1 Engineer s Project Number: Section Page 1 SECTION PART 1 GENERAL 01 SUMMARY A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices. B. Work covered by this section includes the furnishing of labor, equipment, and materials for the complete design, including drawings, calculations and material submittals, O&M manuals and installation and testing of the fire alarm system as indicated on the drawings and specifications. C. The Fire Detection and Alarm System shall consist of all necessary hardware equipment and software programming to perform the following functions: Fire alarm and detection operations in the building: a. King County Youth Service Center 02 PROJECT DESCRIPTION A. The FAC (Fire Alarm Contractor) shall totally design and install the system as described below. B. This project consists of design and installation of fire alarm system modifications in the Youth Detention Facility as described on the drawings and these specifications. All equipment and hardware to be vandalproof and be suitable for installation in a detention area. Included in the scope is the following: Replace existing duct smoke detectors with new addressable duct smoke detectors and bases which can be connected to the existing FACP via the existing wiring. Replace existing relays with new relays while retaining the same functions and connections to existing cell lights retaining the same function. 2. Replace existing ceiling smoke detectors with new addressable ceiling smoke detectors and bases which can be connected to the existing FACP via the existing wiring. Provide installation in vandalproof enclosures when located less than 10-0 AFF. 3. Replace existing ceiling heat detectors with new addressable ceiling heat detectors and bases which can be connected to the existing FACP via the existing wiring. Provide installation in vandalproof enclosures when located less than 10-0 AFF. Smoke detectors may be provided in lieu of heat detectors when installation meets code and is acceptable to the AHJ. 4. Replace existing horns, strobes and pull stations with new addressable horns, strobes and pull stations and bases which can be connected to the existing FACP via the existing wiring. 5. Provide new horns, strobes and bases as required to meet audibility and visual requirements of the AHJ. C. The project drawings do not show all alarm sensing devices, all alarm indication devices, or all alarm notification devices. The main fire alarm panel FACP and the remote annunciator are shown on the drawings as well as portions of the required devices. It is the FAC responsibility to determine the number of devices and alarm horns, strobes and pull stations and other devices to meet all codes NFPA72 and other codes and manufacturers requirements for a complete fire detection system.

2 Engineer s Project Number: Section Page 2 03 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and all Specification Sections, apply to this section. B. The work covered by this section is to be coordinated with related work as specified elsewhere in the specifications. Requirements of the following sections apply: Requirements for Electronic Safety and Security Installations Requirements for Electrical Installations C. The system and all associated operations shall be designed and installed in accordance with the following, current editions of: Guidelines of the following Building Code: IBC 2. NFPA 72, National Fire Alarm Code 3. NFPA 70, National Electrical Code 4. NFPA 101, Life Safety Code 5. NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems 6. Other applicable NFPA standards 7. Local Jurisdictional Adopted Codes and Standards including City of Seattle Fire Code, Building Code and Electrical Code. 8. ADA Accessibility Guidelines 04 COUNTY FURNISHED PROPERTY A. The project floor plans in AutoCAD format on CD-ROM will be available to use in making the Fire alarm system submittal drawings. 05 INITIAL SUBMITTALS A. Submit shop drawings and equipment catalog data, calculations, and manufacturer's installation operating and maintenance instructions for approval of the following items in accordance with the below. The following are in addition to requirements elsewhere in the specifications: Submit four hard copies of all submittals and one CD-ROM s with electronic files of all submittals. a. Submit all equipment cut sheets, drawings; calculations, materials list in 3 ring binders. b. Accordion fold 11 x17 drawings to fit in binder. c. All material submittals shall be in electronic PDF and hard copy format. 2. All submittals shall be in hard copy and in electronic format as follows: a. Drawings shall be in AutoCAD format and printed 11x17 size. b. All material and equipment cut sheets shall be in Adobe Acrobat format PDF format, and hard copy 8-1/2 x11 c. Calculations and materials lists shall be in hard copy and excel format XLS. 3. All calculations shall be in Excel spreadsheet format and in hard copy. 4. Provide a Materials list spreadsheet (XLS) showing all equipment descriptions, quantities, model numbers and ratings in hard copy and xls format. a. Show on a separate tab in materials list show all spare devices specified below. 5. Product data sheets for system components shall be highlighted to indicate the specific products, features, or functions required to meet this specification. 6. Wiring diagrams from manufacturer. a. Prepare AutoCAD drawings of the building floor plan with shop drawings showing system details including location of FACP, all devices, circuiting, wire numbers and details of remote annunciator. b. The County will furnish contract AutoCAD floor plans to modify.

3 Engineer s Project Number: Section Page 3 c. See Drawings Requirements below for specific details. 7. Power supply and Battery Calculations a. System Power and battery charts with performance graphs and voltage drop calculations to assure that the system will operate per the prescribed backup time periods and under all voltage conditions per all applicable standards. 8. System operation description a. Provide a written system operation description including method of operation and supervision of each type of circuit and sequence of operations for all manually and automatically initiated system inputs and outputs. b. A list of all input and output points in the system shall be provided with a label indicating location or use of SLC, NAC, RAC, Sensor, and auxiliary control circuits. c. All written instructions to be in MS word format. 9. Operating instructions for FACP. a. Provide operation and maintenance data for inclusion in Operating and Maintenance Manual. b. Include data for each type product, including all features and operating sequences, both automatic and manual. c. Provide O&M instructions in MS Word format and hard copy. d. Provide the names, addresses, and telephone numbers of service organizations. 10. Product certification signed by the manufacturer of the fire alarm system components certifying that their products comply with indicated requirements. 1 Certification that system has been designed by NICET Level IV Person(s) and will be installed by NICET certified personnel Level II or above. 12. Listing of specific field tests of system to be performed. 13. Provide a copy of all system program required to make entire system operate. 06 SUBMISSION TO AUTHORITY HAVING JURISDICTION: A. In addition to routine submission of the above material, make an identical submission to the authority having jurisdiction. B. Include copies of shop drawings and all items above under initial submittals as required to depict component locations to facilitate review. C. Upon receipt of comments from the Authority, make resubmissions if required to make clarifications or revisions to obtain approval from the AHJ. 07 DESIGN REQUIREMENTS A. Total system design shall meet all standards listed above under Related Documents, NFPA 72 and all others listed. B. All system design shall be by NICT Level IV certified personnel. C. Design of system shall be total responsibility of installing fire alarm system contractor (FAC). Drawings do not indicate all of the number and locations of detectors, pull stations, strobes, horns, other initiating devices and interconnections to emergency shut off system and other building systems. D. The locations and quantities of initiating and alarm devices shall be as required by standards references above under References: NFPA standards and manufactures requirements and by building physical construction. E. FAC shall physically inspect the building construction and any drawings to determine the physical construction to ensure that all detectors, and alarm devices will cover all areas in the correct locations and numbers of devices.

