Dynamics of Hydronic Systems

Size: px
Start display at page:

Download "Dynamics of Hydronic Systems"

Transcription

1 Valve and Actuator Manual 977 Hydronic System Basics Section Engineering Bulletin H112 Issue Date 0989 Dynamics of Hydronic Systems A hydronic system can be configured in many different ways. This report will discuss the following types: 1. Reverse Return 2. Direct Return 3. Primary/Secondary The variant configurations of the hydronic systems noted above will be analyzed as well as the relative advantages and disadvantages of each. Part-load characteristics will also be considered. Any of the three types of hydronic systems could be utilized in either a heating or cooling system. To simplify the remainder of this report only the case of a cooling system will be considered. Most of the concepts covered however, would be applicable for either heating or cooling systems. It is strongly recommended that the concepts discussed in Engineering Reports H111 and H110 be understood before preceding with this report. Engineering Report H111 includes a detailed discussion of the performance of control valves. Engineering Report H110 discusses the relationship between fluid flow and pressure drop as it pertains to typical hydronic systems. Accurate, stable control is dependent upon two factors. The first is the ability of the controller and control valve to compensate for process nonlinearites. A coil is a good example of a nonlinear process. If the capacity of a coil is plotted for each flow rate through the coil, the result is a logarithmic relationship. Secondly, the physical limitations of the control valve must be considered. As discussed in Engineering Report H111, all control valves have some amount of uncontrollable flow when the valve plug is initially lifted form its seat. The magnitude of this uncontrollable flow is related to the valve rangeability and the pressure differential across the valve. Rangeability values are limited by machining process tolerances. Therefore, it becomes important to minimize the variation in pressure differential across the valve to minimize the uncontrollable flow through it Johnson Controls, Inc. 1 Code No. LIT-351H112

2 Even small amounts of uncontrollable flow can compromise the ability of a hydronic system to be properly controlled. This is the result of the extremely high coil gain at low flow rates. It is important to properly size the control valves. It is also necessary for the consultant to design a hydronic system which is able to maintain a relatively constant branch differential pressure, Pb, regardless of building load. This report discusses how well the standard types of distribution systems are able to maintain a constant Pb. Reverse Return Distribution Systems In a reverse return system the pressure drops in the distribution piping between the circulating pump and each air handling unit are equal. This is true because the system is designed so that the length of the water circuit is the same for each air handling unit regardless of its location with respect to the circulating pump. As a result the Pb for every branch is equal regardless of the magnitude of the building cooling load. If the air handling unit cooling coils are all selected for the same pressure drop this type of system is self-balancing. Unfortunately the installed cost of a reverse return piping system is higher than that of the other types of hydronic systems. This is due primarily to the cost of the additional chilled water return piping (See Figure 1). 2 H112 Engineering Bulletin

3 Reverse Return System with 3-way Valves When 3-way valves are installed in a reverse return system, each valve can be optimally selected based upon the same criteria. Changes in the magnitude of the cooling load will have little effect on the chilled water flow rate. As a result, the value of Pb for every branch will remain constant regardless of changes in the magnitude of the building cooling load. In the case of the reverse return system shown in Figure 1 the Pb for every branch will always be 50ft H2O. Since Pb is always 50ft H2O, every control valve can be optimally selected, based upon the above criterion. If a valve authority of 50% is desired, all of the control valves can be selected for a 25ft H2O pressure drop at design flow. Since the branch pressure drop does not deviate from 50ft H2O, there should be no increase in uncontrollable flow nor will there be any loss in effective valve travel as the building cooling load decreases. As with any system which utilizes 3-way valves, the flow rate through the chiller(s) can always be maintained at a constant level without the requirement for a large central plant bypass with its associated controls. Because the 3-way control valves shown in Figure 1 are mixing valves piped in a bypass configuration, problems associated with control valve actuator spring range shift or the inability to shut off flow through the cooling coil will be minimized. The disadvantages of utilizing 3-way valves are increased installation and operating costs; specifically, a more complex (costly) coil piping arrangement, a high continuous building flow requirement and a lower overall chiller coefficient of performance (C.O.P). When 3-way control valves are installed, the building demand for chilled water does not vary with diversity in the building thermal load. Remember, the flow rate through each branch does not change with the cooling load requirements of the space served by the air handling unit. Only the chilled water flow rate through the cooling coil changes with the load. Consequently, chilled water pumps must often be operated without their associated chiller to insure each branch will have chilled water available to meet the space cooling load. Otherwise the branches nearest the chilled water pumps will consume all of the available chilled water. In the case of a chilled water system the operation of extra chilled water pumps not only increases pumping horsepower requirements but also reduces the overall chiller plant C.O.P. The lower overall chiller plant C.O.P. is the result of mixing relatively warm water passing through a nonoperating chiller with exceptionally cold water leaving a operating chiller. This is required to meet both the building flow and chilled water supply temperature requirements. The C.O.P. of the operating chiller decreases since it is forced to provide a lower chilled water supply temperature for a given building thermal load. This problem is illustrated in Example 1. H112 Engineering Bulletin 3

