SECTION FIRE DETECTION AND ALARM SYSTEM

Size: px
Start display at page:

Download "SECTION 16610 FIRE DETECTION AND ALARM SYSTEM"

Transcription

1 SECTION FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 REQUIREMENTS A. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply to the work specified in this Section SCOPE A. The work covered under this Section shall include engineering, designing, testing, furnishing and installing a complete and operable addressable type analog fire detection and alarm system shown on the Drawings and herein specified. The system shall include, but not be limited to: control panel including backbox; remote graphic annunciator panel including backbox; alarm initiating and indicating peripheral devices; outlet boxes; conduit; line and low voltage wiring; and all accessories required. B. The existing fire detection and alarm system shall remain in operation during the construction period until the new system has been installed, tested, and approved by the Fairfax County Fire Marshal and the Owner. The existing system shall then be removed as shown on the Drawings QUALITY ASSURANCE A. All devices and equipment for this system shall be listed by the Underwriter's Laboratories, Inc. (UL), bear the UL label and shall conform to the applicable sections of National Fire Protection Association (NFPA) 72 and 90A, and the Americans with Disabilities Act (ADA) Code of Federal Regulation. B. The installation shall be in accordance with all requirements of NFPA, the National Electrical Code (NEC), all state and local codes and requirements, and these Specifications. C. This Contractor shall furnish shop drawings submittals for all components of this system in accordance with SECTION of these specifications. Submittals shall include the following for review. Submittals not containing all of the information listed below will be rejected. 1. A complete list by model number of each component of the system with a statement of how many pieces of each model are to be furnished and a listing of the specific data sheet. 2. A description of the system as it functions by component in the system using model numbers where applicable /13

2 3. A complete battery calculation listing by module for the system. 4. A data sheet shall be furnished for each component of the system. The specific information shall be highlighted. 5. A detailed drawing of the control panel shall be furnished showing all modules in their specific location with the specific terminal terminations shown. 6. A detailed set of floor plans for the complete building shall be furnished showing the locations of all equipment and devices, their addresses, and their required interconnections. The interconnections shown shall indicate the system manufacturer's recommended number, size, and type of wires as described in this Specification. The plans shall show the locations of all required control and monitor modules and their addresses. The layout of all fire detection and alarm system equipment, devices, and conduit routings shall closely follow that shown on the Drawings. 7. A detailed drawing shall be furnished of each type of device showing the exact terminal designations. 8. A detailed list shall be furnished of each type of device in the system stating its program function in the system. 9. A detailed list shall be furnished of the relays in the system and their program function. 10. A detailed manufacturer's drawing shall be furnished of the graphic annunciator panel, as it shall appear on the wall in the location of its installation. 11. Certification by the equipment distributor of the required service response time. D. Following review of the submittals by the Architect/Engineer and Owner, and prior to release of the fire alarm equipment, this Contractor shall submit to the Fairfax County Fire Marshal's office all copies of the corrected submittals for review, comment, and approval. This contractor shall not release any equipment prior to receiving the Fairfax County Fire Marshall approved shop drawing. This contractor shall be responsible for paying all fees associated with the Fire Marshall s review. E. The installation of all equipment and the final connection of all components and wiring shall be performed under the direct supervision of the system manufacturer's technical staff /13

