Section Fire Detection and Alarm Page 1 of 13

Size: px
Start display at page:

Download "Section 13850 Fire Detection and Alarm Page 1 of 13"

Transcription

1 SECTION FIRE DETECTION AND ALARM 1.1 APPLICABLE STANDARDS A. Fire detection and alarm systems shall be designed and installed in accordance with the following standards, including appendices (current edition at the time of design completion): 1. NFPA 70, National Electrical Code 2. NFPA 72, National Fire Alarm Code 3. Insurance Carrier Guidelines for Loss Prevention and Control. 4. Applicable Building and Health Codes (9NYCRR - NYSUFPBC & 10NYCRR - NYS Health Code) Fire detection and alarm system equipment shall be listed by Underwriters Laboratories (UL) or approved by Factory Mutual (FM) individually and as a system for their intended use. Compatibility - All fire detection devices that receive their power from the initiating device circuit or signaling line circuit of a fire alarm control unit shall be listed for use with the control unit. B. Utilize standard products of a single manufacturer for each system. Additionally, each system shall be issued a UL Fire Alarm Certificate (UL category UUJS Fire Alarm Firm) by the installing contractor. C. Fire detection and alarm system equipment shall be approved by the U of R Fire Marshal. 1. Acceptable Fire Alarm Equipment Manufacturers: Simplex, Cerberus Pyrotronics, Notifier, Edwards Systems Technology (EST). 2. Qualified contractors who layout & install systems at the U of R from information provided by the design professional of record, (contract documents), shall be National Institute for Certification in Engineering Technologies (NICET) Level III or IV Fire Alarm Technicians who are also factory trained and authorized by the equipment manufacturer of the systems being provided. D. Fire alarm interface with and reporting to the University's Central Fire Alarm Monitoring System shall be submitted for approval to the U of R Director of Security Services. All fire alarm systems shall report to the Central Fire Alarm Monitoring System by floor, zone, and type of device (i.e., water flow, manual pull, smoke detection, heat detection, special extinguishing systems, and supervisory signals). Refer to examples indicated herein. Patient care areas to report on Simplex True Site system (formerly GCC). 1.2 FIRE DETECTION AND ALARM SYSTEMS - GENERAL A. Where Required: Provide fire detection, occupant notification, and U of R central monitoring reporting for all new construction and major renovation projects as required for individual occupancies in the applicable building code and as indicated herein. All normally occupied buildings shall at a minimum (even if not code required) be provided with a manual fire alarm system to alert occupants and emergency forces. Note a manual fire alarm system does not include detection, only manual fire alarm boxes and notification appliances. Exceptions may include remote, small single story buildings and other normally unoccupied buildings, if reviewed and approved by the U of R Fire Marshal. B. All fire detection and alarm system designs and purchases shall be reviewed by the University Fire Marshal's Office. System drawings and equipment submittals shall be reviewed and approved by the University Fire Marshal's Office prior to installation. Submittals shall be in accordance with this and other sections with at least (4) concurrent copies to the U. of R. Representative. Section Fire Detection and Alarm Page 1 of 13

2 1. Product Data: Contractor's NICET/UL certification; manufacturer's catalog cuts with models/options; specifications; wiring diagrams; quantitative equipment list; and installation instructions for components, wiring and materials. Calculations, using actual amperage loads for each device, module, etc. used to determine stand-by battery ampere-hour rating shall be included and show normal, alarm and total amperage requirements. Content of automatic voice message and logic sequences including logic matrix for each system. Bind each set in folder with Table of Contents following specification sequence fully annotated. Submit all components as a set prior to or with any shop drawings. 2. Drawings: Each floor plan, typical and detailed wiring and riser diagrams cross referenced to related drawings; complete information for system installation; symbol legends, title blocks and to scale of 1/8=1. Where applicable, this shall be done on a PER FIRE PROTECTION ZONE basis. a. Floor plans: Locations of devices with device number at each device, appliances, panels, equipment, junction/terminal cabinets, risers, electrical power connections, individual circuits and raceway routing, system zoning; number, size, type raceways and conductors in each raceway; conduit fill calculations with cross section area percent fill for each type and size of conductor and raceway. Only those devices for final system shall be on these floor plans. Do not include locations of removed devices. b. Typical wiring diagrams: For each device showing termination identifications, size and type conductors. c. Detailed wiring diagrams: For control panels, modules, power supplies, electrical power connections, auxiliary relays and annunciators showing termination identifications, size and type conductors, circuit boards, LED lamps, indicators, adjustable controls, switches, ribbon connectors, wiring harnesses, terminal strips and connectors, spare zones/circuits. d. Riser diagrams: For entire system showing number, size and type of riser raceways and conductors in each riser raceway and number of each type device per floor and zone. e. Include information indicating who will certify the system and who will perform the guaranteed period services. f. University wide identification nomenclature system proposed for each device with examples. 3. Together with shop drawing submittals, submit a certification from the fire alarm equipment (control panel) manufacturer indicating that the proposed supervisor of installation and the proposed performer of guaranteed period services is an authorized representative of the fire alarm equipment manufacturer. Include name and address in the certification. 4. Together with the product data submittal, submit a certification from both the fire alarm equipment manufacturer and the detector manufacturer that the detectors being furnished are listed by UL as being compatible with the control equipment. The U. of. R will not accept any submittal without this certification. 5. Together with the product data submittal, submit a certification from the fire alarm equipment manufacturer that the wiring and connection diagrams meet UL and NFPA requirements. The U of R will not accept any submittal without this certification. 6. Submit a copy of the electrical installers Fire Alarm license. C. Equipment installers shall conduct a pre-acceptance test prior to acceptance test of all components in the presence of a representative from the University Fire Marshal's Office and Facilities Maintenance. Test shall be repeated until all defects have been remedied. Refer to Section 01910, Part 1.1 C. Record and Certification documents shall be provided to the U of R as follows: 1. In Each Operation and Maintenance Manual: Product data, drawings, test reports and Certificate of Completion per NFPA 72. Bind in sets. Section Fire Detection and Alarm Page 2 of 13