4 Engineer s Project Number: Section Page 4 F. It is the responsibility of the FAC to determine the extent of all interconnections to other building systems such as fire sprinkler system, HVAC system for shutdown and smoke control, door hold openers, elevator recalls, etc. G. All wiring shall be concealed in walls and ceilings to the extent possible. H. All wiring shall be in raceways. No wiring shall be exposed. 08 SYSTEM PROGRAMMING A. FAC is responsible for all system programming and testing of all devices wiring and panels. B. FACP shall be programmed using an IBM compatible laptop computer. C. Provide in final submittal both hard copy and electronic copy of final as-built FACP program and any documentation to clarify programming. 09 FIRE ALARM SYSTEM DRAWING REQUIREMENTS A. All drawings shall be in AutoCAD format on full size 24 x36 project floor plan drawings. All plots shall be 11 x17. Lettering shall be high minimum on 24x36 sheet size. 2. Roman S font only shall be used. No non standard AutoCAD fonts are to be used. 3. Provide a legend for all symbols. B. Provide a Riser Diagram showing all circuits and main FACP and auxiliary control panels. On riser diagram show the following: Main FACP (fire alarm control panel) showing internal terminal blocks for connection to external sensors and notification devices. 2. Each detector circuit and all devices and identification by room number for location. 3. Each Notification circuit showing the following in a tabular format. a. All notification devices by room number or location. b. Plan circuit c. Number of devices on each circuit d. Total current on each device circuit. 4. Battery calculations showing standby and alarm current required for all devices. Show calculation for 24 hours standby and 5 minutes in alarm. a. Show all device draws in calculation battery sized both standby an in alarm. C. Provide a Symbol Key legend showing device symbol, description, part number and mounting information for all devices used. D. Wire schedule identifying all wiring to be used including number of conductors and wire type and size. E. Scaled floor plan, including room names, gridlines, key plan, north arrow, and location designation. F. Floor plans to show all device locations including: Room numbers and names for all rooms to match contract drawings. 2. Device symbol for all pull station, horns, strobes, FACP, remote annunciator, monitoring devices and all other system components. 3. Circuiting information with point ID name and number. 4. Connections to all supervised devices such as water flow devices, air pressure switches, tamper switches etc. and all others. G. FACP Panel layouts showing position of all boards and termination points for all circuits. Show on the drawings the following: a. Notification appliance circuit schedule. b. Voltage drop calculation for each external circuit.

5 Engineer s Project Number: Section Page 5 c. Battery calculations for battery sizing. d. Physical inner panel construction showing main circuit boards all external terminal blocks. e. All external wiring with wire numbers. f. Power wiring to external circuits. g. Remote annunciator connections. h. Connections to phone line for digital dialer to central station. i. Any external relays for connection to shut down devices such as HVAC and IT room shut downs, elevator recalls, door hold open devices and all other system interlocks. j. All other connections not listed but required for complete operation. H. Alarm notification appliance drawings showing: Internal connections and external wiring and junction box sizes required. 2. Strobe candela rating vs voltage for volts applied vs multi output candela rating. 3. Horn sound output at 10ft., dba vs voltage for 16 24VDC 4. Current draws for horn and strobe vs voltage 16-24VDC I. Provide alarm system matrix for all devices showing the following: Alarm cause / vs. effect: a. Alarm, trouble, supervision, misc, interlocks with other equipment. J. All wiring shall have wire numbers on each end of each conductor. Show on system wiring diagrams. K. Battery calculations for all panels, including manufacturers recommendation for spare capacity due to battery discharge. Also provide any calculations in Excel format, XLS. L. Voltage drop calculations for all notification appliance circuits lump sum method, or distributed load method with a safety factor. Voltage drop calculation to include minimum acceptable voltage drop value and wire specifications. M. Circuit schedules showing all addresses/zones/circuits used. Show equipment ID number, type of detector, location by floor and room number. N. Address list identifying all points on the addressable loop, including device type and location O. Wiring typical showing wiring terminations for all devices used including wire numbers. P. Drawing title block to include drawing number, identification of project designer and drafter, identification of company and contact information, revision notes, and project location information. Q. Wire numbers shall be shown of all wiring from FACP to all devices. All wire numbers shall show on drawings. R. All circuit board termination terminal blocks connections shall be shown for all devices and panels. 10 QUALITY ASSURANCE A. System designer qualifications: Certification that system has been designed by NICET certified personnel Level IV. Designer shall sign all drawings. B. Installer Qualifications: A factory-authorized installer is to perform the work of this section: Installation personnel shall be by persons who are qualified and experienced in the installation, inspection, and testing of fire alarm systems as follows. a. Qualified personnel shall include the following: 1) Factory trained and certified personnel and National Institute of Certification in Engineering Technologies (NICET) fire alarm level II or above certified. 2) In addition to NICET certification all installing personnel shall be licensed or certified by state or local authority.

6 Engineer s Project Number: Section Page 6 C. Each and all items of the Fire Alarm System shall be listed as a product of a single fire alarm system manufacturer under the appropriate category by Underwriters Laboratories, Inc. (UL), and shall bear the "UL" label. 11 MAINTENANCE SERVICE A. Maintenance Service Contract: Provide maintenance of fire alarm systems and equipment for a period of 12 months, using factory-authorized service representatives. Maintenance supplier shall be located within 20 miles of project site. B. Basic Services: Systematic, routine maintenance visits on a annual basis at times scheduled with the Owner. In addition, respond to service calls within 24 hours of notification of system trouble. Adjust and replace defective parts and components with original manufacturer's replacement parts, components, and supplies. C. Other Services: Perform services within the above 12-month period not classified as routine maintenance or as warranty work when authorized in writing. Compensation for additional services must be agreed upon in writing prior to performing services. 12 ACCEPTABLE MANUFACTURERS A. Manufacturers: The existing building has a Siemens fire alarm control panel. The equipment and service described in this specification are those supplied and supported by Siemens and Siemens equipment is to be provided. No exceptions or substitutions allowed. B. The fire alarm organizations on this project shall be a nationally recognized company specializing in Siemens fire alarm and detection systems. This organization shall employ factory trained and NICET certified technicians, and shall maintain a service organization within 20 miles of this project location. 2. The Manufacturer and service organization shall have a minimum of 10 years experience in the fire protective signaling systems industry. C. FAC shall have a service organization within 20 miles of project site with factory-trained technicians. 13 SYSTEM DESCRIPTION A. General: Provide a complete, non-coded, addressable, microprocessor-based fire alarm system with initiating devices, notification appliances, and monitoring and control devices as indicated on the drawings and as specified herein. B. Software: The fire alarm system shall allow for loading and editing instructions and operating sequences as necessary by an IBM format PC. The system shall be capable of 100% on-site programming to accommodate system expansion and facilitate changes in operation. All programming shall be capable of being accomplished via the front panel and via a laptop computer. All software operations shall be stored in a non-volatile programmable memory within the FACP. Loss of primary and secondary power shall not erase the instructions stored in memory. C. History Logs: The system shall provide a means to recall alarms and trouble conditions in chronological order for the purpose of recreating an event history. Separate alarm, supervisory and trouble logs shall be provided. D. Recording of Events: Record all alarm, supervisory, and trouble events by means of system printer. The printout shall include the type of signal (alarm, supervisory, or trouble) the device identification, date and time of the occurrence. The printout differentiates alarm signals from all other printed indications. E. Wiring/Signal Transmission: Transmission shall be addressable signal transmission, dedicated to fire alarm service only. 2. System connections for initiating (signaling) circuits and notification appliance circuits shall be Class B.