3 F. Upon completion, the system shall be thoroughly tested by this Contractor to assure proper interfacing of all components. G. Prior to final inspection, this Contractor shall furnish to the prime Contractor, five (5) copies of the manufacturer's submittal drawings up-dated to reflect: any and all revisions to the system made during construction; and the final addresses of all devices. A printed list of system devices, which will include the following: device type, address, and custom message. H. The equipment to be furnished by this Contractor under these Specifications shall be the standard product of one manufacturer. Acceptable manufacturers shall be engaged in the manufacture of multiplexed fire alarm equipment for at least seven (7) years and have a fully equipped, factory trained and authorized service organization that will have a response time of four (4) hours or less to the job site The acceptable manufacturers shall be as follows EDWARDS SYSTEMS TECHNOLOGY (EST); NOTIFIER; and SIMPLEX TIME RECORDER CO. I. The fire detection and alarm system shall be furnished by a factory authorized distributor certified to design, program, and service the system. This distributor must show evidence of successfully furnishing systems as specified for at least five (5) years. This distributor shall provide twenty four (24) hour, seven (7) day a week (including holidays) service capability with a maximum four (4) hour response time. This distributor shall provide certification of this capability as part of the submittals. J. This contractor shall furnish to the Owner the following keys in the quantities indicated. 1. Fire Alarm Annunciator Panel Access Two (2) 2. Fire Alarm Annunciator Control Switches Five (5). 3. Fire Alarm Control Panel Five (5) 1.04 DESCRIPTION OF SYSTEM A. The fire detection and alarm system shall be individual point addressable, general alarm, electrically supervised, continuously sounding temporal tone signal with audible and visual alarm and trouble indications. 1. Each individual alarm initiating device shall report to the control panel as a separate "address". 2. The remote graphic annunciator panel's fire zone, and sprinkler zone boundaries shall be in accordance with the Fairfax County's regulations and the Architect/Engineer's detail on the Drawings /13

4 B. Activation of a manual fire alarm pull station; automatic smoke, heat detector; kitchen hood extinguishing system; or waterflow switch shall cause the following: 1. All audible/visual-signaling devices shall sound continuously having a temporal tone signal until manually silenced. A subsequent alarm received after silencing shall again cause the alarm indicating circuits to be activated. The fire alarm signals shall be distinctive from all other alarm signals and shall be clearly audible throughout the entire building. 2. The appropriate alarm source indicating lamps shall energize on the remote graphic annunciator panel and indicate type of device and geographic fire zone. Graphic annunciator panel lamps, when lighted, shall be constantly illuminated. Flashing lamps will not be acceptable. 3. Auxiliary contacts shall activate the security intrusion system. 4. Operation of any intelligent thermal detector in the elevator machine room and/or elevator shaft shall automatically shut down the associated elevator. 5. Close all normally held-open smoke doors. 6. Visually indicate via the integral control panel LCD display, the addressable device in alarm. When the control panel goes into the alarm condition: the ALARM (red) LED shall light; the internal control panel alarm shall sound; and the first line of the minimum eighty (80) character LCD shall indicate the REAL TIME, the number of MESSAGES WAITING, and the TIME THAT THE ALARM OCCURRED. The second line shall display the TYPE OF ALARM and the ALARM ZONE NUMBER. The third and fourth lines shall display the user specified message. In order to reduce false alarms, all inputs shall be capable of alarm verification. The system shall be capable of setting the sensitivity of all analog detectors by point and shall be capable of displaying the analog value of the detector by device and/or traditional input and vectoring the value to a remote printer. The system shall automatically identify any analog detector which becomes dirty (maintenance alert) prior to false alarming. 7. (Engineer to edit out for middle and elementary) Activation of a manual striking station (only) shall initiate a three (3) minute delay in activating the signal circuits including the activation of the auxiliary contacts. This delay shall be activated and deactivated through a key switch on the fire alarm graphic annunciator panel and include an "delay activated" indicator light. Alarm indications at the fire alarm control panel and fire alarm graphic annunciator panel shall not be delayed /13