4 Example 1 Refer to Figure 1. This distribution system was designed for a total cooling capacity of 400 tons. There are four air handling units (AHU), each with a design capacity of 100 tons. Each AHU requires 150 gpm of chilled water at a 16 F rise (45-61 F) when fully loaded. Assume that the AHU is Branch #4 serves a computer facility and has a constant cooling load of 100 tons regardless of outdoor conditions. Also assume the AHUs in branches #1 through #3 serve exterior zones in the building. Finally, assume it is a temperate spring day, such that the cooling load on the AHUs located in branches #1 through #3 is 20 tons per AHU. The total building cooling load is 160 tons. It would seem, since each chiller has a capacity of 200 tons only one chiller will need to operate. Unfortunately things aren t that simple. Because this distribution system has 3-way control valves, both chilled water pumps must operate to maintain flow in all branches. The cooling coil in branch #4 is fully loaded. Therefore 150 gpm is passing through this coil and is being heated from 45 F to 61 F. Meanwhile in branches #1 though #3 only 30 gpm of the chilled water actually passes through the cooling coil. The other 120 gpm of 45 F chilled water bypasses the coil. These two streams then mix resulting in a branch chilled water return temperature of 48.2 F. The temperature of the chilled water returning to the central plant will be 51.4 F after the water returning from all four branches is mixed. Here is the problem. A single operating chiller must produce 38.6 F chilled water if 45 F water is to be supplied to the building. This extremely low chilled water temperature requirement is dictated by the fact an equal volume of 51.4 F water is simply passing through the nonoperating chiller and the AHU in branch #4 requires 45 F to meet its cooling load. When a chiller designed to produce 45 F chilled water is forced to produce lower temperature chilled water its C.O.P. drops in a nonlinear manner. For each additional degree drop in chilled water supply temperature increasing amounts of compressor power is required. In this case it is unlikely that the one operating chiller could even provide 38.6 F chilled water. In this extreme case both chillers would be required to operate even though the actual cooling load is less than the capacity of one chiller. This is very inefficient. 4 H112 Engineering Bulletin

5 Reverse Return Systems With 2-way Valves When 2-way valves are installed in a reverse return system the Pb for every branch will the same regardless of load, but the magnitude of the Pb will vary with changes in the building cooling load. This occurs because the pipe-friction factor changes with the variable chilled water flow rate (See Figure 2). A reduction in cooling load will cause one or more of the 2-way control valves to reduce the system chilled water flow rate. The hydronic system depicted in Figure 2 does not have a central plant bypass. Without a bypass the pressure developed by the chilled water pump(s) will increase with the reduction in the cooling load. The pump s operating point will ride up its pump curve as the chilled water flow rate decreases. This increase in pressure developed by the pump, as well as the reduced pipefriction factor, will increase the differential pressure across the branches. This is undesirable. The numbers shown in Figure 2 without parenthesis represent the system pressures at maximum design cooling load. The numbers shown in parenthesis represent system pressures when each branch is at (1/2) of its design load. Notice how each Pb increased from 50ft to 120ft H2O. H112 Engineering Bulletin 5

6 If the distribution system had a central plant bypass, the magnitude of the Pb could have been held constant (See Figure 3). The control valve located in the central plant bypass will be controlled by a differential pressure controller. The high and low reference sensing lines for the controller will be connected across one of the branches in the distribution system. If the sensed differential pressure deviates from the controller set-point, the control valve in the bypass piping will modulate as required to maintain the desired Pb. Since each branch has the same Pb in a reverse return system, common sense would dictate that the sensing location for the differential pressure controller would be across the branch closest to the bypass. This would reduce the length of the controller sensing and/or output lines, therefore reducing installation costs. This system has all of the advantages of a reverse return system with 3-way valves, but does not have its disadvantages. 6 H112 Engineering Bulletin

7 As an alternative to using a central plant bypass to maintain a constant Pb, a variable frequency drive could be installed on the chilled water pump motor. The differential pressure controller would then vary the speed of the chilled water pump to maintain the desired Pb. The main problem with using a variable speed drive in lieu of a central plant bypass is that the flow through the chiller(s) will now vary with changes in the cooling load. This potential problem must be carefully considered, and it would be wise to consult the chiller manufacturer to obtain acceptable guidelines. The major advantage in using a variable speed drive in lieu of a central plant bypass is the potential for energy savings. The variable speed drive will save energy in two areas. First, any energy losses which normally occur within the bypass valve will be avoided. In addition, the reduction in the chilled water flow rate will proportionally decrease the chilled water pump brake-horsepower requirement. Remember, in a system with a central plant bypass the flow rate to the building is directly proportional to the cooling load, but the flow rate through the chilled water pumps actually increases with reductions in the cooling load. In a system utilizing variable speed drives the flow rate through the pumps will vary directly with the cooling load. Keep in mind however, that in a properly sequenced multiple chiller central plant the flow rate through the bypass line will be less than the water flow rate associated with only one chiller. In other words, the excess amount of chilled water produced in the central plant above and beyond the demand required by the building would be less than the amount of water provided by one chilled water pump. This assumes there is one chilled water pump for each chiller. Therefore, the savings provided by using a variable speed drive compared to a central plant bypass is not a function of the total plant chilled water pumping capacity. Instead the potential savings is a function of the capacity of only one, not all, of the chilled water pumps. If the central plant has a large number (greater than four) of chillers and chilled water pumps, variable speed drives will save very little energy over a properly operated constant speed system utilizing a bypass valve. Direct Return Distribution Systems In a direct return distribution system the length of the distribution piping between the chilled water pump and each air handling unit will vary (See Figure 4). As result the Pb for every branch will be different. The closer an air handling unit is located to the chilled water pump, the larger the Pb. The magnitude of the Pb will also be affected by the chilled water flow rate. Remember the pipe friction-factor changes with the square of the flow rate through the pipe. H112 Engineering Bulletin 7