7 Engineer s Project Number: Section Page 7 3. Circuit Supervision: Circuit faults shall be indicated by a trouble signal at the FACP. Provide a distinctive indicating audible tone and alphanumeric annunciation. F. Remote Access: FACP shall have the capability to provide Remote Access through a Dial-Up Service Modem using the public switched telephone system of a private switched telephone system. 2. A personal computer or technician's laptop, configured with terminal emulation software shall have the ability to access the FACP for diagnostics, maintenance reporting, and information gathering. G. Required Functions: The following are required system functions and operating features: a. Priority of Signals: 1) Alarm events have highest priority. Subsequent alarm events are queued in the order received and do not affect existing alarm conditions. Supervisory and Trouble events have second-, and third-level priority respectively. Signals of a higher-level priority take precedence over signals of lower priority even though the lower-priority condition occurred first. Annunciate all events regardless of priority or order received. b. Noninterfering: 1) The activation of an addressable device does not prevent the receipt of signals from subsequent activations. 2) DACT Transmission to Remote Central Station: Provide fire alarm control panel equipment to automatically route alarm, supervisory, and trouble signals to a remote central station service transmitter provided under another contract. a) The DACT shall be an integral part of the fire alarm control panel. The Digital Alarm Receiver shall be located at a UL approved central station for digital alarm reporting. c. Annunciation: 1) Operation of alarm and supervisory initiating devices shall be annunciated at the FACP and any required remote annunciators, indicating the location and type of device. d. General Alarm: 1) A system general alarm shall include: a) Indication of alarm condition at the FACP and the facilities remote annunciator(s). b) Identification of the device that is the source of the alarm at the FACP and any required remote annunciator(s). c) Operation of audible and visible notification appliances throughout the building until silenced at FACP. Audible Alarm Notification shall meet local AHJ requirements. d) Closing doors normally held open by magnetic door holders. e) Unlocking designated doors. f) Shutting down supply and return fans serving zone where alarm is initiated or per AHJ. g) Closing smoke dampers on system serving zone where alarm is initiated or per AHJ. h) Initiation of smoke control sequence. i) Notifying the local fire department. j) Initiation of elevator recall in accordance with ASME/ANSI A17.1, when specified sensors are activated. 2. Supervisory Operations: a. Upon activation of a supervisory device such as fire pump power failure, low air pressure switch, and tamper switch, the system shall operate as follows: 1) Activate the system supervisory service audible signal and illuminate the LED at the FACP and the graphic annunciator.

8 Engineer s Project Number: Section Page 8 2) Pressing the Supervisory Acknowledge key will silence the supervisory audible signal while maintaining the Supervisory LED "on" indicating off-normal condition. 3) Record the event in the FACP historical log. 4) Transmission of supervisory signal to remote central station. 3. Alarm Silencing: a. If the "Alarm Silence" button is pressed, all audible alarm signals shall cease operation. 4. System Reset a. The "System Reset" button shall be used to return the system to its normal state. Display messages shall provide operator assurance of the sequential steps ("IN PROGRESS", "RESET COMPLETED") as they occur. The system shall verify all circuits or devices are restored prior to resetting the system to avoid the potential for re-alarming the system. The display message shall indicate "ALARM PRESENT, SYSTEM RESET ABORTED." b. Should an alarm condition continue, the system will remain in an alarmed state. 5. Drill: a. A manual evacuation (drill) switch shall be provided to initiate an alarm on the FACP. 6. Manual Control: a. Manual controls shall be supervised so that an "off normal" position of any switch shall cause an "off normal" system trouble. The "off normal" status shall be clearly identified in plain-language on the FACP alphanumeric display. b. Manual Bypass Control: The ability to perform a manual bypass of selected automatic functions shall be provided. c. Circuit Enable/Disable Control: The system shall have provisions for disabling and enabling each circuit individually for maintenance or testing purposes. 7. Single person WALKTEST: a. The system shall have a one-person test feature. Enabling the one person test feature at the FACP shall activate the "One Person Testing" mode of the system as follows: b. The city circuit connection and suppression release circuits shall be bypassed for the testing group. c. Control relay functions associated to the testing group shall be bypassed. d. The FACP shall indicate a trouble condition. e. The alarm activation of any initiation device in the testing group shall cause the audible notification appliances to sound a code to identify the device. f. The control panel shall automatically reset itself after signaling is complete. g. Any momentary opening of an initiating or notification appliance circuit wiring shall cause the audible signals to sound for 4 seconds indicating the trouble condition. H. Analog Smoke Sensors: Monitoring: FACP shall individually monitor sensors for calibration, sensitivity, and alarm condition, and shall individually adjust for sensitivity. The FACP shall determine the condition of each sensor by comparing the sensor value to the stored values. 2. Environmental Compensation: The FACP shall maintain a moving average of the sensor's smoke chamber value to automatically compensate for dust, dirt, and other conditions that could affect detection operations. 3. Programmable Sensitivity: Photoelectric Smoke Sensors shall have 8 sensitivity levels ranging from 0.2% to 3.7%, programmed and monitored from the FACP. 4. Sensitivity Testing Reports: The FACP shall provide sensor reports that meet NFPA 72 calibrated test method requirements. The reports shall be viewed on a Maintenance Terminal CRT Display or printed for annual recording and logging of the calibration maintenance schedule.