3 2. One electronic and one hard copy of the final updated operating and maintenance manual to the U of R Representative (Project Manager). These need to be provided in accordance wth the U of R Layering Standard. a. The manual (3-ring, loose-leaf binder or manufacturer's standard binder with space for folded drawings) shall be updated to include any information necessitated by shop drawing review; As installed wiring and schematic diagrams which show all items of equipment and their interconnecting wiring; all terminal identification; information for testing, repair, trouble shooting, assembly, disassembly, and recommended maintenance intervals; a replacement parts list with current prices; and a list of recommended spare parts, tools, and instruments for testing and maintenance purposes. Two weeks prior to final inspection, deliver to the U of R Representative four (4) copies of the certification by the authorized representative of the manufacturer of the fire alarm system equipment that the system has been properly installed, adjusted, and tested. D. Installer/supplier shall conduct up to three scheduled system familiarization classes at times agreed upon with the University Fire Marshal and Facilities. At the end of the warranty period, the supplier shall conduct a second thorough inspection and testing of the entire system, including sensitivity testing. E. Equipment shall be compatible with other University systems within the same category. All equipment provided within a specific project, contract, building, and system shall be of one manufacturer unless otherwise approved by the University Fire Marshal prior to submission of bids. Any equipment of different manufacturer shall be cross-listed with the primary fire alarm system and used only if approved by the U of R Fire Marshal. Each building shall only have one fire alarm system with one location for all control and annunciation to allow easy reset, testing, etc. This does not prohibit multiple control panels or network nodes within the same building provided they were originally designed by the manufacturer to operate as one system. Interconnection via relays and other external methods of smaller control panels not intended to work as one system will not meet this requirement. F. The complete fire protection system shall be fully tested and guaranteed for a period of one year after Owner s Representative written acceptance. 1.3 DESIGN REQUIREMENTS A. All smoke and heat initiating devices shall be Analog Initiating Devices (sensors) as defined in NFPA 72(8) (The National Fire Alarm Code). All manual fire alarm boxes, water flow switches, and other initiating and supervisory devices shall be individually addressable devices. Where project conditions indicate the need for modifications to these requirements, addressable devices or zones of conventional initiating devices may be provided when reviewed and approved by the U of R Fire Marshal (typically small, one and two story simple open floor plans). B. Notification appliances shall be designed and installed to alert building occupants and to transmit a signal to a constantly attended location (U of R Central Security Monitoring). 1. Buildings greater than four (4) stories in height shall utilize emergency voice/alarm notification. Buildings four (4) stories and less in height may use three code temporal pattern utilizing horns and strobes. 2. Health care occupancies shall utilize private mode notification as outlined in NFPA 72 with the exception of public areas (Le. lounges, gift shops, waiting areas, lobbies, etc.). 3. Provide visual indicating appliances as required by the Building Code, NFPA 72, ADA, and in the following areas: mechanical and equipment rooms, rest rooms, areas with a high level of ambient noise. 4. Provide accommodations to add visual notifications to sleeping rooms as needed for residents. 5. Group A occupancies with an occupant load of 1,000 or more shall utilize emergency voice/alarm notification. Section Fire Detection and Alarm Page 3 of 13

4 C. All new or renovated University fire alarm systems must be designed and installed to report the following fire alarm points/zones to the University of Rochester Security Services Central Alarm Monitoring System (currently ADT Centra-Scan 6000). The University Fire Marshal and Director of University Security Service may require more discrete fire zone reporting based on intended use of area being protected or intended use of space adjoining protected area. Special Hazard Areas include hazardous chemical, flammable liquid/gas, high radioactive or biohazard storage areas, high voltage rooms, incinerators, high magnetic field areas, areas where dangerous lasers are in use, generator rooms and other such areas as determined by the University Fire Marshal and Director of University Security Services. The following are examples for reporting fire alarm points/zones to the University Central Alarm Monitoring System: Fire Alarm Interface/Communication Panels 1. Common interface panel supervisory alarm 2. Common interface panel trouble alarm Local Fire Alarm Control Panels 1. Common fire panel supervisory alarm 2. Common fire panel trouble alarm Water Flow Tamper Devices 1. By device location if connected to addressable fire control panel 2. By floor if not connected to addressable fire control panel Medical Center General Office and Lab Areas 1. One zone per device type, by floor, by main grid/wing number 2. One zone per device type, by floor, by room for special hazard areas SMH Outpatient Clinical Areas 1. One zone per device type, by floor, by main grid number 2. One zone per device type, by floor, by room for special hazard areas SMH Inpatient Care Units 1. One zone per device type, per patient care unit, by floor SMH Inpatient Care Public Areas 1. One zone per device type, by floor, by main grid number Elevator Fire alarm Recall Systems - Option For Stand Alone System 1. One zone per device type, by floor for each elevator lobby 2. One zone per device type for each elevator control room 3. One zone per device type for each elevator shaft way 4. One zone per device type for each elevator penthouse 5. One zone per device type for each elevator pit Residential Life Buildings 1. One zone per device type, by floor, by wing Section Fire Detection and Alarm Page 4 of 13