5 C. (Engineer to edit) Activation of a sprinkler valve tamper switch; dry pipe HI/LO air; air duct type detector; fire pump fault; or generator fault shall cause the following: 1. The appropriate amber alarm source indicating lamp shall energize on the remote graphic annunciator panel and the integral audible trouble signal shall sound. 2. Auxiliary contacts shall activate the security intrusion system. 3. Visually indicate via the integral control panel LCD display, the addressable sprinkler valve tamper switch, dry pipe HI/LO air, air duct type detector, fire pump fault, or generator fault in alarm. When the control panel goes into the alarm condition: the NORMAL (green) LED shall extinguish; the SUPERVISORY (amber) LED shall light; and the internal control panel alarm shall sound which shall be distinct from all other alarm sounds. The first line of the minimum eighty (80) character LCD shall indicate the REAL TIME, the number of MESSAGES WAITING, and TIME THAT THE ALARM OCCURRED. The second line shall display the TYPE OF ALARM and the ALARM ZONE NUMBER. The third and fourth lines shall display the user specified message. In order to reduce false alarms, all inputs shall be capable of alarm verification. 4. Operation of any air duct type smoke detector shall automatically shut down the associated air-handling unit and units which serve the same area, such as gymnasiums, cafeteria, auditoriums, etc. D. The system, including the remote graphic annunciator panel, shall remain in alarm condition until the initiating device is reset to normal and the control panel is reset. System reset shall be accomplished on a single key-operated switch on the remote graphic annunciator panel. E. The system shall use 120-volt commercial power as its normal source of power. Upon failure of the normal source, the system shall automatically transfer to the standby power supply which shall be capable of supporting all system supervisory functions for all initiation and signal circuits for a period of four (4) hours as required by NFPA 72A. F. In the event of failure of operating power, an open, or ground condition on the system wiring, the trouble signals (both audible and visual) shall actuate at the remote graphic annunciator panel. It shall be possible to silence audible trouble signals by means of silencing switches; however, it shall not be possible to extinguish the visual signals until the disarrangement has been corrected. Upon correction of the trouble condition, the audible trouble signal shall sound until the silencing switch is returned to normal or the system automatically resets the trouble indication. Alarm or trouble indication shall cause an auxiliary contact operation connected to the security system Field Interface Device /13

6 1.05 TESTING A. Upon final completion of the installation, and acceptance of each construction phased space, and after satisfactory testing of the system by this Contractor in the presence of the equipment supplier, this Contractor shall test the system in the presence of the Architect/Engineer, Fire Marshall, Owner, and other authorities having jurisdiction. The manufacturer shall furnish to the Owner a two (2) year contract effective from the date of acceptance, for maintenance and inspection service of the manufacturers' equipment. The manufacturer shall maintain an adequate supply of spare parts for ten (10) years, and shall provide supervision of the installation. The manufacturer and/or their distributor shall provide twenty-four (24) hour/seven (7) day (including holidays) service to the system as hereinbefore described WARRANTY A. This Contractor shall deliver the work described herein in a first-class operating condition in every respect. This Contractor shall also warrant that the material, equipment, and workmanship furnished shall be entirely free from defects. Any materials, equipment, or workmanship in which defects may develop before or during the warranty period shall be repaired or replaced at the Contractor s own expense. Refer to SECTION for the start of the warranty period. The contractor shall further warrant that all material, equipment, and workmanship used in the installation, but not specifically mentioned in the Drawings and Specifications, is the best of their respective kinds and that the construction and installation was performed in accordance with the best accepted standard practices in all details. B. It is the intention of this Specification that a complete life-safety system be furnished from a single manufacturer. Equipment shall be UL listed for fire alarm use INSTRUCTION AND MANUALS A. The equipment manufacturer shall provide eight (8) hours of instruction to the Owner's maintenance personnel and shall furnish three (3) complete field service manuals SPARE PARTS A. This Contractor shall furnish to the Owner spare parts as follows. Spare parts shall be furnished prior to the installation of the system. 1. Two (2) intelligent smoke detectors including bases. 2. Two (2) intelligent thermal type detectors including bases /13