9 Engineer s Project Number: Section Page 9 5. Peak Value Logging: The FACP shall log the Peak Value of smoke obscuration or degree of temperature for each individual sensor to allow system calibration for maximum response time performance without nuisance alarms based on "actual ambient conditions". 6. The FACP shall automatically indicate when an individual sensor needs cleaning. The system shall provide a means to indicate that a sensor requires cleaning. When a sensor's average value reaches a predetermined value, (3) progressive levels of reporting are provided. a. The first level shall indicate that a sensor is close to a trouble reporting condition and will be indicated on the FACP as "ALMOST DIRTY." This condition provides a means to alert maintenance staff of a dirty sensor without creating a trouble in the system. b. If this indicator is ignored, a second level "DIRTY SENSOR" condition shall be indicated at the FACP.. The sensor base LED shall glow steady giving a visible indication at the sensor location. The "DIRTY SENSOR" condition shall not affect the sensitivity level required to alarm the sensor. c. If a "DIRTY SENSOR" is left unattended, and its average value increases to a third predetermined value, an "EXCESSIVELY DIRTY SENSOR" trouble condition shall be indicated at the control panel. 7. The FACP shall continuously perform an automatic self-test on each sensor which will check sensor electronics and ensure the accuracy of the values being transmitted. Any sensor that fails this test shall indicate a "SELF TEST ABNORMAL" trouble condition. I. Fire Suppression Monitoring: Water flow: Activation of a water flow switch shall initiate general alarm operations. Water flow switches are existing and are to be monitored and wired under this section. 2. Sprinkler valve tamper switch: The activation of any valve tamper switch shall activate system supervisory operations. Tamper switches are existing and are to be monitored and wired under this section. 3. Water flow switch and sprinkler valve tamper switch shall be capable of existing on the same initiating zone. Activation of either device shall distinctly report which device is in alarm on the initiating zone. 4. Fire sprinkler Air compressor low pressure and loss of pressure shall activate system supervisory operations. These are existing and are to be monitored and wired under this section. J. Audible Alarm Notification: By horns in areas as indicated on drawings. For this project not all horns are shown on drawings. Contractor shall design all locations for horns to meet all codes and regulations in accordance with NFPA An additional circuit (16/2 shielded cable) will mirror the horn/strobe circuit for future use for voice communication (speakers). Wiring for future speaker circuits will be terminated between the control panel through each junction box to an end of line device. K. Power Requirements The control panel is existing. Upgrade as required. 2. The system shall be provided with sufficient battery capacity to operate the entire system upon loss of normal AC power in a normal supervisory mode for a period of 24 hours with 5 minutes of alarm operation at the end of this period. The system shall automatically transfer to battery standby upon power failure. All battery charging and recharging operations shall be automatic. 3. All circuits requiring system-operating power shall be 24 VDC and shall be individually fused at the control panel. 4. The incoming power to the system shall be supervised so that any power failure will be indicated at the control panel. A green "power on" LED shall be displayed continuously while incoming power is present. 5. The system batteries shall be supervised so that a low battery condition or disconnection of the battery shall be indicated at the control panel.

10 Engineer s Project Number: Section Page SPARE PARTS 6. The system shall support 100% of addressable devices in alarm operated at the same time, under both primary (AC) and secondary (battery) power conditions. 7. Loss of primary power shall sound a trouble signal at the FACP. FACP shall indicate when the system is operating on an alternate power supply. A. General: Furnish extra materials, packaged with protective covering for storage, and identified with labels clearly describing contents as follows: 15 ALTERNATES Show description and models, and quantities of extra materials in main materials list spreadsheet in a separate tab. Provide this list of extra materials in initial submittal. 2. Strobe Units: Furnish quantity equal to 2 percent of the number of units installed, but not less than one. 3. Smoke Sensors, Fire Detectors, and Flame Detectors: Furnish quantity equal to 2 percent of the number of units of each type installed but not less than one of each type. 4. Sensor Bases: Furnish quantity equal to 2 percent of the number of units of each type installed but not less than one of each type. A. Refer to Section ALTERNATES for possible effect on work of this Section. PART 2 PRODUCTS 2.01 FIRE ALARM CONTROL PANEL EXISTING SIEMENS A. General: Comply with UL 864, "Control Panels for Fire-Protective Signaling Systems." B. The following FACP control panel modifications shall be provided as required: Upgrade the existing Siemens FACP as required to meet Seattle Fire Code for the devices installed. 2. Provide all network interface connections between system components required. 3. FACP shall allow remote devices to be monitored up to 2000 from main fire alarm panel via an addressable network. 4. Addressable points capacity as required inclusive of inputs and outputs in any combination. 5. Class B/Style Y Notification Appliance Circuits (NAC; rated 24VDC, resistive); 6. Form "C" Auxiliary Output Circuits (rated 24VDC, resistive), operation is programmable for trouble, alarm, supervisory or other selective control operations. Provide capability for switching up to ½ 120VAC, inductive loads. 7. Supervised serial communication channel for control and monitoring of remotely located LCD annunciators and I/O panels. 8. Provide additional output contracts for interface to any HVAC shut down system and others as specified elsewhere is this specifications or required. 9. Fire alarm system panel point capacity shall be a minimum of 2,000 points. 10. FACP shall be UL cross listed with the fire alarm system components installed. C. Cabinet: Lockable steel enclosure. Arrange panel so all operations required for testing or for normal care and maintenance of the system are performed from the front of the enclosure. If more than a single panel is required to form a complete control panel, provide exactly matching modular panel enclosures. D. Alphanumeric Display and System Controls: Panel shall include an 80 character LCD display to indicate alarm, supervisory, and component status messages and shall include a keypad for use in entering and executing control commands.

11 Engineer s Project Number: Section Page REMOTE MAINTENANCE TERMINAL (CRT) AND PRINTERS A. Fire Alarm Control Panel shall be capable of operating a remote maintenance terminal and/or printers; output shall be ASCII from an RS-232-C connection with an adjustable baud rate. B. No printers are required for this project, but system must have these capabilities REMOTE LCD ANNUNCIATORS A. Provide new or updated Remote Annunciator(s) as required by AHJ. B. Under normal conditions the Remote Annunciator(s) shall display a "SYSTEM IS NORMAL" message and the current time and date. C. Should an abnormal condition be detected the appropriate LED (Alarm, Supervisory or Trouble) shall flash. The unit audible signal shall pulse for alarm conditions and sound steady for trouble and supervisory conditions. D. Operator keys shall be key switch enabled to prevent unauthorized use. The key shall only be removable in the disabled position. Acknowledge, Silence and Reset operation shall be the same as the FACP EMERGENCY POWER SUPPLY A. General: Components include battery, charger, and an automatic transfer switch. B. Battery: Sealed lead-acid type. Provide sufficient capacity to operate the complete alarm system in normal or supervisory (non-alarm) mode for a period of 24 hours. Following this period of operation on battery power, the battery shall have sufficient capacity to operate all components of the system, including all notification appliances in alarm or supervisory mode for a period of 5 minutes ADDRESSABLE MANUAL PULL STATIONS A. Description: Addressable double-action type, red LEXAN, with molded, raised-letter operating instructions of contrasting color. Station will mechanically latch upon operation and remain so until manually reset by opening with a key common with the control units. B. Pull Station Protective Shield: Provide a tamperproof, clear LEXAN shield and red frame that easily fits over all manual pull stations. C. Addressable pull stations and bases shall be the type that can be connected to the existing wiring. Provide any accessory components required to accomplish the operation on existing wiring ADDRESSABLE SMOKE SENSORS A. General: Comply with UL 268, "Smoke Detectors for Fire Protective Signaling Systems." Include the following features: Factory Nameplate: Serial number and type identification. 2. Operating Voltage: 24 VDC, nominal. 3. Self-Restoring: Detectors do not require resetting or readjustment after actuation to restore normal operation. 4. Plug-In Arrangement: Sensor and associated electronic components are mounted in a module that connects to a fixed base with a twist-locking plug connection. Base shall provide break-off plastic tab that can be removed to engage the head/base locking mechanism. No special tools shall be required to remove head once it has been locked. Removal of the detector head shall interrupt the supervisory circuit of the fire alarm detection loop and cause a trouble signal at the control unit.