5 Academic Buildings 1. One zone per device type, by floor 2. One zone per device type, by floor General University Office Buildings 1. One zone per device type, by floor 2. One zone per device type, by floor Research Facilities 1. One zone per device type, by floor 2. One zone per device type, by floor, by room for special hazard areas Parking Garages 1. One zone per device type, by parking level 2. One zone per device type, by floor, by office or mechanical/work room 3. One zone per device type, by floor, by room for special hazard areas Fire Pumps Zone/Point 1. Pump running 2. AC fail 3. Pump phase reversal D. Large complex systems shall be peer to peer network. E. Fire alarm zones which include all initiating devices and any audible or visual notification appliances shall coordinate with existing fire protection zones (sprinkler and smoke zones) where applicable. This information can be obtained from the U of R Fire Marshal's Office. F. Connect all new and existing electric water flow and tamper devices to the fire alarm system. Monitor fire pumps and transmit signal to University Central Alarm Monitoring System for loss of power, phase reversal, pump running, pump trouble. NOTE THE DIFFERENCE BETWEEN SUPERVISORY SIGNALS AND TROUBLE SIGNALS per NFPA 72 provisions. G. Fire alarm activation shall automatically release all magnetically held open smoke/fire doors upon activation. H. Fire alarm activation shall automatically communicate with building management systems to control selected air handling units where applicable. This information can be obtained from the U of R Facilities Dept. and the U of R Fire Marshal's Office. I. Where smoke detection is required by the applicable building code or this Standard, the following items shall apply: 1. Where required, photo-electric smoke sensors shall be used in all areas except main electrical rooms, laboratories, industrial areas, flammable liquid storage areas. 2. Where required, ionization smoke sensors shall be used in all main electrical rooms, laboratories, industrial areas, flammable liquid storage areas. J. Fire detection for elevators and elevator shafts shall comply with the requirements of the applicable building code, NFPA 70, NFPA 72, ANSI / ASME A17.1 and the following: Section Fire Detection and Alarm Page 5 of 13

6 1. Provide fire alarm system features for elevator Phase I and Phase II recall for new and existing elevators. Where existing elevators do not have Phase I and / or Phase II capability, provide in the elevator machine room immediately near EACH elevator controller, 3 fire alarm relays (phase I recall, phase II recall, elevator power shut down) for future connection to upgraded elevator controllers. 2. Smoke detection and heat detection shall be provided in all elevator hoistways and machine rooms regardless if these spaces are currently sprinklered. This will allow future sprinkler protection without fire alarm system modifications. 3. Phase I recall shall only be initiated by activated smoke detectors located at the elevator lobby, in the elevator machine room, or in the elevator hoistway per ANSI Elevator standard. Other smoke detectors or fire alarm activation shall not recall the elevators unless needed by the fire safety plan of the facility and reviewed with the U of R Fire Marshal. K. All fire alarm system wiring conduit shall be labeled / identified as such every 10 feet; at both sides of the structure where conduit penetrates partitions or floor slabs, at least once on every level, and at every junction box. Each junction box shall be painted red and labeled by stencil or other neat lettering fire alarm. PROVIDE INDIVIDUAL LABELS AT EACH ADDRESSABLE INITIATING OR CONTROL DEVICE WITH EACH DEVICE IDENTIFICATION NUMBER following the defined University wide nomenclature system. This device number shall be the same as that programmed in the fire alarm system and indicated on the LCD fire alarm annunciators and control panel for easy device verification upon alarm and testing. Labels shall be red plastic engraved and adequately secured to the device at the ceiling or immediately adjacent to the device at the ceiling. Wall devices shall be secured by screws into the wall, especially at manual boxes where tampering or removal of the label is probable. L. Smoke detectors / sensors shall not be located within 5 feet of air supply diffusers. M. System shall be 24 VDC power limited with 120 VAC primary input power. All portions of the system shall operate on stand-by rechargeable battery power in addition to the primary power supply. 1. Design load connected to primary power supply and standby batteries shall not exceed 80% of either supply's rated continuous capacity. 2. Primary power supply shall be sized to maintain all initiating devices in alarm and all notification appliances, annunciators and auxiliary function activated simultaneously (full load alarm) for 30 consecutive minutes. 3. Standby batteries shall be sized to maintain non-alarm supervisory power condition for 60 hours where not connected to an emergency generator and 24 hours where connected to an emergency generator with at least a 36 hour fuel supply followed by 5 consecutive minutes in full load alarm on battery power only (requires 15 consecutive minutes in full load alarm for systems utilizing voice communication). N. Manual fire alarm boxes shall be installed where required by the applicable building code and NFPA 72. Pull stations shall be located in Exit corridors near Exit doors for patient care areas. At least two pull stations shall be located in each zone (one by each Exit door) unless approved by the UR Fire Marshal. O. Duct detectors shall be photoelectric employing the sampling tube principle and shall provide remote test capability where the detector housing is over 5 ft. AFF. The fire alarm control panel (FACP) shall employ the capability of controlling ventilation equipment. The FACP shall also have the capability of resetting the duct detector following activation. In addition, the system shall provide the capability to by-pass the fan shut-down sequence for preventative maintenance and testing. Duct detectors shall report as a supervisory condition and report as such. P. Systems shall employ pre-programmed sequence buttons/toggles to enable the users to easily by-pass different outputs (i.e. fan shutdown, door holders, audio/visual devices, smoke watches, elevator recall, etc.). When an output is in the by-pass mode, the panel shall display a trouble signal and shall transmit the same to the University Central Alarm Monitoring System. Section Fire Detection and Alarm Page 6 of 13