8 The following four items can be utilized to minimize the variation in Pb: 1. Properly sizing the distribution piping can help to maintain a constant Pb. This piping should be sized for small (less than 4 ft head loss per 100 ft of pipe) friction-factors. The change in pressure drop of the distribution piping, as flow is varied from maximum to minimum, then should not exceed the design pressure drop across a properly sized control valve. This is true for all but the largest systems. Some central campus systems, and the like, would require booster pumps in remote locations. 2. Utilize a central plant bypass or variable speed pump. The Pb across one of the branches can then be maintained at a constant level. This will prevent unwanted changes in the pressure developed by the chilled water pump from being shifted out to the branches. 3. Utilize control valves with large design pressure drops. 4. In some cases, utilize balancing valves. 8 H112 Engineering Bulletin

9 Direct Return System with 3-way Valves Direct Return Systems with 2-way Valves When 3-way valves are installed in a direct return hydronic system the magnitude of the Pb for each branch will be constant. This is true because the chilled water flow rate is always constant and is not affected by the load. However the magnitude of the Pb will be different for each branch. This occurs because the length of water circuit between the branch and chilled water pump is different for each branch (See Figure 4). The control valves for each branch can, therefore, be optimally sized for any cooling load condition. Unfortunately each branch will have a different sizing criterion since the Pb is different for each branch. In comparison, the 3-way valves in the reverse return system can all be sized for the same pressure drop. As discussed earlier, the 3-way valves will insure a constant flow rate through the chiller(s). Problems with actuator spring range shift, and cooling coil shutoff will also be minimal. Unfortunately, the same disadvantages are still apparent. The installed cost of a system with 3-way valves is higher due to more complex coil piping arrangements. Also as discussed previously the chiller plant C.O.P. will be lower when compared to a system with 2-way valves. This results from the high continuous building demand for chilled water dictating operation of chilled water pumps without their associated chiller. When 2-way valves are installed in a direct return system, the Pb will be dependent upon the location of the branch relative to the chilled water pump and the magnitude of the cooling load (See Figure 5). The numbers in parenthesis indicate the system pressures when each branch is at (1/2) of its design cooling load. The numbers without parenthesis indicate the system pressures when the system is at maximum design cooling load. If the system does not have a central plant bypass the value of Pb will be extremely dynamic. These extreme changes in differential pressure occur for three reasons: the chilled water pump will ride up its curve, the pipefriction factor in the distribution piping will change with load, and the length of the water circuit is different for each branch. This system is as far from optimal as any can get. H112 Engineering Bulletin 9

10 If the system does have a central plant bypass, the pressure fluctuations across each branch are reduced (See Figure 6). The numbers in parenthesis indicate the system pressures when each branch is at (1/2) of design cooling load. Adding the central plant bypass keeps changes in the pressure developed by the chilled water pump from being shifted out to the branches. However, since the pipe-friction factor in the distribution piping will change with load, the value of the Pb will be affected. Whenever the load in the building decreases and the bypass valve opens, the flow rate in the central plant will increase. This occurs because the pressure drop across the bypass will decrease as it is opened. In turn the pressure developed by the pump will decrease. As the pump operating point moves further out on its pump curve, its flow rate will increase. This increased flow rate will, in turn, increase the pipe-friction factor of the central plant piping. Eventually a balance point between the increased central plant piping friction losses and the decreased pressure across the bypass will be found. This is graphically shown in Figures 7, 8 and 9. Notice how the slope (pipe-friction factor) of the line representing 1/2 design load changes within the central plant portion of the graph. 10 H112 Engineering Bulletin

11 Assuming the branches are uniformly spaced in a distribution system, the best differential pressure sensing location for the bypass controller is in the middle of the system. Figure 7 relates the change in Pb with location as a function of cooling load. The graph illustrates the possible variation in Pb as the building load changes from no load to maximum design load. The slope of each of the different load lines is equal to the negative of the respective piping friction factors. The area underneath the lowest load line represents the pressure available for the branch piping, coil and control valve. Depending on the location of the branch in the system the lowest load line could be either the design or no load line. In this case the control valves in the first half of the branches which are closest to the pump should be selected for a higher design pressure drop than those in the second half of the system. H112 Engineering Bulletin 11

12 By sensing differential pressure in the middle of the distribution system the magnitude of the maximum variation in branch differential pressure is minimized when compared to other sensing locations. Compare the maximum variation of Pb in the building portion of Figure 7 to that shown in Figures 8 or 9. The bypass control scheme shown in Figure 8 will provide good pressure control at the end of the system. Unfortunately the variation in Pb at the beginning of the system may be excessive. The bypass control scheme shown in Figure 9 can provide good pressure control at the beginning of the system. Unfortunately the variation in Pb at the end of the system may be excessive. In spite of some inherent problems, direct return hydronic systems with 2- way control valves are very popular. This is likely due to the fact it has a lower initial cost relative to other types of hydronic systems and it is a very energy efficient pumping system. Lastly, a direct return system incorporating either a central plant bypass or variable speed pumping can provide acceptable pressure control when distribution piping is properly sized. Proper distribution pipe sizing is critical to insure trouble free control. If the distribution piping is undersized the Pb can vary significantly with the load. 12 H112 Engineering Bulletin