12 Engineer s Project Number: Section Page Each sensor base shall contain an LED that will flash each time it is scanned by the Control Unit (once every 4 seconds). In alarm condition, the sensor base LED shall be on steady. 6. Each sensor base shall contain a magnetically actuated test switch to provide for easy alarm testing at the sensor location. 7. Each sensor shall be scanned by the Control Unit for its type identification to prevent inadvertent substitution of another sensor type. Upon detection of a "wrong device", the control unit shall operate with the installed device at the default alarm settings for that sensor; 2.5% obscuration for photoelectric sensor, 135-deg F and 15-deg F rate-of-rise for the heat sensor, but shall indicate a "Wrong Device" trouble condition. 8. The sensor's electronics shall be immune from false alarms caused by EMI and RFI. 9. Sensors include a communication transmitter and receiver in the mounting base having a unique identification and capability for status reporting to the FACP. Sensor address shall be located in base to eliminate false addressing when replacing sensors. 10. Removal of the sensor head for cleaning shall not require the setting of addresses. B. Detector Type: Smoke sensors shall be of the photoelectric or combination photoelectric / heat type. Where required ionization type sensors may be used with AHJ approval. C. Detector Bases: Relay output, sounder and isolator bases shall be supported alternatives to the standard base. D. Duct Smoke Sensor: Provide duct detectors as required by Code for system being installed under this contract. 2. Photoelectric type, with sampling tube of design and dimensions as recommended by the manufacturer for the specific duct size and installation conditions where applied. Sensor includes relay as required for fan shutdown. 3. Environmental compensation, programmable sensitivity settings, status testing, and monitoring of sensor dirt accumulation for the duct sensor shall be provided by the FACP. 4. The Duct Housing shall provide a supervised relay driver circuit for driving up to 15 relays with a single "Form C" contact rated at 7A@ 28VDC or 10A@ 120VAC. This auxiliary relay output shall be fully programmable. Relay shall be mounted within 3 feet of HVAC control circuit. 5. Duct Housing shall provide a relay control trouble indicator Yellow LED. 6. Compact Duct Housing shall have a transparent cover to monitor for the presence of smoke. Cover shall secure to housing by means of four (4) captive fastening screws. 7. Duct Housing shall provide two (2) Test Ports for measuring airflow and for testing. These ports will allow aerosol injection in order to test the activation of the duct smoke sensor. 8. Duct Housing shall provide a magnetic test area and Red sensor status LED. 9. For maintenance purposes, it shall be possible to clean the duct housing sampling tubes by accessing them through the duct housing front cover. 10. Each duct sensor shall have a Remote Test Station with an alarm LED and test switch. 1 A NEMA 4X weatherproof duct housing enclosure shall provide for the circulation of conditioned air around the internally mounted addressable duct sensor housing to maintain the sensor housing at its rated temperature range. The housing shall be UL Listed to Standard 268A. E. Addressable smoke sensors and bases shall be the type that can be connected to the existing wiring. Provide any accessory components required to accomplish the operation on existing wiring.

13 Engineer s Project Number: Section Page ADDRESSABLE HEAT SENSORS A. Thermal Sensor: Combination fixed-temperature and rate-of-rise unit with plug-in base and alarm indication lamp; 135-deg F fixed-temperature setting except as indicated. B. Thermal sensor shall be of the epoxy encapsulated electronic design. It shall be thermistor-based, rate-compensated, self-restoring and shall not be affected by thermal lag. C. Sensor fixed temperature sensing shall be independent of rate-of-rise sensing and] programmable to operate at 135-deg F or 155-deg F. Sensor rate-of-rise temperature detection shall be selectable at the FACP for either 15-deg F or 20-deg F per minute. D. Sensor shall have the capability to be programmed as a utility monitoring device to monitor for temperature extremes in the range from 32-deg F to 155-deg F. E. Addressable heat sensors and bases shall be the type that can be connected to the existing wiring. Provide any accessory components required to accomplish the operation on existing wiring ADDRESSABLE CIRCUIT INTERFACE MODULES A. Addressable Circuit Interface Modules: Provide addressable circuit interface modules to monitor one or more system components that are not otherwise equipped for addressable communication. 2. Modules shall be used for monitoring of water flow, valve tamper, non-addressable devices, and for control of evacuation indicating appliances and AHU systems. 3. The addressable output control modules for control of HVAC and similar shut downs, smoke dampers, fire door releases shall be equipped with a auxiliary relays with 10A resistive rating at 120VAC. B. Addressable Circuit Interface Modules will be capable of mounting in a standard electric outlet box. Modules will include cover plates to allow surface or flush mounting. Modules will receive their operating power from the signaling line or a separate two wire pair running from an appropriate power supply as required. C. There shall be the following types of addressable modules: Type 2: Signal Line Communications Powered Monitor Circuit Interface Module: a. This type of module is an individually addressable module that has both its power and its communications supplied by the two wire multiplexing signaling line circuit. It provides location specific addressability to an initiating device by monitoring normally open dry contacts. This module shall have the capability of communicating four zone status conditions (normal, alarm, current limited, trouble) to the FACP. b. Each initiating device shall be by monitored via a separate addressable module for normally closed or normally open dry contact. 1) This module shall provide location specific addressability. The module shall communicate four zone status conditions (open, normal, abnormal, and short). The two-wire signaling line circuit shall supply power and communications to the module. 2. Type 3: Signal Line Communications Powered Monitor Circuit Interface output Module a. This module shall provide control of a Form "C" contact. The two-wire signaling line circuit shall supply power and communications to the module. b. The addressable output control modules for control of HVAC and similar shut downs, smoke dampers, fire door releases shall be equipped with a auxiliary relays with 10A resistive rating at 120VAC. D. All Circuit Interface Modules shall be supervised and uniquely identified by the control unit. Module identification shall be transmitted to the control unit for processing according to the program instructions.