7 Q. Each FACP shall have a data port available for the purpose of downloading reports on the condition of devices on the system to a laptop computer by the FMO. The FMO shall receive any cables, programs, or training necessary to retrieve these reports prior to project turnover. R. For atriums, large open floor spaces and high ceiling areas, consider use of beam type smoke detection in lieu of spot type detection if detection is required for these spaces. All detectors and devices must be positioned to allow access by the University staff for testing and maintenance of devices. 1.4 HEALTH CARE OCCUPANCIES A. Provide detection and notification as required by the building, health and fire codes. B. Smoke detection shall be located within 5 ft. of both sides of required held-open smoke/fire barrier doors. C. Manual pull stations shall be located on both sides of required smoke/fire barrier doors. D. Smoke detection is not required in hospital patient sleeping rooms and other patient areas under constant supervision of staff at ALL TIMES (i.e. where a constantly attended nurses station is surrounded by a suite of patient rooms). E. Audible notification appliances shall not be located in ICU suites, OR suites, and Cardiac Catheter Labs. Careful placement of 15 candela low intensity strobes or other flashing lights which will not cause disturbance of procedures will need review on a case by case basis with the U of R Fire Marshal and user of these spaces. F. Audible notification in the Medical Center including staff shall be by voice announcement. A 3 tone alert will begin the announcement followed by condition three-zero and then the location 3 times. After the announcement the audible device will tone for no more than 3 minutes. Coordinate with UR Fire Marshal. 1.5 DORMITORY OCCUPANCIES A. Provide detection and notification as required by the building and fire code. B. Provide smoke detection within corridors and elevator lobbies. C. Provide 24VDC, single station smoke detectors which are powered and supervised from the fire alarm control panel in each dormitory room with audible integral detector sounder in the room(s). Activation of these room single station detectors shall NOT activate the building wide fire alarm notification appliances but shall be identifiable at the fire alarm annunciator and control panels as an individual room or suite of rooms. A supervisory signal shall be sent to U of R Central security as a room smoke detector if accepted by the U of R Fire Marshal and Director of Security Services. For those dormitory buildings not currently protected throughout with a fire sprinkler system, an integral heat detector on the single station smoke detector shall be provided with the heat detector connected to the fire alarm and activating the building fire alarm notification appliances upon sensing heat. Heat detectors within dormitory areas protected with fire sprinkler systems are not required. Desired protection includes quick response residential sprinklers throughout, single station smoke detectors within sleeping rooms connected to the fire alarm per above, smoke sensors within corridors and at smoke doors, manual pull boxes, and all connected to Central Security Services. Use of 110 candela strobe located within 6 feet of the sleeping bed pillow location is required for those designated ADA and hearing impaired sleeping rooms. Each single station detector base shall have the ability to power this strobe and activate upon either single station device or building alarm activation. Optional 120V AC single station smoke detectors are acceptable in fully sprinklered (quick response) buildings upon review of U of R Fire Marshal. D. Where suites of dormitory sleeping rooms are present, activation of one single station detector within the suite shall automatically activate all detectors within the suite. E. Locate remote annunciators at building front entrances or 24 hour observed locations coordinated with the U of R Fire Marshal. Section Fire Detection and Alarm Page 7 of 13