7 PART 2 - PRODUCTS 3. Four (4) intelligent control modules. 4. Four (4) intelligent monitor modules. 5. Two (2) manual pull stations and intelligent monitor modules for each. 6. Six (6) audio/visual alarm signals. 7. Two (2) exterior alarm signals including surface mounted weatherproof backboxes. 8. Four (4) visual only alarm signals 2.01 NEW MAIN CONTROL PANEL A. The control panel shall be modular for ease of installation, maintenance, and configuration. The controller shall be capable of supporting a minimum of 1,900 supervised inputs/outputs per single line network without any change in hardware. The control panel controller shall have an eighty (80) character alphanumeric display that offers four (4) twenty (20) character lines. B. The control panel shall differentiate between long term drift above the pre-alarm threshold (maintenance alert, indicative of the need for cleaning) and a fast rise above the pre-alarm threshold (indicative of a smoldering fire). The maintenance alert shall be annunciated as an alert on the LCD only and shall not be confused as a trouble or an alarm. The unit shall contain a display module of the membrane style construction with a four (4) line by twenty (20) character liquid crystal display (LCD). The LCD shall use super-twist technology and backlighting for high contrast visual clarity. In the normal mode, the LCD shall display the TIME, the TOTAL NUMBER OF ACTIVE EVENTS, and the TOTAL NUMBER OF DISABLE POINTS. In the alarm mode, the LCD shall display the TOTAL NUMBER OF EVENTS, and the TYPE OF EVENT ON DISPLAY. Forty (40) characters of display space shall be reserved for the user s custom messages. The module shall have visual indicators for the following common control functions: AC POWER; ALARM; SUPERVISORY, MONITOR, TROUBLE, DISABLE, GROUND FAULT, CPU FAILURE, and TEST. There shall be common control keys and visual indicators for: RESET; ALARM SILENCE; TROUBLE SILENCE; DRILL; and one (1) custom programmable key/indicator. The module shall include four (4) pairs of display control keys for selection of event display by type (alarm, supervisory, monitor, and trouble) and forwardbackward scrolling through event listings. The operation of these keys shall be integrated with the related common control indicators to flash the indicators when undisplayed events are available for display and turn-on steady when all events have been displayed. The module shall allow the first event of the highest priority to capture the LCD for display so that arriving fire fighters can view the first alarm /13

8 event hands free. The module shall provide the following system function keys: STATUS; REPORTS; ENABLE; DISABLE; ACTIVATE; RESTORE; PROGRAM; and TEST. The module shall have a numeric keypad, zero (0) through nine (9), with delete and enter keys. C. During the normal state, the NORMAL (green) LED shall flash, the first line of the LCD shall display the time in (HH:MM:SS) as well as the number of active points and the number of disabled points in the system. When the control panel goes into the alarm condition, the first line of the minimum eighty (80) character LCD shall indicate the REAL TIME; the NUMBER OF MESSAGES WAITING; and TIME THAT THE ALARM OCCURED. The second line shall display the TYPE OF ALARM and the ALARM ZONE NUMBER. The third and fourth lines shall be dedicated to user specified messages. To silence audible devices the operator shall press the ALARM SILENCE button. A new alarm shall cause the audible devices to resound. To reset the network the operator shall press the RESET button. D. The control panel controller shall support and control any combination up to five (5) additional true networked slave control modules, serial annunciators and switches, over RS485, RS232, fiber optics, or 20 MA loop, and be Ethernet ready as required. E. The control panel controller shall contain a RS232 printer/programming port for programming locally via a personal computer or down loading through modems from a remote personal computer. F. The main controller shall be supervised, site programmable, and of modular design supporting up to ninety six (96) detectors and ninety four (94) remote modules, and two (2) notification appliance circuits (NAC). Additional support for expansion modules shall be provided to add an additional ninety six (96) detectors and ninety four (94) modules including two (2) additional NAC circuits. The NAC shall be convertible to power risers to serve remote multiple NAC modules for zoned signal applications. The system shall have built-in automatic system programming to automatically address and map all system devices attached to the main controller. A minimum default single stage alarm system operation shall be supported with alarm silence, event silence, drill, lamp test, and reset common controls. The system shall support distributed processor intelligent detectors with the following operational attributes: integral multiple differential sensors; automatic device mapping; electronic addressing; environmental compensation; pre-alarm; dirty detector identification; automatic day/night sensitivity adjustment; normal/alarm LED s; relay bases; sounder bases; and isolator bases. Systems, which only monitor the presence of a conventional detector in an addressable base, shall not be acceptable. G. Each intelligent loop card shall contain its own dedicated resident central processor unit (CPU) and shall provide power, process, store, control, and communicate with detectors and in/out modules via a minimum No. 18 AWG /13