14 Engineer s Project Number: Section Page Modules shall have an on-board LED to provide an indication that the module is powered and communicating with the FACP. 3. The LEDs shall provide a troubleshooting aid since the LED blinks on poll whenever the peripheral is powered and communicating. 2.9 ADDRESSABLE ALARM NOTIFICATION APPLIANCES A. Addressable Notification Appliances: The Contractor shall furnish and install Multicandela Addressable Notification Appliances and accessories to operate on compatible signaling line circuits (SLC). Conventional notification appliance devices will not be accepted. 2. Addressable Notification appliance operation shall provide power, supervision and separate control of horns and strobes over a single pair of wires. The controlling channel (SLC) digitally communicates with each appliance and receives a response to verify the appliance's presence on the channel. The channel provides a digital command to control appliance operation. SLC channel wiring shall be unshielded twisted pair (UTP), with a capacitance rating of less than 60pf/ft and a minimum 3 twists (turns) per foot. 3. Class B (Style 4) notification appliances shall be wired without requiring traditional in/out wiring methods; addressable "T" Tapping shall be permitted. Up to 63 appliances can be supported on a single channel. 4. Each Addressable notification appliance shall contain an electronic module and a selectable address setting to allow it to occupy a unique location on the channel. a. This on-board module shall also allow the channel to perform appliance diagnostics that assist with installation and subsequent test operations. b. A visible LED on each appliance shall provide verification of communications and shall flash with the appliances address setting when locally requested using a magnetic test tool. B. Addressable Controller: Addressable Controller shall supervise Channel (SLC) wiring, communicate with and control addressable notification appliances. It shall be possible to program the High/Lo setting of the audible (horn) appliances by channel from the addressable controller. C. Addressable Horn: Addressable horn shall be listed to UL 464. Horn appliances shall have a High/Lo Setting, programmable by channel from the addressable controller or by appliance from the host FACP. The horn shall have a minimum sound pressure level of 83 or 89 24VDC. The horn shall mount directly to a standard single gang, double gang or 4" square electrical box, without the use of special adapter or trim rings. D. Addressable Visible/Only: Addressable strobe shall be listed to UL 197 The V/O shall consist of a xenon flash tube and associated lens/reflector system. The V/O enclosure shall mount directly to standard single gang, double gang or 4" square electrical box, without the use of special adapters or trim rings. V/O appliances shall be provided with different minimum flash intensities of 15cd, 75cd and 110cd, selectable settings via the fire alarm control panel. Provide a label inside the strobe lens to indicate the listed candela rating of the specific Visible/Only appliance. Strobes shall be synchronized. E. Addressable Audible/Visible: Addressable combination Audible/Visible (A/V) Notification Appliances similar to Wheelock multi-tone, mutli-candela horn strobes Model AMT-24MCW. Shall be listed to UL 1971 and UL 464. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Provide a label inside the strobe lens to indicate the listed candela rating of the specific strobe. The horn shall have a minimum sound pressure level of 83 or 89 24VDC. The audible/visible enclosure shall mount directly to standard single gang, double gang or 4" square

15 Engineer s Project Number: Section Page 15 electrical box, without the use of special adapters or trim rings. The appliance strobes shall be synchronized: F. Addressable interface module Fire Alarm supervisory Analog Monitor Zone Adapter modules will be provided to interface linear analog sensors from critical analog alarm output and levels G. Isolator Module: Isolator module provides short circuit isolation for addressable notification appliance SLC wiring. Isolator shall be listed to UL 864. The Isolator shall mount directly to a minimum 2 1/8" deep, standard 4" square electrical box, without the use of special adapter or trim rings. Power and communications shall be supplied by the Addressable Controller channel SLC; dual port design shall accept communications and power from either port and shall automatically isolate one port from the other when a short circuit occurs. The following functionality shall be included in the Isolator module: 2. Report faults to the host FACP. 3. On-board Yellow LED provides module status. 4. After the wiring fault is repaired, the Isolator modules shall test the lines and automatically restore the connection. 5. Provide a minimum isolator module per floor isolating ground faults per floor and one for any remote buildings. H. Accessories: The contractor shall furnish the necessary accessories to make a complete operational system. I. Addressable alarm notification appliances that replace existing and bases shall be the type that can be connected to the existing wiring. Provide any accessory components required to accomplish the operation on existing wiring WATER FLOW OR PRESSURE SWITCH CONNECTIONS A. Water flow switch or pressure switches are existing to be monitored and wired by fire alarm contractor with a separate addressable module. B. Shall be addressable and be of the type that can be connected to the existing wiring FIRE SPRINKLER AIR COMPRESSOR LOW PRESSURE SWITCH A. Fire sprinkler system air compressor switch if existing to be monitored and wired by fire alarm contractor with a separate addressable module. B. Shall be addressable and be of the type that can be connected to the existing wiring FIRE SPRINKLER TAMPER SWITCH A. Fire sprinkler tamper switches are existing to be monitored and wired by fire alarm contractor with a separate addressable module. B. Shall be addressable and be of the type that can be connected to the existing wiring MAGNETIC DOOR HOLDERS A. Magnetic door holders if existing are to be monitored and wired by fire alarm contractor with a separate addressable module. B. Shall be addressable and be of the type that can be connected to the existing wiring FIRE ALARM SYSTEM CONDUCTORS A. Utilize existing conductors unless new are required. All new wiring shall conform to NEC Article 760 for fire alarm detection.