8 1.6 AMBULATORY CARE OCCUPANCIES A. Provide detection and notification as required by the building, health and fire code. B. Smoke detection shall be located at both sides of required held-open smoke/fire barrier doors. C. Provide audible notification to be heard (15db above ambient noise) in all locations throughout the building. D. Provide visual indicating devices in all public accessible areas of the building. (Note - this does not include individual office spaces unless warranted on an individual basis.) Confer with University Fire Marshal's Office for unique areas or applications. 1.7 BUSINESS OCCUPANCIES A. Provide detection and notification as required by the building and fire code. B. Provide audible notification to be heard (15db above ambient noise) in all locations throughout the building. C. Provide visual indicating devices in all public accessible areas of the building. (Note - this does not include individual office spaces unless warranted on an individual basis). Confer with University Fire Marshal's Office for unique areas or applications. 1.8 ASSEMBLY OCCUPANCIES A. Provide detection and notification as required by the building and fire code. B. Provide audible notification to be heard (15 db above ambient noise) in all locations throughout the building. C. Provide visual indicating devices in all public accessible areas of the building. (Note - this does not include individual office spaces unless warranted on an individual basis). Confer with University Fire Marshal's Office for unique areas or applications. 1.9 STORAGE OCCUPANCIES A. Provide detection and notification as required by the building and fire code. B. Provide audible notification to be heard (15 db above ambient noise) in all locations throughout the building. C. Provide visual indicating devices in all public accessible areas of the building. (Note - this does not include individual office spaces unless warranted on an individual basis). D. Consider additional partial coverage smoke detection for use in high value storage areas. Spot type smoke detection cannot be used in unheated areas. Beam type smoke detection usually provides superior detection and covers larger areas INDUSTRIAL OCCUPANCIES A. Provide detection and notification as required by the building and fire code. B. Provide audible notification to be heard (15 db above ambient noise) in all locations throughout the building. C. Provide visual indicating devices in all public accessible areas of the building. (Note - this does not include individual office spaces unless. warranted on an individual basis). Confer with University Fire Marshal's Office for unique areas or applications. Section Fire Detection and Alarm Page 8 of 13

9 1.11 LABORATORY OCCUPANCIES A. Provide detection and notification as required by the applicable building code. B. Provide audible notification to be heard (15 db above ambient noise) in all locations throughout the building. C. Provide visual indicating devices in all public accessible areas of the building. (Note - this does not include individual office spaces unless warranted on an individual basis). Confer with University Fire Marshal's Office for unique areas or applications. D. Consider additional partial coverage smoke detection for use in specific locations where high value storage and experimentation occur and where smoke or particulates are not normally present FIRE ALARM SYSTEM COMPONENTS A. Fire Alarm Control Panels: 1. The control panel shall provide power, annunciation, supervision and control for the detection and alarm system. The control panel shall be modular in construction and contain all modules necessary for system operation. Modules shall be solid state, microprocessor based construction. 2. The system shall be field programmable, software driven and capable of one person walk test. Software shall reside in nonvolatile memory. 3. The system shall be capable of reading and displaying at the control panel, the sensitivity of remote intelligent/ analog detection sensors. Individual intelligent/analog sensor alarm thresholds shall be adjustable from the control panel. 4. Panel annunciator shall be an 80 character alphanumeric display. Annunciator shall provide a 32 character user definable message associated with each device or zone. Panel function indicating lamps shall be long life light emitting diodes (LED's). 5. Dynamic supervision of system electronics, wiring, detection devices and software shall be provided by the control system. Self testing of operating system shall be indicated by type and location on the alphanumeric annunciator. Software and processor operation shall also be annunciated upon failure. 6. Control Switches: Setup, test, reset, manual evacuation, silence and acknowledge. 7. Panel enclosure shall be designed for surface or recessed mounting. The cover shall have clear windows for viewing operational status and be lockable. Color shall be manufacturer's standard. 8. The panel shall be equipped with battery charging circuits sufficient to recharge fully depleted batteries to within 70% of maximum capacity within 12 hours. B. Smoke Detectors / Sensors: 1. Photo-electronic smoke sensors/detectors shall operate by the light scattering principal and shall contain a solid state LED, a mirror and a light sensing photodiode. Sensors shall operate at nominal 3.0% obscuration sensitivity provisions. 2. Ionization sensors/detectors shall contain two ionization chambers and an LED alarm indicator for activation by the presence of combustion products. The reference chamber and the microcomputer chip's software shall compensate against sensitivity changes caused by environmental factors. Shall operate at nominal 1.5% obscuration sensitivity provisions. Section Fire Detection and Alarm Page 9 of 13

10 3. Sensors shall be microprocessor based integrated circuitry for two-way communication with fire alarm control panel. Circuitry shall be contained in the sensor, not within the mounting base. 4. Common mounting twist-lock base with capability for mounting either smoke sensors or heat sensors. Removable cover and insect screen for field cleaning. 5. Sensors shall operate on a two wire circuit and contain LED indicator(s) which shall pulse whenever checked by the fire alarm control panel and latch on when in alarm. 6. Sensor shall be dynamically supervised and uniquely identifiable by the fire alarm control panel. The sensor's analog value shall be analyzed by the fire alarm control panel for calibration, identification and sensitivity. 7. High bay areas such as mechanical spaces and atriums shall have remote test capabilities. C. Duct-Type Smoke Detectors / Sensors: 1. Each unit shall consist of detector head, detector base, duct housing, and sampling tube. 2. Intelligent photo-electronic sensor shall communicate actual smoke chamber values to the system control panel; system shall automatically compensate for environmental changes. 3. Sensor completely shielded to protect from EMI and RFI. 4. Sensors shall operate on a two wire circuit. Integral LED shall pulse whenever sensor is checked by the fire alarm control panel and latch on when in alarm. 5. Sensors / detectors shall be dynamically supervised and uniquely identifiable by the fire alarm control panel. The sensor's analog value shall be analyzed by the fire alarm control panel for calibration, identification and sensitivity. 6. Size sampling tubes for full width of the duct. 7. Provide a remote test station and LED type remote indicating light directly below each detector and mount on the underside of the ceiling or wall where the detector is concealed. Label duct smoke detector remote indicator. D. System Heat Detectors / Sensors: 1. Fixed temperature detectors / sensors: a. Low profile, white colored, surface mounted on flush box; 135 F fixed temperature electronic thermistor with re-usable temperature element. Visual LED indicator for tripped mode and ensuring power is present and sensor is being polled. b. Thermoplastic housing with mounting to same base as smoke detectors. c. A system addressable initiating module shall be permitted to connect each group of elevator conventional heat detectors to the system. 2. Rate Compensated Heat Detectors: for special hazard systems. E. Manual Fire Alarm Boxes: 1. Semi-flush, non-coded, addressable type with addressable module located within the pull station or within 10' immediately above the pull station. Section Fire Detection and Alarm Page 10 of 13