9 twisted pair cable up to a maximum of 5,000 feet. The cable shall be computer grade. H. The system shall use full digital communications to supervise all addressable loop devices and power supplies for placement, correct location, and operation. It shall allow swapping of same type devices without the need of addressing and impose the location parameters on replacement devices. It shall initiate and maintain a trouble if a device is added to a loop and clear the trouble when the new device is mapped and defined into the system. System circuits shall be configured as follows: addressable analog loops Class <B>; initiating device circuits Class <B>; notification appliance circuits Class <B>; network communications <B>; and annunciator communications <B>. The system shall have an U.L. listed detector sensitivity test feature, which shall be a function of the smoke detectors and performed automatically every four (4) hours. The system shall support one hundred percent (100%) of all remote devices in alarm. All panel modules shall be supervised for placement and return trouble if damaged or removed. The system shall have a CPU watchdog circuit to initiate trouble should the CPU fail. The system evacuation signal rate shall be continuous. The system shall include a signal silence inhibit and an automatic signal silence timer. Audible notification and visual signal appliances shall be affected by signal silence features. For NFPA Style 4 operation, branch circuits (T-Taps) may be made off the loop. The number of T-Taps shall not exceed the manufacturer's recommendations. I. The average time to detect an alarm shall be three (3) seconds or less. The polling time for the system shall remain the same regardless of the number of intelligent loops in the system up to it's maximum. J. The control panel network master shall have the following features without any changes in hardware or firmware: 1. Five hundred seventy six (576) event history log stored in RAM including, but not limited to, facility name, licensee, project compile date, compiler version, project revision, and time and date of history request. 2. Logics statements. 3. Time controls. 4. Sequences. 5. Actions. 6. Weekday/holiday schedules. 7. Analog value reporting of all analog detectors /13

10 8. Maintenance reporting by intelligent detector. 9. Sensitivity setting changed by detector (within UL limits). 10. Sensitivity setting changed by time (Day/Night Mode). 11. Alarm verification by point or zone (0 to 60 seconds in intervals of 5 seconds). 12. Up to ninety nine (99) priorities for any event driven relay/output. 13. Enabling and disabling of any system device. 14. Ground fault detection on all system devices and inputs. 15. Opens detected on all system devices and inputs. K. A main fire alarm control panel, which will meet this Specification, shall consist of an EST Model No. EST-3 wall mounted equipment cabinet(s) complete with the following modules of the quantity required to perform all of the specified functions. 1. EST-3 a. EST Model No. 3-CPU3 central processor unit. b. EST Model No. 3-RS485B network communications card. c. EST Model No. 3-RS232 RS232 communications card. d. EST Model No. 3-SSDC1 signature single driver controller. e. EST Model No. 3-PPS/M power supply INTELLIGENT PERIPHERAL REQUIREMENTS A. This Contractor shall furnish and install intelligent devices as shown on the Drawings and herein specified. All remote intelligent devices shall have a microprocessor with non-volatile memory to support their functionality and serviceability. Each device shall store as required for its functionality the following data: device serial number; device address; device type; personality code; date of manufacture; hours in use; time and date of last alarm; amount of environmental compensation left/used; last maintenance date; job/project number; current detector sensitivity values; diagnostic information (trouble codes); and algorithms required to process sensor data and perform communications with the loop controller. Each device shall be capable of electronic addressing either automatically or application programmed assigned, to support physical/electrical mapping and supervision by location. Setting a /13