13 As a rule, the potential change in Pb must be less than the design pressure drop of the control valve, or problems can occur. These problems can manifest themselves in the following ways: unacceptable uncontrollable valve flow, problems with valve shutoff and spring range shift, valve cavitation, and overflowing marginally sized cooling coils. Primary/ Secondary Distribution Systems A primary secondary distribution system utilizes two sets of pumps. The first set is used to pump water through the chillers. These pumps are called the primary pumps. The second set of pumps are used to pump water through the building. These pumps are called the secondary pumps. The primary and secondary pumps are hydraulically isolated from one another. This isolation is accomplished by installing a bypass line between the primary and secondary pumping systems as shown in Figure 10. H112 Engineering Bulletin 13

14 The bypass line is also often called a decoupler line since it isolates or decouples the primary and secondary systems. The direction of flow in the decoupler piping can be in either direction. The direction of flow will depend upon the amount of chilled water produced in the central plant (primary flow) and the amount consumed by the building (secondary flow). If the primary loop produces a greater volume of chilled water than the secondary system consumes, flow in the decoupler will be from supply to return. If then secondary system consumes a greater volume of water than the primary system produces the water in the decoupler will flow from return to supply. Normally flow within the decoupler should be from supply to return. Otherwise the chilled water supply temperature in the secondary loop will rise to unacceptable levels. The hydraulic isolation allows both the primary and secondary pumping systems to function as if the other was not present. The primary pumps are, therefore, able to maintain a constant flow rate through the chiller regardless of the building load. The secondary system can be configured as either a direct or reverse return distribution system. The same advantages and disadvantages discussed earlier will still apply. However, in either case only two-way control valves should be installed. The chilled water flow rate in the secondary system will then vary in relation to the building load. This is desirable for two reasons. 14 H112 Engineering Bulletin

15 First, a variable flow secondary system will require less pumping energy than other types of systems. The secondary flow rate, in a primary secondary system, can be reduced to extremely low flow rates. The minimum secondary flow rate is not fixed by flow limitations imposed on the system by the chillers. If a variable speed secondary chilled water pumps is installed, the amount of pumping power required will be minimized. In a variable speed pumping system, the pumping power requirement will vary with the cube of the flow rate as dictated by the pump affinity laws. The sensing location for the differential pressure transmitter should be near the middle of the secondary system. Once again, this location is the best compromise for minimizing the variation in the magnitude of the Pb. Secondly, if both the magnitude and direction of the flow rate in the decoupler are known, this information can be utilized in various building automation schemes. Particularly for chiller sequencing. Chiller sequencing is discussed in Engineering Report H324. Decoupler Line Sizing Considerations It is important for the decoupler line which separates the primary and secondary systems to be properly sized. It must be sized so that its pressure drop at full flow is kept very small (i.e., less than 1 psig). Normally full flow is about 115% of the flow rate associated with the largest chiller. Flow rates in excess of this value would indicate an operating chiller should be stopped. The decoupler should be a straight length of pipe with no restrictions. It is very important for the pressure drop in the decoupler to be kept very small to provide the hydraulic isolation between the primary and secondary systems. If the size of the decoupler is too small, pressure changes in the secondary system will be transmitted into the primary system. This interaction can cause stability problems and undesired flow variations through the chillers. Occasionally, a primary secondary distribution system with a check valve installed in the decoupler line is encountered (See Figure 11). H112 Engineering Bulletin 15

16 The purpose of this check valve is to prevent the building chilled water return from flowing directly back to the suction of the secondary pumps. The apparent logic behind this scheme is that at certain low load conditions it may be possible to operate the system without a primary chilled water pump. This is the result of a lower pressure drop in the distribution piping at low chilled water flow rates. This scheme is not recommended! With this check valve installed it is possible to overload the motor on the primary chilled water pump. This can occur when both primary and secondary chilled water pumps are operating at a time when the central plant is not providing enough chilled water to meet the building load. In this case both pumps are in series. Therefore, if the secondary chilled water pump is sized for a larger flow rate than the primary pump (common), the primary pump can overload. It is also possible in the above example to pump an excessive amount of chilled water through a chiller causing maintenance problems due to water side erosion in the evaporator tube bundles. The length of the decoupler line is also an important consideration. The decoupler line should be at least 10 pipe diameters long. If the decoupler line length is too short cross circulation problems can occur. When the decoupler length to diameter ratio is too small (less than 10) the decoupler can act as though it is a tank rather than a pipe. Cross circulation problems induced by turbulence at the fittings can then occur. This is very undesirable because it is possible, even if the primary system is producing a sufficient quantity of chilled water, for the chilled water return to mix with the chilled water supply. It will then be difficult to maintain the proper chilled water supply temperature to the building (See Figure 12). If it is necessary to measure flow in the decoupler line, it should be at least 30 pipe diameters long. This recommendation of 30 pipe diameters considers the amount of straight pipe necessary to measure flow accurately. This is important since flow measurements are often utilized for chiller sequencing schemes. 16 H112 Engineering Bulletin