11 2. Pull down type, single action U of R standard, unless otherwise reviewed and approved by the University Fire Marshal's Office. These devices shall be installed so that the top of the device does not exceed 48 inches AFF. 3. Indoor construction, bright red finish, manufactured from high impact lexan with raised white letters. 4. Mechanically latch open upon operation until manually reset by opening with University standard issue key, including control panel locks. 5. Dynamically supervised and uniquely identifiable by the system. F. System Audible / Visual Notification Appliances: 1. Speakers: a. Surface or flush mounted for wall and flush for finished ceiling mounting. b Hz frequency response. Field selectable 25/70.7V RMS operating line voltage with 1/4, 1/2, 1 and 2 watt taps. Normally set for the 1 watt setting subject to adjustment during the fire alarm system acceptance testing at the discretion of the Fire Safety representative. c. Die-cast housing, water sealed compression driven, vandal resistant grille and baked white or red epoxy finish. 2. Strobe Units: a. Nominal 24 VDC with built-in Xenon flashtube and solid state circuitry. UL 1971 listed. b. Polycarbonate lens, pyramidal shaped with the word a FIRE imprinted in red on white lens side - clear lens at strobe front face. Flush wall mounted. c. Minimum effective intensity rating of 15, 75 or 110 candela per UL 1971; rated life of minimum 500 hours of continuous operation. Synchronized flash rate of 1 per second. Use 15 candela ratings for corridors and public restrooms; and candela ratings arranged per NFP A 72 Chapter 6 for other public areas. 3. Provide separate strobe units or in combination with audible appliances. 4. Audible appliances or audible/strobe combination units use 4 square backbox with extension and single strobes use single gang backbox. 5. Multi-Tone Appliance (Horns): a. 24 volts DC. Basic grille type, surface or flush mounted. Color shall be red as standard or white if required for aesthetic purposes. b. Signaling device shall be capable of producing the following electronic signals: 1. Horn rated 95 10ft. (broadband, continuous) ft. (1560 Hz modulated). 3. Code ft. (ANSI temporal pattern). 4. Code ft. (ANSI temporal pattern). c. Indoor construction, unless noted WP for weatherproof type construction. d. Provide backbox and grille for installation; 4 in. deep box maximum. Section Fire Detection and Alarm Page 11 of 13

12 G. Fire Safety Control Equipment: 1. Addressable Control Relay Modules (ACRM): Supervised addressable relay module which is remotely located from fire alarm control panel; operated via 24 VDC fire alarm power; relay contacts rated 10 amp 120 VAC for releases of magnetic door holder circuits, elevator recall, etc. 2. Addressable Initiating Modules (AIM): Supervised addressable solid state electronic module for mounting in 4 x 4 junction box to interface between tamper, water flow, low air, kitchen fire system, zone of elevator heat detectors, and other contact type non-addressable devices. H. Power Supplies: 1. Primary power supply: 120 VAC, 60 Hz input and transformed, rectified, filtered and regulated, 24 VDC output. Coordinated with standby batteries and charger for automatic transfer without loss of power or data. Protection from lightning, voltage and current transients for entire system. 2. Standby battery and charger: a. Batteries: 24 VDC maintenance free lead calcium wet cell batteries; cell reversal protection; ten year life expectancy; fused battery connections. Batteries shall be supervised. b. Charger: Self-regulating, solid state type, automatic with capability to fully charge the completely discharged batteries within twenty-four hours. c. Provide additional NEMA 1 vented shop painted steel enclosure and steel wall mount brackets for standby batteries where required due to battery sizes. Locate above control panels, verify with U of R Representative. I. Terminal Strip Cabinets (Provide at least 1 per floor with signaling line circuit (SLC) and audible and visual notification circuits to allow future system extensions and modifications without homeruns back to control panel or splicing wiring). 1. Lockable, vandal resistant surface mounted cabinets constructed of 14 gauge steel, size as recommended by the company producing the system. 2. Equip cabinets with barrier type double screw terminals rated 300V minimum, meeting UL 94 requirements for materials classed 94V-O. 3. Use identification strips, tags or labels to identify each conductor. 4. Shop paint cabinets red and stencil on front in 1/2 in. high white letters, to identify the purpose of each terminal strip cabinet. J. Remote Annunciators and Manual Paging Stations: character LCD type display, local piezo sounder upon status change, single master key activated control switches for acknowledgment of alarm and silence of local piezo. Only monitors and displays status of system and shows each device message same as master fire alarm control panel, but shall not permit system notification appliance silencing or reset of any system without the use of a master key lockout switch. 2. Manual paging station shall include press to talk microphone and pre-amplifier. Station to be placed in locked cabinet, keyed to the FACP common key SYSTEM WIRING (REFER TO NFPA 72 NATIONAL FIRE ALARM CODE AND APPENDIX SECTION 13-3 FOR DEFINITIONS AND FURTHER GUIDANCE) Section Fire Detection and Alarm Page 12 of 13