11 device s address by physical means shall not be necessary. B. The intelligent detectors shall be capable of full digital communications using both broadcast and polling protocol. Each detector shall be capable of performing independent fire detection algorithms. The fire detection algorithm shall measure sensor signal dimensions, time patterns, and combine different fire parameters to increase reliability and distinguish real fire conditions from unwanted deceptive nuisance alarms. The devices shall eliminate by digital filters, signal patterns that are not typical of fires. Devices not capable of combining different fire parameters or employing digital filters shall not be acceptable. Each detector shall have an integral microprocessor capable of making alarm decisions based on fire parameter information stored in the detector head. Distributed intelligence shall improve response time by decreasing the data flow between detector and analog loop controller. Detectors not capable of making independent alarm decisions shall not be acceptable. Maximum total analog loop response time for detectors changing state shall be 0.5 seconds. Each detector shall have a separate means of displaying communication and alarm status. A green LED shall flash to confirm communication with the analog loop controller. A red LED shall flash to display alarm status. The detector shall be capable of identifying up to thirty-two (32) diagnostic codes. This information shall be available for system maintenance. The diagnostic code shall be stored at the detector. Each smoke detector shall be capable of transmitting pre-alarm and alarm signals in addition to the normal, trouble, and need cleaning information. It shall be possible to program control panel activity to each level. It shall be possible to individually program each smoke detector to operate at any one of five (5) sensitivity settings. Each detector microprocessor shall contain an environmental compensation algorithm, which shall identify and set ambient environmental thresholds approximately six (6) times an hour. The microprocessor shall continually monitor the environmental impact of temperature, humidity, other types of contaminates, as well as detector aging. The process shall employ digital compensation to adapt the detector to both twenty-four (24) hour long term and four (4) hour short term environmental changes. The microprocessor shall monitor the environmental compensation value and alert the system operator when the detector approaches eighty percent (80%) and one hundred percent (100%) of the allowable environmental compensation value. Differential sensing algorithms shall maintain a constant differential between selected detector sensitivity and the learned base line sensitivity. The base line sensitivity information shall be updated and permanently stored at the detector approximately once every hour INTELLIGENT PHOTOELECTRIC TYPE SMOKE DETECTOR A. This Contractor shall furnish and install intelligent photoelectric type smoke detectors as shown on the Drawings and herein specified. The analog photoelectric type smoke detector shall utilize a light scattering type photoelectric smoke sensor to sense changes in air samples from its surroundings. The integral microprocessor shall dynamically examine values from the sensor and initiate an alarm based on the analysis of data. Systems using central /13

12 intelligence for alarm decisions shall not be acceptable. The detector shall continually monitor any changes in sensitivity due to the environmental affects of dirt, smoke, temperature, aging, and humidity. The information shall be stored in the integral processor and transferred to the analog loop controller for retrieval using a laptop PC or similar program/service tool. The detector shall be rated for ceiling installation at a minimum of thirty (30) feet centers and shall be suitable for wall mount applications. The percent smoke obscuration per foot alarm set point shall be field selectable to any of five (5) sensitivity settings ranging from one percent (1%) to three and a half percent (3-1/2%). The photoelectric smoke detector shall be suitable for direct insertion into air ducts up to 3 ft (0.91m) high and 3 ft (0.91m) wide with air velocities up to 5,000 ft/min. ( m/sec) without requiring specific duct detector housings or supply tubes. The detector shall be suitable for operation in the following environment: 1. Temperature: thirty-two (32) F to one hundred twenty (120) F. 2. Humidity: zero (0) to ninety-three percent (93%) relative humidity, noncondensing. 3. Elevation: no limit. B. Where noted on the Drawings, intelligent photoelectric type smoke detectors shall be furnished and installed by this Contractor complete with wire guards. C. An intelligent photoelectric type smoke detector, which will meet this Specification, is EST Model No. SIGA-PS complete with Model No. SIGA-SB base suitable for mounting over a four (4) inch octagonal or square outlet box INTELLIGENT THERMAL DETECTOR A. This Contractor shall furnish and install intelligent combination fixed temperature/rate-of-rise thermal detectors as shown on the Drawings and herein specified. The thermal detector shall have a low mass thermistor heat sensor and operate at a fixed temperature and at a temperature rate-of-rise. The detector shall continually monitor the temperature of the air in its surroundings to minimize thermal lag to the time required to process an alarm. The integral microprocessor shall determine if an alarm condition exists and initiate an alarm based on the analysis of the data. Systems using central intelligence for alarm decisions shall not be acceptable. The intelligent thermal detector shall have a nominal fixed temperature alarm point rating of one hundred thirty-five (135) F and a rate-of-rise alarm point of fifteen (15) F per minute. The intelligent thermal detector shall be rated for ceiling installation at a minimum of seventy (70) foot centers and be suitable for wall mount applications. B. An intelligent thermal detector which will meet this Specification is EST Model No. SIGA-HRS complete with Model No. SIGA-SB base suitable for mounting over a four (4) inch octagonal or square outlet box /13

