Code. C. 90A Installation of Air Conditioning and Ventilating systems.
SECTION 280513 % FIRE ALARM SYSTEM 1.0 This section is intended to define the general configuration, layout, installation and testing re quirements for the various fire alarm systems at the University
More informationEngineer s Project Number: 298-1062 Section 28 31 00 Page 1 FIRE ALARM AND DETECTION SYSTEMS
Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 SECTION 28 31 00 PART 1 GENERAL 01 SUMMARY A. This Section covers fire alarm systems, including initiating devices, notification appliances,
More information4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES
4-Wire Air Duct Smoke Detector Models DH-60 F-70.05 FEATURES Approvals/Listing UL 268A Listed File S1064 Factory Mutual Approved CSFM Listed #3240-1076:121 NYC MEA Listed #134-95-E City of Los Angeles
More informationBASIC FIRE ALARM TRAINING
BASIC FIRE ALARM TRAINING What is a fire alarm system? Per the defini+on in NFPA 72 A system or por+on of a combina+on system that consists of components and circuits arranged to monitor and annunciate
More information