13 A. Entire system shall be in EMT or other metallic raceway system. Provide at least a 12 foot flexible MC or other metallic flexible conduit whip from each structure mounted j-box to each ceiling mounted device to allow minor relocation of devices without extending conductors. Support all raceways and devices direct to structure and not to ceilings or other systems. Use rigid and other raceway types as required by NEC and NFPA 72. WIRING SHALL BE CONTINUOUS BETWEEN DEVICES WITH NO SPLICES, WIRE NUT CONNECTIONS OR TERMINATIONS AT ANY LOCATIONS OTHER THAN A FIRE ALARM DEVICE, TERMINAL STRIP OR CONTROL PANEL. Control panels shall not be used as junction boxes. Flexible MC cable painted/striped red or FPLP cable without raceways may be used on floors above ceilings only and beyond terminal cabinets if accepted in writing by U of R Fire Marshal & Project Manager due to budget and other considerations. B. Signaling Line Circuits (SLC): 1. Number of and size of conductors as recommended by the fire alarm manufacturer of the system, site conditions, system performance needs of individual building and per NEC Article 760 requirements. 2. Solid copper twisted, shielded and jacketed conductors: Type FPL, FPLP, FPLR, NFPL, NFPLP, NFPLR. Use of TFN or THHN/THWN insulation, rated 600 volts, 90 degree C is generally not permitted. 3. All SLC between control panels (network type systems) and between floor terminal cabinets and control panels shall use Class A Style 7 circuit types. Floor SLC beyond floor terminal cabinets may be Class B style 4 circuits provided isolation modules are included to isolate circuit faults so no more than 1 floor of a building is nonfunctional during a fault condition, otherwise Class A Style 6 or 7 circuits are required. Buildings with very large floor areas will require further review with the U of R Fire Marshal regarding permitted floor areas protected by one SLC. Generally, SLC should be arranged on a horizontal floor basis. C. Initiating Device Circuits (ldc): 1. For those circuits between contact type devices (flow switches, conventional heat detectors, etc.) and an addressable input modules, Class B, Style C IDC are required. For conventional fire alarm systems in existing buildings which are not protected with a fire sprinkler system, IDC shall be Class A, Style D or E. 2. Solid copper jacketed minimum 14 AWG conductors: Type FPL, FPLP, FPLR, NFPL, NFPLP, NFPLR. Use of TFN or THHN/THWN insulation, rated 600 volts, 90 degree C is generally not permitted. D. Notification Appliance Circuits (NAC): 1. Same as signaling line circuits, except that conductor size shall not be less than No. 14 AWG and use of TFN or THHN/THWN conductors may be permitted for strobe circuits upon U of R Fire Marshal approval. 2. Visible devices shall be on circuits separate from audible devices. Class B Style Y required for all NAC, except Class A Style Z required for buildings not protected throughout with fire sprinkler protection and where total building evacuation does not occur (i.e.. protect in place concepts for high rises, hospital, etc.). Modifications may be permitted upon review and approval of the U of R Fire Marshal. END OF SECTION Section Fire Detection and Alarm Page 13 of 13

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus

More information

SECTION 16700 FIRE ALARM SYSTEM

SECTION 16700 FIRE ALARM SYSTEM SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as

More information

A. This Standard outlines the requirements for an addressable fire detection and alarm system.

A. This Standard outlines the requirements for an addressable fire detection and alarm system. 1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

FIRE ALARM SYSTEM Section 16750 Page 1

FIRE ALARM SYSTEM Section 16750 Page 1 FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract

More information

JULY 2013 UCB STANDARDS 16720-1

JULY 2013 UCB STANDARDS 16720-1 SECTION 16720 FIRE ALARM AND DETECTION SYSTEMS PART 1 GENERAL 1.01 Reference A. Related Sections 1. Section 15300 Fire Protection 2. Section 15950 Controls 3. Division 16 Electrical 4. Division 14 - Conveying

More information

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification

More information

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? 5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM

SECTION 28 31 00 FIRE DETECTION AND ALARM SECTION 28 31 00 PART 1 - GENERAL 1.1 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the fire alarm equipment to form a complete coordinated

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

B. NICET: National Institute for Certification in Engineering Technologies.

B. NICET: National Institute for Certification in Engineering Technologies. PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM FIRE DETECTION AND ALARM GENERAL INFORMATION 1.1 In general, follow the guidelines below when designing and specifying addressable fire alarm systems. Unless specifically indicated otherwise, these guidelines

More information

16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC

16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC 1. GENERAL 1. Fire alarm system shall be manufactured by Simplex, Autocall or Edwards. Simplex part numbers are provided in this spec for clarification only and do not exclude equivalent part numbers of