17 Note: Do not use square law type flow meters to measure the flow rate in a decoupler line. Square law type flow meters include annubars, orifice plates, flow nozzles, and venturi tubes. The output signal cannot be accurately measured with these flow meters at turndowns greater than 3:1. A bidirectional turbine flow meter should be utilized because it can indicate both direction and amount of flow accurately at much lower flow rates. Turbine meters with turndown ratios of 10:1 are typical, but are available with ratios up to 30:1. Remember water must be able to flow both ways through the decoupler line. H112 Engineering Bulletin 17

18 18 H112 Engineering Bulletin Notes

19 Notes H112 Engineering Bulletin 19

20 Notes Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI Printed in U.S.A. 20 H112 Engineering Bulletin

VARIABLE VOLUME / VARIABLE SPEED SYSTEMS APPLICATIONS

VARIABLE VOLUME / VARIABLE SPEED SYSTEMS APPLICATIONS Bulletin D-120B Pages D120-115 to D120-118 VARIABLE SPEED PRIMARY CHILLED WATER PUMP CONTROL WITH TWO WAY VALVE DIRECT RETURN SYSTEM DESCRIPTION: The volume of water supplied to the system is varied in

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions System and Valve Basics: 1. Q: What is good cooling coil performance? A: The temperature range is controlled within +/- 0.5 F (0.28 C) off the cooling coil at set point or below.

More information

CHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa

CHILLED WATER PLANT PUMPING SCHEMES. James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa CHILLED WATER PLANT PUMPING SCHEMES James J. Nonnenmann, PE Stanley Consultants, Inc. Muscatine, Iowa ABSTRACT From the advent of central chilled water plants, the system for delivering chilled water to

More information

Building Performance With District Cooling

Building Performance With District Cooling Reprinting this proof for distribution or posting on web sites is not permitted. Authors may request permission to reprint or post on their web site once the fi nal version has been published. A reprint

More information

By Steven C. Severini, P.E., Member ASHRAE

By Steven C. Severini, P.E., Member ASHRAE The following article was published in ASHRAE Journal, July 2004. Copyright 2004 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 Applying Pressure Independent Control Valves in H.V.A.C. Systems A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009 1 Introduction I know, as building design consultants, so much of your effort

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

Basic Hydraulics and Pneumatics

Basic Hydraulics and Pneumatics Basic Hydraulics and Pneumatics Module 1: Introduction to Pneumatics PREPARED BY IAT Curriculum Unit March 2011 Institute of Applied Technology, 2011 ATM 1122 Basic Hydraulics and Pneumatics Module 1:

More information

COUNTERBALANCE VALVES

COUNTERBALANCE VALVES COUNTERBALANCE VALVES Introduction They are modulating valves which allow free flow into the actuator and then block the reverse flow until they feel a pilot pressure inversely proportional to the load

More information

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. ASGMT / Averaging Pitot Tube Flow Measurement Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc. Averaging Pitot Tube Meters Introduction

More information

V47 Series Temperature Actuated Modulating Water Valves

V47 Series Temperature Actuated Modulating Water Valves V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate

More information

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates Chilled Water System Commissioning: Variable Primary Flow John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. History of chilled water system configurations

More information

ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS

ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS ENERGY TRANSFER SYSTEMS AND THEIR DYNAMIC ANALYSIS Many mechanical energy systems are devoted to transfer of energy between two points: the source or prime mover (input) and the load (output). For chemical

More information

Heating Water by Direct Steam Injection

Heating Water by Direct Steam Injection Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space

More information

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING By Philip Sutter Pick Heaters, Inc. DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING INTRODUCTION Many process plants currently use steam or hot water to heat jacketed devices such as tanks,

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

Industrial Steam System Process Control Schemes

Industrial Steam System Process Control Schemes Industrial Steam System Process Control Schemes This paper was developed to provide a basic understanding of the different process control schemes used in a typical steam system. This is however a fundamental

More information

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil Answer: (1) Condenser coil See the video. A.R.E. Building Systems Study Guide

More information

ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS

ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS ICE THERMAL STORAGE IN AIR CONDITIONING APPLICATION FUNDAMENTALS By: T. S. Wan Date: April 19, 1994 (1st draft 3/7/86) Copyright 1994 by T. S. Wan (All rights reserved) ABSTRACT: The technology of energy

More information

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS By: Michael J. Bitondo, Mark J. Tozzi Carrier Corporation Syracuse, New York August 1999 INTRODUCTION In December of 1998, the American Refrigeration Institute

More information

TECHNICAL INFORMATION Bulletin

TECHNICAL INFORMATION Bulletin Peerless Pump Company 2005 Dr. M.L. King Jr. Street, P.O. Box 7026, Indianapolis, IN 46207-7026, USA Telephone: (317) 925-9661 Fax: (317) 924-7338 www.peerlesspump.com www.epumpdoctor.com TECHNICAL INFORMATION

More information

The Piping System Model a New Life Cycle Document. Elements of the Piping System Model

The Piping System Model a New Life Cycle Document. Elements of the Piping System Model Piping System Model as a Life Cycle Document White Paper Introduction When designing piping systems, a variety of documents are created providing the details necessary to design, purchase, build, and test

More information

Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001

Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Pressure Control Chapter 3 Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001 Introduction Pressure control is a key element in the design of any circuit. Used correctly, it can

More information

C. starting positive displacement pumps with the discharge valve closed.

C. starting positive displacement pumps with the discharge valve closed. KNOWLEDGE: K1.04 [3.4/3.6] P78 The possibility of water hammer in a liquid system is minimized by... A. maintaining temperature above the saturation temperature. B. starting centrifugal pumps with the

More information

Chapter 10. Control Design: Intuition or Analysis?