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

SECTION 16700 FIRE ALARM SYSTEM

SECTION 16700 FIRE ALARM SYSTEM SECTION 16700 FIRE ALARM SYSTEM PART ONE: GENERAL 1.1 GENERAL REQUIREMENTS A. Definition of Work : This section of the specification includes the furnishing, installation, connection and testing of the

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION 25-POINT INTELLIGENT COMMUNICATING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1. DESCRIPTION: A. This section of the specification

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

FIRE ALARM SYSTEM Section 16750 Page 1

FIRE ALARM SYSTEM Section 16750 Page 1 FIRE ALARM SYSTEM Section 16750 Page 1 PART 1 - GENERAL 1.1 REQUIREMENTS A. Provide a complete operational, stand-alone local protective signaling system in each defined building as indicated on the contract

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description INTELLIGENT FIRE ALARM CONTROL PANELS MR-2100/MR-2200 Intelligent Fire Alarm Control Panels Description MR-2100/MR-2200 Intelligent Fire Alarm Control Panel (shown with optional LED modules) Secutron's

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description SFC-200 SERIES FIRE ALARM CONTROL PANELS SFC-200 Series Fire Alarm Control Panels Description Summit s SFC-200 Series fire alarm control panels consist of six and twelve zone models which are equipped

More information

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM

SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,

More information

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors

D7050/D7050TH. Installation Instructions. Multiplex Photoelectric Smoke Detectors D7050/D7050TH EN Installation Instructions Multiplex Photoelectric Smoke Detectors D7050/D7050TH Installation Instructions.0 Description Notices These instructions cover the installation of the D7050/D7050TH

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM FIRE DETECTION AND ALARM GENERAL INFORMATION 1.1 In general, follow the guidelines below when designing and specifying addressable fire alarm systems. Unless specifically indicated otherwise, these guidelines

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM

SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM SECTION 28 31 00 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 SECTION INCLUDES A. Fire alarm system requirements B. Fire alarm equipment C. Fire alarm peripheral devices 1.02 RELATED SECTIONS

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19 TECHNICAL SPECIFICATIONS Page 1 of 19 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC analogue addressable, electrically supervised, zone annunciated, fire detection and alarm system as

More information

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? 5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,

More information

Life Alarm Fire Alarm Controls

Life Alarm Fire Alarm Controls FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS

Design and Construction Standards SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16720 FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES: A. Fire alarm and smoke detection systems. 1.2 REFERENCES 1.3 NFPA 72 1.4 NFPA 101 1.5 REGULATORY REQUIREMENTS

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

INTRUSION DETECTION SYSTEM Section 281600

INTRUSION DETECTION SYSTEM Section 281600 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

More information

FIRE ALARM APPLICATION

FIRE ALARM APPLICATION FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

E-PDD Duct Smoke Detector Installation Sheet

E-PDD Duct Smoke Detector Installation Sheet E-PDD Duct Smoke Installation Sheet Operation The duct smoke detector's primary purpose is to provide early warning of an impending fire and shut down the HVAC unit in order to prevent smoke from circulating

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

A. This Standard outlines the requirements for an addressable fire detection and alarm system.

A. This Standard outlines the requirements for an addressable fire detection and alarm system. 1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description

INTELLIGENT FIRE ALARM CONTROL UNITS. MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit. Features. Description INTELLIGENT FIRE ALARM CONTROL UNITS MMX-2017-12NDS Intelligent Network Fire Alarm Control Unit Description Secutron s MMX-2017-12NDS Network Fire Alarm Control Unit offers modular components to meet a

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12)

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions 800-09617V1 Rev A 11/12) UL864 (Commercial Fire) Compliance General Requirements The VISTA-128FBPT/VISTA250FBPT

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work GE Security Small Building Life Safety Solutions Affordable FireShield Conventional Fire Alarm Control Panels imagination at work cost Location: Environment: Solution: Flower shop Finely decorated, gentle

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems.