More information

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 FIRE ALARM AND DETECTION SYSTEMS

Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 FIRE ALARM AND DETECTION SYSTEMS Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 SECTION 28 31 00 PART 1 GENERAL 01 SUMMARY A. This Section covers fire alarm systems, including initiating devices, notification appliances,

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

2012 Ontario Building Code Changes Affecting Fire Alarm Systems 2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development

More information

Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions. EPROM Electrically Programmable Read Only Memory

Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions. EPROM Electrically Programmable Read Only Memory Section 28 31 00: Fire Alarm Detection Systems (formally Section 16720) Definitions EPROM Electrically Programmable Read Only Memory EVAC Emergency Visual Audio Control FACP Fire Alarm Control Panel HVAC

More information

A. Product Data: For each type of product, including furnished options and accessories.

A. Product Data: For each type of product, including furnished options and accessories. SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Non-system

More information

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University

More information

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified. Fire Alarm System Plan Review Checklist 2010 OFC and 2007 NFPA 72 This checklist is for jurisdictions that permit the use of the 2007 NFPA 72 in lieu of IFC s referenced 2002 NFPA 72. Date of Review: Permit

More information

SECTION 16760 - PLANT INTERCOMMUNICATION SYSTEM. City of San Diego, CWP Guidelines

SECTION 16760 - PLANT INTERCOMMUNICATION SYSTEM. City of San Diego, CWP Guidelines PART 1 - GENERAL SECTION 16760-1.1 WORK OF THIS SECTION City of San Diego, CWP Guidelines A. The WORK of this Section includes providing plant intercommunication systems with power supplies, signal amplifiers,

More information

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 AMHERST COLLEGE ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 Michael Zlogar April 11, 2001 Assistant Fire Chief Amherst Fire Department 68 North Pleasant St. Amherst, MA 01004 FIRE ALARM

More information

SECTION 16610 FIRE DETECTION AND ALARM SYSTEM

SECTION 16610 FIRE DETECTION AND ALARM SYSTEM SECTION 16610 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply

More information

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms.

A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms. SECTION 283111 - PART 1 - GENERAL 1.1 SUMMARY A. This Section covers addressable fire alarm systems for wet and dry sprinkler systems, clean agent systems, and building fire alarms. 1.2 GENERAL REQUIREMENTS

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00

DESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES 28 31 00 SECTION 28 31 00 FIRE DETECTION AND ALARM GENERAL This section deals with the fire alarm system, including the control panel and integral equipment, wiring and circuitry, initiating devices, indicating

More information

Prepared For: Prepared By: [INSERT DATE]

Prepared For: Prepared By: [INSERT DATE] STANDARD SPECIFICATIONS FOR THE DESIGN AND INSTALLATION OF AUTOMATIC FIRE ALARM SYSTEMS THE UNIVERSITY OF ALABAMA TUSCALOOSA, ALABAMA [INSERT PROJECT NUMBER] [INSERT PROJECT NAME] Prepared For: University

More information

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this

More information

FIRE ALARM SYSTEM CHECK LIST

FIRE ALARM SYSTEM CHECK LIST FIRE ALARM SYSTEM CHECK LIST BUILDING NAME: DESIGNER: INSPECTION BY: LOCATION: INSTALLER: DATE: Preparation for Acceptance Test Fire authorities have been notified of the system test. Also notify any location

More information

283100 FIRE ALARM AND DETECTION SYSTEMS

283100 FIRE ALARM AND DETECTION SYSTEMS 283100 FIRE ALARM AND DETECTION SYSTEMS PART 1: GENERAL 1.01 QUALITY ASSURANCE A. The integrated fire alarm system including all equipment, components, and accessories shall be UL listed for the purpose

More information

Fire Alarm Systems Permit Packet. City of Greer Fire Department

Fire Alarm Systems Permit Packet. City of Greer Fire Department Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting

More information

5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems.

5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems. PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for Fire Detection and Alarm. B. The design guidelines contained

More information

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14 City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

SECTION 16620 FIRE ALARM SYSTEM

SECTION 16620 FIRE ALARM SYSTEM SECTION 16620 PART 1 GENERAL FIRE ALARM SYSTEM 1.01 SUMMARY A. Work included: Labor, materials and equipment necessary to complete the installation required for the item specified under this Division,

More information

SECTION 16721 MULTI-FIRE ALARM SYSTEM

SECTION 16721 MULTI-FIRE ALARM SYSTEM PART 1. GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification Sections, apply to this Section.

More information

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work GE Security Small Building Life Safety Solutions Affordable FireShield Conventional Fire Alarm Control Panels imagination at work cost Location: Environment: Solution: Flower shop Finely decorated, gentle

More information

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.

More information

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH

More information

PROJECT TITLE PROJECT NO: 0000000 CONTRACT TITLE GRANT NO: 0000000 UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

PROJECT TITLE PROJECT NO: 0000000 CONTRACT TITLE GRANT NO: 0000000 UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA Fire alarm--all types of occupancies. The following standard specification is intended to be edited according to the specifics of the project. Brackets [ ] and areas shaded in gray [e.g. format] indicate

More information