16 Engineer s Project Number: Section Page FIRE ALARM SYSTEM CONDUCTORS SIZING A. FAC shall size all new fire alarm signal and power conductors for all loads to meet loads on each circuit to minimize voltage drop so all devices will function at maximum load conditions, and when on battery backup with 10% spare voltage drop. The FACP shall be capable of performing self NAC load calculations PART 3 EXECUTION 3.01 INSTALLATION, GENERAL A. Installation is in a secure detention facility. All Contractor employees shall have security clearance prior to construction start and be on an approved visitor list. Contractor employees must be escorted at all times unless they are locked in behind secure doors. The allowed Contractor hours of work are Monday Friday 8AM to 5PM. B. Contractor will have access to only two Halls at any one time. (Note: Hall has been completed.) Only when work on one pair of Halls is complete, tested and fully operational will more Halls be vacated of inmates and be assigned for Contractor work. Work will proceed in this manner until all 16 halls have been completed. (Note: Hall Q has been completed.) C. Work in other areas (besides the Halls) is to be scheduled with the owner. D. Contractor shall complete work each day such that the system is fully operational at the end of the day. A fully operational system shall include but not be limited to above systems or a fire watch, plumbing and electrical systems. E. Contractor shall be responsible for declaring needs for a fire watch, at which times shall request to the Owners Project Representative that the County provide such personnel as needed. Contractor shall provide fire watch personnel as required by the AHJ and code for the Siemens equipment needing fire watch. F. Install and test system components and all associated devices in accordance with applicable codes, NFPA Standards and manufacturer's recommendations. G. Installer Qualifications: A factory-authorized installer is to perform the work of this section: Installation personnel shall be by persons who are qualified and experienced in the installation, inspection, and testing of fire alarm systems as follows. a. Qualified personnel shall include the following: 1) Factory trained and certified personnel and National Institute of Certification in Engineering Technologies (NICET) fire alarm level II or above certified. 2) In addition to NICET certification all installing personnel shall be licensed or certified by state or local authority EQUIPMENT INSTALLATION A. Furnish and install a complete Fire Alarm System as described herein and as shown on the drawings. B. Include sufficient control unit(s), annunciator(s), manual stations, automatic fire detectors, smoke detectors, audible and visible notification appliances, wiring, terminations, conduit, electrical boxes, and all other necessary material for a complete operating system. C. Water-Flow and Valve Supervisory Switches: Connect for each sprinkler valve required to be supervised. D. Device Location-Indicating Lights: Locate in the public space immediately adjacent to the device they monitor and make fully operational WIRING INSTALLATION A. System Wiring: New wire and cable shall be a type listed for its intended use by an approval agency acceptable to the Authority Having Jurisdiction (AHJ) and shall be installed in accordance with the

17 Engineer s Project Number: Section Page 17 appropriate articles from the current approved edition of NFPA 70: National Electric Code (NEC) and NPFA 72. B. Contractor shall obtain from the Fire Alarm System Manufacturer written instruction regarding the appropriate wire/cable to be used for this installation. No deviation from the written instruction shall be made by the Contractor without the prior written approval of the Fire Alarm System Manufacturer. C. Color Coding for new conductors: 3.04 WIRING METHODS Color-code fire alarm conductors differently from the normal building power wiring. Use one color code for alarm initiating device circuits wiring and a different color code for supervisory circuits. 2. Color-code notification appliance circuits differently from alarm-initiating circuits. 3. Paint all fire alarm system junction boxes and covers red. A. All wiring shall be in steel raceways, EMT or flexible steel conduit as a minimum, see for allowable raceway types. B. New devices boxes shall be finish quality type suitable for the device installed, see for allowable boxes. C. Only fire alarm cables and conductors shall occupy fire alarm conduits and junction boxes FIELD QUALITY CONTROL A. Manufacturer's Field Services: Provide services of a factory-authorized service representative to supervise the field assembly and connection of components and the pretesting, testing, and adjustment of the system. B. Provide factory trained and qualified personnel employed by an organization listed by a national testing laboratory for the servicing of fire alarm systems. C. Installer Qualifications: A factory-authorized installer is to perform the work of this section: Installation personnel shall be by persons who are qualified and experienced in the installation, inspection, and testing of fire alarm systems as follows. a. Qualified personnel shall include the following: 1) Factory trained and certified personnel and National Institute of Certification in Engineering Technologies (NICET) fire alarm level II or above certified. 2) In addition to NICET certification all installing personnel shall be licensed or certified by state or local authority TESTING A. Pretesting: Determine, through pretesting, the conformance of the system to the requirements of the Drawings and Specifications. 2. Test all wiring for shorts and grounds before connection to equipment. 3. Correct deficiencies observed in pretesting. 4. Replace malfunctioning or damaged items with new and retest until satisfactory performance and conditions are achieved. B. Final Test Notice: Provide a 10-day minimum notice in writing when the system is ready for final acceptance testing. C. Minimum Final System Tests: Test the system according to the procedures outlined in NFPA 72.

18 Engineer s Project Number: Section Page Each device shall individually be tested, all detectors, pull stations, sensing devices, horns, and all other appurtenances, shut down systems, strobes and control panel and remote annunciator. D. Retesting: Correct deficiencies indicated by tests and completely retest work affected by such deficiencies. Verify by the system test that the total system meets the Specifications and complies with applicable standards. E. Report of Tests and Inspections: Provide a written record of inspections, tests, and detailed test results in the form of a test log. F. Final Test, Certificate of Completion, and Certificate of Occupancy: Test the system as required by the Authority Having Jurisdiction in order to obtain a certificate of occupancy. G. Phasing: Above testing shall be after each two halls of the project and each phase of the project CLEANING AND ADJUSTING A. Cleaning: Remove paint splatters and other spots, dirt, and debris. 2. Clean unit internally using methods and materials recommended by manufacturer. B. Occupancy Adjustments: When requested within one year of date of Substantial Completion, provide on-site assistance in adjusting sound levels and adjusting controls and sensitivities to suit actual occupied conditions. a. Provide up to three visits to the site for this purpose TRAINING A. Provide the services of a factory-authorized service representative to demonstrate the system and train Owner's maintenance personnel as specified below. Train Owner's maintenance personnel in the procedures and schedules involved in operating, troubleshooting, servicing, and preventive maintaining of the system. 2. Provide a minimum of 8 hours of onsite training. 3. Schedule training with the County at least seven days in advance FINAL SUBMITTALS AND O&M MANUALS A. Provide the following information in the final operation and maintenance manual. Provide O&M manuals in 3 ring binders with project name, date, contractors name, phone number and contact information. Provide four copies of all items in each O&M manual from initial submittal above including the following in both hard copy and electronic format on CD-ROM: a. As-built drawings of compete system in both hard copy 11x17 and in AutoCAD DWG format on CD-ROM. b. As-built materials list and spare parts list in hard copy and spreadsheet in XLS format. c. As-built cut sheets of all materials and equipment cut sheets in hard copy and in PDF format. All equipment to be specifically identified on each cut sheets. d. As-built calculations in hard copy and XLS format. e. Operation and maintenance instructions in hard copy and electronic copies in MS word format. f. Copy of complete as-built fire alarm system program on CD-ROM and hard copy printout E N D - - -

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

SECTION 16721 MULTI-FIRE ALARM SYSTEM

SECTION 16721 MULTI-FIRE ALARM SYSTEM PART 1. GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification Sections, apply to this Section.