Chapter 10. Control Design: Intuition or Analysis? Chapter 10 Control Design: Intuition or Analysis? Dan P. Dumdie 10.1 Introduction In previous chapters, we discussed some of the many different types of control methods available and typically used in

More information

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers HEAT RECOVERY FROM CHILLED WATER SYSTEMS Applications for Heat Reclaim Chillers April 2008 TABLE OF CONTENTS INTRODUCTION... 3 WASTE HEAT SOURCES... 3,4 Capturing Sufficient Heat for Useful Purposes...

More information

Pressure Relief and Regulating Valves

Pressure Relief and Regulating Valves Pressure Relief and Regulating Valves With blocked center directional valves and variable displacement pumps, or open center directional valves and fixed displacement pumps where fast response, low leakage

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology HWEA 2011 Conference Craig S. Johnson Presentation Overview Introduction Aeration Air & Digester gas challenges Gas flow metering

More information

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes.

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes. providing insights for today s hvac system designer Engineers Newsletter volume 43 2 Chilled-Water Systems Design Issues Learning from past mistakes As with anything in life, you can learn HVAC design

More information

Mixing Valves. ARGUS Application Note: Mixing Valves

Mixing Valves. ARGUS Application Note: Mixing Valves Mixing Valves Most radiant hot water heating systems in greenhouses use mixing valves to control the temperature of heating pipes. Both 3-way and 4- way valves are commonly used. Mixing valves provide

More information

HOT WATER SYSTEMS CONTENTS

HOT WATER SYSTEMS CONTENTS HOT WATER SYSTEMS CONTENTS MECHANICAL CONSIDERATIONS.............................................. 3 Code Considerations..................................................... 3 Boiler Selection Considerations..............................................

More information

Energy and Flow Measurement for Hydronic Systems

Energy and Flow Measurement for Hydronic Systems Energy and Flow Measurement for Hydronic Systems Presented By: George Szyszko Applications Consultant MCR for ONICON Incorporated Why Measure Thermal Energy? To control something, you must first measure

More information

Your tool for designing efficient balancing solutions for heating and cooling systems

Your tool for designing efficient balancing solutions for heating and cooling systems Application guide Your tool for designing efficient balancing solutions for heating and cooling systems 18 applications Our recommended applications for heating and cooling systems will improve comfort

More information

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits)

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits) Page 1 of 6 (Home) Symbols / Visit us on: Fluid Power, Automation and Motion Control for all Industries About Us Products Services Catalogs Place an Order Training & Information Contact Us Employee Access

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information

Principals of Condensing Boiler System Design

Principals of Condensing Boiler System Design Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc. 1 Centrifugal Pump- Definition Centrifugal Pump can be defined as a mechanical device used to transfer liquid of various types. As

More information

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University

More information

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency Randy Mead, C.E.M, CMVP Introduction Chilled water plant efficiency refers to the total electrical energy it

More information

How Ground/Water Source Heat Pumps Work

How Ground/Water Source Heat Pumps Work How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Optimization of Water - Cooled Chiller Cooling Tower Combinations Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator

More information

Sanitary Type Electronic Flow Switches

Sanitary Type Electronic Flow Switches Industries Pharmaceutical Sanitary Type Electronic Flow Switches Food and Beverage Biotechnology Semiconductor Water Treatment S Series Ameritrol, Inc. Instruments and Controls Features No Moving Parts

More information

Application of the Orifice Meter for Accurate Gas Flow Measurement page 1. Application of the Orifice Meter for Accurate Gas Flow Measurement.

Application of the Orifice Meter for Accurate Gas Flow Measurement page 1. Application of the Orifice Meter for Accurate Gas Flow Measurement. Application of the Orifice Meter for Accurate Gas Flow Measurement page 1 DANIEL MEASUREMENT AND CONTROL WHITE PAPER Application of the Orifice Meter for Accurate Gas Flow Measurement www.daniel.com Summary

More information

Basic Symbols. Lines. Circular. Square. Diamond. Miscellaneous Symbols. -continuous line - flow line. -dashed line - pilot, drain

Basic Symbols. Lines. Circular. Square. Diamond. Miscellaneous Symbols. -continuous line - flow line. -dashed line - pilot, drain Airline Hydraulic's Main Page Basic Symbols Lines continuous line flow line dashed line pilot, drain envelope long and short dashes around two or more component symbols. Circular Square Diamond large circle

More information

Chapter 3.4: HVAC & Refrigeration System

Chapter 3.4: HVAC & Refrigeration System Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration

More information

Pump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps

Pump ED 101. Positive Displacement Pumps. Part I Reciprocating Pumps Pump ED 101 Positive Displacement Pumps Part I Reciprocating Pumps Joe Evans, Ph.D http://www.pumped101.com There are many pump designs that fall into the positive displacement category but, for the most

More information

Pressurized Water Reactor B&W Technology Crosstraining Course Manual. Chapter 9.0. Integrated Control System

Pressurized Water Reactor B&W Technology Crosstraining Course Manual. Chapter 9.0. Integrated Control System Pressurized Water Reactor B&W Technology Crosstraining Course Manual Chapter 9.0 Integrated Control System TABLE OF CONTENTS 9.0 INTEGRATED CONTROL SYSTEM... 1 9.1 Introduction... 1 9.2 General Description...