5. Central Control and Monitoring System. 6. Gas Detection Systems (future) 7. Mass Notification Systems (future) 8. Smoke Control Systems. PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University for Fire Detection and Alarm. B. The design guidelines contained

More information

SECTION 28 31 00 FIRE DETECTION AND ALARM

SECTION 28 31 00 FIRE DETECTION AND ALARM SECTION 28 31 00 PART 1 - GENERAL 1.1 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the fire alarm equipment to form a complete coordinated

More information

SECTION 16721 MULTI-FIRE ALARM SYSTEM

SECTION 16721 MULTI-FIRE ALARM SYSTEM PART 1. GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification Sections, apply to this Section.

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es

More information

Fire detection equipment

Fire detection equipment PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC

16720S01 - FIRE ALARM SYSTEM (HARDWIRED), MANUAL AND AUTOMATIC 1. GENERAL 1. Fire alarm system shall be manufactured by Simplex, Autocall or Edwards. Simplex part numbers are provided in this spec for clarification only and do not exclude equivalent part numbers of

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14 City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011 Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA

More information

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION 28 13 00 SECURITY AND ACCESS CONTROL SYSTEM

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION 28 13 00 SECURITY AND ACCESS CONTROL SYSTEM DIVISION 28 ELECTRONIC SAFETY AND SECURITY PART 1 GENERAL 1.01 DESCRIPTION A. Division 28 Contractor shall extend a complete Matrix Systems Access Control System as shown on the Drawings and as specified

More information

CalMod Design-Build Electrification Services

CalMod Design-Build Electrification Services SECTION 28 16 00 INTRUSION DETECTION SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. This section describes the detailed technical requirements for the Intrusion Detection System (IDS), where the Contractor

More information

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University

More information

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

SECTION 17400 ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. SECTION 17400 ACCESS CONTROL SYSTEM CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section. PART 1 - GENERAL 1.1 RELATED WORK A. 16060 Grounding and Bonding B. 16070 Electrical

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

SFC-200 SERIES LCD FIRE ALARM PANEL

SFC-200 SERIES LCD FIRE ALARM PANEL SFC-200 SERIES LCD FIRE ALARM PANEL User Guide LT-954SUM SFC-200 Series LCD Version User Guide Contents Introduction... 1 About this Manual... 1 Technical Support... 1 Main Display... 1 The Buzzer and

More information

FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM

FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM FIRE ALARM AND EMERGENCY VOICE EVACUATION SYSTEM PART 1.0 - GENERAL 1.1 DESCRIPTION: A. This section of the specifications includes the furnishing, installation, and connection of a multiprocessor controlled,

More information

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's

More information

The supplier and installer of the system should be approved by the local civil defence authority.

The supplier and installer of the system should be approved by the local civil defence authority. ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer

More information

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE SP4LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE INSTALLATION AND OPERATION MANUAL MASS NOTIFICATION SYSTEM Part Number: P84767 Rev. A Copyright 2006 Cooper Wheelock, Inc. All rights reserved.

More information

Using your LED Plus keypad

Using your LED Plus keypad Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply

More information

Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 FIRE ALARM AND DETECTION SYSTEMS

Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 FIRE ALARM AND DETECTION SYSTEMS Engineer s Project Number: 298-1062 Section 28 31 00 Page 1 SECTION 28 31 00 PART 1 GENERAL 01 SUMMARY A. This Section covers fire alarm systems, including initiating devices, notification appliances,

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

Section 13850 Fire Detection and Alarm Page 1 of 13

Section 13850 Fire Detection and Alarm Page 1 of 13 SECTION 13850 - FIRE DETECTION AND ALARM 1.1 APPLICABLE STANDARDS A. Fire detection and alarm systems shall be designed and installed in accordance with the following standards, including appendices (current

More information