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as

More information

SECTION 16700 FIRE ALARM SYSTEM

SECTION 16700 FIRE ALARM SYSTEM SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

28 3111 Voice Annunicated Fire Alarm System Page 1 of 26

28 3111 Voice Annunicated Fire Alarm System Page 1 of 26 Last Update: December 8, 2014 Consultant s Handbook Page 1 of 26 A. General: 1. Voice annunciated, intelligent, addressable fire alarm systems at BSU are used in all residence halls, high rise buildings

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM FIRE DETECTION AND ALARM GENERAL INFORMATION 1.1 In general, follow the guidelines below when designing and specifying addressable fire alarm systems. Unless specifically indicated otherwise, these guidelines

More information

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? 5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS

More information

A. Product Data: For each type of product, including furnished options and accessories.

A. Product Data: For each type of product, including furnished options and accessories. SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Non-system

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

A. This Standard outlines the requirements for an addressable fire detection and alarm system.

A. This Standard outlines the requirements for an addressable fire detection and alarm system. 1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and

More information

FIRE ALARM SYSTEM Section 16750 Page 1

FIRE ALARM SYSTEM Section 16750 Page 1 FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's

More information

Life Alarm Fire Alarm Controls

Life Alarm Fire Alarm Controls FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

JULY 2013 UCB STANDARDS 16720-1

JULY 2013 UCB STANDARDS 16720-1 SECTION 16720 FIRE ALARM AND DETECTION SYSTEMS PART 1 GENERAL 1.01 Reference A. Related Sections 1. Section 15300 Fire Protection 2. Section 15950 Controls 3. Division 16 Electrical 4. Division 14 - Conveying

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM

SECTION 28 31 00 FIRE DETECTION AND ALARM SECTION 28 31 00 PART 1 - GENERAL 1.1 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the fire alarm equipment to form a complete coordinated

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00 SECTION 28 31 00 FIRE DETECTION AND ALARM GENERAL This section deals with the fire alarm system, including the control panel and integral equipment, wiring and circuitry, initiating devices, indicating

More information

INTRUSION DETECTION SYSTEM Section 281600

INTRUSION DETECTION SYSTEM Section 281600 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's

More information

C. NICET: National Institute for Certification in Engineering Technologies. D. Definitions in NFPA 72 apply to fire alarm terms used in this Section.

C. NICET: National Institute for Certification in Engineering Technologies. D. Definitions in NFPA 72 apply to fire alarm terms used in this Section. SECTION 283100 - FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped

More information

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011 Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms.

A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms. SECTION 283111 - PART 1 - GENERAL 1.1 SUMMARY A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms. 1.2 GENERAL REQUIREMENTS

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

SECTION 28 31 11 FIRE ALARM AND SMOKE DETECTION SYSTEMS WITH VOICE EVACUATION NOTIFICATION

SECTION 28 31 11 FIRE ALARM AND SMOKE DETECTION SYSTEMS WITH VOICE EVACUATION NOTIFICATION SECTION 28 31 11 FIRE ALARM AND SMOKE DETECTION SYSTEMS WITH VOICE EVACUATION NOTIFICATION PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire Alarm and Smoke Detection Systems with Voice Evacuation Notification.

More information

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.

More information

SECTION 16620 FIRE ALARM SYSTEM

SECTION 16620 FIRE ALARM SYSTEM SECTION 16620 PART 1 GENERAL FIRE ALARM SYSTEM 1.01 SUMMARY A. Work included: Labor, materials and equipment necessary to complete the installation required for the item specified under this Division,

More information

Section 13850 Fire Detection and Alarm Page 1 of 13

Section 13850 Fire Detection and Alarm Page 1 of 13 SECTION 13850 - FIRE DETECTION AND ALARM 1.1 APPLICABLE STANDARDS A. Fire detection and alarm systems shall be designed and installed in accordance with the following standards, including appendices (current

More information

5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems.

5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems. PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for Fire Detection and Alarm. B. The design guidelines contained

More information

The Benefits of ADDRESSABLE Fire Alarm Technology

The Benefits of ADDRESSABLE Fire Alarm Technology The Benefits of ADDRESSABLE Fire Alarm Technology NOTICE: If you were born after 1990 or if you lived through the 60 s and can t remember what happened since, you may be surprised to learn that fire alarm

More information

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH

More information

283100 FIRE ALARM AND DETECTION SYSTEMS

283100 FIRE ALARM AND DETECTION SYSTEMS 283100 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

COMMISSIONING OF FIRE ALARM SYSTEMS

COMMISSIONING OF FIRE ALARM SYSTEMS COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference

More information

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14 City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

B. NICET: National Institute for Certification in Engineering Technologies.

B. NICET: National Institute for Certification in Engineering Technologies. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

FIRE ALARM SYSTEM CHECK LIST

FIRE ALARM SYSTEM CHECK LIST FIRE ALARM SYSTEM CHECK LIST BUILDING NAME: DESIGNER: INSPECTION BY: LOCATION: INSTALLER: DATE: Preparation for Acceptance Test Fire authorities have been notified of the system test. Also notify any location

More information

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

B. All Fire Detection and Alarm design and installation shall comply with the most current and adopted version of NFPA 72.

B. All Fire Detection and Alarm design and installation shall comply with the most current and adopted version of NFPA 72. 28 31 00 PART 1 - GENERAL 1.01 SCOPE A. Background: Washington State University has agreements with Simplex- Grinnell and Siemens Industry, Inc. to provide Fire Detection and Alarm (FDA) systems for the

More information

PROJECT TITLE PROJECT NO: 0000000 CONTRACT TITLE GRANT NO: 0000000 UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: 0000000 CONTRACT TITLE GRANT NO: 0000000 UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA Fire alarm--all types of occupancies. The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this

More information

Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions. EPROM Electrically Programmable Read Only Memory

Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions. EPROM Electrically Programmable Read Only Memory Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions EPROM Electrically Programmable Read Only Memory EVAC Emergency Visual Audio Control FACP Fire Alarm Control Panel HVAC

More information

Module 5. Fire and Emergency Alarm System Part I- Basics

Module 5. Fire and Emergency Alarm System Part I- Basics Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

NATIONAL FIRE ALARM AND SIGNALING CODE

NATIONAL FIRE ALARM AND SIGNALING CODE GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

FIRE ALARM PERFORMANCE GUIDELINES

FIRE ALARM PERFORMANCE GUIDELINES FIRE ALARM PERFORMANCE GUIDELINES 2010 Design Guidelines 1 P a g e TABLE OF CONTENTS PART 1 GENERAL.3 1.1 RELATED DOCUMENTS...3 1.2 SCOPE.....3 1.3 QUALITY ASSURANCE....3 1.4 SUBMITTALS.. 5 PART 2 PRODUCTS..6

More information

Control/Communicator Installation Manual

Control/Communicator Installation Manual DAS NETWORX NX-8 Control/Communicator Installation Manual Page General Description... 2 Ordering Information... 2 Option Definitions... 2 Programming the LED Code Pads... 4 Programming the NX-8... 8 Types

More information

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over

More information