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS Products Include: 60 gpm eductors Style 3060, 3061, 3062 & 3070 95 gpm eductors Style

More information

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION.

IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION. IDEA Presentation SMALL CAMPUS CHILLED WATER PLANT OPTIMIZATION. Pre-Project Details Hawaiian Community College Campus consisting of 16 individual buildings totaling 308,000 sq.ft of conditioned space.

More information

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control Chenggang Liu Research Associate Homer L. Bruner, Jr., CEM Mechanical Systems

More information

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: Simon.Ho@irco.com 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable

More information

Section Vb2: Butterfly Valves

Section Vb2: Butterfly Valves Valve and Actuator Manual 977 Valve Basics and Sizing Information Section Engineering Data Book Vb2 Issue Date 0496 Section Vb2: Butterfly Valves Introduction Page 3 Advantages of Butterfly Valves 3 Disadvantages

More information

BULLETIN NO. TEH-908. Bell & Gossett R T. Hydronic System Design with the Bell & Gossett System Syzer / ON GPM FLOW

BULLETIN NO. TEH-908. Bell & Gossett R T. Hydronic System Design with the Bell & Gossett System Syzer / ON GPM FLOW 2000 BULLETIN NO. TEH-8 Bell & Gossett Hydronic System Design with the Bell & Gossett System Syzer 2 T 3 4 AT R T DIF URE TEMPERA 5 6 2M 7 8 9 10 3M 1 1M 800 600 0 400 GPM/T / ON GPM FLOW P PIPING FRICTION

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

CGC s Hybrid System Loop Control

CGC s Hybrid System Loop Control verview The CGC Group Hybrid Heat Pump System does NT operate with the same fluid loop temperatures as a conventional reversing Water Source Heat Pump system. The CGC system differs from a WSHP system

More information

Demand Based Static Pressure Reset Control for Laboratories

Demand Based Static Pressure Reset Control for Laboratories LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a

More information

VAD. Variable Area Desuperheaters

VAD. Variable Area Desuperheaters Desuperheater overview Steam used in process plants can be superheated, that is, heated to a temperature above saturation. The excess of temperature above its saturation is called 'superheat'. Desuperheated

More information

Select the Right Relief Valve - Part 1 Saeid Rahimi

Select the Right Relief Valve - Part 1 Saeid Rahimi Select the Right Relief Valve - Part 1 Saeid Rahimi 8-Apr-01 Introduction Selecting a proper type of relief valve is an essential part of an overpressure protection system design. The selection process

More information

Example. Fluid Power. Circuits

Example. Fluid Power. Circuits Example Fluid Power Circuits To Enhance Symbol Reading Skills To Work On Circuit Reading Skills With Answers HI LO Pump Circuit 18 A1 B1 17 16 15 13 Set 14 2,000 PSI PG2 Set 500 PSI 12 11 7 8 10 PG1 9

More information

Water Volume Calculation in Hydronic Heating & Cooling Systems

Water Volume Calculation in Hydronic Heating & Cooling Systems Water Volume Calculation in Hydronic Heating & Cooling Systems Preface There are several methods which can be used to calculate the volume of water in a hydronic heating or cooling systems. However, these

More information

Thermal Coupling Of Cooling and Heating Systems

Thermal Coupling Of Cooling and Heating Systems This article was published in ASHRAE Journal, February 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not

More information

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a

More information

ENERGY RETROFIT PROGRAM

ENERGY RETROFIT PROGRAM ENERGY RETROFIT PROGRAM An innovative but simple retrofit for existing hot water and chilled water piping systems that will help you save money. REDUCE FLOW BY 50% REDUCE PUMP HEAD BY 75% REDUCE PUMP POWER

More information

Tips to Reduce Chilled Water Plant Costs

Tips to Reduce Chilled Water Plant Costs This article was published in ASHRAE Journal, October 2013. Copyright 2013 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

presents Hydraulic Separation Beyond Primary / Secondary Piping

presents Hydraulic Separation Beyond Primary / Secondary Piping presents Hydraulic Separation Beyond Primary / Secondary Piping This Webinar is exclusively sponsored and the property of Caleffi Hydronic Solutions. All rights reserved. October 2007 Modern compact boilers

More information

Thermal Mass Availability for Cooling Data Centers during Power Shutdown

Thermal Mass Availability for Cooling Data Centers during Power Shutdown 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116, part 2). For personal use only. Additional reproduction,

More information

2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control...

2A.1 Features of Chiller Control Components... 104. 2A.3 Chilled-Water Supply Temperature Control... 107. 2A.4 Cooling-Water Supply Control... Appendix 2A: Chiller Control Principles... 104 2A.1 Features of Chiller Control Components... 104 2A.2 Start-up and Shutdown... 105 2A.2.1 Start-up...105 2A.2.2 Shutdown...106 2A.3 Chilled-Water Supply

More information

Chapter 11 SERVO VALVES. Fluid Power Circuits and Controls, John S.Cundiff, 2001

Chapter 11 SERVO VALVES. Fluid Power Circuits and Controls, John S.Cundiff, 2001 Chapter 11 SERVO VALVES Fluid Power Circuits and Controls, John S.Cundiff, 2001 Servo valves were developed to facilitate the adjustment of fluid flow based on the changes in the load motion. 1 Typical

More information

Class A Foam Mixing and Application Equipment

Class A Foam Mixing and Application Equipment Class A Foam Mixing and Application Equipment Adding Phos-Chek Class A foam concentrate to water: There are many methods of adding Phos-Chek Class A foam concentrate to water. The different methods have

More information

A descriptive definition of valve actuators

A descriptive definition of valve actuators A descriptive definition of valve actuators Abstract A valve actuator is any device that utilizes a source of power to operate a valve. This source of power can be a human being working a manual gearbox

More information

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)

More information

HVAC and REFRIGERATION

HVAC and REFRIGERATION This is a preview. Some pages have been omitted. PE principles and practice prracticce of engineering mechanical: HVAC and REFRIGERATION sample questions + solutions Copyright 2011 by NCEES. All rights

More information

Energy savings in commercial refrigeration. Low pressure control

Energy savings in commercial refrigeration. Low pressure control Energy savings in commercial refrigeration equipment : Low pressure control August 2011/White paper by Christophe Borlein AFF and l IIF-IIR member Make the most of your energy Summary Executive summary

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

TD10. Selecting Circulators. Technical Documents. Taco Radiant Made Easy Application Guide STEP 1: ESTABLISH THE TARGET FLOW RATE FOR THE SYSTEM

TD10. Selecting Circulators. Technical Documents. Taco Radiant Made Easy Application Guide STEP 1: ESTABLISH THE TARGET FLOW RATE FOR THE SYSTEM EFFECTIVE:August, Taco Radiant Made Easy Application Guide Selecting Circulators Technical Documents TD SUPERSEDES: New This article shows you how to select a Taco circulator that lets the hydronic system

More information

5.2. Vaporizers - Types and Usage

5.2. Vaporizers - Types and Usage 5.2. Vaporizers - Types and Usage 5.2.1. General Vaporizers are constructed in numerous designs and operated in many modes. Depending upon the service application the design, construction, inspection,

More information

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect of Record: SPARCH Project Overview The project is

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 24 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia S TABLE OF CONTENT SCOPE 2 DEFINITIONS

More information

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES 4.0 PUMP CLASSES Pumps may be classified in two general types, dynamic and positive displacement. Positive displacement pumps

More information

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

TES for Medical Center

TES for Medical Center First Place: Industrial Facilities or Processes, New This article was published in ASHRAE Journal, November 2012. Copyright 2012 ASHRAE. Reprinted here by permission from ASHRAE at www.tecothermalenergy.com.

More information

TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?

TOPIC: 191004 KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump? KNOWLEDGE: K1.01 [3.3/3.5] P21 Which one of the following contains indications of cavitation in an operating centrifugal pump? A. Low flow rate with low discharge pressure. B. Low flow rate with high discharge

More information

Entrained Gas Diagnostic with Intelligent Differential Pressure Transmitter

Entrained Gas Diagnostic with Intelligent Differential Pressure Transmitter January Page Entrained Gas Diagnostic with Intelligent Differential Pressure Transmitter Dave Wehrs - Director, Pressure Engineering Andrew Klosinski - Application Engineer, Pressure Diagnostics Emerson

More information

Hydraulic Trouble Shooting

Hydraulic Trouble Shooting Hydraulic Trouble Shooting Hydraulic systems can be very simple, such as a hand pump pumping up a small hydraulic jack, or very complex, with several pumps, complex valving, accumulators, and many cylinders

More information

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems F ox W hi t e Paper Reduce Energy Costs and Enhance Emissions Monitoring Systems A Technical White Paper from Fox Thermal Instruments Rich Cada, VP Sales & Marketing, Fox Thermal Instruments, Inc. 399

More information

Secondary Loop Chilled Water In Super High-Rise

Secondary Loop Chilled Water In Super High-Rise The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

ELECTRIC/DIESEL FIRE PUMP CHECK LIST BUILDING NAME: DESIGNER: SCO REPRESENTATIVE: PUMP MANUF.: LOCATION: INSTALLER: DATE: OWNER NAME: INSTALLATION Certificate for flushing and hydrostatic test furnished Piping been hydrostatically tested

More information

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS

HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS HEAT RECOVERY OPTIONS FOR DRYERS AND OXIDIZERS William K. Scullion, Application Engineering Leader, MEGTEC Systems, De Pere, WI Introduction Competitive pressures continuously motivate us to examine our

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

Typical Cooling Load Profile

Typical Cooling Load Profile Ice Storage Systems and Impact on Electric Demand Georges Hoeterickx Specialists in Heat Transfer Products and Services 1 2 Cooling Load Typical Cooling Load Profile 0 2 4 6 8 10 12 14 16 18 20 22 Time

More information